Rack installation instructions
Be sure to read and understand the documentation that comes with the rack cabinet for safety and cabling information. Before you install the server in a rack cabinet, review the following guidelines:
v Two or more people are required to install devices 2U or larger in a rack cabinet. v Make sure that the room air temperature is below 35°C (95°F). v Do not block any air vents; usually 15 cm (6 inches) of space provides proper airflow. v Do not leave open spaces above or below an installed server in your rack cabinet. To help prevent
damage to server components, always install a blank filler panel to cover the open space and to help ensure proper air circulation.
v Install the server only in a rack cabinet with perforated doors. v Start from the bottom of the rack cabinet for the device installation. v Install the heaviest device in the bottom of the rack cabinet. v Do not extend more than one device out of the rack cabinet at the same time. v Remove the rack doors and side panels to provide easier access during installation. v Connect the server to a properly grounded outlet. v Do not overload the electrical outlet when you install multiple devices in the rack cabinet. v Install the server in a rack that meets the following requirements:
– Minimum depth of 70 mm (2.76 inches) between the front mounting flange and inside of the front
door.
– Minimum depth of 157 mm (6.18 inches) between the rear mounting flange and inside of the rear
door.
– Minimum depth of 740 mm (29.13 inches) and maximum depth of 910 mm (35.83 inches) between
the front and rear mounting flanges to support the use of the cable-management arm.
Use safe practices when lifting.
18 kg (39.7 lb)
Do not place any object on top of rack-mounted devices.
Remove the left and right guide rail components from the package. The illustration below shows the components of the right guide rail. The components of the left guide rail are the same as those of the right.
32 kg (70.5 lb) 55 kg (121.2 lb)
Page 2
1 Retaining screw for the front bracket 2 Pin on the front bracket 3 Front bracket 4 Bearing bracket 5 Rear bracket
Remove the retaining screws on the front and rear brackets.
2
Page 3
According to the length between the front post and the rear post of the rack, adjust the length of rail by moving the rear bracket of the rail 1 until the pins at the front and rear of the brackets click into the holes in the rack posts. When the pins are in place, install the retaining screws on the front and rear of the bracket.
Notes:
1. The stretching range of the outer guide rail is 740 mm (29.13 inches) to 910 mm (35.83 inches). Confirm the size of the rack before the installation.
2. The left and the right outer guide rails should be fixed to the left and the right posts of the rack at the same level.
3. If the holes in the post are square holes, you can operate according to the above methods.
4. If the holes in the post are round holes, remove the retaining screws and pins on the front and rear brackets and install the pins shipped with guide rails. Then install the retaining screws shipped with guide rails to secure the guide rails onto rack.
Place the server on the bearing bracket and push it inside. While pushing the server, you have to support the bottom of the server with hands to avoid the drop of the server.
When the server is in place, install the two retaining screws on the left and right handles to secure the server on the rack.
3
Page 4
To remove the server from the rack, reverse these instructions. Store this information with your server documentation for future use.
First Edition (April 2010)
Printed in USA
Lenovo and the Lenovo logo are trademarks of Lenovo in the United States, other countries, or both.
© Copyright Lenovo 2010.
LENOVO products, data, computer software, and services have been developed exclusively at private expense and are sold to governmental entities as commercial items as defined by 48 C.F.R. 2.101 with limited and restricted rights to use, reproduction and disclosure.
LIMITED AND RESTRICTED RIGHTS NOTICE: If products, data, computer software, or services are delivered pursuant a General Services Administration GSAcontract, use, reproduction, or disclosure is subject to restrictions set forth in Contract No. GS-35F-05925.
(1P) P/N: 46U3543
Loading...