LG AS-H306DGM0 User Manual

Room Air Conditioner
SVC MANUAL(Exploded View)
MODEL :
AS-H306DGM0(S30AHP-ND6/UD6) LS-C306DGB0(S326GC SD0) LS-C306DGB0(S306GC SD0) LS-C306DGM1(S306GP SD1) LSNC306DGB0.AMBAIDA LS-H306DGB0(S306GH SD0) LS-H306DGM1(S326GQ SD1) LS-H306DGM1(S306GQ SD1) LS-H306DGM1(S30LHP) LS-C302DGB1(S302CG SD1) LS-C302DGM1(S302CP SD1) LS-C362DGB1(S362CG SD1)
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
Internal Use Only
http://biz.lgservice.com
LS-C362DGM1(S362CP SD1) LS-H366DGM1(S366GQ SD1) LS-H366DGB0(S366GH SD0) LS-C366DGM1(S366GP SD1) LS-C366DGB0(S366GC SD0) LS-C366DGB0(S386GC SD0) LS-H366DGM1(S386GQ SD1) LS-H362DGB1(S362HG SD1) AS-W246DGH0(S25AWN-ND6/UD6) AS-H366DGM1(S36AHP-ND6/UD6) AS-H366DGM2(S36AHP-ND7/UD7)
- 2 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name ...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions....................................................................................................................................................10
Symbols Used in this Manual...................................................................................................................10
Indoor Unit................................................................................................................................................10
Product Specifications ................................................................................................................................13
Installation .....................................................................................................................................................16
Selection of the Best Location..................................................................................................................16
Piping Length and Elevation.....................................................................................................................16
How to Fix Installation Plate.....................................................................................................................17
Drill a Hole in the Wall..............................................................................................................................17
Drain hose junction...................................................................................................................................17
Flaring work and connection of piping .......................................................................................................18
Flaring work..............................................................................................................................................18
Connection of piping -- Indoor..................................................................................................................18
Connection of the pipes-Outdoor .............................................................................................................22
Connecting the cable between indoor unit and outdoor unit ...................................................................23
Connect the cable to the Indoor unit. .......................................................................................................23
Connect the cable to the outdoor unit ......................................................................................................24
Checking the drainage and forming the pipings........................................................................................25
Checking the drainage .............................................................................................................................25
Form the piping ........................................................................................................................................25
AIR PURGING ................................................................................................................................................26
Air purging................................................................................................................................................26
Air purging with vacuum pump.................................................................................................................26
TEST RUNNING .............................................................................................................................................28
Operation .......................................................................................................................................................29
Function of Controls .................................................................................................................................29
Portection from overheating of power module..........................................................................................33
Portection from overheating of compressor .............................................................................................33
Display Function ......................................................................................................................................34
Self-diagnosis Function............................................................................................................................34
Remote Control Operations......................................................................................................................35
Disassembly ..................................................................................................................................................36
Indoor Unit................................................................................................................................................36
Schematic Diagram.......................................................................................................................................39
Electric Control Device.............................................................................................................................39
Wiring Diagram.........................................................................................................................................41
Components Location ..............................................................................................................................50
Troubleshooting Guide.................................................................................................................................54
Refrigeration Cycle Diagram ....................................................................................................................54
2-way, 3-way Valve .................................................................................................................................56
Cycle Parts...............................................................................................................................................62
Electronic Parts ........................................................................................................................................63
Exploded View...............................................................................................................................................70
- 3 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
LG Model Name
LG Model Name
2003
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing H: Thailand
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
- 4 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
LG Model Name
2004~
12 - 345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z
L Chang_won R22 A Chang_won R410A C Chang_won R407C T China K Turkey R22 E Turkey R410A H Thailand
N India Z Brazil D Indonesia X Mexico V Vietnam S Out sourcing
Refrigerant
2 Product Type A~Z S: Split Type Air Conditioner
3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump X: C/O + E/Heater Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h
6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase 5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase 6: 220-240V/50Hz E: 265V, 60Hz 7: 110V, 50/60Hz F: 200V
CHASSIS Look
D K
L G M N D P
Division Panel Type(Deluxe) Fighting 'Look'
(LG1) (LG2)-SEMI PANEL OEM1 OEM2 Panel Type(Deluxe) LG3
, 50/60Hz 8: 380-415V/50Hz 9: 380-415V/60Hz
7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis
8 Look A~Z Look,
Color (Artcool Model)
9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
R Mirror W White B Blue D Wood M Metal C Cherry
S4/S5
S6 SQ SR
ST
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F NBF F+(A/changeove)+A/clean+Low A G NBF F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K NBF F+(A/changeove)+A/clean L NBF F+(A/changeove)+A/clean+4way M NBF F+(A/changeove)+A/clean+PTC N NBF F+(A/changeove)+Autoclean+4way+PTC P NBF F+(A/changeove)+A/clean+4way+Low A+PTC Q (Nano)Plasma+ION+A/Clean S 4way+(Nano)Plasma F+
Negative ION+Healthy dehumidification
+A/Clean T Nano Plasma F+4Way+(A/changeove)+A/clean+Oxy generator U 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean+Oxy generator
V Dry contact W Wire remocon 8
- 5 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
Always use the power plug and socket with the ground terminal.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
.Do not modify or extend the power cord.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Installation
- 6 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Do not install the product on a defective instal­lation stand.
Be sure the installation area does not deteriorate with age.
• It may cause injury, accident, or damage to the product.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Sharp edges could cause injury. Be especially care­ful of the case edges and the fins on the condenser and evaporator.
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
For installation, always contact the dealer or an Authorized service center
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
• There is risk of fire, electric shock, explosion, or injury.
- 7 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Safety Precautions
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
Do not place a heater or other appliances near the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Wax
Thinner
- 8 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
Installation
90˚
Unplug the unit if strange sounds, odors, or smoke comes from it.
Be cautious that water could not enter the product.
There is risk of electric shock or fire. There is risk of fire, electric shock, or product dam­age.
Safety Precautions
- 9 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
There is risk of fire, electric shock, or damage to the plastic parts of the product.
There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
There is risk of personal injury and failure of product. There are sharp and moving parts that could cause
personal injury.
Operation
Wax
Safety Precautions
- 10 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Dimensions
Dimensions
Installation plate
D
H
W
W mm 1209
H mm 346
D mm 205
Model
Dimension
24k~38k Btu Series
Indoor Unit
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Dimensions
- 11 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
MODEL
DIM
W
L7 L6 L8 L9
D
L1
L2
L3
L10L11
L4L5
H
Gas side 3-way valve
Liquid side 2-way valve
W mm 870
H mm 800
D mm 320 L1 mm 370 L2 mm 340 L3 mm 25 L4 mm 775 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54
L10 mm 79 L11 mm 76.4
24k, 30k, 32k Btu Series
• 24k, 30k, 32k Series
- 12 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
L6L7 L8
L9
L4
H
L5
W
D
L1
L3
L2
L10 L11
Gas side 3-way valve
Liquid side 3-way valve
36k, 38k Btu Series
MODEL
DIM
W mm 870
H mm 1038
D mm 320
L1 mm 360
L2 mm 340
L3 mm 25
L4 mm 1035
L5 mm 25
L6 mm 546
L7 mm 160
L8 mm 160
L9 mm 44
L10 mm 75
L11 mm 80
• 36k, 38K Series
Dimensions
Model Name
Item Unit
Cooling Capacity
kW
Heating Capacity
Moisture Removal l/h
Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
W/W
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant
(R410A)
g
(R22)
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
Product Specifications
Product Specifications
Table-1
8.5 8.21 8.21 8.21 6.8
9.08 - 8.8 - 7.5
3.8 3.8 3.8 3.8 3.8
1Ø, 220V-240V, 50Hz 1Ø, 220V-240V, 50Hz 1Ø, 220V-240V, 50Hz 1Ø, 220V, 60Hz 1Ø, 220V-240V, 50Hz
20/21.5 20 20/21.5 20 20/21.5
58 58 58 58 58
48 48 48 48 46
58 58 58 58 58
3250 3150 3150 3200 1980
3450 - 3440 - 2350
14.7 14.5 14.5 14.5 9
14.9 - 15.5 - 11
2.62 2.6 2.6 2.57 3.43
2.63 - 2.56 - 3.19
55 55 55 55.8 55
88 88 88 82 88
1209*346*205 1209*346*205 1209*346*205 1209*346*205 1209*346*205
870*800*320 870*800*320 870*800*320 870*800*320 870*800*320
18 18 18 18 18
75 75 75 75 75
2450 - - - 1700
- 2400 2400 2500 -
OOOOO
OOOOO
OOOOO
24Hr On/OFF 24Hr On/OFF 24Hr On/OFF 24Hr On/OFF 24Hr On/OFF
OOOOO
L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless
1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35) 1/4"(6.35)
5/8"(15.88) 5/8"(15.88) 5/8"(15.88) 5/8"(15.88) 5/8"(15.88)
OOOOO
OOOOO
0.75mm2*3, 0.75mm
2
*3 0.75mm2*3, 0.75mm
2
*2 0.75mm2*3, 0.75mm
2
*3 0.75mm2*3, 0.75mm
2
*2 0.75mm2*3, 0.75mm
2
*2
2.5mm2*3 2.5mm2*3 2.5mm2*3 2.5mm2*3 2.5mm2*3
AS-H306D
SERIES
LS-C306D
SERIES
LSNC306DGB0.
AMBAIDA
LS-H306D
SERIES
LS-C302D
SERIES
AS-W246DGH0
- 13 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
- 14 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Model Name
Item Unit
Cooling Capacity
kW
Heating Capacity
Moisture Removal l/h
Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
W/W
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant
(R410A)
g
(R22)
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
Table-2
9.97 10.55 10.55 10.55 10.00
- 10.55 - 10.55 10.25
4.2 4.2 4.2 4.2 4.2
1Ø, 220V, 60Hz 1Ø, 220V-240V, 50Hz 1Ø, 220V-240V, 50Hz 1Ø,220V,60Hz 1Ø,220V-240V,50Hz
22 22 22 22 25
64 64 64 64 58
51 51 51 51 51
60 60 60 60 60
3750 4200 4200 3700 3650
- 3900 - 3900 3600
17.5 19 19 17 16
- 18 - 18 16
2.66 2.51 2.51 2.85 2.73
- 2.69 - 2.71 2.85
77.2 76.1 76.1 77.2 76.1
41 41 41 41 41
1209*346*205 1209*346*205 1209*346*205 1209*346*205 1209*346*205
870*1038*320 870*1038*320 870*1038*320 870*1038*320 870*1038*320
19 19 19 19 19
80 80 80 80 80
- - - - 2600
2650 2660 2660 2600 -
OOO OO
OOO OO
OOO OO
24Hr On/OFF 24Hr On/OFF 24Hr On/OFF 24Hr On/Off 24Hr On/OFF
OOO OO
L.C.D wireless L.C.D wireless L.C.D wireless L.C.D wireless L.C.D Wireless
3/8"(9.52) 3/8"(9.52) 3/8"(9.52) 3/8"(9.52) 3/8"(9.52)
5/8"(15.88) 5/8"(15.88) 5/8(15.88) 3/4"(19.05) 3/4"(19.05)
OOO OO
OOO OO
0.75mm2*3, 0.75mm
2
*2 0.75mm2*3, 0.75mm
2
*2 0.75mm2*3, 0.75mm
2
*2 0.75mm2*3, 0.75mm
2
*2 0.75mm*3,0.75mm*3
3.5mm2*3 3.5mm2*3 3.5mm2*3 3.5mm2*3 3.5mm*3
LS-C362D
SERIES
LS-H366D
SERIES
LS-C366D
SERIES
LS-H362D
SERIES
AS-H366DGM1
Product Specifications
- 15 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Model Name
Item Unit
Cooling Capacity
kW
Heating Capacity
Moisture Removal l/h
Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
W/W
C.O.P Heating
Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor
Refrigerant
(R410A)
g
(R22)
Airflow Direction Control (Up & Down)
Airflow Direction Control (Left & Right)
Chaos Wind
Timer
Self Diagnosis
Remocon Type
Service Valve
Liquid
inch(mm)
Gas
Sleeping Operation
Drain Hose
Connecting Cable
Power Cord
Table-3
9.3
10.15
4.2
1_,220V-240V,50Hz
25
58
51
60
3680
3700
16
16
2.53
2.74
76.1
41
1209*346*205
870*1038*320
19
80
2600
-
O
O
O
24Hr On/OFF
O
L.C.D Wireless
3/8"(9.52)
3/4"(19.05)
O
O
0.75mm*3, 0.75mm*3
3.5mm*3
AS-H366DGM2
Product Specifications
- 16 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be conveniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a
place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
More than "B"
More than
"A"
More than 2.3m
More than
"A"
Capacity is based on standard length and maxi­mum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
24K, 30~38K 30 12
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
Length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
30k~32k 5/8"(Ø15.88) 1/4"(Ø6.35) 7.5 15 30 40
36k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 40
3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 40
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
- 17 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the hole
which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so as not to disconnect.
Close the Front Grille.
How to Fix Installation Plate Drill a Hole in the Wall
Drain hose junction
Remove the rubber stopple in the desired drain direc­tion.
Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by.
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Connecting
part
Adhesive
Drain hose
Only the desired direction
Type "A" screw
Installation Plate
Installation plate
Left rear piping Right rear piping
C
D
B
A
Chassis
Hook
ABCD
SD(24k, 30~38k) 120 110 43 43
CHASSIS
(Grade)
Distance (mm)
- 18 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Flaring work and connection of piping
Flaring work
Flaring work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the follow­ing procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared sec-
tion and re-flare it.
Preparing the indoor unit's piping and drain hose for instal­lation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.(Optional)
Carry out flaring work using flaring tool as shown below.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direc­tion as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
Drain hose
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Ø19.05 3/4 1.0~1.3
Outside diameter A
Connection of piping -- Indoor
When install, make sure that the remaining parts must be removed clearly so as not to damage the pip­ing and drain hose, especially power cord and connecting cable.
- 19 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Flaring work and connection of piping
Route the indoor tubing and the drain hose in the direction of rear right.
Drain hose
Connecting
cable
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Plastic bands
Insulation material
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Indoor unit tubing Flare nut Pipes
Connecting pipe
Connecting cable
Tape
Drain hose
Drain hose
Insert the connecting cable into the indoor unit from the out­door unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
NOTE: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Indoor unit installation
Hook the indoor unit onto the upper portion of the installa­tion plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installa­tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(click­ing sound).
Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material and the
indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
For right rear piping
- 20 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tighten the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit, install the
drain pipe.
Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Route the indoor tubing and the drain hose to the required piping hole position.
Insert the piping, drain hose, and the connect­ing cable into the piping hole.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.
Indoor unit installation
Hang the indoor unit from the hooks at the top of the instal­lation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Tape the drain hose and the connecting cable.
Connecting cable
Drain pipe
Connecting cable
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Indoor unit tubing Flare nut Pipes
Installation plate
Spacer
Indoor unit
8cm
Plastic bands
Insulation material
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
For left rear piping
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
- 21 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Installation Information (For left piping)
Good case For left piping. Follow the instruction below.
Press on the upper side of clamp. ( )
Flaring work and connection of piping
Wrap the area which accommodates the rear piping hous­ing section with vinyl tape.
Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the installa-
tion plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
Reroute the pipings and the drain hose across the back of the chassis.
Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis and push the bottom of tubing holder to be engaged at the bottom of chassis.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Tubing holder
Drain hose
Connecting
cable
Unfold the tubing to downward slowly. ( )
Bend the tubing to the left side of chassis.
- 22 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Flaring work and connection of piping
Align the center of the pipings and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.
Bad case
Following bending type from right to left could cause
problem of pipe damage.
Connection of the pipes-Outdoor
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
- 23 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connect the cable to the Indoor unit.
Connecting the cable between indoor unit and outdoor unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection.
(Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker or time delay fuse.
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Connecting the cable between indoor unit and outdoor unit
CAUTION
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H07RN-F approved by HAR or SAA).
20mm
7.5mm
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
20mm
7.5mm
8.5mm
20mm
GN/YL
NORMAL CROSS-SECTIONAL AREA 2.5mm
2
8.5mm
20mm
GN/YL
NORMAL CROSS-SECTIONAL AREA 3.5mm
2
30k, 32k 36k, 38k
4(N)
Terminals on the indoor unit
3(L)
5 67
6
7
4(N)
Terminals on the outdoor unit
Color of Wires
POWER INPUT
Color of Wires
Cooling & Heating Models
3(L)2(N)1(L)
5
G/Y
BROWN
BLUE
REDWHITE BLACK
REDWHITE BLACK
G/Y
BROWN
BLUE
2(N)
Terminals on the indoor unit
1(L)
34
6
4(N)
Terminals on the outdoor unit
Color of Wires
POWER INPUT
Color of Wires
Cooling Only Models
3(L)2(N)1(L)
5
G/Y
BROWN
BLUE
WHITE
RED
WHITE
RED
G/Y
BROWN
BLUE
- 24 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Connecting the cable between indoor unit and outdoor unit
Remove the control cover from the unit by loosening the screw.
Connect the wires to the terminals on the con­trol board individually.
Secure the cable onto the control board with the cord clamp.
Refix the control cover to the original position with the screw.
Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately discon­nect all supply lines must be fitted.
Over 5mm
Cover control
Connecting cable
The power connecting cable
Terminal block
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring,
be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations
to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness. (Refer to page 21)
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func­tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
Connect the cable to the outdoor unit
24k, 30k, 32k 36k, 38k
30 35
Circuit Breaker
(A)
Grade
- 25 -
Copyright ©2009 LG Electronics. Inc. All right reserved. Only for training and service purposes
LGE Internal Use Only
Checking the drainage and forming the pipings
Checking the drainage and forming the pipings
Checking the drainage Form the piping
To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
Form the piping by wrapping the connecting portion of the indoor unit with insulation mate­rial and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable from down to up.
Secure the tapped piping along the exterior wall using sad­dle or equivalent.
To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down to up.
Secure the taped piping along the exterior wall. Form a trap
to prevent water entering the room.
Fix the piping onto the wall by saddle or equivalent.
Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
Pull the right and the left side.
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap