LEYBOLD MAG W 1600 C, MAG 1600 C, MAG W 1600 CT, MAG 2000 C, MAG W 2000 C Operating Instructions Manual

...
Page 1
MAG 1600 C, CT MAG W 1600 C, CT MAG 2000 C, CT MAG W 2000 C, CT
Turbomolecular Pump with Magnetic Bearing
MAG.DRIVE L, L2
Electronic Frequency Converter
Cat. Nos. 894 14 /28 894 15 /29 894 16 /30 894 17 /31 857 24 /23
Operating Instructions
Vacuum Solutions Application Support Service
LEYBOLD VACUUM
GA 05.130/3.02
Page 2
Description
Contents
Page
1 Description . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 System overview . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Compatibility with pumped media . . . . . . . . . . 4
1.3 Design of the MAG . . . . . . . . . . . . . . . . . . . . 4
1.4 Function and design of the MAG.DRIVE . . . . 6
1.5 Standard specification . . . . . . . . . . . . . . . . . . 8
1.6 Technical data . . . . . . . . . . . . . . . . . . . . . . . . 9
1.7 Ordering information . . . . . . . . . . . . . . . . . . 10
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . 22
2.1 General safety information . . . . . . . . . . . . . . 22
2.2 Unpacking - storing - transportation . . . . . . . 22
2.3 Operating environment . . . . . . . . . . . . . . . . 23
2.4 Connecting the MAG
to the vacuum chamber . . . . . . . . . . . . . . . . 23
2.5 Connecting the backing pump . . . . . . . . . . . 28
2.6 Connecting the cooling water . . . . . . . . . . . . 28
2.7 Connecting the purge gas . . . . . . . . . . . . . . 30
2.8 Installing the MAG.DRIVE . . . . . . . . . . . . . . 32
2.8.1 Power supply connection X10 . . . . . . . . . . . 33
2.8.2 Pump connection . . . . . . . . . . . . . . . . . . . . . 33
2.8.3 Control plug X1 . . . . . . . . . . . . . . . . . . . . . . 36
2.8.4 Interface connector . . . . . . . . . . . . . . . . . . . 38
2.8.5 Connection X33 . . . . . . . . . . . . . . . . . . . . . . 39
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.1 Switching on . . . . . . . . . . . . . . . . . . . . . . . . 40
3.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.3 Switching off . . . . . . . . . . . . . . . . . . . . . . . . 41
4 Converter Control . . . . . . . . . . . . . . . . . . . 43
4.1 Functions of the front panel keys . . . . . . . . . 43
4.2 Operating display . . . . . . . . . . . . . . . . . . . . . 43
4.3 Remote control . . . . . . . . . . . . . . . . . . . . . . 44
4.4 Operating statuses . . . . . . . . . . . . . . . . . . . 46
4.5 Operating menu for the MAG.DRIVE L . . . . . 48
4.5.1 Basic menu . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.5.2 Settings converter . . . . . . . . . . . . . . . . . . . . 49
4.5.3 Settings pump . . . . . . . . . . . . . . . . . . . . . . . 50
4.5.4 Settings active magnetic bearing . . . . . . . . . 50
4.5.5 Settings temperature management system . 51
4.5.6 Settings purge / vent . . . . . . . . . . . . . . . . . . 51
4.5.7 Total view of the menu . . . . . . . . . . . . . . . . . 52
4.6 Operating menu for the MAG.DRIVE L2 . . . . 53
4.6.1 Basic menu . . . . . . . . . . . . . . . . . . . . . . . . . 53
4.6.2 Settings converter . . . . . . . . . . . . . . . . . . . . 54
4.6.3 Settings pump . . . . . . . . . . . . . . . . . . . . . . . 55
4.6.4 Settings temperature management system . 55
4.6.5 Settings purge / vent . . . . . . . . . . . . . . . . . . 56
4.6.6 Total view of the menu . . . . . . . . . . . . . . . . . 57
4.7 Temperature management system . . . . . . . . 58
4.7.1 TMS for the MAG.DRIVE L . . . . . . . . . . . . . 58
4.7.2 TMS for the MAG.DRIVE L2 . . . . . . . . . . . . 60
5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . 62
5.1 Removing the pump from the system . . . . . . 62
5.2 Service at Leybold’s . . . . . . . . . . . . . . . . . . 64
6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . 65
6.1 Troubleshooting for the MAG.DRIVE L . . . . . 66
6.1.1 Warning and failure messages . . . . . . . . . . . 66
6.1.2 Failure messages . . . . . . . . . . . . . . . . . . . . 67
6.1.3 Warning messages . . . . . . . . . . . . . . . . . . . 68
6.1.4 Malfunctions . . . . . . . . . . . . . . . . . . . . . . . . 69
6.2 Troubleshooting for the MAG.DRIVE L2 . . . . 70
6.2.1 Warning messages . . . . . . . . . . . . . . . . . . . 70
6.2.2 Failure messages . . . . . . . . . . . . . . . . . . . . 72
6.2.3 Malfunctions . . . . . . . . . . . . . . . . . . . . . . . . 77
Certifications . . . . . . . . . . . . . . . . . . . . . . . . 78
Forms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figures
The references to diagrams, e. g.(1/2) consist of the Fig. No.and the Item No. in that order.
We reserve the right to alter the design or any data given in these Operating Instructions. The illustrations are not binding.
The Operating Instructions are included with the pump and the converter. If they have different editions, the version delivered with the pump describes the pump correctly and the version delivered with the converter describes the converter correctly. The version number is the digit behind the „/“ in the GA No.. Example: GA
05.130/1.02 is the first edition.
Differences between the versions:
/1 → /2
• We added the operation diagram and the pumping speed curve for the MAG W 1600.
• We corrected some minor text mistakes.
/2 → /3
• We separated the Troubleshooting for the MAG.DRIVE L & L2 and made it more detailed for the MAG.DRIVE L2.
• We added technical data, the dimensional drawing, the operation diagram, and the pumping speed curve for the MAG 1600.
• We added ordering data.
• We added an installation instruction for the splinter guard.
• We corrected some minor text mistakes.
Thus, you may use v ersion /3 instead of v ersions /1 and /2 for the pump and the converter.
If you have a MAG pump with a MAG.DRIVE 2000 con­verter you must use the Operating Instructions deliver­ed with the converter for the operation of the converter.
2
GA 05.130/3.02 - 05/98
Page 3
Description
3
GA 05.130/3.02 - 05/98
Fig. 1 MAG W 2000 CT
MAG.DRIVE L(2)
Fig. 2 MAG.DRIVE Front panel
1 Description
1.1 System overview
The Leybold MAG pumping system consists of:
• The MAG W 1600, MAG 2000, or MAG W 2000 turbopump
The MAG are turbomolecular pumps utilizing magne­tic bearings.They are designed to evacuate vacuum chambers down to pressure values in the high-vacu­um range and to pump high gas throughputs.
The C versions are equipped with a purge gas valve and a Pt 100 temperature sensor for the cooling water temperature.
The CT versions are additionally equipped with a temperature management system (TMS) to control the base flange temperature.
The pumps are available with 2 different rotors:
MAG version: 11 turbo pump stages MAG W version: 6 turbo pump stages and 1 drag
stage.
• The MAG.DRIVE L or MAG.DRIVE L2 frequency converter
The electronic converter converts the single-phase line supply voltage into a three-phase DC voltage to drive the pump motor.It also evaluates measured sig­nals and controls
- the pump functions
- the temperature management system (TMS) and
- the active magnetic bearing system
• A cable set consisting of:
- BEARING cable
- TMS cable
- DRIVE cable
Fig. 3 Cable Set
Page 4
Description
1.2 Compatibility with pumped media
The MAG (W) 1600/2000 C/CT are specifically designed for the needs of the semiconductor industry.
Corrosion protection
To protect the pump from corrosive gases it is mandatory to use dry Nitrogen purge during operation of the pump.The purge gas protects the bearing section and the motor from corrosive gases.
The rotor and the stator of the pump are KEPLA-coated to prevent corrosiv e attac k caused b y the process gases. The corrosion protection of the pump is effective only when the pump is protected from moisture during standstill and storage. If the process gas contains moi­sture, contact Leybold for recommendations.
Sublimation
Some media (e.g. AlCl3) can sublimate in the pump and form deposits. Thick coatings can infringe on the requi-
red operating clearence and ultimately cause the pump to seize.These deposits can also react with moisture and generate corrosive gases (e.g. HCl).This can become very critical when the pump is exposed to air. Deposits can be avoided in many processes by heating the pump with TMS (Temperature Management System).
The TMS is integrated in all CT-versions.The pur pose of the TMS is to keep the baseflange temperature in a con­stant range. To achieve the temperature the pump is equipped with a heaterband.
Some media ( e.g. metall organic compounds ) can decompose at the hot surface of the pump and build lay­ers. Please direct any inqueries to the manufacturer.
Ignition danger
During operation the pressure inside the MAG is so low that there is no danger of ignition (at pressures below about 100 mbar). A hazardous condition will be created if flammable mixtures enter the hot pump at pressures above 100 mbar. Dur ing operation the pump can reach temperatures as high as 120°C (248°F). If the pump is damaged, sparks could occur which could ignite explosi­ve mixtures.
Please consult us regarding the media which can safely be handled with this unit, with or without purge gas.
4
GA 05.130/3.02 - 05/98
1.3 Design of the MAG
The MAG comprises basically the pump housing, the multistage rotor with the stator package, the drive, and a magnetic bearing.
Rotor
The rotor is made from a high strength aluminium alloy. The rotor and the lower stator plates are protected with a special ceramic layer ( KEPLA-coat ). The standard rotor is a multi-stage axial-flow turbine.In addition to the turbine stage the wide range rotor has a screw stage.
Both rotors are machined from one piece and the geo­metry of the the blades is optimized for high compressi­on and pumping speed of the typical gases used in semi­conductor manufacturing processes ( e.g.SF6, Ar, BCl3).
Bearings
The MAG 1600/2000 has a built-in precision 5-axis con­trolled magnetic bearing. The rotor is suspended by trouble-free magnets:
• along two orthogonal axes in each of two radial planes
• and completely in the axial direction The bearing concept allows for low vibration operations
and insures operation of the pump in any mounting posi­tion. Magnetic bearings also guarantee ultra-clean vacu­um because no grease is used for lubrication of bea­rings.
Two touch down bearings are provided to stabilize the rotor mechanically if impacts occur during operation. They are only used in case of the breaking of the power supply cable during operation, strong shocks, or faulty electronics.
Motor and control
A DC motor without commutator is used to power the rotor.
Drive voltage for the motor and the operating voltage for the magnetic bearing are supplied by the MAG.DRIVE frequency converter.It also handles the automatic moni­toring of these systems.
The pump is equipped with a data storage device which stores the important operating parameters during the complete operation time of the pump.
The converter monitors continously all important opera­ting parameters and provides warning and alarm signals in case the operating conditions exceed the specification or the set threshold.
Page 5
GA 05.130/3.02 - 05/98
Description
5
Fig. 4 Section of a MAG (W) 2000
Wide range rotorStandard rotor
Page 6
GA 05.130/3.02 - 05/98
Description
6
Front panel
Main switch 9-pin connecting socket for the RS232 interface 7 short-stroke keys 1 backlit LCD with 2 lines, each 16 characters, 8 mm
character height 1 green/red STATUS LED 1 green COM LED (communications interface) 1 green MAIN LED (line supply voltage)
Rear panel
X1 25-pin D socket connector for remote monitoring
and open-loop control X7.29-pin D connector for RS232 X10 3-pin Hirschmann connector for the connection to
the mains supply X24 64-pin Harting socket connector for internal sen-
sors and magnetic bearing connection X26 10-pin Harting socket connector for the motor
connection X31 25-pin Harting socket connector for the TMS and
purge valve connection X33 3-pin terminal strip, 24 V output voltage (e.g. for the
power failure airing valve) F1 Fuse for mains power supply (only MAG.DRIVE L2) F2 Fuse for power supply of the active magnetic bea-
ring (only MAG.DRIVE L2) F3 Fuse for the heating (TMS) 1 or 2 protective earth terminals
1.4 Function and design of the MAG.DRIVE
The MAG.DRIVE L and MAG.DRIVE L2 electronic con­verters are used to drive the MAG turbo-molecular pumps.
The electronic converters convert the single-phase line supply voltage into a three-phase DC voltage to control and monitor the electronically-commutated DC motor. It also evaluates measured signals and controls (open­loop and closed-loop) the pump functions.
The temperature management system (TMS) and the magnetic bearing control system are integrated into the converter.The TMS regulates the pump temperature by switching the heating on/off or cooling the pump. The magnetic bearing control system actively controls the pump rotor in five axes (closed-loop control).
All parameters required for pump operation and the listed faults and operating hours are stored in a non-vola­tile memory in the pump.When the converter is switched on, the data are loaded into the converter from the pump.
The outputs of the electronic converter are no-load and short-circuit proof.
The electronic converter can be connected via its serial interface to external open-loop control and monitoring devices. More detailed information on the serial interface and the interface protocol are provided in the Option Manual “MAG.DRIVE serial interface”.
For remote control via control connector X1 we recom­mend that either a relay or optocoupler is used to provi­de electrical isolation.
Housing
The converter is supplied with a closed housing. It can be installed in a 19” cabinet
Page 7
X1 X7.2
X26
X31
F3
PEPE
1
13
14
25
1
ABCD
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ABCD
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
X24
4 5
9
3
2
1
10
8
7
6
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
CBA
1
5
6
9
X10
1
3
1 2 3
s
X33
X7.2
PE
X1
X33
F3
X24
X31
X26
X10
PE
X1
X7.2
X26
X31
F3
PE
1
13
14
25
1
ABCD
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ABCD
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
X24
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
CBA
1
5
6
9
X10
1
3
1 2 3
s
F1F2
X33
4
5
9
3
2
1
10
8
7
6
X7.2
PE
X1
X33
F3
X24
F1
X31
F2
X26
X10
GA 05.130/3.02 - 05/98
Description
7
MAG.DRIVE L(2)
Connection serial interface RS 232
Fig.6 Rear panel with connections
Fig. 5 Front panel
Main switch
X1 Connection control plug X7.2 Connection serial interface
RS 232 X10 Mains connection X24 Connection magnetic
bearing X26 Connection pump motor X31 Connection TMS X33 Output 24 V F1 Fuse mains F2 Fuse bearing F3 Fuse TMS PE Protective earth
MAG.DRIVE L
MAG.DRIVE L2
Page 8
Description
8
GA 05.130/3.02 - 05/98
1.5 Standard specification
MAG
The turbomolecular pumps are shipped complete, sealed in a PE bag containing a desiccant.
The maximum effective life of the desiccant is one year. The intake flange is sealed with a transport seal, the
forevacuum flange with a plastic cap. For the intake flange, a centering ring with FPM O-ring,
outer ring, and a splinter guard are enclosed. We also provide the bolts for attaching the pump to your
tool.To avoid any safety risk we highly recommend using only the bolts provided with the pump.Refer also to Sec­tion 2.4 „Connecting the MAG ...“.
The electronic frequency converter MAG DRIVE as well as the cables required for operation must be ordered seperately.
In addition, a seal kit is included to seal the pump tightly if it is removed from the process.
MAG.DRIVE
• Converter
• Line supply cable with USA connector, approx.3m
• Line supply cable with EURO connector, approx. 3 m
• Spare fuses (miniature fuses 5 x 20 mm) F1 for the mains power supply (F8A) (only MAG.DRIVE L2) F2 for the power supply of the active magnetic bea­ring (T3.15A) (only MAG.DRIVE L2) F3 for the heating (F4A)
Cable Set
• Bearing cable
• TMS cable
• Drive cable
Page 9
Description
1.6 Technical data
MAG 1600 C/CT W 1600 C/CT 2000 C/CT W 2000 C/CT
Pumping speed for N2measured with splinter guard (PNEUROP) l·s
-1
1250 1300 1550 1650
Gas flow (continuous operation with Argon) sccm 1000 1000 1000 1000
Compression for N
2
>10
8
>10
8
>10
8
>10
8
Ultimate pressure as to DIN 28 400 mbar < 10
-8
< 10
-8
< 10
-8
< 10
-8
Max. forevacuum pressure
with Nitrogen mbar 1.5 3.3 1.5 3.3 with Argon mbar 1.5 4.1 1.5 4.1
Rotor Speed min
-1
28,800 Run-up time min < 10 Braking time with/without venting min 1 / < 7.5 Cooling water
Cooling connection, Swagelok elbow for tube OD mm 6.4 (1/4“) Cooling water temperature °C 15 to 30
°F 59 to 86
Base flange temperature C version °C 30 to 50 (depending on the load) °F 86 to 122
Base flange temperature CT version °C 30 to 63 (controlled) °F 86 to 145
Weight approx. kg 70 65 68 62 High-vacuum connection flange DN 200 ISO-F 200 ISO-F 250 ISO-F 250 ISO-F Forevacuum connection flange DN 40 KF 40 KF 40 KF 40 KF Recommended backing pump DRYVAC 100 50 100 50 Admissible ambient temperature °C 5 to 40
°F 40 to 104
Storage temperature °C -10 to +60
°F 14 to 140
9
GA 05.130/3.02 - 05/98
Page 10
Purge Gas
Purge gas connection pressure, abs. 1.2 - 2.0 bar Purge gas: dry nitrogen, argon or similar Purge gas throughput
at purge gas pressure 1.5 bar abs. 0.6 mbar·l·s
-1
36 sccm
Connection:VCR Nut 1/4“
MAG.DRIVE
Voltage range 200 - 240 V +10% -15% Line supply frequency 50 / 60 Hz
Load Stand-by approx. 100 W Continuous (rated speed) 810 W Maximum 1800 W
Max. voltage motor 60 V Maximum pump current (Accel.) 20 A dc_peak
Continuous pump current, max. 13 A dc_peak Maximum frequency 480 Hz Load capability, relay output 42 V, 1 A Temperature during operation
MAG.DRIVE L 0-40° C MAG.DRIVE L2 0-45° C
Storage temperature - 10° C to + 60° C Relative air humidity Class F acc. to DIN 400 40 Weight 16 kg Dimensions W x H x D (mm) 465 x 222 x 350
+ connector depth 130
The units have degree of protection IP20 in accordance with EN 60529
(protection against the ingress of solid foreign bodies > 12 mm diameter (finger). It is not protected against the ingress of water with damaging effects.)
An increased degree of protection, e.g.IP54 can only be implemented by mounting the converter in an additional housing.
1.7 Ordering data
Order No. MAG 1600 C 894 14 MAG W 1600 C 894 15 MAG 2000 C 894 16 MAG W 2000 C 894 17 MAG 1600 CT 894 28 MAG W 1600 CT 894 29 MAG 2000 CT 894 30 MAG W 2000 CT 894 31
Seal Kit DN 200 200 91 684 Seal Kit DN 250 200 91 641
MAG.DRIVE L converter 857 24 MAG.DRIVE L2 converter 857 23
Connecting cables, converter / pump Length Cable Cable Cable
BEARING DRIVE TMS ———————————————————————— 3 m 859 50 859 51 859 52
5 m* 859 53 859 54 859 55 10 m* 859 56 859 57 859 58 20 m* 859 62 859 63 859 64 3 m with
bended plugs 859 68 859 69 859 70 The cables with straight plugs are shown in Fig.3, the
cables with bended plugs in Fig. 34.
• MAG.WIN, an operator control interface
which can run under Windows with user instructions as Windows help on request
• Connecting cable serial interface (front panel,
9-pin D-connector), approx. 5 m long on request
* only permissible if the pump is mounted in a vertical position
Description
10
GA 05.130/3.02 - 05/98
Page 11
Description
11
GA 05.130/3.02 - 05/98
483
465
146
10
7
222
130
353
20
233
Fig. 7 Dimensional drawing of the MAG.DRIVE; dimensions in mm
1500
1000
500
0
2000
10
-2
10
-1
1
Torr
10
-3
10
-4
l/s
MAG 1600 CT MAG W 1600 CT MAG 2000 CT MAG W 2000 CT
High Vacuum Pressure
Fig. 8 Pumping speed curves for Nitrogen
Pumping speed
Rotor speed 480 Hz Purge gas flow 36 sccm Nitrogen with splinter guard Forepump
for MAG 1600 CT D 65 B + WS 501 for MAG W 1600 CT D 65 B + WS 251 for MAG 2000 CT D 65 B + WS 501
for MAG W 2000 CT D 65 B + WS 251 Pipe 1 m DN 40 according to PNEUROP
Page 12
Description
12
GA 05.130/3.02 - 05/98
10
-1
10
-2
10
-3
10
-4
50 sccm
100 sccm
200 sccm
500 sccm
1000 sccm
10
-2
10
-1
1 10
Torr
Torr
Fig. 10 MAG W 1600 C/CT: operation diagram for nitrogen
High vacuum pressure
Forevacuum pressure
Rotor speed 480 Hz Purge gas flow 36 sccm Nitrogen with splinter guard Forepump D 65 B + WS 251 Pipe 1 m DN 40 according to PNEUROP
10
-1
10
-2
10
-3
10
-4
50 sccm
100 sccm
200 sccm
500 sccm
1000 sccm
10
-2
10
-1
1 10
Torr
Torr
Fig. 9 MAG 1600 C/CT: operation diagram for nitrogen
High vacuum pressure
Forevacuum pressure
Rotor speed 480 Hz Purge gas flow 36 sccm Nitrogen with splinter guard Forepump D 65 B + WS 501 Pipe 1 m DN 40 according to PNEUROP
Page 13
Description
13
GA 05.130/3.02 - 05/98
10
-1
10
-2
10
-3
10
-4
50 sccm
100 sccm
200 sccm
500 sccm
1000 sccm
10
-2
10
-1
1 10
Torr
Torr
Fig. 11 MAG 2000 C/CT: operation diagram for nitrogen
High vacuum pressure
Forevacuum pressure
Rotor speed 480 Hz Purge gas flow 36 sccm Nitrogen with splinter guard Forepump D 65 B + WS 501 Pipe 1 m DN 40 according to PNEUROP
10
-1
10
-2
10
-3
10
-4
50 sccm
100 sccm
200 sccm
500 sccm
1000 sccm
10
-2
10
-1
1 10
Torr
Torr
Fig. 12 MAG W 2000 C/CT: operation diagram for nitrogen
High vacuum pressure
Forevacuum pressure
Rotor speed 480 Hz Purge gas flow 36 sccm Nitrogen with splinter guard Forepump D 65 B + WS 251 Pipe 1 m DN 40 according to PNEUROP
Page 14
Description
14
GA 05.130/3.02 - 05/98
DN 40
12x30° = 360°
408
202
436
368
353
322
ø285
ø210
ø339
ø199
DN 200 ISO F
30°
260
11
18°
18°
51°
30°
35°
102
192
115
16
Fig. 13 MAG 1600 C, Dimensions in mm
MAG 1600 C Cat. No. 894 14
Page 15
Description
15
GA 05.130/3.02 - 05/98
322
ø285
DN 200 ISO F
ø210
DN 40
ø339
ø199
202
16
436
353
368
408
260
18°
18°
51°
30°
102
115
12x30° = 360°
30°
11
Fig. 14 MAG W 1600 C, Dimensions in mm
MAG W 1600 C Cat. No. 894 15
Page 16
Description
16
GA 05.130/3.02 - 05/98
408
202
436
368
353
322
16
ø285
ø210
ø355
ø199
12x30° = 360°
DN 40
DN 200 ISO F
30°
260
11
421
18°
18°
51°
30°
35°
102
192
115
Fig. 15 MAG 1600 CT, Dimensions in mm
MAG 1600 CT Cat. No. 894 28
Page 17
Description
17
GA 05.130/3.02 - 05/98
ø310 ø285
ø210
353
368
408
436
16
DN 200ISO F
322
ø199
202
DN 40
,00
260
355
18°
18°
51°
102
115
30°
12x30° = 360°
30°
11
Fig. 16 MAG W 1600 CT, Dimensions in mm
MAG W 1600 CT Cat. No. 894 29
Page 18
Description
18
GA 05.130/3.02 - 05/98
DN 40
DN 250 ISO F
318
202
358
16
303
386
272
ø339
ø199
ø335
ø261
12x30° = 360°
30°
310
11
18°
18°
51°
30°
35°
102
192
115
Fig. 17 MAG 2000 C, Dimensions in mm
MAG 2000 C Cat. No. 894 16
Page 19
Description
19
GA 05.130/3.02 - 05/98
DN 40
318
202
358
16
303
386
272
ø335
ø199
ø335
ø261
12x30° = 360°
DN 250 ISO F
18°
18°
51°
35°
102
115
30°
310
11
30°
Fig. 18 MAG W 2000 C, Dimensions in mm
MAG W 2000 C Cat. No. 894 17
Page 20
Description
20
GA 05.130/3.02 - 05/98
DN 250 ISO F
DN 40
202
272
303
318
358
386
ø339
ø199
ø261
ø335
16
12x30° = 360°
421
30°
310
11
18°
18°
51°
30°
35°
102
192
115
Fig. 19 MAG 2000 CT, Dimensions in mm
MAG 2000 CT Cat. No. 894 30
Page 21
Description
21
GA 05.130/3.02 - 05/98
DN 250 ISO F
DN 40
358
318
16
303
386
202
272
ø335 ø261
ø355
ø199
12x30° = 360°
18°
18°
51°
30°
35°
421
102
30°
310
11
115
Fig. 20 MAG W 2000 CT, Dimensions in mm
MAG W 2000 CT Cat. No. 894 31
Page 22
Installation
22
GA 05.130/3.02 - 05/98
Warning
Before opening the converter, always dis­connect from the mains! When applying external voltage in excess of 42 V to termi­nals of the device, observe local safety regulations! Unauthorized device conversion and modi­fications are prohibited for safety reasons.
Please keep this Operating Instruction for future referen­ce.
2.2 Unpacking - storing ­transportation
Remove the equipment from the transportation box and keep the packaging. Make sure that the product has not been damaged during transportation. If this unit is dama­ged contact your carrier and inform LEYBOLD if neces­sary. For storage of the product, use the packaging pro­vided.
Lift the pump by the crane eyelets or mo v e it with at least two persons.
You can position the pump on the base plate for trans­port with a lift-truck. Protect the pump against slipping and tipping over.
Caution
Be careful not to damage the sockets and coolant connections during transportation.
Do not stand below the pump while connecting or remo­ving the MAG.
The MAG is shipped in a sealed PE bag with desiccant. Do not open the sealed package until immediately befo­re installing.
Do not remove the covers and blanking flanges until you are ready to make the connections, to ensure that the MAG is installed under the cleanest possible conditions.
2 Installation
2.1
General safety information
Warning
Indicates procedures that must be strictly observed to prevent hazards to persons.
Caution
Indicates procedures that must be strictly observed to prevent damage to, or destruction of the MAG.
Warning
Never expose any parts of the body to the vacuum.
Warning
The converter has dangerous voltage levels.
Failure to strictly follow the instructions in this Manual can result in death, severe bodily injuries or significant material dama­ge.
Only suitably qualified personnel are per­mitted to work on the pump or converter. Personnel m ust be completely kno wledgea­ble of all warning information and measures which are specified in this Instruction manual for transporting, installing, and ope­rating the unit.
Qualified personnel
Qualified electrical personnel in this instruction manual means a person who has received electrical engineering instruction or is an electrical expert in accordance with EN 60204, Part 1, 3.30 respectivly 3.55.
Warning
The device contain electrostatically sensiti­ve devices (ESD)!
Page 23
Installation
23
GA 05.130/3.02 - 05/98
1
2
1 Aluminum cover 2 Screws
Fig. 21 Removing the transport seal
2.3 Operating environment
When using the MAG inside a magnetic field, the magne­tic induction at the pump housing must not exceed 5 mT; (1 mT (milliTesla) = 10 G (Gauß))
Exceeding this limit can cause excessive rotor heating due to the eddy currents generated in this situation. It is therefore necessary to provide suitable shielding in such cases.
The standard version of the MAG is resistant to radiation at levels up to 103Gy. (1 Gy (Gray) = 100 rad)
The ambient temperature must not exceed 40°C (104 °F).
The noise level when the pump is running is below 70 dB(A). No acoustic insulation is required.
2.4 Connecting the MAG to the vacuum chamber
The MAG is shipped in a sealed PE bag with desiccant. Do not open the package until immediately before instal­ling.
Do not remove the covers and blanking flanges until you are ready to make the connections, to ensure that the MAG is installed under the cleanest possible conditions.
Pay attention to maximum cleanliness when connecting. Remove the transport seal from the intake flange.To do
so unscrew the screws (21/2) and remove the aluminum cover.We recommend saving the transport seal for main­tenance.
Page 24
GA 05.130/3.02 - 05/98
Installation
24
Foreign objects entering the pump through the high-va­cuum flange can cause serious damage to the rotor. That’s why the splinter guard must always be installed.
Damages caused during operation without the splinter guard are excluded from warranty.
Caution
Install the splinter guard as shown in Fig.
23. Installing the splinter guard upside down may lead to contact between splinter guard and rotor during fast venting of the pump.
Fig. 22 Connection elements
Intake flange
Forevacuum flange
Cooling water out
Cooling water in
Correct
Wrong
Fig. 23 Installing the splinter guard
Page 25
Installation
25
GA 05.130/3.02 - 05/98
Warning
The pump must be securely attached.If the pump should suddenly seize, inadequate attachment could cause the pump to break away or allow internal pump parts to be dis­charged. Never operate the pump (in bench tests, for instance) without its being con­nected at the vacuum chamber.
If the pump should suddenly seize, the dec­celeration torque of 60,000 Nm will have to be absorbed by the system. To accomplish this, use all 12 bolts provided by Leybold for fastening the high-vacuum flange; see also Fig. 25.
Mount the MAG as close as possible to the vacuum chamber. If the MAG is permanently flanged to a vacuum chamber with a weight exceeding 500 kg, it will not be necessary to secure it in any other way.
In case of lighter vacuum vessels secure the pump addi­tionally. The pump’s bottom is equipped with tappered holes for fastening a support; see Fig. 26.
If the pump is exposed to shocks, e.g. by a gate valve, secure the pump so that it is supported in the direction of the shock.
We recommend installing an isolation valve between the pump and the chamber. The valve should be closed during wet cleans of the chamber and in case of pump failures which will lead to a pump shut down.The valve should normally be closed with power off.
Warning
The basic flange heater can become so hot during operation (> 80°C, > 176 °F) that it represents a burn hazard: Provide protection against contact with the hot components.
Mounting position and cable length
If the pump is mounted in a vertical position (intake flange up or down) the permissible length of the pump­converter cables is 3 to 20 meters.
If the pump is mounted in a horizontal position the per­missible length of the pump-converter cables is 3 meter.
Purge gas in
TMS connection
BEARING connection
DRIVE connection
Fig. 24 Connection elements
Purge gas valve
Page 26
Installation
26
GA 05.130/3.02 - 05/98
21.5
l
l > 15 mm in aluminium l > 10 mm in steel
Outer ring (stainless steel)
Sealing (FPM)
Centering ring (stainless steel)
Splinter guard
Max. torque = 60,000 Nm
Fig. 25 Fixing the intake flange
Bolts: M10 x 40 Quality 12.9 according to DIN 898:
0,2% yield strength > 1080 N/mm
2
Bolt torque: 40 Nm
Page 27
Installation
27
GA 05.130/3.02 - 05/98
15°
30°
70°
125°
Ø 310
Fig. 27 Layout of a turbomolecular pump system
Key to Fig. 27
1 Turbomolecular pump 2 Forevacuum gauge point 3 Backing pump 4 Anti-vibration bellows 5 Forevacuum valve 6 High vacuum valve 7 Purge gas connection 8 Valve in the roughing line 9 Electronic frequency converter
— — — — roughing line; recommended if shorter cycle times are to be achieved
— · — · — · — · drive, bearing, and TMS cable
Fig. 26 Fixing the pump at the bottom
Boreholes M8,
15 mm deep
Page 28
Installation
28
GA 05.130/3.02 - 05/98
2.5 Connecting the backing pump
A two stage rotary vane pump or dry-compression backing pump is required to support operation of the MAG.
We recommend using the DRYVAC or our TRIVAC-B pump for this purpose.
In case of high gas throughput, it may also be necessary to use a roots blower to achieve the backing pressure necessary for operating the MAG. We recommend our RUVAC blower for this purpose or our DRYVAC 251/501 systems.
Fig. 27 shows schematically the design of a pump system incorporating a MAG with an additional foreline valve and an isolation v alv e between chamber and MAG.
The foreline isolation valve is recommended to protect the MAG from shock v enting in case of uncontrolled shut down of the backing pump. This valve must be able to close fast enough to avoid pressure increase in the MAG.
In case of an oil-sealed backing pump the foreline isola­tion valve protects the MAG from backstreaming oil vapor during standstill.
Connect the forevacuum flange of the MAG to the backing pump.
The torque on the forevacuum connection flange must not exceed the values shown in Fig. 28.
Warning
The forevacuum line must be tight. Hazar­dous gases can escape at leaks or the gases being pumped can react with the air or humidity. We recommend a leak check.
2.6 Connecting the cooling water
Cooling water specifications
Inlet temperature 15 - 30 °C Inlet pressure 3 to 7 bar absolute Cooling water requirement See Fig. 30 Appearance Colorless, clear,
free of oils and greases Sediments < 250 mg/l Particle size < 150 µm Electrical conductivity < 500 µS/cm pH value 7 to 8.5 Overall hardness (total alkaline earths)
max. 20 ° Ger man hardness scale
(= 3.57 mmol/l)
Further information on request.
M
M
q
M < 150 Nm Mq< 150 Nm
Fig. 28 Maximum torques for the forevacuum connection
Page 29
Installation
29
GA 05.130/3.02 - 05/98
Connect the cooling water to the connectors;see Fig. 29. Make sure that you do not mix up the inlet and the outlet
connection. Tur n off the cooling water supply when the pump is
switched off in order to a void condensate f ormation in the pump.
If you do not close the cooling water it ma y tak e longer to achieve ultimate pressure after start up of the system.
Fig. 29 Connecting the cooling water
Cooling water out 1/4“ tube
Cooling water in 1/4“ tube
5 10 15 20 25 30 35 40
°C
220 200 180 160 140 120 100
80 60 40
l/h
Fig. 30 Recommended cooling water flow as a function of cooling water temperature
Temperature
Flow
maximum
optimum
minimum
Page 30
Installation
30
GA 05.130/3.02 - 05/98
2.7 Connecting the purge gas
The MAG is equipped with a purge gas and venting valve. It is controlled by the MAG.DRIVE. Additional monitoring with a flow controller is not necessary.
Connect the purge gas and venting valve to the purge gas supply via a pressure reducer.
Connection:VCR Nut 1/4“ Purge gas connection pressure, abs. 1.2 - 2.0 bar Purge gas: dry nitrogen, argon or similar Purge gas throughput
at purge gas pressure 1.5 bar abs. 0.6 mbar·l·s
-1
36 sccm
With no voltage applied the purge gas and venting valve is closed.
The purge gas valve will be open when switching on the MAG.DRIVE.The red LED at the purge gas valve lights.
The venting valv e can be opened via the control plug X1. The red LED at the venting valv e lights when the valve is open. A blind-flanged pump will be vented within 1 minu­te via the open venting valve.
Warning
Monitor the purge gas continuously. Insufficient purge gas flow can result in:
- Process gases entering the motor and bearing area of the MAG
- Process gases escaping from the purge gas valve
- Humidity entering the pump.
24 V
24 V 24 V
Connection to Nozzle Connection to
purge gas supply pump
Purge valve venting valve
Fig. 31 Schematic drawing of purge and venting valve
Status Purge Valve
No Purge: Purge closed Purge Vent
Vent closed
Page 31
Installation
31
GA 05.130/3.02 - 05/98
Fig. 32 Purge gas connection with connection kit
VCR Nut 1/4“
Port connector: Tube to VCR
Male connector: Tube OD 1/4“ ­ISO male pipe size: 1/4“
Seal
LED purge valve
LED vent valve
Page 32
Caution
The connecting cables between the conver­ters and pump may only be inserted or removed when the converter is switched off or is isolated from the line supply. If a connector is inserted or withdrawn when the converter is switched on, the converter and the pump could be damaged or dest­royed!
Warning
Hazardous voltages are present inside the converter.Death or severe injury can occur if you come into contact with these hazar­dous voltages. Before opening the conver­ter, isolate the converter from the line supp­ly, and lock the switch so that it cannot be accidentally switched on again.
Installation instructions to maintain EMC
The MAG.DRIVE L2 complies with the Electromagnetic Compatibility (EMC) Directives of the EC. In order to maintain this the following installation instructions must be observed:
• The housing must be connected to a good ground connection (e.g. mounting rack) using a large cross
section (e.g.1.5 mm2) cable which should be as short as possible.The PE connection is located on the rear panel.
• To connect the pump to the converter the prescribed Leybold cables must be used.
• A shielded cable must be used for the connections to the terminal strip X33. The shield should be connec­ted to ground to a low-impedance connection.
• The connection cables to the analog interface (control plug X1) and to the serial interfaces (connectors X7.1 and X7.2) must be shielded. The shields must be connected to the metal housings of the SUB-D­connector and SUB-D-socket.
Installation
32
GA 05.130/3.02 - 05/98
2.8 Installing the MAG.DRIVE
The converter can be installed in a 19” cabinet Mounting depth: 350 mm + 130 mm for the connectors
on the rear side (133/4“ + 51/8“); height: 5 height units (83/4“)
Caution
In order to guarantee sufficient cooling, there must be a minimum clearance of 1 height unit (44.2 mm) at the bottom and 1 height unit at the top.A fan assembly can be inserted. During operation the temperature of the ambient air must not exceed 40 °C for the MAG.DRIVE L and 45 °C for the MAG.DRIVE L2.
Warning
The pump may be operated only with a sui­table frequency converter and a suit­able connector cable. Peak voltages of up to 130 V may be pre­sent at the connector line between the fre­quency converter and the pump; mains vol­tage is present at the heater. Route all cables so as to protect them from
damage. The protection rating for the connectors is IP 30. Do not expose the pump, the frequency converter or the
connections to dripping water. Install 16 A fuses for the converter.
Warning
Only adequately trained electrical/electronic
personnel may connect-up the equipment in
accordance with valid IEC (international),
EN (European) and/or national guidelines,
or under their management and supervisi-
on.
Page 33
GA 05.130/3.02 - 05/98
Installation
33
1 2 3
s
1 = Phase L 2 = Not assigned 3 = Neutral N S = PE
Fig. 33 Connector assignment X10, supply connection
2.8.1 Power supply connection X10
The converter is ready to be connected to line supply voltages between 200-240 V 50/60 Hz.The connection is established using the power cable supplied, which is ins­erted at connector X10 at the rear of the converter.
Caution
The converter will be damaged if it is ope­rated with the incorrect supply voltage.
BEARING
TMS
DRIVE
Fig. 34 Cable set with bended plugs; cable set with straight plugs similar
2.8.2 Pump connection
Connect the converter (X26) to the pump motor connec­tion (X25) using the DRIVE connecting cable.
Connect the converter (X24) to the magnetic bearing connection of the pump (X23) using the BEARING connecting cable.
Connect the converter (X31) to the TMS connection of the pump (X30) using the TMS connecting cable.
Also refer to Fig. 35 or 36. Make sure that you have fixed all cables properly by
using the clamps fixed to the converter.
Mounting position and cable length
If the pump is mounted in a vertical position (intake flange up or down) the permissible length of the pump­converter cables is 3 to 20 meters.
If the pump is mounted in a horizontal position the per­missible length of the pump-converter cables is 3 meter.
Page 34
Installation
34
GA 05.130/3.02 - 05/98
TMS
BEARING
DRIVE
X 24
BEAR-
ING
X 31 TMS
X 26
DRIVE
X 33
External
valve
F3
TMS Fuse
X 10
Mains plug
X 1 X 7.2
Control plug RS 232
PE
PE
MAINS ANALOG INTERFACE INTERFACE
Fig. 35 Block wiring diagram for MAG.DRIVE L
X25
X23
X30
Page 35
Installation
35
GA 05.130/3.02 - 05/98
X1
X7.2
X26
X31
F3
PE
1
13
14
25
1
ABCD
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ABCD
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
X24
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
CBA
1
5
6
9
X10
1
3
1 2 3
s
F1F2
X33
4
5
9
3
2
1
10
8
7
6
X7.2
PE
X1
X33
F3
X24
F1
X31
F2
X26
X10
Fig. 36 Block wiring diagram for MAG.DRIVE L2
X25
X23
X30
MAINS
ANALOG INTERFACE
INTERFACE
TMS
BEARING
DRIVE
Page 36
Installation
2.8.3 Control plug X1
Relay outputs
The MAG.DRIVE L converter has 4 relay outputs.Three relay outputs are permanently assigned a signal.
Normal operation (changeover contact) Failure (changeover contact) Warning (NO contact)
The option relay (changeover contact) can output one of the following signals:
Threshold motor temperature reached (only MAG.DRIVE L)
Threshold bearing temperature reached (only MAG.DRIVE L2)
Threshold motor current reached Threshold frequency reached No cooling water No purge gas TMS temperature OK Vent
The selection of signals for the option relay and the adjustment of their thresholds can be achieved via the operator control menu; see Sections 4.5.2 or 4.6.2.
Signaling outputs
Open-collector outputs are available to signal
start command applied power supply O.K. pump standstill
at control plug X1. The outputs can have a maximum load of 15 V DC, 80 mA.
Analog output
The converter has an analog output which provides an analog signal (0..10 V) with a 10-bit resolution.The ana­log output function can be alternatively used to output
motor current actual frequency motor temperature rotor displacement signals (PW24, PV13, PZ12)
The output value can be increased or reduced by a sca­ling factor; refer to the operator control menu “Scaling”; see Sections 4.5.2 and 4.6.2 Settings Converter.
36
GA 05.130/3.02 - 05/98
1
13
14
25
1 Remote/Local 2 Start/Stop 3 Ground 4 Analog output 0..10V 5 Analog ground 6 Relay „Failure“ com. 7 Relay „Failure“ n.c. 8 Relay „Failure“ n.o. 9 Relay „Norm. operation“ com. 10 Relay „Norm. operation“ n.o. 11 Relay „Norm. operation“ n.c. 12 Option relay com 13 Option relay n.o.
14 Option relay n.c. 15 Signal „Star t command present“ 16 Signal „Power supply o.k.“ 17 Output +15 V;max 80 mA 18 Signal „Pump stands still“ 19 Digital input: TMS OFF 20 Digital input: Purge gas OFF 21 Relay „Warning“ n.o. 22 Relay „Warning“ com. 23 Digital input: Vent 24 Analog input 2 25 Analog input 1
n.o.= normally open com. = common n.c. = normally closed
Fig. 37 Assignment control plug X1
Page 37
Installation
37
GA 05.130/3.02 - 05/98
X1.6
X1.
8
X1.
7
X1.9
X1.10
X1.11
0
1
2
X1.12
X1.13
X1.14
X
X1.4 X1.5
X1.15
X1.16
X1.17
+15 V
3
4
5
&
X1.22
X1.21
X1.18
2,5 Hz
6
0
1
2
4
5
6
Strombegrenzung
80 mA
Open collector Ausgänge
Keine Störung
Relais Normalbetrieb
Normalbetrieb
Melderelais Option
Funktion
Melderelais
Funktion
Analogausgang
Analogausgang
Analog Masse
Startbefehl steht an
Stromversorgungo.k.
Skalierung
Kein Kühlwasser
Kein Sperrgas
TMS o.k.
Startbefehl
steht an
Relais Warnung
Warnung
Pumpe steht
Schwellwert
Motorstrom
Schwellwert
Motorstrom
Schwellwert
Frequenz
Frequenz-Istwert
Aktuelle Lager-Temp.
Schwellwert Lager-Temp.
Frequenz-Istwert
Fluten
Rotorlage
Istwert PVW 13
Istwert PZ 12
Istwert PVW 24
Relais Störung
Frequenz-Istwert
Fig. 38 Function diagram outputs
Relay failure
Relay warning
Relay normal operation
Relay option
Function
relay option
Function
analog output
Scale
Analog output
Analog ground
Open collector outputs
Pump standstill
Current limit
80 mA
No failure
Warning
Start command
applied
Actual frequency
Normal operation
Motor or bearing
temperature
Threshold
Motor current
Threshold
Actual frequency
Threshold
No cooling water
No purge gas
TMS temperature ok
Vent
Rotor displacement
actual PVW 13 actual PVW 24
actual PZ12
Start command applied
Power supply
Actual frequency
Page 38
Installation
38
GA 05.130/3.02 - 05/98
Analog inputs
The converter has two analog inputs with a 10-bit reso­lution.
Input signal: 0...10V standard
4...20mA on request
A supplementary function can be set for analog input 2 via the operator control menu; see Sections 4.5.2 or
4.6.2: No function: The input signal can be output via
the serial interface.
Frequency setpoint: In addition to the function descr i-
bed above, the drive frequency set­point is entered via analog input 2.
Analog ground
Analog ground X1.5 is the reference ground for the ana­log output as well as for the analog inputs.
Digital inputs
The converter has 3 digital inputs with the following fun­ctions:
TMS OFF Purge gas OFF Vent ON
The functions are active if an High signal (15 V) is connected at the digital input.
2.8.4 Interface connector
A 9-pin sub-D socket is provided at the front panel and a 9-pin sub-D connector at the rear panel to connect a hig­her-level open-loop control and monitoring unit or a PC with the MAG.WIN operator control program.
The front connector X7.1 is assigned the serial interface RS232. If the front connector is to be used, to select connector X7.1, pin 1 must be connected to pin 5 (signal ground). To upload the software, pin 4 (boot) must be connected with pin 5 (signal ground).
The rear connector X7.2 is assigned with the serial RS232 interface.
Further information on the serial interface and the inter­face protocol to be used are provided in the optional manual „Serial interface MAG.DRIVE”.
1
5
6
9
1
5
6
9
1 Select front connector
X7.1 2 TxD 3 RxD 4 Boot 5 Signal ground
Fig. 39 Connector assignment, interface X7.1 (front side)
Fig. 40 Connector assignment, interface X7.2 (rear side)
5 Signal ground 4 +5V output through 390 Ω 3 RS232 RxD 2 RS232 TxD 1 -
Page 39
Installation
39
GA 05.130/3.02 - 05/98
3 2 1
1 PE 2 + 24 V output,
max. 300 mA
3 Ground
Fig. 41 Connector assignment X33, supply voltage
2.8.5 Connection X33
The internal +24 V supply voltage can be accessed for external loads at connector X33; for example, to connect relays or solenoid valv es.The output is short-circuit-proof and the output current is limited to 300 mA.
Page 40
Operation
40
GA 05.130/3.02 - 05/98
3 Operation
This Section describes the normal operation of the MAG pumping system
• via the front panel keys START and STOP,
• with pump and converter in the state of delivery from Leybold, and
• if no failure occurs.
If you want to operate the pumping system differently or if you want more background information about the pum­ping system operation refer to the following Sections:
• Explanation of the front panel keys 4.1
• Explanation of the display 4.2
• Operate the pump via remote control 4.3
• Explanation of the displayed operating statuses 4.4
• Change pump parameters via the operating menu 4.5 or 4.6
• Explanation of the temperature management system 4.7
• A failure message is displayed 6
3.1 Switching on
• Switch on the MAG.DRIVE.The display reads Ready
0.0 A 0 Hz
If the pump has the optional TMS (including e.g.the red heater band) the heater will be activated. The setpoint temperature will be reached within 30 - 60 minutes depending on cooling water temperature and flow.
In case of corresponding connection the backing pump will be activated when switching on the MAG.DRIVE.
• Open the purge gas supply.
• Open the cooling water supply.
• Press the START button.
The pump runs-up.
Acceleration
20.0 A 250 Hz
is diplayed until the frequency setpoint has been rea­ched. Then
Normal Operation
1.0 A 480 Hz is displayed. The backing pump and the MAG can be switched on
simultaneously. In such a situation the MAG serves from the very outset as an effective baffle.
Do not suddenly expose the MAG to an already evacua­ted vacuum chamber .The pressure surge may cause the rotor to make contact with the touch-down bearings.This will cause increased wear.
The pump may make noise during the run-up and run­down phases.This has neither an influence on the pump nor on the process.
Page 41
Operation
3.2 Operation
The magnetic bearing in the MAG are immune to wear. In addition to the magnetic bearings, the MAG is equip­ped with touch-down bearings which protect the rotor against mechanical contact with the stator if the pump is subjected to external shock loading or when the pump is switched off.These touch-down bearings have a limited service life. Please observe the following in order to obtain maximum service life.
• Avoid shock and vibrations when the pump is run­ning. Shocks perpendicular to the rotation axis are particularly har mful. If the pump appears to be run­ning in the mechanical bearings continuously it is switched off.
• Avoid frequent run up and down. The converter may overheat. You may run up und down the pump twice immediately after each other.
• Do not disconnect the MAG and MAG.DRIVE while they are operating. If MAG and MAG.DRIVE have been disconnected accidently do not re-connect them while the MAG is operating.
Warning
Monitor the purge gas continuously. Insufficient purge gas flow can result in:
- Process gases entering the motor and bearing area of the MAG
- Process gases escaping from the purge gas valve
- Humidity entering the pump. Refer to Section 2.7.
MAG with heating collar:
Warning
The heating collar will be hot during oper­ation. Burn hazard!
3.3 Switching off
The MAG.DRIVE controls the venting automatically pro­vided purge gas is connected to the MAG and the MAG.DRIVE is programmed correspondingly („Vent on“).
Caution
The values shown in the pressure rise curve must be maintained; see Fig. 42.
Caution
Do not stop the MAG with the mains. Use the STOP key. Switching off the mains while the pump is running will wear out the touch down bearings.
• Press the STOP key. Deceleration
20.0 A 400 Hz
will be displayed.When the display reads
Ready
0.0 A 0 Hz
the pump has come to a standstill.
• Close the cooling water supply when the pump is
switched off in order to a v oid condensate formation in the pump.
The backing pump may be switched off once the MAG has stopped.
If the MAG has been used for pumping corrosive gases it should be purged with dry nitrogen for one hour before switching off.During down times of the system take care that neither ambient air nor cleaning agents enter the pump.
41
GA 05.130/3.02 - 05/98
Page 42
Operation
42
GA 05.130/3.02 - 05/98
10
3
Forevacuum pressure/mbar
10
2
10
1
10
0
10
-1
10
-2
10
-3
Fig. 42 Curve for safe venting of the MAG; pressure rise as a function of venting time
0 10 20 30 40 50 60
Time/s
Page 43
4 Converter Control
4.1 Functions of the front panel keys
• Starts the pump (only possible
if there is no fault).The start key is only active if the user is in the basic menu or in the operating display.
• Returns to the operating display
from any point in the program­ming menu.
• Stop when the pump is opera-
tional. The pump is braked down to < 1 Hz.
• Acknowledges a failure after the
cause of the failure has been removed.
• Selects a sub-menu
• Acknowledges a modified value
• Changes from the operating
display into the programming menu
• Selects the programming menu
• Returns to the last main menu
in the programming menu
• Increases a parameter value or
proceeds to the next option
• Lowers a parameter value or
returns to the previous option
GA 05.130/3.02 - 05/98
Converter Control
43
4.2 Operating display
All operating states, warning and failure are displa y ed on the display and three lamps on the front side of the con­verter.
If a critical operating status occurs, e.g. “Warning Temp. Pump”, this warning is displayed, alternating with the operating display.
Plain text display
1st line: Operating status 2nd line: Motor current / Actual frequency /
(TMS status code for MAG.DRIVE L2)
or 1st line: Failure message 2nd line: Failure cause
TMS status code (only for MAG.DRIVE L2)
No. Code Descr iption
————————————————————————
1 H Heating pump (range below T
set
- 5K)
2 H O K Temp.TMS ok, heater ON
(range T
set
- 5K to T
set
)
3 O K Temp.TMS ok (range T
set
± 2K)
4 C O K Temp.TMS ok, cooling ON
(range T
set
+ 5K to T
set
)
5 W Warning Temp. TMS
(Temp. > T
set
+ 5K)
O F F TMS cancelled via control plug X1
see also Section 4.7.2 „TMS for the MAG.DRIVE L2“
Failure
Accel.Time
Acceleration
9.7 A 254 Hz
START
STOP
ENTER
Page 44
Converter Control
Significance of the lamps
COM (green)
Is lit if communication has been established via the inter­face.
STA TUS(green/red)
Red, steady light = Failure Red, flashing = Warning Green, flashing (slow) = Start delay, Acceleration Green, flashing (fast) = Deceleration,
Kinetic buffering
Green, steady light = Nor mal operation
MAINS (green)
This lamp is lit if the power is switched-on, and all of the supply voltages for operation are available.
Flashes when the power fails as long as the power sup­ply voltages in the converter are maintained by the kine­tic buffering.
4.3 Remote control
The converter permits 3 operating modes. They can be selected via contact X1.1 of the control connector at the rear panel of the converter or via the serial interface. Operating mode 0 is automatically selected after the line supply voltage has been applied.
Operating mode 0
The pump can be switched-on or off using the START/ STOP keys or via control connector X1. The reference frequency can be selected in the operating menu.
• X1.1 not connected = Start/Stop via the operator con­trol panel
• Jumper X1.1-X1.3 = Start/Stop via control input X1.2
Operating mode 1
This operating mode can only be selected via the serial interface.
The pump can only be started and stopped via the seri­al interface.
The frequency setpoint can only be changed via the seri­al interface, e.g.from MAG.WIN
44
GA 05.130/3.02 - 05/98
Remote
Start
Masse
X1.1
X1.2
X1.3
Switch closed: START Switch open: STOP
Remote
Start
Masse
X1.1
X1.2
X1.3
Autostart
Remote
Start
Ground
Remote
Start
Ground
Fig. 43 Connecting-up example remote control
Page 45
Converter Control
Operating mode 2
This operating mode can only be set via the serial inter­face.
The pump can be switched-off via the keyboard, but it cannot be started via the keyboard.
The frequency setpoint can only be changed via the seri­al interface, e.g.from MAG.WIN.
Automatic starting after the power has been connected
Connect contacts X1.1, X1.2 and X1.3 with one another. The converter starts automatically when the power is applied.
45
GA 05.130/3.02 - 05/98
0
1
0
1
2
S
R
Q
Q
&
s
0
1
2
START
REMOTE
+15 V
X1.1
X1.2 X1.3
START Pumpe
STOP Pumpe
START Bedienfeld
STOP Bedienfeld
STOP Schnittstelle
START Schnittstelle
Störungen, die Bremsbetrieb verursachen
0 V = 0
15 V = 1
10 K
Ω
Keine Störung
≥1
≥1
Startverzögerungszeit
P36
P12
-1
(Bremsbetrieb mit dem Pulswiderstand)
Betriebsart: Programmierung nur über Schnittstelle
Fig. 44 Function diagram START/STOP
Operating mode:
Programming only via
serial interface
Start delay time
START pump
STOP pump
decelerating the pump with the pulsed resistor
START serial
interface
START
key pad
STOP
key pad
STOP serial
interface
No
failure Failures
causing
deceleration
Page 46
Converter Control
46
GA 05.130/3.02 - 05/98
4.4 Operating statuses
Switch-On Guard
The converter goes into the “Switch On Guard”operating status after the power is switched on and after initializa­tion. If there is no warning or failure, it changes over into the “Ready” condition.
After a failure has been acknowledged, the converter goes into the “Switch On Guard” operating status. The failure must be acknowledged a second time, so that it then goes into the “Ready” condition.
Ready
The converter is ready and waits for the START com­mand. All parameters can be interrogated or changed via the operator control panel or the serial interface.
The basic menu parameters (refer to 4.5/4.6, operating menu) can be scanned via the operator control panel.
Acceleration
The pump continuously accelerates with the maximum current. The acceleration time is monitored to ensure that it lies within a programmed value (refer to the menu “set­tings pump/max. Accel. Time”). If the converter hasn’t reached the normal operating mode during the monito­ring time, then it is shutdown with the failure message „max. Accel. Time”.
Normal operation
After a programmable frequency threshold has been rea­ched (refer to the menu “settings pump/Normal Operati­on”), the converter goes into the normal operation mode but the pump continues to accelerate up to the frequen­cy setpoint.
Maximum power or Overload
„Maximum power“ for MAG.DRIVE L or „Overload“ for MAG.DRIVE L2.
The speed is continuously monitored and controlled. If the speed, even at maximum current, cannot be held at the setpoint, as a result of external influences, e.g. excessive gas intake, the speed reduces until the con­verter goes into the „max.pow er”or „Overload“ operating condition when the programmable frequency threshold is fallen below (refer to the menu “settings pump/Normal Operation”). The acceleration time is restarted. If the converter hasn’t gone into the normal operating mode after the monitoring time, it is shutdown with the failure message „max. power time” or „Failure Overload Time“.
Kinetic buffering
If the power fails when the converter is switched on, the converter regenerates due to the pump up to a minimum frequency of < 170 Hz. When the power returns, the pump is again accelerated up to the frequency setpoint.
The acceleration time is now restarted. If the converter hasn’t gone into the normal operating mode after the monitoring time, it is shutdown with the failure message „max. Accel.Time” .
Deceleration
After a stop command, the pump is braked down to a speed < 1 Hz as quickly as possible. A brake resistor is integrated into the converter which converts the regene­rative energy into heat.
Failure
The converter was shutdown with a failure message and waits for a failure acknowledgement after the failure has been removed.The failure type can be read from the dis­play. The failure message can be acknowledged by depressing the STOP key or via the serial interface.
Page 47
Converter Control
47
GA 05.130/3.02 - 05/98
Mains switched on
Initialization
Switch On Guard
Acceleration
Normal Operation
Kinetic Buffer
Maximum Power
or Overload
Deceleration
Failure
After a failure, quit a second time
START command
Mains ok
Frequency > P 25 x P24
Mains failure
Mains failure
Frequency > P25 x P24
Frequency < P25 x P24
Mains failure
STOP command
If a failure occurs the pump is decelerated
Frequency < 1 Hz
Failure occurs
Failure acknowledgement only possible if f<5 Hz
Ready
Start Delay
STOP command
Parameter: P24 = Frequency setpoint P25 = Factor normal operation
Fig 45 Diagram: Operation status
Page 48
Converter Control MAG.DRIVE L
48
GA 05.130/3.02 - 05/98
Ready
0.0 A 0 Hz Enter
Setpoint
480 Hz
Enter
Pump life
0.00 h Enter
Temp. Motor
50 °C Enter
Temp. Converter
40 °C Enter
Temp. Pump
50 °C Enter
actual PVW 13
10%
Enter
actual PVW 24
10%
Enter
actual PZ 12
5%
Enter
power
400 W
Enter
Not active
Temp.TCU
63 °C
Enter
Not active
Temp. Cooling
20 °C
Enter
4.5.1 Basic menu
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Ready Operating display - - - - -
Setpoint Sets the speed for operation 0 480 480 Hz r/w
Pump life Total operating hours of the pump actual value h r
Temp.Motor Motor temperature actual value °C r
Temp.Converter Temperature of the power actual value °C r
electronic
Temp.Pump Temperature of the magnetic actual value °C r
bearing
Temp.TCU Temperature of the Temperature actual value °C r
Management System
Temp.Cooling Cooling water temperature actual value °C r
Diff. pressure Difference pressure actual value mbar r
Only active at pump models with purge valve flow control (MCF, MCTF)
actual PVW 13 Rotor displacement in the
magnetic bearing actual value % r plane VW13
actual PVW 24 Rotor displacement in the
magnetic bearing actual value % r plane VW24
actual PZ 12 Rotor displacement in the
magnetic bearing actual value % r axis Z12
power Power consumption of the drive actual value W r
r (read) = value can only be read r /w (read/write) = value can be read and written
Enter
Not active
Diff. pressure
100 mbar
4.5 Operating menu for the MAG.DRIVE L
Page 49
Converter Control MAG.DRIVE L
49
GA 05.130/3.02 - 05/98
inductance ...
analog 1 4%
German
4.5.2 Settings converter
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Option Relay Relay with change -over Threshold motor
contact; the operator can temperature reached °C r/w select one of the functions Threshold motor described current reached A
Threshold frequency the thresholds are adjusted reached Hz in the next three menu items No cooling water -
no purge gas -
TMS temperature o.k. -
Vent -
„analog1 4%“ not used
Threshold Threshold motor temp. 0 100 60 °C r/w
for option relay
Threshold Threshold motor current 0 20 10 A r/w
for option relay
Threshold Threshold frequency 0 480 300 Hz r/w
for option relay
analog output Analog output 0...10V; Motor current;
the operator can select 20 A =10Vxscale factor V r/w one of the functions Act.frequency ; described 500 Hz = 10Vxscale factorV
Bearing temp.;
100 °C = 10Vxscale factor V
Actual PVW13;
100% = 10Vxscale factor V
Actual PVW24;
100% = 10Vxscale factor V
Actual PZ12; 100% = 10Vxscale factor V „inductance“ not used
scale factor Scale factor for the analog output 0 2 1 - r/w Analog Input 2 Analog input 0...10V ; No function - r/w
optionally frequency setpoint via analog input 2 Function frequency (10V = max. frequency setpoint) setpoint -
Start delay Waiting time between start
command and acceleration 0 1200 0 s r/w
Display Display language English - r/w
German -
Bus adress Bus adress for the converter for
operation via 0 31 0 - r/w serial interface RS232
venting
Temp.TCU ok
no purge gas
no cooling water
frequency
Converter data
Enter
current
option relay
temperature
Enter
Threshold
60 °C Enter
Threshold
10.0 A Enter
Threshold
300 Hz
Enter
PZ12 peak
PVW24 peak
PVW13 peak
temperature
frequency
analog output
current
Enter
scale factor
1.0 x Enter
freq. setpoint
Analog Input 2
no function
Enter
Start delay
0 s
Enter
Display English
Enter
Bus address
0
Enter
r (read) = value can only be read r /w (read/write) = value can be read and written
Page 50
Converter Control MAG.DRIVE L
50
GA 05.130/3.02 - 05/98
4.5.3 Settings pump
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Normal operation Threshold for normal operation
corresponding to the 35 99 95 % r/w frequency setpoint
max. accel.time Monitor time for acceleration
and overload 600 3600 1000 s r/w
Motor current Limits the maximum motor
current; used to limit the 5 100 65 % r/w pump rotor temperature.
!!! See warning below!!!
Pump Type Displays the installed pump type Installed pump type - r/w
!!! Do not change the pump setting!!!
Warning
Setting the motor current to more than 65% may result in rotor overheating. Setting the motor current to more than 65% or changing the pump setting without permission from Leybold voids the warran­ty.
4.5.4 Settings active magnetic bearing
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
ident.magn.bear. Code to identify AMB type actual value - r
Emerg. bearing Counts actual value - r
Emerg. bearing Time actual value s r
Prog.Pump
Enter
Normal operation
95 %
Enter
max. accel. time
800 s Enter
r (read) = value can only be read r /w (read/write) = value can be read and written
Magnetic bearing
Enter
ident.magn.bear.
7
Enter
Emerg. bearing
0
Enter
Emerg. bearing
0.0 s
Enter
Motor current
65%
Enter
MCFT
MCF
M
MC
Pump Type
MCT
Enter
Page 51
Converter Control MAG.DRIVE L
51
GA 05.130/3.02 - 05/98
4.5.5 Settings temperature management system
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Setpoint Temp. Setpoint Temperature 20 75 63 °C r/w
Management System
Warn.Temp. TCU Warning temperature
Temperature Management 0 85 70 °C r/w System
FailTemp.TCU Shutdown temperature
Temperature Management 0 100 72 °C r/w System
speaker Intermittent = warning off - r/w
Continuous = failure on -
4.5.6 Settings purge / vent
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
P-Nr.HE Testdis Not used
TCU
Enter
Setpoint Temp
63 °C Enter
Purge/Vent
Enter
P-Nr.HE-Testdis
0
Enter
r (read) = value can only be read r /w (read/write) = value can be read and written
Warn.Temp.TCU
70 °C Enter
Fail Temp.TCU
72 °C Enter
on
speaker
off
Enter
Page 52
Converter Control MAG.DRIVE L
52
GA 05.130/3.02 - 05/98
4.5.7 Total view of the menu
Programming menu
Selects the parameterization menu from the
operating display.
Switches forward to the next main menu.
Switches back to the last main menu.
Selects submenu.
Confirms to store changed parameters.
Increases a parameter value or switches
forward to the next option.
Reduces a parameter value or switches
back to the last option.
Starts the pump. Only possible from the
basic menu.
Stops the pump.
Return to the operating display from
parameterization menu.
START
STOP
ENTER
Stop
Data to Eeprom?
Stop=no Enter=yes
Enter
Ready
00.0 A 0000 Hz
Stop
Data are stored
in the EPROM
To exit the parameterization menu
Basic menu
ororor
Ready
0.0 A 0 Hz
Enter
Setpoint
480 Hz
Enter
Pump life
0.00 h
Enter
Temp. Motor
50 °C
Enter
Temp. Converter
40 °C
Enter
Temp. Pump
50 °C
Enter
actual PVW 13
10%
Enter
actual PVW 24
10%
Enter
actual PZ 12
5%
Enter
power
400 W
Enter
Not active
Temp. TCU
63 °C
Enter
Not active
Temp. Cooling
20 °C
Enter
Enter
Not active
Diff. pressure
100 mbar
inductance ...
analog 1 4%
German
venting
Temp. TCU ok
no purge gas
no cooling water
frequency
Converter data
Enter
current
option relay
temperature
Enter
Threshold
60 °C
Enter
Threshold
10.0 A
Enter
Threshold
300 Hz
Enter
PZ12 peak
PVW24 peak
PVW13 peak
temperature
frequency
analog output
current
Enter
scale factor
1.0 x
Enter
freq. setpoint
Analog Input 2
no function
Enter
Start delay
0 s
Enter
Display
English
Enter
Bus address
0
Enter
Prog.Pump
Enter
Normal operation
95 %
Enter
max. accel. time
800 s
Enter
Motor current
65%
Enter
MCFT
MCF
M
MC
Pump Type
MCT
Enter
Magnetic bearing
Enter
ident.magn.bear.
7
Enter
Emerg. bearing
0
Enter
Emerg. bearing
0.0 s
Enter
TCU
Enter
Setpoint Temp
63 °C
Enter
Warn. Temp. TCU
70 °C
Enter
Fail Temp. TCU
72 °C
Enter
on
speaker
off
Enter
Purge/Vent
Enter
P-Nr. HE-Testdis
0
Enter
or or
Software version 1.2.3
Page 53
4.6.1 Basic menu
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Ready Operating display - - - - -
Freq.Setpoint Sets the speed for operation 0 480 480 Hz r/w
Operation Hours Total operating hours of the pump actual value h r
Motor Temp. Motor temperature actual value °C r
Converter Temp. Temperature of the power actual value °C r
electronic
Bearing Temp. Temperature of the magnetic actual value °C r
bearing
Actual Value TMS Temperature of the Temperature actual value °C r
Management System
Cooling Temp. Cooling water temperature actual value °C r
Actual PVW 13 Rotor displacement in the
magnetic bearing actual value % r plane VW13
Actual PVW 24 Rotor displacement in the
magnetic bearing actual value % r plane VW24
Actual PZ 12 Rotor displacement in the
magnetic bearing actual value % r axis Z12
Power Power consumption of the drive actual value W r
Software Version Actual software version actual value - r
Converter Control MAG.DRIVE L2
53
GA 05.130/3.02 - 05/98
Ready
0.0 A 0 Hz Enter
Freq.Setpoint
480 Hz
Enter
Operation Hours
0.00 h Enter
Motor Temp.
50 °C Enter
Converter Temp.
40 °C Enter
Bearing Temp.
50 °C Enter
Actual PVW 13
10%
Enter
Actual PVW 24
10%
Enter
Actual PZ 12
5%
Enter
Power 400 W
Enter
Not Active
Actual Value TMS
63 °C
Enter
Not Active
Cooling Temp.
20 °C
Enter
r (read) = value can only be read r /w (read/write) = value can be read and written
4.6 Operating menu for the MAG.DRIVE L2
Software Version
103.04
Enter
Page 54
Converter Control MAG.DRIVE L2
54
GA 05.130/3.02 - 05/98
r (read) = value can only be read r /w (read/write) = value can be read and written
4.6.2 Settings converter
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Option Relay Relay with change -over Threshold bearing
contact; the operator can temperature reached °C r/w select one of the functions Threshold motor described current reached A
Threshold frequency the thresholds are adjusted reached Hz in the next three menu items No cooling water -
no purge gas -
TMS temperature o.k. -
Vent -
Threshold Threshold bearing temp. 0 100 60 °C r/w
for option relay
Threshold Threshold motor current 0 20 10 A r/w
for option relay
Threshold Threshold frequency 0 480 300 Hz r/w
for option relay
Analog Output Analog output 0...10V; Motor current;
the operator can select 20 A =10Vxscale factor V r/w one of the functions Act.frequency ; described 500 Hz = 10Vxscale factorV
Bearing temp.;
100 °C = 10Vxscale factor V
Actual PVW13;
100% = 10Vxscale factor V
Actual PVW24;
100% = 10Vxscale factor V
Actual PZ12;
100% = 10Vxscale factor V
Scale Factor Scale factor for the analog output 0 2 1 - r/w Analog Input 2 Analog input 0...10V ; No function - r/w
optionally frequency setpoint via analog input 2 Function frequency (10V = max. frequency setpoint) setpoint -
Start Delay Waiting time between start
command and acceleration 0 1200 0 s r/w
Display Display language English - r/w
German -
Bus Adress Bus adress for the converter by
operation via 0 31 0 - r/w serial interface RS232/485
Acoustic Alarm OFF - r/w
Intermittent = warning ON ­Continuous = failure
German
Vent
TMS ok
No Purge gas
No Cooling Water
Frequency
Set Converter
Enter
Motor Current
Option Relay
Bearing Temp.
Enter
Threshold
60 °C Enter
Threshold
10.0 A Enter
Threshold
300 Hz
Enter
Actual PZ12
Actual PVW24
Actual PVW13
Bearing Temp.
Actual Frequency
Analog Output Motor Current
Enter
Scale factor
1.0 x
Enter
Freq.Setpoint
Analog Input 2
No Function
Enter
Start delay
0 s
Enter
Display English
Enter
Bus address
0
Enter
Acoustic Alarm
Off
Enter
Page 55
Converter Control MAG.DRIVE L2
55
GA 05.130/3.02 - 05/98
4.6.3 Settings pump
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Normal Operation Threshold for normal operation
corresponding to the 35 99 95 % r/w frequency setpoint
Max. Accel.Time Monitor time for acceleration
and overload 600 3600 1000 s r/w
Pump Type Displays the installed pump type Installed pump type - r
4.6.4 Settings temperature management system
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
TMS Setpoint Setpoint Temperature- 20 70 63 °C r/w
Management-System
Set Pump
Enter
Normal Operation
95 % Enter
Max. Accel. time
800 s Enter
Pump Type
MAG 1600/2000 CT
Enter
Set TMS
Enter
TMS Setpoint
60 °C
Enter
r (read) = value can only be read r /w (read/write) = value can be read and written
Page 56
Converter Control MAG.DRIVE L2
56
GA 05.130/3.02 - 05/98
4.6.5 Settings purge / vent
Menu item Description Adjustable value / option Ac-
cess
min. max. stan- Unit
value value dard
Purge / Vent The operator can select one Purge OFF - r/w
of the beside standing Purge ON ­options for purge and vent Controlling purge / vent
via control plug X1 -
Option P / V Displays the factory installed
option for purge and vent Installed option - r
Via X1
Purge ON
Set Purge/Vent
Enter
Purge/Vent Purge OFF
Enter
Option P/V
Option 1
Enter
r (read) = value can only be read r /w (read/write) = value can be read and written
Page 57
Converter Control MAG.DRIVE L2
57
GA 05.130/3.02 - 05/98
4.6.6 Total view of the menu
Programming menu
German
Vent
TMS ok
No Purge gas
No Cooling Water
Frequency
Set Converter
Enter
Motor Current
Option Relay
Bearing Temp.
Enter
Threshold
60 °C
Enter
Threshold
10.0 A
Enter
Threshold
300 Hz
Enter
Actual PZ12
Actual PVW24
Actual PVW13
Bearing Temp.
Actual Frequency
Analog Output
Motor Current
Enter
Scale factor
1.0 x
Enter
Freq. Setpoint
Analog Input 2
No Function
Enter
Start delay
0 s
Enter
Display
English
Enter
Bus address
0
Enter
Acoustic Alarm
Off
Enter
Selects the parameterization menu from the
operating display.
Switches forward to the next main menu.
Switches back to the last main menu.
Selects submenu.
Confirms to store changed parameters.
Increases a parameter value or switches
forward to the next option.
Reduces a parameter value or switches
back to the last option.
Starts the pump. Only possible from the
basic menu.
Stops the pump.
Return to the operating display from
parameterization menu.
START
STOP
ENTER
Stop
Data to Eeprom?
Stop=no Enter=yes
Enter
Ready
00.0 A 0000 Hz
Stop
Data are stored
in the EPROM
To exit the parameterization menu
Ready
0.0 A 0 Hz
Enter
Freq. Setpoint
480 Hz
Enter
Operation Hours
0.00 h
Enter
Motor Temp.
50 °C
Enter
Converter Temp.
40 °C
Enter
Bearing Temp.
50 °C
Enter
Actual PVW 13
10%
Enter
Actual PVW 24
10%
Enter
Actual PZ 12
5%
Enter
Power
400 W
Enter
Not Active
Actual Value TMS
63 °C
Enter
Not Active
Cooling Temp.
20 °C
Enter
Basic menu
Via X1
Purge ON
Set Pump
Enter
Normal Operation
95 %
Enter
Max. Accel. time
800 s
Enter
Pump Type
MAG 1600/2000 CT
Enter
Set TMS
Enter
TMS Setpoint
60 °C
Enter
Set Purge/Vent
Enter
Purge/Vent
Purge OFF
Enter
Option P/V
Option 1
Enter
ororor
Main menus
Software Version
103.04
Enter
or
Page 58
Converter Control MAG.DRIVE L
4.7. Temperature Manage­ment System
4.7.1 Temperature Management System for the MAG.DRIVE L
Function description
The TMS is only in function, when a MAG1600/2000 CT version is connected.The heater will be activated when the mains is switched on. The TMS (TCU) controls the heating and water cooling to maintain the pump at the specified setpoint temperature.
Settings
Principally the factory presettings will be used. The set­tings are saved in the pump’s memory chip.Before chan­ging any setpoint value request Leybold! The following parameters are progammable via the key panel or the serial interface when the pump stands still.
• Setpoint Temperature
• Warning Temperature
• Failure Temperature
For the settings refer to 4.5.5 Operating menu, Settings TMS.
Heat up
The setpoint temperature will be reached within 30 to 60 minutes depending on cooling water temperature and flow. If the flow is very high and the temperature low a high temperature setpoint might not be reached. For temperature sensitive applications observe the cooling water specifications (refer to section 1.6 Technical Data).
Actual temperature
The actual TMS is displayed on the operating display (refer to 4.5.1 Operating menu, Basic menu)
Signal TMS OK
If the actual TMS (TCU) temperature lies in the range ±5K from the setpoint temperature, the TMS OK signal can be output via the option relay. The option relay must be programmed for this function (refer to Section 2.8.3 Control plug X1, Relay outputs)
Warning message
If the actual temperature exceeds the warning tempera­ture the converter displays the message:
warning
TCU
Failure message
If the actual temperature exceeds the failure temperatu­re the converter displays the message:
failure
TCU
The pump is decelerated. After the pump has cooled down, the failure can be ackno wledged and the pump re­started.
58
GA 05.130/3.02 - 05/98
Page 59
Converter Control MAG.DRIVE L
59
GA 05.130/3.02 - 05/98
Setpoint Temp. T
Failure
Warning
Heater ON
Cooling ON
Signal TMS OK
Failure
Warning
T + 5 K T + 2 K
T - 5 K
T - 2 K
Fig. 46 Function diagram TMS for the MAG.DRIVE L
Page 60
Converter Control MAG.DRIVE L2
60
GA 05.130/3.02 - 05/98
4.7.2 Temperature Management System for the MAG.DRIVE L2
Function description
The TMS is only in function, when a MAG1600/2000 CT version is connected.The heater will be activated when the mains is switched on.The TMS controls the heating and water cooling to maintain the pump at the specified setpoint temperature.
Settings
The temperature (TMS) setpoint can be programmed via the front panel keys or the serial interface when the pump stands still.
Principally the factory presetting will be used.The setting is saved in the pump’s memor y chip. Before changing any setpoint value request Leybold!
For the setting refer to 4.6.4 Operating menu, Settings TMS.
Heat up
The setpoint temperature will be reached within 30 to 60 minutes depending on cooling water temperature and flow. If the flow is very high and the temperature low a high temperature setpoint might not be reached. For temperature sensitive applications observe the cooling water specifications (refer to section 1.6 Technical Data).
TMS status code
The TMS status code is displayed on the operation dis­play, see Section 4.2.
Actual temperature
The actual temperature is displayed on the oper ating dis­play (refer to 4.6.1 Operating menu, Basic menu)
Signal TMS OK
If the actual TMS temperature lies in the r ange ±5K from the setpoint temperature, the TMS OK signal can be out ­put via the option relay. The option relay must be pro­grammed for this function (refer to Section 2.8.3 Control plug X1, Relay outputs)
Warning message (Temp > T
set
+5K)
If the actual temperature exceeds the warning tempera­ture the converter displays the message:
Warning
TMS
Page 61
Converter Control MAG.DRIVE L2
61
GA 05.130/3.02 - 05/98
T - 5 K
T - 2 K
T + 2 K
T + 5 K
2)
2)
T + 15 K
1)
1 2
3
2 3
4
3 2 2 133
4 455
Sollwert TMS
TMS Code Heizung EIN Kühlung EIN
TMS OK
Warnung TMS
Störung TMS
1) The TMS status code is displayed on the operation display;see Section 4.2.
2) Heater or cooling active
Fig. 47 Function diagram TMS for the MAG.DRIVE L2
Setpoint temp.T
TMS Code Heater ON
Cooling ON
TMS ok
Warning Temp.TMS
Failure TMS 5
Page 62
5 Maintenance
The MAG is maintenance-free. Wear only occurs at the touch-down bearings when hard shocks have to be sup­ported or when the pump frequently runs down without venting.
Maintenance is also required after removing the bearing cable during operation of the pump.
Under these conditions the rotor can not be controlled by the magnet bearing and the pump will have a full run down on the touch down bearing.
5.1 Removing the pump from the system
MAG which hav e been used in semiconductor processes are contaminated by semiconductor process gases. Most of these gases form acids when exposed to moist air which causes serious corrosion damage to the pump.
To prevent corrosion damage during storage and ship­ping, use the seal kit.
Failure to seal a contaminated MAG voids the warranty. The seal kit contains the following
- dry car tr idge,
- plastic cap for forevacuum connection flange,
- plastic adhesive film and
- aluminum cover and screws for the high-vacuum
connection flange.
Proceed as follows to seal the turbomolecular pump immediately after removing it from your process.
Purge the pump for two hours with the backing pump running. This helps to remove a large quantity of the pro­cess gases from the pump.We recommend purging the pump via the intake flange and the purge valve with approx. 200 sccm.
Press the STOP button at the MAG.DRIVE and wait until the pump has come to a standstill.
Afterwards turn the mains switch to the „0“ position. The cables between the MAG and MAG.DRIVE may be
disconnected only after the MAG has come to a full still­stand and the mains is switched off.
Warning
When the pump has been pumping hazar­dous gases, ensure that proper safety pre­cautions are taken before opening the inta­ke or exhaust connections.
Use gloves or protective clothing to avoid skin contact with toxic or highly corrosive substances. Work under a fume hood if available.
Disconnect the cables from the pump. Disconnect the forevacuum line. Disconnect the cooling water lines. Remaining cooling
water may flow out.Protect all par ts below. Remove 10 of the 12 bolts which hold the intake flange.
The 2 remaining bolts must be directly opposite. Support the pump with a lift-truck at the base plate and
remove the 2 remaining bolts. Clean the intake and forevacuum connection flange as
necessary for good adhesion of tape. Place the dry cartr idge into the forevacuum port. Don’t
use loose crystals. Firmly seal all ports with plastic adhesive film. Cover the forevacuum connection port with its plastic
cap. Seal the high-vacuum connection flange with the cover
and the screws. Pack the pump so that it may not be damaged during
transportation. Particularly protect the flanges, the coo­ling water connectors and the current feedthrough.
Only for MAG 1600
As the plastic adhesive film is too large for the high-v acu­um connection flange slit it a little bit at the screw holes.
GA 05.130/3.02 - 05/98
Maintenance
62
Page 63
Maintenance
63
GA 05.130/3.02 - 05/98
Fig. 48 Sealing the MAG tightly
ring nut (2x)
aluminum cover
plastic adhesive film
washer (6x)
screw (6x)
nut (4x)
dry cartridge
plastic adhesive film
plastic cap
Page 64
Maintenance
64
GA 05.130/3.02 - 05/98
5.2 Service at Leybold’s
If you send a pump to Leybold indicate whether the pump is free of substances damaging to health or whether it is contaminated.If it is contaminated also indi­cate the nature of hazard.To do so, you must use a pre­printed form which we shall send to you upon request.
A copy of this form is printed at the end of the Operating Instructions: „Declaration of Contamination of Vacuum Equipment and Components“.
Either fasten this form at the pump or simply enclose it to the pump.
Don’t pack the form with the pump into the PE bag. This declaration of contamination is necessary to comp-
ly with legal requirements and to protect our staff. Leybold must return any pump without a declaration of
contamination to the sender’s address.
Page 65
6 Troubleshooting
In case of a malfunction, the MAG will be braked and the first line of the display shows
FAILURE
Malfunction messages can be cancelled once the pump has come to a stop and after the malfunction has been rectified; do so with the STOP function (button or serial interface).
Warning
The MAG shall be stopped completely and the mains power cord detached before you open the MAG.DRIVE. Since dangerous voltages may nonetheless be encountered, the housing must be opened only by a qua­lified electrician.
Troubleshooting
65
GA 05.130/3.02 - 05/98
Page 66
Troubleshooting for the MAG.DRIVE L
66
GA 05.130/3.02 - 05/98
Warning/Failure Message on Display
Temp. Motor
Temperature sensor inside the motor reads a higher temperature than the limitati­on.
temp. pump
Temperature sensor inside the pump reads a higher temperature than the limitati­on.
temp. cool. water
Temperature sensor at coo­ling water block reads a hig­her temperature than the limitation.
TCU
Temperature sensor at base flange reads a higher tempe­rature than the limitation.
temp. converter
Temperature sensor inside of the converter reads a higher temperature than the limitati­on (65 °C).
unbalanc. PVW13 unbalanc. PVW24 unbalanc. PZ12
Converter senses that rotor displacement has exceeded the limitation.
Corrective Action
Check BEARING connector and cable. Measure resistance of KTY (temperature sensor motor) at BEARING connector (pump side) between X23/x - X23/w, default
2kΩ ± 1 %. Service pump.
Set cooling water according to specificati­ons. Check cooling lines for deposits. See Section 2.6.
Check cable, Pt 100 wires and connector. In particular measure resistance between X23/v - X23/u and X23/v - X23/t, typical resi­stances are in the range of 110 Ω to 130 Ω at 20 °C to 70 °C.
Set cooling water according to specificati­ons. Check cooling lines for deposits. See Section 2.6.
Check TMS cable, Pt 100 wires and connec­tor.In par ticular measure resistance bet­ween X30/V - X30/S, typical resistances are in the range of 110 Ω to 130 Ω at 20 °C to 70 °C.
Set cooling water according to specificati­ons. Check cooling lines for deposits. See Section 2.6.
Check TMS cable, Pt 100 wires and connec­tor.In par ticular measure resistance bet­ween X30/F - X30/H and X30/F - X30/G, typical resistances are in the range of 110 Ω to 130 Ω at 20 °C to 70 °C.
If temperature sensor TMS (Pt 100) is ok,unplug it.The water valve should open instantly with a clicking noise and the red LED inside the valve connector lights up.
Let the converter cool down and restart. Check mounting position and clearences
inside the rack. See Section 2.8.Check ambient temperature and watch for other heat sources.
Acknowledge failure by by pressing stop and try to restart pump.
Check unbalance PV13 / PW24 / PZ12 rea­ding via display (basic menu) during accelle­ration. Check BEARING connector and cable for bended pins.
Check the chamber pressure in the operati­on cycle. Remove transport seal; see Sec­tion 2. 4.
Replace pump or converter or whole system.
Possible Cause
BEARING cable or connector damaged.
Drive failure.
No or too low cooling water.
BEARING cable or connector damaged. Pt 100 (temp.sensor bear ing) damaged.
No or too low cooling water.
Temperature sensor cooler (Pt 100) failure. TMS cables damaged.
No or too low cooling water.
Temperature sensor TMS (Pt 100) failure or TMS cable or connectors damaged.
Water valve malfunction.
Frequent run up and down. No sufficient air circulation.
Mechanical shocks, perhaps due to tool maintenance.
BEARING cable or connector damaged.
High active magnetic bearing current due to shock venting or transport seal not removed.
Internal failure.
6.1 Troubleshooting for the MAG.DRIVE L
6.1.1 Warning and failure messages
Page 67
Troubleshooting for the MAG.DRIVE L
67
GA 05.130/3.02 - 05/98
Failure Message on Display
MB-Code wrong
Converter senses that magnetic bearing is not active.
no motor current
max. accel.Time
The maximum acceleration time has been exceeded.
max. power time
Rotational speed dropped below normal operation range for more than the max. accel. time.
min. frequency
Rotational speed dropped below the minimum frequen­cy threshold.
Corrective Action
Replace converter.
Check cables and connectors, straighten pins if required.
Replace pump.
Check pressures.
Set parameter max. Accel.time to default 1000 s. See Section 4.5.3/4.6.3 Settings pump.
Check pressures.
Set parameter max. Accel.time to default 1000 s. Set parameter Normal Operation to default 95 %. See Section 4.5.3/4.6.3 Settings pump.
Check pressures.
Possible Cause
Internal fuse for power supply active magne­tic bearing PC boards blown.
Overloaded active magnetic bearing. BEARING cable connected while the con-
verter was powered.
DRIVE cable not connected or damaged. Connectors damaged or pins have no contact.
Motor coils damaged.
Backing pressure or inlet pressure too high during start-up.
Parameter max.Accel. time is not set pro­perly.
Backing or inlet pressure too high. Process flows too high.
Parameters max.Accel. time or Normal Operation not set properly.
Backing or inlet pressure too high. Process flows too high.
6.1.2 Failure messages
Page 68
Troubleshooting for the MAG.DRIVE L
68
GA 05.130/3.02 - 05/98
Warning Message on Display
PK communication
Converter does not commu­nicate with the memory chip inside of the pump.
max. power
max. frequency
Kin. Buffer
The converter works in generator mode.
Corrective Action
Check BEARING cable and connectors.
Replace pump.
Check pressures.
Set parameter max. Accel.time to default
1000 s.
Set parameter Normal Operation to default
95 %.
See Section 4.5.3/4.6.3 Settings pump.
Motor current decreases to 0 Amp.The rotor
frequency decreases to the normal operati-
on range via gas friction.
Switch the mains power on. Locate and eli-
minate the cause of the mains failure.The
pump should handle numerous power failu-
res.
Possible Cause
BEARING cable not connected or damaged. Memory chip inside magnetic bearing car-
tridge is damaged.
Backing or inlet pressure too high. Process flows too high.
Parameters max.Accel. time or Normal Operation not set properly.
Frequency exceeds the setpoint for more than 2 Hz.
Mains power off.
6.1.3 Warning messages
Page 69
Troubleshooting for the MAG.DRIVE L
69
GA 05.130/3.02 - 05/98
Malfunction
Converter dead, nothing happens after mains swit­ched on.
Display malfunction, confu­sing failure messages.No reaction when pressing keys.
Leaks of the vacuum cham­ber while the pump is stop­ped.
No purge gas flow
Pump does not accelerate to more than 16 Hz
Base pressure not reached.
MAG does not heat up.
Display becomes blurred.
Corrective Action
Check if the green LED above the mains switch lights up.Check mains cable and connectors. Check power supply.
Replace converter.
Replace converter.
Open and close purge gas and venting valve via control plug X1. LED on the valve must light up and a clicking noise can be heard. Foreline pressure drops while the valve is closed.
Set purge flow according to specification. Open and close purge gas and venting valve
via control plug X1. LED on the valve must light up and a clicking noise can be heard. Foreline pressure drops while the valve is closed.
Compare pump type (label on the pump) with parameter setting. Refer to Section
4.5.3/4.6.3 Settings pump.
Check pressures. Replace converter or pump or whole
system.
Let the pump system run for 3 to 5 hours to reach a base pressure below 10-5mbar.
Check TMS setpoint.Default 63 °C. Refer to Section 4.5.5.
Replace fuse (F 4 A, 5x20 mm).
Measure resistance of heater, typical approx. 70 Ω (connector pump side X30/A and X30/B).
Measure resistance between pins X31/A1 and X31/A2 at TMS cable when pump is connected.
It’s just the display. It becomes distinct at moderate temperatures.
Possible Cause
No power supply.
Fuse F1 blown.
Internal failure.
Purge gas and venting valve open or mal­functioning.
No purge gas flow. Valve malfunction.
Wrong setting in the programming menu: Settings pump: pump type
No vacuum at all. Internal converter or pump failure.
Degassing surfaces of rotor and stator. If the pump was not stored in a dry environment or was too long open to wet ambient air all internal surfaces will be covered with a layer of water.
Wrong setting TMS setpoint.
Fuse F3 at rear panel of converter blown or damaged.
TMS heater jacket defective.
TMS cable or connectors damaged.
Converter temperature high or very low.
6.1.4 Malfunctions
Page 70
Troubleshooting for the MAG.DRIVE L2
70
GA 05.130/3.02 - 05/98
Warning Message on Display
Motor Temp.
Temperature sensor inside the motor reads a higher temperature value than the warning threshold (100 °C).
Message will not be activa­ted as long as warning thres­hold = failure threshold.
Bearing Temp.
Temperature sensor inside the pump reads a higher temperature value than the warning threshold (68 °C).
Cooling Temp.
Temperature sensor at coo­ling water block reads a hig­her temperature value than the warning threshold (40 °C).
Converter Temp.
Temperature sensor inside of the converter reads a higher temperature value than the warning threshold (69 °C).
Overspeed
The frequency exceeds the frequency setpoint by more than 10 Hz.
TMS
TMS temperature sensor reads a temperature higher than the TMS setpoint +5 °C.
Unbalanc. PVW13 Unbalanc. PVW24 Unbalanc. PZ12
A rotor displacement excee­ding the warning threshold occured.The code designa­tes the affected axis.
Overload
The rotational speed drop­ped below normal operation frequency.
Measures
Take the actual motor temperature reading
from the display; see Section 4.6.1.
Reduce gas load. If the warning persists contact Leybold service.
Contact Leybold service.
Apply cooling water according to specificati­ons. Check cooling water tubes for deposits. See also Section 2.6.
Allow pump to cool down between the cycles.
Apply cooling water according to specificati­ons. Check cooling water tubes for deposits. See also Section 2.6.
Allow converter to cool down between the cycles.
Refer to Section 2.8 for the correct mounting
of the converter in a rack; max.ambient tem-
perature 45 °C.
Motor current decreases to 0 Amp.The rotor
frequency decreases to the setpoint via gas
friction.
Apply cooling water according to specificati-
ons. Check cooling water tubes for deposits.
See also Section 2.6.
Check the TMS setpoint (default 63 °C). For
the correct setting refer to Section 4.6.4.
If warning message persists contact Leybold
service.
Check the chamber pressure during operati-
on.
Contact Leybold service.
Reduce backing pressure.Additionally, check process gas flow.
Set parameter „Normal Operation“ to default 95%. Refer also to Section 4.6.3.
Possible Cause
Motor temperature exceeds the warning threshold e.g. due to a high gas load.
Drive failure or internal converter failure.
Cooling water flow too low or cooling water temperature too high.
Frequent acceleration and deceleration of the pump.
Cooling water flow too low or cooling water temperature too high.
Frequent acceleration and deceleration of the pump.
No sufficient air circulation.
Changing the frequency setpoint during ope­ration to a lower value.
Cooling water flow too low or cooling water temperature too high.
Wrong TMS temperature setpoint.
Mechanical shocks, perhaps due to tool maintenance.
Shock venting.
Converter failure.
Backing pressure too high during operation. Parameters „Normal Operation“ are not set
correctly.
6.2 Troubleshooting for the MAG.DRIVE L2
6.2.1 Warning messages
Page 71
Troubleshooting for the MAG.DRIVE L2
71
GA 05.130/3.02 - 05/98
Warning Message on Display
Kinetic Buffer
The converter is in the gene­rator mode.
Op.Without Purge
The warning indicates that a C/CT type of pumpis opera­ted while the purge gas valve is closed.
Measures
Reconnect converter to the mains. Switch on the converter.
Set purge gas function to Purge ON. (Key panel or control connector X1).
Possible Cause
Mains interrupted or converter switched off during operation of the pump.
Purge gas function disabled.
Page 72
Troubleshooting for the MAG.DRIVE L2
72
GA 05.130/3.02 - 05/98
Failure Message on Display
Motor Temp.
Temperature sensor inside the motor reads a higher temperature value than the failure threshold (100 °C).
Cooling Temp.
Temperature sensor at coo­ling water block reads a hig­her temperature value than the failure threshold (50 °C).
Measures
Acknowledge failure message. Take the actual motor temperature reading from the
display; see Section 4.6.1. Reduce gas load. If the warning persists contact Leybold service.
Step 1: Check pump (temperature sensor)
Check pump connector X23. In particular measure resistance between pins X23/x and X23/w.The resistance is typically 2kΩ ± 1 %. In case of abnor­mal values (> 3.4 kΩ) are measured contact Ley­bold service.
Step 2: Check BEARING cable
If step 1 was successful do the following: Check BEARING cable for bent pins
Measure the resistance between pins X24/A9 and X24/B9 with the cable connected to the pump.The resistance is typically 2kΩ ± 1 %.
Replace the cable if it is damaged or in case the measurement of the resistance shows abnormal values (> 3.4 kΩ) now.
Contact Leybold service.
Apply cooling water according to specifications. Check cooling water tubes for deposits. See also Section 2.6.
Step 1: Check cooling water temperature sen­sor
Check pump connector X30. In particular measure resistance between pins X30/S and X30/V. The resistance is typically between 110 Ω and 130 Ω (20 °C to 70 °C).
Step 2: Check TMS cable and connectors
If step 1 was successful do the following: Check TMS cable for bent pins
Measure the resistance between pins X31/A4 and X31/A5 with the TMS cable connected to the pump. The resistance is typically between 110 Ω and 130 Ω (20 °C to 70 °C).
Replace TMS cable if it is damaged or in case the measurement of the resistance shows abnormal values now.
Contact Leybold service.
Possible Cause
Motor temperature exceeds the failu­re threshold e.g. due to a high gas load.
Motor temperature sensor defective.
BEARING cable or connector dama­ged.
Converter failure.
Cooling water flow too low or cooling water temperature too high.
Pt 100 (cooling water temperature sensor) damaged.
TMS cable or connectors damaged.
Converter failure.
6.2.2 Failure messages
Page 73
Troubleshooting for the MAG.DRIVE L2
73
GA 05.130/3.02 - 05/98
Failure Message on Display
Bearing Temp.
Temperature sensor inside the pump reads a higher temperature value than the failure threshold (70 °C).
Converter Temp.
Temperature sensor inside of the converter reads a higher temperature value than the failure threshold (74 °C).
TMS 1
The converter measures a heating current of less than 300 mA when heater is on.
Measures
Apply cooling water according to specifications. Check cooling water tubes for deposits. See also Section 2.6.
Allow pump to cool down between the cycles.
Step 1: Check pump (temperature sensor)
Check pump connector X23. In particular measure resistance between pins X23/v and X23/u as well as between pins X23/v and X23/t.The resistance is typically between 110 Ω and 130 Ω (20 °C to 70 °C). In case abnormal values are measured contact Leybold service.
Step 2: Check BEARING cable
If step 1 was successful do the following: Check BEARING cable for bent pins
Measure the resistance between pins X24/B7 and X24/C7 as well as between pins X24/B7 and X24/D7 with the cable connected to the pump.The resistance is typically between 110 Ω and 130 Ω (20 °C to 70 °C).
Replace the cable if it is damaged or in case the measurement of the resistance shows abnormal values now.
Contact Leybold service.
Allow converter to cool down between the cycles.
Refer to Section 2.8 for the correct mounting of the converter in a rack; max.ambient temperature 45 °C.
Contact Leybold service.
Acknowledge TMS 1 failure message (possibly several times).
Step 1: Check fuse
Replace fuse F3 (F4A, 5x20 mm) if blown.
Step 2: Check pump (heating element)
Check if the connector of the heating element is connected.
Check pump connector X30. In particular measure resistance between pins X30/A and X30/B.The resistance is typically between 70 Ω and 75 Ω. In case abnormal values are measured contact Ley­bold service.
Step 3: Check TMS cable
If step 2 was successful do the following: Check TMS cable for bent pins
Measure resistance between pins X31/A1 and X31/A2 with the cable connected to the pump.The resistance is typically between 70 Ω and 75 Ω.
Replace the cable if it is damaged or in case the measurement of the resistance shows abnormal values now.
Contact Leybold service.
Possible Cause
Cooling water flow too low or cooling water temperature too high.
Frequent acceleration and decelerati­on of the pump.
Pt 100 (temperature sensor bearing) damaged.
BEARING cable or connectors dama­ged.
Converter failure.
Frequent acceleration and decelerati­on of the pump.
No sufficient air circulation.
Converter failure.
A TMS 2 ...5 failure occured and was subsequently acknowledged.
Fuse F3 (rear panel) blown.
Heating element or internal pump connection damaged.
TMS cable or connectors damaged.
Converter failure.
Page 74
Troubleshooting for the MAG.DRIVE L2
74
GA 05.130/3.02 - 05/98
Failure Message on Display
TMS 2
The converter measures a heating current of more than 4 A.
TMS 3
TMS temperature sensor reads a temperature higher than 99 °C.
TMS 4
TMS temperature sensor reads a temperature lower than 1 °C.
TMS 5
TMS temperature sensor reads a temperature higher than the TMS setpoint + 15 °C.
Measures
Check the line voltage (200-240 V +10% / -15%). Repeat step 2of failure TMS 1. In case the measu-
red value is less than 60 Ω contact Leybold servi­ce.
Contact Leybold service.
Step 1: Check TMS sensor
Check pump connector X30. In particular measure resistance between pins X30/F and X30/H as well as between pins X30/F and X30/G.The resistance is typically between 110 Ω and 130 Ω (20 °C to 70 °C).
Step 2: Additional TMS sensor test
If temperature sensor TMS (Pt 100) has the correct resistance, unplug it while the pump is on power. The water valve should open instantly with a clicking noise and a red LED inside the cooling water valve connector lighting up.This LED should be on if the actual TMS temperature is higher than the TMS setpoint + 2 °C.
Contact Leybold service if the sensor is defective.
Step 3: Check TMS cable
Check TMS cable connector X31. In particular measure resistance between pins X31/A8 and X31/C8 as well as between pins X31/A8 and X31/B8.The resistance is typically between 110 Ω and 130 Ω (20 °C to 70 °C).
Contact Leybold service if the TMS cable is dama­ged.
Contact Leybold service.
Repeat steps 1 and 2 of failure TMS 3. Contact Leybold service if the sensor is defective.
Repeat step 3 of failure TMS 3. Contact Leybold service if the cable is damaged.
Contact Leybold service.
Apply cooling water according to specifications. Check cooling water tubes for deposits. See also Section 2.6.
Repeat step 2 of failure TMS 3. Contact Leybold service if cooling water valve is malfunctioning.
Check the TMS setpoint (default 63 °C). For the correct settings refer to Section 4.6.4.
Possible Cause
Overvoltage. Heating element defective.
Converter failure.
TMS sensor damaged.
TMS cable damaged.
Converter failure.
TMS sensor short-circuited.
TMS cable short-circuited.
Converter failure.
Cooling water flow too low or cooling water temperature too high.
Cooling water valve malfunctioning.
Wrong TMS temperature setpoint.
Page 75
Troubleshooting for the MAG.DRIVE L2
75
GA 05.130/3.02 - 05/98
Failure Message on Display
Overload PZ 12 Overload PV 13 Overload PW 24
An abnormal displacement ot the rotor occured at fre­quencies between 0 and 5 Hz.The code designates the affected axis.
MB MB, Purge ON MB, Purge OFF
An abnormal displacement ot the rotor occured at fre­quencies between 130 Hz and 480 Hz.
The additional message gives information on the sta­tus of the purge gas valve the moment the failure occu­red. It can be used to esti­mate the run down time of the pump.
PK Communication
Converter does not commu­nicate with the memory chip inside of the pump.
MB-Code Wrong
Magnetic bearing controller does not work.
Starting Time
The frequency has not rea­ched 40 Hz 2 minutes after the start command was applied.
Accel.Time
The pump does not reach the normal operation fre­quency after the set maxi­mum acceleration time.
Overload Time
The rotational speed has dropped below normal ope­ration frequency and stays there for longer than the maximum „Accel.Time“.
Shutdown Freq.
Rotational speed dropped below the shutdown frequen­cy threshold (140 Hz).
Measures
Acknowledge failure message and restart the pump.If failure message persists contact Leybold service.
Remove transport seal; see Section 2.4.
Check BEARING connector and cable for bent pins. Contact Leybold service if the cable is damaged.
Acknowledge failure message and restart the pump.If failure message persists contact Leybold service.
Check the chamber pressure during the operation. Refer to Section 3.3 for correct venting of the pump.
Contact Leybold service.
Check BEARING connector and cable for damages or bent pins. Contact Leybold ser­vice if the cable is damaged.
Contact Leybold service.
Contact Leybold service.
Reduce backing pressure. Check if the rotor rotates freely. Contact Ley-
bold service if the rotor is damaged or blocked.
Reduce backing pressure. Set parameter „Accel.Time“ to default 1000
s; see Section 4.6.3.
Reduce backing pressure.Additionally check process gas flow.
Set parameter „Normal Operation“ to default 95 % and parameter „Accel.Time“ to default 1000 s; see Section 4.6.3.
Reduce backing pressure.Additionally check process gas flow.
Possible Cause
Mechanical shocks, possibly due to tool maintenance whwn the rotor stands still.
Pump is still protected with transport seal on power up.
BEARING cable or connector damaged.
Mechanical shocks, possibly due to tool maintenance.
Shock venting.
Converter failure.
BEARING cable not connected or damaged.
Memory chip inside of magnetic bearing car­tridge malfunctioning.
Converter failure.
Backing pressure too high during start-up. Rotor blocked.
Backing pressure too high during start-up. Parameter „Accel.Time“ is not set correctly.
Backing pressure too high during operation.
Parameters „Accel.Time“ or „Normal Opera­tion“ are not set correctly.
Backing pressure too high during operation.
Page 76
Troubleshooting for the MAG.DRIVE L2
76
GA 05.130/3.02 - 05/98
Failure Message on Display
Cooling Temp. SC
The cooling water tempera­ture sensor reads a tempera­ture lower than 1 °C.
Bearing Temp. SC
The magnetic bearing tem­perature sensor reads a tem­perature lower than 1 °C.
Motor Temp. SC
The motor temperature sen­sor reads a temperature lower than 1 °C.
Connection pump
Frequency
Abnormal motor current or frequency
Measures
Repeat step 1 of „failure Cooling Temp.“.
Contact Leybold service if the resistance of
the sensor is less than 100 Ω.
Repeat step 2 of „failure Cooling Temp.“.
Contact Leybold service if the resistance of the sensor is less than 100 Ω.
Contact Leybold service.
Repeat step 1 of „failure Bearing Temp.“. Contact Leybold service if the resistance of the sensor is less than 100 Ω.
Repeat step 2 of „failure Bearing Temp.“. Contact Leybold service if the resistance of the sensor is less than 100 Ω.
Contact Leybold service.
Repeat step 1 of „failure Motor Temp.“. Contact Leybold service if the resistance of the sensor is less than 1.62 kΩ.
Repeat step 2 of „failure Motor Temp.“. Contact Leybold service if the resistance of the sensor is less than 1.62 kΩ.
Contact Leybold service.
Check if the BEARING cable is connected to the pump and the converter.Acknowledge failure message.
Contact Leybold service.
Check cables and connectors, straighten pins if required.
Acknowledge failure message;see Section
4.4. If failure persists contact Leybold servi­ce.
Acknowledge failure message and restart the pump.
Possible Cause
Temperature sensor Pt 100 shor t-circuited.
TMS cable short-circuited.
Converter failure.
Temperature sensor Pt 100 shor t-circuited.
BEARING cable short-circuited.
Converter failure.
Temperature sensor KTY shor t-circuited.
BEARING cable short-circuited.
Converter failure.
BEARING cable not connected.
Converter failure.
On START command: DRIVE cable not connected or connectors damaged.
The rotor frequency exceeds 515 Hz.
A STOP commend followed by a START command given while the warning „Over­speed“ is displayed.
Page 77
Troubleshooting for the MAG.DRIVE L2
77
GA 05.130/3.02 - 05/98
Malfunction
Converter dead, LED „mains“ does not light up after switching on.
Display malfunction, confu­sing messages. No reaction when pressing keys.
Vacuum chamber pressure rises above normal backing pressure while the pump is stopped.
No purge gas flow
Base pressure not reached.
MAG 1600/2000 CT does not heat up.
Display blurred.
Measures
Check the line voltage. Contact Leybold service.
Switch the converter off and on again. If the converter still malfunctions contact Leybold service.
Open and close purge gas and/or venting valve via control plug X1.LED on the valve must light up and a clicking noise can be heard. Foreline pressure drops while the valve is closed.
Set purge flow according to specification. Open and close purge gas and venting valve via control plug X1. LED on the valve must light up and a clicking noise can be heard. Foreline pressure drops while the valve is closed.
Leave the pump system run for 3 to 5 hours to reach a pressure below 10-5mbar.
See TMS failures.
Operate the converter according to the spe­cifications.
Possible Cause
No power supply. Fuse F1 blown or converter failure.
Converter failure.
Purge gas and venting valve open or mal­functioning.
Valve malfunctioning.
Degassing surfaces of rotor and stator. If the pump was stored in a humid environment or was exposed to humid ambient air all surfa­ces will be covered with condensation.
TMS failure.
Ambient temperature too high or too low.
6.2.3 Malfunctions
Page 78
Certifications
78
GA 05.130/3.02 - 05/98
EC declaration of manufacture
in accordance with Art. 4 paragraph 2 of EC directive 89/392/EEC changed by 91/368EEC and 93/44/EEC, Appendix IIB
Document No.: MSR0196 / MAG.DRIVE L Manufacturer: REFU elektronik GmbH Product Identification: MAG.DRIVE L2 Catalog No.: 857 24
The product indicated solely for fitting in anorther machine.Commissioning is prohibited until the conformity of the end product with EC directive 89/392/EEC has been established.
Standards applied: EN 60204-1 (DIN VDE 0113 part 1)
EN 61010-1 (DIN VDE 0411 part 1)
1.10. 1997 REFU elektronik GmbH
...................................................
H. Baumann President
The savety notes given in the product documentation must be observed.
Page 79
Certifications
79
GA 05.130/3.02 - 05/98
EC declaration of conformity
Document No.: MSR0196 / MAG.DRIVE L Manufacturer: REFU elektronik GmbH Product Identification: MAG.DRIVE L2 Catalog No.: 857 24
Herewith, we declare that this product, as a result of ist design and type of construction, and the version marketed by us, correspond to the basic health and safety regulations specified in the EEC Directives.
This declaration is no longer valid if the product is modified without us being in full agreement.
The product conforms to the EEC Low-Voltage Directive (73/23/EEC).
Standards applied: EN 61010-1 (DIN VDE 411 Teil 1) Edition 1994-03
Display the CE-mark: 1997
1.10. 1997 REFU elektronik GmbH
...................................................
H. Baumann President
The savety notes given in the product documentation must be observed.
Page 80
Certifications
80
GA 05.130/3.02 - 05/98
Factory certificate
Document No.: MSR0196 / MAG.DRIVE L Manufacturer: REFU elektronik GmbH Product Identification: MAG.DRIVE L2 Catalog No.: 857 24
The named product, when put to ist intended use, satisfies the requirements of Directive 89/336/EEC concerning electromagnetic compatibility.
The applicable measurements were made taking into account the following standards:
EN 500 81-1 EN 500 82-2 EN 55011 (DIN VDE0875 Teil 1) EN 61000-3-2 EN 61000-3-3
Note
Attention must be paid to the information provided on proper installation with respect to elektromagnetic compatibility and to other pertinent notes in the documentation supplied with the product, as well as to the relevant informa­tion concernning electrical connection.
1.10. 1997 REFU elektronik GmbH
...................................................
H. Baumann President
The savety notes given in the product documentation must be observed.
Page 81
81
GA 05.130/3.02 - 05/98
Form TMP-1 … Turbopump Field Failure Report
Field Service IR No.: RMA No. (if returning to factory): Service Center: Customer: Turbopump Model: Turbopump Pump Part Number: Turbopump Serial Number: Complaint:
Process: OEM Equipment Name and Model: Process Gas: Was the turbopump replaced? ❐ Yes; ❐ No. If yes, replacement pump P/N: replacement pump S/N: Date Installed: Date Removed: Date Received: Date Examined: Examined by: Received Condition:
Findings:
Cause of Failure:
Recommendations:
Remarks/Questions:
LEYBOLD AG
Fax to:Service LV Fax#:(0049) 221 347 1945
LEYBOLD VACUUM
Page 82
GA 05.130/3.02 - 05/98
82
S A M P L E
Declaration of Contamination of Vacuum Equipment and Components
The repair and/or service of vacuum equipment and components will only be carried out if a correctly completed declaration has been submitted. Non-completion will result in delay. The manufacturer could refuse to accept any equipment without a declara­tion. This declaration can only be completed and signed by authorized and qualified staff.
1. Description of Vacuum Equipment and Com­ponents
- Equipment type/model: _________________________________
- Code No.: _________________________________
- Serial No.: _________________________________
- Invoice No.: _________________________________
- Delivery date:
__________________________
2. Reason for Return
____________________________________________ ____________________________________________ ____________________________________________ ____________________________________________
____________________________________________ ____________________________________________
3. Condition of the Vacuum Equipment and Com­ponents
- Has the equipment been used?
yes
❒ no ❒
- What type of pump oil/liquid was used? _________
- Is the equipment free from potentially
harmful substances?
yes ❒ (go to Section 5) no ❒ (go to Section 4)
4. Process related Contamination of Vacuum Equipment and Components:
- toxic yes ❒ no ❒
- corrosive yes ❒ no ❒
- explosive*) yes ❒ no ❒
- biological hazard*) yes ❒ no ❒
- radioactive*) yes ❒ no ❒
- other har mful substances yes ❒ no ❒
*) Vacuum equipment and components which have been contaminated by biological e xplosiv e or r adioactiv e substances , will
not accepted without written evidence of decontamination!
Please list all substances, gases and by-products which may have come into contact with the equipment:
Trade name Product name Chemical name Dangerous Measures First aid in case of Manufacturer (or Symbol) material class if spillage human contact
1.
2.
3.
4.
5.
Copies: Page 1 (white) to manufacturer or representative - Page 2 (yellow) attach to consignment packaging securety - Page 3 (blue) copy for file of sender
5. Legally Binding Declaration
I hereby declare that the information supplied on this form is complete and accurate.The despatch of the contaminated vacuum equipment and components will be in accordance with the appropriate regulations covering Packaging, Transpor­tation and Labelling of Dangerous Substances.
Name of organisation or company:_____________________________________________________________________ Address: _____________________________ Post code:______________________________________ Tel.: ______________________________________________________________________________ Fax: _____________________________ Telex: _________________________________________ Name: ______________________________________________________________________________ Job title: ______________________________________________________________________________ Date: _____________________________ Company stamp:
Legally binding signature:____________________________________________________________________________
Copyright © 1991 by MaschinenbauVerlag GmbH, Lyoner Straße 18, 6000 Frankfurt/M. 71 Order No.: 2121
Page 83
Notes
83
GA 05.130/3.02 - 05/98
Page 84
LEYBOLD VAKUUM GmbH
Bonner Strasse 498 (Bayenthal) D-50968 Cologne
Tel.: + 49 (221) 347-0 Fax: + 49 (221) 347-1250 http://www.leyboldvac.de e-mail:[email protected]
80000740 05.98 RSP Printed in Germany on chlorine-free bleached paper Technical alterations reserved
Loading...