Lg Asnc091f2g0, Asnc121f2g0, Asnh091f2g1, Asnh121f2g1, Asnh121f2g0 Owner's Manual

...
Page 1
Universal Air Conditioner
SVC MANUAL(Exploded View)
MODEL : LAN126HNP(ASNH121F2G1) LAU126HNP(ASUH121FUG1)
LAN096HNP(ASNH091F2G1) LAU096HNP(ASUH091FUG1) LAN091CNP (ASNC091F2G0) LAU091CNP (ASUC091FUG0) LAN121CNP (ASNC121F2G0) LAU121CNP (ASUC121FUG0) LAN091HNP (ASNH091F2G0) LAU091HNP (ASUH091FUG0) LAN121HNP (ASNH121F2G0) LAU121HNP (ASUH121FUG0) LA090CPI (ASNC091F2G0) LA090CPO (ASUC091FUG0) LA120CPI (ASNC091F2G0) LA120CPO (ASUC091FUG0) LA090HPI (ASNH091F2G0) LA090HPO (ASUH091FUG0) LA120HPI (ASNH121F2G0) LA120HPO (ASUH121FUG0)
CAUTION
Internal Use Only
http://biz.lgservice.com
Page 2
- 2 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions ...........................................................................................................................................................3
Dimensions .......................................................................................................................................................................9
Symbols Used in this Manual .....................................................................................................................................9
Indoor Unit ..................................................................................................................................................................9
Outdoor Unit .............................................................................................................................................................10
Product Specifications ..................................................................................................................................................11
Installation ......................................................................................................................................................................13
Installation Parts .......................................................................................................................................................13
Installation Tools.......................................................................................................................................................13
Installtion Map...........................................................................................................................................................14
Confirm the Refrigerant ............................................................................................................................................15
Select the best Locations..........................................................................................................................................16
Piping Length and Elevation .....................................................................................................................................17
Preparing Work for Installation .................................................................................................................................18
Fixing Indoor Unit......................................................................................................................................................19
Flaring work and connection of piping ........................................................................................................................20
Flaring work ..............................................................................................................................................................20
Connection of piping-Indoor......................................................................................................................................21
Connection of the drain hose....................................................................................................................................22
Connection of piping-Outdoor...................................................................................................................................24
Connecting the cable between indoor unit and outdoor unit ....................................................................................25
Connect the cable to the Indoor unit.........................................................................................................................25
Connection method of the connecting cable(Example) ............................................................................................26
Checking the drainage and forming the pipings.........................................................................................................27
Checking the drainage..............................................................................................................................................28
Forming the piping ....................................................................................................................................................29
AIR PURGING .................................................................................................................................................................30
Air purging ................................................................................................................................................................30
Charging ...................................................................................................................................................................32
Panel front assembly ................................................................................................................................................33
Test running..............................................................................................................................................................34
How to replace picture & photograph ..........................................................................................................................36
Operation ........................................................................................................................................................................37
Functions ..................................................................................................................................................................37
The function of main control .....................................................................................................................................38
Display Function ......................................................................................................................................................44
Self-diagnosis Function ............................................................................................................................................44
Remote Control Operations ......................................................................................................................................45
Disassembly ...................................................................................................................................................................46
Indoor Unit ................................................................................................................................................................46
Schematic Diagram ........................................................................................................................................................48
Heat Pump/Cooling Only Series(Indoor Unit) ...........................................................................................................48
Heat Pump Series (Outdoor Unit).............................................................................................................................49
INDOOR UNIT P.W.B. ASSEMBLY .........................................................................................................................50
OUTDOOR UNIT P.W.B. ASSEMBLY .....................................................................................................................51
DISPLAY P.W.B. ASM..............................................................................................................................................52
Wiring Diagram .........................................................................................................................................................53
Troubleshooting Guide..................................................................................................................................................55
Refrigeration Cycle Diagram.....................................................................................................................................55
Pipe length and the elevation ...................................................................................................................................56
3-way Valve ..............................................................................................................................................................57
Cycle Parts ...............................................................................................................................................................63
Electronic Parts.........................................................................................................................................................64
Exploded View ................................................................................................................................................................73
Page 3
- 3 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Installation
Do not use damaged power cords, plugs, or a loose socket.
• There is risk of fire or electric
shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
• There is risk of fire or electric shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Install the panel and the cover of control box securely.
• There is risk of fire or electric shock.
Do not modify or extend the power cord.
• There is risk of fire or electric shock.
Do not install, remove, or re­install the unit by yourself (customer).
• There is risk of fire, electric shock, explosion, or injury.
Page 4
- 4 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Operation
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
• There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
• It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• Moisture may condense and wet or damage furnishings.
Take care to ensure that power cords could not be pulled out or damaged during operation.
• There is risk of fire or electrical shock.
Do not place anything on the power cord.
• There is risk of fire or electric shock.
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
• There is risk of fire or electrical shock.
Page 5
- 5 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
• There is risk of fire or electrical shock.
Do not place a heater or other appliances near the power cable.
• There is risk of fire and electric shock.
Do not allow water to run into electric parts.
• It may cause There is risk of fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustibles near the air conditioner.
• There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
• Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on. DO NOT use the telephone or turn switches on or off.
• There is risk of explosion or fire.
Unplug the unit if strange sounds, odors, or smoke comes from it.
• There is risk of electrical shock or fire
Stop operation and close the window in storm or hurricane. If possible, remove the air conditioner from the window before the hurricane arrives.
• There is risk of property damage, failure of product, or electric shock.
Thinner
Wax
Page 6
- 6 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Installation
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
• There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), contact an Authorized Service Center.
• There is risk of fire or eletric shock.
Ventilate the product from time to time when operating it together with a stove, etc.
• There is risk of fire or electrical shock.
Unplug the appliance before performing cleaning or maintenance.
• There is risk of electrical shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
• There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• This could result in personal injury and product damage.
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
• A bad connection may cause water leakage.
Keep level even when installing the product.
• To avoid vibration or water leakage.
90˚
Page 7
- 7 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Operation
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
• It may cause a problem for your neighbors.
Use two or more people to lift and transport the air conditioner.
• Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
• It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Do not direct airflow at room occupants. (Don't sit in the draft.)
• This could damage your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
• There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
• It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
• There is risk of personal injury and failure of product.
Page 8
- 8 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
• A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the unit.
• It is not sanitary and could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the air conditioner.
• Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
• There is risk of fire or explosion
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
• They may burn or explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
• The chemicals in batteries could cause burns or other health hazards.
Disuse
Safety Precautions
Page 9
- 9 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Dimensions
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
Symbols Used in this Manual
Pipe Hole
Fix Hole
Hanger Hole
H
W
D
W mm(inch) 600(23.6)
H mm(inch) 600(23.6)
D mm(inch) 146(5.7)
Model
Dimension
INDOOR UNIT
NOTICE
Page 10
- 10 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Outdoor Unit
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
9k, 12k Models
DIM unit
W mm 770(30.3)
H mm 540(21.3)
D mm 245(9.6)
L1 mm 285(11.2)
L2 mm 64(2.5)
L3 mm 518(20.4)
L4 mm 10(0.4)
L5 mm 100(3.9)
Page 11
- 11 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Product Specifications
Product Specifications
Models
Cooling Capacity kW (Min~Rating~Max) Btu/h Heating Capacity kW (Min~Rating~Max) Btu/h Power Input Cooling/Heating W Running Current Cooling/Heating A Starting Current Cooling/Heating A
EER
W/W
Btu/h.W COP W/W Power Supply Ø / V / Hz Power Factor %
Air Flow Rate
Indoor,Max
m3/min(cfm)
Outdoor,Max
m3/min(cfm)
Moisture Removal l/h Sound Level
Indoor,H/M/L dB(A)+3 Outdoor,Max dB(A)+3
Refrigerant & Charge(at 7.5m) g(oz)
Compressor
Type Model Motor Type Oil Type Oil Charge cc O.L.P Name
Fan(Indoor)
Type Motor Output W
Fan(outdoor)
Type Motor Type
Motor Output W Circuit Breaker* A Power Supply Cable No.*mm
2
Power and Transmission Cable
No.*mm2+No.mm
2
Piping Liquid Side mm(in) Connections Gas Side mm(in) Drain Hose O.D , I.D mm(in)
Indoor(W*H*D)
mm
Dimension
inch
Outdoor(W*H*D)
mm inch
Indoor kg(lbs) Net Weight
Outdoor kg(lbs) Tool Code(Chassis) Indoor + Outdoor
Temperature Control Functions Plasma Filter
Prefilter(washable/anti-fungus)
Auto Clean
CHAOS Wind(Auto Wind)
Steps, Fan/Cool/Heat
Airflow Direction Control(up&down)
Airflow Direction Control(left&right)
Remocon Type
Setting Temperature Cooling
Range Heating
Auto Operation (Micom Control)
Auto Changeover (Micom Control)
Self Diagnosis
Timer
Sleep Operation
Soft Dry Operation
Restart Delay(minute)
Deice Control(Defrost)
Hot Start
Jet Cool
Low Ambient Operation
Special Function
Network Functions
Dry Contact
Network Solution(LGAP)
PI485
2.87 3.37 2.87 3.37
9,800 11,500 9,800 11,500
- - 2.87 3.37
- - 9,800 11,500
980 1,100 980/980 1,100/1,100
9.4 10 9.4/9.4 10/10
57.0 57.0 57.0/57.0 57.0/57.0
2.93 3.06 2.93 3.06
10.0 10.5 10.0 10.5
- - 2.93 3.06
1/115/60 1/115/60 1/115/60 1/115/60
90.7 95.7 90.7 95.7
9.3(330) 9.3(330) 9.3(330) 9.3(330) 25(883) 25(883) 25(883) 25(883)
1.4 1.4 1.4 1.4
41/35/29 41/35/29 41/35/29 41/35/29
48 48 48 48
R410A, 900(31.8) R410A, 900(31.8) R410A, 900(31.8) R410A, 900(31.8)
Rotary Rotary Rotary Rotary
GK113CAA GK113CAA GK113CAA GK113CAA
PSC PSC PSC PSC
FVC68D(PVE) FVC68D(PVE) FVC68D(PVE) FVC68D(PVE)
330 330 330 330
MRA12053-12027 MRA12053-12027 MRA12053-12027 MRA12053-12027
Turbo Fan Turbo Fan Turbo Fan Turbo Fan
24 24 24 24
Propeller Propeller Propeller Propeller
AC Induction AC Induction AC Induction AC Induction
27 27 27 27 20 20 20 20
3*2.5 3*2.5 3*2.5 3*2.5
4*0.75 4*0.75 4*0.75 4*0.75
6.35(1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4)
12.7(1/2) 12.7(1/2) 12.7(1/2) 12.7(1/2)
21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 600*600*146 600*600*146 600*600*146 600*600*146
23.62*23.62*5.75 23.62*23.62*5.75 23.62*23.62*5.75 23.62*23.62*5.75 770*540*245 770*540*245 770*540*245 770*540*245
30.31*21.26*9.65 30.31*21.26*9.65 30.31*21.26*9.65 30.31*21.26*9.65
15(33.1) 15(33.1) 15(33.1) 15(33.1) 32(70.5) 32(70.5) 32(70.5) 32(70.5) SF + UL SF + UL SF + UL SF + UL
Thermistor Thermistor Thermistor Thermistor
OOOO OOOO OOOO OOOO
3/4 3/4 3/4/3 3/4/3 Auto Auto Auto Auto Auto Auto Auto Auto
Wireless LCD Wireless LCD Wireless LCD Wireless LCD
18 ~ 30 18 ~ 30 18 ~ 30 18 ~ 30
- - 16 ~ 30 16 ~ 30 OOOO OOOO OOOO
24h, On/Off 24h, On/Off 24h, On/Off 24h, On/Off
OOOO OOOO
3333
--
OO
--
OO
OOOO
----
----
----
----
----
Note: O : Applied, - : No relation * For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.
The specification may be subject to change without notic for purpose of improvement.
AS-C091F2G0(LA091CNP)
AS-C091F2G0(LA090CP)
AS-C121F2G0(LA121CNP)
AS-C121F2G0(LA120CP)
AS-H091F2G0(LA091HNP)
AS-H091F2G0(LA090HP)
AS-H121F2G0(LA121HNP)
AS-H121F2G0(LA120HP)
Page 12
Product Specifications
- 12 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Models
Cooling Capacity kW (Min~Rating~Max) Btu/h Heating Capacity kW (Min~Rating~Max) Btu/h Power Input Cooling/Heating W Running Current Cooling/Heating A Starting Current Cooling/Heating A
EER
W/W
Btu/h.W COP W/W Power Supply Ø / V / Hz Power Factor %
Air Flow Rate
Indoor,Max
m3/min(cfm)
Outdoor,Max
m3/min(cfm)
Moisture Removal l/h Sound Level
Indoor,H/M/L dB(A)+3 Outdoor,Max dB(A)+3
Refrigerant & Charge(at 7.5m) g(oz)
Compressor
Type Model Motor Type Oil Type Oil Charge cc O.L.P Name
Fan(Indoor)
Type Motor Output W
Fan(outdoor)
Type Motor Type
Motor Output W Circuit Breaker* A Power Supply Cable No.*mm
2
Power and Transmission Cable
No.*mm2+No.mm
2
Piping Liquid Side mm(in) Connections Gas Side mm(in) Drain Hose O.D , I.D mm(in)
Indoor(W*H*D)
mm
Dimension
inch
Outdoor(W*H*D)
mm inch
Indoor kg(lbs) Net Weight
Outdoor kg(lbs) Tool Code(Chassis) Indoor + Outdoor
Temperature Control Functions Plasma Filter
Prefilter(washable/anti-fungus)
Auto Clean
CHAOS Wind(Auto Wind)
Steps, Fan/Cool/Heat
Airflow Direction Control(up&down)
Airflow Direction Control(left&right)
Remocon Type
Setting Temperature Cooling
Range Heating
Auto Operation (Micom Control)
Auto Changeover (Micom Control)
Self Diagnosis
Timer
Sleep Operation
Soft Dry Operation
Restart Delay(minute)
Deice Control(Defrost)
Hot Start
Jet Cool
Low Ambient Operation
Special Function
Network Functions
Dry Contact
Network Solution(LGAP)
PI485
2.9 3.37
9,900 11,500
2.9 3.22
9,900 11,000
1,100/1,070 1,150/1,100
9.4/9.4 10-10
57.0/57.0 57.0/57.0
2.63 2.93 910
2.71 2.93
1/115/60 1/115/60
90.7 95.7
9.3(330) 9.3(330) 25(883) 25(883)
1.4 1.4
43/35/29 43/35/29
48 48
R410A, 900(31.8) R410A, 900(31.8)
Rotary Rotary
GK113CAA GK113CAA
PSC PSC
FVC68D(PVE) FVC68D(PVE)
330 330
MRA12053-12027 MRA12053-12027
Turbo Fan Turbo Fan
24 24
Propeller Propeller
AC Induction AC Induction
27 27 20 20
3*2.5 3*2.5
4*0.75 4*0.75
6.35(1/4) 6.35(1/4)
12.7(1/2) 12.7(1/2)
21.5,16(0.85,0.63) 21.5,16(0.85,0.63) 600*600*146 600*600*146
23.62*23.62*5.75 23.62*23.62*5.75 770*540*245 770*540*245
30.31*21.26*9.65 30.31*21.26*9.65
15(33.1) 15(33.1) 32(70.5) 32(70.5) SF + UL SF + UL
Thermistor Thermistor
OO OO OO OO
2003-04-03 2003-04-03
Auto Auto Auto Auto
Wireless LCD Wireless LCD
18 ~ 30 18 ~ 30 16 ~ 30 16 ~ 30
OO OO OO
24h, On/Off 24h, On/Off
OO OO
33 OO OO OO
--
--
--
--
--
Note: O : Applied, - : No relation * For circuit breaker rating, please conform to local standards wherever necessary.
Some of functions are slightly different depending upon models.
The specification may be subject to change without notic for purpose of improvement.
AS-H091F2G1
(LA096HNP)
AS-H121F2G1
(LA126HNP)
Page 13
- 13 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
Installation
Installation Parts
Installation Tools
Read carefully, and then follow step by step.
Type "A" screw and plastic anchor
Type "B" screw
Remote control holder
Installation guide map
Figure FigureName
Screw driver
Electric drill
Measuring tape, Knife
Hole core drill
Spanner
Torque wrench
Ohmmeter
Hexagonal wrench
Ammeter
Leak detector
Thermometer,
Horizontal meter
Flaring tool set
Name
Page 14
- 14 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation Map
Installation parts you should purchase.
NOTICE
(Left and right
are identical)
More than 28"(70cm)
More than
23.6"(60cm)
Sleeve Bushing-Sleeve
Putty(Gum Type Sealer)
Vinyl tape (Wide)
• To carry out the drainage test, remove the air filter and pour water into the heat exchanger.
• Apply after carrying out a drainage test.
Saddle
More than
19.6"(50cm)
Gas side piping (Optional part) Liquid side piping (Optional part) Additional drain pipe
Vinyl tape (Narrow)
Connecting cable (Optional part)
Bend the pipe as close as possible on the wall but be careful so that it may not break.
More than More than
11.8"(30cm )11.8"(30cm )
More than
11.8"(30cm )
More than More than
11.8"(30cm) 11.8"(30cm)
More than
11.8"(30cm)
More than More than
3.9"(10cm) 3.9"(10cm)
More than
7.9"(20cm)
Installation
Page 15
- 15 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
1. Check the quality label on the indoor and outdoor unit.
2. Make certain that the refrigerant is R-410A.
THIS PRODUCT CONTAINS R-410A REFRIGERANT
1) Different compressor oil
- R-410A(Polyol ester) / R-22(Mineral).
- Do not mix the existing mineral oil.
- Do not apply used pipe, tools and gauges covered with the existing mineral oil.
2) Absorption of moisture
-Compressorʼs oil has the high absorption rate of moisture.
3) Composition
- R-410A(R32:R125=50:50wt%). NOTE: Never mix with other refrigerants
4) High pressure.
- 1.6 times higher than R-22.
- High Pressure refrigerant may cause personal injury.
Do not handle the pipe by yourself (customer) High-pressure refrigerant may cause personal injury.
- manifold gauge ,charging and any piping tools must be dedicated to R-410A systems.
Confirm The Refrigerant
Boiling Pt.(
°C) Vapor pressure(25°C)(kg f/cnf) Vapor density(25°C)(kg/m2)
R-410A -51.4 15.9 64 R-22 -40.8 9.6 44.4
Installation
NOTICE
Example : Split type 12,000 Btu/h
Capacity
[%]
120
100
80
100
93
89
84
76
60
40
20
0 R-410A R-22
100%
70% 50% 30%
0%
100%70%50%30%0%
Page 16
- 16 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Indoor unit
1. Do not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.
5. Ensure that the interval between a wall and the left (or right) of the unit is more than 19.6"(50cm). The unit should be installed as high as possible on the wall, allowing a minimum of 7.9"(20cm) from ceiling.
6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure that the space around the back and sides is more than 11.8"(30cm). The front of the unit should have more than 28"(70cm) of space.
3. Do not place animals and plants in the path of the warm air.
4. Take the weight of the air conditioner into account and select a place where noise and vibration are minimum.
5. Select a place where the warm air and noise from the air conditioner do not disturb neighbors.
Select the best Location
CAUTION: Install the indoor unit on the wall where the height from the floor is more than 4.9 feets(1.5 meters).
Rooftop Installations
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
If the outdoor unit is installed on roof structures or walls, this may result in excessive noise and vibration, and may be also classed as non serviceable installation.
Installation
More than
19.6"(50cm)
More than
4.9ft(1.5m)
More than
7.9"(20cm)
More than
19.6"(50cm)
More than
11.8"(30cm)
More than
23.6"(60cm) More than
11.8"(30cm)
More than
28"(70cm)
More than
23.6"(60cm)
Page 17
- 17 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Piping Length and Elevation
Installation
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max.
length
m(ft)
Additional
Refrigerant
g/m(oz/ft)
Max.
ElevationⒷ m(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25) 7.5(25) 15(49) 20(0.22)
CAUTION: Capacity is based on standard length and maximum allowance length is
on the basis of reliability.
Oil trap should be installed every 16.4~23feets (5~7 meters).
Standard
Length m(ft)
Indoor unit
A
B
Outdoor unit
Outdoor unit
Indoor unit
A
B
Oil trap
Indoor unit
If piping length is more than 16.4ft(5m)
Outdoor unit
A
B
Page 18
- 18 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
Preparing Work for Installation
Open panel front
1. Pull the upper part of the front panel.
2. Lift up the panel.
3. To detach the front panel, remove the two screws at the lower part.
4. Detach the front panel from the body.
5. To detach the panel, disconnect the connector at the upper part.
Cover pipe and cover side remove
1. Please remove the screw of the center tuning cover.
2. Pull up the side cover of desired connecting direction, then cover side is separated.
3. Pick the pipe hole of the side cover.
CAUTION: After removing the pipe hole, cut the burr for safety.
When making pipe path through rear wall, you donʼt need to pick the pipe hole.
Drain hose junction
1. Remove the rubber stopple in the desired drain direction.
2. Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
Panel Front
Connector
Side cover
Pipe hole
Only the
desired direction
rubber cap
Only the
desired direction
Connecting
part
Adhesive
Drain hose
NOTICE
Page 19
- 19 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
Fixing Indoor Unit
• Drill the piping hole with a ø50mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Drill a Hole in the Wall
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
Plastic anchors
INSTALLATION GUIDE MAP
10mm
INSTALLATION GU
I
N
S
T
A
I
I
A
T
I
ON GUI
DE
M
A
P
Plastic anchors
INSTALLATION
GU
ID
E M
A
P
I
N
STA
LLATI
O
N
G
U
I
D
E MA
P
Hanger hole
(Rear side of
the product)
3. Make a hole with a diameter of 6mm and depth of 30-35mm by piercing a screw point.
5. Drive the fore plastic anchors into drilled points.
7. Hang the hole of product at the upper screws, and remove the map. (Falling attention)
9. Check the fixed product with light power.
1. Attach an Installation guide map on the desired surface.
2. Look at suited horizon by horizontal meter on the horizontal setting line, and fix lightly the map by adhesive tape.
4.
Drill the pierted part as a diameter of 50mm
for connecting piping. (In case of piercing rear surface)
6.
First, Drive the two points of the upper
parts by screws. (Leave 10mm for hanging the product)
8. Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws.
10.
In case of nothing wrong, connect the pipe and the wire. (Refer to installation manual)
I
Horizontality
NSTAL
LA
TION G
UI
DE
M
AP
Page 20
- 20 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Flaring work and connection of piping
Flaring Work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cutting the pipes and the cable.
1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 4.9ft(1.5m) longer than the pipe length.
Removing burrs
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
• Remove flare nuts attached to indoor and outdoor unit,
then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
1. Firmly hold copper pipe in a die in the dimension shown in the table below.
2. Carry out flaring work with the flaring tool.
Copper
pipe
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm Ø6.35 1/4 1.1~1.3 Ø9.52 3/8 1.5~1.7 Ø12.7 1/2 1.6~1.8
Ø15.88 5/8 1.6~1.8 Ø19.05 3/4 1.9~2.1
Outside diameter A
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Page 21
- 21 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Check
1. Compare the flared work with the figure by.
2. If a flared section is defective, cut it off and do flaring work again.
Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
CAUTION: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
1. Route the indoor tubing and the drain hose in the direction of rear left or right
2. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connecting the Piping
Drain hose
Connecting cable
Gas side piping
Liquid side piping
Drain hose
Loop
Page 22
- 22 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the piping with the indoor unit and drain hose with drain pipe
1. Align the center of the pipings and sufficiently tighten
the flare nut by hand.
2. Tighten the flare nut with a wrench.
3. When extending the drain hose at the indoor unit,
install the drain pipe.
Wrap the insulation material around the connecting portion.
1. Overlap the connection pipe insulation material and
the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
2. Wrap the area which accommodates the rear piping
housing section with vinyl tape.
3. Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Flaring work and connection of piping
mm inch kgf.cm Ø6.35 1/4 180~250 Ø9.52 3/8 340~420 Ø12.7 1/2 550~660
Outside diameter Torque
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Indoor unit tubing Flare nut Pipings
Torque wrench
Indoor unit tubing
Spanner (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Page 23
- 23 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
CAUTION: Installation Information
For right piping. Follow the instruction below.
Good case
• Press on the upper side of clamp and unfold the tubing to downward slowly.
Bad case
• Following bending type from left to right may cause damage to the turbing.
Page 24
- 24 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Put a couple drops of refrigerant oil on the face of the flare before assembling taking care not to add any contaminants.
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
mm inch kgf.cm Ø6.35 1/4 180~250 Ø9.52 3/8 340~420 Ø12.7 1/2 550~660
Ø15.88 5/8 630~820 Ø19.05 3/4 980~1210
Outside diameter Torque
Outdoor unit
Liquid side piping (Smaller diameter)
Gas side piping (Bigger diameter)
Torque wrench
Connection of Piping -Outdoor
Page 25
- 25 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the cable between indoor unit and outdoor unit
Connecting the cable between indoor unit and outdoor unit
Connecting the Cables
1. Remove the cover control from the unit by loosening the screw.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on the conduit panel.
4. Properly connect both the power supply and low voltage lines to the corresponding terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
Connector trade size for this unit is 1/2"(12.7mm). Refer to "How to connect wiring to the terminals" for instructions on connecting depending on the wire type you are using.
WARNING:
• Be sure to comply with local codes while
running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).
• Every wire must be connected firmly.
• No wire should be allowed to touch
refrigerant tubing, the compressor or any moving parts.
Power Supply
1
Indoor Unit Outdoor Unit
2
3
4
1
2
3
4
5
6
G
To branch circuit
Ground
Power supply
a
L1
*
L2
Connecting cable(Low voltage)
b
Terminal
(4P)
Terminal
(6P)
Wiring Diagram
*
L1 is neutral for 115V models.
Outdoor unit
Terminal block
Over 5mm
(0.2")
Cover control
Conduit panel
Connecting
cable
Power supply
cord
1. shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of withstanding temperatures up to 167°F(75°C).
4. Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)
Model
9k/12k
1Ø, 115V
14 18 20A
Power source
Fuse or breaker
Capacity
AWG(MIN)
ⓐⓑ
NOTICE
NOTICE
Page 26
- 26 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the cable between indoor unit and outdoor unit
Connection method of the connecting cable(Example)
1. Dismount two-caps on the conduit panel.
2. Make a hole appropriate for the passage of connection cable through on cap by tool. (for low voltage line)
3. Pass the connecting cable through the hole.
4. Properly connect the cable on the terminal block.
5. Fix the connection cable with clamp cord provided on the unit not to have strain at the terminal when the connection cable is pulled outside up to a 35 pound weight.
6. Wind the vinyl tape round the connecting cable for sealing between the surface of the connection cable and cap.
7. Mount the taped part of cable on the cap.
8. Finally, mount the holed cap with the wound cable on the conduit panel.
WARNING:
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
• For solid core wiring (or F-cable)
1. Cut the wire end with a wire cutter of wire-cutting pliers, then strip the insulation to expose the solid wire about 25mm(15/16")
2. Using a screwdriver, remove the terminal screw(s) on the terminal plate.
3. Using pliers, bend the solid wire to from a loop suitable for the terminal screw.
4. Shape the loop wire properly, place it on the terminal plater and tighten securely with the terminal screw using a screwdriver.
• For strand wiring
1. Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to expose the strand wiring about 10mm(3/8").
2. Using a screwdriver, remove the terminal screw(s) on the terminal plate.
3. Using a round terminal fastener or pliers, securely clamp each stripped wire end with a round terminal.
4. Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.
G
Terminal block
Cap (Remove)
Clamp cord
Lock nut
Conduit panel
Cap(Reuse)
Taping
(for sealing)
Low voltage line
(connecting cable)
Power supply line (1ø, 115V, 208/230V)
Hole
(for low
voltage line)
Loop
Round terminal
Insulation
Strip 25mm(15/16")
Strip 10mm(3/8")
Solid wire
Strand wire
Screw with special washer
Screw with special washer
Round terminal
Terminal plate
Wire
Wire
Round terminal
Page 27
- 27 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the cable between indoor unit and outdoor unit
After the confirmation of the above conditions, prepare the wiring as follows:
1)
Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) Confirm that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7) Always install an GFCI circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, open fuse, disturbance of the normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm(0.12in) in each active(phase) conductors.
CAUTION
Page 28
- 28 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the Drainage
To check the drainage.
1. Pour a glass of water on the evaporator.
2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
Drain piping
1. The drain hose should point downward for easy drain flow.
2. Do not make drain piping like the following.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
(mm2)
Page 29
- 29 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Checking the drainage and forming the pipings
Forming the Piping
Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes.
• If you want to connect an additional drain hose, the
end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
1. Tape the piping, drain hose and connecting cable
from down to up.
2. Secure the tapped piping along the exterior wall
using saddle or equivalent.
In cases where the outdoor unit is installed above the Indoor unit perform the following.
1. Tape the piping and connecting cable from down to
up.
2. Secure the taped piping along the exterior wall. Form
a trap to prevent water entering the room.
3. Fix the piping onto the wall by saddle or equivalent.
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Page 30
- 30 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
AIR PURGING
Air Purging
Air purging
The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system. Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
Air purging with vacuum pump
1. Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected
and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
2. Leak test
• Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION:
Be sure to use a manifold valve for air purging. If it is not available, use a stop
valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.
• Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the
gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
CAUTION:
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
1. Do a leak test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Pressure gauge
Page 31
- 31 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
Soap water method
1. Remove the caps from the 2-way and 3-way valves.
2. Remove the service-port cap from the 3-way valve.
3. To open the 2-way valve turn the valve stem counterclockwise approximately 90°, wait for about 2~3 sec, and close it.
4. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping.
5. If bubbles come out, the pipes have leakage
Evacuation
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
2. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run.
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h vacuum
pump is used
10 min. or more 15 min. or more
If tubing length is less
than 10m (33 ft)
If tubing length is longer
than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Page 32
- 32 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
Charging
Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set.
Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the refrigerant charge has to be adjusted.
Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are
either added or removed based on 20g(0.22oz) of R-410A per meter(foot).
Example: A 30ft line set is used
5 additional ft X 0.22 ounce per foot= add 1.1 ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).
Confirm the refrigerant R-410A. Use manifold gauge and hose for R-410A.
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max.
length Ⓐm(ft)
Additional
Refrigerant
g/m(oz/ft)
Max.
Elevation Ⓑm(ft)
Standard
Length m(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25) 7.5(25) 15(49) 20(0.22)
Page 33
- 33 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air purgingd
1. First, Check the side cover assembly
exactly, and fix the power cord in the bottom groove of cover side left.
2. Assemble connecting lead wire with
controller, fix the upper part of panel front, and match the lower part of panel front.
3. Screw up panel front, and suspend the
hook of panel front in the groove.
Panel Front
Connector
Panel Front Assembly
Page 34
- 34 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Test running
TEST RUNNING
R-410A 95°F(35°C) 8.5~9.5kg/cm2G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the
gas side service valve.
1. Check that all tubing and wiring are properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote controller
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
3. Reattach the cover by pushing it back into position.
• Use 2 AAA(1.5volt) batteries. Do not use rechargeable
batteries.
• Remove the batteries from the remote controller if the
system is not used for a long time.
Settlement of outdoor unit
1. Anchor the outdoor unit with a bolt and nut(ø0.39"(ø10mm)) tightly and horizontally on a concrete or rigid mount.
2. When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
3. If the vibration of the unit is transmitted to the hose, secure the unit with an anti-vibration rubber.
Evaluation of the performance
Operate the unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake temperature and the discharge is more than
46.4°F(8°C)
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
The air conditioner is now ready for use.
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
Test Running
NOTICE
Page 35
- 35 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Test running
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
PUMP DOWN
This is performed when the unit is relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant.
CAUTION: Be sure to perform Pump Down procedure in the cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant.
3. Close the liquid side service valve(all the way).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm
2
G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve and then quickly turn off the unit. Now Pump Down procedure is completed, and all refrigerant is collected into the outdoor unit.
NOTICE
Page 36
- 36 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
How to replace picture & photograph
How to replace picture & photograph
1.
Turn off power and then open the upper part of front panel.
2.
Pull out the both links of lower part of front panel, as described in the below picture.
3.
Push and close the top part of the front panel and then pull the bottom part of the panel forward until it is secured.
4.
Take out picture.
5.
Turn upside-down of the picture and turn over mat, then take off a protective tape attached at the mat.
6.
Place the picture/photograph between the exited picture and mat. (Recommended size of a photo/picture: 450mm x 450mm)
7.
Cover mat and press down with hand(s) until contacting closely.
8.
Slide the photo graph/drawing requested under both hanger parts as following, and fix them. Press the front panel lightly to close.
9.
Push both links of lower part of panel inside and fix it. Then turn on.
In case a mat is not used, recommended size of a photo/picture: 522mm x 522mm
When powering on after replacing filter and picture, the front panel doesn't intervene.
Mat
450mm
450mm
522mm
522mm
Mat
Protective tape
Page 37
- 37 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Operation
Indoor Unit
Operation ON/OFF by Remote controller
Sensing the Room Temperature
Room temperature control
Starting Current Control
Time Delay Safety Control
Indoor Fan Speed Control
Operation indication Lamps (LED)
Healthy Dehumidification Mode
Sleep Mode Auto Control
Auto Air Control by the unit electronic control
Chaos Swing
Defrost control(Heating)
Hot-start Control (Heating)
• Room temperature sensor (THERMISTOR)
• Maintains the room temperature in accordance with the Setting Temp.
• Indoor fan is delayed for 5 seconds at the starting.
• Restarting is inhibited for approx. 3 minutes.
• High, Med, Low and Auto
• Intermittent operation of fan at low speed
• Both the indoor and outdoor fan stops during defrosting.
• Hot start will be operated after defrosting ends.
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F(28°C).
• The fan is switched to low(Cooling), med(Heating) speed.
• The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
• The fan is switched to intermittent or irregular operation.
• The fan speed is automatically switched from high to low speed.
• The louver can be set at the desired position or swing up and down automatically.
--- Lights up in operation
Functions
Page 38
- 38 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
The function of main control
INTAKE AIR TEMP.
SETTING TEMP. +1
°
F
(Compressor ON)
SETTING TEMP. -1
°
F
(Compressor OFF)
Setting fan speed
Setting fan speed
More than 3 minutes
More than 3 minutes
Setting fan speed
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN SPEED Low Low
Protection of the indoor heat exchanger from frosting
• Compressor and outdoor fan stop when indoor pipe temperature is below 32°F(0°C) and restart at the pipe temperature is above 45°F(7°C).
3. Cooling Operation Mode
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote control and the operation diagram is shown below.
CLOSED
OPEN
< Cooling Mode >
8°
CLOSED
OPEN
< Heating Mode >
8°
1. Time delay Safety Control
• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle. (Protection of compressor)
• 5sec.;
The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical louver and wind.
• 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when the heating operation is OFF or switched to the other operation mode while compressor is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Chaos Swing Mode
• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the
desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
Operation
Page 39
- 39 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
. Auto Operation (Electronic control mode)
• The operation procedure is shown below. (Cooling & Heating Model)
If initial mode is decided, that mode is continued without the room temperature changing.
Auto Operation for Cooling
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode Indoor fan speed are decided automatically by the unit electronic control. Setting temperature
Intake-air
temperature
Operation Mode
Over below 70
°
F76
°
F
Soft Dry
below 70
°
F
Heating
Over 76
°
F
Cooling
~
INTAKE AIR TEMP.
SETTING TEMP. +1°F (Compressor OFF)
SETTING TEMP. -1°F (Compressor ON)
COMPRESSOR ON OFF ON OFF
INDOOR FAN SPEED The electronic control operation
Intake-air Temperature Setting Temperature
Over 78°F 77°F
Over 76°F~below 78°F Intake air -1°C
Over 72°F~below 76°F Intake air -0.5°C
Over 68°F~below 72°F Intake air temperature
below 64°F 64°F
Over 64°F~below 86°F Electronic control
below 64°F 64°F
over 86°F 86°F
Operation Condition
When Auto Operation initial start
Controlled by the electronic control
In this mode, when pressing the vertical air direction control button, vertical louver swings up and down automatically.
Fan Speed Air Direction Control
When pressing room temperature setting button during Auto Operation
Operation
Page 40
- 40 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Auto Operation for Dehumidification(only Heating Model)
• The Setting temperature will be same that of the auto operation for cooling.
- Compressor ON temperature; Setting temperature +2°F
- Compressor OFF temperature; Setting temperture -1°F
Auto Operation for Heating(only Heating Model)
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +6°F
Intake-air temp. below 68°F Over 68°F~below 70°F over 86°F
Setting temp. 68°F Intake air temperature +1°F 86°F
Vertical louver auto operation
: During Auto Operation, pressing the chaos swing button makes the
horizontal louvers swing up and down automatically. If you want to stop auto-swing, press chaos swing button again.
5. Healthy Dehumidification
• When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
79°F ≤ Intake Air Temp ➲ 77°F 75°F ≤ Intake Intake Air Temp<79°F ➲ Intake Air Temp-2°F 64°F ≤ Intake Intake Air Temp<75°F ➲ Intake Air Temp-1°F Intake Air Temp<64°F ➲ 64°F
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+1°F Compressor OFF Temp. Setting Temp-1°F
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Page 41
- 41 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
6. Heating Operation Mode(only Heating Model)
The unit will operate according to the setting conditions by the remote controller. The operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. +6
°
F
(Compressor OFF)
SETTING TEMP. (Compressor ON)
Selecting fan speed
Selecting fan speed
A
B
A
minimum
10sec.
minimum
1 min.
minimum
10sec.
COMPRESSOR ON OFF ON OFF
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the indoor pipe temperature becomes lower than 95°F, indoor fan stops.
• B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.
INDOOR FAN SPEED
Low
OFF
Low Low OFF
OFF OFFLOW
ON
Selecting fan speed
INDOOR PIPE
TEMP.
82°F
78°F
1min
INDOOR FAN SPEED
COMPRESSOR
Hot-Start Control
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.
• The operation diagram is shown below.
Page 42
- 42 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
7. Cooling or Heating Mode with Sleep Mode Auto Control
• When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Control( ), the operation diagram is as following.
Cooling Mode with the Sleep Mode
• The setting temperature will be automatically raised by 2°F 30 minutes later and by 4°F 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Heating Mode with the Sleep Mode(only Heating Model)
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
INTAKE AIR TEMP.
SETTING TEMP. +1
°
F
(Compressor ON)
SETTING TEMP. -1
°
F
(Compressor OFF)
30 minutes
30 minutes
More than
3 minutes
2°F
2°F
More than
3 minutes
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN SPEED Low Low Low Low Low
SETTING TEMP. +6
°
F
(Compressor OFF)
SETTING TEMP. (Compressor ON)
COMPRESSOR ON OFF ON OFF ON OFF
INDOOR FAN SPEED Med Low or OFF Med Low or OFF Med Low or OFF
INTAKE AIR TEMP.
More than
3 minutes
More than
3 minutes
More than 3 minutes
Operation
Page 43
- 43 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
8. Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
Operation
9. Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions. So there is no need of activating this function by pressing any key or button. In the initial mode, the fan operates at a low speed and the compressor starts 2.5~3 minutes later. As the compressor starts, the fan speed also resumes its previous setting mode.
Helpful information
Fan speed and cooling capacity.
The cooling capacity indicated in the specification is the value when the fan speed is set to high, and the capacity will be lower at low or medium fan speed.
High fan speed is recommended when you wish to cool the room quickly.
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room temperature and resets in 18 minutes. During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, Press and hold the ON/OFF button for 3~5 seconds, then the buzzer sound 1 "beep". If you want to stop the operation, re-press the button.
Auto restart function has set enable as factory default. But customer can set up by following this instruction.
To be disable function
- Press and hold the ON/OFF button for 6 seconds, then the buzzer sound 2 "beep" and the indicator lamp (1) blinks 4 times.
To be enable function
- Press and hold the ON/OFF button for 6 seconds, then the buzzer sound 2 "beep" and the indicator lamp (1) brights 4 times.
High
Speed
ON/OFF
button
Cooling Heat pump Model
Model
Room Temp. ≥ 76°F(24°C)
70°F(21°C) ≤ Room Temp. < 76°F(24°C)
Room Temp. < 70°F(21°C)
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed
High High
Healthy Dehumidification Rule
High
Setting Temperature
72°F(22°C) 72°F(22°C) 74°F(23°C) 76°F(24°C)
NOTICE
Page 44
- 44 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Display Function
Self-diagnosis Function
Signal Receptor
Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.)
Operation Indication Lamps
On/Off : Lights up during the system operation.
3sec 3sec 3sec
(once)
3sec 3sec
(twice)
3sec
(5times)
Error
Code
1
2
5
Error LED
(Indoor body operation LED)
Error contents
• Indoor room temperature thermistor open/short
• Indoor pipe temperature thermistor open/short.
• Outdoor pipe temperature thermistor open/short.
• Poor communication.
• Indoor TH assy check
• Outdoor TH assy check
• Communication line/circuit check
SVC check point
Page 45
- 45 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Operation
Controls
ON
OFF
CANCEL
SET
°C/°F
AUTO CLEAN
1
3
5
4
9
10
12
18
16
7
2
8
13
15
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door (opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
17
Operation Mode
14
The controls will look like the following.
Remote Control Operations
1. START/STOP BUTTON
Operation starts when this button is pressed and stops when the button is pressed again.
2. OPERATION MODE SELECTION BUTTON
Used to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONS
Used to select the room temperature.
4. INDOOR FAN SPEED SELECTOR
Used to select fan speed in four steps low, medium, high and CHAOS.
5.
JET COOL/HEATING(OPTIONAL)
Used to start or stop the speed cooling/heaing. (speed cooling/heating operates super high fan speed in cooling/heatig mode.)
6. CHAOS SWING BUTTON
Used to stop or start louver movement and set the desired up/down airflow direction.
7. ON/OFF TIMER BUTTONS
Used to set the time of starting and stopping operation.
8. TIME SETTING BUTTONS
Used to adjust the time.
9. TIMER SET/CANCEL BUTTON
Used to set the timer when the desired time is obtained and to cancel the Timer operation.
10. SLEEP MODE AUTO BUTTON
Used to set Sleep Mode Auto operation.
11. AIR CIRCULATION BUTTON
Used to circulate the room air without cooling or heating.
12. ROOM TEMPERATURE CHECKING BUTTON
Used to check the room temperature.
13. NEO PLASMA(OPTIONAL)
Used to start or stop the plasma-purification function.
14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL)
Used to set the desired vertical airflow direction.
15. RESET BUTTON
Used prior to resetting time.
16. 2nd F Button
Used prior to using modes printed in blue at the bottom of buttons.
17. AUTO CLEAN (OPTIONAL)
Used to set Auto Clean mode.
18. °C/°F SWITCH BUTTON
Used to switch temperature reading from Centigrade to Fahrenheit.
Page 46
- 46 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
Disassembly
Indoor Unit
WARNING:
Disconnect the unit from power supply before making any checks. Be sure the power switch is set to "OFF"
1. To remove the Grille from the Chassis.
- Pull the grille bottom, the remove 2 securing screws.
- Lift the both lower parts of panel front.
- After pull down this panel a bit, separate connecting wire with product.
2. To remove the Control Box.
- Before removing the control box, be sure to disconnect the wires from PWB.
- Pull the cover control out from the control box and disconnect other wires.
- Remove securing screws.
- Pull the control box out from the chassis carefully.
Panel Front
Connector
Communication Connector
Motor Connector
Sensor Connector
Step Motro Connector
Front Panel Connector
Page 47
- 47 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Disassembly
3. To remove the Evaporator.
- Remove hole tubing holde.
- Remove 2 screws securing the evaporator.
- Pull the evaporator out from the chassis carefully.
4. Before removing the Turbo Fan.
- Remove the securing screws from the chassis.
- Pull the pipe, top cover and the air guide.
5. To remove the Motor.
- Remove the securing bolt from the motor shaft.
- Pull the fan out from the motor shaft.
- Remove 4 screws securing motor mount from the chassis and lift up the motor mount and the bracket.
Top Cover
Air Guide
Motor Mount
Bolt
Turbo Fan
Bracket
Page 48
- 48 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Schematic Diagram
Heat Pump/Cooling Only Series(Indoor Unit)
Page 49
- 49 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Heat Pump Series/ Cooling Only Series (Outdoor Unit)
Page 50
- 50 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
INDOOR UNIT P.W.B. ASSEMBLY
• P/No.: 6871A20999A (PCB ASSEMBLY, MAIN)
Top View
Bottom View
Page 51
- 51 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
• P/No.: 6871A20901C (PCB ASSEMBLY, MAIN)
OUTDOOR UNIT P.W.B. ASSEMBLY
Top View
Bottom View
Page 52
- 52 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
DISPLAY P.W.B. ASM
• P/No.: 6871A20921A (PCB ASSEMBLY)
Page 53
- 53 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
Wiring Diagram
(1) Indoor Unit (Cooling Only Models, & Heating Models)
Page 54
- 54 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Schematic Diagram
(2) Outdoor Unit(Cooling Only Models, & Heating Models)
Page 55
- 55 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Troubleshooting Guide
Refrigeration Cycle Diagram
INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
COMPRESSOR
GAS SIDE
GAS SIDE
LIQUID SIDE
LIQUID SIDE
CAPILLARY TUBE
CAPILLARY TUBE
CHECK VALVE
COOLING HEATING
REVERSING VALVE
(1) Cooling Only Models
(2) Cooling & Heating Models
Page 56
- 56 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Piping Length and Elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
If piping length is more than 16.4ft(5m)
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 16.4~23feets (5~7 meters).
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max.
length
m(ft)
Additional
Refrigerant
g/m(oz/ft)
Max.
Elevation Ⓑm(ft)
9k, 12k
Ø12.7mm(1/2") Ø6.35mm(1/4")
7.5(25) 7.5(25) 15(49) 20(0.22)
Standard
Length m(ft)
Page 57
- 57 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Pumping Down
3-way Valve
• Procedure
(1) Confirm that both liquid side and gas side
valves are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the Gas side valve.
– Connect the charge hose to the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the liquid side valve to the closed position.
(6) Operate the air conditioner in cooling mode
and stop it when the gauge indicates 1kg/cm
2
g.
(7) Immediately set the Gas side valve to the
closed position.
– Do this quickly so that the gauge ends up
indicating 3 to 5kg/cm
2
g.
(8) Disconnect the charge set, and mount the
Liquid side and Gas side valveʼs stem nuts and the service port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way valve
3-Way valve
CLOSE
Page 58
- 58 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
1) Re-air purging
(Re-installation)
• Procedure
(1) Confirm that both the liquid side valve and the
gas side valve are set to the closed position.
(2) Connect the charge set and a gas cylinder to
the service port of the Gas side valve.
– Leave the valve on the gas cylinder closed.
(3) Air purging.
– Open the valves on the gas cylinder and the
charge set. Purge the air by loosening the flare nut on the liquid side valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.
– After purging the air, use a torque wrench to
tighten the flare nut on liquid side valve.
(4) Check for gas leakage.
– Check the flare connections for gas leakage.
(5) Discharge the refrigerant.
– Close the valve on the gas cylinder and
discharge the refrigerant until the gauge indicates 3 to 5 kg/cm
2
g.
(6) Disconnect the charge set and the gas
cylinder, and set the Liquid side and Gas side valves to the open position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(7) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
* CAUTION:
Do not leak the gas in the air during Air Purging.
Lo
Closed
OPEN
Closed
Gas cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
3-Way valve
3-Way valve
Refrigerant
Page 59
- 59 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
2) Balance refrigerant of the 3-way valve
(Gas leakage)
• Procedure
(1) Confirm that both the liquid side and gas side
valves are set to the back seat.
(2) Connect the charge set to the 3-way valveʼs
port.
– Leave the valve on the charge set closed. – Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indicates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm
2
G), discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm
2
G. if this is the case, it will not be
necessary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is
discharged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 60
- 60 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
2. Evacuation
(All amount of refrigerant leaked)
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
Page 61
- 61 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
3. Gas Charging
(After Evacuation)
• Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-
connected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the system can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the
specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valveʼs service port.
– Stopping partway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
CAUTION
This unit is charged with R-410A. Pay attention not to charge R-22.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Lo
Charging cylinder
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
3-Way valve
3-Way valve
OPEN
Open
Check valve
(1)
Page 62
- 62 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suction pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor temperature. Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚C)
Indoor Temp. (˚C)
12
11
10
9
8
7
6
5
5 10152025303540
50˚C
40˚C
30˚C
20˚C
10˚C
0˚C
P = 3 + 0.0123 x Tout
1.5
+ 0.8 x Tin
0.5
Where, P : Suction Pressure(kg/cm
2
.
g) Tout : Outdoor Temperature(˚C) Tin : Indoor Temperature(˚C)
Operating Suction Pressure (For R410A)
(According to Indoor & Outdoor Temperature)
Page 63
- 63 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Cycle Parts
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0˚F(0°C) Current : less than 80% of
rated current
Temp. difference : approx. 14°F(8°C) Current : less than 80% of
rated current
Temp. difference : less than 14°F(8°C) Current : over the reated
current
Temp. difference : over 14°F(8°C)
Operating Current
• All amount of refrigerant leaked out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle Defective compressor
• Excessive amount of refrigerant
• Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.
Insufficient amount of Current is low.
Lower Higher refrigerant (Leakage)
Clogging Current is low.
High
Higher
NOTICE
NOTICE
Page 64
- 64 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Electronic Parts (9k model)
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 115V, 60Hz)
• Main power's voltage
• Voltage applied to the unit
• Connecting method of Indoor/Outdoor connecting cable
• Check PWB Ass'y(Outdoor unit)
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
• Connector related to CN-POWER
• Connector related to CN-FAN
• Connector contacting of Outdoor Fan/Compressor
• Display PWB Ass'y Check
• Connector related to CN-DC/DC
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector(including connecting cable of Indoor/Outdoor Unit)
PCB Board Operation Check
Items
• Power Transformer (Outdoor unit)
- Input Voltage
- Output Voltage
• IC01D(7812) Output (Indoor/Outdoor unit)
• IC02D(7805) Output
(Indoor unit)
IC03D(7805) Output
(Outdoor unit)
• IC01A(KIA7036, Reset IC) OSC01B(4MHz) (Indoor/Outdoor unit)
• Replace SMPS Module
• Replace IC01D
• Replace IC02D(Indoor unit) IC03D(Outdoor unit)
• Replace faulty parts
- About AC115V±10% - Check the power voltage
- About DC15V±3
• DC +12V
• DC +5V
• Voltage of Outdoor unit Micom No. 18, Voltage of Indoor unit Micom No. 43 and soldering condition
Content Remedy
NO
YES
(After 20 seconds)
Page 65
- 65 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote controller
Cause by the remote controller
When the mark( ) is displayed in LCD screen, replace battery.
Check the contact of CN-DISP connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN DISP ① - ⑩ : DC +5V
When the detect switch(double key) inside the remote controller door is fault, it is impossible to operate temperature regulating(▲ /▼ ) and wind speed selecting.
Check the connecting circuit between the remote controller
MICOM (No. ) - R17(2Ω) - IR LED - Q1 - R16(2.2KΩ).
Check point
• Check the connecting circuit between PIN ㊸ -
R11L(1K) - C11L(680PF) - MICOM PIN
• Check Receiver Ass'y
Page 66
- 66 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 2°F at least.
When in Fan Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the related circuit of R02H(12.1K), R04H(6.2K), Micom (No.27) (Indoor unit).
• Check the indoor temperature sensor is disconnected or not(About 10kΩ / at 77°F).
When the temperature around Outdoor PWB Ass'y is above 163°F the compressor is stop and only Outdoor Fan is operating.
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of Compressor/Outdoor Fan Motor.
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC200V) is applied to the connecting wire
terminal support transferred to compressor, PWB Ass'y is normal.
• Check the circuit related to the relay(Outdoor unit).
Check point COMP ON COMP OFF
Between Micom(No.
DC5V DC0V
5, 6) and GND
Between IC01M, IC02M(No. 9)
Below DC 1V
About DC12V
and
IC01M, IC02M(No. 8)
(app)
Page 67
- 67 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
When indoor Fan does not operate.
Check connecting condition of the CN-MOTOR CONNECTOR
Does the voltage of terminal of CN-DC/DC CONNECTOR in Indoor unit corresponds to the values in the table of page 72
Do the voltage of terminal of CN-DC/DC CONNECTOR in Outdoor unit corresponds to the values in the table of page 72
Check the patterns and the conditions of outdoor unit PWB Assy's.
Check the connecting condition and disconnection of connecting wires between Indoor and Outdoor unit.
Check the pattern and the condition of Indoor unit PWB Ass'y.
Check the interference of Indoor Fan.
Does the voltage of each terminals of CN-MOTOR CONNECTOR in Indoor unit corresponds to values in the Table of page 72
Check the motor of Indoor Fan
Indoor Fan may be stopped in the Soft Dry Mode(change to the Cooling Operation Mode).
Indoor Fan is to be stopped when Indoor pipe(coil) termperature is lower than 79°F. (At that times, Defrost indicator is turned on)
NO
YES
Page 68
- 68 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
When Vertical Louver does not operate.
• Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with hands Normal
• Check the connecting condition of CN-UP/DOWN Connector
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector
Check the operating circuit of the Vertical Louver
• Confirm that there is DC +12V between pin(RED) of CN-UP/DOWN and GND.
• Confirm that there is a soldering short at following terminals.
- Between
77 , 78 , 79 and 80 of MICOM
- Between 4 , 5 , 6 and 7 of IC02M
- Between 10 , 11 , 12 and 13 of IC01M
- Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts in
the rotation radial of the Vertical Louver
Page 69
- 69 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
• The operation indicator of Indoor unit blinks five times.
• The red indicator of Outdoor unit blinks five times.
Check the connecting wires between Indoor and Outdoor unit for the connecting error and the contacting condition.
Check the installation condition of outdoor unit.
Check for the communication error and the operating condition of product after also operating with the remote controller, then taking above 2 minutes.
Apply the power again after about 20 seconds by the power of Outdoor unit is off.
Check for the communication error and the operating condition of product after also operating with the remote controller, then taking above 2 minutes.
Check the PWB assembly of Indoor and Outdoor unit.
Caution: If the connecting wires of Indoor and Outdoor unit are not connected within 2 minutes after the power
of Outdoor unit is applied, a communication error will occur. Therefore, the power should be applied after connecting them.
When a comunication error occurs.
Page 70
- 70 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
The phenomena in case of connecting error
INDOOR UNIT
Connector Type
Condition
Open and connecting error
Open
Open
Open
Open
Short between terminals
(and ) of ROOM-TH.
Short between terminals
(and ) of PIPE-TH.
Short between terminals
• The same as the phenomenon of Outdoor Unit.
• The up/down vane does not operate.
• The up/down vane does not smoothly operate.
• It does not operate with a remote controller.
• The operation indicator blinks once (on for 0.5 second, off for 3 seconds).
• The compressor operates continuously regardless of the setting temperature and the variation of room temperature.
• The operation indicator blinks once (on for 0.5 second, off for 3 seconds)
• Continuous operation
• The operation indicator blinks once.
• The compressor and the outdoor fan stop.
• The indoor fan speed is low.
• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.
CN-DC/DC
CN-MOTOR
CN-UP/DOWN
CN-DISP
CN-TH
BlueBlackBrownRed
Phenomena
①②③④⑤
On for 0.5 second
Off for 3 seconds
Page 71
- 71 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
OUTDOOR UNIT
Connector Type
Condition
OPEN
• PWB pattern is damaged when applying the power.
Connecting reversely
Connecting reversely
OPEN
OPEN
OPEN
OPEN
Connecting error
(① ↔ ②)
Connecting error
(① ↔ ③)
Connecting error
(① ↔ ④)
Connecting error
(② ↔ ③)
Connecting error
(② ↔ ④)
Connecting error
(③ ↔ ④)
• All functions stop.
• The operation with the remote controller, forced and test one do not operate.
• All functions stop.
• The operation with the remote controller, forced and test one do not operate.
• The Indoor Fan does not operate.
• The signal of remote controller is inputted, but the product does not operate.
• The RED indicator of outdoor unit and the operation indicator of indoor one blinks 5 times after 2 minutes with applying the power.
• No power for Indoor unit.
• The signal input of the remote controller and operation of product is impossible.
• The thermal protector of the Power Trans operates when let it alone for long time.
• The signal of the remote controller is inputted.
• The fuse and Q61 in the Outdoor unit are damaged when the indoor fan is operated.
• No power for Indoor unit.
• The signal input of the remote controller and operation of product is impossible.
• The RED indicator of the Outdoor unit blinks 5 times after 2 minutes with applying the power.
• All functions stop.
• The operation with the remote controller, forced and test one do not operate.
• The only signal of remote controller operation/stop is inputted, but the product does not operate.
• The RED indicator of outdoor unit blinks 5 times after 2 minutes with applying the power.
• The beep sound, such as "beep, beep, beep, beep, beep", occurs periodically in Indoor unit.
• The signal input of a remote controller and operation of product is impossible.
• The RED indicator blinks 5 times after 2 minutes with applying the power.
• All functions stop or the compressor does not operate.
• The operation with the remote controller, forced and test
one do not operate.
• All functions stop.
• The operation with the remote controller, forced and test
one do not operate.
CN-POWER
RY-COMP
terminal
CN-TRANS
CN-FAN
The connecting
wire of CN-
DC/DC, and
Indoor and
Outdoor Unit
④③②①
BlueBlackBrownRed
Phenomena
Page 72
- 72 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Voltage of Connectors according to Indoor Fan Speed
1 2 3 4
1
3
4
1 2 3 4 5
INDOOR
FAN
MOTOR
INDOOR PWB ASSY
Connecting wires
between Indoor
and Outdoor
Indoor
Connecting Terminal
Outdoor
Connecting Terminal
Input Power
TAB-N
CN-MOTOR
CN-DC/DC
RY-COMP-A
3
4
RY-COMP-B
BL BK BR RD
4
3
2
1
CN-DC/DC
BL BK BR
RD
+
-
S-Hi Hi Med Low Off
12k
OUTDOO
R CN-
DC/DC
INDOOR
CN-
DC/DC
INDOOR
CN-
MOTOR
No. of pins
DC Voltage(±10%)
4
2
4
3
4
3
3
3
2
2
2
2
35.5
11.97
35.5
15.87
35.5
15.87
32.96
11.97
32.96
15.87
32.96
15.87
25.17
11.97
25.17
15.87
25.17
15.87
17.28
11.97
17.28
15.87
17.28
15.87
0
11.97
0
15.87
0
15.87
Troubleshooting Guide
Page 73
- 73 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
Exploded View
352150
35211B
354210
135515
131410
146811A
135316
268711A
152302
268711B
135500B
145200
146811B
135500A
266090
268711C
W6640
249951
159830
330871
267110
349600
346810
359012
352380
147581
146811A
135080
567480C
INLET AIR
+
EVA MIDDLE
Indoor Unit
NOTE) *Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List)on GCSC. (GCSC Website http://biz.Lgservice.com)
Page 74
- 74 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Exploded View
2. Outdoor Unit (C/O Series)
NOTE) *Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List)on GCSC. (GCSC Website http://biz.Lgservice.com)
437212
554031
559010
437211
546810
447910
549610
649950
W0CZZ
W6640A
135500A
268711
W6640B
W6920
SUCTION
263230B
263230A
552201
554160
550140
552113
W6631
552203B
435511
135500B
552112
349480
435301
237202
430410
152503
W49810
552203A
Page 75
- 75 -
Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
2. Outdoor Unit (H/P Series)
NOTE) *Please ensure GCSC since the replacement parts may be changed demending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List)on GCSC. (GCSC Website http://biz.Lgservice.com)
Exploded View
437212
554031
559010
546810
447910
549610
135500A
W0CZZ
649950
W6640A
268711
W6640B
W6920
263230A
566000
SUCTION
263230B
554160
552201
552113
435511
135500B
552116
552202
561410 Applied to
Heating Models
437211
553000
430410
349480
435301
152503
237202
W6631
550140
W49810
552203A
552112
552203B
Page 76
P/NO : 3828A20926C
FEBRUARY, 2010
Service call Number # : (888) LG Canada, (888) 542-2623
1. Please call the installing contractor of your product, as warranty service will be provided by them.
2. If you have service issues that have not been addressed by the contractor, please call 1-888-865-3026.
US
CANADA
Loading...