Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
CEILING CASSETTE - 1 WAY
Original instruction [Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu,
Changwon-si, Gyeongsangnam-do, KOREA
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
MFL68686521
Rev.00_052219
www.lg.com
Copyright © 2017 - 2019 LG Electronics Inc. All Rights Reserved.
Page 2
Table of Contents
TABLE OF CONTENTS
3 INSTALLATION PARTS
4 SAFETY PRECAUTIONS
10 INSTALLATION
10 Selection of the Best Location
12 Ceiling Dimension and Hanging Bolt Location
13 Wiring Connection
14 Installation of Decoration Panel (Panel Type)
15 Installation of Decoration Panel (Grille Type)
16 Drain Piping
17 DIP Switch Setting
18 Group Control Setting
23 Model Designation
23 Airborne Noise Emission
23 Limiting concentration
2 Indoor Unit
Page 3
Installation Parts
Panel type Grille type
Air Intake
Installation Parts
ENGLISH
Air Outlet
Air Outlet
Installation Tool
Name
Quantity
Shape
Drain hose
1 EA
Name
Quantity
Shape
Air
Intake
Wired Remote Controller
Clamp metal
2 EA
Paper pattern for installation
(Accessory)
Washer for
hanging bracket
1 EA
8 EA
Air
Intake
Plastic band
4 EA
Installation and Owner's manual
Wired Remote Controller
Insulation for
for gas pipe
for liquid pipe
1 EA
(Accessory)
fitting
1 SET
• Screws for fixing panels are attached to decoration panel.
Installation Manual 3
Page 4
Safety Precautions
Safety Precautions
The following symbols are displayed on indoor and outdoor units.
Read the precautions in this manual carefully before operating the unit.
This symbol indicates that the Operation Manual should be read carefully.
To prevent injury to the user or other people and property damage, the following instructions must be followed. n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
This appliance is filled with flammable refrigerant (R32)
This symbol indicates that a service personnel should be handling this equipment with reference to the Installation Manual.
!
WARNING
!
CAUTION
n Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Be sure not to do.
Be sure to follow the instruction.
!
WARNING
Installation
• Compliance with national gas regulations shall be observed.
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or
electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
4 Indoor Unit
Page 5
Safety Precautions
ENGLISH
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case
edges and the fins on the condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing
property damage, product failure, and personal injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard" and "Interior Wire Regulations" and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is
performed improperly, electric shock or fire may result.
• Always intstall a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. (for R32)
• The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
• Keep any required ventilation openings clear of obstruction.
• Mechanical connections shall be accessible for maintenance purposes.
• To prevent the mixing of different types of refrigerants, be sure to check the type of refrigerant used in the outdoor unit.
Operation
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
Installation Manual 5
Page 6
Safety Precautions
• Take care to ensure that power cable could not be pulled out or damaged during operation.
- There is risk of fire or electric shock.
• Do not place anything on the power cable.
- There is risk of fire or electric shock.
• Do not plug or unplug the power supply plug during operation.
- There is risk of fire or electric shock.
• Do not touch(operate) the product with wet hands.
- There is risk of fire or electrical shock.
• Do not place a heater or other appliances near the power cable.
- There is risk of fire and electric shock.
• Do not allow water to run into electric parts.
- There is risk of fire, failure of the product, or electric shock.
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
• Do not use the product in a tightly closed space for a long time.
- Oxygen deficiency could occur.
• When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
- Do not use the telephone or turn switches on or off. There is risk of
explosion or fire.
• If strange sounds, smell or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
- There is risk of property damage, failure of product, or electric shock.
• Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Ventilate the product from time to time when operating it together with a stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the product.
- There is risk of electric shock.
6 Indoor Unit
Page 7
Safety Precautions
ENGLISH
• When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
- There is risk of product damage or failure, or unintended operation.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• When mechanical connectors are reused indoors, sealing parts shall be renewed. (for R32)
• When flared joints are reused indoors, the flare part shall be re­fabricated. (for R32)
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• Do not pierce or burn refrigerant cycle part.
• Be aware that refrigerants may not contain an odour.
!
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the
condenser and evaporator fins, could cause product malfunction or inefficient operation.
Installation Manual 7
Page 8
Safety Precautions
• Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry­accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification. (for R32)
• The appliance shall be stored so as to prevent mechanical damage from occurring.
• Refrigerant tubing shall be protected or enclosed to avoid damage.
• Flexible refrigerant connectors (such as connecting lines between the indoor and outdoor unit) that may be displaced during normal operations shall be protected against mechanical damage.
• The installation of pipe-work shall be kept to a minimum.
• Pipe-work shall be protected from physical damage.
• A brazed, welded, or mechanical connection shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts.
• Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
Operation
• Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
- This could harm to your health.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow.
- It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic parts of
the product.
• Do not touch the metal parts of the product when removing the air filter. They are very sharp!
- There is risk of personal injury.
• Do not step on or put anything on the product. (outdoor units)
- There is risk of personal injury and failure of product.
• Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
- A dirty filter reduces the efficiency of the air conditioner and could
cause product malfunction or damage.
8 Indoor Unit
Page 9
Safety Precautions
ENGLISH
• Do not insert hands or other objects through the air inlet or outlet while the product is operated.
- There are sharp and moving parts that could cause personal injury.
• Do not drink the water drained from the product.
- It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning or maintaining the product.
- Be careful and avoid personal injury.
• Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
- There is risk of fire or explosion.
• Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
- They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health hazards.
• Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. (for R32)
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Installation Manual 9
Page 10
Installation
Floor
Installation
Read completely, then follow step by step.
Selection of the Best Location
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must have the maintenance space.
20 ±3
CAUTION
!
Ceiling
Ceiling board
500 or more
1 000
or more
10 or more
Above 1 800
3 300 or less
Floor
Floor
Ceiling board
200 or more
500 or more
300 or less
Unit:mm
In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
NOTE
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.
Air conditioner
Take enough distance
Cooking table
Use the ventilation fan for smoke-collecting hood with sufficient capacity.
10 Indoor Unit
Page 11
Installation
Minimum floor area
(for R32)
- The appliance shall be installed, operated and stored in a room with a floor area larger than the minimum area.
- Use the graph of table to determine the minimum area.
ENGLISH
Amin (m2)
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant charge + additional refrigerant amount
- Amin : minimum area for installation
600
500
400
300
200
100
0
Floor location
m (kg) Amin (m
< 1.224
1.224
12.9
1.4 16.82
1.6 21.97
1.8 27.80
2 34.32
2.2 41.53
2.4 49.42
2.6 58.00
2.8 67.27
3 77.22
3.2 87.86
3.4 99.19
3.6 111.20
3.8 123.90
4 137.29
4.2 151.36
4.4 166.12
0 1.224 2 3 4 5 6 7 8
2
)
-
Floor location
m (kg) Amin (m
4.6 181.56
4.8 197.70
5 214.51
5.2 232.02
5.4 250.21
5.6 269.09
5.8 288.65
6 308.90
6.2 329.84
6.4 351.46
6.6 373.77
6.8 396.76
7 420.45
7.2 444.81
7.4 469.87
7.6 495.61
7.8 522.04
2
)
Wall mounted
m (kg) Amin (m
< 1.224
1.224
1.43
1.4 1.87
1.6 2.44
1.8 3.09
2 3.81
2.2 4.61
2.4 5.49
2.6 6.44
2.8 7.47
3 8.58
3.2 9.76
3.4 11.02
3.6 12.36
3.8 13.77
4 15.25
4.2 16.82
4.4 18.46
2
)
-
Wall mounted
m (kg) Amin (m
4.6 20.17
4.8 21.97
5 23.83
5.2 25.78
5.4 27.80
5.6 29.90
5.8 32.07
6 34.32
6.2 36.65
6.4 39.05
6.6 41.53
6.8 44.08
7 46.72
7.2 49.42
7.4 52.21
7.6 55.07
7.8 58.00
2
)
Ceiling Mounted
m (kg) Amin (m
< 1.224
1.224
0.956
1.4 1.25
1.6 1.63
1.8 2.07
2 2.55
2.2 3.09
2.4 3.68
2.6 4.31
2.8 5.00
3 5.74
3.2 6.54
3.4 7.38
3.6 8.27
3.8 9.22
4 10.21
4.2 11.26
4.4 12.36
2
)
-
Floor standing
Wall mounted
Ceiling mounted
m (kg)
Ceiling Mounted
m (kg) Amin (m
4.6 13.50
4.8 14.70
5 15.96
5.2 17.26
5.4 18.61
5.6 20.01
5.8 21.47
6 22.98
6.2 24.53
6.4 26.14
6.6 27.80
6.8 29.51
7 31.27
7.2 33.09
7.4 34.95
7.6 36.86
7.8 38.83
2
)
Installation Manual 11
Page 12
Installation
Ceiling Dimension and Hanging Bolt Location
• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
1 385(Ceiling opening)
1 285(Hanging bolt)
50
Ceiling
600
50
Level gauge
CAUTION
!
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
• Select and mark the position for fixing bolts and piping hole.
• Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10) Spring washer
(M10)
Keep the length of the bolt from the bracket to 40 mm
Flat washer for M10 (accessory)
Flat washer for M10
(accessory) Nut (W3/8 or M10)
Ceiling board
306
400 4040
600
400 4040
306
250
Paper model for installation
Adjust the same height
1 180
250
TT Chassis
1 065(Ceiling opening)
965(Hanging bolt)
50
860
TU Chassis
Ceiling
Air conditioner body
Set screw of paper model (4 pieces)
Open the ceiling board along the outer edge of the paper model
448
448
354
50
354
(Unit: mm)
Ceiling board
Ceiling board
466
(Hanging bolt)
(Ceiling opening)
466
(Hanging bolt)
(Ceiling opening)
70 mm
• The following parts are local purchasing.
• The following parts are local purchasing.
Hanging bolt - W 3/8 or M10
Hanging bolt - W 3/8 or M10
Nut - W 3/8 or M10
Nut - W 3/8 or M10
Spring washer - M10
Spring washer - M10
Plate washer - M10
Plate washer - M10
CAUTION
!
CAUTION
!
Tighten the nut and bolt to prevent unit from falling off.
• When mechanical connectors are reused indoors, sealing parts shall be renewed. (for R32)
• When flared joints are reused indoors, the flare part shall be re-fabricated. (for R32)
12 Indoor Unit
Page 13
Installation
ENGLISH
Wiring Connection
• Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.
Terminal Block Indoor
1(L) 2(N) 3 4
INDOOR
POWER INPUT
WARNING
!
Make sure that the screws of the terminal are free from looseness.
CAUTION
!
The Power cord connected to the unit should be selected according to the following specifications.
CAUTION
!
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 % of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
Terminal Block of outdoor unit
INTERNET
IDUSODU
A ----BABAB
DRY2DRY1
GND 12 V
Outdoor Unit
Installation Manual 13
Page 14
Installation
Installation of Decoration Panel (Panel Type)
The decoration panel has its installation direction.
Before installing the decoration panel, always remove the paper template.
1. Open the air outlet vane, and extract side covers.
2. Remove the air inlet panel from the decoration panel.
3.
Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel.
4. Arrange wires not to get caught between decoration panel and indoor unit.
5. Screw 7 fixing screws. (7, 9, 12 kBtu : 6 screws)
6. Connect the vane motor connector ,display connector and air inlet panel connector.
7. Install the air inlet panel (including the air filter) and side covers.
Air conditioner unit
Mesh
Control box cover
Plasma filter (applied only to plasma model)
Air inlet panel
Side cover
Decorative panel fixing screws (hexagon M6 screws) (tightening about 20 mm)
Decorative panel
Air outlet vane
CAUTION
!
Install certainly the decoration panel. Cool air leakage causes sweating. Waterdrops fall.
14 Indoor Unit
Good example
Fit the insulator (this part) and be careful for cool air leakage
Bad example
Air conditioner unit
Ceiling
board
Decoration panel
Air
Air conditioner unit
Cool air leakage
(no good)
Ceiling
board
Decoration panel
Page 15
Air conditioner unit
Ceiling
board
Decoration panel
Decoration panel
Fit the insulator (this part) and be careful for cool air leakage
Good example
Air
Cool air leakage
(no good)
Bad example
Ceiling
board
Air conditioner unit
Installation of Decoration Panel (Grille Type)
Installation
ENGLISH
The decoration panel has its installation direction.
Before installing the decoration panel, always remove the paper template.
1. Open the air outlet vane, and extract side covers.
2. Remove the air inlet grille from the decoration panel.
3.
Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel.
4. Arrange wires not to get caught between decoration panel and indoor unit.
5. Screw 7 fixing screws. (7, 9, 12 kBtu : 6 screws)
6. Connect the vane motor connector and display connector. (Plasma connector for plasma model)
7. Install the air inlet grille (including the air filter) and side covers.
Air conditioner unit
Mesh
Control box cover
Side cover
Plasma filter (applied only to plasma model)
Decorative panel fixing screws (hexagon M6 screws) (tightening about 20 mm)
Air inlet grille
Decorative panel
Air outlet vane
CAUTION
!
Install certainly the decoration panel. Cool air leakage causes sweating. Waterdrops fall.
Installation Manual 15
Page 16
Maintenance drain port
Upward routing not allowed
Pipe clamp
Indoor unit
1/50~1/100
Max 700 mm
Feed water
Drain pump
Drain pan
Flexible drain hose (accessory)
Main drain pipe
Glue the joint
Drain port
Drain hose connection Use the clip (accessory)
1/50~1/100 slope
Hanger
distance
Hanger bracket
Max 700 mm
Flexible drain hose
Insulation
Metal clamp
Max 300 mm
1~15 m
Installation
Drain Piping
• Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
• During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor unit is 32 mm.
Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings.
Be sure to install heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thickness more than 8 mm.
Drain Test
The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
• Feed water to the flexible drain hose and check the piping for leakage.
• Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
• When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
CAUTION
!
The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.
16 Indoor Unit
Page 17
DIP Switch Setting
1. Indoor Unit
Function Description Setting Off Setting On Default
Communication
SW1
Cycle
SW2
Group Control
SW3
Dry Contact Mode
SW4
Installation
SW5
Heater linkage
SW6
Ventilator linkage
SW7
Vane selection (Console)
Region selection
Etc.
SW8
CAUTION
!
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
N/A (Default)
N/A (Default)
Selection of Master or Slave
Selection of Dry Contact Mode
Fan continuous operation
N/A
Selection of Ventilator linkage
Selection of up/down side Vane
Selection tropical region
Spare
-
-
Master
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Continuous operation Removall
-
Linkage Removal
Up side + Down side Vane
General model
-
Up side Vane
Tropical model
-
-
Slave
Auto
-
-
Working
Only
-
Installation
ENGLISH
Off
Off
Off
Off
Off
Off
Off
Off
2. Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automatically with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
* Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch 7 segment
Outdoor Unit PCB Outdoor Unit DIP Switch
Installation Manual 17
Page 18
Installation
Group Control Setting
1. Group Control 1
n Wired remote controller 1 + Standard Indoor Units
or
Master Slave Slave Slave
LGAP Network System
GND Signal 12 V
Display Error Message
Master
Only connect serial signal and
GND lines between indoor units.
n DIP Switch in PCB
¿ Master Setting
- No. 3 Off
¡ Slave Setting
- No. 3 On
Indoor Unit DIP Switch
Some products have no DIP switch on PCB. It is possible to set indoor units to Master or Slave by using the wireless remote controller instead of DIP switch. For the details of the setting, please refer to the manual of the wireless remote controller.
1. It is possible to 16 indoor units(Max.) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote controller.
It is possible to control the other indoor units except the error units.
18 Indoor Unit
Page 19
h It is possible to connect indoor units since Feb. 2009. h It can be the cause of malfuctions when there is no setting of master and slave.
h In case of Group Control, it is possible to use following functions.
- Selection of operation, stop or mode
- Temperature setting and room temperature check
- Current time change
- Control of flow rate (High/Middle/Low)
- Reservation settings It is not possible to use some functions.
2. Group Control 2
n Wired remote controllers + Standard Indoor Units
Installation
ENGLISH
LGAP Network System
Slave
GND Signal 12 V
Master
Donʼt connect serial 12 V line
Display Error Message
MasterMaster
Master
or
Slave
h It is possible to control 16 indoor units(Max.) with the master wired remote control. h Other than those, it is same with the Group Control 1.
Installation Manual 19
Page 20
Installation
3. Group Control 3
n Mixture connection with indoor units and Fresh Air Intake Unit
LGAP Network System
Slave
Display Error Message
GND Signal 12 V
M
FAU
Master
Master
FAU
Slave
Display Error Message
or
Master
N
Master
h In case of connecting with standard indoor unit and Fresh Air Intake Unit, separate Fresh
Air Intake Unit with standard units. (N, M ≤ 16) (Because setting temperature are different.)
h Other than those, it is same with Group Control 1.
FAU
FAU FAU
Standard Standard
Standard
FAU
Standard
20 Indoor Unit
* FAU : Fresh Air Intake Unit Standard: Standard Indoor Unit
Page 21
4. 2 Remote Control
n Wired remote controller 2 + Indoor unit 1
Installation
ENGLISH
LGAP Network System
Slave
GND Signal 12 V
Master
Master
Display Error Message
Slave
Slave
or
Slave
1. It is possible to connect two wired remote controllers (Max.) with one indoor unit.
Set only one indoor unit to Master, set the others to Slave. Set only one wired remote controller to Master, set the others to Slave.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote controller.
6. There isnʼt limits of indoor unit function.
Installation Manual 21
Page 22
Installation
5. Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA + Wired remote controller
h
PZCWRCG3 cable used for connection
Master
PZCWRCG3
Master
CAUTION
!
1 EA Indoor unit 1 EA + Wired remote controller 2 EA
h
PZCWRC2 cable used for connection
Slave
PZCWRC2
Master Slave
• Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum cable usage.
22 Indoor Unit
Page 23
ARN U G24 DTT 4
Serial Number
Chassis Name Electrical Ratings
1 : 1Ø, 115 V, 60 Hz 6 : 1Ø, 220 - 240 V, 50 Hz 3 : 1Ø, 208/230 V, 60 Hz
2 : 1Ø, 220 V, 60 Hz 7 : 1Ø, 100 V, 50/60 Hz G :
1Ø, 220 - 240 V, 50 Hz/1Ø, 220 V, 60 Hz
Total Cooling Capacity in Btu/h EX) 5 000 Btu/h '05' 18 000 Btu/h '18'
Combination of Inverter Type and Cooling Only or Heat Pump N : AC Inverter and H/P V : AC Inverter and C/O U : DC Inverter and H/P and C/O
System with Indoor Unit using R32/R410A
LGETA : U Ex) URN
Combinations of functions A/B : Basic function L : Neo Plasma(Wall Mounted) C/D : Plasma(Ceiling Cassette) G : Low Static K : High Sensible Heat U : Floor Standing without Case SE/S8 - R : Mirror V : Silver B : Blue(ART COOL Type Panel Clolr) SF - E : Red V : Silver G : Gold 1 : Kiss (Photo changeable) Q : Console Z : Fresh Air Intake Unit
Model Designation
Airborne Noise Emission
The A-weighted sound pressure emitted by this product is below 70 dB. ** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a correlation between the emission and exposure levels, this cannot be used reliably to determine whether or not further precautions are required. Factor that influence the actual level of exposure of the workforce include the characteristics of the work room and the other sources of noise, i.e. the number of equipment and other adjacent processes and the length of time for which an operator exposed to the noise. Also, the permissible exposure level can vary from country to country. This information, however, will enable the user of the equipment to make a better evaluation of the hazard and risk.
Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall be described in the unit of kg/m
n Calculate refrigerant concentration
Refrigerant concentration =
Installation
3
(Freon gas weight per unit air volume) for facilitating calculation
Limiting concentration: 0.44 kg/m3(R410A)
Total amount of replenished refrigerant in refrigerant facility (kg)
Capacity of smallest room where indoor unit is installed (m
Installation Manual 23