Lenovo RT1.5kVA, RT2.2kVA, RT3kVA Product Manual

RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies
Product Guide
The RT1.5kVA, RT2.2kVA, and RT3kVA 2U Rack or Tower Uninterruptible Power Supply (UPS) offerings provide extended power protection with increased efficiency and simplified power management to safeguard the high-availability of Lenovo server environments. With efficiency ratings of up to 99%, these compact 2U rack or tower designs can help reduce energy usage without compromising performance or reliability.
The 2U Rack or Tower UPS units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required.
The 2U Rack UPS unit with the Extended Battery Module is shown in Figure 1.
Figure 1. 2U Rack UPS unit (top) with Extended Battery Module (bottom)
Did you know?
2U Rack or Tower UPS units feature Advanced Battery Management (ABM) technology that uses a unique, three-stage charging technique that significantly extends battery service life and optimizes recharge time compared to traditional charging methods.
2U Rack or Tower UPS units can enhance system availability with individual receptacle groups or load segments that can be programmed and controlled, which allows mission-critical devices to be prioritized during shutdown to preserve battery run time if there is a prolonged power outage.
2U Rack or Tower UPS units come standard with UPS Power Manager software that integrates seamlessly with the major virtualization platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 1
Ordering information
Table 1 shows the orderable part numbers and feature codes for the 2U Rack or Tower UPS models and options.
Table 1. Ordering part numbers and feature codes
Description Part number Feature code
UPS units
RT1.5kVA 2U Rack or Tower UPS (100-125VAC) 55941AX A53S (5594-RU1)
RT1.5kVA 2U Rack or Tower UPS (200-240VAC) 55941KX A53T (5594-RU1)
RT2.2kVA 2U Rack or Tower UPS (100-125VAC) 55942AX A53U (5594-RU2)
RT2.2kVA 2U Rack or Tower UPS (200-240VAC) 55942KX A53V (5594-RU2)
RT3kVA 2U Rack or Tower UPS (100-125VAC) 55943AX A53W (5594-RU3)
RT3kVA 2U Rack or Tower UPS (200-240VAC)* 55943KX A53X (5594-RU3)
Extended Battery Modules (EBMs)
1.5kVA/2.2kVA 2U Rack or Tower Extended Battery Module 55942BX A53Y
3kVA 2U Rack or Tower Extended Battery Module 55943BX A53Z
Options
UPS Network Management Card* 46M4110 6145
Environmental Monitoring Probe 46M4113 6146
* RT3kVA 2U Rack or Tower UPS (200-240VAC) comes standard with the UPS Network Management Card.
The UPS models are shipped with the following items:
An accessory kit that contains the following items:
Rack-mount kit Rack installation instructions Tower kit Serial cable: 3.7 m (12 ft) USB cable Remote On/Off (ROO) and Remote Power Off (RPO) connector
Documentation package
Software CD, which contains UPS Manager power management software
The Extended Battery Modules are shipped with the following items:
An accessory kit that contains the following items:
Rack-mount kit Tower kit EBM power cable EBM detection cable
The 100-125 V UPS models ship with the following fixed line cords:
RT1.5kVA 2U Rack or Tower UPS (100-125VAC): 2.5 m (8 ft) line cord with NEMA 5-15P plug RT2.2kVA 2U Rack or Tower UPS (100-125VAC): 2.5 m (8 ft) line cord with NEMA 5-20P plug RT3kVA 2U Rack or Tower UPS (100-125VAC): 2.5 m (8 ft) line cord with NEMA L5-30P plug
The RT1.5kVA, RT2.2.kVA, and RT3kVA 200-240 V UPS models do not ship with line cords. Table 2 and Table 3 list the compatible line cords which are suitable for RT1.5kVA and RT2.2kVA/RT3kVA 200-240 V UPS models, respectively.
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 2
Table 2. Line cords for 200-240 V units (RT1.5kVA models)
Description Part number Feature code
Argentina 10A/250V C13/ IRAM 2073 4.3m line cord 81Y2384 6492
Australia 10A/250V C13/ AS/NZS 3112/2000 4.3m line cord 81Y2383 6574
Brazil 10A/250V C13/ NBR 14136 4.3m line cord 81Y2387 6404
China 10A/250V C13 / GB2099.1 4.3m line cord 81Y2378 6580
Denmark 10A/250V C13/SB107-2-DI 4.3m line cord 81Y2382 6575
Europe 10A/250V C13 / CEE 7/7 4.3m line cord 81Y2376 6572
India 10A/250V C13/IS 6538 4.3m line cord 81Y2386 6567
Israel 10A/250V C13/ SI 32 4.3m line cord 81Y2381 6579
Italy 10A/250V C13/ CEI 23-16 4.3m line cord 81Y2380 6493
Korea 12A/250V C13/KSC 8305 4.3m line cord 81Y2385 6494
South Africa 10A/250V C13/ SANS 164-1 4.3m line cord 81Y2379 6576
Switzerland 10A/250V C13/SEV 1011 4.3m line cord 81Y2390 6578
Taiwan 10A/250V C13/CNS 10917 4.3m line cord 81Y2389 6531
United Kingdom 10A/250V C13 / BS 1363A 4.3m line cord 81Y2377 6577
Table 3. Line cords for 200-240 V units (RT2.2kVA/RT3kVA models)
Description Part number Feature code
C19 4.3m cord - NEMA L6-20P 40K9772 6275
C19 4.3 meter Line Cord - UK 40K9767 6278
C19 4.3 meter Line Cord - Europe 40K9766 6279
C19 4.3 meter Line Cord - S Africa 40K9770 6280
C19 4.3 meter Line Cord - Italy 40K9768 6281
C19 4.3 meter Line Cord - Israel 40K9771 6282
C19 4.3 meter Line Cord - Dmk/Swiss 40K9769 6283
C19 4.3 meter Line Cord - Australia/NZ 40K9773 6284
C19 4.3 meter Line Cord - India 40K9776 6285
Taiwan 16A/250V C19/CNS 10917 4.3m line cord 90Y3035 6287
C19 4.3 meter Line Cord - China 40K9774 6288
South Korea 15A/250V C19/KSC 8305 4.3m line cord 90Y3034 6289
Japan 15A/200V C19/JIS C-8303 4.3m line cord 41Y9233 6291
C19 4.3 meter Line Cord - Argentina 40K9777 6276
C19 4.3 meter Line Cord - Brazil 40K9775 6277
All 2U Rack or Tower UPS models except model 3KX come equipped with a communication bay for the installation of an optional Network Management Card (46M4110). Model 3KX comes standard with a Network Management Card (NMC) installed.
The NMC provides convenient, over-the-network UPS remote monitoring and management through a standard web browser or UPS Power Manager software. Figure 2 shows the UPS NMC.
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 3
Figure 2. UPS Network Management Card
The NMC has the following features:
Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
Simultaneous shutdown of protected servers
Configuration of automatic email messages in response to UPS alarms and to transmit reports
Customizable actions, including automatic shutdown if there is an extended power failure with standard UPS Power Protector software
Control of UPS on/off switching with a web browser
Adjustment and control of load segments through the HTML interface, including sequential starting of the installation and optimization of backup time by shutting down non-priority systems
Automatic date and time adjustment through an NTP server
Dual stack IP v4/IP v6
Recording of events and measurements in the card log
Data and event logging in the nonvolatile memory
Card firmware update through the network
10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
Measurement of humidity and temperature with the optional Environmental Monitoring Probe (EMP)
Easy installation (can be installed while the UPS is online, which maintains the highest availability)
An optional EMP (part number 46M4113) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC.
Figure 3. Environmental Monitoring Probe
The EMP has the following features:
Monitors temperature, humidity, and status of two user-provided contact devices/sensors
Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable included with the EMP)
Can be located up to 20 m (65.6 ft) from the UPS
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 4
Measures ambient temperatures between 0 - 80 °C (32 - 176 °F) with an accuracy of ±1 °C
Measures relative humidity between 10 - 90% with an accuracy of ±5%
Temperature, humidity, and contact closure status can be displayed through a web browser
Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
Events are stored in the NMC's event log
Sends SNMP alarms to network management systems
Sends e-mail notifications through SMTP
Features
A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure.
In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial impact on all sized businesses. The typical utility power is 99.9% available, but that means that there can be almost 9 hours of downtime a year, not to mention brownouts and other power quality problems. Selecting the right UPS can help protect against these potentially costly incidents.
The RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower UPS units are most effective against power failures, power sags, power surges, under-voltage, and over-voltage.
The RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower UPS models offer the following features:
High-efficiency protection for more real power (Watts) in a compact tower or 2U rack design, which lowers power and cooling consumption
A graphical Liquid Crystal Display (LCD) that provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
English French German Spanish Russian Portuguese Italian
Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
Standard UPS Power Manager software that provides effective local or remote power monitoring and management for servers and virtual machines, and allows for graceful remote system shutdown
ABM technology that significantly extends battery service life and optimizes recharge time
Load segments for individual control of receptacle groups to manage sequential shut downs and start ups and reserve battery run time for the most critical equipment
Optional external battery modules (EBMs) that provide extra run time to critical systems during a prolonged power outage
An optional NMC for enhanced UPS monitoring and control over-the-network through a standard web browser
An optional EMP for thermal management requirements (temperature and humidity)
Dual channel communication through the USB or RS-232 port and an optional NMC at the same time to maximize communications flexibility
The USB port supports HID (Human Interface Device) Power Device Class which means that the UPS can be directly managed by operating systems that support such USB classes.
Remote flash upgradeable firmware for the UPS and NMC, which makes it an ideal solution for
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 5
remote locations
An ROO/RPO port to control power of the UPS unit through a wired remote switch
Technical specifications
Table 4 lists the technical specifications for the 100-125 V UPS models.
Table 3. Technical specifications for 100-125 V models
Specification
RT1.5kVA 2U Rack or Tower UPS (100-125VAC)
RT2.2kVA 2U Rack or Tower UPS (100-125VAC)
RT3kVA 2U Rack or Tower UPS (100­125VAC)
General
Part number 55941AX 55942AX 55943AX
Form factor 2U Rack or Tower 2U Rack or Tower 2U Rack or Tower
Topology Line interactive, high frequency, sinewave output
VA/Watts rating 1440 VA/1440 W @ 120 V 1950 VA/1920 W 3000 VA/2700 W
Efficiency (on utility power) Up to 98% Up to 99% Up to 99%
Energy Star compliant Yes Yes Yes
Electrical input
Input voltage 100 - 125 V AC 100 - 125 V AC 100 - 125 V AC
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz
Max input amperage 12 A 16 A 24 A
Input connector NEMA 5-15P (12 A) NEMA 5-20P (16 A) NEMA L5-30P (24 A)
Input line cord Fixed 2.5 m (8 ft) NEMA 5-
15P
Fixed 2.5 m (8 ft) NEMA 5­20P
Fixed 2.5 m (8 ft) NEMA L5-30P
Electrical output
Output voltage settings 100/120/125 V AC 100/120/125 V AC 100/120/125 V AC
Output frequency 50/60 Hz 50/60 Hz 50/60 Hz
Output power capacity 100 V AC: 1200
VA/1200 W
120-125 V AC: 1440 VA/1440 W
100 V AC: 1330 VA/1300 W
120-125 V AC: 1950 VA/1920 W
100 V AC: 2400 VA/2160 W
120-125 V AC: 3000 VA/2700 W
Output connectors 8x NEMA 5-15R (12
A)
8x NEMA 5-20R (16 A)
6x NEMA 5-20R (16 A)
1x NEMA L5-30R (24 A)
Output load segments Master: 4x 5-15R
Group 1: 2x 5-15R
Group 2: 2x 5-15R
Master: 4x 5-20R
Group 1: 2x 5-20R
Group 2: 2x 5-20R
Master: 2x 5-20R, 1x L5-30R
Group 1: 2x 5-20R
Group 2: 2x 5-20R
Batteries
Battery type Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, leak-proof
Battery capacity 7.2 Ah 9 Ah 9 Ah
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 6
Battery management ABM technology or temperature-compensated charging method (user selectable),
automatic battery test and deep discharge protection, automatic recognition of external battery units
Battery replacement Hot-swap internal battery and extended battery modules
External battery support Up to 4 (PN 55942BX) Up to 4 (PN 55942BX) Up to 4 (PN 55943BX)
Typical backup times See Table 6
Communications and management
USB port (Type B) Yes Yes Yes
RS-232 serial port (RJ-45) Yes Yes Yes
10/100 Mbps Ethernet port (RJ-45)
Optional with Network Management Card, 46M4110
Environmental monitoring Optional with Environmental Monitoring Probe, 46M4113 (requires Network
Management Card, 46M4110)
Management software UPS Power Manager (UPM) and UPS Power Protector (UPP)
Control panel Intelligent 5-button graphical LCD
LED indicators Power On, On Battery, and Alarm
Remote On/Off and Power Off
Remote On/Off (ROO) and Remote Power Off (RPO) terminal block connector
Specification
RT1.5kVA 2U Rack or Tower UPS (100-125VAC)
RT2.2kVA 2U Rack or Tower UPS (100-125VAC)
RT3kVA 2U Rack or Tower UPS (100­125VAC)
The following table lists the technical specifications for the 2U Rack or Tower 200-240 V UPS models.
Table 4. Technical specifications for 200-240 V models
Specification
RT1.5kVA 2U Rack or Tower UPS (200-240VAC)
RT2.2kVA 2U Rack or Tower UPS (200-240VAC)
RT3kVA 2U Rack or Tower UPS (200-240VAC)
General
Part number 55941KX 55942KX 55943KX
Form factor 2U Rack or Tower 2U Rack or Tower 2U Rack or Tower
Topology Line interactive, high frequency, sinewave output
VA/Watts rating 1500 VA/1100 W 2200 VA/1980 W 3000 VA/2700 W
Efficiency (on utility power) Up to 98% Up to 99% Up to 99%
Energy Star compliant Yes Yes Yes
Electrical input
Input voltage 200 - 240 V AC 200 - 240 V AC 200 - 240 V AC
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz
Max input amperage 10 A 16 A 16 A
Input connector IEC 320 C14 (10 A) IEC 320 C20 (16 A) IEC 320 C20 (16 A)
Input line cord Optional (See Table 2) Optional (See Table 3) Optional (See Table 3)
Electrical output
Output voltage settings 200/208/220/230/240 V AC 200/208/220/230/240 V AC 200/208/220/230/240 V AC
Output frequency 50/60 Hz 50/60 Hz 50/60 Hz
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 7
Output power capacity 200-240 V AC: 1550 VA /
1100 W
200 V AC: 1700 VA/1530 W
208 V AC: 1980 VA/1780 W
220-240 V AC: 2200 VA/1980 W
200 V AC: 2700 VA/2430 W
208-240 V AC: 3000 VA/2700 W
Output connectors 8x IEC 320 C13 (10 A) 8x IEC 320 C13 (10
A)
1x IEC 320 C19 (16 A)
8x IEC 320 C13 (10 A)
1x IEC 320 C19 (16 A)
Output load segments Master: 4x C13
Group 1: 2x C13
Group 2: 2x C13
Master: 4x C13, 1x C19
Group 1: 2x C13
Group 2: 2x C13
Master: 4x C13, 1x C19
Group 1: 2x C13
Group 2: 2x C13
Batteries
Battery type Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, leak-proof
Battery capacity 7.2 Ah 9 Ah 9 Ah
Battery management ABM technology or temperature-compensated charging method (user selectable),
automatic battery test and deep discharge protection, automatic recognition of external battery units
Battery replacement Hot-swap internal battery and extended battery modules
External battery support Up to 4 (PN 55942BX) Up to 4 (PN 55942BX) Up to 4 (PN 55943BX)
Typical backup times See Table 7
Communications and management
USB port (Type B) Yes Yes Yes
RS-232 serial port (RJ-45) Yes Yes Yes
10/100 Mbps Ethernet port (RJ-45)
Optional with the Network Management Card, 46M4110 Yes (on the NMC)
Environmental monitoring Optional with the Environmental Monitoring Probe, 46M4113 (requires the Network
Management Card, 46M4110)
Management software UPS Power Manager (UPM) and UPS Power Protector (UPP)
Control panel Intelligent 5-button graphical LCD
LED indicators Power On, On Battery, and Alarm
Remote On/Off and Power Off
Remote On/Off (ROO) and Remote Power Off (RPO) terminal block connector
Specification
RT1.5kVA 2U Rack or Tower UPS (200-240VAC)
RT2.2kVA 2U Rack or Tower UPS (200-240VAC)
RT3kVA 2U Rack or Tower UPS (200-240VAC)
The following two tables list the expected period that the 2U Rack or Tower UPS models operate based only on batteries, depending on the load.
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and temperature.
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies 8