Leonard TM-500A, TM-550A, TM-500A-LF Installation And Operating Instructions For The Installer

BULLETIN G-6B
August, 2018
INSTALLATION SETUP AND OPERATING INSTRUCTIONS
THERMOSTATIC WATER MIXING VALVE SYSTEM
IMPORTANT! Provide valve serial number (located on valve body) when ordering parts!!
Starting with TM551A, TM552A, TM553A, …..
Compliance…………ANSI Z 358-1
HOT
INLET
OUTLET
°C °F
ASSE 1017
PRIMARY THERMOSTATIC
MIXING VALVE
HOT
INLET
THERMOMETER
°C °F
CHECKSTOPS
COLD
INLET
TM-500A, TM-500A-LF TM-550A
WARNING: This product can expose you to
chemicals including lead, which is known to the State
!
of California to cause cancer. For more information, go to www.P65Warnings.Ca.gov
INSTALLATION
1. Valve should be installed at a location where it can easily be cleaned, adjusted or repaired.
2. The inlets are clearly marked on the valve body casting. Connect the hot water into the inlet marked "HOT" and cold water into the inlet marked "COLD." These are NOT to be confused with the "C-H" markings on the front cover.
3. Use solder or pipe cement sparingly. Supply pipes should be flushed before the valve is connected. Flush outlet pipe and valve as soon as it is connected.
Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water.
COLD
INLET
REDUNDANT THERMOSTATIC MIXING VALVE
INLINE CHECK
NOTE: TM-500Aand TM-550A are designed for multiple face/eye washes and not to be
used for drench shower applications.
IMPORTANT! These systems are designed to provide mixed water from 60 to 90°F (15 to 32°C) for eye/face wash applications only. Call Leonard for systems designed to operate at temperatures outside of this range.
REMEMBER! THIS IS A CONTROL SYSTEM WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1000).
CAUTION
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
ADJUSTMENT AND SERVICE
Leonard Type TM Thermostatic Water Mixing Valves are simple in design and may be easily cleaned, adjusted and repaired. If the installation is accessible, servicing may be completed without disconnecting the valve.
TO RESET ADJUSTABLE HIGH TEMPERATURE LIMIT STOP:
FINE
POINTER SCREW
POINTER
STOP
1. Loosen LTR Set Screw, remove POINTER SCREW.
2. Adjust POINTER to maximum desired temperature.
3. Remove POINTER, replace POINTER on spline rod with STOP (which is cast into the underside on the pointer), resting against the BOTTOM side of the WEB on the FINE ADJUSTMENT SCREW.
4. If fine adjustment is needed, adjust FINE ADJUSTMENT SCREW on the cover, loosenforhotter or tighten for cooler temperature.
5. Replace POINTER and check temperature, if set to desired temperature replace POINTER SCREW, and tighten LTR SET SCREW.
6. The new maximum temperature has now been set. Test this temperature by holding a thermometer under the flow of water to be certain it is as desired.
* LIMIT STOP MUST BE RESET AND RECHECKED EACH
TIME HANDLE IS REMOVED.
ADJUSTMENT
SCREW
(REST STOP AGAINST SCREW)
LTR
SET SCREW
COLD HOT
ASSE 1017
WEB
Leonard Type TM Thermostatic Water Mixing Valves are simple in design and may be easily cleaned, adjusted and repaired. If the installation is accessible, servicing may be completed without disconnecting the valve.
WARNING
WARNING! This Thermostatic Mixing Valve has an adjustable high
temperature limit stop, which must be checked. If temperature is too high, the installer MUST RESET this stop immediately. Always check the temperature of the mixed water when the lever handle is turned to full
HOT. Excessively hot water is DANGEROUS AND MAY CAUSE SCALDING!
The high temperature limit stop is factory set at approximately 90°F (32°C) with an incoming hot water supply temperature of 135°F (57°C). If the incoming hot water on the job is higher than 135°F (57°C), the valve when turned to full hot will deliver water in excess of 90°F (32°C) and the high temperature limit s top MUST BE RESET BY THE
INSTALLER.
TROUBLESHOOTING INSTRUCTIONS
PARTS REQUIRED:
PACKINGS & GASKETS
PORT SLEEVE ASSEMBLY
THERMOSTAT GROUP
1. Leak at pointer rod.
2. Leak between valve cover and base.
3. Valve delivers all cold water, or will not mix consistently.
4. After cleaning or replacing port sleeve assembly, valve will not hold temperature.
KIT# 1/26 (PACKINGS & GASKETS)
KIT# R/25M (REBUILDING KIT) OR TM25M-1-8B BRIDGE ASSEMBLY
KIT# R/25M (REBUILDING KIT) OR TM25M-G2 THERMOSTAT GROUP
5. Hot water bypass into cold line.
CHECKSTOPS
6. Supplies cannot be shut off completely.
KIT# 4/M20 (CHECKSTOP KIT)
7. Leak at checkstop bonnet.
SEE PAGE 5 FOR COMPLETE PARTS BREAKDOWN, PARTS KITS
Check for significant variations in outlet flow. Thermostatic valves will NOT provide the desired accuracy outside of their flow capacity range. Minimum flows must be no less than shown (see Flow Capacities, page 6).
If installed on a circulated hot water system, make certain the valve is piped according to Leonard Required Methods of Piping (see page 3).
REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000).
2
REQUIRED METHOD OF PIPING TM VALVE
METHOD #1
Required when hot water is to be circulated to a thermostatic mixing valve, which is a substantial distance from
the hot water source.
(THIS PIPING IS NOT TO BE USED FOR AN ENTIRE BUILDING!)
OUTLET
°C °F
THERMOSTATIC
MIXING VALVE
CIRCULATE HOT WATER FROM END OF LINE BACK TO TANK
COLD SUPPLY
HOT SUPPLY
HOT
INLET
OUTLET
COLD INLET
HOT
INLET
(THIS PIPING IS NOT TO BE USED FOR AN ENTIRE BUILDING!)
CIRCULATE HOT WATER FROM END OF LINE BACK TO TANK
COLD INLET
HOT SUPPLY
COLD SUPPLY
°C °F
ASSE 1017
PRIMARY THERMOSTATIC
SECONDARY
THERMOSTATIC
MIXING VALVE
MIXING VALVE
TM-500A TM-550A
The TM-550 Redundant Thermostatic Mixing Valve has been factory set at 90°F (32°C). This set point can be field adjusted with a 3/8” wrench (see diagram). ”Clockwise” direction will increase temperature. Maximum set point is
ADJUSTMENT
100°F (38°C).
SCREW
REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000).
This unit must be cycled each time the emergency equipment is checked. See ANSI Z358.1, Maintenance and Training section:
1. Cycle redundant thermostatic valve by loosening the pointer set screw and setting the primary thermostatic mixing valve to full hot. (TM-550 only)
2. Open eye/face wash and allow temperature to reach the set point.
3. Turn primary thermostatic valve to full cold and wait ten seconds.
4. Turn primary thermostatic valve to full hot and wait for ten seconds.
5. Check to be sure outlet temperature does not climb above 90°F (32°C)
6. Turn primary thermostatic mixing valve to full cold and wait ten seconds.
7. Set primary thermostatic mixing valve to the desired temperature and close eye/fac e wash.
3
INSTRUCTIONS FOR DISMANTLING VALVE (DWG. 1)
1. Shut off hot and cold supplies to valve.
2.Remove four Cover ScrewsM-20-2C to release entire thermostatic control assembly.
WHEN RE-ASSEMBLING VAL VE, insert Cover Gasket M-20-3C in base. Lubricate TM­28-6B O'Rings before re-insertingassembly.
After installing new parts, it will probably be necessary to reset high temperature limit. See instructions "TO RESET ADJUSTABLE HIGH TEMPERATURE LIMIT STOP" (page 2).
TO REMOVE BRIDGE ASSEMBLY (DWG. 2)
Remove MU-10B Pointer Rod Nut, remove TM25M-1-8B Bridge Assembly from pointer rod.
Failure to properly blend the water may be caused by a sticking condition in the TGM-1/25M Port Sleeve Assembly. The Thimble shouldslidefreely on the Port Sleeve.
Clean with a NON-CORROSIVE CLEANING AGENT AND SOFT CLOTH. DO NOT USE ABRASIVES, then wash parts thoroughly.
1.
TM-28-6B
HOLDER NUT O'RING
2.
TM-25M-1-8B
BRIDGE ASSY
M20-2C COVER
SCREWS
M20-3C COVER
GASKET
To reassemble, replace Bridge Assembly on pointer rod. Driving ball on Thimble MUST engage hole in coil bracket. Replace pointer rod nut.
DO NOT apply grease or lubricants to the TGM-1/25M Port Sleeve Assembly.
TO DISASSEMBLE BRIDGE ASSEMBLY (DWG. 3)
Remove TM25-3A Holder Nuts using a screwdriver in the slots provided. Clean or replace TGM-1/25M Port Sleeve Assembly following instructions above. When reassembling, check TM25-3B port sleeve packings and replace if necessary.
TO CLEAN OR REPLACE THERMOSTAT GROUP
Remove stop retaining ring and stop. Loosen gland nut. Push rod through cover. BE CAREFUL NOT TO PULL THERMOSTAT COIL OUT OF SHAPE.
To clean, if a deposit has collected on the thermostat group, brush in a non-corrosive cleaning solution. Rinse in clean water and replace in cover with parts as shown.
57-D
GLAND NUT
M20-3C COVER
GASKET
MU-10B
POINTER ROD NUT
M20-1C COVER
M20-4C
GLAND PACKING (2 REQD)
POINTER ROD NUT
3.
TM-25-3A
P.S. HOLDER NUT
(2 REQ'D)
TM-28-6B
HOLDER NUT O'RING
(2 REQ'D)
TM-25-5 BRIDGE
P.S. HOLDER
4.
To replace entire Thermostatic Control
Assembly specif y TM-25M-1-12B
MU-10B
TM25-3
327 (HOT SIDE)
P.S. HOLDER
329 PACKING
TGM-1/25M
PORT SLEEVE
ASSEMBLY
TM-25-3B
P.S. PACKING
(COLD SIDE)
(HOT SIDE)
NOTE: AFTER INSTALLING NEW PARTS IT WILL BE NECESSARY TO RESET THE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP (SEE PAGE 2).
REMEMBER: THIS IS A CONTROL DEVICE, WHICH MUST BE CLEANED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD, MGR-1001).
TM25M-G2
THERMO GROUP
4
TM-500A, 550A VALVE PARTS
LTR SET SCREW
6910
POINTER SCREW
7520
7628
POINTER
TM25M-1-8B
BRIDGE ASSEMBLY
CHECKSTOP PARTS
57-D
GLAND NUT
MU-4C
GLAND PACKING
(2 REQ'D)
M20-1C COVER
TM-25-3A
P.S. HOLDER NUT
(2 REQ'D)
TM-28-6B
HOLDER NUT O'RING
(2 REQ'D)
TM25-5
BRIDGE
TO CLEAN THERMOSTAT GROUP
Push rod through cover. Be careful not to pull coil out of shape. If a deposit has collected on the thermostat group (TM25M-G2) brush in a non-corrosive cleaning solution.
M20-3C COVER
GASKET
TM25M-G2
THERMOSTAT GROUP
327 (HOT SIDE)
P.S. HOLDER
TM25-3 (COLD SIDE)
P.S. HOLDER
P.S. PACKING (COLD SIDE)
P.S. PACKING (HOT SIDE )
M20-2C
COVER SCREWS (4 REQD)
MU-10B
POINTER ROD NUT
TGM-1/25M
PORT SLEEVE
ASSEMBLY
TM25-3B
329
MU-4A RF/CP
UPPER STEM
M20-9A
AND PACKING
M20-2A RF/CP
CHECK BONNET
MU-5A UPPER
STEM PKG.
CHECKSTOPS
M20-3A BONNET
PACKING
M20-6A LOWER
STEM & PACKING
CHECK SPRING
REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000).
NOTE: AFTER INSTALLING NEW PARTS IT WILL BE NECESSARY TO RESET THE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP ON EACH VALVE (SEE PAGE 2).
KIT 1/26 PACKINGS & GASKETS
MU-4C
GLAND PKG.
(2 EACH)
M20-3A
BONNET PKG.
(2 EACH)
M20-3C COVER
GASKET
M20-9A
(2 EACH)
CHECK SPRING
TM-28-6B
HOLDER NUT
O'RING (2 EACH)
KIT R/25M REBUILDING KIT
M20-3C COVER
GASKET
KIT 4/M20 CHECKSTOP KIT
2 EACH:
LOWER STEM
& PACKING
M20-6A
CHECK SPRING
M20-9A
MU-5A UPPER
STEM O'RING
M20-6A
LOWER STEM
& PKG. (2 EACH)
MU-5A
O'RING
(2 EACH)
TM-25M-1-12B
THERMOSTATIC
CONTROL ASSEMBLY
M20-3A
BONNET PKG.
5
FLOW CAPACITIES
55
50
40
30
20
PRESSURE DROP P.S.I.G.
10
0
234567
MAXIMUM FLOW CAPACITY GALLONS PER MINUTE
CAUTION! All thermostatic water mixing valves have limitations. They will not provide the desired accuracy outside of their flow capacity range. Consult the capacity chart and DO NOT OVERSIZE. Minimum flow must be no less than shown below.
IMPORTANT! These systems are designed to provide mixed water from 60 to 90°F (15 to 32°C) for face/eyewash applications only, these systems are not designed for drench shower applications. Call Leonard for systems designed to operate at temperatures outside of this range.
TM-500A/550A
30810 20 6040 50 70 80 100 150 200
MODEL
TM-500A
TM-550A
IN
OUT
3/4" 3/4"
3/4" 3/4"
MINIMUM
FLOW (GPM)
L\MIN
3.0 11
3.0 11
INTERNAL
COLD WATER
BY-PASS
MINIMUM
8
30
8
30
MAXIMUM FLOW CAPACITY
5
.3
7
26
7
26
SYSTEM PRESSURE DROP
10
15 20 25
.7
1.0
1.4161.7
9
12
13
34
45
49 61
93412
45
13 49
16 18 61
2.1
18 68
20 76
20 76
2.8
22 83
22 8368
4530 35 40
3.12.4 24
91
24 26
50
3.4 26
98
9891
PSI BAR
GPM
L\MIN
GPM
L\MIN
LIMITED WARRANTY
Leonard Valve Company warrants the original purchaser that products manufactured by them (not by others) will be free from defects in materials and workmanship under normal conditions of use, when properly installed and maintained in accordance with Leonard Valve Company's instructions, for a period of one year from date of shipment. During this period the Leonard Valve Company will at its option repair or replace any product, or part thereof, which shall be returned, freight prepaid, to the Leonard factory and determined by Leonard to be defective in materials or workmanship. There are no warranties, express or implied, which extend beyond the description contained herein. There are no implied warranties of merchantability or of fitness for a particular purpose. In no event will Leonard be liable for labor or incidental or consequential damages. Any alteration or improper installation or use of the product will void this limited warranty.
© 2018 Leonard Valve Company Printed in USA
1360 Elmwood Avenue, Cranston, RI 02910 USA
6
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
Loading...