This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance
is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
In the Commonwealth of Massachusetts:
• Installation must be performed by a licensed plumber or
gas fitter.
See Table of Contents for location of additional
Commonwealth of Massachusetts requirements.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING: IF THE INFORMATION IN THIS MANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapors or liquids in the vicinity of this or any other appliance.
INSTALLATION
INSTRUCTIONS
DIRECT VENT
ELITE® SERIES
VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS
P/N 850,017M REV. K 06/2008
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE
LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE
BLESSURE OU LA MORT.
FOR YOUR SAFETY: What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• If your gas supplier cannot be reached, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
US
A French manual is available upon request. Order Form Number
850,017CF.
Ce manuel d’installation est disponible en francais, simplement
en faire la demande. Numéro de la pièce 850,017CF.
OTL Report No. 116-F-05-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser
d'essence ni d'autre vapeurs ou liquides inflammables
dans le voisinage de cet appareil ou de tout autre
appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une
odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où
vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié
installeur, agence de service ou le fournisseur de gaz.
This installation manual will help you obtain a
safe, efficient, dependable installation for your
appliance and vent system.
Please read and understand these
instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace heater is
packaged with:
1 - the logs are packaged in a carton located
within the firebox.
2 - one plastic bag of glowing embers is lo-
cated in the bottom compartment.
3 - one envelope containing the literature
package which consists of the homeowner's
manual, installation instructions, log set
supplement and warranty; envelope is located in the bottom compartment.
4 - one vent restrictor to be applied as shown
page 10
on
envelope.
5 - one hood taped to the front of the standoff
bracket at the top of the unit.
6 - three-piece ceramic ember panel.
; restrictor is taped to the
INTRODUCTION
These fireplaces are designed, tested and listed
for operation and installation with, and only with,
Secure Vent™ Direct Vent System Components,
Secure Flex™ Flexible Vent Components manu-
factured by Security Chimneys International and
Z-Flex™ Model GA Venting Systems, listed to
UL1777 and ULCS635 manufactured by Flexmaster Canada Limited. These approved vent
system components are labeled for identification. DO NOT use any other manufacturer's vent
components with these appliances.
Millivolt appliances are designed to operate
on natural or propane gas. A millivolt gas
control valve with piezo ignition system provides safe, efficient operation. External electrical power is required to operate the optional
blower if installed in these units.
Electronic appliances are designed to operate
on natural or propane gas. An electronic intermittent pilot ignition system provides safe,
efficient operation. External electrical power is
required to operate these units.
These appliances comply with National Safety
Standards and are tested and listed by OmniTest Laboratories (Report No. 116-F-05-5) to
ANSI Z21.88 (in Canada, CSA-2.33), and CAN/
CGA-2.17-M91 in both USA and Canada, as
vented gas fireplace heaters.
The appliance, when installed, must be electrically grounded in accordance with local
codes or, in the absence of local codes, with
National Electrical Code, ANSI/NFPA 70
the
Canadian Electrical Code, CSA C22.1
or the
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
GENERAL INFORMATION
Note: Installation and repair should be per-
formed by a qualified service person. The appliance should be inspected annually by a qualified
professional service technician. More frequent
inspections and cleanings may be required due
to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways
of the appliance be kept clean. S'assurer que le
brùleur et le compartiment des commandes sont
propres. Voir les instructions d'installation et
d'utilisation qui accompagnent l'appareil.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front openings of the appliance.
These appliances are designed to operate on
natural or propane gas only.
TYPICAL INSTALLATION
,
.
Both millivolt and electronic versions of
these appliances are listed by Omni-Test
Laboratories for installation in bedrooms
and mobile homes.
The Installation must conform to local codes
or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA
, or the
54
tion Code, CSA B149.1
2
Natural Gas and Propane Installa-
.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 1
Millivolt Models -
Millivolt models come standard with the manually-modulated gas valve; flame appearance and
heat output can be controlled at the gas valve.
Input of millivolt models is shown in the following table:
htiwsledoMtlovilliM
evlaVsaGdetaludoM-yllaunaM
.oNledoM
tupnI
etar
)H/UTB(
007,02
ot
000,72
002,42
ot
000,03
005,62
ot
000,33
DEV 0353
DEV 5304
DEV 0454
saGlarutaNsaGenaporP
.oNledoM
tupnI
etar
)H/UTB(
000,12
ot
DEV 0353
000,72
005,32
ot
DEV 5304
000,03
000,62
ot
DEV 0454
000,33
Electronic Models -
Electronic models have a fixed rate gas valve.
Input of electronic models is shown in the
following table:
evlaVsaGetaR-dexiFhtiwsledoMcinortcelE
saGenaporPdnalarutaN
.oNledoM)H/UTB(etartupnI
E53VD03000,72
5304VDE000,03
0454VDE000,33
All Models -
Maximum manifold pressure is 3.5 in. w.c.
(0.87 kPa) for natural gas and 10 in. w.c.
(2.49 kPa) for LP/Propane gas.
Installations at Altitudes of 0 to 4500 ft.Units are tested and approved for elevations
of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.For elevations above 4500 feet (1372
meters), install the unit according to the
regulations of the local authorities having
jurisdiction and, in the USA, the latest edition
of the National Fuel Gas Code (ANSI Z223.1)
or, in Canada, the latest edition of the
CAN1-B149.1 and .2 codes.
Table 1
shows the units' gas orifice size for
the elevations indicated.
ledoM
.oN
0353VDE04#35#
5304VDE63#25#
0454VDE33#15#
ezisecifirO
.taN.porP
noitavelE
teeF
)sretem(
0054-0
)2731-0(
The millivolt appliances are manually controlled
and feature a spark ignitor (piezo) that allows the
appliance's pilot gas to be lit without the use of
matches or batteries. This system provides
continued service in the event of a power outage.
Do not use these appliances if any part has been
under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control
system and any gas control which have been
under water.
Ne pas se servir de cet appareil s'il a été plongé
dans l'eau, complètement ou en partie. Appeler
un technicien qualifié pour inspecter l'appareil et
remplacer toute partie du système de contrôle et
toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home,
where not prohibited by local codes. This
appliance is only for use with the type of
gas indicated on the rating plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
Cet appareil peut être installé dans un
maison préfabriquée (É.-U. seulement)
ou mobile déjà installée à demeure si
les réglements locaux le permettent.
Cet appareil doit être utilisé uniquement
avec les types de gaz indiqués sur la
plaque signalétique. Ne pas l'utiliser
avec d'autres gaz sauf si un kit de conversion certifié est installé.
Test gage connections are provided on the
front of the millivolt gas control valve (identified IN for the inlet and OUT for the manifold
side). A 1/8" NPT test gage connection is
provided at the inlet and outlet side of
the electronic gas control valve.
Minimum inlet gas pressure to these appliances is 5.0 inches water column (1.24 kPa)
for natural gas and 11 inches water column
(2.74 kPa) for propane for the purpose of input
adjustment.
Maximum inlet gas supply pressure to these
appliances is 10.5 inches water column (2.61
kPa) for natural gas and 13.0 inches water
column (3.23 kPa) for propane.
These appliances must be isolated from the
gas supply piping system (by closing their
individual manual shut-off valve) during any
pressure testing of the gas supply piping
system at test pressures equal to or less than
1/2 psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas
supply piping system during any pressure
testing of that system at pressures in excess of
1/2 psig (3.5 kPa).
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
These heater rated appliances are intended
for use as supplemental heaters only.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
the flu with headaches, dizziness and/or
nausea. If you have these signs, obtain fresh
air immediately. Turn off the gas supply to
the appliance and have it serviced by a
qualified professional, as it may not be operating correctly.
WARNING: FAILURE TO COMPLY WITH
THE INSTALLATION AND OPERATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OPERATING APPLIANCE, VOIDING ITS WARRANTY.
ANY CHANGE TO THIS APPLIANCE AND/
OR ITS OPERATING CONTROLS IS DANGEROUS. IMPROPER INSTALLATION
OR USE OF THIS APPLIANCE CAN CAUSE
SERIOUS INJURY OR DEATH FROM FIRE,
BURNS, EXPLOSION OR CARBON MONOXIDE POISONING.
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES. USE
CAUTION AROUND THE APPLIANCE TO
AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN
THE SAME ROOM AS THE APPLIANCE.
WARNING: DO NOT PLACE CLOTHING
OR OTHER FLAMMABLE MATERIALS
ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDES À VAPEUR INFLAMMABLES À
COTE DE L'APPAREIL.
Table 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
REAR VENT
APPLICATION
TOP VENT
APPLICATION
APPLICATION
TOP VENT
INSTALLATION
RECESSED
REAR VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
TOP VENT
APPLICATION
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to the
exterior and access to the fuel supply are also
important. Due to high temperatures the ap-
pliance should be located out of traffic and
away from furniture and draperies. Consid-
eration should be given to traffic ways, furniture, draperies, etc., due to elevated surface
temperatures (
also be free of electrical, plumbing or other
heating/air conditioning ducting.
Figure 2
). The location should
VERTICAL VENT
(Rear Vent
Application)
Typical Locations
HORIZONTAL VENT
(Rear Vent Application
without a chase)
.oNledoM
0353VDE
5304VDE
2/135)9531(4/155)3041(44/10)2201(44/10)2201(
0454VDE
Do not insulate the
space between the
appliance and the
area above it.
HORIZONTAL VENT
(Rear Vent Application
With a chase)
These direct vent appliances are uniquely suited
for installations requiring a utility shelf positioned directly above the fireplace. Utility shelves
like these are commonly used for locating television sets and decorative plants.
To provide for the lowest possible shelf surface
use the alternate rear vent outlet with attached
venting routed in a way to minimize obstructions to the use of the space above the appliance. Do not insulate the space between the
appliance and the area above it. See
Figure 3
The minimum height from the base of the
appliance to the underside of combustible materials used to construct a utility shelf in this
fashion is shown in the table in
Figure 3
.
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a
metal or wood barrier covering the entire bottom surface must be used.
.
Figure 3
Shelf Height
see table)
(
Shelf Above Fireplace With Rear Venting
KCAB
SEDIS
)mm31(.ni2/1
srecaps)mm0(.ni0
**)mm31(.ni2/1
srecaps)mm0(.ni0
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
fomottoBmorF
gnilieCottinU
)mm6261(.ni46
TNEV*)mm4.52(.ni1
SECNARAELCECIVRES
TNORF)sretem9.0(.teeF3
Shelf Height
see table)
(
Shelf Above Fireplace With Top Venting
*Note: 3 in. (75 mm) above any horizontal/
inclined vent component.
**Note: See page 6, step 1 for clearance
requirements to the nailing flange located at
each side of the unit and any screw heads
adjacent to it.
Table 2
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
APPLIANCE AND VENT CLEARANCES
The appliance is approved with zero clearance
to combustible materials on all sides (as detailed in
Table 2
), with the following exception: When the unit is installed with one side
flush with a wall, the wall on the other side of
the unit must not extend beyond the front edge
of the unit. In addition, when the unit is recessed, the side walls surrounding the unit
must not extend beyond the front edge of the
unit. See
Figure 2
.
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and B149.2 in Canada.
Vertical Vent Termination Clearances
Terminate single vent caps relative to building
components according to
multiple vent terminations according to the
installation codes listed on this page.
Figure 4
. Terminate
TERMINATION HEIGHTS FOR VENTS ABOVE
Horizontal Overhang
2 FT MIN.
Termination
Storm Collar
Flashing
Concentric
Vent Pipe
FLAT OR SLOPED ROOFS
Vent
2 FT
MIN.
Lowest
Discharge
Opening
H*
1 inch (25.4 mm) Minimum
Clearance to Combustibles
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
The horizontal vent termination must have a
minimum of 3" (76 mm) clearance to any
overhead combustible projection of 2-1/2" (64
mm) or less. See
exceeding 2-1/2" (64 mm), see
horizontal terminations may be located as
close as 6" (152mm) to any (non-combustible
and combustible) exterior sidewall. This distance may be decreased to 2" (51mm) for noncombustible exterior sidewalls only, if the
SV4.5HT-2 termination is used. For additional
vent location restrictions refer to
page 7
.
H
)teef(
Figure 5.
For projections
Figure 5
. All
Figure 8 on
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows,
however, each installation is unique resulting in
variations to those described.
See the page numbers references in the following steps for detailed procedures.
Step 1. (page 6) Construct the appliance framing. Position the appliance within the framing
and secure with nailing brackets.
Step 2. (page 6) Route gas supply line to
appliance location.
Step 3. (page 10) Install the vent system and
exterior termination.
Step 4. (page 22) Field Wiring
a. Millivolt Appliances – The operating control
The appliance is shipped with all gas controls
and components installed and pre-wired. Remove the shipping carton, exposing the front
glass door. Remove the top panel. Remove the
cardboard from underneath the pressure relief plates. Press in simultaneously the left and
right side of the bottom hinged panel, to release
it. Lower the bottom hinged panel. Open the
two latches (located under the firebox floor)
securing the glass door. Remove the door by
tilting it outward at the bottom and lifting it up.
Set the door aside protecting it from inadvertent damage.
See Figure 52on page 25.
Horizontal Vent Termination Clearances
Combustible Projection
2-1/2 inches or less in length
greater than inches in length
Ventilated
(457 mm)
Figure 5 -
Combustible Projection
2-1/2
Soffit
Unventilated
18"
Soffit
3"
(76 mm)
12"
(305 mm)
Termination Kit
Side Elevation View
Step 1. FRAMING
Frame these appliances as illustrated in
on page 8,
in a corner
See
unless the appliance is to be installed
.
Figure 10 on page 8
for corner framing
installations. All framing details must allow for
a minimum clearance to combustible framing
members as shown in
Table 2 on page 4
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed.
Headers may be in direct contact with the
appliance top spacers but must not be supported by them or notched to fit around them.
All construction above the appliance must be
self supporting, DO NOT use the appliance for
structural support.
The fireplace should be secured to the side
framing members using the unit's nailing flanges
- one top and bottom on each side of the
fireplace front. See
Figure 6.
their equivalent.
Figure 9
.
Use 8d nails or
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line along the inside
of the right side framing as shown in
Gas lines must be routed, constructed and
made of materials that are in strict accordance
with local codes and regulations.
All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff
valve. (See step 6 on page 23).
Figure 7
All horizontal terminations
may be located as close
as 6” (152mm) to any
(non-combustible and
combustible) exterior
sidewall. This distance
may be decreased to
2” (51mm) for noncombustible exterior
sidewalls only, if the
SV4.5HT-2 termination
Side
Framing
Left Side Front Corner of Fireplace Shown
(Right Side Requirements the Same)
Unit Being Secured By Its Nailing Flanges
Note: The nailing flanges, combustible members
and screw heads located in areas directly adjacent
to the nailing flanges, are EXEMPT from the 1/2”
clearance to combustible requirements for the
firebox outer wrapper. Combustible framing may be
in
direct contact with the nailing flanges and may
be located closer than 1/2” from screw heads and
the firebox wrapper in areas adjacent to the nailing
flanges. Frame the opening to the exact dimensions
specified in the framing details of this manual.
TOP CONCENTRIC VENT
FLUE OUTLET - 4¹⁄₂ (114),
COMBUSTION AIR - 7¹⁄₂ (190)
10⁷⁄₈
(275)
NOTE -
3 (76)
B
Hood shown as positioned
in louvered front model.
GAS INLET
(Either Side
and bottom)
3 (76)
10¹⁄₈
(257)
20⁷⁄₈
(531)
¹⁄₂
(13)
2¹⁄₄
(57)
ELECTRICAL
INLET
F
Front View
Unit is shipped with vent seal cap and flue cover plater installed on both flue outlets.
Unit Dimensions
ledoM
.oN
ABC DEFGH
.ni8/1048/173422/1928/1532/1722/1124/301
0353VDE
mm9101349906947298896645372
.ni8/1048/173422/1438/1042/17222/164/331
5304VDE
mm91013499066789101896576733
.ni8/1048/173422/1938/1542/1722/1134/351
0454VDE
mm641134990630016411896208104
Figure 11
Step 3. INSTALL THE VENT SYSTEM
General Information
7
(
179)
Right Side View
These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these
instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and -B149.2 in Canada.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
9
These fireplaces are designed, tested
and listed for operation and installation
with, and only with, Secure Vent™ Direct
Vent System Components, Secure Flex™
Flexible Vent Components manufactured
by Security Chimneys International and
Z-FLEX™ Model GA Venting Systems listed
to UL1777 and ULCS635 manufactured by
Flexmaster Canada Limited. These approved vent system components are labeled for identification.
DO NOT use
any other manufacturer's vent components with these appliances.
Massachusetts And New York City, NY
Requirements
These appliances are approved for installation
in the following USA locations listed in the
following:
Massachusetts:
Installation of these fireplaces are approved
for installation in the US state of Massachusetts if the following additional requirements
are met-
• Installation and repair must be done by a
plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not
exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a Thandle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
• A hard wired carbon monoxide detector with
an alarm and battery back-up must be installed
on the floor level where the gas fireplace is
installed. The carbon monoxide detector must
comply with NFPA 720, be ANSI/UL 2034
listed and be ISA certified.
• A metal or plastic identification plate must be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade and be directly in line with the
horizontal termination. The sign must read, in
print size no less than one-half (1/2) inch in
size, GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS.
New York City, NY:
Installation of these fireplaces are approved
for installation in New Your City in the US state
of New York.
10
These fireplaces must be vented directly
to the outside.
The vent system may not service multiple
appliances, and must never be connected to a
flue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclosing wall (such as a chase). There is no requirement for inspection openings in the enclosing
wall at any of the joints in the vent pipe.
Preparing the Appliance Vent Collar
Each of the unit's two vent collars are sealed
with a cover plate and a seal cap. The cover
plate and seal cap must be removed from the
cent collar being used. Refer to
top vent usage and
Figure 13
Figure 12
for
for rear, and the
following steps to prepare the appropriate
collar for use.
From the vent collar being used, remove the
screw securing the vent seal cap. Twist the
cap counterclockwise to disengage it from the
vent collar. Remove and discard the seal cap.
When the top vent is being used, remove the
lintel cover plate by pushing it back towards
the rear of the fireplace by its front flange. It
can then be removed by pulling it forward.
Loosen the two screws in the keyhole slots of
the vent cover plate and remove the remaining
two vent cover plate securing screws. Remove and discard the vent cover plate. Reinstall and securely tighten all four cover plate
screws. Reinstall the lintel cover plate.
TOP VENT SEAL CAP & COVER PLATE
REMOVAL WHEN USING THE TOP VENT
(OUTSIDE UNIT)
SECURING SCREWS
CABINET TOP
FIREBOX TOP
VENT COVER PLATE
SECURING SCREW
LINTEL
COVER PLATE
TOP VENT
VENT
COVER PLATE
PUSH TO BEGIN REMOVAL
PROCESS OF LINTEL COVER PLATE
(INSIDE UNIT)
CROSS SECTION
VENT SEAL CAP
LINTEL
Figure 12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
When the rear vent is being used, from inside
the firebox, remove the two screws securing the
baffle to the rear wall of the firebox, then remove
the baffle. Loosen the two screws in the keyhole
slots of the cover plate and remove the remaining two cover plate securing screws. Remove
and discard the cover plate. Reinstall and securely tighten all four cover plate screws. Resecure the baffle to the rear wall of the firebox.
WARNING: FAILURE TO REINSTALL AND
SECURELY TIGHTEN COVER PLATE
SCREWS COULD RESULT IN LEAKAGE OF
FLUE PRODUCTS INTO THE LIVING SPACE.
VENT COVER PLATE AND VENT SEAL CAP
MUST REMAIN SECURELY INSTALLED ON
UNUSED VENT COLLAR. FAILURE TO DO
SO COULD RESULT IN LEAKAGE OF FLUE
PRODUCTS INTO LIVING SPACE.
REAR VENT SEAL CAP & COVER PLATE REMOVAL
BAFFLE
(INSIDE UNIT)
WHEN USING THE REAR VENT
COVER PLATE
SECURING SCREWS
BAFFLE
SECURING
SCREWS
REAR VENT
CABINET BACK
CROSS SECTION
SECURING SCREWS
VENT SEAL CAP
(OUTSIDE UNIT)
Figure 13
VENT RESTRICTOR INSTALLATION
Vent restrictor may be needed when vertically
terminating the vent system above the roof (when
using the appliance top vent), install a vent
restrictor in the top vent of the fireplace outlet.
If needed, install the restrictor as shown, either
from inside or outside the unit, in the inner
RESTRICTOR
fireplace collar.
APPLIANCE TOP
VENT OUTLET
Figure 14
Preparing the Appliance Top Vent Outlet when
vertically terminating the vent system above
the roof
Install a vent restrictor (provided) in the appliance top flue outlet as shown in
Figure 14
. It
is held in place by friction, only.
Select Venting System - Horizontal or Vertical
With the appliance secured in framing, determine vent routing and identify the exterior
termination location. The following sections
describe vertical (roof) and horizontal (exterior
wall) vent applications. Refer to the section
relating to your installation. A list of approved
venting components is shown in the tables on
pages 26 and 27.
VERTICAL TERMINATION SYSTEMS (ROOF)
Figures 15, and 25 through 29 on pages 14
and 15
and their associated Vertical
Vent Tables illustrate the various vertical venting configurations that are possible for use with
these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex
pipe may also be used. A Vertical Vent Table
summarizes each system’s minimum and maximum vertical and horizontal length values that
can be used to design and install the vent
components in a variety of applications.
SV4.5CGV-1
Termination
40' Max
(12.2 M)
SV4.5FA OR
SV4.5FB Flashing
AND SV4.5SC
STORM COLLAR
1" (25.4 mm)
Minimum
Clearance to
Combustibles
*SV4.5VF
Firestop/Spacer
SV4.5L6/12/24/36/48
Vent Sections
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
Figure 15
lanimoN
htgneLnoitceS
621426384
)sehcni(
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
sehcnitf
5.4573.0100001
957.0200002
5.01578.0010001
5152.1110002
5.91526.1210003
1257.1020002
5.22578.1001001
5.52521.2120003
5.13526.2030003
5.43578.2000101
5.73521.3111003
5.34526.3021003
5457.3002002
5.64578.3000011
5.94521.4102003
1552.4100012
5.55526.4012003
7557.4001102
6652.5022004
5.76526.5003003
9657.5000202
27 6103004
5.37521.6100203
5.97526.6010203
1857.6000112
095.7021014
5.19526.7002013
3957.7000022
69 8101204
5.79521.8100023
2015.8200024
5.301526.8000303
801 9100304
4115.9020024
71157.9105006
5.811578.9110305
6215.01001304
5.031578.01101305
53152.11006006
8315.11000404
5.931526.11000033
5.241578.11100405
Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is specified in ANSI Z223.1-(latest edition) (In Canada,
the current CAN-1 B149 installation code) by
major building codes. Always consult your
local codes for specific requirements. A general guide to follow is the Gas Vent Rule (refer
to
TRAHCHTGNELNOITCESTNEV
Figure 4
on page 5).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
T
O
T
A
L
Q
T
Y
44121100034
0515.21010034
5.451578.21110035
5.061573.31020035
5.271573.41000505
77157.41100506
38152.51010506
6815.51000044
5.091578.51100045
5.691573.61010045
5.502521.71011507
70252.71000606
5.112526.71100607
5.712521.81010607
5.922521.91001607
5.232573.91000055
73257.91100056
5.142521.02000707
6425.02100708
25212010708
46222001708
67232000808
97252.32000066
5.082573.32100809
5.382526.32100067
5.982521.42010067
5.103521.52001067
5.013578.52000909
5135.621009001
5.523521.72000077
0335.72100078
63382010078
54357.8200001001
5.943521.9210001011
27313000088
5.673573.13100089
5.973526.1300011011
5.814578.43000099
32452.531000901
56457.8300000101
sehcnitf
noitceSlanimoN
621426384
)sehcni(htgneL
noitceSteN
2/1-42/1-012/1-222/1-432/1-64
)sehcni(htgneL
tneVfothgieHsnoitceStneVforebmuN
Vertical (Straight) Installation
Determine the number of straight vent sections required. 4-1/2" (114 mm), 10-1/2" (267
mm), 22-1/2" (572 mm), 34-1/2" (876 mm)
and 46-1/2" (1181 mm) net section lengths are
available. Plan the vent lengths so that a joint
does not occur at the intersection of ceiling or
roof joists. Refer to the Vent Section Length
Chart.
TRAHCHTGNELNOITCESTNEV
T
O
T
A
L
Q
T
Y
11
Vertical (Offset) Installation
Analyze the vent routing and determine the
quantities of vent sections and number of elbows required. Refer to Vertical Vent Figuresand Tables on page 14 and 15 to select the type
of vertical installation desired. Vent sections
are available in net lengths of 4 ¹⁄₂" (114 mm),
10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2"
(876 mm) and 46-1/2" (1181 mm). Refer to the
Vent Section Length Chart on page 11 for an
aid in selecting length combinations. Elbows
are available in 90° and 45° configurations.
Refer to
Figure 20
for the SV4.5E45 and
SV4.5E90 elbow dimensional specifications.
Where required, a telescopic vent section(SV4.5LA) may be used to provide the installer
with an option in installing in tight and confined
spaces or where the vent run made up of fixed
length pieces develops a joint in a undesirable
location, or will not build up to the required
length. The SV4.5LA Telescopic Vent Section
has an effective length of from 1-1/2" (38 mm)
to 7-1/2" (191 mm). The SV4.5LA is fitted with
a locking inclined channel end (identical to a
normal vent section component) and a plain
end with 3 pilot holes. Slip the plain end over the
locking channel end of a standard SV4.5 vent
component the required distance and secure
with three screws.
Maintain a minimum 1" (25 mm) clearance to
combustible materials for all vertical elements.
Clearances for all horizontal elements are 3"
(76 mm) on top, 1" (25 mm) on sides and 1"
(25 mm) on the bottom.
A. Frame ceiling opening - Use a plumb
line from the ceiling above the appliance to
locate center of the vertical run. Cut and/or
frame an opening, 10-1/2" x 10-1/2" (267mm
x 267mm) inside dimensions, about this
center mark (
Figure 16
10-1/2” Min.
(267 mm)
).
10-1/2” Min.
(267 mm)
Figure 16
B. Attach vent components to appliance Secure Vent SV4.5 direct vent system com-
All of the appliances covered in this document are
fitted with collars having locking inclined channels. The dimpled end of the vent components fit
over the appliance collar to create the positive
twist lock connection.
First Vent
Component
Align the dimple (four places)
with the opening of the locking
incline channel on appliance
collar. Twist vent component
clockwise to engage and seal.
Dimple
Locking
Incline Channel
Appliance collar
Vent / Appliance Collar
Connection
Figure 17
Arrow
Arrow
Align the dimple (four places) of the
upper vent section with the opening of
the locking incline channel on the
lower vent section. Twist vent
component clockwise to engage and
seal until arrow and dimple align.
Dimple
Locking
Incline Channel
Connected
Vent Sections
Vent / Vent Section
Connection
Arrow
Figure 18
To attach a vent component to the appliance
collar, align the dimpled end over the collar,
adjusting the radial alignment until the four
locking dimples are aligned with the inlet of the
four inclined channels on the collar (
Figure 17
). Push the vent component against
the collar until it fully engages, then twist the
component clockwise, running the dimples
down and along the incline channels until they
seat at the end of the channels. The unitized
design of the Secure Vent components will
engage and seal both the inner and outer pipe
without the need for sealant or screws. If
desired a #6 x 1/2" screw may be used at the
joint, but it is not required as the pipe will
securely lock when twisted.
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
C. Attach vent components to each other -
Other vent sections may be added to the previously installed section in accordance with the
requirements of the vertical vent figures and
tables. To add another vent component to a
length of vent run, align the dimpled end over
the inclined channel end of the previously installed section, adjusting the radial alignment
until the four locking dimples are aligned with
the inlets of the four incline channels of the
previous section.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
refer to
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.This seating position
is indicated by the alignment of the arrow and
dimple as shown in
Figure 18.
D. Install firestop/spacer at ceiling - When
using Secure Vent, use SV4.5VF firestop/spacer
at ceiling joists; when using Secure Flex, use
SF4.5VF firestop/spacer. If there is living space
above the ceiling level, the firestop/spacer must
be installed on the bottom side of the ceiling. If
attic space is above the ceiling, the firestop/
spacer must be installed on the top side of the
joist. Route the vent sections through the framed
opening and secure the firestop/spacer with 8d
nails or other appropriate fasteners at each
corner. Remember to maintain 1" (25 mm)
clearance to combustibles, framing members,
and attic or ceiling insulation when running
vertical chimney sections. Attic insulation shield
(96K94) may be used to obtain the required
clearances indicated here. See installation
accessories table on page 27.
E. Support the vertical vent run sections -
Note - Proper venting support is very impor-
tant. The weight of the vent must not be supported by the fireplace in any degree.
Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent
outlet. One method of support is by utilizing
field provided support straps (conventional
plumber's tape). Secure the plumber's tape to
the framing members with nails or screws.
Loop the tape around the vent, securing the
ends of the tape to the framing. If desired, sheet
metal screws #6 x 1/2" length may be used to
secure the support straps to the vent pipe. See
Figure 19.
Blocking
Support Straps
(Plumber’s tape)
8 feet (2.4 m)
Maximum
1 inch
(25.4 mm)
minimum
clearance to
combustibles
Figure 19
F. Change vent direction to horizontal/in-
Storm
Collar
clined run - At transition from or to a horizon-
tal/inclined run, install the SV4.5E45 and
SV4.5E90 elbows in the same manner as the
straight vent sections. The elbows feature a
twist section to allow them to be routed about
the center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the
possiblity of unlocking any of the previously
connected vent sections. See
4-13/16"
(122 mm)
Swivel Joint
(360
°
swivel)
SV4.5E45
(45° Elbow)
Swivel Joint
(360
°
swivel)
SV4.5E90
(90
Figure 20
°
Elbow)
.
8-1/8"
(206 mm)
Figure 20
G. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps
every 5' (1.52 m) along horizontal/inclined vent
runs using conventional plumber’s tape. It is
very important that the horizontal/inclined run
be maintained in a straight (no dips) and slightly
elevated plane in a direction away from the
fireplace 1/4" per foot (20 mm per meter) of
horizontal vent. Use a carpenter’s level to measure from a constant surface and adjust the
support straps as necessary.
C
D
Framing Dimensions for Roof
PitchCD
0/1210¹⁄₂ in.10¹⁄₂ in.
(267 mm)(267 mm)
6/1210¹⁄₂ in.12 in.
(267 mm)(305 mm)
12/1210¹⁄₂ in.17 ³⁄₄ in.
(267 mm)(451 mm)
Figure 21
I. Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and position
such that the vent column rises vertically (use
carpenters level) (
rimeter to secure flashing or adjust roofing to
overlap the flashing edges at top and sides only
and trim where necessary. Seal the top and
both sides of the flashing with waterproof
caulking.
Figure 22
). Nail along pe-
Figure 23
K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections to
the height as shown in the "Vertical vent termination section" on page 5. The SV4.5CGV-1 Vertical Termination (
same fashion as any other Secure Vent section.
Align the termination over the end of the previously installed section, adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four
incline channels of the last vent section. Push the
termination down until it fully engages, then twist
the termination clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels.
Figure 24
) installs in the exact
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and
Figure 21
.
Figure 22
J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the vent/
flashing joint. See
collar screw. Slide collar down until it meets the
top of the flashing. Tighten the adjusting screw.
Apply non-combustible caulking or mastic
around the circumference of the joint to provide a water tight seal.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 23.
Loosen the storm
Figure 24
If the vent system extends more than 5' (1.5 m)
above the roof flashing, stabilizers may be
necessary. Additional screws may be used at
section joints for added stability. Guide wires
may be attached to the joint for additional
support on multiple joint configurations.
13
VERTICAL VENT FIGURES/TABLES
Note: Secure Vent (rigid vent pipe) is shown
in the figures; Secure Flex (flexible vent pipe)
may also be used.
Note: It is very important that the horizontal/
inclined run be maintained in a straight (no
dips) and recommended to be in a slightly
elevated plane, in a direction away from the
fireplace of
meter) which is ideal, though rise per foot run
ratios that are smaller are acceptable all the way
down to at or near level.
Flex) firestop/spacer must be used anytime vent
pipe passes through a combustible floor or ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure
Flex)firestop/spacer must be used anytime vent
pipe passes through a combustible wall.
Note: Two 45 degree elbows may be used in
place of one 90 degree elbow. The same rise to
run ratios, as shown in the venting figures for 90
elbows, must be followed if 45 degree elbows
are used.
Note: An elbow is acceptable as 1 foot of
vertical rise, except where an elbow is the only
vertical component in the system. (See Figure
34 on page 18 ).
*Ceiling
Firestop/Spacer
(SV4.5VF)
40 feet (12.2 meters)
Maximum
*When using
Secure Flex, use
Firestop/Spacer
SF4.5VF
Example: If 8 feet of (H) horizontal
vent run is needed, then 4 feet minimum (V) vertical vent will be required.
This table shows a 1 (V) to 2 (H) ratio.
For every 1 foot of (V) vertical, you are
allowed 2 feet of (H) horizontal run, up
to a maximum horizontal run of 8 feet.
H
*Ceiling
Firestop/Spacer
(SV4.5VF)
*When using Secure Flex,
V1
Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
use Firestop/Spacer
SF4.5VF
**Wall
(SV4.5HF)
H
Figure 26
-
Rear Vent -
ONE 90 DEGREE ELBOW
TABLE B
H Maximum
(meters)
feet
(1.524)
5
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H = 40 feet (12.2 m) Max.
H = 20 feet (6.096 meters) Max.
feet
Example: If 20 feet of (H) horizontal
vent run is needed, then 4 feet minimum of (V) vertical vent will be
required.
V
This table shows a 1 (V) to 5 (H)
ratio. For every 1 foot of (V) vertical,
you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of
vertical rise except where an elbow
is the only vertical component in the
system. See Figure 34.
V Minimum
(meters)
Elbow Only
(0.305)
1
(0.610)
2
(0.914)
3
(1.219)
4
A Vent Restrictor, as shown in Figure 14 on
Page 10, must be used in this application.
Figure 25
- Top Vent - STRAIGHT
14
Figure 27
-
Top Vent - TWO 90 DEGREE ELBOWS
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS
OF CONCENTRIC FLEXIBLE VENT PIPE BE JOINED TOGETHER.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
VERTICAL VENT FIGURES/TABLES
(continued)
TABLE C
+H
H
MaximumH MaximumV Minimum
1
2
4
6
8
(meters)
(0.610)
(1.219)
(1.829)
(2.438)
(meters)
feetfeetfeet
(1.524)
5
(3.048)
10
(4.572)
15
(6.096)
20
V + V1+ H + H1 = 40 feet (12.2 m) Max
H = 8 feet (2.438 meters) Max.
H + H1= 20 feet (6.096 meters) Max.
Example: If 20 feet of (H) horizontal vent run is needed, then
4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
V1
H1
*Ceiling
Firestop/Spacer
(SV4.5VF)
**Wall
Firestop/Spacer
(SV4.5HF)
V
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
*Ceiling
Firestop/Spacer
(SV4.5VF)
Figure 28
- Rear Vent - THREE ELBOWS
TABLE D
H
Maximum
H +
1
feetfeet
5
5
10
15
20
(meters)(meters)
(1.524)Elbow Only
(1.524)
(3.048)
(4.572)
(6.096)
V Minimum
1
2
3
4
(0.305)
(0.610)
(0.914)
(1.219)
H + H1 = 20 feet (6.096 m) Max.
+ H + H1 = 40 ft. (12.192 m) Max.
V + V
1
Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet
minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V) vertical,
you are allowed 5 feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
V
1
H
1
*When using Secure Flex,
use Firestop/Spacer
SF4.5VF
**When using Secure
Flex, use Firestop/Spacer
SF4.5HF
*Ceiling
Firestop/Spacer
(SV4.5VF)
H
H
**Wall
Firestop/Spacer
(SV4.5HF)
V
An elbow is acceptable as 1 foot of vertical rise except where an
elbow is the only vertical component in the system. See Figure 34.
Figure 29 -
Top Vent - THREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM
Figures 30, and Figures 34 to 40 on pages 18
and their associated Horizontal Vent
to 20
Table illustrate the various horizontal venting
configurations that are possible for use with
these appliances. Secure Vent pipe applications are shown in these figures; Secure Flex
pipe may also be used. A Horizontal Vent Table
summarizes each system’s minimum and maximum vertical and horizontal length values that
can be used to design and install the vent
components in a variety of applications.
Both of these horizontal vent systems terminate
through an outside wall. Building Codes limit or
prohibit terminating in specific areas. Refer to
on page 12). All of the appliances
covered in this document are fitted with collars
having locking inclined channels. The dimpled
end of the vent components fit over the appliance
collar to create the positive twist lock connection.
A.Plan the vent run -
Analyze the vent routing and determine the types
and quantities of sections required
4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572
mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net
section lengths are available. Plan the vent lengths
so that a joint does not occur at the intersection of
ceiling or roof joists. Make allowances for elbows as
indicated in
Figure 20 on page 12
.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clearances
for the horizontal runs are; 3" (76 mm) on top, 1"
(25 mm) on sides, and 1" (25 mm) at the bottom.
B. Frame exterior wall opening -
Locate the center of the vent outlet on the
exterior wall according to the dimensions shown
in
Figure 9
on page 8. Cut and/or frame an
opening, 10-1/2" x 12-1/8" (267 mm x 308mm)
inside dimensions, about this center.
C.Frame ceiling opening - If the vertical
route is to penetrate a ceiling, use plumb line
to locate the center above the appliance. Cut
and/or frame an opening, 10-1/2" x 10-1/2"
(267 mm x 267 mm) inside dimensions, about
this center (refer to
Figure 16
on page 11 ).
D. Attach vent components to appliance - To attach
a vent component to the appliance collar, align the
dimpled end over the collar, adjusting the radial
alignment until the four locking dimples are aligned
with the inlets of the four incline channels on the
collar (
refer to Figure 17
on page 12).
Push the vent component against the collar until it
fully engages, then twist the component clockwise,
running the dimples down and along the incline
channels until they seat at the end of the channels.
16
refer to
TYPICAL HORIZONTAL VENT INSTALLATION
Building
Support
Framing
SV4.5E90
Elbow
Vertical
Rise
Support
Brackets
Ceiling
Firestop/Spacer
Horizontal / Inclined Run
See Figure 19 on page 12 for
vertical vent section support.
Figure 30
The unitized design of the Secure Vent components will engage and seal both the inner and
outer pipe elements with the same procedure.
Sealant and securing screws are not required.
Note: An elbow may also be attached to the
appliance collar. Attach in the same manner as
you would a vent section.
E. Attach vent components to each other -
Other vent sections may be added to the previously installed section in accordance with the
requirements of the vent tables. To add another
vent component to a length of vent run, align the
dimpled end of the component over the inclined
channel end of the previously installed section,
adjusting the radial alignment until the four
locking dimples are aligned with the inlets of the
four incline channels of the previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.This seating position is
indicated by the alignment of the arrow and
dimple as shown in
F. Install firestop/spacer at ceiling -
When using Secure Vent, use SV4.5VF firestop/
spacer at ceiling joists; when using Secure Flex,
use SF4.5VF firestop/spacer. If there is living
space above the ceiling level, the firestop/ spacer
must be installed on the bottom side of the
ceiling. If attic space is above the ceiling, the
firestop/ spacer must be installed on the top
side of the joist. Route the vent sections
through the framed opening and secure the
firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Remember to maintain 1" (25 mm) clearance
to combustibles, framing members, and attic
or ceiling insulation when running vertical
chimney sections.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 18 on page 12.
SV4.5HT-2
Termination
SV4.5L6/12/24/36/48
Vent Sections
Support Bracket Spacing
Every 5 ft (1.52 m)
Fireplace
Exterior
Wall
SV4.5HT-2
Termination
Exterior
Wall
G. Support the vertical run sections -
On the vertical run, support the venting system every 8 feet (2.4m) above the fireplace
vent outlet with field provided support straps
(Plumber's tape). Attach the straps to the vent
pipe and secure to the framing members with
nails or screws. See
Figure 19 on page 12.
H. Change vent direction - At transition from
or to a horizontal/inclined run, install the
SV4.5E45 and SV4.5E90 elbows in the same
manner as the straight vent sections. The
elbows feature a twist section to allow them
to be routed about the center axis of their
initial collar section to align with the required
direction of the next vent run element. Twist
elbow sections in a clockwise direction only
so as to avoid the possiblity of unlocking
any of the previously connected vent sections. See
Figure 20 on page 13
I. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined
run as described in Step E. Install support
straps every 5 ft. (1.52 m) along horizontal/
inclined vent runs using conventional
plumber’s tape. See
Figure 30
important that the horizontal/inclined run be
maintained in a straight (no dips) and recommended to be in a slightly elevated plane,
in a direction away from the fireplace of ¹⁄₄"
rise per foot (20 mm per meter) which is ideal,
though rise per foot run ratios that are smaller
are acceptable all the way down to at or near
level. Use a carpenter’s level to measure from
a constant surface and adjust the support
straps as necessary.
It is important to maintain the required clearances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs
.
, it is very
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening as
described in Step B. Assemble the vent system
to point where the terminus of the last section is
within 7 in. (178 mm) to 11-1/4 in. (286 mm)
inboard of the exterior surface to which the SV4.5
HT termination is to be attached, see
Figure 32
If the terminus of the last section is not within this
distance, use the telescopic vent sectionSV4.5LA, as the last vent section. For wall thicknesses greater than that shown in
refer to
Table 3 on page 18
. This table lists the
Figure 32
additional venting components needed (in addition to the termination and adapter) for a particular range of wall thicknesses.
K.Attach termination adapter - Attach the
adapter (adapter - SV4.5RCH - provided with
the termination) to the vent section or telescoping vent section), elbow or appliance collar as shown in
Figure 31
in the same manner
as any SV4.5 vent component (refer to Step E).
L.Install Firestop/Spacer at exterior wall -
When using the square termination, install
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)
Firestop/Spacer over the opening at the exterior side of the framing, long side up, with the
3 inch spacer clearance at the top as shown in
Figure 31
, and nail into place.
(The Firestop/Spacer may also be installed over
the opening at the interior side of the framing.)
M. Install the desired termination -
1. Install the square termination (SV4.5HT-
2)- For the last step , from outside the
exterior wall, slide the collars of the termination onto the adapter (the outer over the outer
and the inner inside the inner) until the termination seats against the exterior wall surface
to which it will be attached. Orient the housing of the termination with the arrow pointed
upwards. Secure the termination to the exterior wall. The horizontal termination must
not be recessed into the exterior wall or
siding by more than the 1-1/4" (32 mm) as
shown in
Figure 32
.
SVHRK Snorkel Cap –The snorkel cap is designed to be fitted into a basement window
box. The SVHRK cap is for use with flex vent
The vertical distance between the inlet and
outlet of the cap is 28 in. (711 mm). pipe.
IMPORTANT: The vent termination is hot
while in operation and for a period of time
following use of the fireplace. To prevent
contact with hot surfaces, we recommend
the use of a Termination Guard. This can be
purchased at your local dealer.
Firestop/Spacer (SV4.5HF) shown
on the exterior side of the wall. It
may also be installed on the
interior side.
7"
5-1/8"
(130 mm)
(178)
12-1/8"
(308 mm)
.
10-1/2"
(267mm)
,
Adapter
SV4.5RCH
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Figure 31
*Use silicone caulking to
seal the top and sides of
the termination, up to the
underlayment, stucco, or
masonry wall surface.
*Caulk
*Caulk
Stucco
Installing the Square Horizontal Termination (SV4.5HT-2)
Siding
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
Interior Surface of
Finished Wall
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Last Vent Section. Use
Telescopic Vent
Section (SV4.5LA), If
Necessary
SV4.5HT-2
Square Termination
**For thicknesses greater
than 10”, see Table 4.
the Framed Opening.
Base of Appliance
Adapter
SV4.5RCH
See Figure 9 on page 8
for Min. Distance to Base
of Appliance.
(25.4 mm)
Maximum wall thickness
10 in.(254 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9-1/4 in.
(152 to 235 mm)**
Square Termination
1-1/4" Maximum Recess of
Square Termination into
Exterior Finishing Material
Venting Connection and Exterior Wall Recessing of the
Horizontal Square Termination (SV4.5HT-2).
Figure 32
Horizontal terminations have been designed to perform in a wide range of weather
conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the
termination where water from eaves and adjoining rooflines may create a heavy flow
of cascading water onto the termination cap. If the cap must be placed where the
possibility of cascading water exists, it is the responsibility of the builder to direct the
water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including
the use of silicone caulking where required.
1"
SV4.5HT-2
SV4.5HT-2
Termination
3"
(76 mm)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
HORIZONTAL VENT FIGURES/TABLES
Note: Secure Vent components (rigid vent pipe and terminal) are shown in
the figures; Secure Flex components (flexible vent pipe and terminal) may
also be used.
Note: Two 45 degree elbows may be used in place of one 90 degree elbow.
The same rise to run ratios, as shown in the venting figures for 90 elbows, must
be followed if 45 degree elbows are used.
Note: It is very important that the horizontal/inclined run be maintained
in a straight (no dips) and recommended to be in a slightly elevated
plane, in a direction away from the fireplace of
per meter) which is ideal, though rise per foot run ratios that are smaller
are acceptable all the way down to at or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be
used anytime vent pipe passes through a combustible floor or ceiling.
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used
anytime vent pipe passes through a combustible wall.
1/4" rise per foot (20 mm
TABLE F
H MaximumV Minimum
(meters)
feet
(0.914)
3
*When using Secure Flex,
use Firestop/Spacer
SF4.5HF
(meters)
feet
Elbow Only
H
*Wall
Firestop/Spacer
(SV4.5HF)
V
WARNING: UNDER NO CIRCUMSTANCES MAY SEPARATE SECTIONS OF CONCENTRIC FLEXIBLE VENT PIPE
BE JOINED TOGETHER.
horizontal vent run is needed,
then 4 feet minimum of (V)
vertical vent will be required.
This table shows a 1 (V) to 5
(H) ratio. For every 1 foot of
(V) vertical, you are allowed
5 feet of (H) horizontal run,
up to a maximum horizontal
run of 20 feet.
H
*Ceiling
Firestop/Spacer
(SV4.5VF)
V
18
Only the square termination (SV4.5HT-2) may be used.
See
Table 3
as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 33
- Rear Vent - NO ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Square termination (SV4.5HT-2) shown.
Table 3
See
as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Example: If 20 feet of (H) horizontal vent run is needed,
then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of
(V) vertical, you are allowed 5 feet of (H) horizontal run, up
to a maximum horizontal run of 20 feet.
See
Table 3 on page 18
as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Square termination (SV4.5HT-2) shown.
Figure 36
-
Rear Vent - TWO 90 DEGREE ELBOWS
*Wall Firestop/Spacer
(SV4.5HF)
H
1
*When using Secure Flex,
use Firestop/Spacer
SF4.5HF
**Note - When using
Secure Flex, use
Firestop/Spacer SF4.5VF
*Wall Firestop/Spacer
(SV4.5HF)
Firestop/Spacer
Square termination (SV4.5HT-2) shown.
Table 3 on page 18
See
as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Figure 37
-
Top Vent - TWO 90 DEGREE ELBOWS
H
**Ceiling
(SV4.5VF)
TABLE J
+ H
H
Maximum
1
(meters)
feet
(0.914)Elbow Only
3
(1.524)
5
(3.048)
10
V
(4.572)
15
(6.096)
20
V +H+ H1 = 40 feet (12.2 m) Max.
+ H1 = 20 ft. (6.096 m) Max.
H
V Minimum
(meters)
feet
1(0.305)
2(0.610)
3(0.914)
4(1.219)
Example: If 20 feet of (H) horizontal vent run
is needed, then 4 feet minimum of (V) vertical
vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed 5
feet of (H) horizontal run, up to a maximum
horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical rise
except where an elbow is the only vertical
component in the system. See Figure 34.
needed, then 4 feet minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every
1 foot of (V) vertical, you are allowed 5 feet of (H)
H
horizontal run, up to a maximum horizontal run
of 20 feet.
Square termination (SV4.5HT-2) shown.
See
Table 3 on page 18
Figure 38
- Rear Vent - THREE 90 DEGREE ELBOWS
**Wall Firestop/Spacer
(SV4.5HF)
as an aid in venting component selection for a particular range of exterior wall thicknesses.
*When using Secure Flex,
use Firestop/Spacer
H
1
V
1
**Wall Firestop/Spacer
**When using Secure
Flex, use Firestop/Spacer
(SV4.5HF)
Square termination (SV4.5HT-2) shown.
See
Table 3 on page 18
as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Figure 39
-
Top Vent - THREE 90 DEGREE ELBOWS
SF4.5VF
SF4.5HF
*Ceiling
Firestop/Spacer
(SV4.5VF)
H
TABLE L
H
Maximum
(meters)
feet
(1.524)
5
(1.524)
5
10
15
20
V
(3.048)
(4.572)
(6.096)
+ H1 = 20 feet (6.096 m) Max.
H
+ V +H+ H = 40 ft. (12.192 m) Max.
V
11
V Minimum
feet
Elbow Only
1
2
3
4
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
Example: If 20 feet of (H) horizontal vent
run is needed, then 4 feet minimum of (V)
vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For
every 1 foot of (V) vertical, you are allowed
5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only
vertical component in the system. See
Figure 34.
20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
KITS AND COMPONENTS
Secure Flex venting kits and components may
be used in any venting application where rigid
Secure Vent (SV4.5) direct vent components
can be used. All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting.
Secure Flex
kits may
not be modified; also, under no circumstances
may separate sections of flex pipe be joined
together. Secure Flex kits may be added to the
end of a vent run made up of rigid Secure Vent
(SV4.5) vent sections provided that doing so
does not violate any of the venting length,
height, routing, horizontal to vertical ratio requirements or clearance considerations detailed in this manual.
Secure Flex kits come with an included adapter
that can be fitted to the appliance collar or the
inclined channel end of the last Secure Vent
(SV4.5) vent section in a rigid system in the
exact same fashion as any other Secure Vent
section. Align the dimpled end of the adapter
over the previously installed section or appliance collar, adjusting the radial alignment until
the four locking dimples of the adapter are
aligned with the inlets of the four incline channels of the last vent section or collar. Push on
the adapter until it fully engages, then twist the
adapter clockwise running the dimples down
and along the incline channels until they seat at
the end of the channels.
Attach the flexible vent to the adapter as
follows
(see Figure 40)
:
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around the
inner flexible vent pipe, push it back out of the way.
2. Apply a bead of Mill-Pac Black (700°F)
high temperature sealant - Catalog No.
10K81) to the inner adapter collar, approxi-
mately ¹⁄₂ inch from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adapter
collar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1³⁄₄
inches from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adapter
inner collar approximately ³⁄₄ inch from the end
of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connection.
B. Install the Outer Flex Pipe -
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out of
the way.
NOTE: OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE
Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adapter (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inner and outer adapter collars.
1-3/4 in. (44 mm)
Flexible Pipe and
Adapter Outer
Collar Overlap
Adapter
(SV4.5RF)
Attach Adapter to Appliance
Collar, or Secure Vent Sections
Figure 40
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81) to
the outer adapter collar; to the grooves of the
collar which extend approximately 1 inch from
the end and to the flat surface, approximately
1³⁄₈ inches from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adapter
collar. Ensure the flexible vent pipe completely
engages the adapter collar to a distance of 1³⁄₄
inches from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adapter
outer collar approximately ³⁄₄ inch from the
end of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adapter collar just below the gear clamp to
provide additional security to the connection.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to
provide the required clearance. Do Not allow
the flexible vent to bend in a radius tighter than
5" (127 mm). Refer to
horizontal sections of flex with metal straps at
2 foot (0.61 m) intervals.
D. Install Firestop/Spacers at ceilings and
walls -
When Secure Flex penetrates a wall or ceiling,
a firestop/spacer is required: use the SF4.5 VF
firestop/spacer for ceilings and the SF4.5 HF
firestop/spacer for walls.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 41
. Support
FLEX VENT
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
GEAR
CLAMPS
1-3/4 in. (44 mm)
Flexible Pipe and
Adapter Inner
Collar Overlap
SECURING SCREW
(3 PLACES EQUIDISTANT
JUST BELOW GEAR CLAMP)
See the appropriate sections and figures
shown throughout the venting section for
their installation requirments.
Flexible Vent Section
5" (127 mm)
Radius Minimum
Figure 41
E. Attach Flex Vent to Termination Secure Flex components can be purchased
separately and attached to bulk lengths of
Secure Flex flexible tubing cut to size at the
job site. Secure the flexible vent to the Secure
Flex terminations in the same manner (see
Figure 40)
Note:
Secure Flex
substitute
Secure Vent
nents. The collars of
tions and adapters have a different circumference than that used with the
pipe. Additionally,
have an extended length center tube for use
in attaching the flexible vent.
as it was attached to the adapter.
Secure Flex
vent must be attached to
terminations only. DO NOT
Secure Vent
adapter for
terminations or the
Secure Flex
Secure Flex
Secure Flex
components
compo-
termina-
Secure Vent
21
Step 4. FIELD WIRING
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after servicing.
Refer to Section A for millivolt appliances and
Section B for electronic appliances. The gas
valve is set in place and pre-wired at the
factory on both models.
A. Millivolt Wiring
(See Figure 42 )
1. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed in
the modesty panel. Optional wall-mounted
switch, thermostat, or one of the optional
remote control kits may also be used.
2. If wall-mounted ON/OFF control or thermostat is selected mount it in a convenient location on a wall near the fireplace.
3. Wire the control switch within the millivolt
control circuit using the 15 feet of 2 conductor
wire supplied with the unit.
Note: The supplied 15 feet of 2 conductor
wire has one end of each conductor connected to the gas valve circuit and the other
end of each conductor placed loose inside
the bottom compartment.
Caution: Do Not connect the optional wall
switch to a 120V power supply.
4.If an optional control switch is installed, turn
the appliance-mounted ON/OFF burner control
switch to the OFF position.
Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced,
it must be replaced withType A WM 105°C – 18 GA. wire.
TP
TP
Thermopile
APPLIANCE-MOUNTED ON/OFF SWITCH
*OR OPTIONAL WALL-MOUNTED ON/OFF SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE CONTROL RECEIVER
*Turn the appliance-mounted ON/OFF burner
control switch to the OFF position if an
optional control switch is installed.
Schematic Representation Only
TH
Figure 42
B. Electronic Wiring
either Figures 43 or 44 )
(See
Note: The electronic appliance must be con-
nected to the main power supply.
22
–
TH
Field Wired
Factory Wired
–
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Remove the electrical inlet cover plate from
the side of the unit by removing the plate's
securing screws.
See Figure 11 on page 9.
3. Remove the cover plate's knockout and then
feed the power supply wire through the knockout opening and into the unit junction box.
4. Connect the black power supply wire to the
lower outlet's red pigtail lead and the white
power supply wire to the common terminal of
the outlet as shown in
Figures 43 or 44.
5. Connect the ground supply wire to the pigtail
lead attached to outlet's green ground screw.
6. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed in
the modesty panel. Optional wall-mounted
switch, thermostat, or one of the optional
remote control kits may also be used.
7. If wall-mounted ON/OFF control or thermostat is to be used, mount it in a convenient
location on a wall near the fireplace.
8. If an optional control is to be used, wire it
in the the low voltage circuit as shown in
Figures 43 or 44.
Note: The supplied 15 feet of 2 conductor wire has
one end of each conductor connected to the gas
valve circuit and the other end of each conductor
placed loose inside the bottom compartment.
9. If an optional control switch is installed,
turn the appliance-mounted ON/OFF burner
control switch to the OFF position.
10. After the wiring is complete, replace the
cover plate.
Note: The gas valve-mounted ON/OFF switch
is shown in Figure 43. It is integral with the gas
valve and should be set to the ON position.
IMPORTANT: Ground supply lead must be
connected to the wire attached to the green
ground screw located on the outlet box. See
Figure 43 and 44
. Failure to do so will result
in a potential safety hazard. The appliance
must be electrically grounded in accordance
with local codes or, in the absence of local
codes, the National Electrical Code, ANSI/
NFPA 70-(latest edition). (In Canada, the
current CSA C22-1 Canadian Electrical Code.)
Note: The tab connecting the receptacles of
the outlet box must be broken in FBK-100 and
FBK-200 blower kit applications.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-100 and FBK-200 Kits
1. If any of the original wire as supplied must be replaced,
1. it must be replaced withType AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
**ON/OFF Switch (Integral
with Gas Valve)
Gas Valve
BK
R
BL
BLOWER
W
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH
*Blower speed control switch is provided in FBK200 blower kit.
**Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
PILOT
ASSEMBLY
IGNITER
Green
White
Neutral
Side of
Receptacle
W
Black
Ta b
Broken
Red
Hot
Side of
Receptacle
B
G
Transf.
120 V.
24 V
R
OPT
Tab Intact
Green
Ground
Screw
BL
OR OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
Factory WiredField Wired
Schematic Representation Only
Junction Box
Optional
Accessory
Switch
BK
G
r
-
lartueN
120 VAC - Black
Figure 43
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-250 Kits
1. If any of the original wire as supplied must be replaced,
1. it must be replaced withType AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
*ON/OFF Switch (Integral
with Gas Valve)
Gas Valve
BK
R
BL
OPT
BLOWER
WH
OPTIONAL APPLIANCE-MOUNTED ON/OFF SWITCH
OR OPTIONAL WALL SWITCH OR OPTIONAL THERMOSTAT
*Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
PILOT
ASSEMBLY
IGNITER
Optional
FBK-250
Module
W
OR OPTIONAL REMOTE RECEIVER
Factory WiredField Wired
Schematic Representation Only
Tab Intact
Green
Ground
Screw
Green
White
Black
Red
Hot
Neutral
Side of
Side of
Receptacle
Receptacle
B
G
BL
Ta b
Broken
G
r
120 VAC - Black
Junction Box
Transf.
120 V.
24 V
R
BK
-
lartueN
Optional
Accessory
Switch
Figure 44
neerG-dnuo
e
tihW
neerG-dnuo
e
tihW
WARNING: ELECTRONIC MODELS OF
THESE APPLIANCES ARE EQUIPPED
WITH A THREE-PRONG (GROUNDING)
PLUG UTILIZED IN CONNECTING THE
ELECTRONIC COMPONENTS TO THE
JUNCTION BOX IN THE LOWER COMPARTMENT. THIS GROUNDING PLUG
PROVIDES PROTECTION AGAINST
SHOCK HAZARD AND SHOULD BE
PLUGGED DIRECTLY INTO THE PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE
THE GROUNDING PRONG FROM THE
PLUG.
Step 5.WIRING - OPTIONAL FORCED AIR
BLOWER KIT
FBK-100 and FBK-200 Kits
(See Figure 43 on page 22)
An electrical outlet box is provided for the installation of the FBK-100, FBK-200 forced air blower
kits. Electrical power must be provided to this
box to operate these blowers. Install the blower
kits according to the installation instructions
provided with the kits.
FBK-250 Blower Kit
(See Figure 44 on page 22)-
An electrical outlet box is provided for the installation of the FBK-250 forced air blower kit.
Electrical power must be provided to this box to
operate these blowers. Install the blower kit
according to the installation instructions provided with the kit.
-
Step 6. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-off valve mounted in the supply line.
illustrates two methods for connecting
ure 45
the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation
must be in compliance with local codes.
These appliances are equipped with a gas flex
line for use (where permitted) in connecting the
unit to the gas line. A gas flex line is provided
to aid in attaching the direct vent appliance to
the gas supply. The gas flex line can only be
used where local codes permit. See
for flex line description. The flex line is rated for
both natural and propane gas. A manual shut
off valve is also provided with the flex line.
The gas control valve is located in the lower
control compartment.
To access the valve open the lower control
compartment door (
see Figure 46
ing in the right top corner of the door. (The
door is hinged at the bottom.) Remove the
bottom compartment door by sliding the hinge
pin, located at the door’s left side, to the right
until it disengages from the left corner post
hole. Pull the door diagonally to the left, away
from the fireplace.
Remove the modesty panel. To remove the
modesty panel, slide the panel forward until it
contacts the cabinet bottom panel, then lift
straight up and tilt forward.
Remove the modesty panel carefully, so
that none of the wires become loose or
disconnected.
Fig-
Figure 45
) by push-
Gas
Valve
Hinge Pin
ON/OFF
Switch
Piezo Ignitor
Control
Compartment
Access Panel
Modesty Panel
Figure 46
The millivolt control valve has a 3/8"
(10 mm) NPT thread inlet port. The electronic
control valve has a 1/2" (13 mm) NPT thread inlet
port and is fitted with a 1/2" x 3/8" (13 mm x
10 mm) NPT fitting.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane resistant compounds are used in propane applications).
Turn on gas supply and test for gas leaks,
using a gas leak test solution (also referred to
as bubble leak solution).
Note: Using a soapy water solution (50% dish
soap, 50% water) is an effective leak test
solution but it is not recommended, because
the soap residue that is left on the pipes/
fittings can result in corrosion over time. Never
use an open flame to check for leaks.
Figure 45 -
Gas
Valve
3/8" Nipple
3/8" Union
3/8" Close Nipple
GAS CONNECTION
Optional Gas Flex Line Connector
3/8" NPT x 3/8"
Flare Fitting
3/8" Flex Tubing
1/2" x 3/8"
Reducer
3/8" Shut-Off Valve
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
1/2" x 3/8" Flare
Shut-Off Valve
Gas
Stub
A. Light the appliance (refer to the lighting
instructions label in the control compartment
or in the Homeowner's Care and Operation
Instructions).
B. Brush all joints and connections with the
gas leak test solution to check for leaks. If
bubbles are formed, or gas odor is detected,
turn the gas control knob to the “OFF” position. Either tighten or refasten the leaking
connection and retest as described above.
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution.
D. When the gas lines are tested and leak free,
observe the individual tongues of flame on the
burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.
23
Step 7. INSTALLING CERAMIC EMBER
PANEL, LOGS AND GLOWING EMBERS
The logs are packaged in a carton located
within the firebox. One plastic bag of glowing embers is located in the bottom compartment. Refer to the Log Set PlacementSupplement for detailed placement instructions for the ceramic ember panel, logs and
glowing embers.
Step 8. CHECKING APPLIANCE OPERATION
With gas line installed run initial system checkout before closing up the front of the unit.
Follow the pilot lighting instructions provided
in the Homeowner's Care and Operation Instructions. For piezo ignitor location see
ure 46 on page 23
(millivolt appliances only).
Note: Lighting Instructions are also found on
the literature tag tied to the gas piping next to
the gas valve. To access the tag, open the
lower control compartment door (Figure 46 onpage 23 ) by pushing in simultaneously the left
and right top corners of the door. (The door is
hinged at the bottom.) Remove the bottom
compartment door by sliding the hinge pin,
located at the door’s left side, to the right until
it disengages from the left corner post hole.
Remove the modesty panel. To remove the
modesty panel, slide the panel forward until it
contacts the cabinet bottom panel, then lift
straight up and tilt forward. Remove the
modesty panel carefully, so that none of the
wires become loose or disconnected.
When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lighting
of the appliance will not require such purging. Inspect the pilot flame (remove logs, if
necessary, handling carefully).
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or
floating. Flame should be blue in color with
traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" min (tip) of the
quick drop out thermocouple should be engulfed in the pilot flame.
Fig-
The flame should project 1" (25 mm) beyond
the hood at all three ports
(Figure 47).
Re-
place logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall
switch and rotate the gas valve control knob
counterclockwise to the “ON” position (“ON”
will be at the bottom side of the valve).
MILLIVOLT
Thermocouple
Pilot
Nozzels
Hood
Thermopile
Ignitor Rod
³⁄₈" Min
(9 mm)
Figure 47
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the optional
remote wall switch and turn the gas control
switch to the “ON” position. Ensure the ignitor
lights the pilot. The pilot flame should engulf
the flame rod as shown in
ELECTRONIC
Proper Flame
Adjustment
Pilot
Nozzle
Figure 48
(9 mm to 13 mm)
.
3/8 To 1/2 Inch
Ground
Electrode
Flame Rod
Hot Surface
Igniter
Figure 48
Step 9. INSTALLING THE GLASS DOOR
To access the glass door securing latches,
first open the lower control compartment
door (
Figure 49
the left and right top corners of the door. (The
door is hinged at the bottom.) Remove the
bottom compartment door by sliding the hinge
pin, located at the door’s left side, to the right
until it disengages from the left corner post
hole. Pull the door diagonally to the left, away
from the fireplace.
) by pushing in simultaneously
Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket
surface must be clean, free of irregularities and
seated firmly.
Position the door in front of the firebox opening
with the bottom of the door held away from the
fireplace
(Figure 49 )
. Hook the top flange of
the door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently
in towards the fireplace ensuring that the gasket seats evenly as the door frame draws shut.
Fasten the two latches located underneath the
firebox floor to the door's vee-flange. Close
both the latches securely.
Lower Compartment Door and Hinge
Top Flange
Glass Door Frame
Glass Door
Modesty
Panel
Bottom Vee-flange
Glass Door Frame
Glass Door Latch
Figure 49
-
Firebox Floor
INSTALLING THE GLASS DOOR
WARNING: HANDLE THIS GLASS WITH
EXTREME CARE! THE GLASS PANEL IS
SUSCEPTIBLE TO DAMAGE — DO NOT
SCRATCH WHILE HANDLING OR WHILE
RE-INSTALLING THE GLASS DOOR
FRAME.
WARNING: DO NOT OPERATE APPLIANCE WITH THE GLASS FRONT REMOVED, CRACKED OR BROKEN. REPLACEMENT OF THE GLASS SHOULD
BE DONE BY A LICENSED OR QUALIFIED
SERVICE TECHNICIAN.
24
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 10. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a matter of taste.
Generally, most people prefer the warm glow of
a yellow to orange flame. Appliances operated
with air shutter openings that are too large will
exhibit flames that are blue and transparent.
These weak, blue and transparent flames are
termed anemic. If the air shutter opening is too
small sooting may develop.
Sooting is indicated by black puffs developing
at the tips of very long orange flames. Sooting
results in black deposits forming on the logs,
appliance inside surfaces and on exterior surfaces adjacent to the vent termination. Sooting
is caused by incomplete combustion in the
flames and lack of combustion air entering the
air shutter opening. To achieve a warm yellow
to orange flame with an orange body that does
not soot, the shutter opening must be adjusted
between these two extremes.
No smoke or soot should be present. Reposition the logs if flames impinge on any of them.
If the logs are properly positioned and sooting
conditions exist, the air shutter opening on the
main burner tube should be adjusted. Normally,
the more offsets in the vent system, the greater
the need for the air shutter to be opened further.
Burner Adjustment
WARNING: AIR SHUTTER ADJUSTMENT SHOULD ONLY BE PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN.
IMPORTANT: ENSURE THAT THE FRONT
GLASS PANEL IS IN PLACE AND SEALED
DURING ADJUSTMENT.
CAUTION: THE AIR SHUTTER DOOR
AND NEARBY APPLIANCE SURFACES
ARE HOT. EXERCISE CAUTION TO
AVOID INJURY WHILE ADJUSTING
FLAME APPEARANCE.
To adjust the flame, rotate the adjustment rod
toward the back or toward the front of the fireplace (rod located in the lower control area).
Position the air shutter to the factory setting as
shown in the table in
Figure 50
to operate for at least 15 minutes.
. Allow the burner
Observe the flame continuously. If it appears
weak or sooty as previously described, adjust the
air shutter by pushing or pulling on the adjustment rod until the flame appearance is as desired. The adjustment rod and associated adjustable air shutter is patented technology.
Flame adjustments can be made quickly and
accurately to taste without the need of disassembling the appliance and waiting for 30
minutes after each adjustment.
Propane models may exhibit a flame pattern
that may candle or appear stringy. If this is
problematic or persists as the appliance is
continually operated, adjust the air shutter
closed as described in the previous paragraphs.
Operate the appliance for a period of time as the
effect diminishes, ensuring that the appliance
does not develop sooty flames. When satisfied
that the appliance operates properly, proceed
to finish the installation.
Burner
Venturi
Tube
Air Shutter
Opening
Orifice
Air
Shutter
Door
Increase
Air Shutter
Opening
Air Shutter
Adjusting
Arm
Decrease
Air Shutter
Opening
RENRUBNIAM
GNITTESGNINEPORETTUHSYROTCAF
sledoM
saGlarutaN
)mm(sehcni
0353VDE
8/1)2.3(
5304VDE)5.9(8/3
saGenaporP
)mm(sehcni
8/3)5.9(
0454VDE)5.9(8/3
Figure 50
Leave the control knob in the ON position and
the remote switch OFF. Close the lower control
compartment door.
Step 11. HOOD INSTALLATION
All of these appliances must have hoods
installed prior to operating.
On all clean face units, slide the hood into the slots
on the lower edge of the radiant panel
(Figure 51 )
On louvered face units, slide the hood into the slots
on the lower edge of the cabinet top
(Figure 52 )
.
FINISHING REQUIREMENTS
Wall Details
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thickness of the finished wall (
Combustible
Finished Wall
Materials
Combustible
material
may touch the
appliance top.
Combustible
materials not
allowed below
this point on
the face of the
appliance.
Hood must be installed as shown.
Clean Face Models
Figures 51 and 52
This Area Must Remain
Clear of Combustible
Materials
1" Min
(25 mm)
Spacer
Top of Appliance
Radiant panel
Top of Door Frame
Figure 51
Combustible
Finished Wall
Materials
Combustible
material
may touch the
appliance top.
Combustible
materials not
allowed below
this point on
the face of the
appliance.
Hood must be installed as shown.
Louver Face Models
This Area Must Remain
Clear of Combustible
Materials
1" Min
(25 mm)
Spacer
Top of Appliance
Louvers
Top of Door Frame
Figure 52
.
)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
25
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth
extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face
(black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face. See Figures 51 and52 on page 25.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must
not cover any portion of the glass or louvers; they may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel
up to the installed hood.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See
Figure 53
. Mantels constructed of non-
combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the hood.
Combustible materials may project beyond the
sides of the fireplace opening as long as they
are kept within the shaded areas illustrated in
Figure 54
Combustible Materials
Allowed In Shaded
Area “Safe Zone”
17"
.
Side
Wall
14"
12"
Top View Of
45°
Side
Wall
5"
8-1/4"
Min. Distance To
Unprotected Side Wall
Fireplace
Min. Distance
To Protected
Side Wall
14
(356)
MANTEL CLEARANCES
Inches (mm)
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
6 (152) MANTEL
12
(305)
10
(254)
8
(203)
6
(152)
NOTE - Hood shown as positioned in louvered
front model. The hood position in the flush
faced front model is lower than shown.
(102)
4
4 (102) MANTEL
2 (51) MANTEL
TOP OF
APPLIANCE
Figure 54
Figure 53
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is
especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line
holes and other openings should be caulked or stuffed with unfaced fiberglass insulation. In cold climates, if the fireplace is being installed on a cement
slab, a sheet of plywood or other raised platform can be placed underneath to prevent conducting cold up into the room. It also helps to sheetrock
inside surfaces and tape for maximum air tightness and caulk firestops.
WARNING: THIS CONVERSION KIT SHALL BE
INSTALLED BY A QUALIFIED SERVICE AGENCY IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND ALL APPLICABLE CODES AND
REQUIREMENTS OF THE AUTHORIZED HAVING
JURISDICTION. IF THE INFORMATION IN THESE
INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A
FIRE, EXPLOSION OR PRODUCTION OF CARBON
MONOXIDE MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CONVERTED
APPLIANCE IS CHECKED AS SPECIFIED IN THE
OWNER INSTRUCTIONS SUPPLIED WITH THE KIT.
THE QUALIFIED SERVICE AGENCY PERFORMING
THIS INSTALLATION ASSUMES RESPONSIBILITY
FOR THIS CONVERSION.
In Canada:
THE CONVERSION SHALL BE CARRIED OUT
IN ACCORDANCE WITH THE REQUIREMENTS
OF THE PROVINCIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN1-B149.1
AND .2 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE
CONFORMÉMENT AUX RECOMMANDATIONS
DES AUTORITÉS PROVINCIALES AYANT
JURIDICTION ET CONFORMÉMENT AUX
EXIGENCES DU CODE D'INSTALLATION CAN1B149.1 ET.2.
Gas conversion kits are available to adapt your
appliance from the use of one type of gas to the
use of another. These kits contain all the necessary components needed to complete the task
including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the following
steps detail the conversion procedure.
Open the bottom drop-down door. Open it
Figure 46 on page 23 )
neously the left and right top corners of the
door. (The door is hinged at the bottom.) Remove the bottom compartment door by sliding
the hinge pin, located at the door’s left side, to
the right until it disengages from the left corner
post hole. Pull the door diagonally to the left,
away from the fireplace.
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION
SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SERVICE
CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET
TOUTES EXIGENCES ET CODES APPLICABLES DE
L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION
DANS CETTE INSTRUCTION N'EST PAS SUIVIE
EXACTEMENT, UN FEU, EXPLOSION OU PRODUCTION DE
PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES
CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE
PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE
EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET
ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET
COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL
CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS
DANS LES INSTRUCTIONS DE PROPRIÉTAIRE
PROVISIONNÉES AVEC L'ÉQUIPEMENT.
Step 1. Turn off the gas supply to the appliance.
Open the bottom drop-down door. Open it
Figure 46 on page 23 )
neously the left and right top corners of the door.
28
by pushing in simulta-
.oN
noisrevnoCsaGenaporPoTlarutaN
golataC
(See
Remove the modesty panel.To remove the modesty panel lift the modesty panel by the tab on
the panel’s right end, pull the right end of the
panel away from cabinet and then pull the panel
diagonally out of the corner post slots on the
left side of the unit. Remove the modesty panel
carefully, so that none of the wires become
loose or disconnected. Remove the front glass
door/frame from the appliance.
Step 2. Carefully remove the logs. Exercise
care so as not to break the logs.
Step 3. Refer to
A. Above the burner, remove the two baffle
securing screws. Remove the baffle.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Figure 55
.
B. Remove the two screws securing the trapezoidal plate to the burner. Remove the plate.
C. Remove the burner assembly with attached
venturi tube.
Millivolt Appliances
Step 4. SIT Systems - Refer to
page 29
and the instructions provided with the
kit. Using a Torx T20, remove and discard the
three pressure regulator mounting screws.
Remove the pressure regulator, spring, poppet, diaphragm and bushing. Discard all re-moved components. Ensure the rubber gasket
installed on the back of the replacement pressure regulator is properly positioned and install
the new pressure regulator using the new screws
supplied with the kit. Tighten screws to 25 In.
lb. torque.
Figure 56 on
Pressure
Regulator
Remove
These
Components
Figure 56
Step 5. Attach manometer to the manifold
side pressure test fitting and verify manifold
pressure reads 3.5 inches water column (0.87
kPa) for natural gas, and 10.0 inches water
column (2.49 kPa) for propane gas.
Step 6. Refer to
Figure 57
pilot hood assembly to access the hexed pilot
orifice. Remove and replace the orifice with
the one provided with the kit.
and remove the
CONTROL
IGNITE
Manifold
Pressure
Test Port
Slotted
Cap
OFFION
Inlet Pressure Test Port
PSI
Adjusting
Screw
Spring
Figure 58
See
Figure 59
follows: Remove the ignitor assembly retainer
clip, and carefully remove the ignitor assembly.
Exercise extreme care to prevent damage to
or breakage of the ignitor assembly. Remove
the screw securing the pilot assembly to its
mounting bracket. Back off the flare nut at the
end of the pilot gas line to free the pilot assembly from the gas line. Remove the pilot orifice
and replace it with the one provided with the
conversion kit. Reinstall the pilot assembly by
reversing the steps detailed here.
and replace the pilot orifice as
All Models
Step 8. (Refer to
Figure 55 on page 28
)
A. Remove the orifice from the manifold and
replace it with the one provided in the kit. See
the following table for orifice sizes for natural
and propane models
. Figure 60
illustrates the
orifice.
B. Retrieve the burner and hold the venturi tube
above the orifice . Place the shutter adjusting
rod in the propane slot of the shutter arm (see
Figure 50 on page 25)
. Set the burner assembly into its position and secure the trapezoidal
plate with the two screws previously removed.
C. Reinstall the baffle with the two baffle
securing screws.
ezisecifirO
.oNledoM
larutaNenaporP
0353VDE04#35#
5304VDE63#25#
0454VDE33#15#
Pilot
Orifice
Figure 57
Electronic Appliances
Step 7. Honeywell Electronic Valves - See
Figure 58
kit. Remove the slotted cap screw, o-ring,
pressure-regulating adjusting screw and spring.
Retain all parts for possible later use. Install new
components from the kit. Black cap and red
spring for propane gas units. Silver cap and
stainless steel spring for natural gas units. Before installing the cap, attach manometer to the
manifold side pressure test fitting and adjust
screw until pressure reads 3.5 inches water
column (0.87 kPa) for natural gas, and 10.0
inches water column (2.49 kPa) for propane gas.
and the instructions provided with the
When reinstalling the ignitor assembly, use
extreme care to prevent damage and breakage. Do not apply any leverage to the ignitor
assembly while restoring the retainer clip to
its original position.
Pilot
Orifice
Retaining
Flare Nut
Pilot
Assembly
Ignitor
Assembly
Clip
Note: If the ignitor is damaged, a replacement
kit is available, order Catalog Number 87L54.
Figure 59
Figure 60
Step 9. Reassemble the remaining compo-
nents by reversing the procedures outlined in
the preceding steps. Use pipe joint compound
or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are
used in propane applications, do not use pipe
joint compounds on flare fittings).
Step 10. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance.
Step 11. Turn on gas supply and test for gas
leaks.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
29
30
NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
NOTE: THIS PAGE INTENTIONALLY LEFT BLANK.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
31
Lennox Hearth Products reserves the right to make changes at any time, without notice, in
design, materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.