LG AS-W1264GH0, AS-W0964GH0, AS-W1865DH0, AS-W091264DH0, AS-W1424DH0 User Manual

Page 1
LG
Room Air Conditioner
SERVICE MANUAL
LG
MODELS: AS-W0964DH0
AS-W1264DH0 AS-W1865DH0 AS-W0964GH0 AS-W1264GH0 AS-W1224DH0 AS-W1424DH0 AS-W1825DH0
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Page 2
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name.................................................................................................................................3
Safety Precautions ...........................................................................................................................5
Dimensions ...............................................................................................................................
......10
Installation...............................................................................................................................
........14
Flaring work and connection of piping.........................................................................................16
Connecting the cable between indoor unit and outdoor unit.....................................................21
Checking the drainage and forming the pipings.........................................................................23
Air purging ......................................................................................................................................24
Test running ....................................................................................................................................26
Functions.........................................................................................................................................27
Operation.........................................................................................................................................30
Disassembly....................................................................................................................................41
Troubleshooting Guide ..................................................................................................................44
Schematic Diagram ........................................................................................................................65
Product Specifications ..................................................................................................................73
Exploded View ................................................................................................................................75
Replacement Parts List..................................................................................................................78
Page 3
Service Manual 3
LG Model Name
LG Model Name
2003
12 -345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 0~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
N Walnut A Gogh S Sisley Q Quran K Mecca
Page 4
4 Room Air Conditioner
LG Model Name
2004~
12 -345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z
L Chang_won R22 A Chang_won R410A C Chang_won R407C T China K Turkey R22 E Turkey R410A H Thailand
N India Z Brazil D Indonesia X Mexico V Vietnam S Out sourcing
Refrigerant
2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V
CHASSIS Look
D K
L G M N D P
Division Panel Type(Deluxe) Fighting 'Look'
(LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 0~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
R Mirror W White B Blue D Wood M Metal C Cherry
S4/S5
S6 SQ SR
ST
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F NBF F+(A/changeove)+A/clean+Low A G NBF F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K NBF F+(A/changeove)+A/clean L NBF F+(A/changeove)+A/clean+4way M NBF F+(A/changeove)+A/clean+PTC N NBF F+(A/changeove)+Autoclean+4way+PTC P NBF F+(A/changeove)+A/clean+4way+Low A+PTC Q (Nano)Plasma+ION+A/Clean S 4way+(Nano)Plasma F+
Negative ION+Healthy dehumidification
+A/Clean T Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator U 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator
V Dry contact W Wire remocon 8
Page 5
Service Manual 5
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
Always use the power plug and socket with the ground terminal.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
Do not modify or extend the power cord.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Installation
Page 6
6 Room Air Conditioner
Safety Precautions
Do not install the product on a defective instal­lation stand.
Be sure the installation area does not deteriorate with age.
• It may cause injury, accident, or damage to the
product.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Sharp edges could cause injury. Be especially care­ful of the case edges and the fins on the condenser and evaporator.
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
For installation, always contact the dealer or an Authorized service center
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
• There is risk of fire, electric shock, explosion, or injury.
Page 7
Service Manual 7
Safety Precautions
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
Do not place a heater or other appliances near the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Wax
Thinner
Page 8
8 Room Air Conditioner
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away pro perly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
Installation
90˚
Unplug the unit if strange sounds, odors, or smoke comes from it.
Be cautious that water could not enter the product.
There is risk of electric shock or fire. There is risk of fire, electric shock, or product dam­age.
Safety Precautions
Page 9
Service Manual 9
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of fire, electric shock, or damage to the plastic parts of the product.
There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There is risk of personal injury and failure of product. There are sharp and moving parts that could cause
personal injury.
Operation
Wax
Safety Precautions
Page 10
10 Room Air Conditioner
Dimensions
Dimensions
Installation plate
D
H
W
W mm 840
H mm 270 D mm 153
Model
Dimension
7k, 9k, 12k, 14k Btu Series
Indoor Unit
This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the
air conditioner.
This symbol indicates special notes.
Symbols Used in this Manual
NOTICE
Page 11
Service Manual 11
Dimensions
Installation plate
D
H
W
W mm 1090
H mm 300 D mm 178
Model
Dimension
18k, 24k Btu Series
Page 12
12 Room Air Conditioner
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
DIM unit
W mm 770
H mm 540
D mm 245 L1 mm 285 L2 mm 65 L3 mm 518 L4 mm 10 L5 mm 100
Dimensions
Outdoor Unit
7k, 9k, 12k, 14k Btu Series
Page 13
Dimensions
Service Manual 13
W
L7 L6 L8 L9
D
L1
L2
L3
L10L11
L4L5
H
Gas side
Liquid side
MODEL
DIM
W mm 870
H mm 655
D mm 320 L1 mm 370 L2 mm 340 L3 mm 25 L4 mm 630 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54
L10 mm 74.5 L11 mm 79
18k, 24k Btu Series
Page 14
14 Room Air Conditioner
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a
place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
More than 10cm
More than
5cm
More than 2.3m
More than
5cm
Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
5K~28K 10 5
30K~38K 30 12
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
5k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
Page 15
Service Manual 15
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so as not to disconnect.
Close the Front Grille.
How to Fix Installation Plate Drill a Hole in the Wall
Drain hose junction
Remove the rubber stopple in the desired drain direc­tion.
Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
Installation Plate
Type "A" screw
Chassis
Hook
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation plate
Left rear piping Right rear piping
Ø70mm
Ø70mm
DB
A
C
Connecting
part
Adhesive
Drain hose
Only the desired direction
ABCD
7k, 9k, 12k, 14k 75 65 105 65
18k, 24k 105 65 260 65
CHASSIS
(Grade)
Distance (mm)
Page 16
16 Room Air Conditioner
Flaring work and connection of piping
Flaring work and connection of piping
Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Preparing the indoor unit's piping and drain hose for instal­lation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.(Optional)
Carry out flaring work using flaring tool as shown below.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Drain hose
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5 Ø15.88 5/8 0~1.0 Ø19.05 3/4 1.0~1.3
Outside diameter A
Connection of piping -- Indoor
When install, make sure that the remaining parts must be removed clearlysoasnottodamagethepip­ing and drain hose, especially power cord and connecting cable.
Copper
pipe
Slanted Uneven Rough
90°
Page 17
Service Manual 17
Flaring work and connection of piping
Route the indoor tubing and the drain hose in the direction of rear right.
Drain hose
Connecting
cable
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Plastic bands
Insulation material
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Indoor unit tubing Flare nut Pipes
Drain hose
Connecting pipe
Connecting cable
Tape
Drain hose
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Indoor unit installation
Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensurethatthehooksareproperlyseatedontheinstalla­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click­ing sound).
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
For right rear piping
Page 18
18 Room Air Conditioner
Flaring work and connection of piping
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Route the indoor tubing and the drain hose to the required piping hole position.
Insert the piping, drain hose, and the connect­ing cable into the piping hole.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Indoor unit installation
Hang the indoor unit from the hooks at the top of the instal­lation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Tape the drain hose and the connecting cable.
Connecting cable
Drain pipe
Connecting cable
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Indoor unit tubing Flare nut Pipes
Installation plate
Spacer
Indoor unit
8cm
Plastic bands
Insulation material
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
For left rear piping
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Page 19
Service Manual 19
Installation Information (For left piping)
Good case For left piping. Follow the instruction below.
Press on the upper side of clamp. ( )
Flaring work and connection of piping
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Reroute the pipings and the drain hose across the back of the chassis.
Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Tubing holder
Drain hose
Connecting
cable
Unfold the tubing to downward slowly. ( )
Bend the tubing to the left side of chassis.
Page 20
20 Room Air Conditioner
Flaring work and connection of piping
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Bad case
Following bending type from right to left could cause
problem of pipe damage.
Connection of the pipes-Outdoor
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Page 21
Service Manual 21
Connect the cable to the Indoor unit.
Connecting the cable between indoor unit and outdoor unit
Connecting the cable between indoor unit and outdoor unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
The above circuit diagram is subject to change without notice.
The earth wire should be longer than the common wires.
When installing, refer to the circuit diagram behind the panel front of the indoor unit.
Connect the wires firmly so that they may not be pulled out easily.
Connect the wires according to color codes, referring to the wiring diagram.
If a power plug is not used, provide a circuit breaker between power source and the unit as shown by.
The power cord connected to the "A" unit should be selected according to the following specifications(Type "B" approved by HAR or SAA).
The power connecting cable connecting the indoor and outdoor unit should be selected according to the following specifications (Type "B" approved by HAR or SAA).
Air
Conditioner
Main power source
7k 9k~14k 18k 24k
0.75 1.0 1.5 2.5
Unit(A) Indoor Indoor Indoor Indoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05VV-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm2)
7k 9k~14k 18k 24k
0.75 1.0 1.5 2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F H07RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm2)
Circuit Breaker
Use a circuit breakerortime delay fuse.
Page 22
22 Room Air Conditioner
Connecting the cable between indoor unit and outdoor unit
Remove the control cover from the unit by loosening the screw.
Connect the wires to the terminals on the con­trol board individually.
Secure the cable onto the control board with the cord clamp.
Refix the control cover to the original position with the screw.
Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately discon­nect all supply lines must be fitted.
Terminal block
Over 5mm
Cover control
Connecting cable
Connecting cable
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 21))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
Connect the cable to the outdoor unit
5k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Circuit
Breaker
(A)
Grade
Page 23
Service Manual 23
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the drainage Form the piping
To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using sad­dle or equivalent.
To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap
to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
Pull the right and the left side.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Page 24
24 Room Air Conditioner
Air purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
Pressure in the system rises.
Operating current rises.
Cooling(or heating) efficiency drops.
Moisture in the refrigerant circuit may freeze and block cap-
illary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Do a leak test of all joints of the tubing(both indoor and out­door) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been complet­ed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leak test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
Air Purging
Air purging
Air purging with vacuum pump
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Page 25
Service Manual 25
Air purging
Evacuation
Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
(1) Remove the caps from the 2-way and 3-way valves. (2) Remove the service-port cap from the 3-way valve. (3) To open the 2-way valve turn the valve stem counter-
clockwise approximately 90°, wait for about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent on the
indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h vacuum
pump is used
10 min. or more 15 min. or more
If tubing length is less than 10m (33 ft)
if tubing length is longer than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Page 26
26 Room Air Conditioner
Test running
Test Running
1. Check that all tubing and wiring have been properly con-
nected.
2. Check that the gas and liquid side service valves are fully
open.
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration bushing.
NOTE: If the actual pressure is higher than shown, the system is
most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
Power-Failure Compensation Function User Selection ON/OFF
1) Operation Sequence Press the forced switch until BUZZER sounds 2 times
(beep~beep~). Release the forced switch if BUZZER sounds. Check the function selection ON/OFF with the operation LED.
2) Checking function-selection ON/OFF
- Function-Selection ON: One time blinking of operation LED
would repeat 4 times.
- Function-Selection OFF: Two times blinking of operation LED
would repeat 4 times.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C(95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C(95°F) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to
0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Power
button
Page 27
Service Manual 27
Functions
Functions
Indoor Unit
Cooling Mode Operation
Healty dehumidification Mode Operation
Heating Mode Operation
Jet Cool Mode Operation
Jet Heat Mode Operation
Energy Saving Cooling Mode Operation
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature sensor. (Thermistor)
Pipe temperature sensor. (Thermistor)
Room temperature control
Maintain the room temperature in accordance with the Setting Temp.
Starting the Current Control
Indoor fan is delayed for 5 sec at the starting.
Time Delay Safety Control
Restarting is for approx. 2 minutes.
Indoor Fan Speed Control
Super High, High, Med, Low
Operation indication Lamps (LED)
--- Lights up in operation
--- Lights up in Sleep Mode (Optional)
--- Lights up in Timer Mode
--- Lights up in Preheat Mode (for Heating Model)
--- Lights up in Plasma Air Clean Mode
--- Lights up in during Energy-Saving Cooling Mode Operation (Optional)
Page 28
28 Room Air Conditioner
Functions
Sleep Mode Auto Control
The fan is switched to low(Cooling), low(Heating) speed.
The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Natural Air Control by CHAOS Logic
The fan is switched to intermittent or irregular operation
The fan speed is automatically switched from high to low speed.
Airflow Direction Control
The louver can be set at the desired position or swing up and down automatically.
Auto Changeover
Energy-Saving Control(Optional)
Horizontal airflow Direction Control(Optional)
Auto Clean(Optional)
Plasma
The function will be operated while in any operation mode with selecting the function.
The function is to be stopped while it isoperating with selecting the function.
Defrost(Deice) Control (Heating)
Both the indoor and outdoor fan stops during defrosting.
Hot-start Control (Heating)
The indoor fan stops until the evaporator pipe temperature will be reached at 34°C.
Heater (Optional)
Page 29
Service Manual 29
Functions
If power is on, it will operate to chage capacitor on controller and power relay will operate after about 2~5sec.
The active power filter is designed to correct power factor(cos θ) and to regulate DC link voltage.
It will be operated PFC circuit when the compressor freq. is over 30Hz and wattage is over 450 watt.
The final operating freq. of comp. is set the lowest freq. that limited outdoor temp., discharge pipe temp.,
heat-sink temp., target freq., owing to CT.
It will be changed the drive freq. of comp. according to temp. of indoor and outdoor.
It is only operated in the heating operation mode except defrosting operation.
High speed
- Although fan motor speed is middle, it will change high speed in case of below AC193V, over 45°Cof outdoor temp., and over fc, fh of comp. Freq.
Middle speed
- Nomal mode
Low speed
- Although fan motor speed is middle, it will change Low speed in case of over AC 270V, over 21°C (Heating Mode) of outdoor temp. below 24°C (Cooling Mode) of outdoor temp.
When the temp. of power module increases to 85°C, controller decreases Freq. of Comp.
Outdoor Unit
Power Relay Control
Active Power Filter Control(PSC)
Comp. Freq. Control
OverheatIng. Protection(Power Module)
Freq. Speed Control(Up/Down Speed)
Total Current Control (Over Current Protection)
DC Peak Current Control
4 way Valve Control
Outdoor Fan Motor Control
Discharge Pipe Temp. Control
Low Ambient
Comp. Torque Control
Over Heating Protection (Comp.)
Page 30
30 Room Air Conditioner
Operation
Function of Controls
Operation
• DISPLAY
1) C/O Model Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
OFF except when hot start during heating mode operation or while in defrost control.
If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode, compressor, outdoor fan are turned off.
When indoor pipe temp. is 7°C or higher after 2 min pause of compressor compressor, outdoor fan is turned on according to the condition of the room temperature.
Comp. free
Comp. Step 4 Comp. Step 2
Comp. off
0˚C
3˚C
6˚C
7˚C
Indoor pipe temp.
Protection of the evaporator pipe from frosting
Page 31
Service Manual 31
Operation
Cooling mode operation
Operating frequency of compressor depend on the difference of the temperature. (= intake air Temp.- Compressor off Temp.
Compressor off temp.= setting temp.-0.5°C
on temp. = setting temp. +0.5°C
If compressor operates at some operating frequency, the operating frequency of compressor cannot be changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp.
-
0.5°C and setting temp.
-
1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp.
-
1.0°C.
Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences Comp. Operating frequency
over 2.5°C Step 7
2.0~2.49°C Step 6
1.5~1.99°C Step 5
1.0~1.49°C Step 4
0.5~0.99°C Step 3
0.0~0.49°C Step 2
0.5~0°C Step 1
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
AS-W0964DH0/GH0 35 39 43 47 52 57 62 AS-W1264DH0/GH0 20 35 47 56 63 70 78 AS-W1865DH0/GH0 16 32 58 64 70 75 85
AS-W1224DH0 20 35 47 54 65 70 74 AS-W1424DH0 20 35 47 54 72 74 78 AS-W1825DH0 16 32 53 62 72 75 85
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5(Fc) Step 6 Step 7
Healthy Dehumidification mode operation
When the dehumidification operation is set by the remote controller the intake air temperature is detected and the setting temp. is automatically set according to the intake air temperature.
When intake air temp reaches above the temp of setting +1.0°C, condition of compressor same as cooling mode operation.
When intake air temperature reaches bolow the temp of setting –1.0°C, compressor operate step1~step3 and indoor fan speed repeatly operate low or stop.
Intake air Temp.
26°C intake air temp.
24°C intake air temp.< 26°C
18°C < intake air temp. < 24°C
intake air temp. ≤ 18°C
Setting Temp.
25°C
intake air temp. -1°C
intake air temp. -0.5°C
18°C
Page 32
32 Room Air Conditioner
Operation
Operating frequency of compressor depend on the difference of the temperature (= compressor off temp. - intake air temp.)
Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
If compressor operates at some operation frequency, the operating frequency of compressor cannot be changed within 30 seconds.
Condition of compressor turned off
- When intake air temperature reaches +3°C above the setting temperature.
Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 30°C
While in defrost control, between the indoor and outdoor fans are turned off.
Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C ~0.0°C
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Heating mode operation
Model
AS-W0964DH0/GH0 35 44 53 62 69 74 80 AS-W1264DH0/GH0 20 38 53 63 72 79 86 AS-W1865DH0/GH0 16 38 47 65 79 87 96
AS-W1224DH0 20 35 53 63 70 79 86 AS-W1424DH0 20 35 53 63 77 79 86 AS-W1825DH0 16 38 47 62 79 87 90
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation(cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated super-high speed for 30 min. at cooling mode operation.
In the Jet Cool mode, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode input while the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vane is reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet cool mode operation
Page 33
Service Manual 33
Operation
While in cooling mode or Fuzzy operation, the Jet Heat key cannot be input. When it is input while in the Heating mode operation (dehumidification), the Jet Heat mode is operated.
In the Jet Heat mode, the indoor fan is operated super-high speed for 60 min. at Heating mode operation.
In the Jet Heat mode, the room temperature is controlled to the setting temperature, 30°C.
When the sleep timer mode input while the Jet Heat mode operation, the Jet Heat mode has the priority.
When the Jet Heat key is input, the upper/lower vane is reset to those of the initial Jet heating mode and
then operated in order that the air outflow could reach under flow.
1. New Chaos swing mode
By the Chaos swing key input, the upper/lower vane automatically operates with the Chaos swing or it is fixed to the desired direction.
Mode2
Mode3
Mode4
Mode5
Mode6
Mode7
Mode8
Mode9
OPEN
CLOSED
8°
Cooling Operation
120°
Mode2
Mode3
Mode4
Mode5
Mode6
Mode7
Mode8
Mode9
OPEN
CLOSED
8°
Heating Operation
120°
Mode1
Mode1
Mode2
Mode3
Mode4
Mode5
Mode6
Mode7
Mode8
OPEN
CLOSED
8°
Cooling Operation
Mode1
Mode2
Mode3
Mode4
Mode5
Mode6
Mode7
Mode8
OPEN
CLOSED
8°
Heating Operation
110°110°
Start
(S4) 7, 9, 12, 14k Model
(S5) 18, 24k Model
Start
Start
Start
Jet heat mode operation
Swing mode
Page 34
34 Room Air Conditioner
Operation
1. Sleep timer operation for cooling cycle
While in cooling mode operation, 30 min. later since the start of the sleep timer, the setting temperature
increase by 1°C. After another 30min. elapse, it increases by 1°C again.
2. Sleep timer operation for heating cycle
While in heating mode operation, 60 min. later since the start of the sleep timer, the setting temperature
decrease by 1°C. After another 60min. elapse, it decreases by 1°C again.
Setting temp. (˚C)
1.0˚C up
1.0˚C up
Cooling ON temp. (Setting temp. +0.5˚C)
Cooling OFF temp. (Setting temp. -0.5˚C)
0.5 1 Sleep time (hr
)
When the sleep time is reached after [1,2,3,4,5,6,7hr] is input by the remote control during the operation, the operation of the appliance stops.
When the appliance is on pause, the sleep timer mode cannot be input.
Sleep timer operation
Setting temp. (°C)
Heating ON temp. (Setting temp)
Heating OFF temp. (Setting temp. +3.0°C)
1.0°C down
1.0°C down
1 2 Sleep time (hr
)
Page 35
Service Manual 35
Operation
Auto restarting operation
Forced operation
Test Operation
When the power is restarted after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
Operation mode that is kept on the memory
- State of operation ON/OFF
- Operation mode/setting temp./selected airflow speed
- Sleep timer mode/remaining time of sleep timer
- Chaos Swing
To operate the appliance by force in case that the remote control is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions.
The operation condition is set according to the outdoor temp. and intake air temperature as follows.
The unit select before operating mode in 3 hours.
Press the Tact Switch for compulsory operation of the main body for 3 seconds in order to operate in the trial operation mode.
- Operation mode: Cold
- Indoor pan: Strong wind
- COMP frequency: Step 5
- COMP compulsorily operates for about 18 minutes irrespective of indoor temperature.
Indoor temp.
over 24°C
21~24°C
below 21°C
Setting temp.
22°C 23°C 24°C
Setting speed of
indoor fan
High speed
Operating Mode
Cooling
Healthy Dehumidification
Heating
Page 36
36 Room Air Conditioner
Operation
Power relay turns on 1 second later after the power is input to the outdoor unit.
Control sequence : power on PTC operating power relay on
CT1 control
If the operating current reaches I1, the operating frequency of the compressor decrease.
After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous-
ly, the operating frequency of compressor increase by 1step.
CT2 control
If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the compressor restart again.
If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.
I1:Current of operating frequency down
I2: Current of compressor cut off
cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.
Control table
DC Peak Current Error by a fault signal of IPM
If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the compressor lock
If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance turns off and display ERROR CODE 6.
DC Peak Current Error by the Outdoor Fan Lock
If its 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is operating, the appliance turns off and display ERROR CODE 6.
Power relay control
Protection from total current control
Protection from DC Peak Current
1 AS-0964DH0 5.5 6.5 6 7 9 2 AS-1264DH0 6.5 7.5 7 8 10 3 AS-1865DH0 9.0 10.5 9.5 11.0 13
I1
Cooling Heating Cooling Heating
Outdoor temp ≥ 38°C Outdoor temp < 38°C
I2
Model
Page 37
Service Manual 37
Operation
If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.
It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)
It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.
If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor
stop instantly.
It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
Temperature range by COMP SPEC varies by 10°C.
Portection from overheating of power module
Portection from overheating of compressor
1 AS-W0964DH0 95 105 2 AS-W1264DH0 95 105 3 AS-W1865DH0 85 95
No. MODEL T on T off
1 AS-W0964DH0 95 105 2 AS-W1264DH0 95 105 3 AS-W1865DH0 98 108
No. MODEL T on T off
T off °C
T = (T off - T on) T1 = T on + T T2 = T on + 2 * T
Heat Sink Temp.
T2 °C
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
D-Pipe T emp .
T off °C
T3 °C
T2 °C
T1 °C
-13 °C
COMP Freq. Free Free
Fh min
T = (T off - T2)/2 T1 = T2 - 2 * T T3 = T2 + T
OFFFc-1 Fc-1Fc-2 Fc-2
Page 38
38 Room Air Conditioner
Operation
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
Defrosting control is available 50 minutes later since heating cycle started and the pipe temperature of out­door unit reaches below -6°C.
Setting Freq.
Operating Freq. of Comp.
4-Way
EEV Open step
Outdoor FAN
Indoor FAN
Pre-Heat LED
Deice STEP
Fh
min
Minimum Time
of Heating
Main Deice time
Fh
min
Fh
min
ON
OFF
Setting Speed
ON
Hot
Start
OFF
Hot
Starting
ON
OFF
OFF
0123456
Setting
Starting step
Setting Freq.
Setting Speed
Setting Speed
Hi Speed
Defrosting control
Page 39
Service Manual 39
Operation
Function used to perform the Self Cleaning to prevent the Unit from Fungus and Bad Odors.
Used after the Shut Down of Cooling Operation to Clean the Evaporator and keep it as fresh for the Next operation.
During Self Cleaning the Outdoor Unit is Switched off.
The function is easy to be operated as It is accessed through the Remote Controller.
Auto Cleaning
Auto Changeover
Low Ambient
Comp.
ON
OFF
Setting Step Low
Indoor Fan
ON
2) Cooling/only Model
Cooling CYCLE
OFF
30 Min
Fan
ON
1) Heat/pump Model
Cooling CYCLE
OFF
Comp.
ON
ONOFF OFF
Indoor Fan Setting Step Low Low Low
13 Min
HeatingFan
60 Sec 120 Sec
Fan
The air conditioner changes the operation mode automatically to keep indoor tempera­ture.
When room temperature vary over ±2°C with respect to setting temperature, air condition­er keeps the room temperature in ±2°C with respect to setting temperature by auto change mode.
If outdoor temperature drops below certain temperature,liquid back is prevented by reducing fan speed. It can prevent frosting of evaporator and keep cooling operation
No matter even if the outdoor temperature reaches -10°C.
You can Cool your room at your desired temperature all your around.
Freq.
- 0°C
°
Outdoor temp.
Outdoor pipe temp. 0°C outdoor fan On/Off control
°
Comp Freq.
Outdoor fan
On
On
Off
Off
Outdoor temp.:-10°C
-5
0
5
10
15
20
25
0 50 100 150 200
Time(Min.)
Temp.(°C)
Outdoor fan On/Off control
Cond . temp.
COOLING
Auto Change Mode.
Outdoor temp. Indoor temp.
Outdoor temp.
30°C
20°C
10°C
+
2°C
+
1°C
+
0.5°C
Set Temp.
-
0.5°C
-
1°C
-
2°C
HEATING
Page 40
40 Room Air Conditioner
Remote Control Operations
Operation
The controls will look like the following.
1. START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high and CHAOS.
5. JET COOL/JET HEAT
Used to start or stop the speed cooling/heating. (speed cooling/heating operates super high fan speed in cooling/heating mode.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
8. TIME SETTING BUTTONS
Used to adjust the time.
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
13. PLASMA(OPTIONAL)
Used to start or stop the plasma function.
14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL)
Used to set the desired horizontal airflow direction.
15. RESET BUTTON
Used prior to resetting time.
16. 2ND F BUTTON
Used prior to using modes printed in blue at the bottom of buttons.
17. AUTO CLEAN (OPTIONAL)
Used to set Auto Clean mode.
ON
OFF
CANCEL
AUTO CLEAN
SET
1
3
5
4
9
10
12
14 16
7
2
8
13 15
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door (opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
17
Operation Mode
Page 41
Service Manual 41
Disassembly
Disassembly
Indoor Unit
Disconnect the unit from power supply before mak­ing any checks. Be sure the power switch is set to “OFF”.
To remove the Grille from the Chassis.
Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Earth Conductor
Page 42
42 Room Air Conditioner
Disassembly
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
Screw
When repair, do not damage the Caution label.
Page 43
Service Manual 43
Disassembly
Unhook the tab on the right inside of the chassis at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.
6. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from the self-aligning bearing.
Motor cover
Bearing
Cross-flow fan
Page 44
44 Room Air Conditioner
Troubleshooting Guide
Troubleshooting Guide
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
EER
COMPRESSOR
ACCUMU LATOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
3-WAY VALVE
COOLING HEATING
REVERSING VALVE
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
ACCUMU LATOR
GAS SIDE
3-WAY VALVE
LIQUID SIDE
3-WAY VALVE
CHECK VALVE
COOLING HEATING
REVERSING VALVE
(1) Cooling Only Models
Refrigeration Cycle Diagram
(2) Cooling & Heating Models
Page 45
Service Manual 45
Troubleshooting Guide
CAUTION:* Capicity is based on standard length and maximum allowance length is the basis of reliability. * Oil trap should be installed per 5~7 meters.
Outdoor unit
Indoor unit
A
B
In case more than 5m
7k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Additional
Refrigerant
(g/m)
Max.
Length
A (m)
Max.
Elevation
B (m)
Standard
Length
(m)
Pipe Length and the Elevation
Oil trap
Indoor unit
A
Outdoor unit
B
Page 46
46 Room Air Conditioner
Troubleshooting Guide
2-way, 3-way Valve
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open Open
Open Open
Works
Shipping
Air purging (Installation)
Operation
Pumping down (Transfering)
Evacuation (Servicing)
Gas charging (Servicing)
Pressure check (Servicing)
Gas releasing (Servicing)
1.
2.
3.
4.
5.
6.
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Open
(with charging cylinder)
Open
(with charging cylinder)
Page 47
Service Manual 47
Troubleshooting Guide
Required tools :
hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the joints, and gas leak detector.
The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not be done correctly and there gas leaks, a gas cylinder and the charge set will be needed.
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity, and could lead to a malfunction.
Procedure
(1) Recheck the piping connections. (2) Open the valve stem of the 2-way valve coun-
terclockwise approximately 90°, wait 10 sec­onds, and then set it to closed position.
– Be sure to use a hexagonal wrench to operate
the valve stem.
(3) Check for gas leakage.
Check the flare connections for gas leakage.
(4) Purge the air from the system.
– Set the 2-way valve to the open position and
remove the cap from the 3-way valve’s service port.
– Using the hexagonal wrench to press the valve
core pin, discharge for three seconds and then wait for one minute. Repeat this three times.
(5) Use torque wrench to tighten the service port
nut to a torque of 1.8kg.cm.
(6) Set the 3-way valve to the back seat. (7) Mount the valve stem nuts to the 2-way and 3-
way valves.
(8) Check for gas leakage.
– At this time, especially check for gas leakage
from the 2-way and 3-way valves stem nuts, and from the service port nut.
Service port nut: Be sure, using a torque wrench to tighten the service port nut (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
CAUTION:
Do not leak the gas in the air during Air purging.
CAUTION:
If gas leakage are discovered in step (3) above, take the following mesures :
If the gas leaks stop when the piping connections are tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, dis­charge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
Liquid side
Outdoor unit
3-way valve
Gas side
Indoor unit
2-way valve
Open
Clsed
Air purging
Page 48
48 Room Air Conditioner
Troubleshooting Guide
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valvesstemnutsandtheser­vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Pumping Down
Page 49
Service Manual 49
Troubleshooting Guide
Re-air Purging
(Re-installation)
Procedure
(1) Confirm that both the liquid side valve and the
gas side valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the Gas side valve.
Leave the valve on the gas cylinder closed.
(3) Air purging.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare nut on the liquid side valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.
– After purging the air, use a torque wrench to
tighten the flare nut on liquid side valve.
(4) Check for gas leakage.
Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and dis-
charge the refrigerant until the gauge indicates 3 to 5 kg/cm2g.
(6) Disconnect the charge set and the gas cylin-
der, and set the Liquid side and Gas side valves to the open position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
CAUTION: Do not leak the gas in the air during Air Purging.
Lo
Closed
OPEN
Closed
Gas cylinder
R22
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
3-Way valve
3-Way valve
Page 50
50 Room Air Conditioner
Troubleshooting Guide
Balance Refrigerant of the 3-way Valve
(Gas leakage)
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
Leave the valve on the charge set closed.Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi­cates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm
2
G), discharge the refrig­erant until the gauge indicates 0.5 to 1 kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 51
Service Manual 51
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Page 52
52 Room Air Conditioner
Troubleshooting Guide
Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys­tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Indoor unit
Check valve
Charging cylinder
Lo
(1)
OPEN
Liquid side
Gas side
CLOSE
3-Way
Open
valve
Open
3-Way valve
Outdoor unit
Page 53
Service Manual 53
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the reated
current
Temp. difference : over 8°C
Operating Current
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakege Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem­perature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.
Insufficient amount of Current is low.
Lower Higher refrigerant (Leakage)
Clogging Current is low.
High
Higher
Cycle Parts
NOTICE
NOTICE
Page 54
54 Room Air Conditioner
Troubleshooting Guide
Self diagnosis Function
1. Error indicator of air conditioner
1) Indoor : Operating LED / Outdoor : LED01M(Red) on the outdoor PCB
2) 2 more errors occur at same time
- Air conditioner Off condition : Display the error code of product off cause
- Air conditioner On condition : Display the prior Error Code
2. Cancellation of Error indicator
1) Error Code 1, 2, 3, 4, 10 : Error indicator canceled when cause of error recovered
2) Error Code 5, 8, 9 : Keep displaying Error indicator by restarting air conditioner, although cause of error recovered
3) Error Code 6, 7 : Error indicator canceled when power reset (Power Cord Off & On)
Error
Code
1
2
4
5
6
7
1 time
3
sec
2
Error Indicator
1
time
sec
3
times
3
sec
4times
3 sec
5times
3 sec
2
times
times
6
3
3
1
time
3
sec
sec
times
7
3
sec
sec
1
time
3 sec
times
2
3
sec
4
times
3
1
2times
sec
5times
sec
3
6
7
time
times
times
Cause of Error
Indoor Temp. sensor error
- Sensor open or short
Outdoor Temp. sensor error
- Sensor open or short
Heat Sink sensor error
- Sensor open or short
- Heat Sink temp is over 95°
Communication error
DC Peak error
Over current error (CT2)
Display
Indoor Outdoor
O
O
O
O
O
O
O
O
O
O
O
Indoor
Operation
ON
ON
ON
OFF
SHUT
DOWN
SHUT
DOWN
9
10
8times 8times
8
sec
3
9times
sec
3
10times
3 sec
9
times
10
Indoor fan lock error (BLDC fan model only)
Outdoor fan lock error (BLDC fan model only)
times
O
O
O
O
O
OFF
OFF
ON
Page 55
Service Manual 55
Troubleshooting Guide
Precaution in Service or Check
Even after stopping the operation of product, it takes some time to discharge the remaining electricity of the electrolytic capacitor that was charged. Before starting a checking or repairing job, pull out the plug out of the outlet and make sure that the lamp on the control board outdoor unit is off.
The Diagnosis Procedure
Check the supplied voltage to product (AC 220V/230V ± 30V).
Check the connecting cable between Indoor and Outdoor.
Check the blinking number of operation indicator
(refer to the self-diagnosis function).
Check the self-diagnosis table
Check the condition of connectors
The condition of P.C.B pattern.
Check the condition of connectors.
The condition of P.C.B pattern.
The electronic components.
Indoor Outdoor
Page 56
56 Room Air Conditioner
Troubleshooting Guide
Electronic Parts
Refer to electronic contorol device drawing & schematic diagram.
The Product doesnt operate at all.
Turn off the main power and wait to 10 seconds
Turn on the main power again.
Does "Beeping" sound is made from the indoor unit?
Primarily, the operating condi­tion of Micom is O.K.
Check CN-DISP1
CN-DISP2 of indoor PCB
Check the voltage of power(AC220V/AC240V, 50Hz).
The voltage of main power.
The voltage applied to the unit.
The connecting method of Indoor/Outdoor connecting cable (each color)
The P.C.B. Ass'y
(Fuse, Noise Filter, Power Module, Bridge Diode, etc.)
Trouble 1
NO
YES
The operation check of the Indoor P.C.B. Ass'y
Procedure
1) The input voltage of power mod­ule.
2) The output voltage of power mod­ule.
4) IC04D(7805)
5) IC01A(KIA7036)
Specification
1) AC230V ± 30V : Check the rated voltage
2) 12V ± 3V
4) DC5V
5) The voltage of micom pin 19 : DC4.5V
Remedy
1) Check the power outlet.
2) Replace P.C.B Ass'y
4) Replace P.C.B Ass'y
5) Replace P.C.B Ass'y
Page 57
Service Manual 57
Troubleshooting Guide
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 2 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force).)
Caused by the remote controller.
Caused by other parts except
the remote controller
When the mark ( ) is displayed in LCD
screen, replace battery.
Check the contact of CN-DISP 1, 2 connector
Check DISP P.C.B Ass'y
-Voltage between CN-DISP1 - :DC+5V
Check point
Check the connecting circuit between MICOM PIN and CN-DISP1 PIN
Check receiver ass'y
Product doesn't operate with the remote controller.
Trouble 2
Page 58
58 Room Air Conditioner
Troubleshooting Guide
Troubleshooting for error code
Error code
Description Cause of error
Indoor TH. is short or
1
open
Check flow
Indoor TH. is connected to Indoor pcb
- Connect to CN-TH1 in indoor pcb assembly
assembly ?
No
Indoor TH. (sensor) is short or open
Indoor TH. (sensor) is not connected to the indoor pcb assembly
Damage or defect on the sensing circuit of indoor pcb assembly.
(R01H, R02H, R03H, R04H, C01H, C02H)
YES
Indoor TH. is right ?
No
Check Indoor TH.
- Measure resistance of TH. (air : about 10k at 25°C, pipe : about 5k at 25 °C)
YES
Sensing circuit of indoor pcb
is right ?
No
- Check soldering state of R01H ~ R04H, C01H, C02H
Error code
Description
Outdoor TH. is short or
2
open
Check flow
Outdoor TH. is connected to outdoor pcb
- Connect to CN-TH1 in outdoor pcb assembly
assembly ?
No
Outdoor TH. (sensor) is short or open
Outdoor TH. (sensor) is not connected to the outdoor pcb assembly
Damage or defect on the sensing circuit of outdoor pcb assembly.
(R03H~R06H, C02H, C03H)
YES
Outdoor TH. is right ?
No
Check outdoor TH.
- Measure resistance of TH. (air : about 10k at 25°C, pipe : about 5k at 25 °C)
Cause of error
YES
Sensing circuit of outdoor
is right ?
pcb
- Check soldering state of R03H ~ R06H, C02H, C03H
No
Page 59
Service Manual 59
Troubleshooting Guide
9K / 12K
18K
Error code
Description Cause of error
Heat-sink Temp. is over 95°C
4
Heat-sink TH. is open or short
Check flow
Heat-sink TH is connected to outdoor PCB assembly?
No
- Connect to CN-TH2 in outdoor PCB assembly
Heat-sink TH. is damaged(short or open).
Heat-sink Temp. is over 95°C
Damage or defect on the sensing circuit of outdoor pcb assembly.
(R01H, R02H, C01H)
YES
Heat-sink TH. in INV-IC is Right ?
No
Check heat-sink TH.
- Measure resistance of TH. (about 10k at 25 °C)
YES
Sensing circuit of outdoor pcb is right ?
No
- Check soldering state of R01H, R02H, C01H
Error code
Heat-sink Temp. is over 95°C
4
Heat-sink TH. in outdoor pcb
Check flow
Heat-sink TH. Is connected to CN-TH2 in outdoor pcb ?
Connect to CN-TH2 in Outdoor pcb assembly
Description
is open or short
No
Heat-sink TH. in outdoor pcb is open or short
Heat-sink Temp. is over 95°C
Damage or defect on the sensing circuit of outdoor pcb assembly.
(R01H, R02H, C01H)
YES
Heat-sink TH. in outdoor pcb is Right ?
No
Check heat-sink TH.
- Measure resistance of TH. (about 10k at 25 °C)
Cause of error
YES
Sensing circuit of outdoor pcb is right ?
No
- Check soldering state of R01H, R02H, C01H
Page 60
60 Room Air Conditioner
Troubleshooting Guide
Error code
5
Communication Error
Check flow
Wiring connection Is right ?
No
Indoor 1(BR) 1(BR) 2(BL) 2(BL) 3(GN/YL) 3(GN/YL) 4(RD) 4(RD)
Outdoor
Description Cause of error
Wrong or missing wiring between indoor and outdoor unit cable
Defect of communication components in indoor pcb assembly
Defect of communication components in outdoor pcb assembly
Defect of power supply components in outdoor pcb assembly
No ground connection in air conditioner unit
(affected by noise in power source)
YES
Is the voltage of T/Block
, in outdoor about
AC 220/240V ?
No
Check power connector Is not connected to the T/Block in indoor unit.
YES
Is the voltage of GND & DC5V in Outdoor pcb about DC 5V ?
No
Check FUSE, NF01/02J, PTC, Power Module, BD-01S in Outdoor pcb assembly
YES
Communication circuit of indoor & outdoor pcb Is right ?
No
Check IC01K, IC02K,D01K~D03K, ZD01K~ZD03K, R01K~R10K, C01K~C04K
YES
Ground connection is installed ? (power outlet or outdoor chassis)
No
Install ground connection from outdoor unit. (In case power outlet has no earth port)
Earth port
Page 61
Service Manual 61
Troubleshooting Guide
Error code
6
Description Cause of error
DC Peak Error
Check flow
Supplied voltage to Outdoor pcb is about AC 220/240V ?
No
Check power source
Supplied power is not normal
Comp Connector (CN-U,V,W) is disconnected or inserted to wrong
position
Compressor is damaged (coil short) replace compressor
Too much Refrigerant
Defect in outdoor pcb assembly replace pcb assembly
YES
Is connector (CN-U,V,W) connected to compressor and inserted to pcb in right position ?
No
Check CN-U,V,W connector (U : RD, V : BL, W : YL)
Cause of error
YES
Refrigerant pressure is right ?
No
Check refrigerant pressure and adjust.
YES
Is the compressor right ?
Check resistance
Between U-V, V-W, U-W port. → Short / Open circuit (Comp.motor coil error) → normal : 1 ~2
Between U,V,W and Body °Ê normal : over10M
U
V
No
W
YES
Inverter components in outdoor pcb assembly are right ?
No
* 9K/12K Model Check
Short of SPM3 pins (GND - P, U, V, W pin) Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z Assembling state of R01P ~ R21P & IC01P Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.
* 18K Model Check
Short of SPM2 pins (GND –
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z Assembling state of R01P ~ R21P & IC01P Assembling state of screw between INV-IC &
Heat-sink
DC 15V output of Power module.
P, U, V, W pin)
Page 62
62 Room Air Conditioner
Troubleshooting Guide
Error code
Description Cause of error
Over current Error
7
Check flow
Supplied voltage to Outdoor pcb is about AC 220/240V ?
No
Check power source
YES
(CT2)
YES
Supplied power is not normal
Indoor/outdoor fan is locked
Too much refrigerant
Defect in current sensing circuit in outdoor pcb assembly
Does indoor / outdoor fan work normally ?
No
Check indoor / outdoor fan and adjust.
YES
Refrigerant pressure is right ?
No
Check refrigerant pressure and adjust.
Current sensing circuit is right ?
No
Check current sensing circuit.
- check CT is damaged in outdoor pcb (output wire is disconnected to pin or not)
- BD01N is inserted in right position (refer marking on pcb and component)
- Spec of R01N (1k), R02N (1.65k) is correct
- Direction of diode (D01N, D02N) is right
Page 63
Service Manual 63
Troubleshooting Guide
Error code
8
Description Cause of error
Indoor fan is locked
(BLDC fan model only)
Indoor fan is locked or separated
Fan connector is not connected to indoor pcb assembly
Defective in DC-fan driving circuit
Check flow
YES
Indoor fan is rotating ? (1) Indoor fan is rotating ? (2)
No
Check indoor unit
- remove obstacles in indoor unit
fan assembled correctly.
-
Check soldering state of CN-Motor1 & assembling state of DC Fan connector
No
YES
DC–fan driving circuit is right ?
No
Check DC Fan Driving circuit (Soldering state & Direction)
- R01F~R09F, C01F~C03F, IC01F~IC03F, Q01F~Q02F, ZD01F
Error code
9
Description Cause of error
Outdoor fan is locked
(BLDC fan model only)
Outdoor fan is locked by an obstacle (ex : branch of tree, baretc)
Fan connector is not connected to outdoor pcb assembly
Defective in DC-fan driving circuit
Check flow
YES
Outdoor fan is rotating ? (1) Outdoor fan is rotating ? (2)
No
Check outdoor unit
- remove obstacles in outdoor unit
Check connector is not connected to outdoor pcb assembly (CN-FAN2)
No
YES
DC–fan driving circuit is right ?
No
Check DC Fan driving circuit (Soldering state & Direction)
- R01F~R05F, C01F~C03F, Q01F~Q04F, ZD01F
Page 64
64 Room Air Conditioner
Troubleshooting Guide
Error code
Description Cause of error
D-Pipe TH. is short or
10
open
Check flow
D_PIPE TH. is connected to Outdoor pcb assembly ?
No
Connect to CN-D_PIPE in outdoor pcb assembly
D_pipe TH. is short or open
D_pipe TH. is not connected to the outdoor pcb assembly
Damage or defect on the sensing circuit of outdoor pcb assembly
YES
D_PIPE TH. is right ?
No
Check D_PIPE TH.
- Measure resistance of TH. (about 200k at 25°C.)
YES
Sensing circuit of outdoor pcb is right ?
No
- Check soldering state of R07H, R08H, C04H
Page 65
Service Manual 65
Wiring Diagram
Schematic Diagram
Indoor Unit
Models: AS-W0964DH0, AS-W0964GH0
Models:AS-W1264DH0, AS-W1865DH0, AS-W1264GH0, AS-W1224DH0, AS-W1424DH0, AS-W1825DH0
Schematic Diagram
Page 66
66 Room Air Conditioner
Schematic Diagram
Outdoor Unit
Models: AS-W0964DH0, AS-W0964GH0
Models: AS-W1264DH0, AS-W1264GH0, AS-W1224DH0, AS-W1424DH0
Page 67
Service Manual 67
Schematic Diagram
Models: AS-W1865DH0, AS-W1825DH0
Page 68
68 Room Air Conditioner
Schematic Diagram
Components Location
TOP VIEW
BOTTOM VIEW
Indoor Unit
Models: AS-W1264DH0, AS-W1865DH0, AS-W1264GH0, AS-W1224DH0, AS-W1424DH0, AS-W1825DH0
Page 69
Service Manual 69
BOTTOM VIEW
TOP VIEW
Schematic Diagram
Models: AS-W0964DH0, AS-W0964GH0
Page 70
70 Room Air Conditioner
TOP VIEW
Schematic Diagram
BOTTOM VIEW
Outdoor Unit
Models: AS-W0964DH0, AS-W1264DH0, AS-W0964GH0, AS-W1264GH0, AS-W1224DH0, AS-W1424DH0
PCB : 6870A90055M_1(040221) Assy : 6871A10128
2004.02.21.
C09S
R03S
-
IGBT
R05S
D01S
IC02S
SPM3:6002EC2005C SPM3:6002EC2005D
C05S
C06S
IC01S
R06S
D01Z
R13Z
D02Z
C08Z
C10Z
1
R14Z
D03Z
C12Z
R15Z
21
22
C16Z
CN-FAN1/PUMP
CN-4WAY
CN-PUMP
RY-PUMP
CT
+
-
C01N
C01S
CN-PC
CN-TH2
C01HC04H
GND
IC01A
C02A R02Y D01Y
R03Y C01Y
5V
OJ01
OSC01B
MICOM
IC02M
C05H
CN-S/VALVE1
CN-LEV
CN-COIL1
J09~12(JAPAN)
J09 J10 J11 J12
J13~15(EUROPE)
J13 J16 J14 J15
RY-H/PUMP RY-4WAY
C01M
J05~08(JAPAN)
J08
J07
J05
BD02S
~
~
R02S
R01S
BD01S
~
+
-
+
~
J01~04(EUROPE)
J01 J02 J03 J04
C03S
J06
CN-COIL2
C02S
C19Z
SPM3
5
R20Z
9
R21Z
R22Z
20
13
17
BL-V
RD-U
YL-W
15
11
R16Z
25 2623
24
27
CN-FAN2
C07D
POWER MODULE
5
6
R04P
R23Z
87 13
L1
C06D
R02D
R21P
R14P
R13P
R11P
R03P
R01P
R12P
R02P
C05D
C03F
CN-D_PIPE
CN-TH1
R01Y
1
3
129
C03H C02H
C02F
ZD01F
R05F
C01C
R01D
C04D
C03D
C01D
D01D
L2
EEPROM
IC01D
C02D
R17P
R15P
R16P
CN-S/VALVE2
T1
3
1
J33
+
~
4
-
~
~
D01N
BD01N D01C
R01N
R02N
C03C
D02N
R07C
GND
LED01M
TXD
7
~
RY_PWR
BD01C
4
R04C
R02C
R03C
C02C
R01C
Q01C
R05C
R06C
D02C
D02K
ZD02K
15V
ZD01K
R10K
C04K
C03K
IC01K
ZD03K
IC02K
RXD
R02F
D03K
R09K
R08K
D01K
R06K
R07K
R05K
C09J
RD
CN-TEST
WCN-NOISE2
PTC
J34
J32
J31
ZNR01J
NF01J
J27~34(JAPAN)
J29
J28
J27
J30
C08J
3
C06J
C07J
N/F02J
J24
J23
J22
J26
J21
J20
J19
J18
J17
C04J
J25
R02J
R03J
C05J
R01J
WCN-NOISE1
ZNR02J
SURGE
FUSE
C02J
C01J
BK
WCN-NOISE3
C10J
WH
J27
J30
J28
J29
J34
C08J
C06J
C07J
WCN-NOISE1
J25
J24
J26
R03J
R02J
C05J
R01J
ZNR02J
SURGE
C02J
WH
J20
J22
J23
J21
J19
N/F02J
C04J
ZNR01J
NF01J
C10J
C01J
BK
WCN-NOISE3
CN-4WAY
CN-OXY2
R01C
D01K
R07K
WCN-NOISE2
T1
+
BD01C
R04C
R02C
R03C
D01C
C02C
Q01C
C03C
R05C
D02C
R06C
D02K
ZD02K
ZD01K
R10K
C04K
C03K
R01K
16
IC01K
ZD03K
1
R04K
C08S
IC02K
R05K
R02F
D03K
C09J
CN-TEST
RD
CT
+
RY-OXYRY-4WAY
BD01N
R01N
D01N
R02N
C01N
D02N
R07C
CN-PC
CN-TH2
C01H
IC01A
LED01M
R03A
R01M
R02M
OSC01B
IC01M
C04C
C07S
R08S
R07S
R02K
C18Z
R02X
R01X
C01F
R01F
C01K
C02K
IC02M
CN-S/VALVE1
C02H
R02A
R02H
C02A
OJ01
R04M
R03M
C02N
R17H
R02Y
C01A
R01A
D01Y
C01B
1
17
C01X
C01T
C06P
33
R19P
C05H
R18P
CN-LEV
J32
J31
J33
RY_PWR
R08C
J18
J17
R09K
R08K
R06K
FUSE
CN-FAN1/PUMP
RY-H/PUMP
J09
J10 J11 J12
C01S
C03H
R01H
R04H
R03H
R03N
C01C
MICOM
1
64
64
C07P
C08P
49
Q01F
R20P
Q03F
CN-S/VALVE2
J13 J16 J14
J15
CN-D_PIPE
CN-TH1
C04H
C02F
R07H
R04F
R06H
R05H
R08H
R03F
Q04F
R03Y
ZD01F
R05F
C01Y
Q02F
C01L
EEPROM
C04D
R02L
R01L
R10Z
R12Z
R08Z
IC01D
R11Z
R09Z
R07Z
C01M
CN-COIL1
R01D
C03D
C02D
J06
J08
J05
J07
C02S
C03F
CN-FAN2
R01Y
315
6
POWER MODULE
12 13
89
7
D01D
C01D
L1
L2
R16P
R02D
C05D
R15P
R17P
BD01S
CN-COIL2
J01 J02 J03 J04
C19Z
C07D
R04P
C04P
C06D
R08P
C05P
1917 2011 13
YL-W
R23Z
BL-V
RD-U
R21P
R14P
27
R01P
R12P
R02P
R10P
C02P
R06P
R07P
IC01P
BD02S
C09S
C03S
R01S
R02S
SPM3
8
5
9
15
R20Z
R21Z
R22Z
R16Z
25
R03P
R11P
C01P
R09P
R05P
C11Z
24 26
2322
R13P
C15Z
C03P
C04Z
R04Z
C06Z
C05Z
R05Z
R03S
IGBT
R05S
C05S
D01S
C06S
IC02S
IC01S
R06S
C07Z
C08Z
D01Z
1
C09Z
R13Z
C10Z
D02Z
R14Z
D03Z
SPM3
C12Z
R15Z
R17Z
C17Z
C13Z
C14Z
R01Z
C01Z
R18Z
21
R19Z
R03Z
C02Z
C03Z
R02Z
C16Z
R06Z
Page 71
Service Manual 71
Schematic Diagram
TOP VIEW
BOTTOM VIEW
Models: AS-W1865DH0, AS-W1825DH0
BD02S
~
~
-
R03S
C09S
D01S
R05S
C06S
C05S
IC01S
R06S
C08Z
R13Z
C10Z
R14Z
C12Z
R17Z
R16Z
IGBT
R02S
R01S
C10S
23 22
21 20
19 18
17 16 15
14 13
12 11 10R15Z
9 8 7 6 5 4 3 2 1
SPM2
C16Z
BD01S
WCN-CAP2 WCN-CAP1
CN-4WAY
JS21~23
RY-4WAY
Y
C05D
P/NO
RY-L
C03S
R02D
C06D
D01D
L1
L2
15V
R01D
C01D
EEPROM
C02D
GND
1A20349
: 687
R17P
R15P
R16P
+
~
+
~
-
C01S
CN-COIL2
5
6
IPM
3
P
987
W
YL-W
V
BL-V
U
RD-U
Nw
Nv
R04P
Nu
25 24
C18Z
R01P
R11P R12P
R02P
R03P
CN-COIL1
C02S
C07D
POWER MODULE
1
13
12
IC02S
PWB P/NO : 6870A90148A(030509)
PWB ASS
R14P
R21P
R13P
CN-FAN1
CT
RY-H
T1
3
4
1
7
C04S
CN-FAN2
C03F
IC01D
C03D
C04D
MICOM
OSC01B
CN-LEV
C05H
C02F
R05F
R02F
ZD01F
CN-TH1
1
CN-D_PIPE
C04H
IC01A
LED01M
CN-TEST
CN-TH2
1
C03H
C02H
C01N
OJ01
C02A
CN-PC
C08J
C07J
PTC
3
RY-PWR
BD01C
C03C
-+
D01C
R04C
R01Y
R03C
R07C
R02C
R02Y
D01Y
R03Y
C01Y
1
C01H
RXD
TXD
C01C
C02C
Q01C
R01C
IC01K
ZD03K
IC02K
R05K
R07K
R06K
D03K
BK(WCN-NOISE4)
JS11~15
NF02J
C09J
JS16~20
4
NF01J
BD01N
+
-
R01N
R05C
R02N
R06C
D01N
D02C
D02N
JS01~05
C03K
C04K
JS24~25
D02K
R10K
ZD01K
ZD02K
D01K
R08K
NF03J
R09K
JS26~27
C11J
BK(WCN-NOISE1)
C01J
FUSE
RD
C06J
C05J
C04J
BK(WCN-NOISE3)
JS06~10
BK(WCN-NOISE2)
C02J
C03J
SURGE
R01J
ZNR01J
ZNR02J
BR
BL
NF02J
C06J
C05J
C04J
R03J
C02J
C01J
C03J
R02J
SURGE
R01J
ZNR01J
ZNR02J
FUSE
C08J
R04J
C09J
C07J
PTC
T1
C04S
RY-PWR
BD01C
NF01J
C04K
JS24~25
NF03J
JS26~27
C03C
BD01N
R01N
R02N
D01N
D02N
C03K
D02K
R10K
ZD02K
D01K
R08K
R09K
C11J
D01C
R05C
R06C
R04C
D02C
R07C C01C
Q01C
IC01K
ZD01K
ZD03K
IC02K
R05K
R07K
R06K
D03K
R01Y
R03C
R02C
R02Y
C02C
D01Y
R01C
R03Y
C01Y
CN-TH2
R02H
R03H
R01H
R04H
C02H
C01H
R01K
R02K
R04K
C01N
C01K
C02K
Q03F
Q04F
R04F
R01F
C01F
R03F
C02F
R05H
R06H
0J01
R17H
CN-PC
Q02F
Q01F
ZD01F
R05F
R02F
CN-TH1
CN-D_PIPE
R07H
R08H
C03H
C04H
R03N
R03M
R04M
C02N
R02M
C01A
C02A
IC01A
R03A
LED01M
R01M
CN-TEST
C05H
CN-FAN1
WCN-CAP2
CT
RY-H
WCN-CAP1
RY-4WAY
RY-L
C03S
CN-FAN2
R02D
C05D
C06D
D01D
L1
C03F
L2
IC01D
C03D
C04D
MICOM
64
1
R02A
OSC01B
R01A
IC01M
IC02M
R01X
R02X
C01X
CN-LEV
C01D
R01D
EEPROM
C02D
C01T
R12Z
C06Z
R19Z
R01L
C01L
C07S
R10Z
R09Z
R11Z
C05Z
C04Z
C02Z
R03Z
R06Z
R05Z
R02Z
C03Z C07P
R18P
R19P
R20P
R10P
C08P
C06P
R08P
R06P
C18Z
R20Z
C05P
C17Z
R16P
R15P
R17P
CN-4AWY
JS21~23
CN-COIL1
C02S
C07D
POWER MODULE
R02L C08S
R08S
R07S
IC02S
R07Z
R08Z
C01Z
R04Z
R01Z
R14P
C04P
R21P
C01P
IC10P
C03P R09P
BD01S
CN-COIL2
P
W
V
U
Nw
Nv
R04P
Nu
24
C18Z
R01P
R11P
R05P
R12P
C02P
R02P
R07P
R13P
R03P
BD02S
R03S
C09S
C01S
IGBT
R02S
R01S
C20Z
SPM2
D01S
R05S
C06S
C05S
C10S
1
IC01S
R06S
D01Z
C08Z
23
C07Z
D02Z
C10Z
C09Z
D03Z
C12Z
C11Z
R15Z
R18Z
R17Z
C13Z
R16Z
C14Z
C15Z
Page 72
72 Room Air Conditioner
Schematic Diagram
DISPLAY ASSEMBLY
6871A20574A
6871A20624A
Page 73
Service Manual 73
Product Specifications
Product Specifications
Table-1
Model Name
Item Unit
W
MIN kcal/h.(W)
Btu/h.
W
Cooling Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
W
MIN kcal/h.(W)
Btu/h.
W
Heating Capacity Type kcal/h.(W)
Btu/h.
W
Max kcal/h.(W)
Btu/h.
IN:20°C,Out: -10°C(Heater ON)
Btu/h.
IN:20°C,Out: -10°C(Heater OFF)
Btu/h.
Power Input Cooling W
Heating W Heating(-10°C,Heater ON)
W
Heating(-10°C,Heater OFF)
W
Running Current Cooling A
Heating A Heating(-10°C,Heater ON)
A
Heating(-10°C,Heater OFF)
A
Starting Current Cooling A
Heating A Cooling kcal/hW
EER Btu/h.W
Heating kcal/hW
Btu/h.W
COP Cooling W/W
Heating W/W Power Supply Ø,V,Hz Power Factor % Air Circulation Indoor,Max m3/min(CFM)
Outdoor,Max m3/min(CFM) Moisture Removal l/h.(pts/h.) Noise Level Indoor,High dB(A)±3 (Sound Med. dB(A)±3 Pressure,1m) Low dB(A)±3
Outdoor,Max dB(A)±3 Refrigerant(R410A)Charge Power Cord AWG#:P*mm
2
Connecting Cable AWG#:P*mm
2
Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in)
Length,std m(in) Drain Hose (O.D , I.D) mm(in)
Indoor mm Dimension inch (W*H*D) Outdoor mm
inch
Net Weight Indoor kg(lbs)
Outdoor kg(lbs)
1,758 1,143 2,755 1,512 983 2,369 6,000 3,100 9,400 2,637 3,516 5,274 2,268 3,024 4,536 9,000 12,000 18,000 3,033 4,043 6,096 2,608 3,478 5,242
10,350 13,800 20,800
1,465 879 1,406 1,260 756 1,210 5,000 3,000 4,800 3,296 4,043 6,065 2,835 3,478 5,216
11,250 13,800 20,700
3,810 4,659 6,651 3,276 4,007 5,720
13,000 15,900 22,700
-- -
-- ­690 970 1,640 910 1,120 1,680
-- -
-- -
3.4 4.2 7
4.2 5.1 8
-- -
-- -
3.4 4.2 7.5
4.2 5.1 8.5
3.29 3.29 2.8
13.04 13.04 10.98
3.12 3.12 3.11
10.36 12.32 12.32
3.82 3.82 3.22
3.62 3.61 3.61
1,220-240,50 1,220-240,50 1,220-240,50
97 97 97
7.2(254) 8.7(307) 13.0(459) 26(918) 26(918) 42(1483)
1.4(2.94) 1.5(3.2) 2.12 38 40 42 35 37 ­29 31 36 48 49 55
810(26.5) 845(28.5) 1200(40.8)
16:3*1.0 16:3*1.0 12:3*2.5 16:4*1.0 16:4*1.0 12:4*2.5
6.35(1/4) 6.35(1/4) 6.35(1/4)
9.52(3/8) 12.7(1/2) 12.7(1/2)
7.5(295) 7.5(295) 7.5(295)
21.5,16.0(0.85,0.63) 21.5,16.0(0.85,0.63) 21.5,16(0.85,0.63) 758*260*160 758*260*160 758*260*160
29.8*10.2*6.3 29.8*10.2*6.3 29.8*10.2*6.3 770*540*245 770*540*245 770*540*245
30.3*21.3*9.6 30.3*21.3*9.6 30.3*21.3*9.6
9(20) 9(20) 13.5(30)
38(83.8) 38(83.8) 60(132.3)
AS-W0964DH0 AS-W0964GH0
AS-W1264DH0 AS-W1264GH0
AS-W1865DH0
Page 74
Product Specifications
74 Room Air Conditioner
Table-2
Buyer Models
Item Unit
Min. kcal/h.(W)
Btu/h.
Cooling Capacity Type kcal/h.(W)
Btu/h.
Max. kcal/h.(W)
Btu/h.
Min. kcal/h.(W)
Btu/h.
Heating Capacity Type kcal/h.(W)
Btu/h.
Max. kcal/h.(W)
Btu/h.
Power Input Cooling W
Heating W
Running Current Cooling A
Heating A
Starting Current Cooling A
Heating A Cooling kcal/hW
EER Btu/h.W
Heating kcal/hW
Btu/h.W
COP Cooling W/W
Heating W/W Power Supply Ø,V,Hz Power Factor % Air Circulation Indoor,Max m3/min(CFM)
Outdoor,Max m3/min(CFM) Moisture Removal µP/h.(pts/h.) Noise Level Indoor,High dB(A)±3 (Sound Med. dB(A)±3 Pressure,1m) Low dB(A)±3
Outdoor,Max dB(A)±3 Refrigerant(R410A)Charge Power Cord AWG#:P*mm
2
Connecting Cable AWG#:P*mm
2
Connecting Tube Liquid Side mm(in) (Ø. Socket Flare) Gas Side mm(in)
Length,std m(in) Drain Hose (O.D , I.D) mm(in) Dimension Indoor mm (W*H*D) inch
Outdoor mm
inch
980(1,140) 989(1,150) 1,548(1,800)
3,890 - 6,142
3,024(3,517) 3,528(4,102) 4,536(5,274)
12,000 14,000 18,000
3,474(4,040) 3,732(4,340) 4,987(5,800)
13,800 14,810 19,790
757(880) 765(892) 1,204(1,400)
3,003 3039 4,777
3,478(4,043) 3,780(4,396) 5,242(6,096)
13,800 15,000 20,800
4,007(4,660) 4,119(4,790) 5,761(6,700)
15,900 16,344 22,861
1,100 1,320 1,600 1,120 1,300 1,685
5.0 5.9 7.0
5.1 5.8 8.0
5.0 6 7.5
5.5 7.1 8.5
2.75 2.67 2.84
10.91 10.61 11.25
3.11 2.91 3.11
12.32 11.54 12.34
3.20 3011 3.30
3.61 3.38 3.62
1,220,60 1, 220, 60 1,220,60
97 97 97
8.7(307) 8.7(307) 13.0(459) 26(918) 26(918) 42(1483)
1.5(3.2) 1.5(3.2) 2.12
40 40 42 37 37 ­29 29 36 49 49 55
845(28.5) 915 1200(40.8)
16:3*1.0 16:3*1.0 12:3*2.5 16:4*1.0 16:4*1.0 12:4*2.5
6.35(1/4) 6.35(1/4) 6.35(1/4)
12.7(1/2) 12.7(1/2) 12.7(1/2)
7.5(295) 7.5(295) 7.5(295)
21.5,16.0(0.85,0.63) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 758*260*160 758*260*160 1090*300*178
29.8*10.2*6.3 29.8*10.2*6.3 42.9*11.8*7.0 770*540*245 770*540*245 870*655*320
30.3*21.3*9.6 30.3*21.3*9.6 34.3*25.8*12.6
AS-W1224DH0 AS-W1424DH0 AS-W1825DH0
Page 75
Service Manual 75
Exploded View
Exploded View
135301
152302
342800
264110
263230
359011
131410 733010
135312
135311
159901
268712
146811
668713
346810
266090
135516
35211B
354210
249951
268714
267110
Indoor Unit
Page 76
76 Room Air Conditioner
Exploded View
Outdoor Unit
Models: AS-W0964DH0, AS-W1264DH0AS-W0964GH0, AS-W1264GH0, AS-W1224DH0, AS-W1424DH0
(UL Chassis)
554031
435511
552202
552116
552201
554160
561410
552111
550140
552203-1
552203-2
430410
649950
552102
437210
435301
559010
546810
658740
447910
263230-1
263230-2
668711
Page 77
Service Manual 77
Exploded View
554031
437212
263230-1
435511
552202
567502
552116
554160
561410
550140
552203-1
552203-2
430410
649950
552102
559010
546810
447910
263230-2
Models: AS-W1865DH0, AS-W1825DH0 (UE Chassis)
Page 78
78 Room Air Conditioner
Replacement Parts List
Replacement Parts List
Parts List (Indoor)
LOCATION
DESCRIPTION
PART No.
REMARKS
No.
131410 CHASSIS ASSEMBLY 3141A20019C 3141A20019C 3141A20020B 135311 GRILLE ASSEMBLY,DISCHARGE 3531A10307A 3531A10307A 3531A20252A 135312 GRILLE ASSEMBLY,FRONT 3531A14002D 3531A14002B 3531A20253K 135516 COVER ASSEMBLY,MOTOR 3551A20156A 3551A20156A 3551A20154A 146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A 152302 FILTER(MECH),A/C 5230A20051A 5230A20051A 5230A20052A 159901 VANE,HORIZONTAL 5990A20048A 5990A20048A 5990A20049A 249951 CONTROL BOX ASSEMBLY 4995A20495B 4995A20495A 4995A20495C 263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A 264110 POWER CORD ASSEMBLY 6411A20013E 6411A20013E 6411A20014Z 266090 H.V ASSEMBLY 6609A10003Z 6609A10003Z ­267110 REMOTE CONTROLLER 6711A20077Y 6711A20077Y 6711A20077Y 268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20574A 6871A20574A 6871A20624A 268714 PWB(PCB) ASSEMBLY 6871A20675A 6871A20156A 6871A20156B 342800 BEARING 4280A20004B 4280A20004B 4280A20004A 346810 MOTOR ASSEMBLY,INDOOR 4681A20151B 4681A20091J 4681A20091J 354210 EVAPORATOR ASSEMBLY,FIRST 5421A20218A 5421A20218A 5421A20220A 359011 FAN ASSEMBLY,CROSS FLOW 5901A20017F 5901A20017F 5901AR2441E 733010 PLATE ASSEMBLY,INSTALL 3301A20011A 3301A20011A 3301A20002A 35211B TUBE ASSEMBLY,TUBING 5211A21363A 5211A21363B 5211A21378C W0CZZ CAPACITOR,DRAWING 3H01487K - -
AS-W0964DH0 AS-W1264DH0 AS-W1865DH0
NOTE)*Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Page 79
Service Manual 79
Replacement Parts List
Parts List (Indoor)
LOCATION
DESCRIPTION
PART No.
REMARKS
No.
131410 CHASSIS ASSEMBLY 3141A20019C 3141A20019C 3141A20019C 3141A20019E 3141A20020B 135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10307A 3531A10307A 3531A10307J 3531A10307P 3531A20252H 135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A14003C 3531A14003D 3531A14002R 3531A14002R 3531A20253S 135314 GRILLE ASSEMBLY,INLET 3531A10339B 3531A10339B 3531A10312D 3531A10312D 3531A20254E 135516 COVER ASSEMBLY,MOTOR 3551A20156B 3551A20156B 3551A20156B 3551A20156B 3551A20154A 146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A 4681A20055A 4681A20055A 152302 FILTER(MECH),A/C 5230A20051A 5230A20051A 5230A20051A 5230A20051A ­159901 VANE,HORIZONTAL 5990A20048A 5990A20048A 5990A20048A 5990A20048A 5990A20049A 249951 CONTROL BOX ASSEMBLY,INDOOR 4995A20495B 4995A20495A 4995A20495E 4995A20495F 4995A20495D 263230 THERMISTOR ASSEMBLY 6323A20004A 6323A20004A 6323A20004A 6323A20004A 6323A20004A 264110 POWER CORD ASSEMBLY 6411A20013E 6411A20013E 6410A20007E 6410A20007E 6410A20007F 266090 H.V ASSEMBLY 6609A10003Z 6609A10003Z 6609A10003Z 6609A10003Z 6609A10003Z 267110 REMOTE CONTROLLER ASSEMBLY 6711A20077Y 6711A20077Y 6711A20124A 6711A20124A 6711A20124A 268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A20574A 6871A20574A 6871A20574A 6871A20574A 6871A20624A 268714 PWB(PCB) ASSEMBLY,MAIN 6871A20675A 6871A20156A 6871A20156D 6871A20156C 6871A20156B 342800 BEARING 4280A20004B 4280A20004B 4280A20004B 4280A20004B 4280A20004A 346810 MOTOR ASSEMBLY,INDOOR 4681A20151B 4681A20091J 4681A20091J 4681A20091J 4681A20091J 354210 EVAPORATOR ASSEMBLY,FIRST 5421A20218A 5421A20218A 5421A20218A 5421A20218A 5421A20220A 359011 FAN ASSEMBLY,CROSS FLOW 5901A20017F 5901A20017F 5901A20017F 5901A20017F 5901AR2441E 733010 PLATE ASSEMBLY,INSTALL 3301A20011A 3301A20011A 3301A20011A 3301A20011A 3301A20002A 35211B TUBE ASSEMBLY,TUBING 5211A21363A 5211A21363B 5211A21363B 5211A21363B 5211A21378C W0CZZ CAPACITOR,DRAWING 3H01487K - - - -
AS-W0964GH0 AS-W1264GH0 AS-W1224DH0 AS-W1424DH0 AS-W1825DH0
NOTE)*Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Page 80
80 Room Air Conditioner
Replacement Parts List
Parts List (Outdoor)
263230 THERMISTOR ASSEMBLY 6323A20003G 6323A20003G ­430410 BASE ASSEMBLY,OUTDOOR 3041A20066A 3041A20066A 3041A20022Q 435301 GRILLE,DISCHARGE 3530A20006B 3530A20006B 3530A20007B 435511 COVER ASSEMBLY,CONTROL 3551A30115G 3551A30115G 3551A30102A 437210 PANEL ASSEMBLY,FRONT 3721A20027Q 3721A20027Q 3721A20005H 437212 PANEL ASSEMBLY,REAR - - 3720AP0003D 447910 BARRIER ASSEMBLY,OUTDOOR 4791A30002G 4791A30002G 2H02110G 546810 MOTOR ASSEMBLY,OUTDOOR 4681A20068G 4681A20122A 4681A20028K 550140 ISOLATOR,COMP 4984AR4387A 4H00982E 4H00982E
552102 TUBE,CAPILLARY BEND 5210A21447E 5210A31380D 552102-1 TUBE,CAPILLARY BEND 5210A21447M - ­552102-2 TUBE,CAPILLARY BEND 5210A33068B - -
552111 TUBE ASSEMBLY,CAPILLARY 5211A21393C 5211A21393B -
552116 TUBE ASSEMBLY,REVERSING 5211A10466B 5211A10466C 5211A21140B
552201 VALVE,CHECK 3H01552F 3H01552F -
552202 VALVE,REVERSING 5220AR3228D 5220AR3228D 5220AR3228E
554031 CONDENSER ASSEMBLY 5403A20019V 5403A20019V 5403A21012B
554160 COMPRESSOR 5416A90045A 5416A90029A 5416A90024A
559010 FAN ASSEMBLY,PROPELLER 5901A10033A 5901A10033A 1A00195B
561410 COIL ASSEMBLY,REVERSING 6141A20010S 6141A20010S 6141A20010H
649950 CONTROL BOX ASSEMBLY, OUTDOOR 4995A21006H 4995A21006J 4995A20346F
668711
PWB(PCB) ASSEMBLY, MAIN(OUTDOOR)
6871A10128P 6871A10128Q 6871A20349F 552203-1 VALVE,SERVICE 5220A20005B 5220A20005B 5220A20006A 552203-2 VALVE,SERVICE 5220A20001Q 5220A20006F 2H02479F
W0CZZ CAPACITOR,DRAWING - 0CZZA90002N 3H00611R
LOCATION
DESCRIPTION
PART No.
REMARKS
No.
AS-W0964DH0 AS-W1264DH0 AS-W1865DH0
NOTE)*Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Page 81
Service Manual 81
Replacement Parts List
Parts List (Outdoor)
263230-1 THERMISTOR ASSEMBLY 6323A20001C 6323A20001C 6323A20001C 6323A20001C 6323A20001B 263230-2 THERMISTOR ASSEMBLY 6323A20003G 6323A20003G 6323A20003G 6323A20003G 6323A20003C
430410 BASE ASSEMBLY,OUTDOOR 3041A20066A 3041A20066A 3041A20066A 3041A20066A 3041A20022Q 435301 GRILLE,DISCHARGE 3530A20006G 3530A20006G 3530A20006G 3530A20006G 3530A20007B 435511 COVER ASSEMBLY,CONTROL(OUTDOOR) 3551A30115G 3551A30115G 3551A30115G 3551A30115G 3551A30102A 437210 PANEL ASSEMBLY,FRONT(OUTDOOR) 3721A20027Q 3721A20027Q 3721A20027Q 3721A20027Q 3721A20005H 437212 PANEL ASSEMBLY,REAR(OUTDOOR) 3721A20026M 3721A20026M 3721A20026M 3721A20026M 3720AP0003D 447910 BARRIER ASSEMBLY,OUTDOOR 4791A30002G 4791A30002G 4791A30002G 4791A30002G 2H02110G 546810 MOTOR ASSEMBLY,OUTDOOR 4681A20068G 4681A20122A 4681A20122A 4681A20122A 4681A20028L
550140 ISOLATOR,COMP 4984AR4387A 4H00982E 4H00982E 4H00982E 4H00982E 552102-1 TUBE,CAPILLARY BEND 5210A21447M 5210A21447E 5210A21447E 5210A21447E 5210A31380D 552102-2 TUBE,CAPILLARY BEND 5210A33068B 5210A33068A 5210A33068A 5210A33068A 5210A31380E
552111 TUBE ASSEMBLY,CAPILLARY 5211A21393C 5211A21393B 5211A21393B 5211A21393E -
552116 TUBE ASSEMBLY,REVERSING 5211A10466B 5211A10466C 5211A10466C 5211A10466D 5211A21140B
552201 VALVE,CHECK 3H01552F 3H01552F 3H01552F 3H01552F 5220A30004A
552202 VALVE,REVERSING 5220AR3228D 5220AR3228D 5220AR3228D 5220AR3228D 5220AR3228E
554031 CONDENSER ASSEMBLY,BENT 5403A20019V 5403A20019V 5403A20019V 5403A20019V 5403A21012B
554160 COMPRESSOR 5416A90045A 5416A90029A 5416A90029A 5416A90029A 5416A90024A
559010 FAN ASSEMBLY,PROPELLER 5901A10033A 5901A10033A 5901A10033A 5901A10033A 1A00195B
561410 COIL ASSEMBLY,REVERSING VALVE 6141A20010S 6141A20010S 6141A20010S 6141A20010S 6141A20010H
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A21006H 4995A21006J 4995A21006M 4995A21006N 4995A20346H 552203-1 VALVE,SERVICE 5220A20005B 5220A20005B 5220A20005B 5220A20005B 5220A20006A 552203-2 VALVE,SERVICE 5220A20001Q 5220A20006F 5220A20006F 5220A20006F 2H02479F
668711 PWB(PCB) ASSEMBLY, MAIN 6871A10128P 6871A10128Q 6871A10128U 6871A10128V 3871A20349G
W0CZZ CAPACITOR,DRAWING 0CZZA90002M 0CZZA90002N 0CZZA90002N 0CZZA90002N 0CZZA90002N
LOCATION
DESCRIPTION
PART No.
REMARKS
No.
AS-W0964GH0 AS-W1264GH0 AS-W1224DH0 AS-W1424DH0 AS-W1825DH0
NOTE)*Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Page 82
P/No.: 3828A20462G
May, 2005
Printed in Korea
Loading...