LG AS-H076QGA2, AS-H096QGA2, AS-H126RGA2 Service manual

Page 1
LG
Room
Air Conditioner
SERVICE MANUAL
LG
MODELS: AS-H076QGA2
AS-H096QGA2 AS-H126RGA2 (Applied to new Refrigerant R410A)
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Page 2
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
LG Model Name...............................................................................................................................................3
Safety Precautions..........................................................................................................................................5
Dimensions ...................................................................................................................................................10
Symbols Used in this Manual...................................................................................................................10
Indoor Unit................................................................................................................................................10
Outdoor Unit.............................................................................................................................................11
Product Specifications ................................................................................................................................12
Installation.....................................................................................................................................................13
Select the Best Location .........................................................................................................................13
Piping Length and Elevation.....................................................................................................................13
How to Fix Installation Plate.....................................................................................................................14
Drill a Hole in the Wall..............................................................................................................................14
Flaring Work.............................................................................................................................................15
Connection of Piping Indoor.....................................................................................................................16
Connection of the Pipes-Outdoor.............................................................................................................19
Connect the Cable to the Indoor Unit.......................................................................................................20
Connect the Cable to the Outdoor Unit....................................................................................................21
Checking the Drainage.............................................................................................................................22
Form the Piping........................................................................................................................................22
Test Running ............................................................................................................................................23
Operation ......................................................................................................................................................24
Function of Controls.................................................................................................................................24
Display Function.......................................................................................................................................28
Self-diagnosis Function............................................................................................................................28
Remote Control Operations......................................................................................................................29
Disassembly..................................................................................................................................................30
Indoor Unit................................................................................................................................................30
Schematic Diagram.......................................................................................................................................33
Electric Control device..............................................................................................................................33
Wiring Diagram.........................................................................................................................................35
Components Location ..............................................................................................................................36
Troubleshooting Guide.................................................................................................................................38
Refrigeration Cycle Diagram....................................................................................................................38
Pipe Length and the Elevation .................................................................................................................39
2-way, 3-way Valve...................................................................................................................................40
Cycle Parts...............................................................................................................................................46
Electronic Parts........................................................................................................................................47
Exploded View ..............................................................................................................................................54
Indoor Unit...............................................................................................................................................54
Outdoor Unit............................................................................................................................................55
Replacement Parts List ................................................................................................................................56
Indoor......................................................................................................................................................56
Outdoor ....................................................................................................................................................57
Page 3
Service Manual 3
LG Model Name
12
3456789
Code Type Code of Model Meaning
1,2 Type of Airconditioner A~Z LS: LG Split Type Airconditioner
3 Chassis A~Z Name of toll of Unit
Ex. LS-R S R Chassis
4,5 Capacity(Btu/h) 1~9 Cooling/Heating Capacity
Ex. "09" 9,000Btu/h
6 Electric Range 1~9 Electric Standard
1 115V/60Hz 6 220~240V/50Hz 2 220V/60Hz 7 110V, 50/60Hz 3 208~230V/60Hz 8 ➔ 380~415V/50Hz 5 200~220V/50Hz 9 380~415V/60Hz
7 Serial No. 0~9
A~Z
8 Cooling/Heating A~Z
9 LG/OEM Brand A~Z L: LG Brand M: 1st OEM Brand
G: 2nd LG Brand N: 2nd OEM Brand
-
Basic A 0 Plasma Filter B 1 Auto Swing
+ Plasma Filter C 2 Telephone + LED Display D 3 Telephone + LCD Display E 4 Auto Swing
+ Plasma Filter + Telephone + LCD
F5 Low Ambient + Ambient/change G 6 Plasma Filter + Low Ambient + Ambient/change
H7 Internet J 8 Auto Swing + Plasma Filter + Oxygen Generator
K9 Auto Swing + Soft Start ZL Auto Swing + Star Rating M Y Auto Swing + Star Rating + Plasma Filter N X Auto Swing + Soft Start + Star Rating P W Auto Swing + Soft Start + Star Rating 4 + Plasma
QV Auto Swing + Telephone + LCD R U Auto Swing + Telephone + LCD + Soft Start
ST
C/O
C A D G K
H/P
H B E J L
E/H+C/O
X 5 7
-
-
E/H+H/P
Y 6 8
-
-
C/O
F M Q
-
-
H/P
R P S
-
-
C/O
V
W
1 3
H/P
N
Y 2 4
H/PTH/P
U
INDOOR
BASIC
BASIC PLASMA PLASMA
GOLD FIN
OUTDOOR
BASIC GOLD FIN GOLD FIN
BASIC GOLD FIN
UNIT
R22
HFC R22+AC INV.
HFC+AC
INV.
HFC+DC
INV.
2002
Page 4
4 Room Air Conditioner
12 -345678910
Code Type Code of Model Meaning
1 Producing Center, A~Z L: Chang-won R22 N: India
Refrigerant A: Chang-won R410A Z: Brazil
C: Chang-won R407C D: Indonesia T: China M: Mexico K: Turkey R22 V: Vietnam E: Turkey R410A S: Out Sourcing
H: Thailand 2 Product Type A~Z S: Split Type Air Conditioner 3 Cooling/Heating/Inverter A~Z C: Cooling only
H: Heat pump
X: C/O + E/Heater
Z: H/P + E/Heater
V: AC Inverter C/O N: AC Inverter H/P Q: DC Inverter C/O W: DC Inverter H/P
4, 5 Capacity 0~9 Cooling/Heating Capacity
Ex. "09" 9,000 Btu/h 6 Electric Range 1~9 1: 115V/60Hz, A: 220V, 50Hz, 3Phase
A~Z 2: 220V/60Hz B: 208~230V, 60Hz, 3Phase
3: 208-230V/60Hz C: 575V, 50Hz, 3Phase
5: 200-220V/50Hz D: 440~460, 60Hz, 3Phase
6: 220-240V/50Hz E: 265V, 60Hz
7: 110V, 50/60Hz F: 200V, 50/60Hz
8: 380-415V/50Hz
9: 380-415V/60Hz 7 Chassis A~Z Name of Chassis of Unit
Ex. LSP SP Chassis 8 Look A~Z Look,
Color (Artcool Model) 9 Function A~Z
10 Serial No. 1~9 LG Model De
* ARTCOOL COLOR
velopment Serial No.
Basic A Basic+4Way B Plasma Filter C Plasma Filter+4 Way D Tele+LCD E Tele+LCD+Nano plasma+4Way F Nano Plasma F+(A/changeove)+A/clean+Low A G Nano Plasma F+(A/changeove)+A/clean+4way+Low A H Tele+LED+4way I Internet J Plasma F+4Way+Oxy generator K Nano Plasma F+(A/changeove)+A/clean L Nano Plasma F+(A/changeove)+A/clean+4way M Nano Plasma F+(A/changeove)+A/clean+PTC N Nano Plasma F+(A/changeove)+Autoclean+4way+PTC P Nano Plasma F+(A/changeove)+A/clean+4way+Low A+PTC Q Negative ION+A/Clean R (Nano)Plasma+Negative ION+A/Clean S 4way+(Nano)Plasma F+Negative ION+Healthy dehumidification+A/Clean
T
Nano Plasma F+4Way+(A/changeove)+A/clean+ U
R Mirror W White B Blue D Wood M Metal C Cherry
2003
Page 5
Service Manual 5
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
Do not use damaged power cords, plugs, or a loose socket.
Always use the power plug and socket with the ground terminal.
• There is risk of fire of electric shock. • There is risk of electric shock.
Install the panel and the cover of control box securely.
.Do not modify or extend the power cord.
• There is risk of fire of electric shock. • No grounding may cause electric shock.
Installation
Page 6
6 Room Air Conditioner
Safety Precautions
Do not install the product on a defective instal­lation stand.
Be sure the installation area does not deteriorate with age.
• It may cause injury, accident, or damage to the
product.
• If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
• Sharp edges could cause injury. Be especially care­ful of the case edges and the fins on the condenser and evaporator.
There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
For installation, always contact the dealer or an Authorized service center
For re-installation of the installed product, always contact a dealer or an authorized ser­vice center.
Do not install, remove, or re-install the unit by yourself.
• There is risk of fire, electric shock, explosion, or injury.
• There is risk of fire, electric shock, explosion, or injury.
Page 7
Service Manual 7
Safety Precautions
Operation
Do not turn the air-conditioner ON or OFF by plugging or unplugging the power plug.
Use a dedicated outlet for this appliance.
• There is risk of fire or electrical shock. • There is risk of fire or electrical shock.
Grasp the plug to remove the cord from the outlet. Do not touch it with wet hands.
Do not place a heater or other appliances near the power cable.
• There is risk of fire or electrical shock. • There is risk of fire and electric shock.
Do not allow water to run into electrical parts. Do not store or use flammable gas or com-
bustibles near the air conditioner.
• There is risk of fire, failure of the product, or electric shock.
• There is risk of fire or failure of product.
Wax
Thinner
Page 8
8 Room Air Conditioner
Always check for gas (refrigerant) leakage after installation or repair of product.
Install the drain hose to ensure that water is drained away properly.
• Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage.
Keep level even when installing the product. Use two or more people to lift and transport
the air conditioner.
• To avoid vibration or water leakage. • Avoid personal injury.
Installation
90˚
Unplug the unit if strange sounds, odors, or smoke comes from it.
Be cautious that water could not enter the product.
• There is risk of electric shock or fire. • There is risk of fire, electric shock, or product dam­age.
Page 9
Service Manual 9
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
Do not touch the metal parts of the product when removing the air filter. They are very sharp!
• There is risk of fire, electric shock, or damage to the plastic parts of the product.
• There is risk of personal injury.
Do not step on or put anyting on the product. (outdoor units)
Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in.
• There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause
personal injury.
Operation
Wax
Page 10
10 Room Air Conditioner
Dimensions
Dimensions
Installation plate
D
H
W
W mm 824 900
H mm 260 285 D mm 155 156
Model
Dimension
AS-H076QGA2 AS-H096QGA2
AS-H126RGA2
Indoor Unit
This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the
air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Page 11
Service Manual 11
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
7k, 9k, 12k Btu Series
DIM unit
W mm 575
H mm 525
D mm 260 L1 mm 301 L2 mm 73 L3 mm 392 L4 mm 35 L5 mm 100
Dimensions
Outdoor Unit
Page 12
Model Name
Item Unit
Cooling Capacity
Btu/h
Heating Capacity Moisture Removal l/h Power Source Ø, V, Hz
Air Circulation
Indoor
m3/min
Outdoor
Noise Level
Indoor
dB (A)±3
Outdoor
Input
Cooling
W
Heating
Running
Cooling
A
Current
Heating
E.E.R. Cooling
Btu/hW
C.O.P Heating Motor Output
Indoor
W
Outdoor
Dimensions
Indoor
mm
(W x H x D)
Outdoor
Net. Weight
Indoor
kg
Outdoor Refrigerant (R410A) g Airflow Direction Control (Up & Down) Airflow Direction Control (Left & Right) Chaos Wind Timer Self Diagnosis Remocon Type
Service Valve
Liquid
inch(mm)
Gas Sleeping Operation Drain Hose Connecting Cable Power Cord
12 Room Air Conditioner
Product Specifications
Product Specifications
Table-1
7,000 9,000 12,000 7,300 9,300 12,500
11.21.2
1Ø, 220-240V, 50Hz 1Ø, 220-240V, 50Hz 1Ø, 220-240V, 50Hz
5.1 / 5.5 5.9 / 6.6 8.8 / 9.5 20 20 20 34 36 39 49 49 49
730 940 1,250 760 970 1,300
3.2 4.1 5.6
3.3 4.2 5.8
9.59 9.57 9.60
2.81 2.81 2.82
3.7 7.0 9.5 18 18 18
824 x 260 x 155 824 x 260 x 155 900 x 285 x 156 575 x 525 x 260 575 x 525 x 260 575 x 525 x 260
778
25 26 27
640 660 830
OOO
---
OOO
7 Hr OFF 7 Hr OFF 7 Hr OFF
OOO
L.C.D Wireless L.C.D Wireless L.C.D Wireless
1/4" (6.35) 1/4" (6.35) 1/4" (6.35) 3/8" (9.52) 3/8" (9.52) 1/2" (12.7)
OOO OOO
1.0mm2x 3, 0.75mm2x 2 1.0mm2x 3, 0.75mm2x 2 1.0mm2x 3, 0.75mm2x 2
1.0mm
2
1.0mm
2
1.0mm
2
AS-H076QGA2 AS-H096QGA2 AS-H126RGA2
Page 13
Service Manual 13
Installation
Installation
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in
front of the unit.
Make sure that condensation drainage can be con­veniently routed away. Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
Use a stud finder to locate studs to prevent unnec­essary damage to the wall.
Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place where noise and vibration are mini­mum.
Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than "A"
More than "B"
More than 2.3m
More than "B"
More than 10cm More than 10cm
More than 60cm
More than 60cm
More than 70cm
CAUTION: Install the indoor unit on the wall
where the height from the floors more than 2.3 meters.
CAUTION:
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters.
Grade
Clearance(cm)
AB
7K~28K 10 5
30K~38K 30 12
Pipe Size
Capacit
y
(Btu/h)
GAS LIQUID
Max.
Length
A
(m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
7k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
If case more than 5m
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
I
Selection of the Best Location
Piping Length and Elevation
Page 14
14 Room Air Conditioner
Installation
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with four type A screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typi­cally. Drilling the hole through the wall for pip­ing connections must be done safely.
Drill the piping hole with a ø70mm hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Open the Front Grille.
Pass Telephone Control Cord Wire through the
hole which the power cord goes through.
Connect Telephone Control Cord Wire to the phone jack of telephone PCB of Control Box.
Fix Telephone Control Cord Wire inside Control box so as not to disconnect.
Close the Front Grille.
Installation Plate
Type "A" screw
5-7mm
(3/16"~5/16")
Indoor
WALL
Outdoor
Installation plate
Ø70mm
Left rear piping Right rear piping
C
D
B
A
Ø70mm
Ø70mm
Left rear piping
Right rear piping
CE A
B
D
Installation plateInstallation plate
ABCD
SJ 90 20 80 20
SL, SK 45 40 80 20
SQ 75 12 80 12 SR 0 40 20 40 ST 105 0 210 0
CHASSIS
(Grade)
Distance (mm)
How to Fix Installation Plate Drill a Hole in the Wall
ABCDE SM 180 115 - 115 50 SN 180 115 195 115 -
CHASSIS
(Grade)
Distance (mm)
Page 15
Service Manual 15
Installation
Flaring Work
Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure.
Cut the pipes and the cable.
Use the piping kit accessory or pipes purchased locally.
Measure the distance between the indoor and the outdoor unit.
Cut the pipes a little longer than the measured distance.
Cut the cable 1.5m longer than the pipe length.
Burr removal
Completely remove all burrs from the cut cross section of pipe/tube.
Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table above.
Carry out flaring work using flaring tool as shown below.
Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared
section and re-flare it.
Copper
pipe
90°
Slanted Uneven Rough
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Pipe
Reamer
Point down
Flare nut
Copper tube
mm inch mm
Ø6.35 1/4 0~0.5 Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5 Ø15.88 5/8 0~1.0 Ø19.05 3/4 1.0~1.3
Outside diameter A
Page 16
16 Room Air Conditioner
Installation
Connection of Piping Indoor
Preparing the indoor unit's piping and drain hose for installation through the wall.
Remove the plastic tubing retainer(see illustration below) and pull the tubing and drain hose away from chassis.
Replace the plastic tubing holder in the original position.
For right rear piping
1. Route the indoor tubing and the drain hose in the direction of rear right.
2. Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insula­tion material* so that dripping from "sweating"(condensation) will not dam­age furniture or floors.
*Foamed polyethylene or equivalent is recom-
mended.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are prop­erly seated on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
4. Connecting the pipings to the indoor unit and drain hose to drain pipe.
Align the center of the pipes and sufficiently tight-
en the flare nut by hand.
NOTICE
CAUTION:
When install, make sure that the remaining
parts must be removed clearly so as not to dam­age the piping and drain hose, especially power cord and connecting cable.
Tubing holder
Connecting cable
Loop
Gas side piping
Liquid side piping
Drain hose
Drain hose
Connecting
cable
Indoor unit tubing Flare nut Pipes
Drain hose
Page 17
Service Manual 17
Installation
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
5. Wrap the insulation material around the con­necting portion.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear pip­ing housing section with vinyl tape.
Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
For left rear piping
1. Route the indoor tubing and the drain hose to the required piping hole position.
2. Insert the piping, drain hose, and the connecting cable into the piping hole.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Wrench
Indoor unit tubing
Open-end wrench (fixed)
Connection pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Drain hose
Connecting
cable
Drain pipe
Connecting cable
Page 18
18 Room Air Conditioner
Installation
3. Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connec-
tion later.
4. Tape the drain hose and the connecting cable.
Connecting cable
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of the installation plate.
Insert the spacer etc. between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
6. Connecting the pipings to the indoor unit and the drain hose to drain pipe.
Align the center of the pipes and sufficiently tight­en the flare nut by hand.
Tighten the flare nut with a wrench.
When extending the drain hose at the indoor unit,
install the drain pipe.
7. Wrap the insulation material around the con­necting portion.
Overlap the connection pipe heat insulation and
the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
Wrap the area which accommodates the rear pip-
ing housing section with vinyl tape.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Vinyl tape
Adhesive
Drain hose
Indoor unit drain hose
(narrow)
Plastic bands
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Indoor unit piping
Pipe
Vinyl tape (wide)
Wrap with vinyl tape
Installation plate
Spacer
Indoor unit
8cm
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Connection pipe
Flare nut
Open-end wrench (fixed)
Page 19
Service Manual 19
Installation
Bundle the piping and drain hose together by wrapping them with cloth tape over the range with­in which they fit into the rear piping housing sec­tion.
8. Reroute the pipings and the drain hose across the back of the chassis.
9. Set the pipings and the drain hose to the back of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be engaged at the bottom of chassis.
10. Indoor unit installation
Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
1. Align the center of the pipings and sufficiently tighten the flare nut by hand.
2. Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on the wrench.
mm inch kg.m
Ø6.35 1/4 1.8 Ø9.52 3/8 4.2
Ø12.7 1/2 5.5 Ø15.88 5/8 6.6 Ø19.05 3/4 6.6
Outside diameter Torque
Drain hose
Vinyl tape(narrow)
Pipe
Wrap with vinyl tape(wide)
Piping for passage through piping hole
Outdoor unit
Gas side piping (Bigger diameter)
Liquid side piping (Smaller diameter)
Torque wrench
Tubing holder
Drain hose
Connecting
cable
Connection of the Pipes-Outdoor
Page 20
20 Room Air Conditioner
Installation
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board in dividually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and
the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker or time delay fuse.
NORMAL CROSS-SECTIONAL AREA 0.75mm
2
CAUTION
The power connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Type "B" approved by HAR or SAA).
The power cord connected to the "A" unit should be complied with the following specifications(Type "B" approved by HAR or SAA).
7k~14k 18k 24k~28k 30k, 32k 36k, 38k
1.0 1.5 2.5 2.5 5.5
Unit(A) Indoor Indoor Indoor Outdoor Outdoor
Cable Type(B) H05VV-F H05VV-F H05VV-F H05RN-F H05RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
7k~14k 18k 24k~28k
1.0 1.5 2.5
Cable Type(B) H07RN-F H07RN-F H07RN-F
NORMAL
CROSS
-SECTIONAL AREA
Grade
30k, 32k 36k, 38k
0.75 0.75
Cable Type(B) H07RN-F H07RN-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm2)
(mm
2
)
(mm2)
CAUTION:
The above circuit diagram is subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out easily.
Connect the wires according to color codes by referring the wiring diagram.
When installing, refer to the circuit diagram on the Control Box of Indoor Unit.
When installing, refer to the wiring diagram on the Control Cover Inside Outdoor Unit.
Connect the Cable to the Indoor Unit.
CAUTION:
If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Page 21
Service Manual 21
Installation
1. Remove the control cover from the unit by loos­ening the screw. Connect the wires to the terminals on the control board individually.
2. Secure the cable onto the control board with the cord clamp.
3. Refix the control cover to the original position with the screw.
4. Use a recognized circuit breaker "A" between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.
Terminal block
Over 5mm
Cover control
Connecting cable
Connecting cable
CAUTION: After the confirmation of the above conditions, prepare the wiring as
follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 20))
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal func-
tion of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.
Outdoor Unit
7k~14k 18k 24k~28k 30k, 32k 36k, 38k
15 20 30 30 40
Circuit
Breaker
(A)
Grade
Connect the Cable to the Outdoor Unit
Page 22
22 Room Air Conditioner
Installation
Checking the Drainage Form the Piping
1. To remove the front panel from the indoor unit.
Set the air direction louvers up-and-down to the position(horizontally) by hand.
Remove the securing screws that retain the front panel. Pull the lower left and right sides of the grille toward you and lift it off.
2. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out the drain exit.
3. Drain piping
The drain hose should point downward for easy drain flow.
Do not make drain piping.
1. Form the piping by wrapping the connecting portion of the indoor unit with insulation materi­al and secure it with two kinds of vinyl tapes.
If you want to connect an additional drain hose,
the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
2. In cases where the outdoor unit is installed below the indoor unit perform the following.
Tape the piping, drain hose and connecting cable
from down to up.
Secure the tapped piping along the exterior wall
using saddle or equivalent.
3. In cases where the Outdoor unit is installed above the Indoor unit perform the following.
Tape the piping and connecting cable from down
to up.
Secure the taped piping along the exterior wall.
Form a trap to prevent water entering the room.
Fix the piping onto the wall by saddle or equiva-
lent.
Pull the right and the left side.
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water from entering into electrical parts.
Seal small openings around pipings with a gum type sealer.
Seal a small opening around the pipings with gum type sealer.
Trap
Trap
Downward slope
Do not raise
Accumulated drain water
Tip of drain hose dipped in water
Air
Waving
Water leakage
Water leakage
Ditch
Less than 50mm gap
Water leakage
Page 23
Service Manual 23
Installation
Test Running
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote control
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly.
3. Reattach the cover by
pushing it back into position.
Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
Remove the batteries from the remote control if the system is not going to be used for a long time.
Settlement of outdoor unit
Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.
When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
In the case when the vibration of the unit is con­veyed to the hose, secure the unit with an anti­vibration bushing.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
2. Measure the temperature of the intake and discharge of air.
3. Ensure the difference between the intake tempera­ture and the discharge is more than 8°C(46°F) (Cooling) or (Heating).
4. For reference; the gas side pressure of optimum condition is as below.(Cooling)
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pres­sure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
NOTICE
NOTICE
Bolt
Tubing connection
Discharge temperature
Discharge air
Intake temperature
R-22 35°C (95°F) 4~5kg/cm2G(56.8~71.0 P.S.I.G.)
R-410A 35°C (95°F) 8.5~9.5kg/cm
2
G(120~135 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
PUMP DOWN
Page 24
24 Room Air Conditioner
Operation
Function of Controls
Operation
DISPLAY
1) C/O Model Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan stop.
When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp Setting Temp+0.5°C Compressor OFF Temp ➲ Setting Temp-0.5°C
While in compressor running, operating with the airflow speed set by the remote control. While in compressor not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp 25°C 24°C Intake Intake Air Temp<26°C Intake Air Temp-1°C 18°C Intake Intake Air Temp<24°C Intake Air Temp-0.5°C Intake Air Temp<18°C 18°C
Page 25
Service Manual 25
Operation
While in compressor off, the indoor fan repeats low airflow speed and pause.
While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat. Compressor ON Temp. Setting Temp+0.5°C Compressor OFF Temp. ➲ Setting Temp-0.5°C
In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
Heating Mode Operation
When the intake air temp reaches +3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on. Compressor ON Temp. Setting Temp. Compressor OFF Temp. ➲ Setting Temp.+3°C
While in compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 28°C , it
operates with the low or setting airflow speed. When the indoor pipe temp is between 20°C and 28°C, it oper­ates with Super-Low(while in sleep mode, with the medium airflow speed).
While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
If overloaded while in heating mode operation, in order to prevent the compressor from OLP operation, the
outdoor fan is turned on/off according to the indoor pipe temp.
While in defrost control, both of the indoor and outdoor fans are turned off.
Defrost Control
While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
After 40 min heating mode operation, at 4 min interval, whether to carry out defrost control or not and the time of defrost control are determined according to the following conditions.
1) While in heating mode operation, the maximum of the indoor pipe temperature is measured and it is com-
pared with the present indoor pipe temperature to get the difference of the indoor pipe temperatures (=the maximum temperature of indoor pipe ? the present temperature of indoor pipe), according to which, whether to carry out defrost control or not is determined.
2) According to the need of defrost control shown above and the elapsed time of heating mode operation at that
moment, the defrost control time is determined.
3) When the determined time of defrost control is below 7 min, heating mode operation continues without carry-
ing out defrost control. According to the procedure stated above, the determination is made again. When the defrost control time is 7 min or longer, defrost control is then carried out.
While in defrost control, the minimum temp of the indoor pipe is measured and it is compared with the present temp of the indoor pipe to get the difference of the indoor pipe temperatures (=the present temperature of the indoor pipe ? the minimum temperature of the indoor pipe). When the difference is 5°C or higher, defrost con­trol is completed and heating mode operation is carried out.
While in defrost control, if the defrost time determined before the start of defrost control is completed, defrost control stops and heating mode operation is carried out regardless of the above condition.
When the indoor pipe temp is 42°C or above, defrost control is not carried out even if the condition is one of the defrost conditions above.
While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
Page 26
26 Room Air Conditioner
Operation
Airflow Speed Selection
The airflow speed of the indoor fan is set to high, medium, low, or chaos (auto) by the input of the airflow speed selection key on the remote control.
Sleep Timer Operation
When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote control while in appli­ance operation, the operation of the appliance stops.
While the appliance is on pause, the sleep timer mode cannot be input.
While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C. After another 30 min elapse, it increases by 1°C again.
When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to
the low.
When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium.
Chaos Natural Wind Mode
When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the air­flow mode is operated for 2~15 sec. randomly by the Chaos Simulation.
Jet Cool Mode Operation (C/O Model)
If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet Cool Mode Operation (H/P Model)
While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.
In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation.
In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C.
When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority.
When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Forced Operation
Operation procedures when the remote control can't be used.
The operation will be started if the power button is pressed.
If you want to stop operation, re-press the button.
While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
Heat pump Model
Cooling Model
Room Temp. 24°C21°C ≤Room Temp. < 24°C Room Temp. < 21°C
Operating mode Cooling Cooling Healthy Dehumidification Heating
Indoor FAN Speed
High High High High
Setting Temperature
22°C22°C23°C24°C
Page 27
Service Manual 27
Operation
Test operation
During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room tem­perature and resets in 18±1 minutes.
During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, open the front panel upward and Press the power button let it be pressed for about 3 seconds.
If you want to stop the operation, re-press the button.
Auto restart
In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions.
Protection of the evaporator pipe from frosting
If the indoor pipe temp is below 0°C in 7 min. after the compressor operates without any pause while in cool­ing cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting.
When the indoor pipe temp is 7°C or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature.
Buzzer Sounding Operation
When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds.
When the appliance-pause key is input by the remote control, the long "beep" sounds.
When a key is input by the remote control while the slide switch on the main unit of the appliance is on the
forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received.
Page 28
28 Room Air Conditioner
Self-diagnosis Function
Operation
Display Function
1. Heating Model 2. Cooling Model
Cooling, Soft Dry, Fan, Heating Cooling, Soft Dry, Fan
Timer Mode Timer Mode
Hot-start, Deice
Operation Indicator
Timer Indicator
Indoor Unit on Indicator Indoor Unit on Indicator
Deicer Indicator
Operation Indicator
Timer Indicator
Compressor on Indicator
OUT
DOOR
IN
DOOR
IN
DOOR
3sec 3sec 3sec
(once)
Error
Code
1
Error Display LED
(Indoor body operation LED)
Error contents
Indoor room temperature thermistor open/short
Indoor pipe temperature thermistor open/short.
Indoor Thermistor assembly check
SVC check point
Page 29
Service Manual 29
Remote Control Operations
The remote control transmits the signals to the system.
Operation
Page 30
30 Room Air Conditioner
Disassembly
Disassembly
Indoor Unit
Warning :
Disconnect the unit from power supply before making any checks. Be sure the power switch is set to OFF.
To remove the Grille from the Chassis.
Set the up-and-down air discharge louver to open position (horizontally) by finger pressure.
Remove the securing screws.
To remove the Grille, pull the lower left and right
side of the grille toward you (slightly tilted) and lift it straight upward.
1. Before removing the control box, be sure to
take out the wire screwed at the other end.
Display P.C.B Conductor
Step Motor Conductor
Earth Conductor
Motor Conductor
Sensor Conductor
Earth Conductor
Page 31
Service Manual 31
Disassembly
2. To remove the Control Box.
Remove securing screws.
Pull the control box out from the chassis
carefully.
3. To remove the Discharge Grille.
Unhook the discharge grille and pull the discharge grille out from the chassis carefully.
4. To remove the Evaporator.
Remove 3 screws securing the evaporator(at the left 2EA in the Eva Holder, at the right 1EA).
Caution label
CAUTION:
When repair, do not damage
the Caution label.
Page 32
32 Room Air Conditioner
Disassembly
Unhook the tab on the right inside of the chassis
at the same time, slightly pull the evaporator toward you until the tab is clear of the slot.
5. To remove the Motor Cover
Remove 2 securing screw.
Pull the motor cover out from the chassis
carefully.
6. To remove the Cross-Flow Fan
Loosen the screw securing the cross-flow fan to
the fan motor (do not remove).
Lift up the right side of the cross-flow fan and the
fan motor, separate the fan motor from the cross-flow fan.
Remove the left end of the cross-flow fan from
the self-aligning bearing.
Motor cover
Page 33
Service Manual 33
Schematic Diagram
Schematic Diagram
VP
16
1
5V
5V
R09H
C104S
Q03T
A104S
Q01T
5V
1K
C104S
Q02T
CN-TELE
C01D
C01T
100uF/25V
0.001uF 1N4148
D01T
A104S
Q04T
50V
TX
5V
C06H
0.1uF/50V
R01T
0.001uF 50V
C02T
RX
1K
CST-3.58M
OSC02B
ZD02H~ZD03H
5.1V, 1/2W
4.7K
R02A
R03A
100
10uF
50V
C01A
RST
R01A
1K
+
KIA7036P
IC01A
1
2
3
5V
DSOQ2Q3Q0DE
EST
15
Q1
D2
NC
X2
D3
DV
121314
VSSD0NC
OE
10
11
D1
100K
VREF
X1
R01X
58964
7
0.1uF/50V
C02H
RY-HOOK
ZNR01
R19H
BSP351L
R15H
10K
R18H
2.7 1/2W
2.7 1/2W
BD
C05H
100V
0.01uF
G6A-234P,5V
HR93F,5V
8
4
R12H
LM358
OP-AMP
1K
-
+
6
5
5V
ZD04H~ZD05H
CN-PHONE
3.9V, 1/2W
1uF DC250V
C01H
ZD05H
ZD04H
R01H
6.2K/1W
RST
DE
BD
100K
R07H
4.7K
R03H
7.5K
C03H
22uF
50V
+
R14H
R13H
750
270
ZD02H
C08H
7
50V
0.1uF
0.15uF
63V
C11H
ZD03H
5V
R05H
27
Q03M
2222A
2
27
3
R06H
63V
Q01M
C3198Y
R01M
4.7K
C09H
1uF
+
1N4004
D01M
100K
R16H
TRANS
T1
1/4W
6.2K
R02H
ZD01H
1.5KE56A
1N4004
D01H~D04H
KTC2016
PC01H
1
R04H
4
TLP621BL
5V
Q02M
RA3
2K
0.1uF
C02X
16
OSC215OSC1
14
4
5
VSS
MCLR3T0CLK
RB4
9
RB3
13
6
RB0
RB5
10
RB6
11
12
8
7
RB2
RB1
RB7
VDD
OP2
10K
DE
DSO
5V
IC-DTMF
(ST9170)
HT9170B
VN
VDD
18
GS
RI
17
50V
51K
R17H
2
3
5V
R01B
1M
Q0Q3Q2
Q1
50V
CST-4.00MGW
OSC01B
C01X
0.01uF
16V
MICOM
RA1
18
17
RA0
1
RA2
2
PIC16C54CR
C04H
1uF
R08H
5V
OP1
10K
TX
RX
S/W(FORCE)
Operation
Defrost
Timer
Sleep
9
13
14
12
16
15
11
10
17
22
20 19
21
18
23
24
63
4
1
3
2
64
5
6
8
7
59
61
60
62
58
57
40
31
25
28 27 26
30 29
36
35
37
33
38
39
34
32
50
53 54 55
51 52
56
45
46
48
47
49
44
41
42
43
DISPLAY
R02E,20
UPD780023AGC-C
ZBF503D
ZD02D
VOLTAGE GND
BZX55C11
2
1
6
8
745
3
HVB
LED1
LED2
LED3
LED4
C01A
RECEIVER
104
Vout
GND
Vcc
R02G 220
R03G 220
R04G 220
R01G 220
AC PART
5V
25V
10V SD
R02D
DC LOW
1/6W
20K
S78DL05L 1W
103
C08D
+
220
C09D
I
O
7805
IC04D
25V
103
C07D
12V
25V SD
C06D
330
L1
IC01G
KID65004AF
HVB OUT
12V
33
1
1
3
2
1
2
2
1
2
1
322
CN-CONT
CN-12V
1
1
3
2
3
CN-HVB
Option
1
2
5V
R11H~R14H
20K 2012
receiver
+
6 66
8
7
8
7
8
7
2
1
5
4
3
4
5
1
2
33
4
251
5V
9
5V
10V
C02L
220uF SD
5V
R11H
OJ1H
OJ2H
OJ3H
8
7
6
5
EEPROM
Vcc
SCL
SDA
WP
G
123
A0
A14A2
CAT24WC01J
R14H
R13H
R12H
20K
R01P
2012
R02P
20K
2012
OJ4H
5V
8
20K
R02F
7
3
4
5
2
6
1
5V
Vss0
Vdd0
C04C
103
Ad1dV
NEC
TERMINAL BOARD
STO2D-200
SD01D
TNY266P
DC HIGH
VOLTAGE GND
D
5
4
1
IC02D
DC HIGH
VOLTAGE GND
TLP421(V4 BL)
C05D
472M
32
104
50V
C02D
EN
4
S
2
BP
1
D07D
UG2D
470/35V/SD
C03D
681
RY-4WAY
1/6W
R03D
39
+
C04D
1
8
5V
CN-ACDC
CN-ACDC2
INT
3
6
2
7
12V
SMPS
5
4
4
5
7
2
6
3
RY-FAN
RY-COMP
4.7uF
VOLTAGE GND
TLP421(V4 BL)
450V/SD
IC01D
DC LOW
IC03D
LL4148
D08D
VOLTAGE GND
1
4
DC HIGH
2
3
1/4W
300K
R06D
NTC SCK-102
+
C01D
INT
INDOOR FAN12V
8
1
12V
12V
R05D
1/4W
300K
3216
5V
27k
1/6W
R04D
D05D
1N4007
IN4007
D01C
D01A
IN4007
R01E
1K
1%
OR1H
F1
OR5H
Med
L2
10nH
Hi
OR6H OR3H
O/L
OR2H
F2
OR4H
Low
C02C
220uF
10V/SD
5V
+
5V
R21H
INT
4WAY
5V
FAN
COMP
R22H
R25H
R26H
R24H
R23H
R21H~R26H
12.1K, 1%
5V
X2
RESET
AVdd
AVref
ssV
A
C03C
103
INT1X1Vss1
INT0
B
Z
CSTS0800MG03-T2
CRTL8.00MSOT
OSC01B
5V
R01B
1M
Q01C
2SC5343
KTC3198-Y
33
6.2K
12.1K
INDOOR FAN
12V
1%
R05H
10K
11
2 2
3.6V
2
1
C01A
3
50V
0.01
R02A,20K
R04H
R02H
KIA7036P
S7136
IC01A
5V
5V
680pF/50V
C01L
R01L 5.1K
R02L,1K
R07D
56K
R06D
12K
BZ01E
5V
receiver
PKM13EPY-4002
5V
INT
44
CN-TH
SM1L43
TRAICS
RY-FAN
250V/T2A
G5N-1A(G5NB-1A)
RY-4WAY
G5N-1A(G5NB-1A)
TVR10561
METAL FILM
METAL FILM
47nM/275V/435D
100nM/275V/436D
4
4
3
3
1/4W
560
R04J
INDOOR FAN
IN4007
D01D
IN4007
D01B
C02J
12V
IC01J
TR01J
TLP762JF
15mH/1A
NF01J
C01J
R02J
100,1/2W
T1
FUSE
ZNR01J
4
5
3
1
2
T2
R03J
680
1/2W
11
13
RY-COMP
G4A-1A-E-LG
12
15
1
4
3
1
1
CN-TAB1
120, 1/2W
RY-COMP
100nF/275V/436D
METAL FILM
C03J
ZNR02J
TVR10561
1
12V
2
6
8
R01J
231
231
CN-MOTOR
12V
RY-COMP
1
3
6
9
5
2
4
SH-CAPACITOR
FAN
MOTOR
INDOOR
PIPE-TH
ROOM-TH
+
123
3.6V
1
1(L)
1
N
L
AC220~240V
50/60Hz
COMPRESSOR
524
2(N)
4
3
OUTDOOR
FAN MOTOR
4-WAY
PK
16
(UP/DOWN)
STEPPING MOTOR
9
KID65004AF
DC PART
CN-U/D
3
2
YLORRD
4
5
PK
BL
1
324
5
1
COMP
HVB OUT
12V
INDOOR FAN
3
2
8
1
4
5
IC01M
6
7
1
STEPPING MOTOR
(LEFT/RIGHT)
BL
2
2
Option
Q03T
C104S
Q02T
A104S
4WAY
9
8
121314 1011
43
7
5
6
FAN
2
15
KID65004AF
IC02M
CN-L/R
RD
545
4
OR
1
1
3
3
YL
12V
1K
5V
C03T
102
R01T
102
A104S
Q04T
Q01T
C104S
5V
C02T
22
104
1N4148
D01T
11
CN-TEL
5V
C01T
33
TELE (OPTION)
2
1
Electric Control Device
Heat Pump Model(LED TYPE)
Page 34
34 Room Air Conditioner
Schematic Diagram
HVB TYPE(PLASMA)
Page 35
Service Manual 35
Wiring Diagram
Schematic Diagram
Indoor Unit
Outdoor Unit
MOTOR
OR
RD BK
BK BK BK BK
BK BK BK BK
POWER
GN/YL
GN/YL
BR(BK/Plained)
BL(WH/Ribbed)
BK
YL
SH-CAPA
T/BOARD
T-BLOCK
RY-4WAY
RY-FAN
CN-MOTOR
THERMISTOR
STEP
MOTOR
CN-ACDC1
CN-ACDC2
CN-THCN-U/DCN-L/RCN-HVBCN-12V
CN-DISP
DISPLAY PWB ASM.
P/No : 3854A20238H
CN-CONT
TRIAC
AC PWB ASM. DC PWB ASM.
CN-TAB
RY-COMP
TO OUTDOOR UNIT
43
1(L)
BR
BR
BL
BK
RD
GN/YL
2(N)
3 4
FUSE
250V T2A
STEP
MOTOR
H.V.
ASM.
S/W1
S/W2
AIR CLEAN (PLASMA)
Page 36
36 Room Air Conditioner
Schematic Diagram
Components Location
MAIN P.W.B ASSEMBLY (AC PART)
HEAT PUMP MODEL
MAIN P.W.B ASSEMBLY (DC PART)
TOP VIEW BOTTOM VIEW
Page 37
Service Manual 37
Schematic Diagram
DISPLAY ASSEMBLY
– 6871A20476(6871A90476)
TOP VIEW
BOTTOM VIEW
Page 38
38 Room Air Conditioner
Troubleshooting Guide
Troubleshooting Guide
INDOOR UNIT OUTDOOR UNIT
INDOOR UNIT OUTDOOR UNIT
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
COMPRESSOR
ACCUMU LATOR
GAS SIDE
GAS SIDE
3-WAY VALVE
LIQUID SIDE
LIQUID SIDE
3-WAY VALVE
CAPILLARY TUBE
CAPILLARY TUBE
CHECK VALVE
(Heating Model only)
COOLING HEATING
REVERSING VALVE (Heating Model Only)
(1) Cooling Only Models
Refrigeration Cycle Diagram
(2) Cooling & Heating Models
Page 39
Service Manual 39
Troubleshooting Guide
CAUTION:* Capicity is based on standard length and maximum allowance length is the basis of reliability. * Oil trap should be installed per 5~7 meters.
Outdoor unit
Indoor unit
A
B
In case more than 5m
7k~14k
3/8"(Ø9.52) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 7 15 20 1/2"(Ø12.7) 1/4"(Ø6.35) 4 or 7.5 15 30 20
18k~28k 5/8"(Ø15.88) 1/4"(Ø6.35) 4 or 7.5 15 30 20
5/8"(Ø15.88) 3/8"(Ø9.52) 4 or 7.5 15 30 30
30k~38k
5/8"(Ø15.88) 3/8"(Ø9.52) 7.5 15 30 30 3/4"(Ø19.05) 3/8"(Ø9.52) 7.5 15 30 50
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Additional
Refrigerant
(g/m)
Max.
Length
A (m)
Max.
Elevation
B (m)
Standard
Length
(m)
Pipe Length and the Elevation
Oil trap
Indoor unit
A
Outdoor unit
B
Page 40
40 Room Air Conditioner
Troubleshooting Guide
2-way, 3-way Valve
2-way Valve (Liquid Side) 3-way Valve (Gas Side)
Shaft position Shaft position Service port
Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
Open Closed Open
(counter-clockwise) (clockwise) (push-pin or with
vacumm pump)
Open Open Closed
(with valve cap) (with valve cap) (with cap)
Closed Open Open
(clockwise) (counter-clockwise) (connected manifold
gauge)
Open Open Open
(with charging
cylinder)
Open Open Open
(with charging
cylinder)
Open Open
Open Open
Works
Shipping
Air purging (Installation)
Operation
Pumping down (Transfering)
Evacuation (Servicing)
Gas charging (Servicing)
Pressure check (Servicing)
Gas releasing (Servicing)
1.
2.
3.
4.
5.
6.
Valve cap
Open position Closed position
Pin
Service port
Service port cap
To outdoor unit
Flare nut
To piping connection
To outdoor unit
Hexagonal wrench (4mm)
Open position Closed position
To piping connection
Flare nut
Open
(with charging cylinder)
Open
(with charging cylinder)
Page 41
Service Manual 41
Troubleshooting Guide
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the open position.
– Remove the valve stem caps and confirm that
the valve stems are in the raised position.
– Be sure to use a hexagonal wrench to operate
the valve stems.
(2) Operate the unit for 10 to 15 minutes.
(3) Stop operation and wait for 3 minutes, then
connect the charge set to the service port of the 3-way valve.
– Connect the charge hose with the push pin to
the service port.
(4) Air purging of the charge hose.
– Open the low-pressure valve on the charge set
slightly to air purge from the charge hose.
(5) Set the 2-way valve to the closed position.
(6) Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates 1kg/cm2g.
(7) Immediately set the 3-way valve to the closed
position.
– Do this quickly so that the gauge ends up indi-
cating 3 to 5kg/cm2g.
(8) Disconnect the charge set, and mount the 2-
way and 3-way valves stem nuts and the ser­vice port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
Lo
Closed
Purge the air
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way valve
3-Way valve
CLOSE
Pumping Down
CAUTION: Do not use the existing charge set for R-22.
It is necessary to use new charge set for R­410A. The pressure of R-410A is 1.6 times higher than that of R-22. Thus, the high pres­sure side gauge of charge set should be used higher pressure gauge of 50kg/cm2range.
Page 42
42 Room Air Conditioner
Troubleshooting Guide
Balance Refrigerant of the 3-way Valve
(Gas leakage)
Procedure
(1) Confirm that both the 2-way and 3-way valves
are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
Leave the valve on the charge set closed. Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi­cates 0 kg/cm2G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running is higher than 1 kg/cm2G), discharge the refrig­erant until the gauge indicates 0.5 to 1 kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will also be discharged.
Lo
Open
Open
3-Way valve
3-Way valve
Gas side
CLOSEOPEN
Outdoor unit
Liquid side
Indoor unit
Page 43
Service Manual 43
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approxima­tely 5 minutes after turning off the vacuum pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way valve
CLOSE
OPEN
CAUTION:
Use vacuum pump equipped with check value applied to be prevented from flowing back­ward.
Page 44
44 Room Air Conditioner
Troubleshooting Guide
Gas Charging
(After Evacuation)
Procedure
(1) Connect the charge hose to the charging
cylinder.
– Connect the charge hose which you dis-con-
nected from the vacuum pump to the valve at the bottom of the cylinder.
– If you are using a gas cylinder, also use a
scale and reverse the cylinder so that the sys­tem can be charged with liquid.
(2) Purge the air from the charge hose.
– Open the valve at the bottom of the cylinder
and press the check valve on the charge set to purge the air. (Be careful of the liquid refriger­ant). The procedure is the same if using a gas cylinder.
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
– If the system can not be charged with the spec-
ified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not suffi­cient, wait approximately 1 minute and then repeat the procedure (pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valves service port.
– Stopping partway will allow the gas to be dis-
charged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose.
(5) Mount the valve stem nuts and the service
port nut.
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage.
CAUTION:
This unit is charged with R-410A. Pay attention not to charge R-22.
\
This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner.
Indoor unit
Check valve
Charging cylinder
Lo
(1)
OPEN
Liquid side
Gas side
CLOSE
3-Way
Open
valve
Open
3-Way valve
Outdoor unit
Page 45
Service Manual 45
Troubleshooting Guide
Additional gas charging
(Gas leakage)
When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc­tion pressure.
Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem­perature. Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚C)
Indoor Temp. (˚C)
12 11 10
9 8 7 6 5
5 10152025303540
50˚C
40˚C
30˚C
20˚C 10˚C
0˚C
P = 3 + 0.0123 x Tout
1.5
+ 0.8 x Tin
0.5
Where, P : Suction Pressure(kg/cm
2
.
g) Tout : Outdoor Temperature(˚C) Tin : Indoor Temperature(˚C)
Operating Suction Pressure
(According to Indoor & Outdoor Temperature)
Page 46
46 Room Air Conditioner
Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. 0°C Current : less than 80% of
rated current
Temp. difference : approx. 8°C Current : less than 80% of
rated current
Temp. difference : less than 8°C Current : over the reated
current
Temp. difference : over 8°C
Operating Current
All amount of refrigerant leaked out. Check refrigeration cycle.
Refrigerant leakege
Clog of refrigeration cycle Defective compressor
Excessive amount of refrigerant
Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem­perature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5 kg/cm2G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
NOTICE
NOTICE
Suction pressure Temperature
(Compared with (Compared with Cause of Trouble Description
the normal value) the normal valve)
Defective compressor Current is low. Defective 4-way reverse valve
Excessive amount of High pressure does not quickly
Normal refrigerant rise at the beginning of
operation.
Insufficient amount of Current is low.
Lower Higher refrigerant (Leakage)
Clogging Current is low.
High
Higher
Cycle Parts
Page 47
Service Manual 47
Troubleshooting Guide
Electronic Parts
Product does not operate at all.
(* Refer to Electronic Control Device drawing and Schematic diagram.)
Turn off Main Power
Turn on Main Power
Does "beeping" sound is made from the Indoor Unit?
Primarily, the operating condition of Micom is OK.
Check the voltage of power(About AC 220V, 60Hz)
(About AC 220/240V, 50Hz)
Main power's voltage
Voltage applied to the unit
Connecting method of Indoor/Outdoor connecting
cable
Check PWB Assembly
- Fuse
- Pattern damage
- Varistor(ZNR01J)
Check the connection housing for contacting
Connector related to CN-TAB1, RY-COMP NO.3
Connector related to CN-MOTOR
Connector contacting of Outdoor Fan/Compressor
Display PCB Assembly Check
Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector
Main PCB Board Operation Check
Items
SMPS Transformer (Indoor unit)
- Input Voltage
- Output Voltage(ZD02D)
IC04D(7805) Output (Indoor/Outdoor unit)
IC01A(KIA7036, Reset IC) X01(8MHz)
Replace Trans
Replace IC04D
Replace faulty parts
- About AC220V/240V±10% - Check the power voltage
- About DC12V
DC +5V
Voltage of Micom No. 2,
(DC +4.5V over) and Soldering condition.
Content Remedy
NO
YES
(After 10 seconds)
Page 48
48 Room Air Conditioner
Troubleshooting Guide
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote control
Cause by the remote control
When the mark( ) is displayed in LCD screen, replace battery.
Check the contact of CN-DISP1 connector.
When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller. (When operated in the Sleeping Mode, the wind speed is set to the low speed by force.)
Check Display PCB Assembly
- Voltage between CN DISP1 - : DC +5V
Check the connecting circuit between the remote controller MICOM (No. ) - R17(2) - IR LED - TR - R16(2.2K).
Check point
Check the connecting circuit between CN-DIS1 ­R01L(5.1k) - C01L(680pF) - MICOM PIN
Check Receiver Assembly
Page 49
Service Manual 49
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the remote controller is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor Fan is stopped.
Check the related circuit of RY-FAN.
Check the indoor temperature sensor is disconnected or not(About 10k / at 25°C).
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor.
Check the "open" or "short" of conmecting wires between indoor and outdoor.
Check Relay(RY - COMP) for driving compressor.
When the power(About AC220V/240V) is applied to the connecting wire terminal support transferred to compressor, PWB Assembly is normal.
Check the circuit related to the relay.
Check point COMP ON COMP OFF
Between Micom(No.
DC5V DC0V
62) and GND
Between IC01M(No. 14) Below DC 1V
About DC12V
and GND (app)
Page 50
50 Room Air Conditioner
Troubleshooting Guide
Check the TRIAC high speed operation by remote control.
(The Indoor Fan Motor is connected)
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Turn ON Main Power
Check the related circuit of indoor Fan Motor.
The pin NO 63 of Micom, and the part for driving TRIAC(the input and output signal of IC01M, PIN NO 7, 10)
Check the pattern
Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
When indoor Fan does not operate.
The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.
About AC 180V over About AC 50V over
TRIAC is not damaged TRIAC Check
Page 51
Service Manual 51
Troubleshooting Guide
Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with hands Normal
Check the connecting condition of CN-U/D Connector
Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver
When Vertical Louver does not operate.
Check the operating circuit of the Vertical Louver
Confirm that there is DC +12V between pin (RED) of CN-U/D and
GND.
Confirm that there is a soldering short at following terminals.
- Between , , and of MICOM
- Between , , and of IC01M
- Between , , and of IC01M
60 61 62 63
Page 52
52 Room Air Conditioner
Troubleshooting Guide
When Heating does not operate
Operate Heating Mode( ) by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
Check the related circuit of RY-4WAY
Check the indoor room temperature is disconnected or not (about 10K/at 25°C).
Check the indoor pipe temperature is disconnected or not (about
5K/at 25°C).
Turn ON Main Power
Check the DC voltage on the PWB ASSEMBLY
The details of check are as followings
Check point
Between Micom
(NO.59) and GND
Between IC01M
(NO.11) and GND
Comp ON
DC 5V
Below DC 1V
Comp OFF
DC 0V
About DC
12V
Check point
Between Micom
(NO.51) and GND
Between IC02M
(NO.11) and GND
4 way ON
DC 5V
Below DC 1V
4 way OFF
DC 0V
About DC 12V
Check point
Between Micom
(NO.53) and GND
Between IC02M
(NO.12) and GND
Fan ON
DC 5V
Below DC 1V
Fan OFF
DC 0V
About DC 12V
Comp Relay.
4 way Relay
Outdoor fan Relay
Page 53
Service Manual 53
Troubleshooting Guide
Turn off Main Power
Check the electrical wiring diagram of outdoor side.
Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor, 4 way.
Check the "open" or "short" of connecting wires between indoor and outdoor.
Page 54
54 Room Air Conditioner
Exploded View
Exploded View
346810
146811
354212
131410
359011
342800
159901
268712
159830
135311
135312
267110
249951
733010
152313
135314
152302
35211B
135516
352150
266090
268714-1
268714-2
W6640
263230
264110
Indoor Unit
Page 55
Service Manual 55
Exploded View
554031
437212
435511
W0CZZ
552202
567502
552116
552201
554160
561410
552111
550140
552203-1
552203-2
430410
447910
649950
552102-2
552102-1
437210
435301
559010
546810
Outdoor Unit
Page 56
56 Room Air Conditioner
Replacement Parts List
Replacement Parts List
Parts List (Indoor)
LOCATION
DESCRIPTION
PART No.
REMARKS
No.
131410 CHASSIS ASSEMBLY 3141A20006A 3141A20006A 3141A20006A R 135311 GRILLE ASSEMBLY,DISCHARGE(INDOOR) 3531A10232T 3531A10232T 3531A10234P R 135312 GRILLE ASSEMBLY,FRONT(INDOOR) 3531A20225B 3531A20225B 3531A10174Z R 135314 GRILLE ASSEMBLY,INLET SUB 3531A20226B 3531A20226B 3531A10273A R 135516 COVER ASSEMBLY,MOTOR 3551A20050H 3551A20050H 3551A20050A R 146811 MOTOR ASSEMBLY,STEP 4681A20055A 4681A20055A 4681A20055A R 152302 FILTER(MECH),A/C 5230A10005C 5230A10005C 5230A20014B R 152313 FILTER ASSEMBLY,DEODORIZER - - - R 159830 AIR CLEANER ASSEMBLY - - - R 159901 VANE,HORIZONTAL 5990A10005A 5990A10005A 5990A20007A R 249951 CONTROL BOX ASSEMBLY,INDOOR 4995A90257R 4995A90257B 4995A90258B R 263230 THERMISTOR ASSEMBLY 6323A20004K 6323A20004K 6323A20004K R 264110 POWER CORD ASSEMBLY 6411A20026D 6411A20026D 6411A20026A R 266090 H.V ASSEMBLY - - - R 267110 REMOTE CONTROLLER ASSEMBLY 6711A90023C 6711A90023C 6711A90023C R
268712 PWB(PCB) ASSEMBLY,DISPLAY 6871A90476C 6871A90476C 6871A90476C R 268714-1 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20272R 6871A20272A 6871A20272A R 268714-2 PWB(PCB) ASSEMBLY,MAIN(DC) 6871A20310B 6871A20310G 6871A20309F R
342800 BEARING 4280A20004B 4280A20004B 4280A20004B R
346810 MOTOR ASSEMBLY,INDOOR 4681A20062N 4681A20062L 4681A20048R R
35211B TUBE ASSEMBLY,TUBING 5211A21046R 5211A21046R 5211A21046S R
352150 HOSE ASSEMBLY,DRAIN 5251AR2575F 5251AR2575F 5251AR2575F R
354212 EVAPORATOR ASSEMBLY,FINAL 5421A10040A 5421A10040A 5421A20087X R
359011 FAN ASSEMBLY,CROSS FLOW 5901A20007E 5901A20007E 5901A20007D R
733010 PLATE ASSEMBLY,INSTALL 3301A10003A 3301A10003A 1H00843A R
W0CZZ CAPACITOR,DRAWING 3H01487A 3H01487A 3H01487A R
W6640 PWB(PCB) ASSEMBLY,MAIN(AC) 6871A20283A 6871A20283A 6871A20283A R
AS-H076QGA2 AS-H096QGA2 AS-H126RGA2
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Page 57
Service Manual 57
Replacement Parts List
Parts List (Outdoor)
LOCATION
DESCRIPTION
PART No.
REMARKS
No.
430410 BASE ASSEMBLY,OUTDOOR 3041A20016A 3041A20016A 3041A20016A R 435511 COVER ASSY,CONTROL(OUTDOOR) 3551A30023Q 3551A30023Q 3551A30023Q R 437210 PANEL ASSEMBLY,FRONT(OUTDOOR) 3720A10171A 3720A10171A 3720A10171A R 437212 PANEL ASSY,REAR(OUTDOOR) 3720A10172A 3720A10172A 3720A10172A R 447910 BARRIER ASSY,OUTDOOR 4790A10025B 4790A10025B 4790A10025B R 546810 MOTOR ASSEMBLY,OUTDOOR 4681A20121A 4681A20121A 4681A20121A R
550140 ISOLATOR,COMP 4H00982E 4H00982E 4H00982E R 552102-1 TUBE,CAPILLARY BEND 5210A21238R 5210A21238M 5210A20897H R 552102-2 TUBE,CAPILLARY BEND - - 5424AR7208Q R
552111 TUBE ASSEMBLY,CAPILLARY 5211A21143C 5211A21143B 5211A30708A R
552116 TUBE ASSEMBLY,REVERSING 5211A20188T 5211A20188P 5211A20188R R
552201 VALVE,CHECK - - 5220AR7182A R
552202 VALVE,REVERSING 5220AR3228J 5220AR3228J 5220AR3228J R 552203-1 VALVE,SERVICE 2H02479P 2H02479P 2H02479P R 552203-2 VALVE,SERVICE 5220A20001Q 5220A20001Q 5220A20006F R
554031 CONDENSER ASSEMBLY,BENT 5403A20059B 5403A20059B 5403A20045Z R
554160 COMPRESSOR SET 2520UZBP2AA 2520UGAP2HB 2520UGHP2CA R
559010 FAN ASSEMBLY,PROPELLER 5900AR1266C 5900AR1266C 5900AR1266C R
561410 COIL ASSEMBLY,REVERSING VALVE 6141A20017A 6141A20017A 6141A20017A R
567502 O.L.P 6750U-L023A 6750U-L061A 6750U-L076A R
649950 CONTROL BOX ASSEMBLY,OUTDOOR 4995A10032B 4995A10032J 4995A10032K R
W0CZZ CAPACITOR,DRAWING 6120AR2194H 2H01451P 2H01451T R
435301 GRILLE,DISCHARGE 3530A10059G 3530A10059G 3530A10059G R
AS-H076QGA2 AS-H096QGA2 AS-H126RGA2
NOTE) *Please ensure GCSC since these parts may be changed depending upon the buyer's request.
(GCSC WEBSITE http://biz.LGservice.com)
Page 58
58 Room Air Conditioner
Memo
Page 59
P/No.: 3828A20462A
January, 2004
Printed in Korea
Loading...