LG DELUXE HIGH WALL MINI SPLIT, 3828A30087L, LSC091PMA Installation Instructions Manual

DELUXE HIGH WALL MINI SPLIT
INSTALLATION INSTRUCTIONS
IMPORTANT! Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
CAUTION
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-22 causes frostbite burns.
• R-22 is toxic when burned.
NOTE TO INSTALLING DEALER:
The Owners Instructions and Warranty are to be given to the owner or prominently displayed near the indoor Furnace/Air Handler Unit.
P/No:3828A30087J
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water
damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid, level foundation for the
outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds:
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is higher than drifting snow.
Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
Turn the power OFF at the main power box(mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Installation or repairs made by unqualified persons can result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
WARNING
Special warnings
ENGLISH
INSTALLATION OVERVIEW
2
The following should be always observed for safety
....................
3
Installation of indoor, outdoor unit
................................................
4
Flaring work and connection of piping
...........................................
7
Connecting the cable between indoor unit and outdoor unit..10
Checking the drainage and Forming the piping
..................
12
Air purging
...............................
14
Panel Front Assembly
............
16
Test running
.............................
17
Installation guide mapFour type "A" screws & plastic
anchors
Connecting cable
Pipes: Gas side
....................
1/2"
Liquid side
.................1/4"
(Refer to page 4)
Insulation materialsAdditional drain pipe
Outer Diameter
......
15.5mm(
5
/
8")
Two type "B" screws
Level gaugeScrew driverElectric drillHole core drill Ø50mm(1.97")Horizontal meter
Flaring tool setSpecified torque wrenches
Liquid side - 1.8kg.m(13ft.lbs):9K,12K,18K
4.0kg.m(28.9ft.lbs):24K
Gas side - 5.5kg.m(39.8ft.lbs):9K, 12K
6.6kg.m(47.7ft.lbs):18K, 24K
(Refer to page 9)
Spanner......................Half union
A glass of waterScrew driver
Hexagonal wrench 4mm(5/32") ❏Gas-leak detectorVacuum pumpGauge manifold
Owner's manualThermometerHolder Remote Control
Installation
Requirements
Required Parts Required Tools
ENGLISH
THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY
3
Be sure to read "THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY" before installing the air conditioner.
Be sure to observe the cautions specified here as they include important items related to safety.
The indications and meanings are as follows.
After reading this instructions, be sure to keep it together with the owner's manual in a handy place on the customer's site.
WARNING
: Could lead to death, serious injury, etc.
CAUTION
: Could lead to serious injury in particular environments when operated
incorrectly.
WARNING
Incorrect installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or special installer.
Do not install it yourself (customer).
When installed in an insufficiently strong place, the unit could fall causing injury.
Install the unit securely in a place which can bear the weight of the unit.
Incorrect connection and fixing could cause fire.
Use the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to the terminal board connecting sections so the stress of the wires is not applied to the sections.
If the electrical part cover of the indoor unit and/or the service panel of the outdoor unit are not attached securely, it could result in a fire or electric shock due to dust, water, etc.
Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely.
The use of defective parts could cause an injury due to a fire, electric shock, the unit falling, etc.
Be sure to use the part provided or specified parts for the installation work.
Check that the refrigerant gas does not leak after installation is completed.
Incorrect installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water.
Perform the installation securely referring to the installation instruction.
If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
Perform electrical work according to the installation manual and be sure to use an exclusive circuit.
CAUTION
If there is a defect in the drainage/piping work, water could leak from the unit and household goods could get wet and be damaged.
Perform the drainage/piping work according to the installation instruction.
If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
Do not install the unit in a place where an inflammable gas leaks.
4
9K 1/2" 1/4"
7.5 7 15 20
(24.6ft)
(23ft) (50ft)
12K 1/2" 1/4"
7.5 7 15 20
(24.6ft)
(23ft) (50ft)
INSTALLATION OF INDOOR, OUTDOOR UNIT
Read completely, then follow step by step.
Select the best location
Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the unit.
Make sure that condensation drainage can be conveniently routed away.
Do not install near a doorway.
Ensure that the space around the left and right of the unit is more than 50cm(19.7”). The unit should be installed as high on the wall as possible, allowing a minimum of 10cm(3.9”) from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
If an awning is built over the unit to
prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
Ensure that the space around the back
and sides is more than 10cm(3.9”). The front of the unit should have more than 70cm(27.5”) of space.
Do not place animals and plants in the
path of the warm air.
Take the air conditioner weight into
account and select a place where noise and vibration are minimum.
Select a place so that the warm air and
noise from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Piping length and elevation
More than 10cm(3.9")
More than 50cm(19.7")
More than 2m(6.6ft)
More than 50cm(19.7")
More than 10cm(3.9") More than 10cm(3.9")
More than 60cm(24")
More than 60cm(24")
More than 70cm(28")
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B (m)
Standard
Length
(m)
In case more than 5m(16.4ft)
A
B
Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Oil trap should be installed every 5~7 meters(16.4~23ft).
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION
Install the indoor unit on the wall where the height from the floors more than 2m(6.6ft).
CAUTION
ENGLISH
5
Open panel front
First,Pull the grille bottom, then remove
screws(2 pieces), and close grille bottom again.
The moment of lifting the both lower parts
of panel front, you can hear sound this panel came out, In this time panel front is separated
After pull down this panel a bit, and
separate connecting wire with product.
Pipe hole
Panel Front
Connector
A
Cover pipe and cover side remove
Remove two screws(for fixing cover pipe)
Pull up the cover side of desired connecting
direction, then cover side is separated.
In case connecting direction is left or right, path
through the hole of cover side.
B
When connecting pipe path through rear wall, dont remove the hole.
Drain hose junction
Remove the rubber stopple of desired drain
direction.
As the following picture, Insert drain hose in the
handle of drain pan, and join drain hose and connecting hose.
C
rubber cap
Only one
desiring direction
Connecting
part
Adhesive
Drain hose
Preparing work for Installation
After removing the pipe hole, cut the burr for safety.
CAUTION
Plastic anchors
INSTALLATION GUIDE MAP
10mm(0.39")
INSTALLA TION GU
IN
STAIIATIO
N GU
IDE M
A
P
Put an Installation Guide Map on the desired surface.
Make a hole with diameter of 6mm(0.24") and depth of 30-35mm(1.18"~1.38") when piercing a screw point.
Drive the fore plastic anchors into drilled points.
Hang the hole of product at the upper screws. (In this time, Remove the map)
(Falling attention)
Check the fixed product with light power.
Look at suited horizon by horizontal meter on the horizontal setting line, and Fix lightly the map by adhesive tape.
Drill the piercing part for connecting pipe as diameter 50mm(1.97"). (In case of piercing rear surface)
Refer to No. 5 on this page when making a hole in the wall.
First, Drive the two points of the upper parts by screws. (Leave 10mm(0.39") for hanging product)
Drive the lower parts after facing the hole of product with plastic anchors, and fix completely the upper screws.
In case of nothing wrong in the matter, connect the pipe and the wire. (Installation manual reference)
Horizontality
I
N
S
T
A
L
L
A
T
I
O
N
G
U
I
D
E
M
A
P
Plastic anchors
IN
S
T
A
L
L
A
T
IO
N
G
U
ID
E
M
A
P
IN
STA
LLA
TIO
N
G
U
ID
E
M
A
P
Hanger hole
(Rear side of
product)
6
Preparing work for installation
Drill a hole in the wall
Drill the piping hole with a Ø50mm(1.97”) hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
5-7mm
(0.2~0.3")
Indoor
WALL
Outdoor
A
A
B
C
D
E
F
G
H
I
J
Sticking the installation guide map and fixing Indoor unit