This documentation provides you with information about the intended use of the monitor
panel.
The present manual is part of the "Controller−based automation" or "PC−based
automation" manual collection which you can find on the DVDs of the same name.
Target group
This documentation is directed at qualified skilled personnel according to IEC 60364.
Qualified skilled personnel are persons who have the required qualifications to carry out
all activities involved in installing, mounting, commissioning, and operating the product.
Tip!
Information and auxiliary devices related to the Lenze products can be found
in the download area at
http://www.Lenze.com
About this documentation1
Validity
These instructions are valid for
ƒ MP 800 DVI
ƒ MP 1000 DVI, MP 1000s DVI
ƒ MP 1050 DVI, MP 1050s DVI
ƒ MP 2000 DVI
ƒ MP 2050 DVI
ƒ MP 5000 DVI
ƒ MP 5020 DVI
ƒ MP 5050 DVI
ƒ MP 5070 DVI
ƒ MP 9000 DVI
BA_MP9000DVI DE 4.0
5
1
About this documentation
Document history
1.1Document history
Material numberVersionDescription
.NpW4.002/2014TD06New:
134330853.003/2013TD29General revision
133923032.011/2011TD29Supplement of the note concerning the protection
133855111.007/2011TD29First edition
l UL notes (French language)
l Notes RJ45 cable laying
against direct solar radiation, as well as chapter
"Repair"
6
BA_MP9000DVI DE 4.0
About this documentation
Conventions used
1
1.2Conventions used
This documentation uses the following conventions to distinguish between different
types of information:
Type of informationIdentificationExamples/notes
Spelling of numbers
Decimal separatorPointIn general, the decimal point is used.
Warnings
UL warnings
UR warnings
Text
Program name» «PC software
Icons
Page referenceReference to another page with additional
Documentation referenceReference to another documentation with
For instance: 1234.56
Given in English and French
For example: »Engineer«, »Global Drive
Control« (GDC)
information
For instance: 16 = see page 16
additional information
For example: EDKxxx = see
documentation EDKxxx
BA_MP9000DVI DE 4.0
7
1
About this documentation
Notes used
1.3Notes used
The following pictographs and signal words are used in this documentation to indicate
dangers and important information:
Safety instructions
Structure of safety instructions:
Danger!
Pictograph and signal wordMeaning
Danger!
Danger!
Stop!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous
situations)
Danger of personal injury through dangerous electrical voltage.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of personal injury through a general source of danger.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of property damage.
Reference to a possible danger that may result in property
damage if the corresponding measures are not taken.
Application notes
Pictograph and signal wordMeaning
Note!
Tip!
Special safety instructions and application notes
Pictograph and signal wordMeaning
Warnings!
Warnings!
Important note to ensure troublefree operation
Useful tip for simple handling
Reference to another documentation
Safety note or application note for the operation according to
UL or CSA requirements.
The measures are required to meet the requirements according
to UL or CSA.
8
BA_MP9000DVI DE 4.0
2Safety instructions
2.1General safety information
Scope
The following general safety instructions apply to all Lenze drive and automation
components.
The product−specific safety and application notes given in this documentation must be
observed!
For your own safety
Danger!
Disregarding the following basic safety measures may lead to severe personal
injury and damage to material assets!
Safety instructions
General safety information
2
ƒ Lenze drive and automation components ...
... must only be used for the intended purpose.
... must never be operated if damaged.
... must never be subjected to technical modifications.
... must never be operated unless completely assembled.
... must never be operated without the covers/guards.
... can − depending on their degree of protection − have live, movable or rotating parts
during or after operation. Surfaces can be hot.
ƒ For Lenze drive and automation components ...
... only use approved accessories.
... only use original manufacturer spare parts.
ƒ All specifications of the corresponding enclosed documentation must be observed.
This is vital for a safe and trouble−free operation and for achieving the specified product
features.
The procedural notes and circuit details provided in this document are proposals which
the user must check for suitability for his application. The manufacturer does not
accept any liability for the suitability of the specified procedures and circuit proposals.
ƒ Only qualified skilled personnel are permitted to work with or on Lenze drive and
automation components.
According to IEC 60364 or CENELEC HD 384, these are persons ...
... who are familiar with the installation, assembly, commissioning and operation of
the product,
... possess the appropriate qualifications for their work,
... and are acquainted with and can apply all the accident prevent regulations, directives
and laws applicable at the place of use.
BA_MP9000DVI DE 4.0
9
2
Safety instructions
General safety information
Transport, storage
ƒ Transport and storage in a dry, low−vibration environment without aggressive
atmosphere; preferably in the packaging provided by the manufacturer.
– Protect against dust and shocks.
– Comply with climatic conditions according to the technical data.
Mechanical installation
ƒ Install the product according to the regulations of the corresponding
documentation. In particular observe the section "Operating conditions" in the
chapter "Technical data".
ƒ Provide for a careful handling and avoid mechanical overload. During handling
neither bend components, nor change the insulation distances.
ƒ The product contains electrostatic sensitive devices which can easily be damaged by
short circuit or static discharge (ESD). Thus, electronic components and contacts
must not be touched unless ESD measures are taken beforehand.
Electrical installation
ƒ Carry out the electrical installation according to the relevant regulations (e. g. cable
cross−sections, fusing, connection to the PE conductor). Additional notes are
included in the documentation.
ƒ When working on live products, observe the applicable national regulations for the
prevention of accidents (e.g. BGV 3).
ƒ The documentation contains notes for the EMC−compliant installation (shielding,
earthing, arrangement of filters and installation of the cables). The manufacturer of
the system or machine is responsible for the compliance with the limit values
required in connection with EMC legislation.
ƒ For compliance with the limit values for radio interference emission at the site of
installation, the components − if specified in the technical data − have to be mounted
in housings (e. g. control cabinets). The housings have to enable an EMC−compliant
installation. In particular observe that for example control cabinet doors preferably
have a circumferential metallic connection to the housing. Reduce openings or
cutouts through the housing to a minimum.
ƒ Only plug in or remove pluggable terminals in the deenergised state!
Commissioning
ƒ If required, you have to equip the system with additional monitoring and protective
devices in accordance with the respective valid safety regulations (e. g. law on
technical equipment, regulations for the prevention of accidents).
10
BA_MP9000DVI DE 4.0
Maintenance and servicing
ƒ The components are maintenance−free if the required operating conditions are
observed.
ƒ If the cooling air is polluted, the cooling surfaces may be contaminated or the air
vents may be blocked. Under these operating conditions, the cooling surfaces and air
vents must be cleaned at regular intervals. Never use sharp objects for this purpose!
ƒ After the system has been disconnected from the supply voltage, live components
and power connections must not be touched immediately because capacitors may
be charged. Please observe the corresponding notes on the device.
Disposal
ƒ Recycle or dispose of the product according to the applicable regulations.
2.2Product−specific safety instructions
Safety instructions
Product−specific safety instructions
2
ƒ Protect the device against direct solar radiation, since the housing may heat up
strongly.
ƒ The device is classified as a class A device and can cause radio interference in
residential areas. In this case, the operator may have to take special measures. Any
costs arising from these measures have to be paid by the operator.
ƒ A touchscreen does not comply with the Ergonomics Directive ZH 1/618. This is why
it is only designed for short−time inputs and monitoring functions. For longer inputs,
connect an external keyboard.
ƒ In the event of a fault, unplug the power connector immediately and send back the
device to the manufacturer. The address can be found on the self−addressed
envelope included in this documentation. Please use the original packaging to
return the device!
ƒ Printed circuit boards which might be damaged by short circuit or electrostatic
discharge (ESD) must be handled appropriately.
BA_MP9000DVI DE 4.0
11
2
Safety instructions
Safety instructions for the installation according to UL
2.3Safety instructions for the installation according to UL
Original − English
Approval
Underwriter Laboratories (UL), UL508 and CSA C22.2 No. 142−M1987, (UL File Number
E236341)
Ratings
ƒ Input 24 V DC, 65 W
ƒ For use on an isolated power supply rated 24V DC 4A max.
ƒ Max. ambient temperature 40°C
ƒ Max. surrounding temperature 50 °C
ƒ Optional communication ratings:
– RS232−Connection (APL and DPL version only): max. 3 A
– USB−Connection (DVI version only): max. 1 A
– PS/2−Connection: max. 1 A
– VGA−Connection (APL version only): max. 4 A
– FBAS−Connection (APL version only): max. 4 A
– DVI−Connector (DVI version only): max. 4 A
– DPL−Connection (DVI version only): max. 4 A
– External Power Supply for DVI/USB Extender: max. 4 A
– Video−DSUB Connection for DVI/USB Extender: max. 4 A
– Data−DSUB Connection for DVI/USB Extender: max. 4 A
ƒ Environmental ratings: If these devices are mounted into a door or front cover of an
enclosure: Type 1 Enclosure.
Warnings!
Conditions of acceptability
ƒ These devices are for Type 1 front panel mounting only.
ƒ The external power supply connection is suitable for field wiring. An isolated
power supply rated 24 V DC, 4 A max. must be used.
Safety instructions for the installation according to UL
Original − French
Homologation
Underwriter Laboratories (UL), UL508 et CSA C22.2 n° 142−M1987, (n° de dossier UL
E236341)
Caractéristiques assignées
ƒ Entrée 24 V CC, 65 W
ƒ Equipement destiné à une alimentation avec isolation galvanique de 24V CC, 4A
maximum (tension assignée).
ƒ Température ambiante maximale : 40°C
ƒ Température ambiante maximale : 50 °C
ƒ Caractéristiques de communication assignées (option) :
– Port RS232 (versions APL et DPL uniquement) : maximum 3 A
– Port USB (version DVI uniquement) : maximum 1 A
– Port PS/2 : maximum 1 A
– Port VGA (version APL uniquement ) : maximum 4 A
– Port FBAS (version APL uniquement) : maximum 4 A
– Port DVI (version DVI uniquement) : maximum 4 A
– Port DPL (version DVI uniquement) : maximum 4 A
– Alimentation externe pour carte d’extension DVI/USB : maximum 4 A
– Port vidéo DSUB pour carte d’extension DVI/USB : maximum 4 A
– Port de données DSUB pour carte d’extension DVI/USB : maximum 4 A
2
ƒ Evaluations environnementales : en cas de montage des équipements dans la porte
ou le capot avant d’un coffret de protection : coffret de type 1.
Warnings!
Conditions of acceptability
ƒ Ces équipements sont conçus pour un montage de type 1 sur panneau
avant uniquement.
ƒ Le raccord d’alimentation externe est adapté à un câblage à pied d’oeuvre.
Utiliser impérativement une alimentation avec isolation galvanique de 24V
CC, 4A maximum (tension assignée).
Marquage du câblage à pied d’oeuvre
Bornier de câblage MSTB 2,5/3−STF−5,08 :
ƒ Utiliser exclusivement des conducteurs en cuivre.
ƒ AWG 18 ... AWG 12 (0,82 mm
ƒ Couple de 5 à 7 lb−in (0,5 ... 0,6 Nm)
1Connection plug for voltage supply
1DVI−D cable (length 2 m)
1USB cable (length 2 m)
1DVD "PC based Automation"
1Test report
1Device pass card
Note!
After receipt of the delivery, check immediately whether the items match the
accompanying papers. We do not accept any liability for deficiencies claimed
subsequently.
Claim
ƒ visible transport damage immediately to the forwarder
ƒ visible deficiencies/incompleteness immediately to your Lenze
representative.
14
BA_MP9000DVI DE 4.0
3.2Application as directed
The monitor panel is used as intended if it is used solely for providing information in
common industrial and commercial areas. Another use or any further use is not
permissible.
A use that is not intended also includes a use harbouring fatal risks or dangers which,
without the provision of exceptionally high safety measures, may result in death, injury or
damage to material assets.
The monitor panel must in particular not be used ...
ƒ in private areas.
ƒ in potentially explosive atmospheres.
ƒ in areas with harmful gases, oils, acids, radiation, etc.
ƒ in applications where vibration and impact loads occur, exceeding the requirements
of EN 50178.
Product description
Application as directed
3
ƒ for performing safety functions, for instance
– in air traffic control / in flight−control systems
– for the monitoring/control of nuclear reactions
– for the monitoring/control of means of mass transport
– for the monitoring/control of medical systems
– for the monitoring/control of weapon systems
Higher−level safety systems must be used to guarantee the protection of persons and
material assets!
3.3Device features
Designl PC housing of sheet steel
Mountingl For installation in control cabinets, machine enclosures, and control
Electrical supplyl 24 V DC voltage supply
Interfacesl 1 x DVI
MP 800 DVI ... MP 9000 DVI
l Front frame of anodised and etched aluminium
l Front made of polyester foil
boards
l 2 x USB type A (V 2.0)
l 1 x USB type B (V 2.0)
Accessories
ƒ DVI/USB extender
BA_MP9000DVI DE 4.0
15
3
Product description
Device features
Overview
Monitor panel MP 800 DVI / MP 1000 DVI / MP 1000s DVI / MP 2000 DVI / MP 5000 DVI / MP 9000 DVI
l MP 800 DVI: VGA touchscreen 20.3 cm (8")
MP 1000 DVI: VGA touchscreen 26.4 cm (10.4")
MP 1000s DVI: SVGA touchscreen 26.4 cm (10.4")
MP 2000 DVI: SVGA touchscreen 30.7 cm (12.1")
MP 5000 DVI: XGA touchscreen 38.1 cm (15")
MP 9000 DVI: SXGA touchscreen 48.3 cm (19")
l 3 freely assignable function keys
l XGA touchscreen 38.1 cm (15")
l 12 freely assignable function keys
l 14 freely assignable special keys
Monitor panel MP 5020 DVI
S1
S2
S3
S4
S5
S6
S7
Power
Fail
Status
F1
F2
+
F3
-
CS57x0−026
S8
S9
S10
S11
S12
S13
S14
+
Power
Fail
Status
-
F4
F3F2
F1
Esc
F11 F12F6F5F7 F8 F9 F10
Enter
ELx7xx−002
Monitor panel MP 1050 DVI / MP 1050s DVI / MP 2050 DVI / MP 5050 DVI
l MP 1050 DVI: VGA touchscreen 26.4 cm (10.4")
MP 1050s DVI: SVGA touchscreen 26.4 cm (10.4")
MP 2050 DVI: SVGA touchscreen 30.7 cm (12.1")
MP 5050 DVI: XGA touchscreen 38.1 cm (15")
l 12 freely assignable function keys
l Numeric keypad, control keys, level switch−over
Alpha
Q+R
ST
-
F1 F2F5
F3 F4
A
BCD
-
8
9
7
E
FGH
+6
4
5
I
JKL
3
1
2
*
M
NOP
,
.
0
/
Power
PgUp
Fail
Status
Home
End
PgDn
EscDelIns
Bs
Menu
AltCtrl
Shift
Space
Alpha
Enter
WVU
F7F6
F11F10YXF9F8F12
@\Z
CS57x0−028
16
BA_MP9000DVI DE 4.0
Monitor panel MP 5070 DVI
+
-
F4
F3F1 F2
F5
EWQ
T
R
@
€
D
SA
F
XY
GHJ
VC
OIPÜUZ
LK
;
M
NB
,
μ
F9F8F6 F7F10
Ö
:
.
Product description
3
Device features
l XGA touchscreen 38.1 cm (15")
l 12 freely assignable function keys
/
(
)
-
879
&
$
+
546
§
"
!
123
*
=
>
,
|
<
/
0
Power
Fail
Status
Bs
Entf
Bild
Einfg
AltGr
Bild
Pos1
Ende
AltStrg
F12
Esc
F11
*
~
+
Enter
Ä
\?ß
_
Space
-
CS57x0−029
l MF2 keyboard
BA_MP9000DVI DE 4.0
17
3
107AT12345
Product description
Identification
3.4Identification
31855 Aerzen; Germany
Madein Germany
Typ e
107AT12345
Type codexxxx2x1
5201 = MP 1000 DVI
5202 = MP 1000s DVI
5203 = MP 2000 DVI
5204 = MP 5000 DVI
5205 = MP 9000 DVI
5206 = MP 5020 DVI
5207 = MP 1050 DVI
5208 = MP 1050s DVI
5209 = MP 2050 DVI
5210 = MP 5050 DVI
5211 = MP 5070 DVI, keyboard layout German
5212 = MP 5070 DVI, keyboard layout English
5213 = MP 800 DVI
Type designation
Type code (catalogue/order no.)
Technical data
Customised material number
Bar code with serial number
Manufacturer address
Certification
CE mark
DVIUSB−012
18
Front face USB socket
0 = without
1 = with (IP65)
BA_MP9000DVI DE 4.0
3.5Controls and displays
Product description
3
Controls and displays
10
0V U
2
3
+
DVI
USB-A
USB-B
24 V DC
Power
Fail
Status
4
F1
F2
+
5
F3
-
0V U
01
Pos.Description
Monitor panel (here MP 5000 DVI)
Front face USB port (option)
Screw clamp fixings
Nameplate
Status LEDs (Power, Fail, Status)
Front face control and display elements
Note!
Further information on the control and display elements can be gathered from
the chapter "Operation" ( 32).
MP9000DVI−001
BA_MP9000DVI DE 4.0
19
4
Technical data
General data and operating conditions
4Technical data
4.1General data and operating conditions
General data
Conformity and approval
Conformity
CE
Approbation
URUL 508
Other
RoHS−Products lead−free in accordance with CE Directive
EN 61000−6−4
EN 61000−6−2
CSA C22.2
EMC Directive Class A, industrial premises
Programmable Controllers (File−No. E236341)
2011/65/EU
Protection of persons and equipment
SafetyVDE0805 (EN60950),
EnclosureEN 60529IP65 (front) / IP20 (back)
Class of protection3
EMC
Noise emissionEN 61000−6−4
Noise immunity zone BEN 61000−6−2
*Due to the high−energy single current pulses, surges require suitable external wiring with lightning protection
elements like for example lightning conductors and overvoltage arresters.
VDE0870, UL
UL 508 (NEMA 250)Type 1 enclosure
Class A (industrial premises)
Industrial premises
EN 61000−4−2ESD; severity level 3, i. e.
8 kV for air discharge,
4 kV for contact discharge
EN 61000−4−3RF interference (housing)
80 MHz 1000 MHz, 10 V/m 80 % AM (1 kHz)
EN 61000−4−4Burst, severity level 3
EN 61000−4−5Surge, severity level 1 *
EN 61000−4−6RF cable−guided
150 kHz 80 MHz, 10 V/m 80 % AM (1 kHz)
20
BA_MP9000DVI DE 4.0
Technical data
General data and operating conditions
Operating conditions
Mounting conditions
Place of installation
Mounting positionConnections at the bottom
Ambient conditions
Climatic
Storage
Transport−10 ... +60 °C
Operation+5 ... +45 °C
Relative humidity10 ... 90 %, non−condensing
Site altitude
StoragetTransport< 12000 m amsl
Operation< 3000 m amsl
Chemical resistance
Decor film
Touch/display
Mechanical load capacity
Decor film
Touch/display
Switching element
DIN 42115
DIN 42115max. 100 N
In the control cabinet, screen protected against direct solar
radiation
−10 ... +60 °C
4
BA_MP9000DVI DE 4.0
21
4
Technical data
Electrical data
4.2Electrical data
VoltageCurrent at
[V DC][A][cm][pixels][cd/m2][h]
MP 800 DVI
MP 1000 DVI
MP 1050 DVI
MP 1000s DVI
MP 1050s DVI
MP 2000 DVI
MP 2050 DVI
MP 5000 DVI
MP 5020 DVI
MP 5050 DVI
MP 5070 DVI
MP 9000 DVI1.448.3 (19")5:41280 x 10243001 : 200050 000
24
(+18 ... 30)
4.3Mechanical data
SupplyScreen
24 V
0.4
0.7
0.938.1 (15")1024 x 7682501 : 55040 000
Visible
size
20.3 (8")
26.4
(10.4")
30.5
(12.1")
Aspect
ratio
4:3
Resolution Brightness ContrastMTBF
1 : 25050 000
640 x 480400
4001 : 500
800 x 600
3001 : 200
1 : 30040 000
50 000
Versions and weights
MP 800 DVI
MP 1000 DVI
MP 1000s DVI
MP 1050 DVI
MP 1050s DVI
MP 2000 DVI
MP 2050 DVI
MP 5000 DVI
MP 5020 DVI
MP 5050 DVI
MP 5070 DVI
MP 9000 DVI
Front frame / housingTouchscreenMass
[kg]
3.0
4.2
4.2
4.6
4.6
Aluminium/sheet steel
Polyester foil
5.4
5.6
6.2
6.4
6.4
7.2
10.2
22
BA_MP9000DVI DE 4.0
Technical data
Mechanical data
a
b
All dimensions in millimetres.
Dimensions
abe
[mm]
MP 800 DVI
MP 1000 DVI
MP 1000s DVI
MP 1050 DVI
MP 1050s DVI
MP 2000 DVI
MP 2050 DVI
MP 5000 DVI
MP 5020 DVI
MP 5050 DVI
MP 5070 DVI
MP 9000 DVI49040069
265
325
365
390300
425310
450325
483
200
240
310 (7 U)
399 (9 U)
6e
65
4
MP9000DVI−003
59
BA_MP9000DVI DE 4.0
23
5
Mechanical installation
Important notes
5Mechanical installation
5.1Important notes
The installation must be carried out by qualified, skilled personnel familiar with the
applicable national standards.
Stop!
Sensitive front frame gasket
During mounting, the gasket of the front frame is exposed and can be
damaged.
Possible consequences:
ƒ The degree of protection provided by the enclosure mentioned in the
technical data is not attained.
Protective measures:
ƒ Handle the gasket with care during mounting.
ƒ Protect the gasket against ultraviolet rays.
ƒ Each time before you mount the device, check whether the gasket is intact.
Stop!
Sensitive touchscreen surface
The touchscreen foil is very sensitive to external forces and can be damaged by
improper handling.
Possible consequences:
ƒ The touchscreen foil becomes damaged, scratched or dull.
Protective measures:
ƒ Avoid contact of the touchscreen foil with pointed or hard objects.
ƒ Always use a touch pen or your fingers to operate the touchscreen. Never
use objects such as ballpoint pens, pencils, etc.
ƒ When removing dirt and fingerprints, observe the notes given in the chapter
"Cleaning" ( 38).
Note!
When selecting the place where the PC is to be installed, pay attention to an
ergonomic positioning of the screen and to the incidence of light which might
cause reflections on the screen.
24
BA_MP9000DVI DE 4.0
5.2Mounting cutout
b3
b4
b1
b5
b2
a2
a1
Mechanical installation
Mounting cutout
1
0
5
D
Mounting cutout
Outline of front panel
Control board
2
£ 5
ELx7xx−004
All dimensions in millimetres.
Dimensions
a1a2b1b2b3b4b5D
[mm]
MP 800 DVI246−188−−−−−
MP 1000 DVI
MP 1000s DVI
MP 1050 DVI
MP 1050s DVI
MP 2000 DVI
MP 2050 DVI
MP 5000 DVI
MP 5020 DVI
MP 5050 DVI
MP 5070 DVI
MP 9000 DVI438.0451.0386.0172.0172.060.060.08 x Æ4.5
305.0−228.0−−−−−
343.0−228.0−−−−−
340.0351.0288.0122.0122.00.0−
375.0386.0288.0122.0122.00.0−
400.0411.0313.0134.5134.50.0−
452.0462.4299.0104.9104.615.7−
452.0462.4388.2149.3149.315.9−
6 x Æ5.5
BA_MP9000DVI DE 4.0
25
5
5.3Mounting steps
5.3.1MP 1000(s) DVI / MP 1050(s) DVI
Mechanical installation
Mounting steps
MP 1000(s) DVI / MP 1050(s) DVI
How to perform the installation:
1. Cut the mounting cutout into the control board ( 25).
2. Check that the gasket under the front panel is located correctly.
3. Place the device in the mounting cutout and secure it against falling−down with one
hand.
4. Fit all screw clamp fixings as explained below:
– Insert the screw clamp fixing into the slot in the housing of the device (see above
figure).
– Press the screw clamp fixing downwards, tilt it towards the housing and check
that it has firmly snapped into place.
– Tighten the screw clamp fixing hand−tight with a screwdriver.
5. Check that the device is securely located in the mounting cutout and that the front
panel gasket is located correctly.
– If necessary, realign the device/gasket.
– If the gasket is not located correctly, protection class IP65 is not achieved on the
front of the device!
ELx7xx−011
26
BA_MP9000DVI DE 4.0
Mechanical installation
Mounting steps
MP 2xxx DVI / MP 5xxx DVI / MP 9xxx DVI
5
5.3.2MP 2xxx DVI / MP 5xxx DVI / MP 9xxx DVI
Note!
Types MP 5020 DVI, MP 5050 DVI, and MP 5070 DVI can be installed in any
control panel and in 19" mounting racks in accordance with DIN 41494.
Control board mounting
How to perform the installation:
1. Prepare the control board by cutting the mounting cutout and drilling the mounting
holes into it ( 25).
2. Check that the gasket under the front panel is located correctly.
3. Place the device in the mounting cutout, secure it by hand against falling down and
screw the nuts and washers onto the threaded bolts.
4. Fit all screw clamp fixings as explained below:
ELx7xx−012
– Insert the screw clamp fixing into the slot in the housing of the device (see above
figure).
– Press the screw clamp fixing downwards, tilt it towards the housing and check
that it has firmly snapped into place.
– Tighten the screw clamp fixing hand−tight with a screwdriver.
5. Check that the device is securely located in the mounting cutout and that the front
panel gasket is located correctly.
– If necessary, realign the device/gasket.
– If the gasket is not located correctly, protection class IP65 is not achieved on the
1. Remove the set screws from the back of the front frame.
2. Drill through the blind holes at the back of the front frame using a 6.5 mm drill.
3. Place the device in the 19" mounting rack and screw it.
BA_MP9000DVI DE 4.0
27
6
Electrical installation
Important notes
6Electrical installation
6.1Important notes
The installation must be carried out by qualified, skilled personnel familiar with the
applicable national standards.
Stop!
Short circuit and static discharge
The device contains components which are endangered in the case of short
circuit or static discharge.
Possible consequences:
ƒ The device or parts of it will be destroyed.
Protective measures:
ƒ Always switch off the voltage supply when working on the device. This
particularly applies:
– Before connecting / disconnecting connectors.
– Before plugging in / plugging out modules.
ƒ All persons handling printed circuit boards have to take account of ESD
measures.
ƒ Contacts of plug connectors must not be touched.
ƒ Printed circuit boards may be touched only at places free from electrical
contacts and may be placed only on appropriate materials (e.g. on ESD
packaging or conductive foam material).
ƒ Printed circuit boards may only be transported and stored in ESD packaging.
28
BA_MP9000DVI DE 4.0
6.2Wiring according to EMC
Electrical installation
Wiring according to EMC
6
General notes l The electromagnetic compatibility of the system depends on the type and accuracy of the
installation. Please especially note the following:
– Structure
– Shielding
– Earthing
l In the case of a differing installation it is required for evaluating the conformity to the EMC
Directive to check the system with regard to compliance with the EMC limit values. This for
instance applies to:
– The use of unshielded cables
l The end user is responsible for compliance with the EMC Directive.
– If you observe the following measures, you can be sure that no EMC problems will occur
during operation and that the EMC Directive or the EMC law is met.
– If devices which do not meet the CE requirement with regard to noise immunity
EN 61000−4−2 are actuated near the system, these devices can be affected
electromagnetically by the system.
Structurel Connect device to the earthed mounting plate:
– Mounting plates with an electroconductive surface (zinc−coated or stainless steel) allow for
continuous contacting.
– Coated plates are not suitable for an EMC−compliant installation.
l If you use several mounting plates:
– Connect mounting plates to each other on a large surface and in a conductive manner (e.g.
by means of copper strips).
l When installing the cables, observe a spatial separation of signal and mains cables.
l Route the cables as near to the reference potential as possible. Freely suspended cables act
like aerials.
Shieldingl Preferably only use cables with a braid.
l The coverage of the shield should be more than 80%.
l In the case of data lines for a serial coupling, always use metallic or metallised plugs. Connect
the shield of the data line on the connector shell.
Earthingl Earth all metallically conductive components by the use of corresponding cables from a
central earthing point (PE rail).
l Comply with the minimum cross−sections defined in the safety instructions:
– With regard to EMC, however, not the cable cross−section, but the surface of the cable and
of the extensive contacting is decisive.
BA_MP9000DVI DE 4.0
29
6
Electrical installation
Connecting the supply and peripheral devices
Terminal diagram supply
6.3Connecting the supply and peripheral devices
6.3.1Terminal diagram supply
L1
N
PE
0
0 V
PE+24 V
+
Monitor panel
Power supply unit
S
F
L1
~=
1
N
+
+
+24
0V
MP9000DVI−006
Note!
6.3.224 V connection
0VU
Observe the max. permissible input voltage.
Professionally fuse the device on the input side against voltage variations and
voltage peaks.
DescriptionConnection typeCable type
DC 24 V connection
IPC001
PE connectionM4 threaded bolt
IPC001
3−pole Phoenix Combicon
socket
Cable (conductor
cross−section max. 2.5 mm
with Phoenix Combicon plug,
MSTB 2.5 / 3−STF−5.08
Separate earthing conductor
(min. 2.5 mm
2
) with ring
cable lug
2
)
30
BA_MP9000DVI DE 4.0
Electrical installation
Connecting the supply and peripheral devices
DVI interface
6
6.3.3DVI interface
Note!
Only use the DVI cable from the scope of supply or one of the DVI cables
specified in the following table, featuring a maximum length of 2 m.
Otherwise a faultless signal transmission is not guaranteed.
Greater distances can be covered with the following Lenze accessories:
2 ... 5 m: "DVI/USB" cable set
5 ... 35 m: DVI/USB extender V4
IPC001
6.3.4USB interface
IPC001
DescriptionConnection typeCable type
DVI interfaceDVI−D socket
DescriptionConnection typeCable type
USB 2.0 host connection
Max. load: 5 V/500 mA
USB−A socketUSB cable with USB−A plug
DVI−D single link (18+1)
DVI−D double link (24+1)
DescriptionConnection typeCable type
USB
DVI/USB−010
USB device connectionUSB−B socketUSB cable with USB−B plug
6.3.5USB interface on the front face (option)
DescriptionConnection typeCable type
USB 2.0 host connection with
IP 65 cover
Max. load: 5 V/500 mA
EL100−013
Note!
If you use USB interfaces routed to the outside, the data integrity cannot be
guaranteed. On the "PC based Automation" DVD you’ll find the "FM Tool"
software which can be used to deactivate the front USB interface if it is not
needed.
USB−A socketUSB cable with USB−A plug
BA_MP9000DVI DE 4.0
31
7
Operation
Important notes
7Operation
7.1Important notes
Stop!
Sensitive touchscreen surface
The touchscreen foil is very sensitive to external forces and can be damaged by
improper handling.
Possible consequences:
ƒ The touchscreen foil becomes damaged, scratched or dull.
Protective measures:
ƒ Avoid contact of the touchscreen foil with pointed or hard objects.
ƒ Always use a touch pen or your fingers to operate the touchscreen. Never
use objects such as ballpoint pens, pencils, etc.
ƒ When removing dirt and fingerprints, observe the notes given in the chapter
"Cleaning" ( 38).
32
BA_MP9000DVI DE 4.0
Operation
Controls and displays
Monitor Panel MP 800 DVI / MP 1000 DVI / MP 1000s DVI / MP 2000 DVI /
7.2Controls and displays
7.2.1Monitor Panel MP 800 DVI / MP 1000 DVI / MP 1000s DVI / MP 2000 DVI /
MP 5000 DVI / MP 9000 DVI
0
Power
Fail
Status
1
F1
F2
+
F3
2
-
7
CS50x0−022
Pos. Designation
Function
Standard modeService mode
Switch on mode:Press "" for 4 s
Switch off mode:Press "" or wait for 35 s
DisplayApplication−dependent
Status LEDsPower (green):
l Is ON when the supply voltage is present.
Fail (red):
l Is On when a power supply failure has occurred.
l Is blinking when the screen signal is missing.
Status (yellow):
l Application−dependent
Function keysF1 ... F3: Send key code for Shift−F1 ...
Function keysF1 ... F12: Send key code for Shift−F1 ...
MF2 keysStandard function of a MF2 keyboard
/
(
)
879
&
$
546
§
"
!
123
=
>
,
|
<
0
Bs
Entf
Einfg
Alt Gr
Pos 1
Ende
F9F8F6 F7F10
*
OIPÜUZ
+
Ä
LK
Ö
_
;
:
,
-
.
AltStrg
F12
Esc
F11
~
Enter
\?ß
Space
0
-
+
3
*
/
Power
Fail
Status
1
3
Bild
Bild
3
2
3
Function
Standard modeService mode
l Is ON when the supply voltage is present.
Fail (red):
l Is ON when a power supply failure has occurred.
l Is blinking when the screen signal is missing.
Status (yellow):
l Indicates access to a storage medium.
Tool: Application−dependent
Shift−F12
+: Increase screen brightness
−: Reduce screen brightness
CS50x0−025
36
BA_MP9000DVI DE 4.0
8Maintenance
Stop!
Short circuit and static discharge
The device contains components which are endangered in the case of short
circuit or static discharge.
Possible consequences:
ƒ The device or parts of it will be destroyed.
Protective measures:
ƒ Always switch off the voltage supply when working on the device. This
particularly applies:
– Before connecting / disconnecting connectors.
– Before plugging in / plugging out modules.
ƒ All persons handling printed circuit boards have to take account of ESD
measures.
ƒ Contacts of plug connectors must not be touched.
ƒ Printed circuit boards may be touched only at places free from electrical
contacts and may be placed only on appropriate materials (e.g. on ESD
packaging or conductive foam material).
ƒ Printed circuit boards may only be transported and stored in ESD packaging.
Maintenance
Regular checks
8
8.1Regular checks
The device is free of maintenance. Nevertheless, visual inspections should be carried out
at regular intervals which must not be too long, depending on the ambient conditions.
Please check the following:
ƒ Does the environment of the device meet the operating conditions specified in the
Technical data?
ƒ Is the heat dissipation of the device not impeded by dust or dirt?
ƒ Are the mechanical and electrical connections o.k.?
BA_MP9000DVI DE 4.0
37
8
8.2Cleaning
Maintenance
Cleaning
Stop!
ƒ Before cleaning, disconnect the device from the power supply as otherwise
unintentional commands may be activated via the touchscreen, for example a
response of the control.
Sensitive surfaces and components
The device can be damaged if it is not appropriately cleaned.
Possible consequences:
ƒ The housing or the screen gets scratched or dull if you use alcoholic,
solvent−containing or scouring cleaning agents.
ƒ Electrical components can be damaged ...
– by a short circuit caused by humidity.
– by static discharge.
Protective measures:
ƒ Observe the following notes.
ƒ Clean the device front (screen and frame) as follows:
– Use a clean, lint−free and soft cloth.
– Moisten the cloth with the detergent. Do not spray the detergent directly on the
device.
– Only use water with a fluid addition as detergent or a detergent declared
especially for flat screens.
ƒ Clean the rear side of the device with a clean, lint−free and soft cloth. Do not use
liquid or foaming detergent since it may enter the housing or terminals.
38
BA_MP9000DVI DE 4.0
8.3Repair
For the repair of the monitor panel, its housing has to be removed.
8.3.1Removing and mounting the housing
Dismounting
Maintenance
Repair
Removing and mounting the housing
8
24 V DC
Mounting
MP9000DVI−015
24 V DC
MP9000DVI−016
BA_MP9000DVI DE 4.0
39
8
Maintenance
Repair
Fuse change
8.3.2Fuse change
Stop!
Damage of the device by non−permissible fuse possible
The baseboard in the device is protected by a fuse which will be damaged if
the supply voltage applied is too high.
Possible consequences:
ƒ The device can be damaged if a non−approved fuse is installed.
Protective measures:
ƒ The fuse may only be replaced by an approved type.