LG ARNU12GTRB4 INSTALLATION MANUAL

INSTALLATION MANUAL
AIR CONDITIONER
ENGLISH
BAHASA INDONESIA
Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly.
Ceiling Cassette – 4Way
Original instruction
I.15.LEI24.03756.0817
www.lg.com
P/NO : MFL69440020
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
Table of Contents
TABLE OF CONTENTS
3 INSTALLATION PARTS 4 SAFETY PRECAUTIONS 6 INSTALLATION
6 Selection of the best location
7 Ceiling dimension and hanging bolt location
8 Wiring Connection
10 Installation of Decoration Panel
11 Drain Piping
13 DIP Switch Setting
14 Group Control Setting
19 Model Designation
19 Airborne Noise Emission
19 Limiting concentration
2 Indoor Unit
Installation Parts
Name
Quantity
Shape
for gas pipe
for liquid pipe
Clamp metal
2 EA
Insulation for
fitting
1 SET
Drain hose
1 EA
Clamp
(Tie Wrap)
8 EA
Washer for
hanging backet
4 EA
(Other)
• Paper pattern for installation
• Owner's manual
• Installation manual
Air Outlet
Installation Tool
Air
Intake
Wired Remote Controller(Optional)
Air Filter
Installation Parts
ENGLISH
• Screws for fixing panels are attached to decoration panel.
Installation Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
n Be sure to read before installing the air conditioner. n Be sure to observe the cautions specified here as they include important items related to safety. n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the
following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
n Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on
the condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
4 Indoor Unit
Safety Precautions
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage,
product failure, and personal injury.
• Use a vacuum pump or inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or oxygen, and do not use flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazrd.
• This equipment shall be provided with a supply conductor complying with the national regulation.
• Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
ENGLISH
Installation Manual 5
Unit:mm
Ceiling
Ceiling Board
Ceiling Board
300 or more
Above 2 500
4 000 or less
1 000
or more
500 or
more
500 or
more
300 or less
Floor
Installation
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
Installation
Read completely, then follow step by step.
Selection of the best location
• If the temperature might rise above 30 ℃ or the humidity might rise above RH 80%, attach the Dew­Protective kit or use another insulation to the indoor body. h Dew Protective kit is sold separately.
Use glass wool material or polyethylene foam and make sure at least 10mm thick.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must have the maintenance space.
h Please use an annexed sheet or the corrugated
6 Indoor Unit
CAUTION : In case that the unit is installed near the sea, the installation parts may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
h When using the bottom sheet, please use it cardboard on the bottom of packing as installation sheet.
after separating the installation sheet from packing of the product floor by using a knife etc as a picture below.