Levelpro TK3P-08-SS, TK3P-25-SS, TK3P-40-SS, TK3P-10-SS, TK3M-10-SS User manual

...
Page 1
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
(Industry's Toughest Built Paddle Wheel Flow Meter)
No K-Factor Programming
TK SERIES
Flow Rate + Flow Totalizer 2 Levels of Password Security
LED Display
No Tools Required
Read the User's Manual Carefully before Starting to Use the Unit.
All TK Series Flow Meters are Factory Calibrated and do not require
K-flow Factor Programming.
Manufacturer reserves the right to implement changes without prior notice.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 2
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
PRODUCT SELECTION
EXAMPLE
TKP -------- 25 -------- A -------- P
(1) (2) (3) (4)
1. SERIES
TKS = Paddle Wheel Flow Meter with Relay Output
TKP = Paddle Wheel Flow Meter - Flow Rate + Flow Total Pulse Output
TKM = Paddle Wheel Flow Meter- 4-20mA Output Flow Rate + Flow Total Pulse Output
2. PIPE SIZE
15 = (½") / 20 = (¾") 25 = (1") / 40 = (1 ½") 50 = (2") / 80 = (3") / 100 = (4")
3. BODY MATERIAL
P = PVC PP = Polypropylene PF = PVDF
4. COMMUNICATION
RS = TKP Series with RS-485 MODBUS selectable
5. CONNECTION METHOD
M-M12 Connector - 2Meter - other lengths available
01
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 3
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
PARTS TK SERIES
1. Flow Controller
2. Power Supply
3. Hall Sensor
4. Paddle Wheel
5. Body (PVC, PP, PVDF)
6. T
efzel Paddle
7. Rotor Pin
8. Bearing
Zirconium Ceramic Rotor Pin & Bearings... The Only thing Harder is Diamond
SPECIFICATIONS
Fluid Accuracy
6
7
8
Water or Chemicals Liquid - Viscosity Range : .5-20 centistokes > + 1.0% of F.S. @ 20°C (68°F) - Repeatability + .5% of Full Scale
1 2
3 4
5
Max Flow Velocity Min Flow Operating press Turndown Response time Material of
Construction
Operating Temperature
Electronics Protection Class Approval Current Draw
10 m/s max - (32.8 ft/s max)
0.3 m/s min. - (.98 ft/s min) 150 psi 33:1 Real Time
Paddle : Tefzel Body : PVC/PP/316 Shaft : Zirconium Ceramic Seals : EPDM/FPM
PVC < 60°C (140°F) PP < 80°C (176°F) 316 SST< 120°C (148°F)
+ 50°C (122F) IP66 NEMA 4X CE Rohs 60mA Max
Battery
Find Quality Products Online at: sales@GlobalTestSupply.com
10-30VDC
02
www.GlobalTestSupply.com
Page 4
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Programming TKP/TKM Model
Please Follow Hand To Program
TKP/TKM Series Only
24V DC POWER ONLY DISPLAY DESCRIPTION
Step-1
Home Screen
SET
F
(Together)
Step-2
Programming of Lock
SET
Step-3
SET
No Programming Required
Step-4
SET
SET
Press
[SET] + F
Out Feature
SET
Press
Programming
Units of Flow
SET
Press
Coefficient of
Flow Volume
SET
Press
+
F
(3 sec)HOLD
[SET]
[SET]
[SET]
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
CV
SV
LPM FTM
CV
SV
TKP/TKM Series Only Power On Flow Meter with DC Power
Display will Show
Totalizer (Top)
0 0 Flow Rate (Bottom)
Programming Lock Out Feature TKP/TKM Series Lck = 10 (Unlocked) : Factory Default, IF Lck is Changed
from the # 10 the Flow Meter will be in Lockout Mode.
LPM FTM
CV
SV
LPM FTM
CV
SV
LPM FTM
LCK 10 (Default) To Unlock ensure Lck # is set to 10.
Programming Units of Flow TKP/TKM Series Only
Program Flow Units 0,1,2,3 Ut = 0 : (LPM) Ut = 1 : (GPM) Ut = 2 : {Kiloliter (KL)}
UT 1 (Default)
TKP/TKM Series
K-Factor : 0.1 - 999.9 (K-Factor is Factory Preset)
K-Factor Preset (Do Not Change)
*Divide K Factor BY 3.8 TO CHANGE FROM GPM TO LPM
Step - 5 For Programming 4-20mA Analog Output
TKM (4-20mA) and TKP with (RS 485 Option) Only
Step-5
Program Range of Transmitter
(TKM Series Only)
SET
SET
Press
[SET]
Find Quality Products Online at: sales@GlobalTestSupply.com
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
CV
SV
LPM FTM
TKM + TKP (RS 485 Only)
Programming Analog Transmitter Range Output 4-20mA Range : 0.1 - 999.9 4 mA = 0 20 mA = Entered Number.
TR 100 (
Default )
4 mA = 0 GPM 20mA =100 GPM This can be Change to Conform to Customers Application Ex. Number Changed to 150
www.GlobalTestSupply.com
03
Page 5
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Programming NPN Pulse Output (TKP / TKM Series)
Please Follow Hand To Program
Steps Only Necessary If NPN Pulse Output is Required
TKP/TKM Series Only
24V DC POWER ONLY DISPLAY DESCRIPTION
Step-1
Programming Flow Meter
SET
Press Then Press SET
2
1
SET
Flow Meter & Transmitter
OP2
TKM
SET
F
CV
SV
FTM
OP1 GPM
GPM FTM
TKP/TKM Series Only CV  Display Reads 0 SV  Display Reads 0 0  Totalizer Default
0.0  Flow Rate Default
Press then Press Set & Adjust
Step-2
Programming Flow Rate
Pulse Output
Press
Op1
To
Change
Value
Flow Meter & Transmitter
Flow Meter & Transmitter
OP2
OP2 OP1
TKM
TKM
SET
SET
F
F
CV
CV
SV
SV
FTM
OP1 GPM
GPM
LPM
FTM
FTM
TKP/TKM Series Only (Pulse ON-OFF)
Program Value of (Flow Rate) Pulse (NPN) Output
CV
Preset Value of Flow Rate
Change to a Value that meets your Flow Rate Pulse Output
CV > SV Flow Rate Pulse Output ON
SV
<
SV Flow Rate Pulse Output OFF
CV
1000  Default
(One Pulse Per Gallon Default)
Press SET to Move to Save and Move to Next Screen
Step-3
Programming Flow total
Pulse Output
SET
Press Then Press SET
2
1
Op2
SET
Flow Meter & Transmitter
OP2
TKM
SET
F
CV
SV
FTM
OP1 GPM
GPM FTM
TKP/TKM Series Only
Program Value of Flow Totalizer Pulse (NPN) Output
CV
SV : Preset value of Flow Total CV > SV Flow Rate output ON
SV
2000
Default
Next Page Programming OP2 Output for Options for Totalizer
Flow Totalizer Pulse (Step #2-Next Page)
this can be Changed to Desired Value Refer to
Press SET Button to Move to Save Add Move to Next Screen
CV = Current Value SV = Programmed Value
(Flow Rate) Pulse
Step-4
Programming Flow total
Pulse Output
Press
Flow Meter & Transmitter
OP2
TKM
SET
F
CV
TKP/TKM Series Only
SV
FTM
OP1 GPM
GPM FTM
Return to Home Screen
0  Totalizer Default
0.0  Flow Rate Default
Op1 & Op2 = 150mA Max Switching Currency Current + Consumption is 60mA Max. CV = Current Value = Current Flow Rate on Display SV = Selected Value (Programmed Value Customer Entered) NPN Pulse is a Transistor
04
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 6
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Programming NPN Pulse Control Function (TKP / TKM Model Only)
OP1 = NPN Pulse Output (Flow Rate) OP2 = NPN Pulse Output (Flow Totalizer)
Please Follow Hand To Program
TKP/TKM Series Only
24V DC POWER ONLY DISPLAY DESCRIPTION
Step-1
Home Screen (Flow Rate)
SET
SET
Press
Step-2
Programming OP2 Output
Pulse Control (Totalizer)
SET
Press
Step-3
Programming OP2 Output
Pulse Reset Time
SET
Press
SET
SET
[SET]
(3 sec)HOLD
OP2
[SET]
OP2
[SET]
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
CV
SV
LPM FTM
Power On Flow Meter With 10-30 V DC 0 Flow Totalizer
0.0 Flow Rate
TKP/TKM Series Only
CV
SV
LPM FTM
CV
SV
Progam (NPN) Pulse Output (OP2) Totalizer
Range E.n.r.c. Con = n : Manual Reset; Con = c : time (1=10 Secs) Auto Reset Using Timer Con = c : time (secs) Auto Reset Using Timer i.e 5 =Pulse On (5 secs) Co
n = r : Auto Reset when Total Volume Value = Selct Value (SV)
on = E : Pulse Output of Unit volume (Default) = One Gal/Pulse
C Co
n = F ----> Paddle Pulse ----> Frequency Max 5 KHZ
Co
n = E (Default)
TKP/TKM Series Only (Length of Time Pulse relay remains On) Program Output NPN Pulse Reset Time For Totalizer
Range : 0 - 999.99 sec
T1 Only Applicable if Con r or Con C are Selected above if (Con = n
LPM FTM
or E ----> Timer Control ----> will not be an option) T1 0.50 Sec (Default)
TKP/TKM Series Only
Program Flow Rate Pulse (NPN) Output (OP1) Range: 0 - 3 CV > SV ----> Pulse (NPN) ON CV < SV - HYS CV > SV ----> Pu CV > SV + HY
ALT 0 (Default) Most Common
ulse (NPN) OFF
----> P lse (NPN) ON
S
----> P
ulse (NPN) OFF
CV = Current Value SV = Programmed Value Hys  =
See below
TKP/TKM Series Only
Program Hysteresis of NPN Output Pulse Range 0.1-999.99 (GAL) Hysteresis
HYS ± 1.0 GPM (Default)
Hys
- Hysteresis is a buffer around the Programmed Set Point Example
(Example) Liquid Caused by Pump Stopping or Valve Closing i.e.-sloshing
TKP/TKM Series Only - Flow Rate
Program Time Delay for NPN Pulse (OP1) on Initial Start Up Range : 0-9999 (Secs) Time Delay of Pulse Output (Flow Rate)
T2 = 20 (Secs) (Default) Flow Rate
CV = Current Value SV = Programmed Value
[SET]
(3 sec)HOLD
[SET]
(3 sec)HOLD
[SET]
OP1
OP1
OP1
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Step-4
Programming (OP1) Output
Pulse Option (Flow Rate)
SET
SET
Press
Step-5
Programming Hysteresis
of Output Flow Rate Pulse
SET
SET
Press
Step-6
Programming OP1 Power on Delay
Time For Initial Start UP (Sec)
SET
SET
Press
OP1 = NPN Pulse Output (Flow Rate) OP2 = NPN Pulse Output (Flow Totalizer)
CV
SV
LPM FTM
CV
SV
LPM FTM
CV
SV
LPM FTM
05
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 7
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Mode of NPN Pulse Output TKP/TKM Models
DESCRIPTIONALT NO.
ALt = 0 ALt = 1 ALt = 2 ALt = 3
Current Value = Flow Rate
Hys = Hysteresis ACTS Lika Buffer ± Around Pulse Output (Measured in GPM)
CV > SV ON: CV < SV - HyS OFF CV < SV ON: CV > SV + HyS OFF
SV + HyS > CV > SV - HyS ON: CV > SV + HyS or CV < SV - HyS OFF SV + HyS > CV > SV - HyS OFF: CV > SV + HyS or CV < SV - HyS ON
SV = Selected Value = Programmed Value (Customer)
K-Factors for TK Series Flow Meters (All Models)
Size
½"
LPM
124
GPM
471
¾"
1"
1 ½"
2" 3" 4"
72 45 19
10.3
4.7
2.1
274 171
72 39 18
8
Required when programming remote display or controller.
K-Factor Pre Programmed by Factory - No Flow Meter Programming of a K-Factor is required.
06
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 8
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Programming TKS Model Only
Please Follow Hand To Program
TKS Series Only
24V DC POWER ONLY DISPLAY DESCRIPTION
Step-1
Home Screen
SET
F
Step-2
Progamming Lock
SET
Step-3
No Programming Required K Value
SET
Step-4
Programming Communication
SET
SET
Press
[SET] + F
Output
SET
Press
SET
Press
Output Type
SET
Press
+
F
(3 sec)HOLD
[SET]
[SET]
[SET]
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
CV
SV
LPM FTM
CV
SV
LPM FTM
CV
SV
LPM FTM
CV
SV
TKS Series Only
Power Up Flow Meter with DC Power
000.0
Programming Lock - Out Secure Feature Lk = 10 (Unlocked Status) - (Default) Changing Number will Lock Flow Meter
LK.10 (D 10 = U
I
efault)
nlocked
f any other Number is entered the Programming will be restricted
K-Factor Range : 0.1-999.9 (Depends on Meter Size ­Factory Pre- Programmed) Ut = 0 : (LPM) Ut = 1 : (GPM) Ut = 2 : {Kiloliter (KL)}
UT 1 (Default)
Value Preset (Do Not Change)
K
Programming NPN Pulse Output con.E - Output = 1 Pulse / Gal con.F - Paddle Pulse Output 5KHZ MAX-Remote Display
LPM FTM
con.E (Default)
Step-5
Programming
of Relay Set Point
SET
SET
Press
[SET]
Step-6
Programming Relay
Time Delay
SET
SET
Press
[SET]
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
CV
SV
Programming Relay Setpoint ON - OFF Options Select ALT.0 ALT.1 ALT.2 ALT.3
ALT.0 (Default)
LPM FTM
CV
SV
LPM FTM
See Next Page for Relay Alarm Options
Programming Initial Start-Up Relay Time Delay Range : 0-99 sec Delay Time to Power on Alarm Output Relay T.20 (Default) (20 Seconds) Initial Start up of Flow Meter or Process (Allows for System Steady State before Relay Switch becomes Active).
07
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 9
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Programming TKS Model Only
Program Relay Set Point And Relay Delay (Prevents Relay Chatter)
Please Follow Hand To Program
TKS Series Only
24V DC POWER ONLY DISPLAY DESCRIPTION
Step-1
Home Screen
SET
SET
Press
Step-2
Programming Relay
SET
Set Point
Press
Step-3
Programming Relay
Hysteresis
SET
Press
SET
SET
[SET]
[SET]
[SET]
Flow Meter & Transmitter
OP2 OP1
TKM
SET
(3 sec)HOLD
F
Flow Meter & Transmitter
CV
SV
Power On Flow Meter - 24VDC
000.0 (Defaut) Home Screen
LPM FTM
CV
Programming Relay Set Point. (When Relay Switches) Range : 0.1 - 999.9 GPM
OP2 OP1
TKM
SET
F
Flow Meter & Transmitter
OP2 OP1
TKM
SET
F
SV
LPM FTM
CV
SV
LPM FTM
100.0 GPM (Defaut)
Relay will Activate when this Set Point or (Flow Rate) is Reached
Program Relay Hysteresis - Prevents Relay Chatter -Due to Constant Flow Rate Change around Setpoint in Dynamic Flow Process (Cushion ±) (Prevents Relay
d = Delay 0.10 (Defaut) GPM
In the Programming Stage, the Display will Flash
Relay ON - OFF Options For TKS Series Only (Not for TKP/TKM Series)
DESCRIPTIONALT NO.
ALt = 0 ALt = 1 ALt = 2 ALt = 3
CV = Current Display Value = Flow Rate
d = (GPM) Hysteresis Measured around Relay Set Point (± Measured in Gallons)
Find Quality Products Online at: sales@GlobalTestSupply.com
CV > SV Relay ON : CV < SV - d Relay OFF CV < SV Relay ON : CV > SV + d Relay OFF
SV + d > CV > SV - d Relay ON: CV > SV + d or CV < SV - d Relay OFF SV + d > CV > SV - d Relay OFF: CV > SV + d or CV < SV - d Relay ON
SV = Selected Value = Programmed Value
08
www.GlobalTestSupply.com
Page 10
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
General Terms
1)
2)
3)
5)
K tr
NPN Con
Coefficient of Flow Volume, Note : Factory Set Do Not Change
:
TKM Range of Transmitter - Flow Rate 4-20 mA 4mA = 0 20mA = Max Range
:
TKP - RS 485 Option Transistor Relay - No Moving Parts
:
Output Control of Flow Total OP2, Con = n Manual Reset
:
Con = C - Time Reset (1=10 Secs) Auto Reset, Con = r Auto Reset, Based on Volume (GPM) Con = E Pulse Output of Unit Volume, Con = F Pulse Output of Paddle = 5 KHZ Max
Important
Totalizer Reset TKP/TKM To Reset the Flow Totalizer to Zero Press
Standard Pipe Size
Pipe Size (O.D.)
ANSI (ID) (Inches)
Sch (40) Sch (80)
SET
[SET] +
DIN (ID)
(mm)
for (3 sec)
Important
Flow Rate (LPM) / USGPM
0.3m/s min. 10m/s max.
DN15 (1/2") Ø20 3.5 / 1.0 120 / 32 DN20 (3/4") Ø25 5.0 / 1.5 170 / 45
DN25 (1") Ø32 9.0 / 2.5 300 / 79
DN40 (1 ½") Ø50 25.0 / 6.5 850 / 225
DN50 (2") Ø63 40.0 / 10.5 1350 / 357
2 ½ Ø75 60.0 / 16 1850 / 357
DN80 (3") 90.0 / 24 2800 / 739
DN100 (4") 125.0 / 33 4350 / 1149
0.62
0.82
1.00
1.40
2.00
2.50
3.10
4.00
0.55
0.74
0.96
1.50
1.90
2.30
2.90
3.80
Ø78
Ø96.50
Pressure vs. Temperature (psi, water, non-shock)
NOMINAL SIZE
INCHES mm
1/2-2 2-1/2
3 4
15-50
65 80
100
30° F 70° F
150 150 150 150
71° F
105° F
120 120 120 120
PVC
106° F 120° F
100 100 100 100
121° F 140° F
30 NA NA NA
- 5° F 85° F
150 150 150 150
PP PVDF
86° F
120° F
110
95 95 95
121° F 140° F
90 70 70 70
141° F 175° F
55 40 40 40
- 5° F 70° F
150 150 150 150
105° F
71° F
125 125 125 125
106° F 140° F
100 100 100 100
141° F 175° F
85 85 85 85
176° F 210° F
55 55 60 60
09
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 11
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
MODEL TKP FLOW RATE + FLOW TOTALIZER + NPN PULSE
Brown
Flow
Meter Output Circuit
1 4
Black White
2
Yellow
5
Grey
6 3
Blue
Flow Rate Totalizer
Load Load
RS-485
+V
Pulse (NPN) Pulse (NPN)
+
Special Option
0V
Brown Yellow
Blue
White
10 - 30 VDC (+) (+) RS-485 (OPT)
0V (-)
Totalizer Pulse
Output NPN
Yellow & Grey with RS485 (Only) Black Wire can be Changed for Flow Total Limit Output or Unit Volume Pulse Output
MODEL TKM (4-20mA Or 0-5V DC + NPN Pulse)
Grey
Black
(-) RS-485 1 OPT
RS485 is a Special
Order Item
Flow Rate Pulse
Output (NPN)
FLOW RATE + FLOW TOTALIZER + PULSE
Green Brown
Flow
Meter
Output
Circuit
1 4
2 5 6 3
Black White
Yellow Grey Blue
Flow Rate
Totalizer
4-20
Black Wire can be Changed for Flow Total Limit Output or Unit Volume Pulse Output
Load Load
+V+
A
or
Ground
+V
Pulse (NPN) Pulse (NPN)
5V DC
0V
Brown Yellow
Blue
White
10 - 30 VDC (+)
0V (-)
Totalizer Pulse
Output NPN
Grey
Black
+ (4-20mA) or (0-5V)
Totalizer Output NPN
(4-20mA or 0 - 5V DC)
(4-20mA
Default -0-5VDC
Option-Special Order)
Flow Rate Pulse
Output NPN
MODEL TKS NPN (FLOW RATE - RELAY + PULSE)
Brown
TKS
Flow
Meter
Output
Circuit
1
4
5
6 3
Black Grey White Blue
Load
1 AMP
+V
NO
COM
0V
Brown White
Blue
Black
10 - 30 VDC (+) COM
0V (-)
Flow Rate Pulse Output (NPN)
Grey
NO
1 Amp
Black Wire is a Unit Volume NPN Pulse Output-1 pulse for every gallon
TKP - Yellow & Grey wires with RS - 485 Option Only Current output (4 - 20mA) : 120 max. Voltage output (0 - 5V) : 10K min.
DC Power Only
TKM Series (0-5VDC) Optional 4-20mA is Standard
10
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 12
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Instruction Manual / RS-485 RS-485 Modbus Protocol -IV
Thank you very much for using Truflo TK series flow meter Please read this instruction manual before operating it to avoid from the malfunction.
Connection Diagram
1
Brown +V
Output
Circuit
1
Black
1
White
1
Yellow
1
Grey
1
Blue 0V
Load
Load
RS-485
#1 Flowmeter +V
RS + RS -
OV : : :
#NFlowmeter +V
RS +
RS -
OV
Communication Standard
Communication
Mode
RS=0 : MODBUS- RTU mode RS=1 : MODBUS-ASCII mode
EIA-RS 485
Configuration of Communication (8N1)
Brown +V Yellow Grey Blue
Brown +V Yellow Grey Blue
Communication Speed
Communication
Station No.
Master RS + RS ­SG
9600 or 19200 or 38400 bps
ID No. = 01 ~ 99
(01H ~ 63H)
0 B0 B1 B2 B3 B4 B5 B6 B7 N 1
8 bit
Non Parity
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Stop BitStart bit
11
Page 13
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
RS-485 communication Address of parameter register
Address
No.
00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H 00H 01H
Decimal point FAll value of the parameter is processed to integer, Ex. 123.4 1234 Con* : 0 = n , 1 = r , 2 = c , 3 = E ur S* : 0 = Modbus - RTU mode , 1 = Modbus - ASCII mode bPS* : 0 = 9600 , 1 = 19200 , 2 = 38400
Lck
Ut
k
t r (iLo word)
t r (iHi word)
SPn
OSt (iLo word)
OSt (iHi word)
Con*
t 1
ALt
HYS
t 2
r S*
bPS*
I d
SV1 (Lo word)
SV1 (Hi word)
SV2 (Lo word)
SV2 (Hi word)
PV (Lo word)
PV (Hi word)
CV (Lo word)
CV (Hi word)
Output status*
Lock setting Unit selecting K value setting
Transmitter range Transmitter span Transmitter offset Control mode
Reset time Output status (LPM Op 1) Hysteresis (LPM) Delay time (OP1) RS-485 mode Baud rate Station No.
Flow rate setting
Flow volume setting
Flow rate value
Flow volume value Out1 & Out2 output status
Read Write
R / W R / W R / W
R / W R / W R / W R / W
R / W R / W R / W R / W R / W R / W
R
R / W
R / W
R
R / W
R
Decimal
point
Output Status****
Data
00H 00H 00H 01H 00H 02H 00H 03H
Out1
Out2 Data Out1
Off Off
Out2 Data Out1 Out2 Data Out1 Out2
On On On OnOff Off
Range of DataParameter Description
0 0 1
1 3 3 0
2 0 1 0 0 0 0
1
0
1
0 0
0 ~ 9999 0 ~ 3
0.1 ~ 999.9
0.1 ~ 9999.9
0.000 ~ 9.999
0.000 ~ 999.999 0 ~ 3
0.1 ~ 999.9 0 ~ 3
0.1 ~ 999.9 0 ~ 99 0 ~ 1 0 ~ 2 0 ~ 99
0.0 ~ 99999.9
0 ~ 999999
0.0 ~ 99999.9
0 ~ 999999 0 ~ 3
Remarks
Symbol
@
R W CR
-
A
B
Find Quality Products Online at: sales@GlobalTestSupply.com
ASCII code Description Symbol ASCII Code Description Symbol ASCII Code Description
40 Start code C 43 Hex 4 52
57 0D 2D
41
42
Read Write
Stop code
Minus
Hex Hex
D
E F 1 2 3
44 45 46 31 32 33
Hex Hex
Hex Hex / BCD Hex / BCD
Hex / BCD
5
6 7 8 9
:
34 Hex / BCD 35 36 37 38 39 3A
Hex / BCD Hex / BCD Hex / BCD Hex / BCD Hex / BCD
Hex
www.GlobalTestSupply.com
12
Page 14
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Message format
MODBUS
RTU
MODBUS
ASCII
Read command : Read response :
Read command : Read response :
Station No. Function code Address Batches of Data CRC Station No. Function code Data byte counts Data CRC
Start code Start code
Station No. Station No.
Function code Function code
Address Address
Data Data
Function code
Function code
03H 06H 10H 08H
Ex :
Read the CV value (flow volume) of No.01 flow meter ; CV=123456 (01E240H) (Liters ) and Write the K value (K factor) of No.01 flow meter ; K=123.4 (04D2H) Write the SV1 value (Flow rate setting) of No.01 flow meter; SV1=12345.6 (01E240H) (S
tation No= 01H,CV address = 22H/23H,CV = 123456 (01E240H) , K address = 03H,K=123.4 (04D2H)
(SV1 addr
ess = 14H/15H, SV1 = 123456 (01E240H)
Communication mode : RS = 0 : MODBUS . RTU code
Read command Read response Write command
Write response
Write command
Write response
Station No.
01H
Station No.
01H
Station No.
01H
Station No.
01H
Station No.
01H
Station No.
01H
Function Description
Read
Write (Single word)
Write (Double word)
Diagnose
Function code
03H 00H 22H
Function code
03H
Function code
06H
Function code
06H
Function code
10H
Function code
10H
Data byte counts
To diagnose the error of message format
Address
04H
Address
00H 03H
Address
00H 03H
Address
00H 14H
Address
00H14H
To read the data on register To write the preset value on register To write the preset value on register
Batches of data
00H 02H 64H 01H
Data
E2H 40H 00H 01H
Data
04H D2H
Data
04H D2H
Data
E2H 40H 00H 01H
Data
E2H 40H 00H 01H
LRC LRC
E2H A3H
FBH 57H
FBH 57H
56H 69H
56H 69H
Stop code Stop code
CRC
CRC
CRC
CRC
CRC
CRC
Communication mode : RS = 1 FMODBUS . ASCII code
Read Start code command Read response Write command Write response
Data byte counts** : 2 ASCII code byte = 1 data byte
3AH
Start code Station No.
3AH
Start code
3AH
Start code
3AH
45H32H 34H30H 30H 30H34H 44H32H30H30H 31H
Find Quality Products Online at: sales@GlobalTestSupply.com
Station No. Function code
30H 31H 30H 33H
Function code
30H 31H
Station No.
30H 31H
Station No.
30H 31H
30H 33H
Function code
30H 33H
Function code
30H 33H
(4 data bytes) (2 data bytes)*2 :*1 :
www.GlobalTestSupply.com
Address
30H 30H 42H 36H 0DH 0AH
Data byte counts**
30H 30H 30H33H
30H 30H 30H33H
32H 32H
30H 34H Address
Address
Batches of data*
30H30H
30H32H
Data LRC Stop code
*1
Data
*2
Data
*2
LRC Stop code
33H 43H
LRC
39H 43H
LRC
39H 43H
0DH0AH
Stop code
0DH0AH
Stop code
0DH0AH
13
Page 15
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Calculation of FCS
(RS = 0 FMODBUS . RTU code) : FCS = CRC .16 (Cyclic redundancy check) Procedure of CRC-16 calculation
To load FFH FFH to the 16 bit CRC register
1. To exclusive OR (*) the first byte of the message format with the low order byte of the 16 bit CRC
2. register, then put the result in the 16 bit CRC register. To shift the CRC register one bit to right (toward the LSB) and fill the MSB with zero.
3.
o repeat the step 3 If the carry flag is 0 (LSB is 0), Exclusive OR the CRC register with A001H
T
4. which is the v register. To repeat the step3 and 4 until the 16 bit CRC register is shifted 8 times
5.
o repeat from step 2 to step 5 for the next byte of the message format until final byte of message is
T
6.
ompleted. (Except the CRC bytes)
c To get the CRC value by changing the high order and low order byte of the final CRC register.
7.
alue of p
olynomial if the carry flag is 1 (LSB is 1), then put the result in the 16 bit CRC
(RS = 1 FMODBUS . ASCII code) FFCS = LRC Proce
1.
2.
3.
dure of LRC calculation
To add all bytes in the message format, excluding the start code F and ending code (0DH 0AH), then put this value in an 8-bit field To get a Two's complement from this 8-bit field. it is named Y (8-bit field also)
o get the LRC value by changing the Hex code to ASCII code from the Y .
T
.
Error response code
Message format
RS = 0 FMODBUS . RTU code
Function
Read CRC-16
Write CRC-16
RS = 1 FMODBUS . ASCII code
Function
Read
Write
Station No.
~
01H 01H 63H 86H
Start code Station No. Function code FCS Stop codeError code
3AH 30H 31H 3AH
63H 83H
~
30H 31H
Function code Error code FCS
~
01H 05H
~
01H 05H
~ ~
36H 33H
38H 33H 38H 36H
30H 31H 30H 35H36H 33H 30H 31H 30H 35H
~ ~
LRC LRC
0DH 0AH 0DH 0AH
Error code
Code Description Code Description
MODBUS – RTU MODBUS – ASCII MODBUS – RTU MODBUS – ASCII MODBUS – RTU MODBUS – ASCII
Find Quality Products Online at: sales@GlobalTestSupply.com
01H
03H 31H
02H
30H 32H
05H
30H 35H
Command error
Address overflow error
CRC or LRC error
www.GlobalTestSupply.com
MODBUS – RTU MODBUS – ASCII MODBUS – RTU MODBUS – ASCII
03H
30H 33H
04H
30H 34H
Data overflow error
Data error
14
Page 16
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Dimensions- TK3 Series
47.046.5
93.5
15.0 15.0
15.0 15.0
40.0
70.0
40.0
70.0
15.0
15.0
RC1/4"
RC3/8"
40.0
46.0
47.046.5
93.5
40.0
46.0
47.046.5
93.5
15.0 15.0
Find Quality Products Online at: sales@GlobalTestSupply.com
40.0
70.0
www.GlobalTestSupply.com
15.0 RC1/2"
40.0
46.0
15
Page 17
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Dimensions- TKS/TKP/TKM Series
H
1.81±0.05(inch)
Pipe Size Ød (inch) ØD (inch) ØC (inch)L (inch)H (inch)
(1/2") DN (15)
(3/4") DN (20)
(1") DN (25)
4.09±0.05
4.17±0.05
4.30±0.05
L
5.48±0.05
6.12±0.05
6.76±0.05
0.84±0.05
1.05±0.05
1.32±0.05
Ød
ØD
1.07±0.05
1.36±0.05
1.68±0.05
ØC
1.61±0.05
2.08±0.05
2.36±0.05
(1-1/2") DN (40)
(2") DN (50)
Find Quality Products Online at: sales@GlobalTestSupply.com
5.02±0.05
5.56±0.05
www.GlobalTestSupply.com
7.66±0.05
8.39±0.05
1.91±0.05
2.38±0.05
2.33±0.05
2.86±0.05
3.26±0.05
4.33±0.05
16
Page 18
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
½" DN15-UNION-PP SDR 11 IR FUSION½" DN15-UNION-NPT-PP
NPT-1/2"
Ø 1.18±0.05(inch)
Ø 0.63±0.05(inch)
Ø 1.10±0.05(inch)
Ø 1.15±0.05(inch)
Ø 0.58±0.05(inch)
Ø 0.78±0.05(inch)
Ø 1.05±0.05(inch)
0.24±0.05(inch)
0.98±0.05(inch)
3/4" DN20-UNION-NPT
NPT-3/4"
Ø 1.53±0.05(inch)
Ø 0.86±0.05(inch)
0.20±0.05(inch)
0.98±0.05(inch)
0.75±0.05(inch)
Ø 1.41±0.05(inch)
0.79±0.05(inch)
0.23±0.05(inch)
0.58±0.05(inch)
0.97±0.05(inch)
0.75±0.05(inch)
3/4" DN20-UNION-PP SDR 11 IR FUSION
Ø 1.48±0.05(inch)
Ø 0.78±0.05(inch)
0.20±0.05(inch)
0.70±0.05(inch)
1.09±0.05(inch)
Ø 0.97±0.05(inch)
Ø 1.38±0.05(inch)
0.81±0.05(inch)
1" DN25-UNION-NPT
Ø 1.75±0.05(inch)
Ø 1.02±0.05(inch)
0.24±0.05(inch) 0.75±0.05(inch)
0.98±0.05(inch)
NPT-1"
Ø 1.63±0.05(inch)
1" DN25-UNION-PP SDR 11 IR FUSION
Ø 1.72±0.05(inch)
Ø 0.97±0.05(inch)
0.23±0.05(inch)
0.82±0.05(inch)
1.21±0.05(inch)
Ø 1.25±0.05(inch)
Ø 0.61±0.05(inch)
1.01±0.05(inch)
17
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 19
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
1½" DN40-UNION-NPT-PVC- PP, PVDF
NPT-1-1/2"
1½" DN40-UNION-PP PVDF
Ø 2.48±0.05(inch)
Ø 1.57±0.05(inch)
0.28±0.05(inch) 1.00±0.05(inch)
1.28±0.05(inch)
Ø 2.30±0.05(inch)
Ø 2.43±0.05(inch)
Ø 1.56±0.05(inch)
SDR 11 IR FUSION
Ø 1.95±0.05(inch)
Ø 2.23±0.05(inch)
2" DN50-UNION-NPT-PVC-PP, PVDF
NPT-2"
Ø 3.08±0.05(inch)
Ø 2.16±0.05(inch)
1.27±0.05(inch)
Ø 2.91±0.05(inch)
0.97±0.05(inch)0.31±0.05(inch)
0.27±0.05(inch)
0.90±0.05(inch)
Ø 3.01±0.05(inch)
1.48±0.05(inch)
Ø 1.95±0.05(inch)
1.28±0.05(inch)
2" DN50-UNION-PP, PVDF
SDR 11 IR FUSION
Ø 2.46±0.05(inch)
Ø 2.83±0.05(inch)
0.30±0.05(inch)
1.01±0.05(inch)
1.60±0.05(inch)
1.38±0.05(inch)
18
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 20
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
3" ANSI JIS
Ø80.0
Ø190.5
0.75"
5.98"
PVC 4" ANSI JIS
9.0"
3.94"
2.6"
7.3"
8.94"
2.6"
0.75"
2.6"
7.50"
8.0"
9.4"
Remarks : Different Options Are Available
19
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 21
TKS/TKP/TKM SERIES
MULTI-FUNCTION PADDLE WHEEL FLOW METER
Installation Positions
10x 3x
10x 3x
CORRECT INCORRECT
CORRECT
CORRECT
10x 3x
INCORRECT
INCORRECT
CORRECT
INCORRECT
10x 3x
Please make sure the pipe is filled with the fluid under normal operation. TK Series can be installed in a horizontal or vertical direction. Please ensure enough length of straight pipe to avoid turbulence that can effect readings.
Note: Min 10x Pipe Diameters Upstream 3x Pipe Diameters Downstream.
A Plastic Basket Strainer, Bag Filter or Y Strainer Filtering Device upstream to Avoid the Paddle Wheel from being damaged by the solids or fibers - max 10% Particle Size - Not to Exceed .5mm Cross Section or Length.
Please do not flush the pipe after the Flow Meter is installed with Compressed Air this may damage the ceramic shaft and will Void Warranty
20
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com