Lennox GWB8-280E-2, GWB8-262E-2, GWB8-245E-2, GWB8-299E-2 User Manual

Lennox Industries Inc. Dallas, Texas
INSTALLATION
INSTRUCTIONS
GWB8-262E-2 GWB8-245E-2 GWB8-299E-2 GWB8-280E-2
GAS FIRED BOILER
RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE
These instructions must be affi xed on
or adjacent to the boiler .
This boiler cannot be used with all types of chimneys. Read these instructions carefully
before installing.
!
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualifi ed installer, service agency, or the gas supplier.
GAS-FIRED HOT WATER BOILERS
These Gas-Fired Water boilers are low pressure, sectional cast iron boilers Design Certifi ed by CSA (Canadian Standards Association) for use with Natural and Propane Gases. They are constructed and hydrostatically tested for maximum working pressure of 50 psi (pounds per square inch) in accordance with A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards for Cast Iron Heating Boilers.
C.S.A. Certifi ed for
Natural gas or Propane
Tested for 50 psi. ASME
Working Pressure
P/N# 240009276, Rev. A [03/2012]
Figure 1 - Dimensions
1 - DIMENSIONS
Table 1 - Dimensions
DIMENSIONS
BOILER MODEL NUMBER
GWB8-245E-2/GWB8-262E-2
GWB8-280E-2/GWB8-299E-2
Add 5½” to height for vent Damper.
FLUE
DIAMETER
(INCH.)
“A”
WIDTH
727½
7 30¾
2
2 - BOILER RATINGS AND CAPACITIES
Table 2 - Ratings and Capacities
† NATURAL GAS † PROPANE GAS AFUE
(2)
(2)
BOILER MODEL NUMBER
(1)
Input
(3)
Mbh
Heating
Capacity
(3)
Mbh
NET AHRI
RATING
Water,
(3)
Mbh
GWB8-262E-2 262.5 220 191
GWB8-299E-2
299 251 218
GWB8-245E-2
GWB8-280E-2
Input rating for sea level to 2,000 ft. (610m) above sea level.
HIGH
ALTITUDE
INPUT
(3)
Mbh
236
269
INPUT
(3)
Mbh
HEATING
CAPACITY
(3)
Mbh
245 206 179
280 235 204
• United States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every 1000 ft (304m)
above sea level.
• *Canada, 2000 ft (610m) to 4500 (1350m) above sea level, reduce input per table. Over 4500 ft
(1350m) above sea level. Contact Provincial authority having jurisdiction.
+ Heating Capacity based on D.O.E. (Department of Energy) test procedure.
NET
AHRI
RATING
Water,
(3)
Mbh
HIGH
ALTITUDE
INPUT
(3)
Mbh
220
252
INTERMITTENT
IGNITION
WITH VENT
DAMPER
83.9
83.7
83.9
83.7
(2)
Net AHRI Water rating shown based on piping and pickup allowance of 1.15. Consult manufacturer before
selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
(3)
Mbh = 1,000 Btuh = British Thermal Unit Per Hour
- Ratings marked “Net AHRI Ratings” indicate amount of remaining heat input used to heat radiation or terminal units. Net AHRI Ratings shown are based on allowance of 1.15 in accordance with factors shown on AHRI Standard as published by The Hydronics Institute.
- Selection of boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated heat loss of the building.
- Consult manufacturer before selecting boiler for installations having unusual piping and pickup requirements.
BOILERS FOR USE AT HIGH ALTITUDE
Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above 2,000 feet above sea level, input ratings are reduced by change in main burner orifi ce size.
For altitudes above 2,000 feet above sea level, input ratings should be reduced at rate of 4% for each 1,000 feet above sea level. Consult National Fuel Gas Code, ANSI Z223.1/NFPA 54, or manufacturer for correct orifi ce sizing information. In Canada, a high altitude conversion kit is available to convert to altitudes of 2,000 to 4,500 feet above sea level. Please consult your dealer.
3
3 - TABLE OF CONTENTS
!
1 - Dimensions .................................................... 2
2 - Ratings And Capacities .................................... 3
3 - Table of Contents ............................................4
4 - Installation Procedure .....................................5
5 - Ventilation & Combustion Air ............................6
6 - Connecting Supply And Return Piping ................7
7 - Chimney And Vent Pipe Connection ................. 11
8 - Vent Damper Operation ................................. 14
9 - Gas Supply Piping ......................................... 15
10 - Electrical Wiring .......................................... 15
11 - Wiring Diagrams ......................................... 16
12 - General Instructions .................................... 19
13 - Lighting Instructions ................................... 20
14 - Operating Your Boiler .................................. 21
15 - Maintaining Your Boiler ................................ 23
16 - Service Hints .............................................. 24
17 - Equipment And Optional Accessories ............ 25
Appendix A - Control Module ............................... 27
SAFETY SYMBOLS & WARNINGS
The following defi ned symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
!
DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious injury
KEEP THIS MANUAL NEAR BOILER
RETAIN FOR FUTURE REFERENCE
IMPORTANT: Read the following instructions COMPLETELY before installing!!
WARNING
!
Fire, explosion, asphyxiation and electrical shock hazard. Improper installation could result in death or serious injury. Read this manual and understand all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible materials, gasoline and other fl ammable vapors and liquids.
DO NOT obstruct air openings to the boiler room. Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may result in personal injury or loss of life.
TO THE OWNER - Installation and service of this boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with boiler for future reference.
When this product is installed in the Commonwealth of Massachusetts the installation must be performed by a Licensed Plumber or Licensed Gas Fitter.
!
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
!
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Used to address practices not related to personal injury.
4
4 - INSTALLATION PROCEDURE
!
WARNING
Improper installation, adjustment, alteration, service or maintenance could result in death or serious injury
.
1.
Installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1.
2.
Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically fi red Boilers, ANSI/ASME CSD-1.
3.
Boiler series is classifi ed as a Category I. Vent installation shall be in accordance with "Venting of Equipment ," of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or "Venting Systems and Air Supply for Appliances," of the Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
4.
Boiler has met safe lighting and other performance criteria with the gas manifold and control assembly on the boiler per the latest revision of ANSI Z21.13/CGA
4.9.
5.
Install boiler such that gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service, (circulator replacement, condensate trap, control replacement, etc.).
6.
Locate boiler on level, solid base as near chimney as possible and centrally located with respect to heat distribution system as practical.
7.
Allow 24 inches (610mm ) at front and right side for servicing and cleaning.
8.
When installed in utility room, door should be wide enough to allow largest boiler part to enter, or to permit replacement of another appliance such as water heater.
!
WARNING
Fire hazard. Do not install boiler on combustible ooring or carpeting. Failure to follow these instructions could result in death or serious injury.
1.
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY - For installation on combustible
ooring special base must be used. (See Replacement
Parts Section.) Boiler can not be installed on
carpeting.
Table 3 -
Top 6” (152mm)
Rear 6” (152mm)
Control Side 7” (178mm)
Opposite Side 6” (152mm)
Front
Flue/Vent Connector 6” (152mm)
Near Boiler Piping 1/2” (13mm)
NOTE: Greater clearances for access should supersede fire
* Defi nition of Alcove is three sided space with no wall in front of boiler. ANSI standard for alcove is 18 inches from front of appliance to leading edge of side walls as shown below.
MINIMUM CLEARANCE DIMENSIONS
Inches (mm)
18” (457mm)
protection clearances.
Minimum Clearances to Combustible
Construction (as seen from above)
6"
6"
BOILER
7"
Control
Side
Front
18"
5
5 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of local
building codes.
Provide make-up air where exhaust fans, clothes dryers, and kitchen ventilation equipment interfere with proper operation.
National Fuel Gas Code recognizes several methods of obtaining adequate ventilation and combustion air. Requirements of the authority having jurisdiction may override these methods.
• Engineered Installations. Must be approved by authority having jurisdiction.
• Mechanical Air Supply. Provide minimum of 0.35 cfm per Mbh for all appliances located within space. Additional requirements where exhaust fans installed. Interlock each appliance to mechanical air supply system to prevent main burner operation when mechanical air supply system not operating.
• All Indoor Air. Calculate minimum allowable room volume for all appliances in space. Use a different method if minimum volume not available.
A. Standard Method. Cannot be used if known air
infi ltration rate is less than 0.40 air changes per hour. See Table 4 for space with boiler only. Use equation for multiple appliances.
3
Volume 50 ft
B. Known Air Infi ltration Rate. See Table 4 for
space with boiler only. Use equation for multiple appliances. Do not use an air infi ltration rate (ACH) greater than 0.60.
Volume 21 ft3⁄ACH x Total Input [Mbh]
C. Refer to National Fuel Gas Code for opening
requirements between connected indoor spaces.
x Total Input [Mbh]
• All Outdoor Air. Provide permanent opening(s)
• Refer to National Fuel Gas Code for additional
• Combination Indoor and Outdoor Air. Refer to National
Canada
National Gas and Propane Installation Code Requires providing air supply in accordance with:
communicating directly or by ducts with outdoors.
A. Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second opening commencing within 12 inches of bottom of enclosure.
 Direct communication with outdoors or
communicating through vertical ducts. Provide minimum free area of 1 in² per 4 Mbh of total input rating of all appliances in enclosure.
 Communicating through horizontal ducts.
Provide minimum free area of 1 in² per 2 Mbh of total input rating of all appliances in enclosure.
B. One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure. Provide minimum clearance of 1 inch on sides/back and 6 inches on front of boiler (does not supersede clearance to combustible materials).
requirements for louvers, grilles, screens and air ducts.
Fuel Gas Code for application information.
• Section 8.2 and 8.3 when combination of appliances has a total input of up to and including 400 Mbh (120 kW).
• Section 8.4 when combination of appliances has total input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code for specifi c air supply requirements for enclosure or structure where boiler is installed, including air supply openings and ducts.
Table 4 - Minimum Room Volume, Indoor Air Only*
Room Cubic Feet Volume
Input Mbh
Standard
Method
0.1 0.2 0.3 0.4 0.5 0.6
Known Air Infi ltration Rate Method (Air Changes Per Hour)
262.5 13125 55125 27563 18375 13781 11025 9188 299 14950 62790 31395 20930 15698 12558 10465
* Table values based on boiler only. Add volume for any additional appliances.
6
6 - CONNECTING SUPPLY AND RETURN PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum distance from fl oor or allowable safe point of discharge;
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line;
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or place any obstruction in discharge line;
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
• allow complete drainage of the valve and the discharge line;
• be independently supported and securely anchored to avoid applied stress on the relief valve;
• be as short and straight as possible;
• terminate with plain end (not threaded);
• be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.
Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation requirements.
Figure 2 - Safety Relief Valve
DISCHARGE
LINE
Check local
codes for
maximum
distance
from fl oor or allowable safe point of
discharge.
RELIEF VALVE
7
6 - CONNECTING SUPPLY AND RETURN PIPING
!
WARNING
Burn and scald hazard. Safety relief valve could discharge steam or hot water during operation. In­stall discharge piping per these instructions.
1.
Boiler is shipped assembled. Install discharge piping from safety relief valve. See Warning, Page 7.
2.
Install temperature pressure gauge.
• Apply pipe sealant to threads on shaft of gauge.
• Thread gauge into supply water tee. See Figure 3.
NOTICE
DO NOT TIGHTEN GAUGE BY HAND!! Gauge should be tightened using crescent wrench or 9/16” open end wrench. See Figure 3.
3.
Connect supply and return lines to boiler. Connections may require additional fi ttings and parts, as shown on diagrams.
Figure 3 - Temperature Pressure Gauge
Verify clean water supply is available to water inlet valve. Install sand strainer when water supply is from a well or pump.
Install hot water boiler above radiation level or as required by Authority having jurisdiction install low water cutoff device at time of installation. Periodic inspection is necessary, as is fl ushing of fl oat type devices, per manufacturers specifi c instruction.
FOR USE WITH COOLING UNITS
A. Boiler used in connection with refrigeration
system, must be installed so that chilled medium is piped in parallel with heating boiler. Appropriate valves must be used to prevent chilled medium from entering heating boiler. See Figure 5 page 9.
B. Boiler connected to heating coils located in air
handling units where they may be exposed to refrigerated air circulation, piping system shall be equipped with fl ow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle.
LOW WATER TEMPERATURE AND LARGE WATER CONTENT SYSTEM (See Figures 6 and 7, Page 10.)
Signifi cant condensation may form in boiler and/or venting system if boiler is operated for long period of time with return temperatures of less than 120° F.
Condensate is corrosive and can cause severe damage to boiler and venting system. Minimum design return water temperature to prevent condensation in boiler and venting is 120°F. Minimum high limit setting is 140°F.
1.
Boiler used in heating system where design water temperatures below 140°F are desired (e.g. radiant oor heating), 4-way mixing valve or suitable alternative is required to prevent low temperature return water from entering boiler. Follow mixing valve manufacturer’s instructions.
2.
Boiler connected to system having large water content (such as former gravity system), install system bypass. See Figures 6 and 7, page 10.
3.
If boiler water reset control is used to operate boiler, minimum reset supply water temperature setpoint must be at least 140°F, unless mixing valve is used as in (1) above.
8
6 - CONNECTING SUPPLY AND RETURN PIPING
Figure 4 - Typical Hot Water Piping
Figure 5 - Chilled Water Piping
9
6 - CONNECTING SUPPLY AND RETURN PIPING
Bypass Piping Required For High Mass (Large Water Content) Systems
Figure 6 - BYPASS PIPING - CIRCULATOR ON SUPPLY
Figure 7 - BYPASS PIPING - CIRCULATOR ON RETURN
10
Loading...
+ 22 hidden pages