Leviton D4104-1LW Installation Guide

Page 1
Leviton Manufacturing, Inc. Lighting Managment Systems Division 20497 SW Teton, Tualatin, Oregon, 97062
800.736.6682 - Customer Service
800.959.6004 - Technical Support
InstallationInstructions Dimensions4000seriesarchitecturalcontroller
Revision B, April 2008 # PK-93425-10-00-0B
Itemsrequiredforinstallation
1. Suitable Backbox
• Preferred 4 gang ‘Gang Box’, Raco #943 Leviton P/N BBG04-000
• 5 gang device backbox
2. Appropriate backbox device plate
• Raised cover for 4 gang gang box Leviton P/N WPG04-00R
• 4 gang reducer “mud ring” for 5 gang device backbox
3.
D4006, D4104, D4106, D4206 D4200
• Input power (see specs)
• Output to loads
• Optional Luma-Net network connection
• Luma-Net network connec­tion
GeneralInstallationSteps
1. Read all installation instructions and plan entire system
2. Determine location for device and install the appropriate backbox
D4006, D4104, D4106, D4206 D4200
3. Connect input power.
4. Connect power to loads.
5. Make connections to net­work (if applicable.)
6. Inspect wiring.
7. Install device in wall.
8. Power up and test system.
9. Confi gure.
3. Make network connections.
4. Inspect wiring.
5. Install device in wall.
6. Power up & test system.
7. Confi gure.
SPECIFICATIONS
Power Input
(D4200 N/A)
120VAC 60hz, 10% tolerance
230VAC 50/60hz, 10% tolerance
Power Output
(D4200 N/A)
• 1000 Watts max per zone, minimum load 15W per zone
• 1200 Watts max per side
• 1920 Watts max per device
• 800 Watts max per zone, minimum load 15W per zone
• 1200 Watts max per side
• 2400 Watts max per device
Supported load Types
(D4200 N/A)
• Incandescent
• Tungsten
• Magnetic Low Voltage
• 2-Wire Fluorescent (Advance Mark 10, Lutron Tu-Wire)
• Electronic Low Voltage when rated for use with forward phase dimmers
• Neon / Cold Cathode
• Non-dim loads
Listings & Certifi cations
• UL/cUL
• California Title 24
• FCC Part 15, Class A
Not for use in North America
Environmental
0°-40°C <= 90% non-condensing humidity
Clock Accuracy to +/- 15 seconds per week
Astro Clock accurate to with 15 minutes
Memory Lifetime memory of confi guration and recorded memories.
Clock maintained for up to 10 days in the event of power failures
PowerInput
Installation Steps:
1. Connection to dedicated input power circuit recommended.
2. Confi rm input circuit has enough available power for controller plus all connected loads.
3. Connect line, neutral, and ground to terminals as indicated.
Notes:
1. Use Copper Wire only
2. Max (2) #12AWG per terminal
3. Tighten terminals to 9in-lbs torque
4. 75° min insulation temperature rating
5. Remove 3/8” insulation from each circuit conductor
Earth Ground
Input ‘Hot’
Input ‘Neutral’
AuxilaryInput
Signal/control
input from occupancy
sensor or
switch
+24Vdc
power to
Occupancy
Sensor
Notes:
1. When using low voltage wire with a rating of less than 600V, insulate with the included shrink tube sleeve.
2. Occ terminal requires +V to signal lock/occ mode.
3. Available power for all peripherals can not exceed 300mh.
2. Use Copper Wire only
3. Terminals accept #30-12AWG
4. Tighten terminals to 7in-lbs torque
5. 75° min insulation temperature rating
5. Remove 3/8” insulation from each conductor.
Background:
Some models allow an external input which can trigger scene and/or device lockout. This can be used when it is desired to lockout a device by keyswitch, preventing access from the front panel, or when an Occupancy Sensor is used to turn on the lights.
Installation Steps:
1. Connect +V/COM terminals to the power in­put of the signal device.
2. Output from the signalling device shall be connected to the OCC terminal.
Luma-NetNetwork
Background:
The Luma-Net network is used for entry stations, partition control/room combine stations, dimmer cabinets, relay cabinets, and other devices which may be required.
Installation Steps:
1. Connect all wires as shown. Observe all notes, instructions, and low voltage digital network data cable installation best practices.
2. If necessary, install termination jumper. Termination is required only at both ends of the run. DO NOT terminate mid-point devices.
Notes:
1. Luma-Net networks require a daisy chain topology
2. Use Belden #1502R or #1502P for inter-connection of devices. Belden #9829, #9729, & #88102 are also supported wire types, however, an addition pair of (2) #18AWG wires is required.
3. A maximum run length of 2000 feet is supported on the data pair.
4. Torque terminals to 7in-lbs.
5. 75° min insulation temperature rating.
6. Remove 3/8” insulation from each circuit conductor.
7. Only 1 power supply is allowed on any network segment. If other power supplies are already supplying power to the network segment, do not connect +V between sources. Consult factory if unsure as to the proper power routing or connections for the network.
8. Terminals support 30-12AWG stranded wire.
Lock - (OPTIONAL) - Allows for dry contact (connection between common/lock) to initiate lock mode. This can be used for connection to an external signaling device which triggers a scene and if enabled, locks the device. Unlike the Occ/Lock input however, this input reuqires a connection to common, an ‘Active Low’ signal, to trigger the input.
Termination - Required use on fi rst & last device on run. See more info to right under “Digital netwowrk termination”.
To terminate any D4200 device, install a short piece of wire, aka ‘termination jumper’ between the terminals labeled TERM & REM-
D4200 CONTROL STATION
PRESET SELECT STATION
C
12
18
15
16
17
13 14
6
9 10
11
7 8
3 4
5
1 2
A B
DMX
CANCEL
LUMANE
T
CLEAR
PHASE LOSS
AUXILIAR
Y
FULL BRIGHT
COMMUNICATION PORTS
FAN
SAVE
FULL
SELEC
T
BRIGHT
A2000-D
Ground Shield
at one point only!
Terminate L
umaNet in
these locations








+V/COM - for D4200 model only, this device is the power input. On all other models, these connections are a power supply output to other devices.
Rem+/Rem- - Data connection
Belden 1502 Rem + = Blue Rem - = White
Belden 1502 +V = Red Com = Black
Belden 9829 Rem + = Blue/White Rem - = White/Blue
Belden 9729 Rem + = Red Rem - = Black
2
APPLIES TO:
D4006
D4104
D4106
D4206
N/A D4200
5
APPLIES TO:
N/A D4006
D4104
D4106
D4206
D4200
LineVoltageLoadTermination
Install Steps:
1. Confi rm that the load (watts) is within the specifi cations for your model as shown in the specifi cation chart.
2. Confi rm that the load type is supported. Load types can be found in the specifi cation chart.
3. Identify the terminal to which you need to connect the load, strip the wire as appropriate, and install to the appropriate load terminal.
To load
for Zone 2
Notes:
1. Use Copper Wire only.
2. Max (2) #12AWG per terminal.
3. Torque terminals to 9in-lbs.
4. 75° min insulation temperature rating.
5. Remove 3/8” insulation from each circuit conductor.
6. The number of outputs on a specifi c model may differ from that shown.
3
APPLIES TO:
D4006
D4104
D4106
D4206
N/A D4200
4
APPLIES TO:
D4006
D4104
D4106
D4206
D4200
1
APPLIES TO:
D4006
D4104
D4106
D4206
D4200
4 GANG BOX (4-1/2" WIDE X 2-1/2" DEEP)
4 GANG RAISED COVER (1/2" or 3/4" DEPTH)
RAISED COVER� MOUNTING SCREW� (4 PLACES)
DIMENSIONS MULTIZONE� CONTROLLER / DIMMER
FRONT DOOR�
COVER
OVERLAY
CONTRAST�
ADJUSTMENT�
(under Overlay)
CAUTIONS
CAUTIONS
• To be installed only by a qualifi ed Electrician
• Rated for indoor use only
• To be installed and/or used in accorance with appropriate electrical codes and regulations.
• If you are not sure about any part of these instructions, consult a qualifi ed electrician and Levi­ton Tech Support at (800)959-6004.
• DO NOT connect line voltage wires to low voltage terminals. Product destruction in this manner voids the warranty.
• To reduce the risk of over-heating and possible damage to this device and other connected equipment, do not allow the connection of any portable device or for connections to a wall recep­tacle.
• Do not connect to any unsupported load type (see device specifi cations).
• ALWAYS disconnect power when servicing this or any electrical device.
• All magnetic low voltage transformers should incoprorate a thermal cut-out or fuse on the pri­mary windings in case of over-heating or failure.
• All fl uorescent lighting fi xtures must be grounded
• For use with copper wire only
• DO NOT mix load types on a single zone (ie: Tungsten, Fluorescent, Magnetic low voltage, etc.)
• Observe all lamp and fi xture manufacturer recommendations, warnings, and instructions.
WARNINGS
CAUTIONS
Power Calculation:
When using the D4006, D4104, D4206, or D4206 as a supply to the Luma-Net network, ensure that there is enough supply current.
AVAILABLE SUPPLY CURRENT: +24Vdc, 300ma (12 Unit loads)
D4200 single gange devices each require 1 Unit Load D4200 LCD stations each require 2 Unit Loads Luma-Net hubs require 3 Unit Loads
When using Belden 1502R (or 1502P,) the following maxi­mum run lengths apply:
Unit
Loads
Max run length (ft)
10 3,528
20 1,764
30 1,176
40 882
Digital network termination:
The Luma-Net network requires that both ends of the net­work be terminated:
For applications which do not fi t these condi­tions please contact the factory for assistance.
NOTE:
When using low voltage wire with a rating of less than 600V, insulate with the included shrink tube sleeve.
Exploded Installation View
(beneath
Daisy Chain Toplogy:
Daisy-chain topology is required for each Luma-Net segment. Star or other similar topologies are not allowed. If multiple home-runs are required, this topology can be supported when a Luma-Net Hub, P/N LHUB8-000, is used.:
D4200CONTROL STATION
PRESETSELECT STATION
C
12
18
15
16
17
13 14
6
9 10
11
7 8
3 4
5
1 2
A B
DMX
CANCEL
LUMANET
CLEAR
PHASELOSS
AUXILIARY
FULLBRIGHT
COMMUNICATIONPORTS
FAN
SAVE
FULL
SELECT
BRIGHT
A2000-D
a-2000D
PRESET SELECT STATION
17
16
18
10
11
14
13
15
12
5
8
7
9
6
B
2
4
3
C
1
A
D4200 CONTROL STATION
LUMANET
DM
X
CLEAR
CANCEL
FAN
COMMUNICATION PORTS
FULL BRIGHT
AUXILIARY
PHASE LOSS
BRIGHT
SELECT
FULL
SAVE
a-2000D
PRESET SELECT STATION
17
16
18
10
11
14
13
15
12
5
8
7
9
6
B
2
4
3
C
1
A
D4200 CONTROL STATION
LUMANET
DM
X
CLEAR
CANCEL
FAN
COMMUNICATION PORTS
FULL BRIGHT
AUXILIARY
PHASE LOSS
BRIGHT
SELECT
FULL
SAVE
LUMA-NET III HUB
BAD TOPOLOGY
(STAR)
GOOD TOPOLOGY
(HOME-RUN w/LUMA-NET HUB)
GOOD TOPOLOGY
(DAISY CHAIN)
Ground drain and shield
at only one end.
Common
Page 2
Terminate
each end
(1) 120v, 20A Input Circuit
Luma-Net protocol requires a Low Voltage wire run. Leviton recommends the use of Belden #1502R with a maximum run length as indicated on the other side.
Luma-Net
• Network Address #2
• Slave to Master Station at Address #1
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #3
• Slave to Master Station at Address #1
• 1 Unit Load
Scene 1/Off
Entrance Station
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
{
o
This system represents the starting point for a system with broad application for small restaurants, conference rooms, or offi ces. Incorporated is a master station running up to (6) small loads and two entrance stations for convenient scene recall.
Basic Stand Alone System
o
D4106 Controller
• Network Address #1
• (6) local dimmers
Luma-Net
D4206 Controller
Network Address #1
(6) local dimmers
D4006 Remote Dimmer
• Network Address #3
• Network Channels 21-26
• Network Address #2
• Network Channels 13-20
Z-Max 8 Relay Panel
• Network Address #4
• Slave to Master Station at Network Address #1
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #5
• Slave to Master Station at Network Address #1
• 1 Unit Load
Scene 1/Off
Entrance Station
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
{
(1) 120v, 20A Input Circuit
Up to (8) 20A Input Circuits
{
Up to (8) 20A Ouput Circuits
{
o
Luma-Net protocol requires a Low Voltage wire run. Leviton recommends the use of Belden #1502R with a maximum run length as indicated on the other side.
This system is a step up from our basic system and represents our #1 seller as a typical BOM for a mid-size restaurant. Both the 4206 and remote 4006 handle the dimming loads and the relay panel covers the higher current switch loads both inside and outside the restaurant.
Typical Restaurant System
Terminate
each end
o
These diagrams represent typical systems which are included as reference designs. Systems may deviate from what is shown herein, however, the principals remain sound. Select a system which closely represents system to be installed, then extend it as necessary. For questions or specifi c application help, please contact a Leviton sales representative or Leviton Technical Support directly at (800) 959-6004. When inquiring about a specifi c system it is helpful to have the Leviton bill of materials or equipment list for your particular project.
Typical Systems
D4200 Master Station
Network Address #1
Network Channel 1-6
D4006 Remote Dimmer
• Network Address #4
• Network Channels 19-24
Up to (12) 20A Ouput Circuits
Luma-Net
A2000 Dimmer Cabinet
• Network Address #2
• Network Channel 7-18
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
{
{
Luma-Net protocol requires a Low Voltage wire run. Leviton recommends the use of Belden #1502R with a maximum run length as indicated on the other side.
• Network Address #3
• Network Channels 25-32
Z-Max 8 Relay Panel
Up to (8) 20A Input Circuits
{
Up to (8) 20A Ouput Circuits
{
• Network Address #5
• Slave to Master Station at Network Address #1
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #6
• Slave to Master Station at Network Address #1
• 1 Unit Load
Scene 1/Off
Entrance Station
Terminate
each end
o
Starting with the system above, this system replaces the D4200 controller with the D4206 controller adding an additional (6) local dimmers at the master station. Other than a slightly different allocation of dimmers, systems are similar. Note that if your relay cabinet is larger than 8 relays, or your dimmer cabinet is larger than 12 dimmers, you may have to patch multiple dimmers and/or relays to each Luma-Net address since the controller can only control up to 32 network address.
Typical System with D4200 Controller
o
D4206 Controller
Network Address #1
(6) local dimmers
Luma-Net
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
{
Up to (12) 20A Ouput Circuits
A2000 Dimmer Cabinet
• Network Address #2
• Network Channel 7-18
{
Starting with the system above, this system replaces the D4200 controller with the D4206 controller adding an additional (6) local dimmers at the master station. Other than a slightly different allocation of dimmers, systems are simlar. Note that if your relay cabinet is larger than 8 relays, or your dimmer cabinet is larger than 12 dimmers, you may have to patch multiple dimmers and/or relays to each Luma-Net address since the controller can only control up to 32 network addresses.
Typical System with D4206 Controller
Luma-Net protocol requires a Low Voltage wire run. Leviton recommends the use of Belden #1502R with a maximum run length as indicated on the other side.
D4006 Remote Dimmer
• Network Address #3
• Network Channels 19-24
• Network Address #4
• Network Channels 25-32
Z-Max 8 Relay Panel
Up to (8) 20A Input Circuits
{
Up to (8) 20A Ouput Circuits
{
• Network Address #5
• Slave to Master Station at Network Address #1
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #6
• Slave to Master Station at Network Address #1
• 1 Unit Load
Scene 1/Off
Entrance Station
Terminate
each end
o
o
D4106 Controller
• Network Address #10
• Network Channel #1-32
• 6 Local Zones
• 6 Dimmers
• Network Address #11
• Slave to Master at Network Address #10
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #12
• Slave to Master at Network Address #10
• 1 Unit Load
Scene 1/Off
Entrance Station
D4106 Controller
•Network Address #20
•Network Channel #33-64
• 6 Local Zones
• 6 Dimmers
• Network Address #21
• Slave to Master Station at Address #20
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #22
• Slave to Master Station at Address #20
• 1 Unit Load
Scene 1/Off
Entrance Station
Room A
Room B
D4106 Controller
Network Address #30
Network Channel #65-96
• 6 Local Zones
• 6 Dimmers
• Network Address #31
• Slave to Master Station at Address #30
• 1 Unit Load
Scene 1-8/Max/Off
Entrance Station
• Network Address #32
• Slave to Master Station at Address #30
• 1 Unit Load
Scene 1/Off
Entrance Station
Room C
D42CS-3AW Room
Combine Station
{
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
Luma-Net protocol requires a Low Voltage wire run. Leviton recommends the use of Belden #1502R with a maximum run length as indicated on the other side.
o
Terminate
each end
o
{
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
{
(6) 120V Ouput Circuits to lighting loads
1000W maximum per circuit
1200W maximum per side
1920W maximum
(See load types on other side)
A typical multi-room system with two partitions, a room combine station, and a master station for each room. In any multi-room system using the room combine stations, up to (4) rooms (each room requiring it’s own master station) are permitted.
Multi-Room System
•Network Address #100
(1) 120v, 20A Input Circuit
(1) 120v, 20A Input Circuit
Input feeder 1 0 or 3 0
See datasheet
/
/
Input feeder 1 0 or 3 0
See datasheet
/
/
(1) 120v, 20A Input Circuit
(1) 120v, 20A Input Circuit
{
(6) 120V Ouput Circuits
{
(6) 120V Ouput Circuits
{
(6) 120V
Ouput Circuits
emot
e D
immer
Loading...