Leonard XL-150-2P, XL-150-2P-LF, XL-200-SW-2P-LF, MEGATRON XL-200-LF, MEGATRON XL-200 Installation Adjustment Service

...
INST ALLA TION ADJUSTMENT SER VICE
XL-150-2P, XL-150-2P-LF
XL-200-SW-2P-LF
PARALLEL SYSTEMS
Note: IMPORTANT! Provide serial numbers for both valves when ordering parts!!
INSTALLATION
Valves are ASSE 1017 Certified
8
0
0
6
20
1
30
0 0
0
10
4
R
LEONARD
40
0
50
-10
2
0
0
2 1
60
°C °F
0
0 4 1
8 0
0 6
20
1
30
0 0
0
10
4
R
LEONARD
40
0
50
-10
2
0
0
2 1
60
°C °F
0
0
4 1
Bulletin XL-2P
August, 2018
LF
V
A
L
D
V
R
E
A
N
C
O
O
E
.
L
W
R
A
E
R
M
LF
LF
N
O
E
L
LF
V
A
L
D
V
R
E
A
C
O
.
W
R
A
E
R
M
WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer. For more information, go
!
to www.P65Warnings.Ca.gov
INSTALLATION
2. The inlets are clearly marked on the valve body. Union angle strainer checkstops furnished must be installed on both supply lines as shown above.
125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE
CAUTION
All thermostatic water-mixing valves have limitations. They will not provide the desired accuracy outside of their flow capacity range. Consult the flow capacity chart on page 5.
Minimum flow must be no less than as shown.
3. Flush pipes thoroughly after system has been connected.
4. Refer to page 2 of this bulletin for correct Setup Instructions
REMEMBER! THIS IS A CONTROL SYSTEM WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1000).
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
1
SETUP INSTRUCTIONS
HIGH TEMPERATURE FIXTURES
SYSTEM FIXTURES
BALL VALVE FOR
SETUP (OPTIONAL)
8
0
0
6
20
1
30
0 0
0
10
4
R
LEONARD
40
0
50
2
-10
0
0
2 1
60
°C °F
0
0 4 1
BALL VALVE #2
CHECK
C
CIRCULATOR
FULL RETURN LINE SIZE
TEMPERED CIRCULATOR
ISOLATION
VALVE
TEMPERED RETURN
C
T
AQUASTAT
WATER
SOURCE
COLD SUPPLY
BALL VALVE #1
HOT
HEAT
TRAP
CHECK VALVES
HIGH TEMPERATURE RETURN
BALANCING VALVE #1
METHOD W SET-UP INSTRUCTIONS
Before any attempt is made to adjust this system, be sure the temperature of the hot water
at the source is properly set and maintained.
1. Shut off circulator, turn ball valve #2 off.
2. Open enough fixtures to flow a minimum of 6 GPM.
3. Set mixing valve #1 to the desired temperature, (note Warning Tag attached to the pointer of the valve).
4. Open ball valve #2 and close ball valve #1.
5. Set mixing valve #2 to the desired temperature, (note Warning Tag attached to the pointer of the valve).
6. Open all ball valves.
7. Shut off all fixtures. Note: At this point, be sure NO water is being drawn through any fixture until the temperature in the recirculated line has been set.
8. Fully open the circuit setter and start the circulator. Make sure no water is being drawn.
9. Observe the temperature until it stabilizes.
10. Close the circuit setter slightly if the temperature is to hot, and again let the temperature stabilize. Repeat until the desired recirculated temperature is set.
2
WARNING
WARNING! This Thermostatic Mixing Valve has an Locking Temperature Regulator (LTR) which
must be checked. If the t emperature is too high, the installer MUST RESET this adjustment immediately. Always check the temperature of the mixed water after installation. Excessively hot water is DANGEROUS AND MAY CAUSE SCALDING!
SERVICE
Leonard Type XL Thermostatic Water Mixing Valves are simple in design and may be easily cleaned, adjusted and repaired. If the installation is accessible, servicing may be completed without disconnecting the valve.
NOTE: Thermostatic Water Mixing Valves are REGULATING mechanisms, which must be regularly maintained to provide best performance. Frequency of cleaning depends on quality of local water conditions and usage. (See Maintenance Guide and Record MGR-1000).
TROUBLESHOOTING INSTRUCTIONS
ITEM:
PACKINGS & GASKETS
REBUILD 3. Valve delivers either all hot or all cold water, or will not mix consistently. KIT R/XL150
CHECKSTOPS
ITEM:
PROBLEM:
1. Leak at stem.
2. Leak between valve cover and base.
4. Hot water bypass into cold line.
5. Supplies cannot be shut off completely.
6. Leak at checkstop bonnet.
PROBLEM:
RECOMMENDED REPAIR KITS:
KIT 1/XL150
KIT 4/984
RECOMMENDED REPAIR KITS:
PACKINGS & GASKETS
REBUILD 3. Valve delivers either all hot or all cold water, or will not mix consistently. KIT R/XL200
CHECKSTOPS
1. Leak at stem.
2. Leak between valve cover and base.
4. Hot water bypass into cold line.
5. Supplies cannot be shut off completely.
6. Leak at checkstop bonnet.
KIT 1/XL200
KIT 2/200/C
REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000).
3
KIT KIT T YPE INCL UDES
R/XL150 COMPLETE REPAIR 1-7 1/XL150 O-RING 2,3,6,7
4/984 CHECK 11-15
ITEM # DESCRIPTI ON QTY.
1 SPRING, RE TURN 1 2 O-RING, LOWE R S HUTTLE 1 KIT 1/XL150, KIT R/XL150
3 O-RING, UPPER SHUTTLE 1 KIT 1/XL150, KIT R/XL150 4 SHUTTLE ASSEMBLY 1 KIT R/XL150 5 RETAINING RING, COVE R 1 7611, KIT R/XL150 6 O'RING, COV ER 1 KIT 1/XL150, K IT R/XL150 7 O'RING, STEM 1 KIT 1/XL150, K IT R/XL150 8 STEM ASSEMBLY (DO NOT REMOVE SNAP RING) 1 771800
9 COVER 1 7762 10 KNOB ASSEMBLY 1 764000 11 LOWER STEM & PACKING 2 KIT 4/984 12 SCREEN 2 KIT 4/984 13 SPRING, CHE CK 2 KIT 4/984 14 O -RING, BONNE T 2 KIT 4/984 15 O-RING. UP PE R S TE M 2 KIT 4/ 984 16 STEM, UPPER CHECK 2 1761 17 CHECK BONNET 2 1786 18 SWIVEL 2 1705 19 SWIVEL NUT 2 4611
PA RT # / KI T #
KIT R/XL150
4
KIT KIT TYPE INCL UDES
R/XL200 COMPLETE REPAIR 1-7 1/XL200 O-RING 2,3,6,7
2/200/C CHECK 11-15
ITEM # DESCRIPTI ON QTY.
1 SPRING, RE TURN 1
2 O-RING, LOWE R S HUTTLE 1 KIT 1/XL200, KIT R/XL200
3 O-RING, UPPER SHUTTLE 1 KIT 1/XL200, KIT R/XL200
4 SHUTTLE ASSEMBLY 1 KIT R/XL200
5 RETAINING RING, COVE R 1 7611, KIT R/XL200
6 O'RING, COV ER 1 KIT 1/XL200, K IT R/XL200
7 O'RING, STEM 1 KIT 1/XL200, K IT R/XL200
8 STEM ASSEMBLY (DO NOT REMOVE SNAP RING) 1 781700
9 COVER 1 7856 10 KNOB ASSEMBLY 1 764000 11 LOWER STEM & PACKING 2 KIT 2/200/C 12 SCREEN 2 KIT 2/200/C 13 SPRING, CHE CK 2 KIT 2/200 /C 14 O -RING, BONNE T 2 KIT 2/200/C 15 O-RING. UP PE R S TE M 2 K IT 2/200 /C 16 STEM, UPPER CHECK 2 4727 17 CHECK BONNET 2 4723 18 SWIVEL (IF APPLICABLE) 2 4704 19 SW IVEL NUT (IF APPLICABLE) 2 4707
PA RT # / KI T #
KIT R/XL200
5
FLOW CAPACITIES
DOUBLE FLOWRATE WHEN BOTH VALVES ARE OPERATING
SINGLE VALVE ASSEMBLY FLOWRATES SHOWN
(MINIMUM FLOW RATE HAS BEEN DOUBLED TO 6GPM)
VALVE
XL-150
VALVE
XL-200
MIN FLOW
6
23
MIN FLOW
10 46
167
216
PRESSURE DROP
280231
326
PRESSURE DROP
443363
LIMITED WARRANTY
511
5045403530252015105
PSI
3.43.12.82.42.11.71.410.70.3
BAR
1301241171101039586746144
492469443416390360
2081981881741631481351179669
787750712659617560
GPM l/min
5045403530252015105
PSI
3.43.12.82.42.11.71.410.70.3
BAR GPM
l/min
Leonard Valve Company warrants the original purchaser that products manufactured by them (not by others) will be free from defects in materials and workmanship under normal conditions of use, when properly installed and maintained in accordance with Leonard Valve Company's instructions, for a period of one year from date of shipment. During this period the Leonard Valve Company will at its option repair or replace any product, or part thereof, which shall be returned, freight prepaid, to the Leonard factory and determined by Leonard to be defective in materials or workmanship. There are no warranties, express or implied, which extend beyond the description contained herein. There are no implied warranties of merchantability or of fitness for a particular purpose. In no event will Leonard be liable for labor or incidental or consequential damages. Any alteration or improper installation or use of the product will void this limited warranty.
1360 Elmwood Avenue, Cranston, RI 02910 USA
© 2018 Leonard Valve Company Printed in USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
6
Loading...