Leuze DCR 85 Operating Instructions

DCR 85
CMOS Imager Code Reader
EN 2017/03 - 50134018
We reserve the right to
make technical changes
O r i g i n a l o p e r a t i n g i n s t r u c t i o n s
© 2017 Leuze electronic GmbH & Co. KG In der Braike 1 D-73277 Owen / Germany Phone: +49 7021 573-0 Fax: +49 7021 573-199 http://www.leuze.com
Leuze electronic DCR 85 2

Table of contents

Table of contents
1 About this document ............................................................................................5
1.1 Used symbols and signal words .............................................................................................5
2 Safety .....................................................................................................................6
2.1 Intended use ...........................................................................................................................6
2.2 Foreseeable misuse ............................................................................................................... 6
2.3 Competent persons ................................................................................................................ 6
2.4 Disclaimer ...............................................................................................................................7
3 Device description ................................................................................................8
3.1 Device overview...................................................................................................................... 8
3.1.1 About the DCR85 code reader ...........................................................................................8
3.1.2 Stand-alone operation .........................................................................................................8
3.2 Performance characteristics ...................................................................................................8
3.3 Device construction ................................................................................................................ 9
3.4 Connection technology ...........................................................................................................9
3.5 Display elements .................................................................................................................... 9
4 Mounting..............................................................................................................10
4.1 Selecting a mounting location............................................................................................... 10
5 Electrical connection..........................................................................................11
5.1 Voltage supply ......................................................................................................................11
5.2 Pin assignment .....................................................................................................................11
5.3 Switching input / switching output......................................................................................... 11
5.3.1 Switching input ..................................................................................................................12
5.3.2 Switching output ................................................................................................................12
5.4 PC or terminal connection .................................................................................................... 13
5.5 Cable lengths and shielding.................................................................................................. 13
6 Configuration and diagnostics software - SensorStudio...............................14
6.1 System requirements............................................................................................................ 14
6.2 Installing SensorStudio configuration software.................................................................... 15
6.2.1 Downloading configuration software .................................................................................15
6.2.2 Installing the SensorStudio FDT frame ............................................................................15
6.2.3 Install the communication DTM and device DTM..............................................................15
6.2.4 Connecting device to PC...................................................................................................15
6.3 Starting the SensorStudio configuration software................................................................ 16
6.4 Exiting SensorStudio ........................................................................................................... 17
6.5 Configuration parameters .....................................................................................................17
6.5.1 General tab........................................................................................................................ 18
6.5.2 Decode tab ........................................................................................................................19
6.5.3 Host interface tab ..............................................................................................................20
6.5.4 Diagnosis / Terminal.......................................................................................................... 20
6.5.5 Diagnosis / Image Viewer.................................................................................................. 21
7 Starting up the device - Configuration..............................................................22
7.1 Measures to be performed prior to the initial commissioning ............................................... 22
7.2 Starting the device ................................................................................................................22
7.2.1 Interface ............................................................................................................................22
7.2.2 Online commands .............................................................................................................22
7.2.3 Problems ...........................................................................................................................22
7.3 Setting the communication parameters ................................................................................22
Leuze electronic DCR 85 3
Table of contents
8 Online commands...............................................................................................23
8.1 Overview of commands and parameters ..............................................................................23
8.2 General online commands.................................................................................................... 24
8.3 Text commands ....................................................................................................................25
9 Care, maintenance and disposal .......................................................................34
9.1 Cleaning................................................................................................................................ 34
9.2 Servicing ...............................................................................................................................34
9.3 Disposing ..............................................................................................................................34
10 Service and support ...........................................................................................35
10.1 What to do should servicing be required? ............................................................................ 35
11 Technical data .....................................................................................................36
11.1 General specifications .......................................................................................................... 36
11.2 Reading fields .......................................................................................................................37
11.3 Dimensioned drawings ......................................................................................................... 39
12 Order guide and accessories.............................................................................40
12.1 Type overview....................................................................................................................... 40
12.2 Accessories........................................................................................................................... 40
13 EC Declaration of Conformity ............................................................................41
14 Appendix..............................................................................................................42
14.1 Bar code samples .................................................................................................................42
14.2 Configuration via configuration codes................................................................................... 43
Leuze electronic DCR 85 4

1 About this document

1.1 Used symbols and signal words

Tab.1.1: Warning symbols and signal words
Symbol indicating dangers to persons
NOTE Signal word for property damage
Indicates dangers that may result in property damage if the measures for dan­ger avoidance are not followed.
Tab.1.2: Other symbols
Symbol for tips
Text passages with this symbol provide you with further information.
Symbols for action steps
Text passages with this symbol instruct you to perform actions.
About this document
Symbol for action results
Text passages with this symbol describe the result of the preceding action.
Tab.1.3: Terms and abbreviations
BCL Bar code reader
CMOS Semiconductor process for implementing integrated circuits
(Complementary Metal-Oxide-Semiconductor)
DCR Image-based code reader
(Dual Code Reader)
DTM Software device manager
(Device Type Manager)
EMC Electromagnetic compatibility
EN European standard
FDT Software frame for management of device managers (DTM)
(Field Device Tool)
FE Functional earth
GUI Graphical user interface
HID Device class for input devices with which users directly interact
(Human Interface Device)
IO or I/O Input/Output
LED LED
(Light Emitting Diode)
PLC Programmable Logic Control
(corresponds to Programmable Logic Controller (PLC))
Leuze electronic DCR 85 5

2 Safety

This code reader was developed, manufactured and tested in accordance with the applicable safety stan­dards. It corresponds to the state of the art.

2.1 Intended use

The DCR85 code reader is designed as a stationary scanner with integrated decoder for all common 1D and 2D codes used for automatic object detection.
Areas of application
The DCR85 code reader is intended especially for the following areas of application:
• In automatic analyzers
• For space-critical code reading tasks
• For installation in a housing or beneath covers
Observe intended use!
The protection of personnel and the device cannot be guaranteed if the device is operated in a manner not complying with its intended use.
Ä Only operate the device in accordance with its intended use. Ä LeuzeelectronicGmbH+Co.KG is not liable for damages caused by improper use. Ä Read these operating instructions before commissioning the device. Knowledge of the oper-
Safety
CAUTION
ating instructions is an element of proper use.
NOTICE
Comply with conditions and regulations!
Ä Observe the locally applicable legal regulations and the rules of the employer's liability insur-
ance association.

2.2 Foreseeable misuse

Any use other than that defined under "Intended use" or which goes beyond that use is considered im­proper use.
In particular, use of the device is not permitted in the following cases:
• in rooms with explosive atmospheres
• in circuits which are relevant to safety
• for medical purposes
NOTICE
Do not modify or otherwise interfere with the device!
Ä Do not carry out modifications or otherwise interfere with the device. The device must not be
tampered with and must not be changed in any way.
Ä The device must not be opened. There are no user-serviceable parts inside. Ä Repairs must only be performed by Leuze electronic GmbH + Co. KG.

2.3 Competent persons

Connection, mounting, commissioning and adjustment of the device must only be carried out by competent persons.
Prerequisites for competent persons:
• They have a suitable technical education.
• They are familiar with the rules and regulations for occupational safety and safety at work.
• They are familiar with the technical description of the device.
• They have been instructed by the responsible person on the mounting and operation of the device.
Leuze electronic DCR 85 6
Certified electricians
Electrical work must be carried out by a certified electrician.
Due to their technical training, knowledge and experience as well as their familiarity with relevant standards and regulations, certified electricians are able to perform work on electrical systems and independently de­tect possible dangers.
In Germany, certified electricians must fulfill the requirements of accident-prevention regulations BGV A3 (e.g. electrician foreman). In other countries, there are respective regulations that must be observed.

2.4 Disclaimer

LeuzeelectronicGmbH+Co.KG is not liable in the following cases:
• The device is not being used properly.
• Reasonably foreseeable misuse is not taken into account.
• Mounting and electrical connection are not properly performed.
• Changes (e.g., constructional) are made to the device.
Safety
Leuze electronic DCR 85 7

3 Device description

3.1 Device overview

3.1.1 About the DCR85 code reader
The code reader is based on a CMOS imager with integrated decoder for all of the most popular 1D and 2D codes such as DataMatrix, Aztec, QRCode, 2/5 Interleaved, Code39, Code128, UPC/EAN etc.
The many possible configurations of the device allow it to be adapted to a multitude of reading tasks. Due to the small dimensions of the unit and the large reading field, the scan engine can also be used in highly constrained spaces.
Information on technical data and characteristics: see chapter 11 "Technical data".

3.1.2 Stand-alone operation

The code reader is operated as a "stand-alone" single device. It is equipped with a 6-wire cable with open ends for the electrical connection of the supply voltage, the interface, the trigger input and the switching output.

3.2 Performance characteristics

• High-performance, miniature CMOS Imager with front beam exit
• Compact design for simple integration, even in constrained spaces
• Reading of extremely small high-density codes and recording of standard codes in a large reading area using a special optical system
• Reading of shiny surfaces using a gloss reduction process
• Excellent decoding characteristics
• Clearly visible alignment LED
• RS 232 interface, one triggering input, one switching output
Device description
Leuze electronic DCR 85 8

3.3 Device construction

3
5
5
1
2
4
6
Device description
1 High resolution reading field lens 2 Wide-range reading field lens 3 LED indicators 4 Connection cable 5 LEDs for illumination (red light) 6 Alignment LEDs (blue light)
Fig.3.1: Device construction of the DCR85

3.4 Connection technology

• Connection cable, 6-wire with open cable end
• Cable (approx. 0.15m) with M12 connector, 8-pin

3.5 Display elements

Located on device top are two LEDs that indicates the readiness for operation and the read status.
Tab.3.1: LED indicators
LED State Description
PWR ON (continuous light) Voltage supply OK
GOOD READ ON (continuous light) Reading successful
Leuze electronic DCR 85 9

4 Mounting

α
β
γ
You can fasten the code reader at the M2.5 mounting threads.

4.1 Selecting a mounting location

NOTICE
The size of the code module influences the maximum reading distance and the width of the reading field. Therefore, when selecting a mounting location and/or the code label, take into ac­count the different reading characteristics of the scanner with various code modules.
NOTICE
Observe when choosing the mounting location!
Ä Maintaining the required environmental conditions (temperature, humidity). Ä Possible soiling of the reading window due to liquids, abrasion by boxes, or packaging mate-
rial residues.
Ä Lowest possible chance of damage to the scanner by mechanical collision or jammed parts. Ä Possible extraneous light influence (no direct sunlight).
In order to select the right mounting location, several factors must be considered:
• Size, orientation, and position tolerance of the bar codes or Data Matrix codes on the objects to be scanned.
• The reading field of the code reader in relation to the code module width.
• The resulting minimum and maximum reading distance from the respective reading field (see chapter
11.2 "Reading fields").
• Alignment of the code reader for avoiding reflections.
• Distance between code reader and host system with respect to the interface.
The best read results are obtained when
• the reading distance lies in the middle area of the reading field.
• there is no direct sunlight and extraneous light is avoided.
• the bar code labels are of good print quality and have good contrast ratios.
• you do not use high-gloss labels.
• the bar code or the Data Matrix code is moved past the reading window with an angle of rotation of 10° to 15°.
• the red light beam is narrowed down for its respective reading task in order to avoid reflections on shiny components.
Mounting
NOTICE
The front beam exit of the scan engine is almost vertical to the optics. The code label must be rotated by >10° to avoid a total reflection of the red light beam in the case of glossy labels.
α Azimuth angle β Angle of inclination γ Angle of rotation
Recommended angle of rotation: γ > 10°
Fig.4.1: Definition of the reading angles
Leuze electronic DCR 85 10

5 Electrical connection

CAUTION
Safety notices
Ä Before connecting the device, be sure that the supply voltage agrees with the value printed
on the name plate.
Ä Connection of the device and maintenance work while under voltage must only be carried
out by a qualified electrician.
Ä The power supply unit for the generation of the supply voltage for the code reader and the
corresponding connection units must have a secure electrical insulation according to IEC60742 (PELV). For UL applications: only for use in class 2 circuits according to NEC.
Ä If faults cannot be cleared, the device should be switched off and protected against acciden-
tal use.

5.1 Voltage supply

The code reader is designed for connection to a 5V supply voltage.
• +5V DC (red)
• GND (violet)
An adapter circuit board with spring terminals, Molex plug connector and 9-pin SUB-D socket is available as an accessory (see chapter 12.2 "Accessories").
• With the adapter circuit board, the conductors of the connection cable can be contacted via the spring terminals and connected to the PC via the 9-pin SUB-D socket with an RS 232 interconnection cable.
• With the adapter circuit board, the voltage supply of 10…30V DC can be fed in via spring terminals or, alternatively, 5V DC can be fed in via a micro USB connector.
Electrical connection

5.2 Pin assignment

Tab.5.1: Cable with open wire ends
Wire Assignment Description
Red +5VDC Operating voltage 5VDC IN
Violet GND Operating voltage 0VDC / reference ground IN
Black SW OUT Switching output OUT
Orange SW IN Switching input IN
White RS232 RxD RxD signal line of the RS232 interface IN
Green RS232 TxD TxD signal line of the RS232 interface OUT
Fig.5.1: Cable with M12 connector, 8-pin, A-coded

5.3 Switching input / switching output

The code reader is provided with a switching input and a switching output.
• The switching input is used to trigger code reading.
• The switching output signals successful code reading.
Leuze electronic DCR 85 11

5.3.1 Switching input

+ 5 V DC
TRIGGER
GND
4.5 … 5.5 V DC
GND
2.2 k
1
2
3
+ 5 V DC
OUT
GND
GND
+ 5 … 30 V DC
max. 20 mA !
R
L
4.5 … 5.5 V DC
1
2
3
By means of the SW IN switching input connection, you can trigger a read process in the standard setting (low = active) with the connection TRIGGER (orange) and GND (violet). We recommend wiring a 2.2kΩ pull-up resistor as defined cable termination.
1 Red 2 Orange 3 Violet
Connection version NPN: standard setting (low = active)
Electrical connection
Fig.5.2: Switching input for connection variant NPN (standard setting)

5.3.2 Switching output

The NPN switching output connection between switching output (black) and GND (violet) switches if a code is detected against GND.
1 Red 2 Black 3 Violet
Fig.5.3: Switching output
Leuze electronic DCR 85 12
NOTICE
Maximum loading of the switching output
Ä Do not load the switching output of the code reader with more than 20mA at +5…30 VDC!

5.4 PC or terminal connection

1
2
10 11
3
4
8
9
5 6 7
Via the serial interface, you can configure the code reader by means of a PC or terminal. For this, you need an RS232 connection that establishes the RxD, TxD and GND connections between PC and code reader.
The RS232 connection can be established in the following ways:
• Direct connection of the code reader connection wires to the PC or terminal via its own connector.
• Connection via an MA-CR adapter circuit board
To simplify the connection of the connection wires to the PC interface, an adapter circuit board (MA­CR) is available for implementing individual wire contacting to SUB-D, 9-pin (see chapter 12.2 "Acces­sories").
Electrical connection
1 RS232 connection 2 CR50 or DCR80 connection 3 CR100, CR55, DCR85 connection 4 Molex Micro-Fit, 6-pin 5 USB connection 6 Connection to machine control, PLC, external voltage supply 5VDC 7 External voltage supply 10…30VDC 8 SWIN DIP switch (level for trigger button; 5V if the scanner high switching input is active, GND if the low
input is active)
9 USB/PWR DIP switch (USB position if voltage is supplied via USB; PWR position if voltage is supplied
via(7)) 10 Trigger button 11 Status LEDs
Fig.5.4: Connection options for MA-CR adapter circuit board

5.5 Cable lengths and shielding

The maximum cable length is 3m.
Should a cable extension be necessary, make certain that the cables of the RS232 interface are shielded.
Leuze electronic DCR 85 13
Configuration and diagnostics software - SensorStudio
6 Configuration and diagnostics software - SensorStudio
The SensorStudio configuration software provides a graphical user interface for the operation, configura­tion and diagnosis of the device via the RS232 interface.
A device that is not connected to the PC can be configured offline.
Configurations can be saved and reopened as projects for transferring back to the device at a later time.
NOTICE
Only use the SensorStudio configuration software for products manufactured by Leuzeelec­tronic.
The SensorStudio configuration software is offered in the following languages: German, Eng­lish, French, Italian and Spanish.
The FDT frame application of the SensorStudio supports all languages; all languages may not be supported in the device DTM (Device Type Manager).
The SensorStudio configuration software is designed according to the FDT/DTM concept:
• You make the individual configuration settings for the bar code reader in the Device Type Manager (DTM).
• The individual DTM configurations of a project can be called up via the frame application of the Field Device Tool (FDT).
• Communication DTM for code readers: LeCommInterface
• Device DTM for the DCR 85 code reader
Procedure for the installation of the software and hardware:
Ä Install the SensorStudio configuration software on the PC. Ä Install the communication and device DTM.
Communication and device DTM are included in the LeAnalysisCollectionSetup installation package.
Ä Create DCR85-DTM in the project tree of the Sensor Studio FDT frame. Ä Connect code reader to PC (see chapter 5.4 "PC or terminal connection").

6.1 System requirements

To use the SensorStudio configuration software, you need a PC or laptop with the following specifications:
Tab.6.1: System requirements for SensorStudio installation
Operating system WindowsXP or higher (32bit, 64bit)
Computer Processor type: 1GHz or higher
Graphics card At least 1024x768 pixels
Required hard disk capacity for SensorStudio and communica­tion DTM
NOTICE
Administrator privileges on the PC are necessary for installing SensorStudio.
WindowsVista
Windows7
Windows8
Serial COM interface
CD-ROM drive
Main memory (RAM): at least 64MB
Keyboard and mouse or touchpad
35MB
Leuze electronic DCR 85 14
Configuration and diagnostics software - SensorStudio
6.2 Installing SensorStudio configuration software
NOTICE
The installation files of the SensorStudio configuration software must be downloaded from the Internet at www.leuze.com.
For subsequent updates, you can find the most recent version of the SensorStudio installation software on the Internet at www.leuze.com.

6.2.1 Downloading configuration software

Ä Call up the Leuze home page: www.leuze.com Ä Enter the type designation or part number of the device as the search term. Ä The configuration software can be found on the product page for the device under the Downloads tab.
6.2.2 Installing the SensorStudio FDT frame
NOTICE
First install the software!
Ä Do not yet connect the device to the PC. First install the software.
NOTICE
If FDT frame software is already installed on your PC, you do not need the SensorStudio instal­lation.
You can install the communication DTM and the device DTM in the existing FDT frame. Com­munication DTM and device DTM are included in the LeAnalysisCollectionSetup installation package.
Ä Start the PC. Ä Download the configuration software from the Internet to the PC (see chapter 6.2.1 "Downloading con-
figuration software"). Unpack the installation package.
Ä Start the SensorStudioSetup.exe file. Ä Follow the instructions on the screen.
The Installation Wizard installs the software and places a shortcut on the desktop ( ).

6.2.3 Install the communication DTM and device DTM

Prerequisites:
ü An FDT frame is installed on the PC. Ä Start the LeAnalysisCollection.exe file from the installation package and follow the instructions on the
screen.
The installation wizard installs communication DTM and device DTM for DCR85.

6.2.4 Connecting device to PC

The device is connected to the PC via the RS232 interface.
• You need an RS232 connection that establishes the RxD, TxD and GND connections between PC and device (see chapter 5.4 "PC or terminal connection").
• The 5V DC voltage supply is to be fed in externally (see chapter 5.1 "Voltage supply").
Leuze electronic DCR 85 15
Configuration and diagnostics software - SensorStudio
NOTICE
The MA-CR adapter circuit board with spring terminals and plug connector for connecting the device, as well as 9-pin SUB-D socket for connecting an RS 232 interconnection cable, is avail­able as an accessory. An RS232 interconnection cable to the PC is also available as an acces­sory (see chapter 12 "Order guide and accessories").
The adapter circuit board requires 10V…30VDC as external voltage supply, which can be fed in via spring terminals.
6.3 Starting the SensorStudio configuration software
Prerequisites:
• The device has been mounted (see chapter 4 "Mounting") and connected (see chapter 5 "Electrical connection") correctly.
• The device is connected to the PC via the RS232 interface (see chapter 6.2.4 "Connecting device to PC").
• The SensorStudio configuration software is installed on the PC (see chapter 6.2 "Installing SensorStu­dio configuration software").
Ä Start the SensorStudio configuration software by double-clicking the SensorStudio icon ( ).
The mode selection of the Project Wizard is displayed.
Ä Select the Device selection without communication connection (offline) configuration mode and
click on [Next].
The Project Wizard displays the device selection list of the configurable devices.
Fig.6.1: Device selection for code reader CR85
Ä Select DCR85 in the device selection and click on [Next].
The device manager (DTM) of the connected DCR85 starts with the offline view for the SensorStudio configuration project.
Leuze electronic DCR 85 16
Configuration and diagnostics software - SensorStudio
Ä Establish the online connection to the connected DCR85.
In the SensorStudio FDT frame, click on the [Establish connection with device] button ( ). In the SensorStudio FDT frame, click on the [Upload parameters to device] button ( ).
The current configuration data is displayed in the device manager (DTM).
Fig.6.2: Configuration project: SensorStudio device manager (DTM) for DCR85
Ä The menus of the SensorStudio device manager (DTM) can be used to change or read out the config-
uration of the connected device. The user interface of the SensorStudio device manager (DTM) is largely self-explanatory. The online help system provides information on the menu items and adjustment parameters. Select the
Help menu item in the menu [?] ( ).
Ä Transfer the modified configuration parameters to the device.
If a connection exists, click on the [Download parameters to device] button ( ) on the task bar.
6.4 Exiting SensorStudio
After completing the configuration settings, close the SensorStudio configuration software.
Ä Exit the program via File > Exit. Ä Save the configuration settings as a configuration project on the PC.
You can open the configuration project again at later time via File > Open or with the SensorStudio
Project Wizard ( ).

6.5 Configuration parameters

In this chapter, you will find information and explanations on the configuration parameters of the device manager (DTM).
NOTICE
This chapter does not include a complete description of the SensorStudio configuration soft­ware.
Complete information on the FDT frame menu and on the functions in the device manager (DTM) can be found in the online help system.
The device manager (DTM) of the SensorStudio configuration software offers the following configuration functions:
General (Control)
Decode (see chapter 6.5.2 "Decode tab")
Leuze electronic DCR 85 17
Host Interface (see chapter 6.5.3 "Host interface tab")
Diagnosis (see chapter 6.5.4 "Diagnosis / Terminal")
NOTICE
The online help system displays information on the menu items and configuration parameters for each function. Select the Help menu item in the menu [?].

6.5.1 General tab

Configuration and diagnostics software - SensorStudio
Fig.6.3: General tab
Trigger duration
(Trigger Duration)
Reading fields
(Decode Area)
Scan mode
(Continuous Action)
LED illumination
(Illumination)
Target illumination
(Targeting)
Target illumination time setting
(Target Time before Decode)
Set the time, for which a read cycle remains active after a trigger event.
Example: triggerduration=3000ms means that the scanner tries to decode a code for a maximum of three seconds after a trigger event. The read cycle ends after successful decoding or after the time that has been preset here has relapsed.
Selection of the reading field. The scan engine has two reading fields:
• High resolution reading field
• Wide-range reading field
Selection of the reading behavior:
• Read when triggered
• Presentation mode
• Duration reading
Set the illumination time of the LEDs after successful reading.
Switch the blue alignment LEDs on and off.
Setting of the time until which reading takes place after a trigger event.
The blue alignment LEDs light up immediately when the trigger event occurs.
Leuze electronic DCR 85 18

6.5.2 Decode tab

Configuration and diagnostics software - SensorStudio
Fig.6.4: Decode tab
Code table
(DECODE)
Properties
(SYMBOLOGIES)
Here, the codes which are to be decoded are set. We recommend en­abling only the code types which are to actually be read with the corre­sponding element numbers. Codes which are not enabled are not de­coded!
Use the … button to the right of the given code to select the code-spe­cific settings.
Alternatively, the property settings can be selected directly via the navigation tree under the Decode button.
The properties can be individually set for each code type.
Fig.6.5: Standard settings for the Properties window (SYMBOLOGY SETTINGS) – Decode tab
Leuze electronic DCR 85 19

6.5.3 Host interface tab

Configuration and diagnostics software - SensorStudio
Fig.6.6: Host interface tab
Select the desired baud rate, the stop bits, the data bits, the parity and various transmission modes here.
The desired acknowledgment settings are also to be set in this selection window.

6.5.4 Diagnosis / Terminal

Fig.6.7: Terminal
The Terminal tab provides the following functions:
• Send online commands to the code reader for diagnostic purposes.
• Visualize the code reader output.
The contents of the terminal display can be printed out or saved in a file for subsequent offline evaluation.
Leuze electronic DCR 85 20

6.5.5 Diagnosis / Image Viewer

Configuration and diagnostics software - SensorStudio
Fig.6.8: Diagnosis / Image Viewer
You can use the Image Viewer to display the image captured in the reading field on the screen. This helps you find the optimum position for reliable reading.
If both reading fields are activated (Decode Area Both Fields), the high-resolution reading field and the far-range reading field are displayed in the GUI.
Leuze electronic DCR 85 21
Starting up the device - Configuration

7 Starting up the device - Configuration

7.1 Measures to be performed prior to the initial commissioning

NOTICE
Ä Please observe the notices for device arrangement, see chapter 4.1 "Selecting a mounting
location".
Ä If possible, always trigger the scanner with the aid of commands or an external signal trans-
mitter (photoelectric sensor).
Ä Before commissioning, familiarize yourself with the operation and configuration of the de-
vice(s).
Ä Before connecting the supply voltage, recheck all connections and ensure that they have
been properly made.

7.2 Starting the device

7.2.1 Interface

Proper function of the interface can be most easily tested in service operation using the serial interface with the SensorStudio configuration software and a notebook computer.

7.2.2 Online commands

Using the online commands, important device functions can be checked, e.g. reading activation.

7.2.3 Problems

If a problem occurs that cannot be rectified even after checking all electrical connections and settings on the devices and on the host, contact your responsible Leuzeelectronic subsidiary or Leuzeelectronic cus­tomer service, see chapter 10 "Service and support".

7.3 Setting the communication parameters

You have now commissioned the device. Usually, you will have to configure it before you can use it. Using the configuration options offered in the SensorStudio or by means of the device DTM, the device can be individually configured according to your application. For information on the various configuration options, see chapter 6 "Configuration and diagnostics software - SensorStudio" or refer to the online help.
It is normally sufficient to set the code type and code length in accordance with the 1D or 2D codes that are to be read in order to be able to operate the device.
The setting of code type and code length is usually accomplished by using the SensorStudio configuration software (see chapter 6 "Configuration and diagnostics software - SensorStudio").
Leuze electronic DCR 85 22

8 Online commands

8.1 Overview of commands and parameters

Online commands can be used to send commands directly to the device for control and configuration. For this, the device has to be connected to a computer (host) via the serial interface.
Using the online commands you can:
• query the device version.
• activate and deactivate code reading.
• perform a software reset.
Command syntax
<cmd-prefix><cmd-type><data-size>[<data>]<reserved><crc>
<cmd-prefix> <0xEE><0xEE><0xEE><0xEE>
<cmd-type> One ASCII character
<data-size> Byte value 0…240
Number of bytes in <data>
[<data>] Optional: command data (byte values) in range of 0…255
Online commands
<reserved> One byte, always <0x00>
<crc> Two bytes crc16 check sum
Answer syntax
<start-tag><packet-type>[<packet-data>]<EOT>
<start-tag> <0x01>X<0x1E>ap/
<packet-type> One ASCII character
[<packet-data>] Optional: answer data
<EOT> One byte <EOT> (<0x04> hex.)
Leuze electronic DCR 85 23

8.2 General online commands

Software version number
Command <cmd-prefix>I<0x00><0x00><0x03><0x3C>
Description Requests device version information
Parameter None
Answer <start-tag>iVVVVWWWWXXXXSSSSSSSSSSAOODYYYYHHIIIIJJJJKKKKL-
LLL <TAB>Z…Z<EOT>
• i: "I" string output
• VVVV: application firmware version number
• WWWW:core application firmware version number
• XXXX: reserved
• A: current execution state:
• OO: OEM identifier
• D: display type
• YYYY: reserved
• HH: hardware version
• IIII: hardware type identifier (value in register 21B)
• JJJJ: boot application version
• KKKK: operating system kernel version
• LLLL: root file-system version
• <TAB>: ASCII TAB character
• Z…Z: OEM decoder version:
Example:
i10261026none0020366861A0600000080006001600660002 -> cd(14.2.0)
Online commands
"A": core is running
"0": no display device
null-terminated string of printable ASCII characters
Software reset
Command <cmd-prefix>Z<0x01>1<0x00><0x1C><0x04>
Description Carries out a software reset. The device is restarted and reinitialized, leaving it
in the same state as when the supply voltage is switched on.
Parameter None
Acknowledgment <start-tag>d<EOT>
"d": done response
Start decoding
Command <cmd-prefix>P<0x0C>(35)7FFFFFFF<0x00><0x57><0x5F>
<cmd-prefix>$<0x01><0x03><0x00><0x1F><0x5C>
Description The command consists of two individual commands.
• The first command sets the decoder duration to infinity.
• The second command activates decoding.
Parameter None
Acknowledgment <start-tag>d<EOT>
"d": done response (twice)
Leuze electronic DCR 85 24
Online commands
Stop decoding
Command <cmd-prefix>P<0x05>(35)0<0x00><0x65><0x5B>
Description The command sets the decoder duration to zero and stops decoding.
Parameter None
Acknowledgment <start-tag>d<EOT>
"d": done response
Start continuous decoding
Command <cmd-prefix>P<0x06>(C4)03<0x00><0x01><0x75>
Description The command activates duration decoding.
The read result is continuously output until it is terminated by a command.
Parameter None
Acknowledgment <start-tag>d<EOT>
"d": done response
End continuous decoding
Command <cmd-prefix>P<0x06>(C4)FF<0x00><0x1C><0x71>
Description The command ends duration decoding.
Parameter None
Acknowledgment <start-tag>d<EOT>

8.3 Text commands

Text commands are activated via the following start sequence: ;>PA1<CR>
With PA8<CR>, the input of text commands is ended.
Example:
Tab.8.1: Activate decoding of Interleaved 2 of 5 codes with 10 (0x0A) characters
Command Description
;>PA1<CR> Activate text commands
P(6E)1<CR> Activate decoding of Interleaved 2 of 5 codes
P(C9)0A<CR> Code length: 10 (0x0A) characters
PA8<CR> Deactivate text commands
Command syntax
"d": done response
<Command-Type><Command-Data><CR>
<Command­Type>
P The settings are stored in a register. The settings are lost when the device is
restarted.
C The settings are stored in a register. The settings remain stored when the device is
restarted.
<Command
See tables
Data>
<CR> Carriage return
ASCII control character 0x0D
Leuze electronic DCR 85 25
Command data
Format: (XXX)YYY
• XXX: register number in ASCII hex
• YYY: setting value in ASCII hex
Tab.8.2: Decoding – Common properties
Parameter settings Command data
Online commands
Common proper­ties
Tab.8.3: Decoding – 1D codes
Maximum labels to decode (34)1…10
Ignore duplicate codes (ms) (159)0…7FFFFFF
Code Parameter settings Command data
Code properties 1D barcode aggressiveness
Most aggressive (13)0
Less aggressive (13)1
Less aggressive (13)2
Interleaved 2 of 5 Settings of register C9 are bitwise OR-connected.
• The length (number of digits) is always even and can be represented by an inte­ger value without using bit 0.
• Bit 0 is used to enable/disable Small Quiet Zone (SMZ)
Interleaved 2 of 5 Decoding
enable (6E)1
disable (6E)0
Interleaved 2 of 5 Length (C9)0…64
Interleaved 2 of 5 Small Quiet Zone (SMZ)
enable (C9)1
disable (C9)0
Interleaved 2 of 5 Checksum checking
disable (71)0
enable (71)1
Enable and strip from output (71)2
Code 32
Code 39
Decoding
disable (6B)0
enable Code39 but not Code32 (6B)1
enable Code32 but not Code39 (6B)2
enable Code39 and Code32 (6B)3
Code 39 Checksum checking
disable (70)0
enable (70)1
Enable and strip from output (70)3
Code 39 Full ASCII symbology
disable (49)0
enable (49)1
Leuze electronic DCR 85 26
Code Parameter settings Command data
Code93 Decoding
disable (6C)0
enable (6C)1
Online commands
Code UPC
Code EAN
UPC and EAN codes enabled
disable (6A)0
enable (6A)1
Code UPC Supplemental data output
disable (4E)0
enable (4E)1
Code 128 Decoding
enable (6D)1
disable (6D)0
Codabar Decoding
enable (6F)1
disable (6F)0
Codabar Checksum checking
disable (48)0
enable (48)1
Enable and strip from output (48)3
GS1 DataBar The settings of register 4C are bitwise OR-connected
• Example: Command (4C)06 enables GS1 DataBar Limited decoding and GS1 DataBar Expanded Stacked decoding
• Command (4C)00 disables all GS1 DataBar symbologies
GS1 DataBar Omnidirectional Decoding, Truncated Decoding
enable (4C)08
disable (4C)00
GS1 DataBar Limited decoding
enable (4C)04
disable (4C)00
GS1 DataBar Expanded decoding
enable (4C)01
disable (4C)00
GS1 DataBar Omnidirectional Stacked Decoding, Stacked Decoding
enable (4C)10
disable (4C)00
GS1 DataBar Expanded tacked decoding
enable (4C)02
disable (4C)00
Leuze electronic DCR 85 27
Code Parameter settings Command data
MSI Plessey The settings of register 4F are bitwise OR-connected
• Example: Command (4F)25 enables MSI Plessey decoding with Two Bytes Mod­ulo 11/10 checksum and UK Plessey decoding
• Command (4F)00 disables all MSI Plessey decoding and the checksum settings
MSI Plessey Decoding
enable (4F)01
disable (4F)00
MSI Plessey Checksum method
Checksum checking disabled (4F)00
One Byte Modulo 10 (4F)02
Two Bytes Modulo 11/10 (4F)04
Two Bytes Modulo 10 (4F)06
One Byte Modulo 10 and strip from output (4F)09
Online commands
Two Bytes Modulo 11/10 and strip from
(4F)0A
output
Two Bytes Modulo 10 and strip from out-
(4F)0C
put
MSI Plessey UK Plessey (original) decoding
enable (4F)20
disable (4F)00
Tab.8.4: Decoding extras – 1D codes
Parameter settings Command data
Settings of register 24F are bitwise OR-connected.
Example: Command (24F)8435 enables the following options
• Send Code39 start and stop delimiter
• Force output of all decoding data to upper case
• Remove UPC-A check digit
• Remove UPC-A number system digit
• Convert EAN-8 to EAN-13
• Remove GS1 DataBar “()” characters
Send Code39 start and stop delimiters
enable (24F)0001
disable (24F)0000
Remove Codabar start and stop delimiters
enable (24F)0002
disable (24F)0000
Force all decoding data to upper case
enable (24F)0004
disable (24F)0000
Force all decoding data to lower case
enable (24F)0008
disable (24F)0000
Leuze electronic DCR 85 28
Parameter settings Command data
Remove UPC-A check digit
enable (24F)0010
disable (24F)0000
Remove UPC-A number system digit
enable (24F)0020
disable (24F)0000
Remove UPC-E check digit
enable (24F)0040
disable (24F)0000
Remove UPC-E number system digit
enable (24F)0080
disable (24F)0000
Remove EAN-13 check digit
enable (24F)0100
Online commands
disable (24F)0000
Remove EAN-8 check digit
enable (24F)0200
disable (24F)0000
Convert EAN-8 to EAN-13
enable (24F)0400
disable (24F)0000
Convert UPC-A to EAN-13
enable (24F)0800
disable (24F)0000
Convert Bookland EAN-13 to ISBN
enable (24F)1000
disable (24F)0000
Convert Bookland EAN-13 to ISSN
enable (24F)2000
disable (24F)0000
Remove GS1 DataBar “()” characters
enable (24F)8000
disable (24F)0000
Leuze electronic DCR 85 29
Tab.8.5: Decoding – Stacked codes
Code Parameter settings Command data
PDF417 Decoding
enable (29)1
disable (29)0
Micro PDF417 decoding
enable (2A)1
disable (2A)0
Tab.8.6: Decoding – 2D codes
Code Parameter settings Command data
Code properties Image transform
No transform (14)0
Mirror (14)1
DataMatrix Settings of register 19 are bitwise OR-connected. Example:
• Command (19)5 enables standard and mirror DataMatrix decoding and disables inverse DataMatrix decoding.
Online commands
DataMatrix Standard decoding
enable (19)1
disable (19)0
DataMatrix Inverse decoding
enable (19)2
disable (19)0
DataMatrix Mirror decoding
enable (19)4
disable (19)0
DataMatrix Rectangular symbology
enable (16)1
disable (16)0
Aztec Settings of register 50 are bitwise OR-connected. Example:
• Command (50)5 enables standard and mirror Aztec decoding and disables in­verse Aztec decoding.
Aztec Standard decoding
enable (50)1
disable (50)0
Aztec Inverse decoding
enable (50)2
disable (50)0
Aztec Mirror decoding
enable (50)4
disable (50)0
Leuze electronic DCR 85 30
Code Parameter settings Command data
QRcode Settings of register 2B are bitwise OR-connected. Example:
• Command (2B)11 enables standard and mirror QRCode decoding and disables inverse, micro, and Model1 QRCode decoding.
QRcode Standard decoding
enable (2B)01
disable (50)00
QRcode Inverse decoding
enable (2B)02
disable (2B)00
QRcode Micro decoding
enable (2B)04
disable (2B)00
QRcode Mirror decoding
enable (2B)10
Online commands
disable (2B)00
QRcode Model1 decoding
enable (2B)20
disable (2B)00
Tab.8.7: Output
Parameter settings Command data
Notification of read failure
enable (55)1
disable (55)0
Output result with AIM ID
AIM ID in prefix (ED)1
No AIM ID in prefix (ED)0
Leuze electronic DCR 85 31
Tab.8.8: Control options
Option Parameter settings Command data
Trigger duration
Trigger duration [ms] (35)0…7FFFFFFF
Decode area
Read in both fields (39)3
Read in high-density field (39)5
Read in wide-angle field (39)6
Continuous action
idle (C4)FF
Read continuously in both fields (C4)03
Read continuously in high-density field (C4)05
Read continuously in wide-angle field (C4)06
Motion control (C4)F0
Illumination
Online commands
Targeting
Beep volume
Minimum illumination (04)0
Leave illumination during read (04)1
enable (0F)1
disable (0F)0
Target time before decoding [ms] (33)0…7FFFFFFF
silent (26)00
low (26)21
medium (26)32
high (26)42
full (26)64
Leuze electronic DCR 85 32
Tab.8.9: Host interface settings
Setting Parameter settings Command data
RS232 Baud rate [BAUD]
9600 (1C)02580
19200 (1C)04B00
38400 (1C)09600
57600 (1C)0E100
115200 (1C)1C200
RS232 Data length
7 bits (1E)7
8 bits (1E)8
RS232 Parity
none (22)0
odd (22)1
even (22)2
Online commands
RS232 Stop bits
1 bit (1D)1
2 bits (1D)2
RS232 Flow control
Disabled (1F)0
Hardware (1F)1
Handshake Acknowledgment expected
enable (42)1
disable (42)0
Acknowledgment time limit [ms] (37)0…7FFFFFFF
Leuze electronic DCR 85 33

9 Care, maintenance and disposal

Usually, the device does not require any maintenance by the operator.

9.1 Cleaning

Clean the glass window of the device with a soft cloth before mounting.
NOTICE
Do not use aggressive cleaning agents!
Ä Do not use aggressive cleaning agents such as thinner or acetone for cleaning the device.

9.2 Servicing

Repairs to the device must only be carried out by the manufacturer.
Ä For repairs, contact your responsible Leuzeelectronic subsidiary or Leuzeelectronic customer service
(see chapter 10 "Service and support").

9.3 Disposing

Ä For disposal observe the applicable national regulations regarding electronic components.
Care, maintenance and disposal
Leuze electronic DCR 85 34

10 Service and support

24-hour on-call service at:
+49 (0) 7021 573-0
Service hotline:
+49 (0) 7021 573-123
Monday to Friday 8.00a.m. to 5.00p.m. (UTC+1)
E-mail:
service.identify@leuze.de
Return address for repairs:
Service center
Leuze electronic GmbH + Co. KG
In der Braike 1
D-73277 Owen / Germany
Service and support

10.1 What to do should servicing be required?

NOTICE
Please use this chapter as a master copy should servicing be required!
Ä Enter the contact information and fax the form together with your service order to the fax
number given below.
Customer data (please complete)
Device type:
Serial number:
Firmware:
Display messages:
Status of LEDs:
Error description:
Company:
Contact person/department:
Phone (direct dial):
Fax:
Street/No:
ZIP code/City:
Country:
Leuze Service fax number:
+49 (0) 7021 573-199
Leuze electronic DCR 85 35

11 Technical data

11.1 General specifications

Tab.11.1: Optics
Optical system CMOS Imager, Rolling Shutter (1280x960)
Optical resolution High-resolution reading field 960x640
Reading area 20mm…300mm
Contrast 1D code: 25%
Resolution 1D code: m=0.076mm (3mil), distance dependent
Technical data
Wide-range reading field 960x640
2D code: 35%
2D code: m=0.127mm (5mil), distance dependent
Light sources
• Illumination
• Alignment LEDs (Aimer)
Tab.11.2: Code specifications
integrated LEDs
• visible red light
• visible blue light
Code type: 1D Codabar, Code11, Code32 , Code39, Code93, Code128, Inter-
leaved2of5, GS1DataBar (RSS), MSIPlessey, Pharmacode, UPC/EAN, 2of5 (IATA, Matrix, Hong Kong, Straight, NEC), Telepen
Code type: Stacked 1D PDF417, MicroPDF, GS1Composite, CodablockF
Code type: 2D DataMatrix, AztecCode, QRCode, MicroQR, MaxiCode
Postal Codes AustralianPost, IntelligentMail, JapanPost, KIXCode, KoreaPost, Planet,
Postnet, UKRoyalMail, UPUIDTags
Tab.11.3: Interfaces
Interface type RS232
Baud rate 9600…115200baud, configurable
Data formats configurable
Trigger • Switching input
• active: 0V
• inactive: +5V or not connected
• Presentation Mode (Motion Control)
Switching output NPN transistor output, max. 20mA, Good Read
Tab.11.4: Electrical equipment
Operating voltage 4.5…5.5VDC
Current consumption Duration reading: typ. 350mA
Inactive illumination: typ. 75mA
LEDs 1 device status
1 read status
Leuze electronic DCR 85 36
Tab.11.5: Mechanical data
Degree of protection IP54
Connection type fixed cable, 2m long, 6x0.081mm² (AWG28)
Weight 70g (without cable)
Dimensions (H x W x D) 25x39x55.5mm
Fastening 3x M2.5 bore holes, 5mm deep
Housing Metal, die-cast aluminum
Tab.11.6: Environmental data
Ambient temp. (operation/storage) 0°C…+50°C/-20°C…+60°C
Air humidity 10%…90% rel. humidity, non-condensing
Electromagnetic compatibility EN55022:2006 ClassB
IEC62471:2006
Conformity CE, FCC
Ambient light max. 100000Lux
Technical data

11.2 Reading fields

NOTICE
Please note that the actual reading fields are also influenced by factors such as labeling mate­rial, printing quality, scanning angle, printing contrast etc., and may thus deviate from the read­ing fields specified here. The origin of the read distance always refers to the front edge of the housing of the beam exit.
Leuze electronic DCR 85 37
Technical data
1
2
3
4
3
4
80 102
33 182
20 220
28 280
43 115
33 150
20 180
28 343
1 Reading fields – side view 2 Reading fields – top view 3 High resolution reading field 4 Wide-range reading field
Fig.11.1: Reading fields
Tab.11.7: Reading fields
Code type Resolution Typical reading distance [mm]
Code 39 0.076mm (3mil)
Code 39 0.190mm (7.5mil)
GS1Data bar 0.267mm (10.5mil)
UPCData bar 0.330mm (13mil)
Data Matrix 0.127mm (5mil)
Data Matrix 0.160mm (6.3mil)
Data Matrix 0.254mm (10mil)
Data Matrix 0.528mm (20.8mil)
Leuze electronic DCR 85 38

11.3 Dimensioned drawings

Technical data
all dimensions in mm A 4 integrated LEDs for illumination (red light) B1 High resolution reading field lens B2 Wide-range reading field lens C 2 integrated target LEDs (blue light) D Status LEDs
Fig.11.2: DCR85 dimensioned drawing
Leuze electronic DCR 85 39

12 Order guide and accessories

12.1 Type overview

Tab.12.1: Part numbers
Part no. Part designation Description
50131458 DCR85M2/R2 CMOS Imager code reader for 1D- and 2D-codes,
50131581 DCR85M2/R2-150-M12.8 CMOS Imager code reader for 1D- and 2D-codes,

12.2 Accessories

Tab.12.2: Accessories
Part no. Part designation Description
Order guide and accessories
RS232 interface, permanently attached connection cable, 2m long
RS232 interface, approx. 0.15m cable with M12 connec­tor (8-pin)
50128204 MA-CR Adapter circuit board for contacting the 12-pin plug
connector and conversion to SUB-D, 9-pin
50113396 KB DSub-9P-3000 RS232 interconnection cable, cable length 3m
50104591 K-D M12A-8P-2m-PUR M12 connection cable, axial 8-pin socket, cable
length 2m, shielded
SensorStudio configuration software
Download at www.leuze.com
see chapter 6.2.1 "Downloading configuration soft­ware"
SensorStudio designed according to the FDT/DTM concept. Contains: communication DTM and device DTM
Leuze electronic DCR 85 40

13 EC Declaration of Conformity

The scan engines of the DCR85 series have been developed and manufactured in accordance with the applicable European standards and directives.
EC Declaration of Conformity
Leuze electronic DCR 85 41

14 Appendix

14.1 Bar code samples

Module 0.3
Fig.14.1: Code type 01: Interleaved 2 of 5
Module 0.3
Fig.14.2: Code type 02: Code 39
Appendix
Module 0.3
Fig.14.3: Code type 11: Codabar
Module 0.3
Fig.14.4: Code 128
Module 0.3
Fig.14.5: Code type 08: EAN 128
SC 2
Fig.14.6: Code type 06: UPC-A
Leuze electronic DCR 85 42
SC 3
Fig.14.7: Code type 07: EAN 8
Appendix
Fig.14.8: Example codes

14.2 Configuration via configuration codes

The device can also be configured using configuration codes. The device parameters in the device are set and permanently saved after reading this code.
Leuze electronic DCR 85 43
DCR 80 Configuration Guide
Appendix
Fig.14.9: DCR80 Configuration Guide
Leuze electronic DCR 85 44
DCR 80 Configuration Guide
Appendix
Fig.14.10: DCR80 Configuration Guide
Leuze electronic DCR 85 45
DCR 80 Configuration Guide
Appendix
Fig.14.11: DCR80 Configuration Guide
Leuze electronic DCR 85 46
DCR 80 Configuration Guide
Appendix
Fig.14.12: DCR80 Configuration Guide
Leuze electronic DCR 85 47
DCR 80 Configuration Guide
Appendix
Fig.14.13: DCR80 Configuration Guide
Leuze electronic DCR 85 48
DCR 80 Configuration Guide
Appendix
Fig.14.14: DCR80 Configuration Guide
Leuze electronic DCR 85 49
DCR 80 Configuration Guide
Appendix
Fig.14.15: DCR80 Configuration Guide
Leuze electronic DCR 85 50
DCR 80 Configuration Guide
Appendix
Fig.14.16: DCR80 Configuration Guide
Leuze electronic DCR 85 51
DCR 80 Configuration Guide
Appendix
Fig.14.17: DCR80 Configuration Guide
Leuze electronic DCR 85 52
DCR 80 Configuration Guide
Fig.14.18: DCR80 Configuration Guide
Appendix
Leuze electronic DCR 85 53
Loading...