Improper installation, adjustment, alteration,
service, or maintenance could result in death
or serious injury. Refer to this manual for
assistance. For additional information consult
a qualifi ed installer, service agency, or the gas
supplier.
This boiler cannot be used with all types of
chimneys. Read these instructions carefully
before installing.
C.S.A. Certifi ed
For Natural Gas Or Propane
Tested For 50 psi.
ASME
Working Pressure
GAS-FIRED HOT WATER BOILERS
These Gas-Fired Water boilers are low pressure,
sectional cast iron boilers Design Certifi ed by
CSA (Canadian Standards Association) for
use with Natural and Propane Gases. They
are constructed and hydrostatically tested for
maximum working pressure of 50 psi (pounds
per square inch) in accordance with A.S.M.E.
(American Society of Mechanical Engineers)
Boiler and Pressure Vessel Code Section IV
Standards for Cast Iron Heating Boilers.
A.9 Intermittent Pilot ................................ 30
WARNING
!
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death
or serious injury. Read this manual and understand
all requirements before beginning installation.
WARNING
!
Keep boiler area clear and free from combustible
materials, gasoline and other fl ammable vapors
and liquids.
DO NOT obstruct air openings to boiler room.
Modifi cation, substitution or elimination of factory
equipped, supplied or specifi ed components may
result in personal injury or loss of life.
TO THE OWNER - Installation and service of this
boiler must be performed by a qualifi ed installer.
TO THE INSTALLER - Leave all instructions with
boiler for future reference.
When this product is installed in Commonwealth of
Massachusetts installation must be performed by
Licensed Plumber or Licensed Gas Fitter.
2
BOILER RATINGS & CAPACITIES
Table 1 RATINGS NATURAL AND PROPANE GASES
**Net
Model
GWB8-042IE-242.5363184.443
GWB8-075IE-275.0635583.443
GWB8-112IE-2112.5948283.043
GWB8-150IE-2150.012510982.743
GWB8-187IE-2187.515513582.344
GWB8-225IE-2225.018616282.044
* MBH = 1,000 Btuh = British Thermal Unit Per Hour. Boilers are equipped for altitudes up to 2,000 feet only.
Input
*Mbh
Heating
Capacity
*Mbh
AHRI
Rating
Water
*Mbh
AFUE
Vent Diameter (Inches)
To Chimney
(Category I)
Horizontal Vent
(Category III)
• U.S.A. Only - For altitudes above 2,000 feet, ratings should be reduced at the rate of 4% for each
1,000 feet above sea level.
• Canada Only - Boilers may be used at high altitude (2,000-4500 feet/640-1350m) by using a certifi ed
fi eld conversion kit, resulting in a 10% de-rate. Contact Provincial authority having jurisdiction for
installations above 4500 ft (1350m)above sea level.+ Heating Capacity based on D.O.E. (Department
of Energy) test procedure.
** Net AHRI Water Ratings i
ndicate amount of remaining heat input that can be used to heat the radiation
or terminal units. Net AHRI Ratings shown are based on an allowance of 1.15 Selection of
boiler size should be based upon “Net AHRI Rating” being equal to or greater than calculated
heat loss of building.
Manufacturer should be consulted before selecting a boiler for installations having unusual piping
and pickup requirements.
New York City MEA Number 484-84-E Vol. IV.
This boiler cannot be used with all types of chimneys. Read these instructions carefully before installing.
These Gas-Fired Hot Water Boilers are low pressure, sectional cast iron boilers Design Certifi ed by C.S.A. (Canadian Standards
Association) for use with Natural and Propane Gases. Constructed and hydrostatically tested for maximum working pressure of 50 psi in
accordance with A.S.M.E. Boiler and Pressure Vessel Code Section IV Standards for cast iron heating boilers.
Boilers must stand on noncombustible fl oor. If installed on combustible fl oor, please refer to Repair Parts manual for appropriate
Combustible Floor Base part number.
Boilers For Use At High Altitude
Boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above 2,000 feet above sea level,
input ratings are reduced by change in main burner orifi ce size.
U.S.A. Only - For altitudes above 2,000 feet above sea level, input ratings should be reduced at rate of 4% for each 1,000 feet above
sea level. Consult National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1,
or manufacturer for correct orifi ce sizing information.
Canada Only - For altitudes in the range of 2,000-4,500 feet (610 - 1350m) above sea level, boilers may be fi eld equipped for use
at high altitude by using a certifi ed fi eld conversion kit. The change in main burner orifi ce size results in the boiler’s input rating
being reduced by 10%.The conversion shall be carried out by a manufacturer’s authorized representative, in accordance with the
requirements of the manufacturer, provincial or territorial authorities having jurisdiction and in accordance with the requirements of
CSA-B149 Natural Gas and Propane Installation Code. The certifi ed fi eld conversion kit includes a conversion data plate, which must be
attached to the boiler adjacent to the rating plate, indicating that the boiler has been converted for high altitude use. The conversion
data plate must be fi lled in with the correct conversion information.
For altitudes over 4500 feet (1350m), contact Provincial authority having jurisdiction.
Improper installation, adjustment, alteration, service
or maintenance could result in death or serious
injury
.
1.
The installation must conform to the requirements of
the authority having jurisdiction or, in the absence
of such requirements, to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane
Installation Code, CAN/CSA B149.1
2.
Where required by authority having jurisdiction,
installation must conform to the Standard for Controls
and Safety Devices for Automatically fi red Boilers,
ANSI/ASME CSD-1.
3.
This boiler series is classifi ed as a Category I. Vent
installation shall be in accordance with “Venting of
Equipment ,” of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, or “Venting Systems and Air Supply
for Appliances,” of the Natural Gas and Propane
Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes.
4.
Boiler has met safe lighting and other performance
criteria with gas manifold and control assembly on
boiler per latest revision of ANSI Z21.13/CGA 4.9.
5.
Install such that gas ignition system components are
protected from water (dripping, spraying, rain, etc.)
during appliance operation and service, (circulator
replacement, condensate trap, control replacement,
etc.).
6.
Locate boiler on level, solid base as near chimney as
possible and centrally located with respect to heat
distribution system as practical.
7.
Verify you have the right size boiler before starting
installation. See rating and capacity table.
8.
When installed in utility room, door should be wide
enough to allow largest boiler part to enter, or to
permit replacement of another appliance such as water
heater.
9.
Boiler installed in building under construction, take
care to insure clean combustion air supply during
construction process. Airborne particulates such as
from drywall dust and from fi berglass insulation can
clog burner ports and cause incomplete combustion and
sooting.
!
WARNING
Fire hazard. Do not install boiler on combustible
fl ooring or carpeting. Failure to follow these
instructions could result in death or serious injury.
NOTICE
Follow local regulations with respect to installation
of CO detectors.
10.
FOR INSTALLATION ON NON-COMBUSTIBLE
FLOORS ONLY - For installation on combustible
fl ooring special base must be used. (See Replacement
Parts Section.) Do Not Install Boiler on carpeting.
11.
Verify boiler is supplied with correct type of gas, fresh
air for combustion, and suitable electrical supply.
Figure 1 - Minimum Clearances To Combustible
Construction
6”
8”
Rear
Opposite Side
6”
Boiler
Front
18”
Table 2 - BOILER MINIMUM CLEARANCE TO
COMBUSTIBLES
Unit
Top6” (152mm)
Rear6” (152mm)
Control Side8” (203mm)
Opposite Side6” (152mm)
Front (Alcove)18” (457mm)
Flue/Vent Connector6” (152mm)
Near Boiler Piping1/2” (13mm)
Control Side
8”
Minimum
Clearances
Set unit on concrete or other noncombustible material base or
fl oor. DO NOT INSTALL ON CARPETING.
5
VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,” of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation
Code, CAN/CSA B149.1, or applicable provisions of local
building codes.
Provide make-up air where exhaust fans, clothes dryers,
and kitchen ventilation equipment interfere with proper
operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
• Engineered Installations. Must be approved by
authority having jurisdictions.
• Mechanical Air Supply. Provide minimum of 0.35
cfm per Mbh for all appliances located within space.
Additional requirements where exhaust fans installed.
Interlock each appliance to mechanical air supply
system to prevent main burner operation when
mechanical air supply system not operating.
• All Indoor Air. Calculate minimum volume for all
appliances in space. Use a different method if
minimum volume not available.
о Standard Method. Cannot be used if known air
National Gas and Propane Installation Code Requires
providing air supply in accordance with:
infi ltration rate is less than 0.40 air changes per
hour. See Table 3 for space with boiler only. Use
equation for multiple appliances.
3
Volume ≥ 50 ft
x Total Input [Mbh]
о Known Air Infi ltration Rate. See Table 3 for
space with boiler only. Use equation for multiple
appliances. Do not use an air infi ltration rate
(ACH) greater than 0.60.
Volume ≥ 15 ft3/ACH x Total Input [Mbh]
о Refer to National Fuel Gas Code for opening
requirements between connection indoor spaces.
• All Outdoor Air. Provide permanent opening(s)
communicating directly or by ducts with outdoors.
о Two Permanent Opening Method. Provide opening
commencing within 12 inches of top and second
opening commencing within 12 inches of bottom
enclosure.
Direct communication with outdoors or
communicating through vertical ducts. Provide
minimum free area of 1 in
2
per 4 Mbh of total
input rating of all appliances in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in2 per 2
Mbh of total input rating of all appliances in
enclosure.
о One Permanent Opening Method. Provide opening
commencing within 12 inches of top of enclosure.
Provide minimum clearance of 1 inch on sides
and back and 6 inches on front of boiler (does not
supersede clearance to combustible materials).
о Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for additional requirements
for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air. Refer to
National Fuel Gas Code for application information.
• Section 8.2 and 8.3 when combination of appliances
has a total input of up to and including 400 Mbh (120
kW).
о Does not have draft control device.
• Section 8.4 when combination of appliances has total
input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code
for specifi c air supply requirements for enclosure
or structure where boiler is installed, including air
supply openings and ducts.
Input Mbh
Standard
Method
0.10.20.30.40.50.6
42.52125637531882125159412751063
7537501125056253750281322501875
112.556251687584385625421933752813
150750022500112507500562545003750
187.5937528125140639375703156254688
22511250337501687511250843867505625
Table 3- Air Infi ltration Rate
Known Air Infi ltration Rate Method (Air Changes Per Hour)
6
INSTALLATION SYSTEM PIPING
!
WARNING
Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns,
scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:
• connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum
distance from fl oor or allowable safe point of discharge.
• be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge
line;
• have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or
place any obstruction in discharge line.
• terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;
• allow complete drainage of the valve and the discharge line;
• be independently supported and securely anchored to avoid applied stress on the relief valve;
• be as short and straight as possible;
• terminate with plain end (not threaded);
• be constructed of material suitable for exposure to temperatures of 375° F; or greater.
Refer to local codes and appropriate ANSI/ASME Boiler and Pressure Vessel Code, Section IV, or Boiler,
Pressure Vessel and Pressure Piping Code, CSA B51 for additional installation requirements.
1.
Refer to local codes and appropriate ASME Boiler
and Pressure Vessel Code for additional installation
requirements.
2.
Install relief valve on 3/4” pipe nipple in tapped boiler
opening.
A. Pipe discharge line following guidelines in preceding
Warning. See Figure 2.
B. Discharge line pipe size shall be equal or greater
than that of relief valve outlet over entire length
of discharge line with no intervening shutoff valve
between safety relief valve and discharge to
atmosphere.
C. Discharge line shall terminate with plain end to
atmosphere where any discharge will be clearly
visible and is at no risk of freezing.
D. Discharge line shall be independently supported to
avoid applied stress on relief valve.
E. Installation shall allow complete drainage of relief
valve and discharge line.
3.
Install Drain Valve on lower left side of boiler as
marked.
4.
Install Temperature and Pressure Gauge into ¼”
bushing threaded in tee furnished with supply piping.
See
Figures 3 and 4
5.
Connect Supply and Return Lines to boiler. Figure 3 &
4. Connections may require certain additional fi ttings
and parts.
.
Figure 2 - Safety Relief Valve Discharge Piping
RELIEF VALVE
DISCHARGE
PIPING
Check local codes
for maximum
distance from
fl oor or other
allowable safe
point of discharge
7
INSTALLATION SYSTEM PIPING
Figure 3 -
Forced Hot Water Typical Piping
Figure 4 - Forced Hot Water Typical Piping
With Zone Control Valve
8
INSTALLATION SYSTEM PIPING
• Install radiation units (panels, radiators or cabinets) and
supply and return mains fi rst then make connections at
boiler.
• Verify clean water supply is available when connecting
cold water supply to water valve. Install sand strainer at
pump when water supply is from well or pump.
• Provide low water cutoff device when boiler is installed
above radiation level or as required by the Authority
having jurisdiction, either provide as part of boiler
or at time of boiler installation. Periodic inspection
is necessary, as is fl ushing of fl oat type devices, per
manufacturers specifi c instructions.
• Boiler used in connection with refrigeration systems shall
be installed so chilled medium is piped in parallel with
heating boiler with appropriate valves to prevent chilled
medium from entering heating boiler. See
• Boiler connected to heating coils located in air handling
units exposed to refrigerated air circulation, piping
system shall be equipped with fl ow control valves or
other automatic means to prevent gravity circulation of
boiler water during cooling cycle.
Figure 5
.
Low Design Water Temperature Systems (Below
140°F) And Large Water Content Systems
Condensation is corrosive and can eventually cause severe
damage to boiler and venting system.
• Minimum design return water temperature to prevent
• Boiler used in heating systems where design water
• Boiler connected to system having large water content
condensation in boiler and venting is 120°F. Minimum
high limit setting is 140°F.
temperatures below 140°F are desired (e.g. radiant fl oor
heating), a 3-way or 4-way mixing valve or suitable
alternative is required to prevent low temperature return
water from entering boiler. When using mixing valve,
follow manufacturer’s installation instructions.
(such as former gravity system), suggest use of bypass
piping. See
Figure 6
.
Figure 5
- Piping Arrangements For Boiler When
Used In Connection With Refrigeration
System
Figure 6
- Bypass Piping
9
VENT INSTALLATION
Check Your Chimney
Chimney must be clean, right size, properly constructed
and in GOOD CONDITION.
1.
Installation must conform to requirements of the
authority having jurisdiction or, in absence of such
requirements, to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or of the Natural Gas and Propane
Installation Code, CAN/CSA B149.1, or applicable
provisions of the local building codes..
2.
Boiler’s induced draft blower has 3” outlet. 3” X
4” increaser fi tting is included in parts bag. Locate
increaser fi tting on outlet of induced draft blower, and
secure gas-tight with bead of furnished silicone sealant.
Increaser fi tting is required on this boiler for Category I
venting, and 4” is minimum permissible vent diameter.
This does not imply vent connector is intended to be 4”
diameter pipe. Vent connector shall be sized according
to appropriate venting tables in the National Fuel
Gas Code and may be required to be larger than 4”
diameter.
NOTICE
Boiler installation for chimney venting is not complete
unless increaser fi tting is located and secured.
3.
These are high effi ciency boilers with low stack or
exhaust temperature.
4.
Venting into masonry chimney without liner, line
chimney from top to bottom with either:
A. Listed Type B vent pipe
B. Listed fl exible vent liner
C. Poured ceramic liner.
11.
Fasten sections of vent pipe with sheet metal screws to
make piping rigid. Use stovepipe wires to support pipe
from above.
12.
Do not connect to fi replace fl ue.
13.
Do not install damper on this boiler.
Minimum Vent Pipe Clearance
• Use Type B vent pipe through crawl space. Where vent
pipe passes through combustible wall or partition, use
ventilated metal thimble. Thimble should be 4 inches
larger in diameter than vent pipe.
• Boiler installed with single wall vent, must have 6”
clearance between its surface and any combustible
material. New Type B gas vent or fl exible liner must be
installed in accordance with instructions furnished with
vent. Maintain clearances as specifi ed for vent pipe.
• Verify vent pipe is fi re-stopped where it goes through fl oor or ceiling. It should have approved vent cap with
clearances from roof. If clearances are less than shown
in have vent checked by local authorities. See Figure 7,
Page 11.
• Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of
mechanical draft systems operating under positive
pressure.
5.
Outside chimneys should not be used unless they are
(choose one of the following):
A. Enclosed in a chase
B. Lined with Type B vent pipe
C. Use listed fl exible vent liner
D. Use certifi ed chimney lining system
6.
Vent connector from boiler to chimney should run as
directly as possible with as few elbows as possible.
7.
Where possible, it is recommended to common vent
water heater and boiler. Consult appropriate Vent
Sizing Tables in National Fuel Gas Code for specifi c
requirements of multiple appliance venting.
8.
Boiler is only appliance connected to vent, Type B vent
pipe is recommended for vent connector.
9.
Slope pipe up from boiler to chimney not less than 1/4”
per foot (21mm/m).
10.
End of vent pipe must be fl ush with inside face of
chimney fl ue. Use sealed-in thimble for chimney
connection.
10
Figure 7 - Type B Gas Vent
VENT INSTALLATION
CHECK YOUR CHIMNEY
For boilers for connection to gas vents or
chimneys, vent installations shall be in
accordance with “Venting of Equipment”, of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
or of the Natural Gas and Propane Installation
Code, CAN/CSA B149.1, or applicable provisions
of the local building codes.
11
VENT INSTALLATION
Removing Existing Boiler From Common Venting
System
When an existing boiler is removed from a common
venting system, the common venting system is likely to be
too large for proper venting of the appliances remaining
connected to it.
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliance remaining connected
to the common venting system are not in operation.
1.
Seal any unused openings in the common venting
system.
2.
Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other defi ciencies
which could cause an unsafe condition.
3.
Insofar as is practical, close all building doors and
windows and all doors between the space in which the
appliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliance not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan. Close fi replace dampers.
4.
Place in operation the appliance being inspected. Follow
the lighting instructions. Adjust thermostat so appliance
will operate continuously.
5.
Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use fl ame of a match
or candle, or smoke from a cigarette, cigar, or pipe.
6.
After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fi replace dampers and any
other gas-burning appliance to their previous conditions
of use.
7.
Any improper operation of the common venting system
should be corrected so the installation conforms with
the National Fuel gas Code, ANSI Z223.1/NFPA 54,
and/or the Natural Gas and Propane Installation Code,
CAN/CSA B149.1. When re-sizing any portion of the
common venting system, the common venting system
should be re-sized to approach the minimum size
determined using the appropriate tables in Chapter 13
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and/or the Natural Gas and Propane Installation Code,
CAN/CSA B149.1.
8.
It is recommended that existing gas vents be checked
to be sure they meet local codes.
12
OPTIONAL HORIZONTAL VENTING INSTRUCTION
Horizontal venting with a power venter is an alternate
method of sidewall venting. This boiler is CSA listed for
sidewall venting with standard single wall galvanized or
Type B vent pipe when using the following power venter
kits, which were specifi cally sized for these boilers:
Table 4- Field Controls
Number Of
Boiler Sections
2, 3, 4, 5SWG-4D
6, 7SWG-5D
Some possible reasons for using a power venter for
sidewall venting:
1.
May be preferred by local codes.
2.
Need a vent piping run beyond 30’ (9.1m) (but not
more than 50’ (15.2m)).
3.
The boiler installation site experiences gusting or high
winds. A power venter can help prevent the boiler from
short cycling due to gusting or high winds by providing
vent exhaust pressures greater than the boiler’s
induced draft blower alone.
4.
When installers or homeowners prefer a negative
pressure vent system instead of a positive pressure
vent system.
5.
May be more cost effective than stainless steel
venting, particularly at longer vent length.
The Field Controls power vent kit includes either a
SWG-II-4HD or SWG-II-5 power venter, a MG-1 4”
barometric draft controller, and the CK-43D controls kit.
Field Controls
Power Venter
Confi rm that installing a power venter is an option allowed
by local codes. Follow the specifi c power venter installation
instructions issued with the power venter kits. Although
the power venter is equipped with its own fan, the fan on
the boiler remains in place and is unaltered when a power
venter is used.
When sidewall venting, fl ue gases must be vented to a
point in relation to the prevailing wind so that they may
freely disperse without being blown back at the building
causing discoloration, or into the building through doors or
windows causing odors. Also, under certain conditions fl ue
gases will condense, forming moisture. In such cases, steps
should be taken to prevent building materials at the vent
terminal from being damaged by the exhausted fl ue gas.
When installing single wall galvanized vent pipe for power
venting follow the specifi c power venter installation
instructions for layout, location of the barometric draft
control and termination connections.
When joining and sealing the single wall galvanized or Type
B vent piping, use RTV silicone sealant with a minimum
temperature rating of 400°F. For 3” vent pipe runs, begin with the female end of the vent pipe over the boiler’s
induced draft blower outlet. For 4” vent pipe runs begin
with the galvanized 3” to 4” increaser fi tting (included in
the boiler’s parts bag) over the induced draft blower outlet.
Then follow by placing the female end of the 4” vent pipe
over the increaser fi tting.
When joining pieces of single wall galvanized vent pipe, a
substantial bead of silicone should be used at the joint to
insure a leak proof connection.
13
!
GAS SUPPLY PIPING
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fi re
department.
Figure 8 - Gas Piping At Boiler
Connecting Gas Piping
Gas line enters boiler from right side. Flexible gas
connectors must never breach any boiler openings.
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements:
• USA - National Fuel gas Code, ANSI Z223.1/NFPA 54
• Canada - Natural Gas and Propane Installation Code,
CAN/CSA B149.1
• All pipe compound must be resistant to liquefi ed
petroleum gas.
• Install ground joint union in gas supply line between
shut-off valve and boiler controls.
• Install sediment trap upstream of gas controls.
• Use two pipe wrenches when making connection to gas
valve to keep it from turning.
• Install manual shut-off valve in vertical pipe about 5 feet
(1.5m) above fl oor. See Figure 8.
• Tighten all joints securely.
• Propane gas connections should only be made by
licensed propane installer.
• Two-stage regulation should be used by propane
installer.
• Propane gas piping should be check by propane installer.
Table 5 - Gas Pressures
PRESSURE
MIN. SUPPLY5" w.c.11" w.c.
MAX. SUPPLY13.5" w.c.13.5" w.c.
MANIFOLD3.5" w.c.10" w.c.
Verify minimum pressure while boiler is operating.
Verify maximum pressure when boiler is not operating
NATURALPROPANE
GAS
Check Gas Supply
Gas pipe must be correct size for length of run and for
total BTU per hour input of all gas utilization equipment
connected to it. See Table 6 & 7, Page 15 for proper size.
Be sure your gas line complies with local codes and gas
company requirements.
!
DANGER
Fire Hazard. Do not use matches, candles, open
fl ames, or other methods providing ignition source.
Failure to comply will result in death or serious
injury.
Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation.
• Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from gas
supply system.
• Pressure test at 1/2 psig (3.5 kPa) or less. Isolate
boiler from gas supply system by closing manual gas
shutoff valve. See Figure 8.
• Locate leakage using gas detector, noncorrosive
detection fl uid, or other leak detection method
acceptable to authority having jurisdiction.
• Correct leaks immediately and retest.
14
GAS SUPPLY PIPING
Table 6 - NATURAL GAS
Length of
Pipe - Ft.
2092,000190,000350,000625,000
4063,000130,000245,000445,000
6050,000105,000195,000365,000
Pipe Capacity - BTU Per Hour Input
Includes Fittings
½"¾"1"1¼"
Table 7- PROPANE GAS
Length
of
Pipe - Ft.
20131,000216,000189,000393,000
4090,000145,000129,000267,000
6072,000121,000103,000217,000
Pipe Capacity - BTU Per Hour Input
Includes Fittings
Copper Tubing*Iron Pipe
⅝"¾"½"¾"
*Outside diameter:
Measure length of pipe or tubing from gas meter or propane
second stage regulator.
15
ELECTRICAL WIRING
TH
E
T
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Electrical Wiring
See wiring diagram Figure 10 page 18 for details.
Refer to Ladder Diagram from document envelope
received with boiler.
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1:
Safety Standard for Electrical Installations.
If any of the original wire as supplied with this appliance
must be replaced, it must be replaced with type 105°C
thermoplastic wire or its equivalent
Circulator harness is factory wired to control module.
Connect harness to circulator in fi eld. See Figure 9.
Electric Power Supply
Run a separate 115 volt circuit from separate over current
protective device 15 ampere circuit in electrical service
entrance panel.
Connect 115 volt power supply to terminals L1 (HOT) and
L2 inside J box.
Run 14 gauge or heavier copper wire from boiler to
grounded connection in service panel or properly driven
and electrically grounded ground rod.
Thermostat Installation
1.
Thermostat should be installed on an inside wall about
four feet above the fl oor.
2.
NEVER install a thermostat on an outside wall.
3.
Do not install a thermostat where it will be affected
by drafts, hot or cold pipes, sunlight, lighting fi xtures,
televisions, a fi replace, or a chimney.
4.
Check thermostat operation by raising and lowering
thermostat setting as required to start and stop the
burners.
5.
Instructions for the fi nal adjustment of the thermostat
are packaged with the thermostat (adjusting heating
anticipator, calibration, etc.)
6.
Set heat anticipator at .2 amps. 24 volt thermostat
connects to yellow low voltage wires labled T.
Figure 9 - Control Module Panel
TRANSFORMER
SECONDARY
J BOX
L1 & L2
BLOWER
CIRCULATOR
HARNESS
TRANSFORMERTHERMOSTAT WIRES
16
TRANSFORMER LINE VOLT
R LINE VOL
SEQUENCE OF OPERATION
Sequence of Operation - Figure 10, Page 18.
1.
Thermostat calls for heat, control relay contacts.
2.
Circulator pump is powered through terminals C1 and
C2. Control holds off burner and attempts to satisfy
thermostat with residual boiler heat.
3.
Induced draft blower and transformer primary are
powered.
4.
When blower gets up to speed and blower suction
pressure reaches pressure switch set point, pressure
switch contacts close sending 24 volts to pilot control
from transformer secondary.
5.
Pilot gas valve opens and spark initiates to light pilot
burner.
6.
When pilot fl ame is proven, spark drops out.
7.
Main gas valve opens and pilot burner ignites main
burners.
8.
If boiler water temperature reaches high limit set
point, high limit contacts open, cutting power to
blower and pilot control. Burners extinguish and blower
stops. Circulator pump continues to run as long as
the thermostat continues to call for heat. When boiler
water temperature drops past the high limit set point
and through the differential, high limit contacts close,
repeating steps 3-7.
9.
If venting system becomes blocked, blower suction
pressure will drop below pressure switch set point,
opening pressure switch contacts and cutting power to
pilot control. Burners will extinguish, but blower will
remain powered as long as thermostat continues to call
for heat. If venting system clears, steps 4-7 will repeat.
10.
Thermostat is satisfi ed, ending call for heat. Relay coil
is de-energized, opening contacts. Burners extinguish.
Blower and circulator pump stop.
17
Figure 10 - Control Module
WIRING DIAGRAMS
Damper is not an option.
18
STARTING YOUR BOILER
NOTICE
Do not add water into hot empty boiler.
Filling System With Water
• Close air vents on all radiation units. Open valves to
these units.
• Verify boiler and expansion tank drain valves are closed.
Air bleed screw on tank drain fi tting should be closed.
• Open valve in line from boiler to expansion tank.
• Open water inlet to your boiler and leave open.
• Start with lowest radiation unit. Open air vent on this
unit. When all air has escaped and water starts to fl ow
from vent, close it.
• Go to next radiation unit, and repeat this process.
• Repeat until you have covered every radiation unit in
system. End at highest unit in system.
• If units have automatic vents, manual venting is
unnecessary but it will speed up proper fi lling of system.
• If system is closed expansion tank system, you may
have automatic fi ll valve. Leave it open to refi ll system
automatically as needed.
• Check temperature-pressure gauge. Note position of
hand indicating pressure. This should be between 10
and 15 psi. Any lowering of this movable hand below
10 psi indicates loss of water due to leakage. Automatic
fi ll valve should compensate for this. Instructions are
packaged with valve.
19
STARTING YOUR BOILER
!
!
WARNING
If you do not follow these instructions
exactly, a fi re or explosion may result
causing property damage, personal injury
or loss of life.
• This appliance is equipped with an ignition device
which automatically lights burner. Do NOT try to
light this burner by hand.
• Before operating smell all around appliance area
for gas. Be sure to smell next to fl oor because
some gas is heavier than air and will settle to the
fl oor.
• Use only your hand to turn the gas shutoff
valve. Never use tools. If valve will not turn by
hand, do not try to repair it, call a qualifi ed ser-
vice technician. Force or attempted repair may
result in fi re or explosion.
• Do not use this appliance if any part has
been under water. Immediately call a qualifi ed
service technician to inspect appliance and to
replace any part of control system and any gas
control which has been under water.
LIGHTING PROCEDURE FOR BOILER WITH
INTERMITTENT PILOT SYSTEM
For Your Safety, Read Before Operating!!
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light
appliance by hand.
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
Operating Instructions.
1.
STOP! Read Safety Information on previous page.
2.
Set the thermostat to lowest setting.
3.
Turn off all electric power to the appliance.
4.
This appliance is equipped with an ignition device which
automatically lights the burner. Do not attempt to light
pilot by hand.
5.
Remove burner access panel.
Figure 11 - Gas Control Knob
INLET
GAS CONTROL KNOB
SHOWN IN "ON" POSITION
6.
Depress gas control knob slightly and turn clockwise
to “OFF” position.
7.
Wait fi ve (5) minutes to clear out any gas. If you then
smell gas STOP! Follow WHAT TO DO IF YOU SMELL
GAS. If you don’t smell gas, go to next step.
8.
Turn gas control knob counterclockwise to “ON.”
9.
Turn on all electric power to the appliance.
10.
Set thermostat to desired setting.
11.
After visually inspecting the fl ame, replace lower front
panel.
12.
If appliance will not operate after several tries, turn gas
control knob to “OFF” and call your service technician
or gas supplier.
ON
OFF
• Do not try to light any appliance.
• Do not touch any electrical switches; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fi re
department.
To Turn Off Gas To The Appliance
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance if servicing is
to be performed.
3.
Depress gas control knob slightly and turn clockwise
to “OFF” position. Do not force.
20
CHECKING AND ADJUSTING
Gas Valve Safety Shutdown Test
!
WARNING
Figure 12 - Automatic Gas Valve
Electrical shock hazard. Follow instructions to turn
off electric power. Failure to do so could result in
death or serious injury.
Ignition system safety shutoff device must be tested after
placing boiler in operation.
With main burners fi ring, disconnect ignition cable from
intermittent pilot control box. Gas valve should shut off
main burners. TURN OFF ELECTRIC POWER to boiler before
reconnecting ignition cable, to prevent electric shock.
Adjust Pilot Burner
1.
Remove screw cover over pilot adjusting screw.
2.
Insert small screwdriver and adjust fl ame as needed
See
Figure 12 & 13
to increase fl ame, clockwise to decrease.
Main Burner(S)
Main burners do not require primary air adjustment and are
not equipped with primary air shutters.
Main burner fl ames form sharp blue inner cones in softer
blue outer mantel, with no yellow. Puffs of air from blowing on fl ame or stamping on fl oor will cause fl ames to turn
orange momentarily. This is not unusual. Remain still when
observing main burner fl ames. See
If fl ame appearance is not correct, check main burner
orifi ces, burner throat and fl ame ports for dust and lint
obstruction. It may be necessary to remove rollout shield
to observe main burner fl ames. Replace rollout shield after
observation.
. Turn screw counterclockwise
Figure 14, Page 22
.
Figure 13 - Pilot Flame Adjustment
Adjust Limit Controls
Instructions for each control are included with the controls.
Recommended Boiler Water Temperatures
Settings can be changed after you have had some idea how
the system works. Example:If your system does not give
enough heat in very cold weather, you can raise limit setting
to 190°F.
21
CHECKING AND ADJUSTING
Figure 14 - Main Burner Flame
Main burner fl ame should form sharp blue inner mantel
with no yellow.
Adjust Thermostat Heat Anticipator
Instruction for fi nal adjustment of thermostat are packaged
with thermostat.
1.
Set Heat anticipator at .2.
2.
Check thermostat operation. When set above
temperature indicated on thermometer, boiler burners
should ignite. Verify thermostat turns off boiler when
room temperature reaches selected setting and starts
boiler operating when room temperature falls few
degrees. After setting limit control to desired setting,
check to see if it shuts off gas supply to burners.
3.
Turn your thermostat up to call for heat and let your
boiler run until temperature of water reaches limit
setting. Gas valve shuts off and circulator keeps
running until thermostat is satisfi ed, or water cools
enough to restart burners through limit control.
4.
To check operation of contacts in pressure switch,
disconnect rubber tubing (located between blower and
pressure switch) from pressure switch, while boiler
is operating. Burners extinguish and blower keeps
running. When tubing is reconnected to pressure
switch, ignition sequence begins, resulting in ignition of
main burners.
5.
Set thermostat for desired temperature.
Safe lighting and other performance criteria were met with
gas manifold and control assembly provided on boiler when
boiler underwent tests specifi ed in ANSI Z21.13.
22
MAINTAINING YOUR BOILER
Burners
Beginning of heating season visually check pilot and main
burner fl ames. See
Safety Relief Valve
Test safety relief valve for proper operation. Refer to valve
manufacturer’s instructions packaged with relief valve.
Expansion Tank (Non-diaphragm)
Tank may become waterlogged, or may receive excess
of air. Frequent automatic opening of safety relief
valve indicates water logging. High boiler temperature
accompanied by unusually low radiation unit temperature
(and “knocking”) indicates excess air in tank.
To correct:
1.
Close valve between boiler and tank. Drain tank until
empty.
2.
Check all tank plugs and fi ttings. Tighten as necessary.
3.
Open valve between boiler and tank. Water will rise to
normal height in tank if you have automatic fi ll valve
(otherwise, manually refi ll system).
Boiler Flue Passages
Recommend following checked annually by qualifi ed service
agent.
• fl ue passages
• burner adjustment
• operation of controls
Before start of each season (or whenever system has been
shut down for some time) recheck whole system for leaks
and recheck boiler and vent pipe for leaks. Replace or patch
any boiler seals that are faulty. Before start of each season
(or whenever system has been shut down for some time)
recheck the whole system for leaks . . . and recheck the
boiler and vent pipe for leaks. Replace or patch any boiler
seals that are faulty.
Figures 13, and 14
.
Cleaning Your Boiler And Burners
Flue passages between sections should be examined yearly
and cleaned if necessary.
To clean:
• Remove burners, pilot, and vent pipe.
• Remove top and front jacket panels.
• Remove two screws attaching intermediate front panel
to left and right side jacket panels.
• Remove control panel.
• Remove draft diverter and intermediate front panel.
• Carefully remove cerafelt gasket strips.
• Clean passageways between sections with fl exible
handle wire brush. Remove dirt from bottom of boiler
and from between sections by vacuuming.
• Verify all fl ame ports in burners are open and clear.
Shake out or blow out all loose dirt in burners.
• Reseal seams between adjacent sections as necessary
with 400
• Reassemble all parts.
• Verify tightness of pilot connections and condition of
burner fl ames after reassembly. See Figures 13 and 14.
• Verify vent pipe connections to chimney are secure and
no obstructions are present.
Blower
Blower motor features permanently lubricated ball bearing
construction. Lubrication is not required.
Circulator Pump Isolation Valves
Operate isolation valves in circulator pump fl anges
manually once or twice per year to prevent valves from
becoming stuck in open position
Rotate valves from open position to closed position and
back to open position.
°
F RTV silicone sealant.
Vent Pipe
Venting and piping should be checked at least monthly. If
vent piping shows any sign of leaking, replace immediately.
Water System
If system is to remain out of service during freezing
weather, always drain it completely (water left in to freeze
will crack pipes and/or boiler).
Low Water Cutoff(s)
Inspect fi eld sourced low water cutoffs annually or
as recommended by low water cutoff manufacturer.
Flush fl oat type low water cutoff(s) per manufacturer’s
instructions.
Housekeeping
• Keep boiler area clear and free from combustible
materials, gasoline and other fl ammable vapors and
liquids.
• Keep boiler area clear of debris and other materials
obstructing fl ow of combustion and ventilation air.
23
SERVICE HINTS
!
You may avoid inconvenience and service calls by checking these points before you call for service:
!
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fi re
department.
IF YOUR SYSTEM IS NOT HEATING OR NOT GIVING ENOUGH HEAT . . .
POSSIBLE CAUSEWHAT TO DO
Thermostat is not set correctlyReset thermostat
Check fl ame. If it is yellow, the burner is not getting enough air. Or, if
Burner is not operating properly
fl ame is blue and noisy and seems to lift off the burner, the burner is
getting too much air. Contact your service agency.
No electric power to boiler
Controls out of adjustment Reset according to instructions.
Radiators not heating
Circulating pump not runningCheck over-current protection. Check relay operation.
Poor electrical contactCheck all control terminals and wire joints.
Chimney fl ue is blocked
Rollout switch blown
Check over-current protection. Check to be sure electric power supply
circuit is “ON”.
Open radiator vents to excess air. Check fl ow control valve (if used). It
may be in closed position.
Pressure switch will not close and pilot spark will not operate to start
pilot. Have your service technician check and correct, if necessary.
Have your service technician check heat exchanger for blockage. Replace
rollout switch with exact replacement.
IF BURNER IS NOISY . . .
POSSIBLE CAUSEWHAT TO DO
Gas input amount is incorrectContact your service technician.
RELIEF VALVE LEAKING . . .
POSSIBLE CAUSEWHAT TO DO
Dirt on seat Open valve manually. Allow water to run and clear valve seat.
Water logged expansion tankDrain tank, see manufacurer instructions.
HAVE YOUR SERVICE AGENCY CHECK ANY PROBLEM YOU
ARE UNABLE TO CORRECT.
24
EQUIPMENT & OPTIONAL ACCESSORIES
!
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
AIR ELIMINATING FITTING (AIR PURGER)
Air purger is used to remove excess air from system. It
is installed in supply line. It will eliminate air from water
before it reaches radiators and bleed off this air.
Install discharge piping per these instructions.
SAFETY RELIEF VALVE
Safety relief valve is required on your boiler. Water expands
as it is heated. If there is no place for water to expand
into, water pressure will build up inside boiler and system.
Should this happen, safety relief valve will automatically
open at predetermined pressure. This will relieve the strain
on boiler and system. Run pipe from relief valve outlet
(pipe must be same size as outlet and open end must not
be threaded) to open drain, tub or sink, or other suitable
drainage point not subject to freezing. Failure to do so may
cause water damage or injury should safety relief valve
release.
EXPANSION TANK
Expanding water fl ows into expansion tank. Tank should
be correct size. Tank is fi lled with air. As water expands it
compresses air in the tank to form air pressure cushion.
This “spring-like” cushion serves to maintain correct
operating water pressure regardless of water temperature.
This assures “full measure” of water, even in highest
radiation unit of system. It also prevents blowing off of
safety relief valve. Air in tank in beginning (with system
fi lled with cold water) is suffi cient for proper operation.
Tank also serves as trap for excess air in system. Air
would cause gurgling in pipes and in effi cient circulation in
radiators if left in system.
It is possible for tank to become “waterlogged” (fi lled
with water). It can also become overfi lled with air. This
can happen after fi lling system with new water. Fittings
provided on tank and in line to tank are for bleeding off
excess water or air.
When installing this tank, it is important:
1.
Tank be higher than boiler top.
2.
Pipe to tank continuously rises up to tank (so air
can “bubble” up to it).
DIAPHRAGM TYPE EXPANSION TANK
Diaphragm type expansion tank takes place of conventional
expansion tank. Carefully read instructions packed with
your tank assembly.
Tank comes with 10-12 pounds per square inch air charge.
This is the same as pressure produced in system by
automatic fi ll valve. When system is fi rst fi lled, tank will
contain little or no water.
As water is heated its pressure increases. It expands into
tank, compressing air in tank. Compressed air cushion
permits water in system to expand as temperature
changes. Diaphragm type tank can be mounted on air
purger fi tting or at any convenient place in supply or return
line.
MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR
DIAPHRAGM TYPE EXPANSION TANK
Before system is fi lled with water, there is air in pipes and
radiation units. Some of it will be trapped as system is
fi lled . It is possible to eliminate most of this air through
air vent on radiation units. Main air vent will speed and
simplify this. Install on highest point in supply main when
all radiation is below top of boiler.
AUTOMATIC FILL VALVE
For a safe, effi cient operation, hot water system must be completely fi lled with water. Adding new water, when
needed can be done manually (by use of hand valve in
water supply line). Requires regular attention to system’s
needs. Automatic fi ll valve accomplishes this without
attention. Install in supply line on hot water boilers only.
Valve operates through water pressure differentials. It does
not require electrical connection.
DRAIN VALVE
Manual valve provides means of draining all water from
boiler and system. It is often installed in 3/4” tapping at
bottom of end boiler section. Or it can be installed in tee
where return line enters boiler.
WATER TEMPERATURE CONTROL
Water temperature limit control in relay is adjustable
and may be set as necessary. It may be set as low as
140°F, or as high as 220°F. This depends on type and
amount of radiation involved and weather conditions.
CIRCULATING PUMP
Every forced hot-water system requires circulating pump.
Separate pump or zone valve is required for each zone,
if you have a two or more zone system. Pump must have
capacity to provide circulation required by your system.
Pump is connected into main just ahead of boiler. It is also
wired to electrical system.
BLOWER (Draft Inducer)
Blower provides means for pulling air through boiler and
exhausting fl ue gasses into vent system. Blower shuts
off when burners are not fi ring. This keeps heat in house
rather than having it go up chimney.
25
EQUIPMENT & OPTIONAL ACCESSORIES
PRESSURE SWITCH
Air pressure switch works on negative pressure. When
blower comes on air pressure switch operates intermittent
pilot and gas valve. Air pressure switch is factory set and
will only work when blower operates properly. It will not
allow boiler to come on if blower does not generate enough
pressure or if venting system is blocked.
Factory Pressure Switch Set point:
-0.4” wc. for 2-5 section boilers.
-0.5” w.c. for 6-7 section boilers.
ROLLOUT SWITCH
(FLAME ROLLOUT SAFETY SHUTOFF)
Rollout switch is temperature-sensitive fuse link device.
Located on boiler base just outside fi re box. In event of
heat exchanger fl ueway blockage causing fl ame to roll
out of fi re box, fuse does not change in appearance when
blown.
If rollout switch blows, it must be replaced with exact
replacement. Check heat exchanger fl ueways for blockage
when restoring system to operating condition. DO NOT
operate system without rollout switch.
26
APPENDIX A - CONTROL MODULE
A.1 Installation Environment Considerations
!
WARNING
If you do not follow these instructions
exactly, a fi re or explosion may result
causing property damage, personal injury
or loss of life.
• Do not use this appliance if any part has
been under water. Immediately call a qualifi ed
service technician to inspect appliance and to
replace any part of control system and any gas
control which has been under water.
• Do not allow water to drip on controls. Prevent
condensation by allowing air circulation around
module and gas control.
• Do not use corrosive chemicals around or on
module or gas control.
• Install plastic cover.
• Controls can be damaged by excessively high
temperatures. Verify adequate air circulation around
louvers is maintained when installing boiler.
To discourage unauthorized changing of settings, procedure
to enter adjustment mode is required.
To enter adjustment mode, press UP, DOWN, and I buttons
(see Figure 1) simultaneously for three seconds. Press and
release I button until parameter requiring adjustment is
displayed:
о “SP_” Setpoint (180 °F default setting; adjustable
between 130 and 220 °F)
о “Df_” Setpoint Differential (15 °F default setting;
adjustable between 10 and 30 °F)
о “°F_” Degrees Fahrenheit
Press UP or DOWN button until parameter has reached
desired value. After 60 seconds without any button inputs,
control automatically returns to READ mode.
A.4 Display
In RUN mode, status items and parameters are viewable.
Example, to display setpoint, control fl ashes “sp” (setpoint)
followed by temperature (i.e., 135), followed by °F or °C.
To read settings, press and release I key to fi nd parameter
of interest.
Example, press and release I until setpoint (sp) is
displayed, followed by three-digit number, i.e., 190,
followed by °F or °C. Press I button again will display (S1T)
Sensor 1 Temperature followed by three-digit number and
corresponding degree designator.
See Display Readout.
• Circulator harness to circulator. Harness comes
plugged into module with Molex® plug.
• Thermostat connection to yellow wires marked TT
using wire nuts.
• Ensure remaining Molex® plug connectors have not
worked loose during transit.
• Check sensing bulb is fully inserted in well and is not
loose.
Figure 15 - Display Readout
27
APPENDIX A - CONTROL MODULE
A.5 Operation
Module continuously monitors boiler water temperature and
fi res or shuts off burner based on this temperature data.
1.
When “Call for Heat” occurs, control enables circulator
and monitors boiler water temperature to determine
whether thermostat can be satisfi ed without fi ring
burners.
Table 1 - Operation State Codes
State
Code
Number
1
2
3
4
6
7
8
9
10
11
12
13
14
15
16
17
IdleStandby - no call for heat
Circulator
Wait for pressure switch
to open
Wait for pressure switch
to close
Pre-purgeSystem is purging before ignition trial; includes Pilot Valve circuit diagnostics.
SparkSystem sparking. Flame is not present
Flame stabilization
RunningSystem is running. Flame signal must be present.
Post-PurgeSystem is purging at end of call for heat
Retry delaySuccessful ignition was not detected, and delay is called before retry.
Recycle delayFlame signal was lost, and delay is called before retry
Wait for pressure switch
to open - failed to close
Wait for pressure switch
to close - failed to open
Soft lock-outSoft lockout duration is one hour, may override with manual reset.
Hard lock-outManual reset is required for hard lockout
Wait for limit to closePossible thermostat call for heat; limit switch is open.
Flame out of sequence
Pilot valve diagnosticsPilot valve circuitry diagnostics during pre-purge.
Current leakage detection
Wait for recovery
Defi nitionExplanation
Heat request present. Boiler temperature suffi ciently high to run circulator pump
only.
Inducer is off. Control waits for pressure switch to open.
Checked at beginning of heat cycle before turning on inducer.
If pressure switch does not open in 60 seconds, control goes to State 11.
Inducer is turned on. Control waits for pressure switch to close.
Checked at beginning of heat cycle after turning on inducer.
If pressure switch does not close in 60 seconds, control goes to State 12
Flame signal is being established. Variation in signal is allowed during this state,
fl ame must be stable at end of period
Inducer is still off. Pressure switch has not opened at beginning of heat cycle.
Alarm is sent, but no lockout occurs
Inducer is on. Pressure switch has not closed at beginning of heat cycle.
Alarm message is sent but no lockout occurs.
Flame signal sensed before trial for ignition. Appropriate alarm is sent.
OR
Flame signal sensed during post purge. Appropriate alarm is sent.
OR
Flame signal present when not expected. Appropriate alarm is sent.
Self check performed at start up, again at beginning of heat cycle, and during
“Wait for Recovery “ State.
Self check performed at start up, again at beginning of heat cycle, and during
“Wait for Recovery “ State
2.
Control determines burner operation is required,
module proceeds to start burner (see state codes list)
and heats water in boiler until setpoint temperature is
achieved or thermostat is satisfi ed. .
3.
Burner is de-activated, ignition module completes heating cycle, returns to idle and waits for temperature to
drop again.
4.
Circulator is turned on throughout “Call for Heat.”
28
APPENDIX A - CONTROL MODULE
A.6 Boiler High Limit Temperature Controller
• When water temperature reaches setpoint, controller
ends heating cycle.
• When water temperature drops below setpoint minus
differential, controller restarts heat cycle to re-heat
boiler water.
• If water temperature exceeds maximum allowed
temperature (220°F or 104°C), controller enters manual
reset lockout state.
• For models having reset capability, press any onboard
button or cycle power to reset.
Figure 16 - Basic Control Algorithm Example
A.7 Troubleshooting
• Following service procedures are provided as general
guide.
• On lockout and retry models, meter readings between
gas control and ignition module must be taken within
trial for ignition period. Once ignition module shuts
off, lockout models must be reset through key buttons
and display. On retry models, wait for retry or reset at
thermostat.
• Check for correct installation and wiring before replacing
any component.
• Control module cannot be repaired. If it malfunctions, it
must be replaced.
• Use only qualifi ed service agent to service ignition
systems.
1.
Perform checkout as fi rst step in troubleshooting.
2.
Check troubleshooting guide to pinpoint cause of
problem. See Table 2, page 30.
3.
If troubleshooting indicates ignition problem, see
Ignition System Checks to isolate and correct the
problem.
4.
Perform checkout procedure following troubleshooting
guide again to verify system is operating normally.
A.8 Troubleshooting Error Codes
Integrated boiler control uses advanced diagnostic
capability to assist in troubleshooting error conditions.
Table 2 shows codes that could arise on integrated display
during fault.
Suggestions are provided in Table 8 for servicing these
potential errors.
29
APPENDIX A - CONTROL MODULE
Table 2 - Troubleshooting Error Codes
Error
Code
Number
2
4Flame current too low. Check for fl ame.Non critical alarm
6
18Gas valve relays welded. Five consecutive soft lockouts.Hard lockout
23
24Flame sensed during postpurge (after gas valve signaled closed).Soft lockout
29
32
57
58Igniter fl ame rod shorted to burner ground. Repair or replace igniter.Wait for recovery
59Line Voltage error - voltage out of specifi cation high or low (15-37V (44-66Hz))Wait for recovery
60
61
62
63Soft lockout: maximum number of recycles exceeded.Soft lockout
Note: Soft lockout time is 1 hour or manual reset. Hard lockout requires manual reset.
Pressure switch failed to open (stuck closed).
Flame sensed out of normal sequence (before opening or after closing gas valve).
Flame sensed during prepurge ( before gas valve signaled opened).
Pressure switch failed to close (Contacts stuck open)
Sensor 1 error. Temperature sensor in well is not reading correctly.
Verify it is connected to board. Replace if necessary.
Igniter fl ame rod shorted to burner ground
Applies only to thermostats having on-board transformer.
Polarity is wrong in this case.
Thermostat input higher than threshold.
Line voltage unstable - possibly too may heavy loads switching on and off causing
erratic supply voltage.
Soft lockout: maximum number of retries exceeded.
Soft lockout is reset after one hour if alarm reason disappears.
Over temperature error. Sensor measured temperature in excess of maximum
allowable limit.
Defi nitionConsequence
Wait for recovery
Soft lockout
Soft lockout
Wait for recovery
Wait for recovery
Wait for recovery
Wait for recovery
Wait for recovery
Soft lockout
Soft lockout
A.9 Intermittent Pilot
Ignition System Checks
STEP 1: Check ignition cable.
• Verify ignition cable does not run in contact with metal
surfaces.
• Verify only factory supplied Ignition cable (or approved
replacement) is used.
• Verify connections to ignition module and igniter or
igniter-sensor are clean and tight.
• Verify ignition cable provides good electrical continuity.
STEP 2:
Verify ignition system grounding. Nuisance shutdowns are
often caused poor or erratic grounding.
Common ground is required for module and pilot burner/
igniter sensor.
— Check for good metal-to-metal contact between
pilot burner bracket and the main burner.
— Check ground lead from GND (BURNER) terminal
on module to pilot burner. Verify connections are
clean and tight. If wire is damaged or deteriorated,
replace with No. 14-18 gauge, moisture-resistant,
thermoplastic insulated wire with 105°C [221°F]
minimum rating.
— Check ceramic fl ame rod insulator for cracks or
evidence of exposure to extreme heat, which can
permit leakage to ground. Replace pilot burner/igniter
sensor and provide shield if necessary.
— If fl ame rod or bracket is bent out of position, restore
to correct position.
30
APPENDIX A - CONTROL MODULE
STEP 3: Check spark ignition circuit.
Disconnect ignition cable at SPARK terminal on module.
!
WARNING
Electrical shock hazard. Ignition circuit generates
over 10,000 volts. Turn OFF electrical power
supply at service panel before making electrical
connections. Failure to do so could result in death
or serious injury.
Energize module and listen for audible sparking noise.
When operating normally, there should be buzzing noise
turns on and off twice per second for duration of 1–7
seconds, depending on model.
STEP 4: Verify pilot and main burner lightoff.
• Initiate call for heat. Turn thermostat above room
temperature. Ignition sequence may be delayed by
thermal purge until boiler water temperature is below
140°F (60°C)
• Watch pilot burner during ignition sequence.
— Verify ignition spark continues after pilot is lit.
— Verify pilot lights and spark stops, verify main
burner does not light.
• If so, ensure adequate fl ame current as follows.
• Recheck ignition sequence as follows.
— Reconnect main valve wire.
— Adjust thermostat above room temperature.
— Verify ignition sequence at burner.
— If spark does not stop after pilot lights, replace
module.
— If main burner does not light or if main burner lights
and system locks out, check module, ground wire
and gas control as described in troubleshooting Error
Codes. See Table 2 page 30.
Figure 17 - Pilot Flame
— Turn off boiler at circuit breaker or fuse box.
— Clean fl ame rod with emery cloth.
— Verify electrical connections are clean and tight.
Replace damaged wire..
— Check for cracked ceramic insulator, which can
cause short to ground, and replace igniter-sensor if
necessary.
— At gas valve, disconnect main valve wire from MV
terminal.
— Turn on power and set thermostat to call for heat. Pilot
should light, main burner will remain off because main
valve actuator is disconnected.
— Check pilot fl ame. Verify it is blue, steady and
envelops 3/8 to 1/2 in. [10 to 13 mm] of fl ame rod.
Figure 17 for possible fl ame problems and causes.
— If necessary, adjust pilot fl ame by turning pilot
adjustment screw on gas control clockwise to decrease
or counterclockwise to increase pilot fl ame. Following
adjustment, always replace pilot adjustment cover
screw and tighten fi rmly to assure proper gas control
operation. Figure 12, Page 21.
— Set temperature below room set-point to end call for
heat.
Correct Pilot Flame: 3/8 to 1/2 inch in fl ame.
See Figure 13, Page 21.
31
PRODUCT LITERATURE
Lennox Industries Inc.
Dallas, Texas
Manufacturedby:
ECRInternational,Inc.
2201 Dwyer Avenue, Utica NY 13501
web site: www.ecrinternational.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.