Leviton CDA01-R12, CDA01-L12, CDA01-K12 User manual

Page 1
Leviton Solid Core Current Transformers
Cat. Nos. CDA01, CDA02
WARNINGS AND CAUTIONS
PK-A3225-10-02-5A
TO AVOID FIRE, SHOCK, OR DEATH; DISCONNECT POWER to all related circuits from power distribution system (or service) of building before installing or servicing current transformers!
TO AVOID OVERHEATING, DO NOT install a current transformer in an area where it would block ventilation openings.
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
• Current transformers may not be installed in equipment where they exceed 75 percent of the wiring space of any cross-sectional area within the equipment.
• Installation is intended for Overvoltage Category IV or Service Entrance.
• DO NOT install a current transformer in area of breaker arc venting.
• Current transformers are not suitable for Class 2 wiring methods and are not intended for connection to Class 2 equipment.
• Secure current transformer and route conductors so that they do not directly contact live terminals or bus.
• Current transformer lead lengths may be extended up to 500 feet, although doing so may adversely affect the accuracy of meter readings. When extending lead lengths, use twisted wires matching the gauge of the CT’s attached leads and follow NEC and local electrical codes.
• If this equipment is used in a manner not specified by Leviton, the protection provided by the equipment may be impaired.
• For indoor use only.
NOTE: For complete installation instructions specific to the meter being installed, please refer to the meter installation guide.
INSTALLATION INSTRUCTIONS
DESCRIPTION
Leviton solid core CTs are accurate, cost effective and less susceptible to damage during installation. Solid core CTs slip over power lines to measure the electrical current flowing through the line. The CT "secondary" wires connect to the meter, facilitating power and energy calculations.
Specifications
Operating ambient temperature rating -30 to 55°C
Relative humidity rating ) 90%
Maximum Rated Voltage 600V
Maximum Rated Current
CTs Primary: 100A
100:0.1A
Secondary: 1
200:0.1A CTs Primary: 200A
Secondary: 110mA (0.11A)
Pollution Degree 2 Normally only non-conductive pollution
10mA
(0.11A)
INSTALLATION
WARNING:
related circuits from power distribution system (or service) of building before installing or servicing current transformers!
1. Disconnect the conductor to be measured.
2. Insert the conductor through the center of the current transformer (CT).
NOTE: Ensure that the maximum current of the conductor does not exceed the
3. Repeat Steps 1 and 2 if you are using more than one CT.
4.
5. Connect the colored wire (black, blue, red) on the CT to the negative (-) terminal
6. Reconnect the conductor and restore power.
7. You are now ready to begin your monitoring session.
TO AVOID FIRE, SHOCK, OR DEATH; DISCONNECT POWER to all
The white case half identifies the H1 side, and should be oriented towards the incoming LINE (Fig. 2).
CT's rating.
Connect the white wire on the CT to the positive terminal (+) on the measuring device.
on the measuring device.
Fig. 2
LINE / LIGNE / LÍNEA L1
L2 L3 N
ENGLISH
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
CT1
Fig. 1
A
CT2
CT3
X1
CT3
B
X2
D
C
H1
CT2 CT1
X1 X2 X1 X2 X1 X2
L3
L2 L1 N
J1
J2
J4
J3
Dimensions / Dimensions / Dimensiones
CT Size/Rapport/Tamaño
100:0.1A 0.72"
200:0.1A
AB
2.06"
(18.3mm)
(52.3mm)
Find Quality Products Online at: sales@GlobalTestSupply.com
C D
0.82"
(20.8mm)
48.00"
(1219mm)
LOAD / CHARGE / CARGA
www.GlobalTestSupply.com
© 2017 Leviton Mfg. Co., Inc.