Lennox HP13 Installation Instructions Manual

Page 1
INSTALLATION
';_)2007 Lennox industries Jnc,
0( us
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
A CAUTION
®
Dallas, Texas, USA
WARNING
INSTRUCTIONS
HP13 Series Units
HEAT PUMP UNITS _Technical 505,076M LLJJ Publications
06107 LithoU.S.A. Supersedes 07/06
HP13 Outdoor Unit ............................ 1
Shipping & Packing List ........................ 1
General Information ........................... 3
Unit Dimensions ............................... 2
Setting the Unit ............................... 3
Removing Panels ............................. 5
Electrical ..................................... 6
Refrigerant Piping ............................. 8
Refrigerant Metering Device .................... 10
Manifold Gauge Set ........................... 10
Service Valves ................................ 11
Leak Testing .................................. 11
Evacuation ................................... 12
Start-Up ...................................... 12
Refrigerant Charging ........................... 13
System Operation ............................. 15
Defrost System ............................... 15
Maintenance .................................. 16
Optional Accessories .......................... 16
Homeowner Information ........................ 17
Thermostat Operation .......................... 17
Start-Up and Performance Check List ............ 18
X_ IMPORTANT
06/07
IIIlllllllllllllllllllllllllllllllllllll
Lennox Elite ® Series HP13 outdoor units are approved and warranted only for installation with specially matched indoor coils, line sets, and refrigerant control
devices aC designated by Lennox. Refer to Lennox engineering handbook for check expansion valve (CTXV) kits which may need to be ordered separately.
1 - Assembled HP13 outdoor unit
Check unit for shipping damage. Consult last carrier immediately if damage is found.
Page 1
505,076M
IIIllllllllllllllllllllllllllllllHlllllllll
Page 2
TOP VIEW
4 C
DISCHARGE AIR t
f--
/
'X/
CONTACTOR
SUCTION LINE
CONNECTION FILTER DRIER/
CONNECTIONS
LIQUID LINE CONNECTION
LIQUID LINE CONNECTION
ELECTRICAL
/ INLETS
VAPOR LINE
JCONNECTION
RUN
CAPACITOR
DEFROST
BOARD
REVERSING
VALVE
LIQUID LINE
HP13 PARTS ARRANGEMENT
A
,OUTDOOR FAN
-COMPRESSOR
HIGH PRESSURE SWITCH (-018 MODEL ONLY)
, VAPOR LINE
VAPOR VALVE AND
- GAUGE PORT/SUCTION LINE CONNECTIONS
q
UNIT SUPPORT FEET
8-1/2 (2"
8-3/4
(2
HP13-018, -024, -030, AND -036
HP13 A
-018 35 (889)
-024 35 (889)
-030 31 (787)
-036 35 (889)
-042 35 (889)
-048 39 (991)
-060 39 (991)
SIDE VIEW
(343)
BASE SECTIONS
B
27 (686) 27 (686)
27 (686) 27 (686)
30-1/2 (775)
30-1/2 (775)
35-1/2 (902)
I I
C
28 (711) 28 (711)
28 (711) 28 (711) 35 (889)
35 (889)
39-1/2 (1003)
4-1/4 4-3/4 (108) (121)
f f
9-1/2
41)
8-1/4 (210)
l
D
13-7/8 (352) 7-3/4 (197)
16-7/8 (429) 8-3/4 (222)
E F
2(51) [_-
J
-
UNIT SUPPORT / "_
1 (25)
N
I I i i
SIDE VIEW
FEET\
D (_ @ C)
E
l
HP13 BASE WITH ELONGATED LEGS
G H J K
3-1/4 (83)
3-1/8 (79)
27-1/8 (689)
30-3/4 (781)
3-5/8 (92)
4-5/8 (117)
4-1/2 (114)
3-3/4 (95)
-r
K
_l
J
----I-
20-5/8 (524)
26-7/8 (683)
505076M 06/07
Page 2
Page 3
WARNING
These instructions are intended as a general guide and do not supersede national or local codes in any way.
Authorities having jurisdiction should be consulted before
installation+ When servicing or repairing HVAC components, ensure
the fasteners are appropriately tightened. Table 1 shows torque values for fasteners+
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.- lb. 11 NM Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb. 11 NM
CAUTION
position that will transmit sound or vibration to the living area or adjacent buildings.
2+ Install the unit high enough above ground or roof to
allow adequate drainage of defrost water and prevent ice build-up.
3+ In heavy snow areas, do not locate unit the where
snowdrifts will likely build. The unit base should be elevated above the depth of average snows.
NOTE - Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain
holes in unit base.
4+ Locate the unit so prevailing winter winds will not blow
into the coil.
5. Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil
or into unit.
NOTES:
Service clearanceof30in. (762mm)mustbe maintainedon oneof the sidesadjacentto the control box+
Clearanceto one of the otherthree sides must be 36 in. (914 mm)
Clearanceto one of the remainingtwo sides may be 12 in+(305 mm) and the final side may be 6 in. (152mm),
A clearanceof24 in, (610mm) must be maintained between two units.
48 in. (1219mm)clearancerequired on top of unit,
Outdoor units operate under a wide range of weather conditions; therefore, several factors must be considered
when positioning the outdoor unit+
Position the unit to allow adequate airflow and servicing clearance. Maintain a minimum clearance of 24 inches
(610 mm) between multiple units as illustrated in figure 1+
1+ Place a sound-absorbing material, such as Isomode,
under the unit if it will be installed in a location or
Figure 1. Installation Clearances
SLAB MOUNTING
When installing unit at grade level, the top of the slab should be high enough above grade so that water from
higher ground will not collect around the unit. The slab should have a slope tolerance away from the building of 2
degrees or 2 inches per 5 feet (50 mm per 1500 mm) to prevent ice build-up under the unit during a defrost cycle+
NOTE - If necessary for stability, anchor unit to slab as described in "Stabilizing unit on uneven surfaces".
Page 3
HP13 SERIES
Page 4
INSTALLUNITLEVELOR,IFONASLOPE,MAINTAINSLOPE
TOLERANCEOF2DEGREES(OR2INCHESPER5FEET
[50MMPER1.5M])AWAYFROMBUILDINGSTRUCTURE.
BUILDING STRUCTURE
MOUNTING _ i T SLAB
GROUND LEVEL
__L
Figure 2. Slab Mounting Options
ELEVATING THE UNIT (SMALL-BASE UNITS)
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be
done by cutting four equal true-cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as
illustrated in figure 3.
NOTE - Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend
further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the
pre-installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this
procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1"
(25.4mm) square strips should be adequate to hold the extender in place.
Base
Leg Detail
4" (101.6mm)
SCH 40 Piping
ELEVATING THE UNIT (LARGER-BASE UNITS)
Unlike the small-base units which use round feet, the larger-base units are outfitted with elongated feet as illustrated in figure 4. which uses a similar method for
elevating the unit height.
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be
done with 2" SCH 40 female threaded adapter. The specified coupling will fit snuggly into the recess portion of
the feet. Additional couplers can be used to make additional adjustments to the level of the unit.
NOTE - Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.
Base
Leg Detail
2" (50.8ram)
SCH 40
Female Threaded
Adapter
Figure 4. Elevated Slab Mounting using Feet
Extenders (Larger-Base Units)
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
TYPICAL __,,,t INSTALLATION WITH 3 TO 4 IN.
EXTENDERS
IMPORTANT! STRUCTURE INSTALLED _ BUILDING
ALWAYS USE MOUNTING _ i TSTABILIZER BRACKET ON SLAB ELEVATED
INSTALLATIONS
STABILIZER BRACKETS
GROUNDLEVEL
Figure 3. Elevated Slab Mounting using Feet
Extenders (Small-Base Units)
505076M 06/07
Figure 5. Elevated Slab Mounting using Feet
Extenders
Page 4
Page 5
IMPORTANT
With unit positioned at installation site, remove two side Iouvered panels to expose the unit base pan. Install the
brackets as illustrated in figure 6 using conventional practices; replace the panels after installation is complete.
Slab Side Mounting
prevailing winter winds
wind barrier ]
24"
inlet air ,_ _641'0 ram)
inlet air
inlet a[_
O inlet air
Figure 7. Rooftop Application with Wind Barrier
If unit cannot be located away from prevailing winter winds, construct a wind barrier sized at least the same height and
width as outdoor unit. Position barrier 24" (610 mm) from
the sides of the unit in direction of prevailing winds (fig. 7).
IMPORTANT! Do not allow panels to hang on unit by top tab.
Tab is for alignment and not designed to support weight of panel,
Panel shown slightly rotated to allow top tab to exit (or enter) top
slot for removing (or installing) panel.
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
Figure 6. Installing Stabilizer Brackets
ROOF MOUNTING
Install unit 6" (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support
the unit, Consult local codes for rooftop applications. If unit cannot be located away from prevailing winter winds,
construct a wind barrier sized at least the same height and
width as outdoor unit, Position barrier 24" (610 mm) from
the sides of the unit in direction of prevailing winds as illustrated in figure 7,
LIP
SCREW
HOLES
Detail
J
ROTATE IN THIS
DIRECTION; THEN DOWN TO REMOVE PANEL
Figure 8. Removing/Installing Louvered
Panels (Details A, B and C)
Remove the Iouvered panels as follows:
1, Remove 2 screws, allowing the panel to swing open
slightly (see figure 8).
2. Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinge corner post until lower 3 tabs clear the slots (see figure 8,
Detail B),
Page 5
HP13 SERIES
Page 6
UTDOOR FAN
PURPLE BLACK
ORANGE
RED
CAPACITOR
START
DUAL CAPACITOR
DEFROST CONTROL
,j! o +
BLACK
POTENTIAL _M_SOR (_
o_- ©
Y1ou_
--C
--L
--R
--0
--YI
COMPRESSOR
CRANKCASE
HEATER
LLOW
CONTACTORI / I
DEFROST.ff'"x _'\,REVERSING
THERMOSTAT_ _VALVE
*MAY BE OPTIONAL
Figure 9. Typical Field Wiring Diagram
3. Move panel down until lip of upper tab clears the top MAINTAINMINIMUMPANELANGLE(AS CLOSETOPARALLELWITHTHEUNIT slot in corner post (see figure 8, Detail A). AS POSSIBLE) WHILEINSTALLINGPANEL.
ANGLE MAY BE TOO SIDE TO MAINTAIN
CAUTION
EXTREME _-_ FULLY-ENGAGED TABS
PREFERRED ANGLE
/k
20B-230/60/I
EQUIPMENT GROUND
T
HOLD DOOR FIRMLY TO THE HINGED
Position and Install Panel--Position the panel almost parallel with the unit (figure 8, Detail D) with the "screw
side" as close to the unit as possible, Then, in a continuous motion:
Slightly rotate and guide the lipof top tab inward (figure 8, Details A and C); then upward into the top slot of the
hinge corner post,
Rotate panel to vertical to fully engage all tabs,
Holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw
holes.
When panel is correctly positioned and aligned, insert the screws and tighten,
505076M 06/07
Detail D
Figure 10. Removing/Installing Louvered
Panels (Detail D)
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
Page 6
Page 7
_WARNING
4, Install low voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit, See figures 11 and 12,
1, Install line voltage power supply to unit from a properly
sized disconnect switch,
2, Ground unit at unit disconnect switch or to an earth
ground,
NOTE - Tofacilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box
using a proper conduit fitting. NO TE - Units are approved for use only with copper
conductors. 24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 9
for field wiring diagram. NOTE - For proper voltages, select thermostat wire
gauge per the foflowing chart:
Wire run length AWG # Insulation type less than 1go' (3Om) 18 color-coded, temperature
more than log' (30m) 16 rating 35°C minimum
NOTE - A complete unit wiring diagram is located
inside the unit control box cover.
3, Install room thermostat (ordered separately) on an
inside wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It
should not be installed on an outside wall or where it
can be effected by sunlight, drafts or vibrations,
Thermostat Indoor Unit
24V Power . _ __ 24V j_ower __
1st-stage II
* a-ux_ry heat I_ _ 1st-stage
4 i- _ common
- '- _x_arTh_--
I k
Outdoor Unit
,@
® ._doorb,owor_
reversing
_ valve
compressor
(SOME CONNECTIONS MAY NOT APPLY. REFER TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
Figure 11. Outdoor Unit and Blower
Unit Thermostat Designations
Thermostat
24V power
®-
common
©-
emergency heat i
Indoor Unit Outdoor Unit
\ 24V power
_'_ common I I
I
--_ _ EMERGENCY
--47 O ;TA;oR; AY
/---------THERMOSTAT
1st-stage II auxiliary heat Ii--
_ indoor blower
(_ reversing_alve
compressor
_" SOME CONNECTIONS MAY NOT APPLY. REFER TO
THERMOSTAT AND INDOOR UNIT.)
Figure 12. Outdoor Unit and Blower Unit
Thermostat Designations (with Emergency
@ , Z"'t-s_ge
- ' auxiliary float-- (_
@,
k
@ ®
Heat)
® @
® ©
@
® @
Page 7
HP13 SERIES
Page 8
Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections), Use Lennox L15 (sweat, non-flare) series line sets as
shown in table 2 or use field-fabricated refrigerant lines, Refer to Refrigerant Piping Guide (Corp. 9351-L9) for
proper size, type, and application of field-fabricated lines. Field connection sizes are also listed in table 2.
Table 2. Refrigerant Line Sets
Field
Model
-018
-024 (10 mm) (19 mm)
-030
-036
-042 (10 mm) (22 mm)
-048
-060 (10 mm) (29 mm)
Connections
Liquid Vapor Line Line
3/8 in. 3/4 in
3/8 in. 7/8 in
3/8 in, 1-1/8 in.
Recommended Line Set
Liquid Vapor L15 Line Line Line Sets
3/8 in. 3/4 in L15-41 (10 (19 mm) 15 ft, - 50 ft.
mm) (4.6 m - 15 m) 3/8 in. 7/8 in L15-65
(10 (22 mm) 15 ft, - 50 ft. mm) (4.6 m - 15 m)
3/8 in, 1-1/8 in. Field (10 (29 mm) Fabricated
mm)
NOTE - Units are designed for line sets of up to fifty feet (15 m). For applications longer than fifty feet, consult the Lennox Refrigerant Piping Guide (Corp. 9351-L9). Select
line set diameters from table 2 to ensure that oil returns to the compressor.
INSTALLING REFRIGERANT LINE
Pay close attention to line set isolation during installation of any heat pump or a/c system. When properly isolated from
building structures (walls, ceilings, floors), the refrigerant lines will not create unnecessary vibration and subsequent
noises. Also, consider the following when placing and installing a high-efficiency outdoor unit:
1. Placement--Some localities are adopting sound ordinances based on the unit's noise level observed
from the adjacent property, not from the installation
property. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. Figure 13 shows how to place
the outdoor unit and line set.
Install unit /
away from J
windows
Two 90 ° elbows installed in line set will reduce line set vibration.
Figure 13. Outside Unit Placement and Installation
2. Line Set Isolation--The following illustrations demonstrate procedures which ensure proper refrigerant line set isolation. Figure 14 shows how to
install line sets on horizontal runs. Figure 15 shows how to install line sets on vertical runs. Figure 16
shows how to make a transition from horizontal to vertical.
To hang line set from joist or rafter, use either metal strapping material
or anchored WIRE TIE
STRAPPING MATERIAL (Around vapor line only)
METAL
SLEEVE Strap the vapor line to the joist or
TAPE OR rafter at 8 feet intervals then strap WIRE TIE the liquid line to the vapor line.
ROOF RAFTER _ --
(Around vapor
8 FEET TAPE OR
WIRE TIE
q Ill II
Figure 14. Refrigerant Line Sets: Installing
Horizontal Runs
505076M 06/07
Page 8
Page 9
OUTSIDE WALL lines must not contact wall. VAPOR
IMPORTANT - Refrigerant LIQUID
LINE
LINE
TIE
WALL
ANCHORED
HEAVY NYLON
WIRE TIE
WALL STUD
NOTE - Similar installation
practices should be used if
line set is to be installed on exterior of outside wall.
VAPOR LINE
WRAPPED WITH
ARMAFLEX LIQUID
must not contact structure.
P Cv_\ULK
PIPE
FIBERGLASS
WOOD
BLOCK
STRAP
METAL VAPOR LINE -
SLEEVE WRAPPED IN
AUTOMOTIVE
HANGER
WALL o
MUFFLER-TYPE _
METAL VAPOR LINE - LINE
SLEEVE WRAPPED IN
ARMAFLEX
Ii
ARMAFLEX
Strap Liquid
Line
LIQUID
X Strap Liquid
Line
Line To Vapor
LIQUID
por
Figure 15. Refrigerant Line Sets: Installing Vertical
Runs (New Construction Shown)
Figure 16. Refrigerant Line Sets: Transition from
Vertical to Horizontal
Page 9
HP13 SERIES
Page 10
BRAZING CONNECTION PROCEDURE
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the system.
3. Use silver alloy brazing rods (5 or 6 percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper4o-steel
brazing) which are rated for use with HCFC-22 refrigerant. Wrap a wet cloth around the valve body and the copper tube stub. Braze the line set to the
service valve.
4. Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage during
brazing. Wrap another wet cloth underneath the valve body to protect the base paint.
NOTE - The tube end must stay bottomed in the fitting during final assembly to ensure proper seating,
sealing and rigidity.
5. If required, install a field-provided check expansion valve (approved for use with HCFC-22 refrigerant) in
the liquid line at the indoor coil.
Table 3
Indoor Check Expansion Valve Kits
Model Kit Number
HP13-018, -024, -030, -036 LB-85759F HP13-042, -048 LB-85759G
HP13-060 100188-01
A IMPORTANT
If you install a check expansion valve with an indoor coil
that includes a fixed orifice, remove the orifice before the check expansion valve is installed. See figure 17 for
installation of the check expansion valve.
// j
DISTRIBUTOR (__ LIQUID LINE
................................_ STUB
HP13 units are used in check expansion valve (CTXV) systems only. See the Lennox Engineering Handbook for
approved expansion valve match-ups and application information.
Check expansion valves equipped with Chatleff fittings are available from Lennox. Refer to the Engineering
Handbook for applicable check expansion valves for use
with specific match-ups. See table 3 for valve kits.
DEFROST --....__.._
THERMOSTAT
!
i
DISTRIBUTOR OUTDOOR UNIT
!
CHECK EXPANSION VALVE
DRIER OUTDOOR
LOW Hugh
PRESSURE PRESSURE
II
COiL
!
NOTE- If installing expansion valve with an indoor coil that in- cludes a fixed orifice, remove orifice before installing valve.
Figure 17. Metering Device Installation
When checking the unit charge, use a manifold gauge set that is equipped with "low loss" hoses. Do not use a
manifold gauge set with anything other than a "low loss" hose. See figure 18 for manifold gauge connections.
NOTE - ARROWS INDICATE DIRECTION OF REFRIGERANT FLOW
REVERSING VALVE
VAPOR set- SERVICE vice port J PORT
line
NOTE - USE GAUGE PORTS ON VAPOR LINE VALVE AND LIQUID VALVE FOR EVACUATING REFRIGERANT LINES
AND INDOOR COIL. USE VAPOR GAUGE
PORT TO MEASURE VAPOR PRESSURE DURING CHARGING.
INDOOR UNIT
INDOOR
COIL
o s@:,!.
Figure 18. HP13 Cooling Cycle (Showing Gauge Manifold Connections)
505076M 06/07
f JJ COMPRESSOR _ valve
CHECK EXPANSION VALVE --
Page 10
Page 11
The liquid line and vapor line service valves (figures 19 and
20) and gauge ports are used for leak testing, evacuating, charging and checking charge,
STEM INSERT HEX
SCHRADER VALVE (OPEN TO
LINE SET WHEN VALVE IS CLOSED
(FRONT SEATED)]
TO OUT- DOOR
COIL
SERVICE PORT CAP
CAP
(VALVE FRONT-SEATED)
TO
INDOOR
COIL
Valve in closed position Valve in open position
Figure 19. Front-Seated Liquid Line Service Valve
Each valve is equipped with a service port which has a
factory-installed Schrader valve. A service port cap
protects the Schrader valve from contamination and serves as the primary leak seal, After accessing, opening, closing valves, be sure to appropriately tighten the
components [see table 1 (on Page 3) for torque requirements],
FRONT-SEATED SERVICE VALVE (LIQUID LINE) The front-seated service valve is shown in figure 19, When
this valve is closed, the service port is open to the line set.
Access the service port and open and close valves as
described in the following paragraphs,
A IMPORTANT
2, Use a service wrench with a hex-head extension
(3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly,
3, Replace the stem cap, Tighten finger tight; then torque
per table 1 (Page 3),
Vapor Line Ball Valve
Ball-type service valves (see figure 20) function the same
way as the other valves but cannot be rebuilt; if one fails,
replace with a new valve. The ball valve is equipped with a service port with a factory-installed Schrader valve, A
service port cap protects the Schrader valve from contamination and assures a leak-free seal,
STEMCAP TO
USE ADJUSTABLE WRENCH TO OPEN: ROTATE STEM COUNTER-CLOCKWISE 90° .
TO CLOSE: ROTATE STEM CLOCKWISE 90 ° .
TO _SCHRADER VALVE
INDOOF
COIL SERVICE
STEM
SERVICE PORT
CLOSED)
OUTDOOR COIL
PORT CAP
Figure 20. Bali-Type Vapor Valve (Valve Closed)
After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor unit for leaks,
TO ACCESS SCHRADER PORT:
1, Remove service port cap with an adjustable wrench,
2. Connect gauge to the service port. 3, When testing is completed, replace service port cap,
Tighten finger tight; then torque per table 1 (Page 3),
TO OPEN FRONT-SEATED SERVICE VALVES:
1. Remove stem cap with an adjustable wrench,
2, Use a service wrench with a hex-head extension
(3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go,
3, Replace the stem cap, Tighten finger tight; then torque
per table 1 (Page 3),
TO CLOSE FRONT-SEATED SERVICE VALVES:
1, Remove the stem cap with an adjustable wrench,
WARNING
kWARNING
Page 11
HP13 SERIES
Page 12
WARNING I
USING AN ELECTRONIC LEAK DETECTOR OR HALIDE
1, Connect a cylinder of HCFC-22 to the center port of
the manifold gauge set.
2, With both manifold valves closed, open the valve on
the HCFC-22 cylinder (vapor only).
3, Open the high pressure side of the manifold to allow
the HCFC-22 into the line set and indoor unit. Weigh in a trace amount of HCFC-22, [A trace amount is a
maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure,] Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set, Disconnect the HCFC-22 cylinder,
4, Connect a cylinder of dry nitrogen with a pressure
regulating valve to the center port of the manifold gauge set,
5, Connect the manifold gauge set high pressure hose to
the vapor valve service port, (Normally, the high
pressure hose is connected to the liquid line port;
however, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.)
6, Adjust the dry nitrogen pressure to 150 psig (1034
kPa). Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7, After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks, Purge dry nitrogen and HCFC-22 mixture, Correct any leaks and recheck,
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are
defined as any gas that will not condense under temperatures and pressures present during operation of
an air conditioning system. Non-condensables and water vapor combine with refrigerant to produce substances that
corrode copper piping and compressor parts.
,
Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set,
4.
Open both manifold valves; start the vacuum pump,
5.
Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29,01 inches of mercury). During the early stages of evacuation, it is
desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute
pressure, A rapid rise in pressure indicates a relatively large leak, If this occurs, repeat the leak testing procedure,
NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure,
,
When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor unit, Close the manifold gauge valves.
Xk WARNING
7. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from
the line set and indoor unit,
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
HCFC-22 refrigerant, Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the HCFC-22 cylinder and remove
the manifold gauge set,
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to vapor line service valve
high pressure gauge to liquid line service valve
2. Connect micron gauge.
505076M 0_07
IMPORTANT
Page 12
Page 13
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory- and field-installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and vapor line service valves (counterclockwise) to
release refrigerant charge (contained in outdoor unit) into the system.
4. Replace stem caps and secure finger tight, then tighten an additional (1/6) one-sixth of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit
nameplate. If not, do not start the equipment until the power company has been consulted and the voltage
condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to indoor blower unit and close the outdoor unit
disconnect to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
The unit is factory charged with the amount of HCFC-22 refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 15
foot (4.6 m) line set. For varying lengths of line set, refer to
table 4 for refrigerant charge adjustment.
Table 4. Refrigerant Charge per Line Set Lengths
LiquidLine Oz. per 5 ft. (g per 1.5m)adjust from
SetDiameter 15 ft. (4.6m) line set* 3/8 in. (9.5mm) 3 ounce per 5 ft. (85g per 1.5m)
NOTE - *If line length is greater than 15 ft. (4.6 m), add this amount, If line length is less than 15 ft. (4.6 m), subtract this amount.
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur
in the colder months. The method of charging is
determined by the unit's refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
1, Close manifold gauge set valves. Connect the
manifold gauge set to the service valves,
low pressure gauge to vapor valve service port
high pressure gauge to liquid valve service port
2, Connect the center manifold hose to an upright
cylinder of HCFC-22.
3, Set the room thermostat to call for heat. This will
create the necessary load for properly charging the
system in the cooling cycle,
4, Use a digital thermometer to record the outdoor
ambient temperature,
5, When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68 °F
(20 °C). When pressures have stabilized, use a digital
thermometer to record the liquid line temperature.
6, The outdoor temperature will determine which
charging method to use, Proceed with the appropriate charging procedure,
CHARGE USING THE WEIGH-IN METHOD-- OUTDOOR TEMPERATURE < 65°F (18°C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first, locate and repair any leaks and
then weigh in the refrigerant charge into the unit.
1. Recover the refrigerant from the unit.
2. Conduct leak check; evacuate as previously outlined.
3. Weigh in the unit nameplate charge. If weighing facilities are not available or if charging the unit during
warm weather, use one of the following procedures.
CHARGE USING THE SUBCOOLING METHOD--
OUTDOOR TEMPERATURE < 65°F (18°C)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It
may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 200-250 psig
(1379-1724 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections d air intake panels and move obstructions sideways until the
liquid pressure is in the 200-250 psig (1379-1724 kPa) range. See figure 21.
side at a time with cardboard or plastic sheet until proper testing pressures
*Outdoor coil should be blocked one are reached.
cardboard or plastic sheet *Four-sided unit shown.
Figure 21. Blocking Outdoor Coil
1. With the manifold gauge hose still on the liquid service port and the unit's pressure stabilized, use a digital
thermometer to record the liquid line temperature.
2. At the same time, record the liquid line pressure reading.
3. Use a temperature/pressure chart for HCFC-22 to determine the saturation temperature for the liquid line pressure reading.
4. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine subcooling.
5. Compare the subcooling value results with those in table 5. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add
some refrigerant.
Table 5. HP13 Subcooling Values
o Saturation Temperature °F (°C) o LiquidLine Temperature °F (°C) o SubcoolingValue °F (°C)
Model
oF
(°C)*
NOTE - For best results, use the same electronic thermometer to
check both outdoor-ambient and liquid-line temperatures. *F: +/-1 .O°; C: +/-0.5 °
-018 -024 -030 -036 -042 -048 6 11 8 6 6 4
(3.3) (6) (4.4) (3.3) (3.3) (2.2)
-060
9
(5)
Page 13
HP13 SERIES
Page 14
CHARGE USING THE APPROACH METHOD - OUTDOOR TEMPERATURE > 65_F (18<_C)
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best
results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1. Record outdoor ambient temperature using a digital thermometer,
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize,
3. Compare stabilized pressures with those provided in table 7, "Normal Operating Pressures," Minor variations in these pressures may be expected due to differences in installations, Significant differences could mean that the system is not properly charged or that a problem exists with some component in the
system. Pressures higher than those listed indicate that the system is overcharged, Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method,
4. Use the same digital thermometer used to check outdoor ambient temperature to check liquid line
temperature, Verify the unit charge using the approach method,
5. The difference between the ambient and liquid temperatures should match the approach values
given in table 6. If the values do not agree with the those in table 6, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
Table 6. HP13 Approach Values
o Liquid Line Temperature °F (°C) o Outdoor Temperature °F (°C) o Approach Temperature °F (°C)
Model oF
(°C)*
NOTE - For best results, use the same electronic thermometer to check both outdoor-ambient and liquid-line temperatures.
*F: +/-1.0°; C: +/-0.5 °
-018 -024 -030 -036 -042 -048 -060
7 8 9 13 7 9 6
(3.9) (4.4) (5) (7.2) (3.9) (5) (3.3)
A IMPORTANT
Table 7. HP13 Normal Operating Pressures - Liquid +10 & Vapor +5 PSIG*
HP13-018 HP13-024 HP13-030 HP13-036 HP13-042 HP13-048 HP13-060
°F(°C)** Liquid /Vapor Liquid/Vapor Liquid/ Vapor Liquid/ Vapor Liquid/ Vapor Liquid/ Vapor Liquid / Vapor
Cooling
65 (18) 141 / 81 148 / 80 146 / 78 154 / 78 139 / 67 146 / 75 139 / 74
75 (24) 1631 82 1761 82 171 I 79 180 180 163 174 171 I 77 164 177
85 (29) 191 184 206 / 83 201 / 80 216 / 81 191 181 198 178 193 178 95 (35) 222 / 85 240 / 84 233 / 81 246 / 81 220 / 84 229 / 79 230 / 79
105(41) 256 / 87 277 / 86 271 /81 284 / 82 256 / 85 268 / 81 262 / 82 115(45) 296/89 322/87 313/83 328 / 85 294 / 87 308 / 81 300 / 84
Heating
50(10) 192 / 64 185 / 60 198 / 58 196 / 58 204 / 59 197 / 39 213 / 58
40 (4) 180 / 53 176 / 50 188 / 47 185 / 47 195 / 49 189 / 31 200 / 46
30 (-1) 172 / 43 165 / 49 175 / 35 176 / 37 184 / 39 181 / 25 189 / 37
20 (-7) 164 / 34 162 / 31 163 / 26 170 / 30 178 / 32 175 / 18 177 / 32
*These are most-popular-match-up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary **Temperature of the air entering the outside coil.
505076M 0_07
Page 14
Page 15
Theoutdoorunitandindoorblowercycleondemandfrom theroomthermostat.Whenthethermostatblowerswitch
is in the ON position,the indoorbloweroperates continuously.
FILTERDRIER Theunitisequippedwithabi-fiowfilterdrier.Seefigure18.
Ifreplacementisnecessary,orderanotheroflikedesign. CRANKCASEHEATER
A IMPORTANT
EMERGENCY HEAT FUNCTION (ROOM THERMOSTAT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of outdoor unit is required or when auxiliary electric heat is
staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit
control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the
homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor shutdown, but it should also be used following a power
outage if power has been off for over an hour and the outdoor temperature is below 50°F (10°C). System should
be left in the emergency heat mode at least six hours to allow the crankcase heater sufficient time to prevent
compressor slugging.
The HP13 defrost system includes two components: a defrost thermostat and a defrost control.
DEFROST THERMOSTAT
The defrost thermostat is located on the liquid line between the check expansion valve and the distributor. When
defrost thermostat senses 42°F (5.5°C) or cooler, the thermostat contacts close and send a signal to the defrost
control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
DEFROST CONTROL The defrost control board includes the combined functions
of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring
connections. See figure 22. The control provides automatic switching from normal
heating operation to defrost mode and back. During compressor cycle (call for defrost), the control
accumulates compressor run times at 30-, 60-, or
g0-minute field-adjustable intervals. If the defrost thermostat is closed when the selected compressor run
time interval ends, the defrost relay is energized and defrost begins.
FIELD SELECT
TIMING PINS
TEST
PINS
COMPRESSOR
DELAY PINS REVERSING
VALVE
LOW PRESSURE
SWITCH
(OPTIONAL) _
DEFROST
THERMOSTAT
HIGH PRESSURE
SWITCH
(OPTIONAL)
PI (_ FAN
::, @ (_
OBSI
O_S2
- 0-0UT
/L @ _0
fl-OIJT
P2
L W_
-- ¢
DIAGNOSTIC LEDS
24V TERMINAL STRIP CONNECTIONS
SERVICE LIGHT CONNECTIONS
Figure 22. HP13 Outdoor Unit Defrost
Control Board
DEFROST CONTROL TIMING PINS Each timing pin selection provides a different
accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle
is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes (see figure 22). The
defrost timing jumper is factory-installed to provide a 90-minute defrost interval. If the timing selector jumper
is not in place, the control defaults to a 90-minute defrost interval. The maximum defrost period is 14minutes and
cannot be adjusted.
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or
jumpered. If the jumper is in the TEST position at
power-up, the control will ignore the test pins. When the
jumper is placed across the TEST pins for two seconds,
the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost
mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the
additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the
jumper is removed and re-applied.
COMPRESSOR DELAY
The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling
in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost
mode when the compressor delay jumper is removed.
Page 15
HP13 SERIES
Page 16
NOTE - The 30-second "off" cycle is not functional when
jumpering the TEST pins.
TIME DELAY
The timed-off delay is five minutes long. The delay helps to protect the compressor from short-cycling in case the
power to the unit is interrupted or a pressure switch opens, The delay is bypassed by placing the timer select jumper
across the TEST pins for 0,5 seconds.
_WARNING
Pressure Switch Circuit The defrost control incorporates two pressure switch
circuits, The optional high pressure switch (S4) connects to the board's HI PS terminals. The board also includes
connections for an optional low pressure, or loss-of-charge-pressure, switch (S87), Switches are
shown in figure 22, During a single demand cycle, the defrost control will lock
out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In
addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open
pressure switch (see Table 8). The unit will remain locked out until power to the board is interrupted, then
re-established or until the jumper is applied to the TEST pins for 0,5 seconds,
NOTE - The defrost control board ignores input from the low-pressure switch terminals as follows:
during the TEST mode,
during the defrost cycle,
during the 90-second start-up period,
and for the first 90 seconds each time the reversing valve switches heat/cool modes.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
Table 8
Defrost Control Board Diagnostic LED
Mode Green LED (DS2) Red LED (DS1)
No powerto control OFF OFF Normal operation / Simultaneous Slow FLASH
powerto control
Anti-short cycle lock- out Alternating Slow FLASH
Low pressure switch OFF Slow FLASH
fault (Optional)
Low pressure switch OFF ON lockout(Optional)
High pressure switch Slow FLASH OFF
fault (Optional)
High pressure switch ON OFF lockout(Optional)
Before the start of each heating and cooling season, the
following service checks should be performed by a qualified service technician. First, turn off electrical power
to the unit prior to performing unit maintenance.
Inspect and clean the outdoor and indoor coils. The outdoor coil may be flushed with a water hose.
NOTE - It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which
are corrosive or which block airflow across the coil
(e.g., pet urine, cottonwood seeds, etc.)
Visually inspect the refrigerant lines and coils for leaks.
Check wiring for loose connections.
Check voltage at the indoor and outdoor units (with
units operating).
Check the amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters.
Check the refrigerant charge and gauge the system
pressures.
Check the condensate drain line for free and unobstructed flow; clean, if necessary.
Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM
Refer to the unit information service manual for pressure
drop tables and procedure.
NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. Refer to section on refrigerant charging in this
instruction.
Refer to the Engineering Handbook for optional
accessories that may apply to this unit. The following may or may not apply:
Loss of Charge Kit
High Pressure Switch Kit
Mild Weather Kit
Compressor Monitor
Compressor Crankcase Heater
Mounting Bases
Sound Cover
Low Ambient Kit
Monitor Kit
Dave Lennox Signature Stat'" Room Thermostat
505076M 0_07
Page 16
Page 17
Inordertoensurepeakperformance,yoursystemmustbe properlymaintained.Cloggedfiltersandblockedairflow preventyourunitfromoperatingatitsmostefficientlevel,
1,Air Filter--AskyourLennoxdealertoshowyouwhere
yourindoorunit'sfilterislocated.Itwillbeeitheratthe
indoorunit(installedinternalorexternaltothecabinet) orbehindareturnairgrilleinthewallorceiling.Check thefiltermonthlyandcleanorreplaceitasneeded,
2, Disposable Filter--Disposablefilters should be
replacedwithafilterofthesametypeandsize.
NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
IMPORTANT
3, Reusable Filter--Many indoor units are equipped
with reusable foam filters, Clean foam filters with a
mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or
grille,
NOTE - The filter and all access panels must be in place any time the unit is in operation,
4, Electronic Air Cleaner--Some systems are
equipped with an electronic air cleaner, designed to
remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your
dealer for maintenance instructions.
5. Indoor Unit--The indoor unit's evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the
inside air. Have your dealer show you the location of
the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
IMPORTANT
When removing debris from around the unit, be aware of metal edges on parts and screws, Although special
care has been taken to keep exposed edges to a minimum, physical contact with metal edges and
corners while applying excessive force or rapid motion can result in personal injury,
Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your air
conditioning or heat pump system, HEAT PUMP OPERATION Your new Lennox heat pump has several characteristics
that you should be aware of:
Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space, This
is quite different from gas- or oil-fired furnaces or an
electric furnace which deliver lower volumes of
considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45°F (7°C). An electronic control activates a
defrost cycle lasting 5 to 15minutes at preset intervals
to clear the outdoor coil of the frost.
During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the
conclusion of the defrost cycle. IN CASE OF EXTENDED POWER OUTAGE...
If the outdoor temperature is below 50°F (10°C) and power to your outdoor unit has been interrupted for 6 hours or
longer, observe the following when restoring power to your heat pump system.
Set the room thermostat selector to the "Emergency
Heat" setting to obtain temporary heat for a minimum
of 6 hours. This will allow system refrigerant pressures
and temperatures enough time to return to a stabilized
condition.
In Emergency Heat mode, all heating demand is
satisfied by auxiliary heat; heat pump operation is
locked out. After a six-hour "warm-up" period, the
thermostat can then be switched to the "Heat" setting
and normal heat pump operation may resume.
6. Outdoor Unit--Make sure no obstructions restrict airflow to the outdoor unit. Leaves, trash or shrubs
crowding the unit cause the outdoor unit to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which
collects around the unit.
Though your thermostat may vary somewhat from the description below, its operation will be similar, TEMPERATURE SETTING LEVERS Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both
heating and cooling. Avoid frequent temperature adjustment; turning the unit off and back on before
pressures equalize puts stress on the unit compressor.
Page 17
HP13 SERIES
Page 18
FAN SWITCH In AUTO or INT (intermittent) mode, the blower operates
only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a
priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the
compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired,
SYSTEM SWITCH
Set the system switch for heating, cooling or auto operation. The auto mode allows the heat pump to
automatically switch from heating mode to cooling mode to maintain predetermined comfort settings, Many heat
pump thermostats are also equipped with an emergency heat mode which locks out heat pump operation and
provides temporary heat supplied by the auxiliary heat, INDICATING LIGHT
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the
emergency heat mode, TEMPERATURE INDICATOR
The temperature indicator displays the actual room temperature,
PROGRAMMABLE THERMOSTATS
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the
added feature of programmable time-of-day setpoints for both heating and cooling, Refer to the user's information
manual provided with your particular thermostat for operation details,
PRESERVlCE CHECK If your system fails to operate, check the following before
calling for service:
Check to see that all electrical disconnect switches are ON.
Make sure the room thermostat temperature selector is properly set,
Make sure the room thermostat system switch is properly set.
Replace any blown fuses, or reset circuit breakers,
Make sure unit access panels are in place,
Make sure air filter is clean,
Locate unit model number and have it handy before calling,
Job Name Job Location Installer Unit Model No,
Serial No,
Job no. Date
City State City State
Nameplate Voltage Rated Load Ampacity
Compressor Amperage:
Maximum Fuse or Circuit Breaker Electrical Connections Tight? _1
Indoor Blower RPM
S,P, Drop Over Indoor (Dry)
Indoor Filter clean?
COOLING Liquid Line Pressure;
Vapor Pressure;
HEATING Liquid Line Pressure;
Vapor Pressure;
Refrigerant Lines: - Leak Checked? _1 Properly Insulated? _1 Service Valves: --- Fully Opened? _ Caps Tight?
SEQUENCE OF OPERATION
Heating Correct? _ Cooling Correct?
Service Technician
Outdoor Fan
Supply Voltage (Unit Off) Outdoor Coil Entering Air Temp,
Refrigerant Charge Checked?
Refrigerant Charge Checked? Outdoor Fan Checked?
Voltage With Compressor Operating
THERMOSTAT
Calibrated? _ Properly Set? _ Level?
505076M 0_07
Page 18
Loading...