Leonard MEGATRON 270, MEGATRON 370, MEGATRON 270-LF, MEGATRON 370-LF Installation Adjustment Service

MEGATRON®MODEL 270/370
MODEL 270-LF, 370-370-LF
SYSTEMS
WARNING: This product can expose you to
chemicals including lead, which is known to the State
!
OUTLET
of California to cause cancer. For more information, go to www.P65Warnings.Ca.gov
Bulletin M-270/370
August, 2018
TEST/SETUP CONNECTION
0
4
2 0
INLET
8 0
0
6
20
30
10
R
LEONARD
0
-10 60
°C °F
0
4 1
HOT
8
0
0
6
20
1
30
0 0
0
10
4
R
LEONARD
40
0
50
-10
2
0
0
2 1
60
°C °F
0
0 4
1
1 0 0
40
50
0 2 1
0
0
4
2 0
COLD INLET
INSTALLATION
1. Megatron 270/370 systems is factory pre-assembled and tested System should be installed at a location where it can easily be cleaned,adjusted or repaired.
2. System supplies must be connected as shown (Hot-left, Cold-right). Exercise caution when soldering.
RETURN LINE
8
0
0
6
20
1
30
0 0
0
10
4
R
8
0
0
6
20
1
30
0 0
10
R
LEONARD
40
0
50
-10
0 2 1
60
°C °F
0
0 4
1
LEONARD
40
0
50
-10
2
0
0
2 1
60
°C °F
0
0
4
1
TO HOT
WATER SOURCE
4. Flush pipes thoroughly after system has been connected.
5. Refer to page 4 of this bulletin for correct Setup Instructions.
NOTE: NOT TO BE USED FOR
EYEWASH APPLICATIONS
Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water.
! CAUTION !
All thermostatic water mixing valves have limitations. They will not provide the desired accuracy outside of
their flow capacity range. Consult the capacity chart on page 4.
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
ADJUSTMENT AND SER VICE
TEMPERA TURE ADJUSTMENT
WARNING
WARNING! This thermostatic mixing valve’s
temperature setting MUST be checked. If the temperature is too high (above 110ºF, 43ºC), the temperature knob must be adjusted immediately. Excessively hot water is DANGEROUS AND MAY
1. Open hot and cold water supply valves to mixing valve.
2. Open mixed water outlet.
3. With the fixture in the full open position, calibrate the mixed water outlet temperature by placing a thermometer in the mixed water stream. Loosen knob set screw with 5/64” allen wrench. Adjust the setting of the valve to obtain the desired temperature (counterclockwise, to increase temperature-clockwise to decrease temperature.)
4. Tighten knob set screw to lock temperature setting.
CAUSE SCALDING!!
PRESSURE-TEMPERATURE:
Minimum Flow:0.5 GPM (1.9 l/Min)Maximum Pressure:125 PSI (8.6 BAR)Maximum Hot Water temperature: 200F- (93°C)Approach Temperature 5°F (2.8°C) above set
point.
TROUBLESHOOTING INSTRUCTIONS
GASKET KIT Leaking water under knob.
Leaking water between valve cover and body.
REBUILDING KIT Valve will not control temperature after
cleaning.
CHECKSTOP KIT Hot water by-pass into cold line.
Cold water by-pass into hot line.
SEE PAGE 3 FOR COMPLETE PARTS BREAKDOWN
SEE PAGE 4 FOR PIPING IN RECIRCULATED OR NON-RECIRCULATED WATER SYSTEMS
MODEL
270
370
IN OUT
1/2" 1/2"
3/4" 3/4"
MINIMUM
FLOW (GPM)
L\MIN
0.5
1.96415 23
5
.3
3.50.25 5.5
10
.7
210.95 13
15 20 25
6.5 7.5 8.5
27 30934
PRESSURE DROP
87
GASKET KIT Model 270 1/WX Model 370 1/WX
REBUILDING KIT Model 270 R/270/370 Model 370 R/270/370
CHECK KIT Model 270 4/220 Model 370 4/320
3.4
PSI
50
BAR GPM
12 45
L\MIN
GPM
13 49
L\MIN
30
35 40 45
2.1
1.71.0 1.4
9.5 36
3225 28
10 38
2.82.4 3.1
10.510
11.5
4038 43
11.510.5
12.5
40 43 47
IMPORTANT!! THIS IS A CONTROL SYSTEM WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1001).
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
WEB: http://www.leonardvalve.com 2
VALVE PARTS LIST
CHECK CLIP (MODEL 270/370 ON LY)
RETAINING CLIP
STEM ASSEMBLY O'RING
KNOB
SCREW
DIAL PLATE
K NOB S E T S CREW
MODEL 270, 370
MODEL 270
1/ WX Gasket Kit
Shuttle o’ring Stem assembly o’ring Cover o’ring
R/ 270/370 Complete Rebuild Kit
Return spring Shuttle assembly Shuttle o’ring Stem assembly o’ring Cover o’ring
4/220 Check valve Kit
2 Check valves 2 Check clips
COVER O'RING
STEM ASSEMBLY DO NO T REMOVE SNAP RING ON STEM - INJURY MAY
OCCUR
COVER
1/ WX Gasket Kit
R/ 270/370 Complete Rebuild Kit
4/320 Check valve Kit
CHECK
SHUTTLE ASSEMBLY
RETURN SPRING
SH UTTLE O 'RING
MODEL 370
Shuttle o’ring Stem assembly o’ring Cover o’ring
Return spring Shuttle assembly Shuttle o’ring Stem assembly o’ring Cover o’ring
2 Check valves 2 Check clips
DISMANTLING & CLEANING TROUBLESHOOTING
1. Shut off hot and cold water to the valve as well as the valve outlet port.
2. Loosen lock screw on side of knob with 5/64” allen wrench.
3. Remove the knob screw on top of knob.
4. Remove temperature adjustment knob.
5. Remove valve cover, which includes the stem assembly.
6. The shuttle assembly can now be removed, cleaned and inspected. Be sure to check the condition of the shuttle o-ring and replace if necessary.
7. Lubricate the shuttle o-ring before installing the shuttle assembly.
8. Install the cover assembly including o-ring back onto valve and tighten.
9. Replace knob and knob screw.
10. Valve temperature must be reset after any repairs or cleaning!! See Page 2. Temperature Adjustment
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
WEB: http://www.leonardvalve.com
1. Leaking water under knob, order gasket kit, replace stem assembly o-ring. Remove knob screw and knob, remove retaining clip, thread out the stem assembly and replace o-ring. Lubricate o-ring, thread stem into cover, replace retaining ring, knob and screw. Valve temperature must be reset after any
repairs or cleaning!! See page 2.
2. Leaking water between cover and body, order gasket kit, replace cover o-ring. Remove knob screw and knob and remove valve cover and replace o-ring. Replace valve cover, knob and knob screw. Valve temperature must be reset after any
repairs or cleaning!! See page 2.
3. Hot water bypass into cold line, order checkstop kit and replace checks within inlets of valve.
4. Valve not controlling temperature even after cleaning, order complete rebuild kit. Remove knob screw and knob and remove valve cover. Replace shuttle assembly and return spring being sure to lubricate shuttle o-ring. Replace valve cover, knob and knob screw. Valve temperature must be reset after any
repairs or cleaning!! See page 2.
3
REQUIRED METHOD OF PIPING
(RECIRCULATED DOMESTIC WATER SYSTEMS)
DOMESTIC TEMPERED
WATER
8
0
0
6
20
1
30
0 0
0
10
4
LEONARD
40
0
50
-10
2
0
0
2 1
60
°C °F
0
0 4 1
8
0
0
6
20
1
30
0 0
0
10
4
LEONARD
8
HOT
WATER
SOURCE
HIGH
TEMP.
WATER
HEAT
TRAP
8
0
0
0
0 6
6
1
20
20
30
30
0 0
0
0
10
10
4
4
LEONARD
LEONARD
40
40
0
0
50
50
-10
-10
2
2
0
0
0
2 1
60
60
°C
°C
°F
°F
0
0
0
0
4
4 1
1
40
0
1
50
0
-10
0
2
0
0
2 1
60
°C °F
0
0 4 1
0 2 1
BALANCING VALVE
DOMESTIC
COLD SUPPLY
RECIRCULATED WATER
HIGH TEMPERATURE RECIRCULATED WATER
THIS PIPING METHOD IS NOT TO BE USED FOR MORE THAN ONE BUILDING
PROCEDURE TO BALANCE RECIRCULA TION SYSTEM
1. ADJUST THE BALANCING VALVE TO FULL OPEN, TURN THE RECIRCULATION PUMP OFF AND FLOW WATER BY EITHER USING FIXTURES OR BY USING THE TEST CONNECTION.
2. ADJUST THE VALVE HANDLE TO THE APPROPRIATE TEMPERATURE.
3. CLOSE THE FIXTURES AND / OR TEST CONNECTION, TURN ON THE RECIRCULATION PUMP.
4. OBSERVE THE TEMPERATURE, IF THE TEMPERATURE REMAINS AT THE SET POINT SET UP IS COMPLETE. IF THE TEMPERATURE INCREASES CLOSE DOWN THE BALANCING VALVE SLOWLY UNTIL IT RETURNS TO SET POINT.
LIMITED WARRANTY
Leonard Valve Company (hereinafter, “Leonard”) warrants the original purchaser that products manufactured by Leonard will be free from defects in material or workmanship under normal conditions of use, when properly installed and maintained in accordance with Leonard’s instructions, for a period of one year from the date of shipment. During this period, Leonard will at its option repair or replace any product, or part thereof, which shall be returned, freight prepaid, to the Leonard factory and determined by Leonard to be defective in materials or workmanship. Leonard provides no warranty, express or implied, which extends beyond the description contained herein. LEONARD SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. Nonetheless, some jurisdictions may not allow the disclaimer of certain implied warranties, in which case Leonard hereby limits such implied warranties to the duration of the limited warranty period contained herein. Some jurisdictions may not allow limitations on how long an implied warranty lasts, so the foregoing durational limitation may not apply to you. In no event will Leonard be liable for labor or incidental or consequential damages. Any alteration or improper installation or use of this product will void this limited warranty. If any provision of this limited warranty is prohibited by law in the applicable jurisdiction, such provision shall be null and void, but the remainder of this limited warranty shall continue in full force and effect.