This manual contains information pertaining to
GHR32−1 through −6 model units. GHR32 series units
are high−efficiency horizontal or down flow gas furnaces
manufactured with Lennox DuralokPlust aluminized and
stainless steel clamshell-type heat exchangers. GHR32Q
units are available in heating input capacities of 50,000 to
120,000 Btuh (14.7 to 35.2 kW) and cooling applications
from 2 through 5 tons (7.0 through 17.6 kW). GHR32V units
are available in heating capacities of 75,000 and 100,000 Btuh
(22.0 and 29.3 kW) and 3 and 5 tons (10.5 and 17.5) for cooling. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is
available for conversion to LPG operation. GHR32−1
through −4 units are equipped with the Lennox SureLight
silicon nitride ignition system. GHR32−5 units are
equipped with the two stage (V models will have the variable speed control) integrated control board. Each
GHR32 unit meets the California Nitrogen Oxides (NOx)
Standards and California Seasonal Efficiency requirements. The gas valve is redundant to assure safety
shut−off as required by A.G.A. and C.G.A.
The heat exchanger, burners and manifold assembly can be
removed for inspection and service. The maintenance section
gives a detailed description on how this is done.
Information contained in this manual is intended for
use by qualified service technicians only. All specifica-
tions are subject to change. Procedures outlined in this
manual are presented as a recommendation only and do
not supersede or replace local or state codes.
LPG/Propane kit59L81 (−1 and −2 models) 11M57 (−3 and later models)
Down-Flow Additive Base32K5232K53
Horizontal Support Frame Kit Ship. Wt. − lbs. (kg.)56J18 18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits60G77 − For 1 1/2 inch (38 mm) venting
Roof
Vent/
Intake
Kits
Twinning Kit15L38 (all models)
Condensate Drain Heat Cable26K68 6 ft. (1.8 m) 26K69 24 ft. (7.3 m) 26K70 50 ft. (15.2 m)
Heat Cable Tape39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Determine from venting tables proper intake and exhaust pipe size and termination kit required.
Cleanable polyurethane frame type filter.
For 3 inch (76 mm) ventingNot Available44J40 (close couple) 81J20 (WTK close couple)
ple)
33K97 − For 2 inch
(51 mm) venting
60L46 − For 3 inch
(76 mm) venting
Not Available
HIGH ALTITUDE
No gas pressure adjustment is needed when operating from 0 to 4500 ft. (0 to 1372m). See table below for correct manifold
pressure and prove switch for altitudes greater than 4500 ft. (1372m).
Horizontal Support Frame Kit Ship. Wt. − lbs. (kg.)56J18 18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits60G77 − For 1 1/2 inch (38 mm) venting33K97 − For 2 inch (51 mm) venting
Roof
Termination
Vent/
Intake
Kits
Condensate Drain Heat Cable26K68 6 ft. (1.8 m) 26K69 24 ft. (7.3 m) 26K70 50 ft. (15.2 m)
Heat Cable Tape39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Determine from venting tables proper intake and exhaust pipe size and termination kit required.
Cleanable polyurethane frame type filter.
Kits
Wall
Termination
Kits
For 2 inch (51 mm) venting15F75
For 3 inch (76 mm) venting44J41
15F74 (ring kit)
For 2 inch (51 mm) venting
30G79 (WTKX close couple w/ extension riser)
For 3 inch (76 mm) venting44J40 (close couple) 81J20 (WTK close couple)
22G44 (close couple)
30G28 (WTK Close Couple)
22G44 (close couple)
Page 4
15F74 (ring kit)
Page 5
BLOWER PERFORMANCE DATA −1 through −3 V MODELS
p
Jumper
g
g
Setting
ADJUST
Jumper
s
Positions
ADJUST
Jumper
s
Positions
GHR32V3-75 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 875 cfm (415 L/s) for all positions.
GHR32V5−100 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP3−1 Blower Control Factory SettingsADJUST − NORM
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 1100 cfm (520 L/s) for all positions.
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
Heat Speed 3
VSP Jumper Speed Positions
HIGH" Speed (Cool)HEAT" Speed
106
0
500
107
505 113 0 535
0
127
105
0
5
129
600
0
500 112 0 530 940 445 995 470
610
109
515 117 5 555
0
Heat Speed 1
VSP Jumper Speed Positions
BLOWER PERFORMANCE DATA −4 V MODELS
Heat Speed − 3
Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low SpeedHigh Speed
COOL"
Low SpeedHigh Speed
Heat Speed − 2
Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low SpeedHigh Speed
COOL"
Low SpeedHigh Speed
Page 5
128
605
5
109
515 118 0 555
5
133
630
0
Page 6
GHR32V3−75−5 Blower Motor Performance
Adjust
Jumper
g
Adjust"
Jumper
g
Adj
"
Jumper
Jumper
g
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 875
cfm (415 L/s) for all positions.
Heating
GHR32V5−100/125−5 Blower Motor Performance
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
NOTE − The effect of static pressure and filter resistance is included in air volumes shown.
NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable.
NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 1100
cfm (520 L/s) for all positions.
Heating
Page 6
Page 7
GHR32Q−5 PARTS IDENTIFICATION
(Downflow Application Shown)
CONTROL VOLTAGE
CIRCUIT BREAKER
CONTROL TRANSFORMER
CONTROL BOX COVER
DOOR INTERLOCK SWITCH
COLD END HEADER
(COLLECTOR) BOX
COMBUSTION AIR
BLOWER MOUNTING
COMBUSTION
AIR INDUCER
EXHAUST TEE
PATCH PLATE
WITH BARBED
FITTING
BURNER BOX
COVER
FLAME SIGHT
GLASS
FLAME SENSOR
INTAKE AIR
GASKET
BRACKET
FRESH AIR
INTAKE FITTING
IGNITOR
SURELIGHT TWO−STAGE
INTEGRATED CONTROL
CORBELS
BURNER BOX
TOP
BURNER BOX
ASSEMBLY
ORIFICE
GAS VALVE
AND MANIFOLD
FIGURE 1
SUPPLY AIR
BLOWER
TOP CAP
CONTROL
BOX
GASKET
PRIMARY LIMIT
AUTO−RESET
(ALTERNATE STYLES)
BURNER BOX
GASKET
FLAME ROLL−OUT SWITCH
(MANUAL RESET)
SECONDARY LIMIT
AUTO−RESET
(Located on Backside
of Blower Wrapper)
CABINET
COMBUSTION AIR
PROVING (PRES-
SURE) SWITCH
HOT END HEADER
(COLLECTOR) BOX
CONDENSER
COIL
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
CONDENSATE
TRAP
BACK FILTER
CLIP
FLUE
COLLAR
CONDENSATE
COLLAR
TM
Page 7
Page 8
I−UNIT COMPONENTS
GHR32 unit components are shown in figure 1. The combustion air blower, gas valve and burners can be accessed
by removing the burner access panel. The blower and control box can be accessed by removing the blower access
door.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
WARNING
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch
A−Make-Up Box (Figure 2)
WARNING
Unit must be grounded in accordance with national
and local codes. Electric Shock Hazaed.
Can cause injury or death.
A field make−up box (see figure 2) is provided for line voltage
wiring. Line voltage wiring to unit is done through the J96 jack
from the field make−up box to plug P96 from the control box.
The box may be installed inside or outside the unit (see figures
3 and 4) and may be installed on the unit left or right side.
MAKE-UP BOX
POWER ENTRY KNOCKOUT
BOX
UNIT
GROUND
JACK J96
Box may be installed inside or outside unit.
FIGURE 2
120V LINE VOLTAGE
PIGTAIL CONNECTIONS
COVER
J96
BUSHING
P96
FIGURE 3
EXTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
BUSHING
J96
(Shown with
accessory
wire connected)
P96
FIGURE 4
An accessory (brown) output wire is provided with the makeup box. The wire provides a 120V connection for optional accessories such as electronic air cleaner or humidifier. If
used, the wire is field installed in J96 jack plug by inserting the
pin of the brown wire into the open socket of the jack. See figure 5. 120V accessories rated up to 4 amps total may be connected to this wire. The neutral
leg of the accessory is connected to the neutral white wire
in the make-up box. The acces-
INSTALLING BROWN
ACCESSORY WIRE TO J96
WHITE
NEUTRAL
BROWN
sory terminal is energized
whenever the indoor blower is
in operation.
BLACK
J96
FIGURE 5
Page 8
Page 9
B−Control Box (Figure 6)
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CIRCUIT BREAKER CB8
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s
electronic controls. Precautions will help to avoid
control exposure to electrostatic discharge by
putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all
tools on an unpainted unit surface, such as the
gas valve or blower deck, before performing any
service procedure.
GHR32−1 through −4 CONTROL BOX
TWO−STAGE
CONTROL
CIRCUIT
BREAKER
TRANSFORMER
FIGURE 6
Unit transformer (T1), circuit breaker (CB8), SureLight
control (A92), VSP−2 control (A24) and Two−stage control
(A86) are located in the control box. In addition, a door interlock switch (S51) is located in the control box. Jackplugs
and a snap-off" terminal strip allow the control box to be
easily removed for blower service.
1. Control Transformer (T1)
A transformer located in the control box provides power to
the low voltage 24 volt section of the unit. Transformers on
all models are rated 40VA with a 120V primary and a 24V
secondary.
2. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated 3 amps at 32V. If the current exceeds this limit the breaker will trip and all unit operation will
shut down. The breaker can be manually reset by pressing the
button on the face (figure 7).
VSP−2
CONTROL
(v models only)
SURELIGHT
CONTROL
DOOR INTERLOCK
SWITCH
PRESS TO RESET
FIGURE 7
3.Door Interlock Switch (S51)
A door interlock switch rated 14 amps at 125VAC is located
on the control box. The switch is wired in series with line
voltage. When the blower door is removed the unit will shut
down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
4. SureLight Ignition System A92
All GHR32−1 through −4 units are equipped with the Lennox SureLight ignition system. The system consists of ignitor (figure 8) and ignition control board (figure 9 and
table 3 ). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The SureLight
integrated board controls all major furnace operations.
Table 1 and 2 show jack plug terminal designations. shows
control board terminations. The board also features two
LED lights for troubleshooting and two accessory terminals rated at (1) one amp. See table 4 for troubleshooting
diagnostic codes. Units equipped with the SureLight
board can be used with either electronic or electro−mechanical thermostats without modification. The SureLight
ignitor is made of durable silicon nitride. Ignitor longevity
is also enhanced by voltage ramping by the control board.
The board finds the lowest ignitor temperature which will
successfully light the burner, thus increasing the life of the
ignitor.
NOTE − Do not remove blower access panel to read
Surelight LED lights. A sight glass is provided on the
access panel for viewing.
Page 9
Page 10
13/32’
SURELIGHT IGNITOR
MEASUREMENT IS TO I.D.
5/8"
OF RETENTION RING
FRONT VIEW
TABLE 1
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN #FUNCTION
1Ignitor
2
3
4
Combustion Air Blower Line Voltage
5
6
Combustion Air Blower Neutral
Not Used
Ignitor Neutral
Not Used
TABLE 2
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
5/16"
TOP VIEW
FIGURE 8
SURELIGHT INTEGRATED CONTROL BOARD
GHR32−1 through −4 units
PIN #FUNCTION
1Primary Limit In
2
3
4
5
6
Pressure Switch and Primary Limit Out
7
8
9
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Not Used
Roll Out Switch In
Ground
TABLE 3
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
TERMINAL DESIGNATIONS
Blower − Cooling Speed (Line Volt)
Blower − Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
FIGURE 9
Page 10
Page 11
TABLE 4
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1LED #2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASHON
OFFSLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASHOFF
ONSLOW FLASH
ON
ON
OFF
FAST FLASHSLOW FLASH
SLOW FLASHFAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Limit must close within 3 minutes or board goes
Watchguard pressure switch − 5 minutes. Pressure switch open or has opened 5
times during a single call for heat; OR: Blocked inlet/exhaust vent; OR: Conden-
sate line blocked; OR: Pressure switch closed prior to activation of combustion
Watchguard 60 minute delay − burners fail to ignite.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .61 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
into one hour limit Watchguard.
air blower.
Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.21 microAmps
a−Electronic Ignition Figures 12 and 13
On a call for heat the SureLight control monitors the combustion air blower pressure switch. The control will not begin the heating cycle if the pressure switch is closed (by−
passed). Once the pressure switch is determined to be
open, the combustion air blower is energized. When the
differential in the pressure switch is great enough, the pressure switch closes and a 15−second pre−purge begins. If
the pressure switch is not proven within 2−1/2 minutes, the
control goes into Watchguard−Pressure Switch mode for a
5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. Units with control 97L48: ignitor stays energized during the trial or until flame is
sensed. Units with control 56L83: ignitor stays energized
for the first second of the 4−second trial. If ignition is not
The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
b−Fan Time Control Q Models Only
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 10.
proved during the 4−second period, the control (97L48 or
56L83) will try four more times with an inter purge and
warm−up time between trials of 35 seconds. After a total of
five trials for ignition (including the initial trial), the control
FAN-OFF TIME ADJUSTMENT
60sec.90sec.120sec.180sec.
goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence
again.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 10
Page 11
Page 12
c−Flame Sensor
ЙЙЙЙЙЙЙЙЙ
A flame sensor is located on the left side of the burner support. See figure 11. The sensor is mounted on a bracket in
the burner support and the tip protrudes into the flame envelope of the left−most burner. The sensor is fastened to
burner supports and can be removed for service without removing any part of the burners. During operation, flame is
sensed by current passed through the flame and sensing
electrode. The SureLight control allows the gas valve to remain open as long as flame signal is sensed.
SENSOR
3/8"
IGNITOR
FIGURE 11
NOTE − The GHR32 furnace contains electronic components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
5. Two−Stage Control (A86)
All GHR32−1 through −4 units are equipped with a two−
stage control board. Two different boards have been used.
Boards 43K9001 and 29M9201 (figure 14) are identical,
except the 9 pin connector on 43K9001 is replaced by two
relays with quick connect terminals on board 29M9201.
The two−stage board acts as a go between from the indoor
thermostat to the SureLight ignition board. The board can
be utilized in three modes: with a SINGLE−STAGE thermostat, a TWO−STAGE thermostat or with a second−stage
(high fire) delay called W2 TIMED. The two−stage board is
equipped with a jumper (see figure 14) which changes operating modes and a jumper which adjusts second−stage
heat delay during W2 TIMED mode.
NOTE−The mode of operation jumper on the two−stage
control board is factory set in the TWO−STAGE" position.
While in the single−stage thermostat mode (one−stage
jumper setting), the unit will always operate on second−
stage heat. The combustion air blower (B6) will operate on
high speed and indoor blower (B3) will operate on heating
speed. While in the two−stage thermostat mode the unit will
operate on first−stage heat (low fire). The combustion air
blower (B6) and indoor blower will operate on low speed.
The unit will switch to second−stage heat (high fire) on call
from the indoor thermostat W2. While in the W2 TIMED
mode (factory setting 8 minutes) the unit will fire on first−
stage heat (low fire) with the combustion air blower (B6)
and indoor blower (B3) operating on low speed. After a set
time delay the unit switches to second−stage heat (high
fire). The combustion air blower and indoor blower also
switch to second−stage heat mode.
SureLight Control Ignition Sequence Board 56L8301
15
ON
OFF
DEMAND
CAB
IGNITOR
GAS VALVE
INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −PurgeIgnitor WarmupTrial for
341
35
Ignition
38
Blower On"
Delay
FIGURE 12
SureLight Control Ignition Sequence Board 97L4801
15
ON
OFF
DEMAND
CAB
IGNITOR
GAS VALVE
INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −PurgeIgnitor Warmup
341
Trial for
Ignition
38
Blower On"
Delay
FIGURE 13
5 SEC80
Post
Purge
5 SEC80
Post
Purge
Page 12
Page 13
MODE OF
OPERATION
JUMPER
TWO−STAGE CONTROL BOARD
G32(V) −1 through −4 units
W2 TIMED
DELAY JUMPER
6.VSP2−1 Blower Control Board (A24)
−1 through −3 V Models only
GHR32V−1 through −3 units are equipped with a variable
speed motor that is capable of maintaining a specified CFM
throughout the external static range. The unit uses the
VSP2−1 variable speed control board, located in the blower compartment, which controls the blower speed and
provides diagnostic LEDs. The control has a non−adjustable, factory preset ON" fan timing delay and an adjustable
OFF" fan timing delay (see figure 17).
The VSP2−1 also senses limit trip condition and turns on the
blower. The GHR32 primary limit switch is located in the
middle of the vestibule wall and the secondary limit switch is
located int ehblower compartment. When excess heat is
sensed in the heat exchanger, or blower compartment,
the respective switch will open and interrupt the current to
the gas valve, while at the same time the VSP2−1 energizes
the blower on heating speed. The limit automatically resets
when the unit temperature returns to normal and the blower is
de−energized.
FIGURE 14
HIGH SPEED
SELECTOR PINS
(COOLING ONLY)
LOW SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG
(BOARD TO VARIOUS
POINTS IN FURNACE)
Diagnostic LEDs located on the VSP2−1 control board are provided to aid in identifying the unit’s mode of operation. Certain
scenarios will arise depending on the jumper positions. Refer
to figure 15 for identification.
VSP2−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP
2
HIGHLOWADJUSTHEAT
270
1
2
3
4
DS4
CFM
210
90
150
JP
1
1
1
2
3
4
HTG.
BLOWER
12
1
2
3
4
HEAT
DS2
TEST
−
+
NORM
DS3
ON/OFF
HI/LOW
DS1
JP46
13 PIN PLUG
(BOARD TO MOTOR)
HEATING SPEED
SELECTOR PINS
See table 5 for VSP2
factory settings
OPERATIONAL
SELECTOR PINS
(Affects both heating and
cooling modes)
DIAGNOSTIC
DS LEDS
FAN OFF"
TIMING PINS
FIGURE 15
Page 13
Page 14
IMPORTANT
24 VAC half wave rectified (DC pulse), when measured with a meter, may appear as a lower or higher
voltage depending on the make of the meter. Rather
than attempting to measure the output voltage of the
VSP2 board, see GHR32 BLOWER & VSP2 BLOWER
CONTROL BOARD TROUBLESHOOTING FLOW
CHART in the TROUBLESHOOTING section of this
manual.
VSP2−1 BLOWER CONTROL BOARD (A24)
1
J46
HIGHLOWADJUSTHEAT
1
2
3
4
HTG.
BLOWER
1
2
3
4
HEAT
DS3
TEST
−
+
NORM
HI/LOW
1
2
3
4
DS4
Diagnostic LED Lights
a − DS3 ON/OFF"
ON/OFF−DS3 indicates there is a demand for the blower mo-
tor to run. When the ON/OFF LED−DS3 is lit, a demand is being sent to the motor. In heating mode only, there is a 45 second fan ON" delay in energizing ON/OFF LED−DS3.
The light will not go off until adjustable fan OFF" delay
has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1 &
HEAT LED−DS2 are off, the motor will operate in low
speed.
b − DS2 HEAT"
If HEAT LED−DS2 is on, the blower is running in the heat
speed according to the HEAT" jumper setting. The HEAT
LED−DS2 comes on instantaneous and switches off when
the call for heat is satisfied.
NOTE−When the blower is in OFF" delay mode, the motor runs at low speed, therefore the HEAT LED−DS2 is off. It
switches off when the call for heat is satisfied.
c − DS1 HI/LOW"
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control.
PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output.
PIN 13 - 24V - Input 24 VAC power for the VSP2-1.
PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 1 - Heat - Heat speed input signal to the ICM2 motor.
PIN 4 - High Tap - High Speed programming input.
PIN 5 - Low Tap - Low speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 8 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common.
PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
DS1
270
CFM
210
90
150
HIGH/LOW LED−DS1 indicates whether the blower is operating in high or low speed. When the light is off, the blower is running in low speed according to the LOW" jumper
setting. When HIGH/LOW LED−DS1 is on, the blower is op-
erating in high speed according to the HIGH" jumper setting.
d − DS4 CFM"
CFM LED−DS4 indicates the CFM the unit is operating,
according to the jumper settings. The light flashes once
for approximately every 100 CFM. For example, if the unit
is operating at 1000 CFM, CFM LED−DS4 will flash 10
times. If the CFM is 2050, CFM LED−DS4 will flash 20 full
times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes
place when the control is communicating with the motor between cycles. This is normal operation.
The appropriate speed according to application and CFM
need is selected by moving jumper pins.
Page 14
VOLTAGES INTO VSP2−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0 volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage) if CCB
is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP2−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx.
34 volts
0 volts
Voltage across J46 pins 8 and 9 to 3, is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pins 8 and 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
24VAC Half-Rectified (DC Pulse)
a voltage of 0−25VDC should be present.
@ 60Hz.
FIGURE 16
Page 15
NOTE−On Harmony II zoning applications in the heating
mode, the highest speed obtainable is the same as the highest
cooling speed selection. Also, the heating speed (heat jumper
position) is only used when the primary limit has been tripped.
In non−zoning applications, refer to the section on the VSP2−1
control.
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
not operable. Notice in the GHR32V5−100 table, that the
normal adjustment setting for heat speed position #3 is
2150 CFM (1015L/s). After the adjustment setting has been
determined, c hose th e re main ing speed jumper settings
from those offered in the table.
The TEST pin is available to bypass the VSP2−1 control and
run the motor at approximately 70% to test that the moto r i s
operational. This is beneficial primarily in troubleshooting. G must be energized for motor to run.
b−HEATING BLOWER"
IMPORTANT
Before changing jumper setting, make sure the
motor has completely stopped. Any jumper setting change will not take place while the motor
is running.
To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and conditions associated with each one. Refer to figure 15 for identification.
After the CFM for each application has been determined, the
jumper settings must be adjusted to reflect those given in
the tables in the blower performance section. Using the tables,
determine which row of CFM volumes most closely
matches the desired CFM. Once a specific row has been
chosen (NORMAL or −), CFM volumes from other rows
cannot be used. Below are the descriptions of each of the
jumper selections.
Refer to table 5 for factory settings. Refer to the blower performance tables for the approximate air volume for each setting.
VSP2−1 FACTORY SETTINGS
MODELHIGHLOWADJUSTHEAT
GHR32V−75−
1, −2, −3 units
GHR32V−100
−1, −2, −3
units
a−ADJUST"
The ADJUST pins allow the motor to run at normal speed or
approximately 15% lower than normal speed. The blower
performance tables give two rows (NORMAL and −) with
their respective CFM volumes. The + adjustment setting i s
TABLE 5
43NORM2
42NORM1
For GHRV32 units, place the HEATING BLOWER jumper
across the second and third pins (position #2).
When W1 is energized, the LOW jumper selections are activated. The HEAT jumper selections are activated when
W2 is energized.
NOTE−In Harmony II zoning applications, HEATING
BLOWER jumper must be in position #2.
c−HEAT"
The HEAT jumper is used to set the blower speed to ob-
tain the required CFM as outlined in HEAT SPEED in the
blower performance tables.
The HEAT jumper selections are activated with a call for
second-stage heating (W2).
d−HIGH"
The HIGH jumper is used to determine the CFM during
cooling speed. These jumper selections are activated
when G and DS terminals are energized.
e−LOW"
The LOW jumper is used to determine CFM during low
speed cooling. These jumper selections are activated
when G is energized. The LOW jumper may also be used for
low speed heating. See the HEAT" section for details.
f−FAN OFF"
Fan OFF" timings (time that the blower operates after the
heat demand has been satisfied) are determined by the arrangement of a jumper on the VSP2−1 board. See figure
17. To adjust fan OFF" timings, gently disconnect the
jumper and reposition it across pins corresponding with the
new timing. Fan OFF" time is adjustable from 90 to 330
seconds. The control has a non−adjustable, factory preset
on" fan timing (45 seconds).
WARNING − MAKE SURE TO DISCONNECT POWER
BEFORE CHANGING FAN OFF" TIMINGS.
Page 15
Page 16
FAN-OFF TIME ADJUSTMENT
NOTEIf fan OFF" time is too low, residual heat in heat
exchanger may cause primary limit S10 to trip resulting
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from VSP2−1 and select
one of the other pin combinations to
achieve the desired time.
in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Table 6 outlines the operation of the variable speed motor
in relation to specific modes of operation. Some informa-
270
15090
210
Leave jumper off to achieve
330 second fan−off timing.
TIMING PINS (seconds)
Fan-off timing is factory
set at 90 seconds
tion has been repeated from the previous section to provide
an example. Refer to each diagnostic LED or jumper settings
section for more information.
FIGURE 17
TABLE 6
VSP2−1 GHR32−1 through −3 units OPERATION
HEATING MODECOOLING MODE
UNITS WITH
SINGLE−STAGE HEATING
NON−ZONED
APPLICATIONS
Using a single−stage thermostat with
one−stage" heating, the HEAT LED−
DS2 is lit when the thermostat calls for
heat. The ON/OFF LED−DS3 is lit after
110 seconds (65 seconds pre−purge
and 45 seconds fan ON" time) from
the time a call for heat is made. This indicates the blower is operating in heating speed.
Using a single−stage thermostat with
W2 TIMED," and W1 calling, the ON/
OFF LED−DS3 is lit to indicate the
blower is operating on low speed.
When the HEAT LED−DS2 is lit, the
blower is operating in heating speed,
and second−stage (W2) heating is calling.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the zoning system to the terminal strip’s DS
terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the
blower is operating.
NOTE−In Harmony II zoning applications, HTG. BLOWER jumper must be
in position #2.
NOTE: For zone applications with Harmony, remove the wire from the pin #3 of the J73 terminal on the VSP control board, insulate the
end, and secure it to prevent from shorting.
Using a two−stage thermostat with
first−stage (W1) calling, the ON/OFF
LED−DS3 is lit to indicate the blower is
operating in low speed.
When the ON/OFF LED−DS3 and
HEAT LED−DS2 are lit, the blower is
operating in heating speed and second−stage (W2) heating is calling.
HEAT LED−DS2 is lit with a call for heat
from the thermostat. ON/OFF LED−
DS3 is lit after 110 seconds from the
time a call for heat is made.
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the zoning system to the terminal strip’s DS
terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the
blower is operating.
NOTE−In Harmony II zoning applications, HTG. BLOWER jumper must be
in position #2.
UNITS WITH
TWO−STAGE HEATING
NON−ZONED
APPLICATIONS
HARMONY ZONED
APPLICATIONS
UNITS WITH SINGLE−
SPEED COMPRESSOR
NON−ZONED
APPLICATIONS
The terminals DS and Y must be
jumpered together. With a call for
cooling, terminals G, Y and DS on the
unit control board are energized from
the thermostat. HI/LOW LED−DS1
and ON/OFF LED−DS3 are lit to indicate the blower is operating on high
speed.
NOTEY and DS are factory jumpered for single−stage cooling, non−
zoned applications.
NOTEFor low speed during single−
stage cooling remove jumper from Y
to DS.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the
zoning system to the terminal strip’s
DS terminal. HI/LOW LED−DS1 andON/OFF LED−DS3 are lit to indicate
the blower is operating.
UNITS WITH TWO−SPEED
COMPRESSOR
NON−ZONED
APPLICATIONS
The ON/OFF LED−DS3 is lit to indicate
the blower is operating in first stage
cooling. This LED is energized on
when a 24VAC thermostat demand is
supplied to the control (terminal G" on
the control board terminal strip).
In second stage, the ON/OFF LED−
DS3 and HI/LOW LED−DS1 are lit to
indicate the blower is operating on
high speed (24VAC is supplied to the
unit terminal strip Y2 from Y2 on the
thermostat).
NOTE Jumper must be moved from
Y1 to Y2 In two−speed, non−zoned applications.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the
PWM (pulse width modulation) signal
sent from the control center of the zoning system to the terminal strip’s DS
terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the
blower is operating.
Page 16
Page 17
7.VSP3−1 Blower Control Board (A24)
GHR32V−4 Units
GHR32V−4 units are equipped with a variable speed motor
that is capable of maintaining a specified CFM throughout
the external static range. The unit uses the VSP3−1 variable speed control board, located in the blower compartment, which controls the blower speed and provides
diagnostic LEDs. The control has both a non−adjustable,
factory preset ON" fan timing delay and an adjustable OFF"
fan timing delay (see figure 17).
VSP3−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP2
DELAY PROFILE
SELECTOR PINS
(COOLING ONLY)
DELAYCOOLADJUSTHEAT
1
2
3
4
The VSP3−1 also senses limit trip condition and turns on the
blower. The GHR32V limit switch is located in the middle of the
vestibule wall. When excess heat is sensed in the hea t exchanger, the limit switch will open and interrupt the current
to the gas valve, while at the same time the VSP3−1 energizes
the blower on heating speed. The limit automatically resets
when the unit temperature returns to normal and the blower is
de−energized.
Diagnostic LEDs located on the VSP3−1 control board are provided to aid in identifying the unit’s mode of operation. Certain
scenarios will arise depending on the jumper positions. Refer
to figure 18 for identification.
JP46
13 PIN PLUG
(BOARD TO MOTOR)
1
2
3
4
TEST
−
+
NORM
1
2
3
4
HEATING SPEED
SELECTOR PINS
See table 7 for VSP3−1
factory settings
COOL SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG
(BOARD TO VARIOUS
POINTS IN FURNACE)
JP1
1
HTG.
BLOWER
12
HEAT
DS2
ON/OFF
FIGURE 18
DS3
HI/LOW
DS1
270
210
150
DS4
CFM
OPERATIONAL
SELECTOR PINS
(Affects both heating
and cooling modes)
DIAGNOSTIC
DS LEDS
90
FAN OFF"
TIMING PINS
Page 17
Page 18
VSP3−1 BLOWER CONTROL BOARD (A24)
1
J46
DELAYCOOLADJUSTHEAT
1
2
3
4
HTG.
BLOWER
1
2
3
4
HEAT
DS3
TEST
−
+
NORM
HI/LOW
1
2
3
4
DS4
IMPORTANT
24 VAC half wave rectified (DC pulse), when
measured with a meter, may appear as a lower
or higher voltage depending on the make of the
meter. Rather than attempting to measure the
output voltage of A24, see GHR32V BLOWER &
VSP3 BLOWER CONTROL BOARD TROUBLESHOOTING FLOW CHART in the TROUBLESHOOTING section of this manual.
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control.
PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output.
PIN 13 - 24V - Input 24 VAC power for the VSP2-1.
PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 4 - Delay Tap - Delay profile programming input.
PIN 5 - Cooling blower speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor with CCB1 and
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common.
PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
PIN 1 - Not Used.
PIN 8 - NOT USED
HARMONY only
DS1
270
CFM
210
90
150
Diagnostic LED Lights
DS3 ON/OFF
ON/OFF−DS3 indicates there is a demand for the blower
motor to run. When the ON/OFF LED−DS3 is lit, a demand
is being sent to the motor. In heating mode only, there is a
45−second fan ON" delay in energizing ON/OFF LED−
DS3. Light will not go off until adjustable fan OFF" delay
has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1
& HEAT LED−DS2 are off, the motor will operate in low
speed (heating).
DS2 HEAT
If HEAT LED−DS2 is on, the blower is running in second−
stage heat speed according to the HEAT" jumper setting.
In heating mode only, there is a 45 second delay in energizing HEAT LED−DS2. Light will not go off until adjustable fan
OFF" delay has expired.
DS1 HI/LOW
HIGH/LOW LED−DS1 indicates the blower is operating in
the cooling mode.
DS4 CFM
CFM LED−DS4 indicates the CFM the blower is providing,
according to the jumper settings.
VOLTAGES INTO VSP3−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0
volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage)
if CCB is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP3−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx.
34 volts
0
volts
Voltage across J46 pin 9 to 3 is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pin 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
a voltage of 0−25VDC should be present.
24VAC Half-Rectified (DC
FIGURE 19
Pulse)
@ 60Hz.
Page 18
Page 19
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
IMPORTANT
Before changing jumper setting, make sure the
motor has completely stopped. Any jumper setting change will not take place while the motor
is running.
To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and conditions associated with each one. Refer to figure 18 for identification.
After the CFM for each application has been determined, the
jumper settings must be adjusted to reflect those given in
the blower performance tables. Using the tables, determine
which row of CFM volumes most closely matches the
desired CFM. Once a specific row has been chosen
(NORMAL or −), CFM volumes from other rows cannot be
used. Below are the descriptions of each of the jumper
selections.
Refer to table 7 for factory settings.
TABLE 7
VSP FACTORY SETTINGS FOR GHR32V−4 UNITS
MODEL DELAYCOOLADJUST HEAT
GHR32V3−7544NORM3
GHR32V5−10044NORM2
NOTE − In Harmony II zoning applications in the heating mode,
the highest cooling speed selected is the highest blower speed
obtainable. Also, the fan−only speed is used when the primary limit has been tripped. In non−zoning applications, refer to the section
on the VSP3−1 control.
ADJUST
The ADJUST pins allow the motor to run at normal speed
or approximately 15% lower than normal speed. The blower performance tables two rows (NORMAL and −) with their
respective CFM volumes. The + adjustment setting is not
operable. Notice that the normal adjustment setting for
heat speed position #3 is 2150 CFM (1015 L/s) . After the
adjustment setting has been determined, choose the remainder speed jumper settings from those in the table.
The TEST pin is available to bypass the VSP3−1 control and
run the motor at approximately 70% to test that the motor is
operational. This is beneficial primarily in troubleshooting. G
must be energized for motor to run.
HTG. BLOWER
For GHR32V−4 units only, place the HTG. BLOWER jumper across the second and third pins (position #2).
NOTE − In Harmony II zoning applications, HTG. BLOWER
jumper must be in position #2.
HEAT
The HEAT jumper is used to set the blower speed to obtain
the required CFM as outlined in HEAT SPEED section of
the blower performance tables. The HEAT jumper selec-
tions are activated with a call for first−stage heating (W1)
and second−stage heating (W2).
DELAY
The DELAY jumper is used to set the specific motor fan
mode of operation during cooling. Depending on the application, one of four fan options may be chosen by moving
the jumper to the appropriate set of pins.
Options 1, 2, 3, or 4 will have an increased dehumidification
effect on the system. Option 1 will have the least effect and
option 4 will have the greatest effect.
#1 PIN JUMPERED
A − Motor runs at 100% until demand is satisfied.
B − Once demand is met, motor ramps down to off.
AB
100% CFM
COOLING
DEMAND
OFFOFF
#2 PIN JUMPERED
A − Motor runs at 82% for approximately 7−1/2 minutes.
B − If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
C − Once demand is met, motor ramps down to off.
C
OFF
OFF
A
7 1/2 MIN
82%CFM
B
100% CFM
COOLING DEMAND
#3 PIN JUMPERED
A − Motor runs at 50% for 1/2 minute.
B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor ramps down to off.
CD
100% CFM
OFF
OFF
A
1/2 MIN
50% CFM
B
7 1/2 MIN
82% CFM
COOLING DEMAND
Page 19
Page 20
#4 PIN JUMPERED
A − Motor runs at 50% for 1/2 minute.
B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor runs at 50% for 1/2 min-
ute.
E − Motor ramps down to off.
CD
100%
CFM
1/2 MIN
50% CFM
E
OFF
OFF
A
1/2 MIN
50% CFM
B
7 1/2 MIN
82% CFM
COOLING DEMAND
COOL
The cool jumper is used to set the blower speed to obtain
the required CFM as outlined in the blower performance
tables.
VSP Operation
Table 8 outlines the operation of the variable speed motor
in relation to specific modes of operation. See table 9 for
GHR32V with CCB1 and a two speed outdoor unit. Some
information has been repeated from the previous section to
provide an example. Refer to each diagnostic LED or jumper settings section for more information.
Heating ModeCooling Mode
Units With
Single−Stage Heating
Non−Zoned Applications
Using a single−stage thermostat
with "one−stage" heating, the HEAT
LED−DS2 is lit when the thermostat
calls for heat. The ON/OFF LED−
DS3 is lit after 110 seconds (65 seconds prepurge and 45 seconds fan
"ON" time) from the time a call for
heat is made. This indicates the
blower is operating in high speed
heat.
Using a single−stage thermostat
with "W2 TIMED" and W1 calling,
the ON/OFF LED−DS3 is lit to indicate the blower is operating on low
speed heat.
When HEAT LED−DS2 is lit, the
blower is operating in high speed
heat and second−stage (W2) is calling.
Harmony Zoned Applications
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal
strip’s DS terminal. HI/LOW LED−
DS1 and ON/OFF LED−DS3 are lit
to indicate the blower is operating.
Note − In Harmony II zoning applications, HTG BLOWER jumper
must be in position #2.
GHR32V−4 Units with VSP3−1
TABLE 8
Units With
Two−Stage Heating
Non−Zoned Applications
Using a two−stage thermostat with
first−stage (W1) calling, the ON/OFF LED−DS3 is lit to indicate the
blower is operating in low speed
heat.
When the ON/OFF LED−DS3 andHEAT LED−DS2 are lit, the blower
is operating in high speed heat and
second−stage (W2) is calling.
HEAT LED−DS2 is lit with a call for
heat from the thermostat. ON/OFF
LED−DS3 is after 110 seconds from
the time a call for heat is made.
Harmony Zoned Application
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal
strip’s DS terminal. HI/LOW LED−
DS1 and ON/OFF LED−DS3 are lit
to indicate the blower is operating.
Note − In Harmony II zoning applications, HTG BLOWER jumper must
be in position #2.
Units With
Single−speed Compressor
Non−Zoned Applications
Y1−DS and Y1−Y2 must be jumpered together. With a call for cooling, G, Y1, Y2 and DS on the unit
control board are energized from
the thermostat. HI/LOW LED−DS1
and ON/OFF LED−DS3 are lit to indicate a call for cooling.
Note − Y1 to DS and Y1 to Y2 are
factory jumpered for single−stage
cooling, non−zoned applications.
Harmony Zoned Application
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal strip’s DS terminal. HI/LOW
LED−DS1 and ON/OFF LED−DS3
are lit to indicate the blower is operating.
Units With
Two−speed Compressor
Non−Zoned Applications
Y1−DS must be jumpered together.
With a call for single−stage cooling,
G, Y1, and DS on the unit control
board are energized from the Thermostat. With a call for second−stage
cooling, G, Y1, Y2, and DS on the
unit control board are energized
from the thermostat. In both cases,
HI/LOW LED−DS1 and ON/OFF
LED−DS3 are lit to indicate a call for
cooling.
Note − Jumper Y1−Y2 must be removed for units with two−speed
compressor.
Harmony Zoned Application
The blower speed is controlled by
the PWM (pulse width modulation)
signal sent from the control center
of the zoning system to the terminal
strip’s DS terminal. HI/LOW LED−
DS1 and ON/OFF LED−DS3 are lit
to indicate the blower is operating.
NOTE − For zone applications with Harmony, remove the wire from pin #2 and pin #13 of the J49 terminal at the motor and the wire
from pin #3 of the J73 terminal on the VSP control board, insulate the ends and secure to prevent shorting.
Page 20
Page 21
TABLE 9
p
Normal operation
blower speed follow thermostat
removal during 1st
ifi
ill i
,
When humidity demand is satisfied
satisfied during
th
gpp
Call f
idit
g
Call for 1st stage
Call for 2nd stage
Reduced blower speed (dehumidifi-
mostat demand), slide switch is
GHR32V−4 UNITS WITH CCB1 & TWO−SPEED OUTDOOR UNIT OPERATING SEQUENCE
Operating SequenceSystem DemandSystem Response
System
Condition
Step
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
***Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Call for humidity
removal during 1st
stage thermostat
demand
Significant increase
in humidity during
thermostat demand.
Humidity demand
satisfied during
thermostat demand.
or hum
removal during 2nd
stage thermostat
demand
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase
in humidity
Humidity demand
satisfied between
thermostat demands
(unit off cycle).
y
1Y1Acceptable (None)Low
2Y2Acceptable (None)HighHIGH COOL
1Y1Acceptable (None)Low
2Y1
Demand
3
satisfied
4Y1Slightly over setpoint (1)High
1Y1Acceptable (None)Low
2Y1
1Y1Over SetpointHigh
2Y1
3NoneAcceptable (None)OffOff
4Y1Acceptable (None)Low
1Y2Acceptable (None)HighHIGH COOL
2Y2
3Y2Acceptable (None)HighHIGH COOL
1NoneSlightly over setpoint (1)OffOffDehumidification mode (high speed
2Y1Slightly over setpoint (1)Low
1NoneSlightly over setpoint (1)OffOff
2Y2Slightly over setpoint (1)High
1None
2Y1 or Y2
1NoneOver setpoint (1 or more)OffOff
2Y1 or Y2
Change to slightly
over setpoint (1)
Slightly over setpoint (1)OffOff
Change to significantly
over setpoint (2 or more)
Change to Acceptable
(None)
Change to slightly
over setpoint (1)
Significantly over setpoint
(2 or more)
Significantly over
setpoint (2 or more
Change to
acceptable (None)
Low
High
HighHIGH COOL
High
OffOff
High
HighHIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
Compressor demand and indoor
blower s
Dehumidification mode begins with
next thermostat demand, after initial
thermostat demand is satisfied.
If humidity increases significantly
over setpoint, or if slide switch is
moved sign
ately go into dehumidification mode
(in presence of thermostat demand).
When humidity demand is satisfied
blower immediately shifts to the
HIGH COOL CFM in order to hasten
e end of the cycle. Unit can only
shift out of high speed compressor
operation at beginning of next cycle.
Blower immediately changes speed
in response to thermostat demand.
compressor) begins with next ther-
mostat demand after initial demand is
Reduced blower speed (dehumidifi-
cation speed) begins immediately
If humidity increases significantly
over setpoint, or if slide switch is
moved, unit immediately goes into
dehumidification mode (in presence
While unit is not operating (no ther-
mostat demand), slide switch is
moved down and back up. Blower
and compressor operate at high
speed until next thermostat demand.
eed follow thermostat
demand
cantly, u nit w
satisfied.
with thermostat demand
of thermostat demand).
mmedi-
,
Note − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first thermostat heating demand.
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed
indefinitely. To reset, move humidity slide switch all the way down then back up to desired setpoint (with unit running)
** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5.
***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compressor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 21
Page 22
8.Two Stage Integrated Control (A92)
GHR32Q−5 Units
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
All GHR32Q units are equipped with the Lennox two−
stage integrated SureLight control board. The system
consists of a ignition control board (figure 20 with control
terminal designations in tables 12, 13 and 14) and ignitor
(figure 8). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The board controls all major furnace operations. The board features two
LED lights, DS1 and DS2 for troubleshooting. The board
also has two accessory terminals rated at (1) one amp
each. See table 15 for troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heat cycle, SureLight control monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heating cycle
if the first stage prove switch is closed (by−passed). Likewise the control will not begin the second stage heating
cycle if the second stage prove switch is closed and will allow first stage heat only. However if the second stage prove
switch closes during the first stage pre−purge, the control
will still respond to second stage heat. Once the first stage
prove switch is determined to be open, the combustion air
inducer is energized on low (first stage) heat speed. When
the differential in the prove switch is great enough, the
prove switch closes and a 15−second pre−purge begins. If
the switch is not proven within 2−1/2 minutes, the control
goes into Watchguard−Pressure Switch mode for a 5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4−second period, the control will try four more times with
an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure
mode. After a 60−minute reset period, the control will begin
the ignition sequence again.
The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE
thermostat or TWO−STAGE thermostat. The thermostat
selection jumper E20, located just below dip switches 1
through 4 (figure 20), must be positioned for the particular
application. The jumper is factory set on TWO" for use
with a two−stage thermostat with two stage heat. Re−position jumper to SINGLE" for use with a single stage thermostat with two stage heat.
While in the single−stage thermostat mode (single jumper
setting), the burners will always fire on first−stage heat. The
combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a field selectable 10 or 15 minute delay (dip switch 3), the unit will
switch to second stage heat. While in the two−stage thermostat mode (two jumper setting) the burners will fire on
first−stage heat. The combustion air inducer will operate on
low speed and indoor blower will operate on low heat
speed. The unit will switch to second−stage heat on call
from the indoor thermostat. If there is a simultaneous call
for W1 and W2 (first and second stage heat) the unit will fire
on first stage heat and will switch to second stage heat after
30 seconds of operation. See Sequence of Operation flow
charts in the back of this manual for more detail.
Dip Switch Settings
Dip Switches 1 and 2 − Heating Fan off Delay − The fan on
time of 45 seconds is not adjustable. Fan off time (time that
the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches 1 and 2
located on the SureLight integrated control. The unit is
shipped with a factory fan off setting of 90 seconds. Fan off
time will affect comfort and is adjustable to satisfy individual
applications. For customized comfort, monitor the supply
air temperature once the heat demand is satisfied. Note the
supply air temperature at the instant the blower is de−energized. Adjust the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de−
energized. (Longer delay times allow for lower air
temperature, shorter delay times allow for higher air temperature). See table 10 for dip switch settings.
TABLE 10
Heating Fan Off Delay
Delay (Seconds)
60OffOff
90OffOn
120OnOff
180OnOn
Switch 3 − Second Stage Delay (Used with Single−Stage
Thermostat Only) −− This switch is used to determine the
second stage on delay when a single−stage thermostat is
being used. The switch is factory−set in the ON position,
which provides a 10−minute delay before second−stage
heat is initiated. If the switch is toggled to the OFF position,
Switch 1Switch 2
Page 22
Page 23
it will provide a 15−minute delay before second−stage heat
is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE−stage thermostat use.
Switch 4 − Cooling Fan off Delay − The fan on delay time
of 2 seconds is not adjustable. Fan off time (time that the
blower operates after the cool demand has been satisfied)
can be adjusted by flipping dip switch 4. The unit is shipped
with a factory fan off setting of 45 seconds. Fan off time will
affect comfort and is adjustable to satisfy individual applications. See table 11 for cool fan off time settings.
TABLE 11
Cooling Fan Off Delay
Delay (Seconds)Switch 4
2Off
45On
Diagnostic LED’s (DS1 and DS2)
Two diagnostic LED’S are located on the two−stage integrated control board. See figure 20. These light flashes
correspond with the codes detailed in table 15.
Factory Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the
integrated control board terminal strip must be removed for
two−stage cooling.
TABLE 12
Integrated Control Board Terminals
120VAC Neutral
LINELine
XFMRTransformer
EACElectronic Air Cleaner
CIRCIndoor Blower
HUMHumidifier
120VAC Line
HUMHumidifier
XMFRTransformer
LINELine
PARKFor Unused Leads
COOLCooling Speed
EACElectronic Air Cleaner
HI HEATHigh Heat Speed
LO HEATLow Heat, Low Cool and Continuous Fan
Speed
TWO−STAGE INTEGRATED CONTROL BOARD
SWITCHES
SENSOR
FACTORY−
INSTALLED
JUMPER
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH(ES)FUNCTION
1 and 2Blower Off Delay (Heating Mode)
3Second Stage ON Delay (Single−stage t’stat)
4Blower Off Delay (Cooling Mode)
Diagnostic LEDs are labeled DS1 and DS2. See figure 20 for location of diagnostic LEDs.
DS1DS2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASHON
OFFSLOW FLASH
OFFFAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASHOFFFlame sensed without gas valve energized.
ONON
OFFON
FAST FLASHSLOW FLASHMain power polarity reversed. Switch line and neutral.
SLOW FLASHFAST FLASHLow flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation.
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes
or unit goes into 1 hour Watchguard.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;
OR lost flame sense 5 times in one heating cycle;
OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts.
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on
call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Minimum flame sense current = 0.17−0.22 microAmps.
Page 24
Page 25
9.Two Stage Variable Speed Integrated
Control (A92) GHR32V−5 Units
All GHR32V−5 units are equipped with the Lennox two−
stage, variable speed integrated SureLight control board.
The system consists of a ignition / blower control board
(figure 21 with control terminal designations in tables 16
through 19) and ignitor (figure 8). The board and ignitor
work in combination to ensure furnace ignition and ignitor
durability. The SureLight integrated board controls all major furnace operations. The board features two LED lights,
DS1 and DS2 for troubleshooting and four LED lights
(DS3, DS6, DS7 and DS8) to show furnace status. The
board also has two accessory terminals rated at (1) one
amp each. See table 20 for status code and table 21 for
troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heating cycle, the SureLight control monitors the first stage and second stage combustion
air inducer prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by−
passed). Likewise the control will not begin the second
stage heating cycle if the second stage prove switch is
closed, and will allow first stage heat only. However if the
second stage prove switch closes during the first stage pre−
purge, the control WILL respond to second stage heat call.
Once the first stage prove switch is determined to be open,
the combustion air inducer is energized on low (first stage)
heat speed. When the differential in the prove switch is
great enough, the prove switch closes and a 15−second
pre−purge begins. If the switch is not proven within 2−1/2
minutes, the control goes into Watchguard−Pressure
Switch mode for a 5−minute re−set period.
After the 15−second pre−purge period, the SureLight ignitor
warms up for 20 seconds after which the gas valve opens
for a 4−second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4−second period, the control will try four more times with
an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure
mode. After a 60−minute reset period, the control will begin
the ignition sequence again.
The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the
SureLight control utilizes less power to energize the ignitor
on successive calls for heat. The control continues to ramp
down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition. This
amount of power is used for 255 cycles. On the 256th call
for heat, the control will again ramp down until the lowest
power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE
thermostat or TWO−STAGE thermostat. The thermostat
selection jumper E20, located just below dip switches 1
through 3 (figure 21), must be positioned for the particular
application. The jumper is factory set on TWO" for use
with a two−stage thermostat with two stage heat. Re−position jumper to SINGLE" for use with a single stage thermostat with two stage heat.
While in the single−stage thermostat mode (single jumper
setting), the burners will always fire on first−stage heat. The
combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. After a field selectable 10 or 15 minute delay (dip switch 3), the unit will
switch to second stage heat. While in the two−stage thermostat mode (two jumper setting) the burners will fire on
first−stage heat. The combustion air inducer will operate on
low speed and indoor blower will operate on low heat
speed. The unit will switch to second−stage heat on call
from the indoor thermostat. If there is a simultaneous call
for W1 and W2 (first and second stage heat) the unit will fire
on first stage heat and switch to second stage heat after 30
seconds of operation. See Sequence of Operation flow
charts in the back of this manual for more detail.
TABLE 16
Two Stage Ignition / Blower Control Terminals
120VAC Neutral
LINELine 120VAC Neutral
XFMRTransformer 120VAC Neutral
EACElectronic Air Cleaner 120VAC Neutral
CIRCIndoor Blower 120VAC Neutral
HUMHumidifier 120VAC Neutral
120VAC Line
HUMHumidifier 120VAC Hot
XMFRTransformer 120VAC Hot
LINELine 120VAC Hot
CIRCIndoor Blower 120VAC Hot
EACElectronic Air Cleaner 120VAC Hot
TABLE 17
SureLight Board 5 Pin Terminal Designation
PIN #Function
1Ignitor
2Combustion Air Inducer High Speed
3Combustion Air Inducer Low Speed
4Combustion Air Inducer Neutral
5Ignitor Neutral
Page 25
Page 26
TW0−STAGE, VARIABLE SPEED INTEGRATED
CONTROL BOARD
DIAGNOSTIC
LEDs
LEDs
DS8
DS7
ON−BOARD
JUMPER W914
(cut when CCB1 or
Harmony II are used)
FACTORY−
INSTALLED
DS3
JUMPER
16 PIN BLOWER
CONTROL TERMINALS
(cut when heat pump
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH FUNCTIONS
DIP SWITCH(ES)FUNCTION
1 and 2Blower Off Delay
3Second Stage ON Delay (Single−stage t’stat)
4Not used
5 and 6Cooling Mode Blower Speed
7 and 8Blower Speed Adjustment
DS3−ON indicates that the motor has a demand to operate. (This LED must be on in all
modes).
DS6−blinking indicates the airflow (CFM) demand in the motor. The air flow is determined by
counting blinks between two (2) second pauses. One blink equals roughly 100 CFM.
DS7−ON indicaties the DS to R" jumper has not been cut. When the jumper is cut the system
will be operating with LENNOX HARMONY IIt (See Harmony Installation Instructions) or
with the CCB1 Efficiency Plus control.
CCB1: When ON, a 24 VAC is being applied and when OFF, it has been removed. This on/off
operation varies the indoor blower’s performance so dehumidification can be enhanced.
TABLE 21
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 21 for location of diagnostic LEDs.
DS1DS2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASHON
OFFSLOW FLASH
OFFFAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASHOFFFlame sensed without gas valve energized.
ONON
OFFON
FAST FLASHSLOW FLASHMain power polarity reversed. Switch line and neutral.
SLOW FLASHFAST FLASHLow flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation.
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes
or unit goes into 1 hour Watchguard.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open;
OR: Blocked inlet/exhaust vent;
OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes;
OR lost flame sense 5 times in one heating cycle;
OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts.
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on
call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Minimum flame sense current = 0.17−0.22 microAmps.
Page 27
Page 28
Dip Switch Settings
Switches 1 and 2 − Blower Off Delay The blower−on delay
of 45 seconds is not adjustable. The blower−off delay (time
that the blower operates after the heating demand has
been satisfied) can be adjusted by moving switches 1 and 2
on the integrated control board. The unit is shipped from
the factory with a blower−off delay of 90 seconds. The
blower off delay affects comfort and is adjustable to satisfy
individual applications. Adjust the blower off delay to
achieve a supply air temperature between 90° and 110°F at
the exact moment that the blower is de−energized. Longer
off delay settings provide lower supply air temperatures;
shorter settings provide higher supply air temperatures.The table below provides the blower off timings that will
result from different switch settings.
TABLE 22
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 1Switch 2
60OffOff
90OffOn
120OnOff
180OnOn
Switch 3 − Second Stage Delay (Used with Single−Stage
Thermostat Only) This switch is used to determine the
second stage on delay when a single−stage thermostat is
being used. The switch is factory−set in the ON position,
which provides a 10−minute delay before second−stage
heat is initiated. If the switch is toggled to the OFF position,
it will provide a 15−minute delay before second−stage heat
is initiated. This switch is only activated when the thermostat selector jumper is positioned for SINGLE−stage thermostat use.
Switch 4 − Not used
Switches 5 and 6 − Cooling Mode Blower Speed
Switches 5 and 6 are used to select cooling blower motor
speed. The unit is shipped from the factory with the dip
switches positioned for high speed (4) indoor blower motor
operation during the cooling mode. The table below provides the cooling mode blower speeds that will result from
different switch settings. Refer to blower data tables at the
front of this manual for corresponding cfm values.
Cooling Mode Blower Speeds
TABLE 23
SpeedSwitch 5Switch 6
1 − LowOnOn
2 − Medium LowOffOn
3 − Medium HighOnOff
4 − High (Factory)OffOff
Switches 7 and 8 − Blower Speed Adjustment Switches
7 and 8 are used to select blower speed adjustment settings. The unit is shipped from the factory with the dip
switches positioned for NORMAL (no) adjustment. The dip
switches may be positioned to adjust the blower speed by
+10% or −10% to better suit the application. The table below provides blower speed adjustments that will result from
different switch settings. Refer to blower data tables at the
front of this manual for corresponding cfm values.
TABLE 24
Blower Speed Adjustment
AdjustmentSwitch 7Switch 8
+10% (approx.)OnOff
NORMAL (Factory)OffOff
−10% (approx.)OffOn
Switches 9 and 10 − Cooling Mode Blower Speed
Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramping may be used to enhance dehumidification performance. The switches are factory set at option A which has
the greatest effect on blower motor performance. The table
below provides the cooling mode blower speed ramping
options that will result from different switch settings. The
cooling mode blower speed ramping options are detailed
on the next page. See unit nameplate for manufacturing
date.
TABLE 25
Cooling Mode Blower Speed Ramping
Ramping OptionSwitch 9Switch 10
A (Factory)OffOff
BOnOff
COffOn
D*OnOn
*Only option for CCB1
Page 28
Page 29
GHR32V units manufactured before April 2003
Ramping Option A (Factory Selection)
D Motor runs at 50% for 1/2 minute.
D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 1/2 min-
ute.
D Motor ramps down to off.
GHR32V units manufactured April 2003 and later
Ramping Option A (Factory Selection)
S Motor runs at 50% for 30 seconds.
S Motor then runs at 82% for approximately 7−1/2 min-
utes. If demand has not been satisfied after 7−1/2 minutes.
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 50% for 30 sec-
onds then −
S ramps down to stop.
OFF
1/2 MIN
50% CFM
7−1/2 MIN
82% CFM
COOLING DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
D Motor runs at 50% for 1/2 minute.
D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
1/2 MIN
50% CFM
7−1/2 MIN
82% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
D Motor runs at 82% for approximately 7−1/2 minutes.
D If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
7−1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
OFF
1/2 MIN
50% CFM
7 1/2 MIN
82% CFM
COOLING DEMAND
100%
CFM
1/2 MIN
50% CFM
OFF
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes −
S motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 60 sec-
onds. Then,
S ramps down to stop.
OFF
100% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option D
D Motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
100% CFM
COOLING
DEMAND
Ramping Option D
S− Motor runs at 100% until demand is satisfied.
S− Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING
DEMAND
OFFOFF
Page 29
Page 30
Switches 11 and 12 − Heating Mode Blower Speed
idi
Dehumidification mode begins when rela
satisfied between
d
lid
d
Switches 11 and 12 are used to select heating mode blower
motor speed. The unit is shipped from the factory with the
dip switches positioned for medium low (2) speed indoor
blower motor operation during the heating mode. The table
below provides the heating mode blower speeds that will
result from different switch settings. Refer to blower data
tables at the front of this manual for corresponding cfm values.
TABLE 26
Heating Mode Blower Speeds
SpeedSwitch 11Switch 12
1 − LowOnOn
2 − Medium Low
(Factory)
OffOn
3 − Medium HighOnOff
4 − HighOffOff
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and
R on the integrated control board, must be cut when the furnace is installed with either the Harmony II zone control
board or the CCB1 EfficiencyPlus humidity control. Refer to
table 27 for operation sequence in applications including a
GHR32V, CCB1 and single−speed outdoor unit. Table 28
gives the operation sequence in applications with a two−
speed outdoor unit.
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O
on the integrated control board, must be cut when the furnace is installed in applications which include a heat pump
unit and the FM21 FuelMaster control board.
Factory−Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the
integrated control board terminal strip must be removed if
two−stage cooling will be used.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two−stage, variable speed integrated control just to the left of the first bank
of dip switches. These lights’ flashes correspond with diagnostic codes detailed on in table 15.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate
operating status. The green ON/OFF LED is lit any time the
blower is operating. The green CFM LED indicates the
blower motor speed. Count the number of blinks between
the two−second pauses to determine the CFM. Each blink
represents approximately 100 CFM. The yellow HI/LO LED
is lit when the W914 (DS to R) jumper has not been clipped
for CCB1 or Harmony operation. The yellow HEAT LED is
lit when the indoor blower is operating at the HEATING
speed.
Table 27
Operating Sequence
GHR32V−5, CCB1 and Single−Speed Outdoor Unit
OPERATING MODESYSTEM DEMANDSYSTEM RESPONSE
System Condition
Normal operationY1
*Call for humidity
removal during
cooling demand
Dehumidification
demand satisfied
during cooling demand.
Call for cooling after
call for hum
removal.
Humidity demand
satisfied between
thermostat demands
(unit off cycle).
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first thermostat heating demand.
* Reduced blower speed is 77% of COOL for V3 units and 74% of COOL for the V5 units.
ty
Thermostat
Demand
Y1
Y1
None
Y1
NoneOver setpoint (1 or more)Off
Y1Change to acceptableCOOL
*Relative Humidity
(EfficiencyPlus Lights)
No demand. Humidity
level is acceptable
Humidity level rises
above setpoint. Demand
initiated.
Humidity level falls below
setpoint. No demand
Humidity level above set-
point. Demand initiated.
Humidity level above set-
point. Demand initiated.
Blower
CFM
(COOL)
COOL
77%/74%
of COOL
COOL
Off
77%/74%
of COOL
Comments
Compressor demand and indoor blower
speed controlled by thermostat demand.
Call for dehumidification initiated by CCB1
control. Indoor blower speed reduced by
CCB1 control.
When humidity demand is satisfied, blower speed immediately increases to the
COOL CFM to hasten the end of the cycle.
Dehumidification mode begins when relative humidity is greater than setpoint.
While unit is not operating (no thermostat
emand), s
back up. Blower operates at COOL CFM.
e switch is moved down an
Page 30
Page 31
Table 28
Normal operation
blower speed controlled by
removal during
until after initial thermostat demand is
humidity duri
point,orifslideswitchismovedsignifi
g
When humidity demand is satisfied
satisfied during
speed compressor operation at begin
d
d
compressor) begins with next thermo
satisfied between
Operating Sequence
GHR32V−5, CCB1 and Two−Speed Outdoor Unit
OPERATING MODESYSTEM DEMANDSYSTEM RESPONSE
System
Condition
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
****Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Call for humidity
1st−stage cooling
demand
Significant increase in
ng
thermostat cooling
demand.
Humidity demand
satisfied durin
thermostat demand.
Call for humidity
removal during 2nd
stage thermostat
eman
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase in
humidity
Humidity demand
satisfied between
thermostat demands
(unit off cycle).
Y1No demand. AcceptableLow
Y2No demand. AcceptableHighHIGH COOL
Y1No demand. AcceptableLow
Y1
Demand
satisfied
Y1
Y1
Y1
Y1
Y1
None
Y1
Y2
Y2
Y2
None
Y1
None
Y2
None
Y1 or Y2
None
Y1 or Y2
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
Humidity level remains
slightly (1) above setpoint.
Demand continues.
Humidity level remains
slightly (1) above setpoint.
Demand continues.
No demand. Acceptable
Humidity level rises signifi-
cantly (2 or more) above
setpoint. Demand initiated.
Humidity level
above setpoint.
Humidity level falls below
setpoint. No demand.
No demand. Acceptable
No demand. Acceptable
No demand. Acceptable
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
No demand. Acceptable
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is significantly
above setpoint (2 or more).
Humidity level is significantly
above setpoint (2 or more).
Humidity level is slightly (1)
above setpoint.
Humidity level falls below
setpoint. No demand.
Low
Off
High
Low
High
High
High
Off
Low
High
High
High
Off
Low
Off
High
Off
High
Off
High
55% of
HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
55% of
HIGH COOL
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
Off
Off
Off
Off
Off
Off
Compressor demand and indoor
blower speed controlled by
thermostat demand
Dehumidification mode does not begin
satisfied and new cooling demand is
initiated.
If humidity rises significantly above setpoint, or if slide switch is moved signifi-
cantly, unit will immediately go into de-
humidification mode (in presence of
thermostat demand).
When humidity demand is satisfied,
blower immediately shifts to the COOL
CFM in order to hasten the end of the
cycle. Unit can only shift out of high
speed compressor operation at begin-
ning of next cycle.
Blower immediately changes speed in
response to thermostat demand.
Dehumidification mode (high speed
compressor) begins with next thermo-
stat demand after initial demand is sat-
isfied.
Reduced blower speed (dehumidifica-
tion speed) begins immediately with
thermostat demand
If humidity increases significantly over
setpoint, or if slide switch is moved,
unit immediately goes into dehumidifi-
cation mode (in presence of thermostat
demand).
While unit is not operating (no thermo-
stat demand), slide switch is moved
down and back up. Blower and com-
pressor operate at high speed until
next thermostat demand.
Note − During mode of operation change from cooling to heating, indicating lights will not change until the first thermostat heating
demand.
,
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed
indefinitely. To reset, move the humidity slide switch all the way down then back up to desired setpoint while the unit is running.
** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5.
***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compressor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 31
Page 32
HEAT EXCHANGER
SUPPORT
HOT END HEADER
(COLLECTOR) BOX
GHR32 HEAT EXCHANGER
CONDENSER COIL
COMBUSTION
AIR BLOWER
COMBUSTION AIR
BLOWER MOTOR
COLD HEADER
(COLLECTOR)
BOX
PRIMARY LIMIT
CONTROL (S10)
LENNOX DURALOKPlust
HEAT EXCHANGER
(Assembly)
CLAMSHELL
(Each Segment)
CORBEL
ORIFICE
CUPS
FLAME SENSOR
ASSEMBLY
GAS VALVE
MANIFOLD
BURNER
BOX
BURNERS
FIGURE 22
Page 32
BURNER
ORIFICE
FLAME SIGHT
(VIEWING) GLASS
SURELIGHT
IGNITOR
Page 33
C−Heating Components (Figure 22)
Combustion air blower (B6), primary limit control (S10), SureLight ignitor, flame sensor, burners, flame rollout switch
(S47), gas valve (GV1), combustion air blower switch (S18),
and clamshell heat exchangers are located in the heating
compartment. The heating compartment can be accessed
by removing the burner access panel.
1.Combustion Air Inducer Blower (B6)
All GHR32 units use a two−stage combustion air inducer blower to move air through the burners and heat exchanger during
heating operation. The blower uses a 120VAC motor. The motor operates during all heating operation and is controlled by
the SureLight integrated board (A92) and two−stage control
board (A86). The combustion air inducer blower operates on
low speed during first stage heat (low fire), then switches to
high speed for second stage heat (high fie).
2.Combustion Air Blower Capacitor (C3)
PSC Motors only
GHR32 units with a PSC combustion air blower motor,
will have a thermally protected 3 MFD 300VAC capacitor.
The capacitor is mounted on the combustion air blower
housing.
3.Primary Limit Control (S10)
Figure 23 shows the primary limit (S10) used on GHR32 units.
S10 is located in the middle of the heating vestibule panel.
When excess heat is sensed in the heat exchanger, the limit
will open. If the limit is tripped, the furnace control energizes the supply air blower and closes the gas valve. The
limit automatically resets when unit temperature returns to
normal. The switch is factory set and cannot be adjusted.
See table 29 for limit set points.
SPADE CONNECTORS
GHR32 UNIT SIZELIMiT SET POINT
GHR32-50300°
GHR32-75300°
GHR32Q3/4-100220°
GHR32-120175°
LIMIT CONTROL (S10)
LIMIT
INSULATING COVER (s)
FIGURE 23
TABLE 29
DETAIL VIEW OF BURNER CLUSTER MOUNTING
Burner Box
Raised
Toggle Locks
Burner Cluster
Flange
Screw
FIGURE 24
4.Burners
Figure 22 shows the arrangement of the burner box. Table 30
shows how many burners are used per unit. See figure 24 for
a more detailed view. Notice the position of the raised toggle
lockets.
TABLE 30
NUMBER OF HEAT
GHR32 UNIT SIZE
GHR32-502
GHR32-753
GHR32Q3/4-1004
GHR32-1205
All units use inshot burners Burners are factory set and do not
require adjustment. A sight glas s is fu rnis hed in the burn er
box assembly for flame viewing. Always operate the unit
wit h the burne r box cover in place. Burners can be removed
as an assembly for service. Burner maintenance and service
is detailed in the SERVICE CHECKS sections of this manual. Each burner uses an orifice which is precisely matched to
the burner input. The orifice is threaded into the burner manifold. The burner is supported by the orifice and will easily
slide off for service. Each orifice and burner are sized specifically to the unit. Refer to Lennox Repair Parts Listing for correct sizing information. A flame retention ring in the end of
each burner maintains correct flame length and shape and
keeps the flame from lifting off the burner head. In addition, the
burner entrance to each clamshell (Figure 22) is fitted with a
corbel cup (orifice) used to direct the flow of combustion products.
NOTE−Do not use thread-sealing compound on the orifices. Thread-sealing compound may plug the orifices.
EXCHANGER CLAMSHELLS /
BURNERS
Page 33
Page 34
5.Clamshell Heat Exchanger
GHR32 units use an aluminized steel primary and stainless steel secondary heat exchanger assembly. Table 30
shows how many heat exchanger clamshells are used
per unit. Heat is transferred to the air stream from all surfaces of the heat exchanger. The shape of the heat exchanger ensures maximum efficiency.
The combustion air blower pulls fresh air through the air intake box. This air is mixed with gas in the burner venturi
and at the corbel orifices. The gas / air mixture is then
burned at the entrance of each clamshell. Combustion
gases are then pulled through the primary and secondary heat
exchangers and exhausted out the exhaust vent pipe.
6.Flame Rollout Switch (S47)
Flame rollout switch S47 is a SPST N.C. high temperature limit
located behind the burner air intake fitting on the burner box
assembly (see figure 25). S47 is wir ed to the burne r ign itio n
control A3. When S47 senses flame rollout (indicating a
blockage in the combustion air passages), the flame rollout switch trips, and the ignition control immediately
closes the gas valve.
Switch S47 in all GHR32 units is factory preset to open at
320_F + 12_F (160_C + 6.7_C) on a temperature rise. All
flame rollout switches are manually reset.
7.Gas Valve
The GHR32 uses a gas valve manufactured by White
Rodgers or Honeywell. The valve is two-stage internally
redundant to assure safety shut−off. If the gas valve must
be replaced, the same type valve must be used. The
Honeywell valve can be field converted to LP and is adjustable on both low and high fire. WhiteRodgers supplies two
seperate valves for natural and LP and is adjustable for
high fire ONLY.
24VAC terminals and gas control knob are located on top of
the valve. Terminals on the gas valve are connected to wires
from the SureLight integrated control and the two−stage control. 24V applied to the terminals energizes the valve.
Inlet and outlet pressure taps are located on the valve. A regulator adjustment screw is located on the side of the valve. Refer to figures 26, 27 , and 28 for location of valve features.
NOTE−WhiteRodgers valve is not adjustable on low fire.
Do not attempt to regulate low fire manifold pressure.
WHITE RODGERS 36E SERIES GAS VALVE
NATURAL GAS
(LOW HEAT MANIFOLD PRESSURE FACTORY SET.
DO NOT ADJUST.)
HIGH HEAT
MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
FLAME ROLLOUT SWITCH (S47)
FLAME ROLLOUT
SWITCH (S47)
FIGURE 25
HONEYWELL VR8205 Series Gas Valve
HIGH FIRE ADJUSTMENT
SCREW (UNDER CAP)
LOW FIRE
ADJUSTMENT
SCREW
(UNDER CAP)
INLET PRESSURE TAP
VALVE SHOWN IN OFF POSITION
FIGURE 26
MANIFOLD
PRESSURE
TAP
MANIFOLD
PRESSURE
OUTLET ON
SIDE
FIGURE 27
WHITE RODGERS 36E SERIES GAS VALVE
PROPANE GAS
(LOW HEAT MANIFOLD PRESSURE FACTORY SET.
DO NOT ADJUST.)
PM
HI
C
HIGH HEAT
MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
OUTLET ON
SIDE
FIGURE 28
100% Sealed Combustion
The burner box is completely sealed and operates under
a negative pressure. A pressure hose is connected from the
burner box to the gas valve regulator. The gas valve senses
the pressure in the burner box and changes gas valve outlet
(manifold) pressure based on changes in bu rner box pr essure. The intent is to compensate for different vent configurations which can greatly affect the firing rate of the
unit.
Page 34
Page 35
NORMAL OPERATION (Natural Gas Units)
3.5
3.4
3.3
3.2
3.1
3.0
2.9
2.8
GAS VALVE OUTPUT
2.7
2.6
MANIFOLD PRESSURE (positive inches water gauge)
2.5
Gray area indicates normal operating range + 10% of manifold pressure
The purpose of this chart is to explain unit operation . Each unit may vary depending
on installation, altitude, intake/exhaust configuration and other factors.
OPERATION AT THIS EXTREME
MAY INDICATE A BLOCKED
INLET OR OTHER PROBLEM"
BURNER BOX PRESSURE
(Negative inches water gauge
measured on left side of burner box)
FIGURE 29
NORMAL OPERATION (L.P. Gas Units)
10.0
9.9
9.8
9.7
9.6
9.5
9.4
9.3
GAS VALVE OUTPUT
9.2
9.1
MANIFOLD PRESSURE (positive inches water gauge)
9.0
Gray area indicates normal operating range + 10% of manifold pressure
The purpose of this chart is to explain unit operation . Each unit may vary depending
on installation, altitude, intake/exhaust configuration and other factors.
OPERATION AT THIS EXTREME
MAY INDICATE A BLOCKED
INLET OR OTHER PROBLEM"
BURNER BOX PRESSURE
(Negative inches water gauge
measured on left side of burner box)
Figures 29 and 30 show how gas valve manifold pressure
changes as burner box pressure changes. The GHR32 is a
self adjusting unit to maintain a constant output.
8.Combustion Air Prove Switch
(S18) GHR32−1/−4 Units &
(S102) GHR32−5 Units
GHR32 series units are equipped with a differential
pressure switch S18 or S102 located on either side of
the heating compartment cabinet (factory installed on
left side ).The switch monitors the differential pressure between the downstream and upstream flue gas pressures.
When the unit is installed for horizontal right-hand discharge, the air proving pressure switch must be moved to
the opposite side of the unit. Any one of four different switches
may be on the unit. One is manufactured by MPL. The other
three switches are manufactured by TRIDELTA / HONEYWELL. Each switch operates the same and can be replaced
−1.0−0.20−0.4−0.6−0.8
−1.0−0.20−0.4−0.6−0.8
with one another. See figure 31 for combustion air prove
switch replacment. Hoses must be connected to correcttaps for switch to operate safely and properly. GHR32
model units have color coded tubing to designate positive and
negative sides of the pressure switch. Red/Square tubing
should always be connected to the positive side of the pressure switch. Gray or Black /Round tubing should always be
connected to the negative side of the pressure switch. See figure 31.
The switch is a SPST N.O. pressure switch electrically connected to the integrated control. The purpose of the switch is
to prevent burner operation if the combustion air blower is not
moving enough air for proper combustion.
On start-up, the switch senses that the combustion air blower
is operating. It closes a circuit to the ignition control when
the difference in pressure across the pressure switch exceeds 0.90" W.C. (223.78Pa). If the switch doe s no t s uccessfully sense the required differential, the switch cannot close and the furnace cannot operate. The switch is
factory set and is not adjustable. If the flue or air inlet become obstructed during operation, the switch senses a
loss of pressure differential and opens the circuit to the ignition control. If the condensate line is blocked, water will back
up into the header box and reduce the pressure differential
across the switch. The pressure switch will open if the differential drops below 0.75" W.C. +
05" W.C. (186.48 Pa +
12.4 Pa).
FIGURE 30
Page 35
Page 36
NEGATIVE
PRESSURE
(Marked With "V")
TRIDELTA / HONEYWELL
(All Metal Construction)
NEGATIVE
PRESSURE
(NO Markings)
Hose Connec-
tion Side Only)
MPL
POSITIVE
PRESSURE
(Marked With "P")
POSITIVE PRESSURE (NO
Markings Electrical Terminal
and Hose Connection Side)
NEGATIVE PRESSURE
(Marked With "−")
POSITIVE
PRESSURE
(Marked With "+")
TRIDELTA / HONEYWELL IS2
TRIDELTA / HONEYWELL
(Metal/Plastic Construction)
NEGATIVE PRESSURE
(gray side marked −")
HORIZONTAL LEFT HAND AIR DISCHARGE
Connect hose (red square) to POSITIVE side on pres-
sure switch and open tap on FRONT of collector box.
Pressure
Switch
AIR FLOW
Connect hose (gray or black
round) To "NEGATIVE"side on
pressure switch and open tap on
SIDE of collector box.
NEGATIVE PRESSURE CONNECTIONS
(Gray or Black round tubing beginning with −3 models)
SCALE1.000
POSITIVE PRESSURE
(black side marked +")
DOWN FLOW AIR DISCHARGE
Connect hose (gray or black round) To NEGATIVE side
on pressure switch and open tap on FRONT of collector
box.
AIR FLOW
Pressure
Switch
Connect hose
(red square) to
POSITIVE side
on pressure
switch and open
tap on FRONT
of collector box.
Collector Box
HORIZONTAL RIGHT HAND DISCHARGE
Connect the red square hose to the POSITIVE side on pressure
switch and the open tap on the FRONT of the collector box.
Pressure
Switch
must be
on top side
of unit.
Collector Box
BLANK STEMS EARLY MODEL
UNITS ONLY
POSITIVE PRESSURE CONNECTIONS
(Red tubing)
AIR FLOW
Connect the gray or black round hose to the NEGATIVE
side on the pressure switch and SIDE of the collector box.
FIGURE 31
Page 36
Page 37
To troubleshoot the pressure switch, temporarily jumper the
switch. The unit will not fire with pressure switch jumpered.
Therefore, the pressure switch must be bypassed after the
combustion air blower is activated. This will determine if the
pressure switch and furnace are operating properly. However,
this may not indicate if the sealed combustion system is oper-
ating properly. If the unit cannot attain 0.75" W.C. (186.48 Pa )
differential, the unit will not operate.
D−Blower Compartment (Figures 33 and 34)
Blower motor (B3), capacitor (C4), and secondary limit control (S21) are located in the blower compartment shown in
figure 33. Blower motor (B3), Coil choke (L13) and secondary limit (S21) are shown in figure 34. The blower compartment can be accessed by removing the blower access panel.
IMPORTANT
Unit will not operate with pressure switch bypassed
upon start-up. To troubleshoot pressure switch,
jumper pressure switch following activation of combustion air blower!!
Checks of pressure differential can aid in troubleshooting.
When measuring the pressure differential, readings should be
taken at the pressure switch. Lack of differential usually indi-
cates problems in the intake or exhaust piping, but may ind i-
cate problems in the heat exchanger, condensing coil,
header boxes, combustion blower or other compo-
nents.
Measuring pressure differential
The differential pressure is the difference in pressure mea-
sured on either side of the pressure switch:
1 − Remove thermostat demand and allow unit to cycle
off.
2 − Disconnect hose from front of pressure switch and
install tee as shown in figure 32. Repeat sequence for
hose connected to back of switch.
BLOWER COMPARTMENT
Q MODELS
SECONDARY LIMIT
CONTROL (S21)
BLOWER MOTOR
(B3)
BLOWER MOTOR
CAPACITOR (C4)
FIGURE 33
TEE AND 1/4"i.d. RUBBER HOSE FIELD PROVIDED
TO PRESSURE
SENSING HOSE
TO PRESSURE
SWITCH
TO DRAFT GAUGE
FIGURE 32
3 − Install manometer (draft gauge) to open ends of tee’s.
The hose from the back side of the switch goes to the
zero side of the gauge.
4 − Operate unit and observe draft gauge reading. Read-
ings will change as heat exchanger warms.
a. Take one reading immediately after startup.
b. Take a second reading after unit has reached steady
state (approximately 5 minutes).
Pressure differential should be greater than .75"
W.C. (186.48 Pa).
5 − Remove thermostat demand and allow to cycle off.
6 − Remove draft gauge and Tee’s. Reinstall combustion air
sensing hoses to the pressure switch.
BLOWER COMPARTMENT
V MODELS
SECONDARY
LIMITS (S21)
COIL
CHOKE
(L13)
To Remove Blower From Unit: Remove Bolts and
Wiring Jackplugs. Then Slide Out Front of Unit.
BLOWER
WHEEL
BLOWER
MOTOR (B3)
FIGURE 34
Page 37
Page 38
1.Blower Motor (B3) and Capacitor (C4)
GHR32Q Models
All GHR32Q model units use single phase direct drive blower motors. All motors are 120V permanent split capacitor
motors to ensure maximum efficiency. See motor nameplate or SPECIFICATIONS section for motor ratings. Ratings for capacitor will be on side.
2.Secondary Limit Control (S21)
The secondary limit (S21) on GHR32 units is mounted on
the back side of the blower housing. When excess heat is
sensed in the blower compartment, the limit will open. If the
limit is tripped, the furnace control energizes the supply air
blower and closes the gas valve. The limit automatically resets
when unit temperature returns to normal. The switch opens at
160_F + 5_F (71.1_C + 2.8_C) on a temperature rise and resets at 130_F + 8_F (54.4_C + 4.4_C) on a temperature fall.
The switch is factory set and cannot be adjusted. The setpoint
is printed on the face plate of the limit.
SECONDARY LIMIT CONTROL (S21)
SPADE CONNECTORS
LIMIT
INSULATING COVER (s)
GHR32V BLOWER MOTOR B3
J48
SHAFT
MOTOR
CONTROLLER
J49
FIGURE 36
GHR32V BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 37
A solid-state controller is attached to the motor. The
controller is primarily an A.C. to D.C. converter. Converted D.C. power is used to drive the motor. The controller contains a microprocessor which monitors varying conditions inside the motor (such as motor
workload).
The controller uses sensing devices to sense what position
the rotor is in at any given time. By sensing the position of the
rotor and then switching the motor windings on and off in sequence, the rotor shaft turns the blower.
FIGURE 35
3. Blower Motor (B3) GHR32V MODELS
GHR32V model units use a single−phase, electronically controlled D.C. brushless motor (controller converts single phase
A.C. to three phase D.C.), with a permanent-magnet-type rotor (figure 36). Because this motor has a permanent magnet
rotor it does not need brushes like conventional D.C. motors.
Internal components are shown in figure 37. The stator windings are split into three poles which are electrically connected
to the controller. This arrangement allow s mot or windin gs to
turn on and off in sequence by the controller.
DANGER
Disconnect power from unit and
wait at least five minutes to allow
capacitors to discharge before attempting to adjust motor speed tap
settings. Failure to wait may cause
personal injury or death.
GHR32V series blower motor ratings are listed in the
SPECIFICATIONS section. All GHR32V blower motors
use single phase power. An external run capacitor is not
used. The motor uses permanently lubricated ball-type
bearings. The VSM is a two part component; the motor
and the control module. If motor fails, it is quite possible
the control module only, will need to be replaced. Lennox provides a replacement kit for the control module.
Internal Operation
Each time the controller switches a stator winding (figure 37)
on and off, it is called a pulse." The length of time each pulse
stays on is called the pulse width." By varying the pulse width
(figure 38), the controller varies motor speed (called pulsewidth modulation"). This allows for precise control of motor
speed and allows the motor to compensate for varying load
conditions as sensed by the controller. In this case, the controller monitors the static workload on the motor and varies motor
rpm in order to maintain constant airflow (cfm).
The motor is equipped with 11 incremental taps which are driven by the integral controller. The controller is capable of controlling three of the 11 taps.
Page 38
Page 39
The motor controller is driven by the VSP2−1, VSP3−1 or
two stage integrated SureLight control The VSP receives its demand (PWM signal or fixed 24 VAC or VDC
signal) from optional controls such as the Harmony zone control system, Efficiency Plus Humidity Control (CCB1) or a conventional thermostat.
Motor rpm is continually adjusted internally to maintain
constant static pressure against the blower wheel. The controller monitors the static work load on the motor and motor ampdraw to determine the amount of rpm adjustment. Blower rpm
may be adjusted any amount in order to maintain a constant
cfm as shown in Blower Ratings Tables. The amount of adjustment is determined by the incremental taps which are used
and the amount of motor loading sensed internally. The cfm
remains relatively stable over a broad range of static pressure.
Since the blower constantly adjusts rpm to maintain a specified
cfm, motor rpm is not rated. Hence, the terms blower speed"
and speed tap" in this manual, on the unit wiring diagram and
on blower B3 refer to blower cfm regardless of motor rpm.
When Harmony is used, speed taps are overridden and a
PWM signal generated by the Harmony controller continuously varies motor speed based upon zone demands.
Initial Power Up
When line voltage is applied to B3, there will be a large inrush
of power lasting less than 1/4 second. This in rush charges a
bank of DC filter capacitors inside the controller. If the disconnect switch is bounced (rapid turning on and off) when the disconnect is closed, the disconnect contacts may become
welded. Try not to bounce the disconnect switch when applying power to the unit.
Motor Start-Up
When B3 begins start-up, the motor gently vibrates back and
forth for a moment. This is normal. During this time the electronic controller is determining the exact position of the rotor.
Once the motor begins turning, the controller slowly eases
the motor up to speed (this is called soft-start"). The motor
may take as long as 10-15 seconds to reach full speed. If the
motor does not reach 200rpm within 13 seconds, the motor
shuts down. Then the motor will immediately attempt a restart. The shutdown feature provides protection in case of a
frozen bearing or blocked blower wheel. The motor may attempt to start eight times. If the motor does not start after the
eighth try, the controller locks out. Reset controller by momentarily turning off power to unit.
The DC filter capacitors inside the controller are connected
electrically to the speed tap wires. The capacitors take
approximately 5 minutes to discharge when the disconnect is opened. For this reason it is necessary to
wait at least 5 minutes after turning off power to the
unit before attempting to change speed taps.
Page 39
Page 40
MOTOR SPEED CONTROL WITH D.C. PULSE-WIDTH MODULATION
Motor speed is determined by the size of the electrical pulse sent to the
motor windings. The longer the pulse, the faster the motor.
OUTPUT FROM CONTROLLER TO MOTOR WINDINGS
WINDINGS TURNED OFF
The frequency of the pulses to the windings is 20KHz.
DO NOT ATTEMPT TO MEASURE THESE VOLTAGES.
LOW SPEED HEAT/COOL (output from controller to motor windings)
One
Pulse
One revolution
325VDC
O volts
WINDING #1
325VDC
O volts
WINDING #2
325VDC
O volts
WINDING #3
HIGH SPEED HEAT (output from controller to motor windings)
One revolution
325VDC
O volts
WINDING #1
325VDC
O volts
WINDING #2
325VDC
O volts
WINDING #3
WINDINGS TURNED ON
ON PULSE
OFF PULSE
HIGH SPEED COOL (output from controller to motor windings)
One revolution
325VDC
O volts
WINDING #1
325VDC
O volts
WINDING #2
325VDC
O volts
WINDING #3
FIGURE 38
Page 40
Page 41
External Operation (Speed Tap Priority)
Figure 39 shows the two quick-connect jacks (J48 and J49)
which connect the motor to the GHR32V. Jack J48 is the
power plug and jack J49 connects the unit controls to the
motor.
Line voltage must be applied to J48 pin 5 in order for the
motor to operate. When using 120VAC pins 1 and 2 must
be jumpered. When control voltage is applied to J49 pin 3
and 15 (single stage heating and cooling), the motor is energized on the low speed heat/cool tap.
4.Choke Coil (L13)
A choke coil is used on all GHR32V units. The choke is
located on the blower housing and is used to block radio frequency interference.
Precautions
If the GHR32 V or its electronically controlled blower motor is
improperly or inadequately grounded, it may cause television
interference (commonly known as RFI or radio frequency interference).
When voltage is applied to J49 pin 2 in addition to pin 3 and
15 (second stage heating), the blower is energized on the
high speed heating tap. When voltage is applied to J49 pin
10 in addition to pin 3 and 15 (second stage cooling), the
blower is energized on the high speed cooling tap. The motor assigns priority to J49 pin 2 so that if a call for cooling and a
call for heating are concurrent, heating call overrides and the
blower operates on high speed heating tap.
ICM2 with VSP3 or Two stage Variable Speed Control
The ICM2 operates slightly different than stated above
when matched with the VSP3 or Two stage variable speed
control. When control voltage is applied to J49 pin 3 and 15,
the motor is energized on continuous fan. When voltage is
applied to J49 pin 2 in addition to pin 3 and 15 (first stage
heating), the blower is energized on the low speed heating
tap. When voltage is applied to J49 pin 13 in addition to pin
3 and 15 (second stage heating), the blower is energized
on the high speed heating tap. The motor assigns priority to
J49 pin 2 so that if a call for cooling and a call for heating are
concurrent, heating call overrides and the blower operates
on high speed heating tap.
BLOWER B3 HARNESS CONNECTORS
POWER
CONNECTOR J48
J48
PIN 1 - Jumper PIN 1 to PIN2 for 120VAC line input only.
PIN 2 - Jumper PIN 1 to PIN2 for 120VAC line input only.
PIN 3 - Ground
PIN 4 - AC Line
PIN 5 - AC Line
CONTROL
CONNECTOR J49
1
J49
PIN 1 - C1
PIN 2 - W / W1
PIN 3 - C2
1
PIN 4 − Delay
PIN 5 - Cool
PIN 6 - Y1
PIN 7 - Adjust
PIN 8 - 0ut
PIN 9 - 0
PIN 10 - BK / PWM
PIN 11 - Heat
PIN 12 - R
PIN 13 - EM / W2
PIN 14 - Y / Y2
PIN 15 - G
PIN 16 - Out +
FIGURE 39
This interference is caused by internal switching frequencies of the motor controller (see figure 40). TV interference may show up as small specks or lines which
randomly appear on the TV screen accompanied by pops or
clicks in the sound. Before attempting any service, make sure
the indoor unit is causing the interference. To check, disconnect power to indoor unit then check TV for continued signs of
interference.
TV interference may be stopped by making sure the motor is solidly grounded to the cabinet (metal to metal) and
by making sure the cabinet is solidly grounded. If TV interference persists, make sure the television (and all affected RF appliances) are moved away from the GHR32V.
Also make sure affected appliances are connected to a separate electrical circuit.
ECM SWITCHING FREQUENCY
The electrical pulses to the windings cycle on and off at a rate of
20,000 cycles per second (20Khz, this is called the switching
frequency). The effective D.C. voltage can be varied by chang-
ing the pulse width. The switching frequency is necessary in
order to vary the speed of the motor. If the motor is not securely
grounded to the cabinet and if the cabinet is not securely
grounded, the switching frequency may cause television inter-
OUTPUT FROM CONTROLLER TO MOTOR WINDINGS
One Pulse
325VDC
O volts
325VDC
O volts
325VDC
O volts
PULSE ON
PULSE OFF
WINDING OFF
WINDING #1
WINDING #2
WINDING #3
One cycle
ference.
ELECTRICAL
325VDC
PULSE
O volts
Switching Frequency
20Khz
ONE
FIGURE 40
Page 41
Page 42
II−PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation instructions and applicable codes.
A−PVC Joint Cementing Procedure
WARNING
DANGER OF EXPLOSION! Fumes from PVC glue
may ignite during system check. Remove spark
plug wire from ignition control before 120V power
is applied. Reconnect wire after two minutes.
B−Venting Considerations
All GHR32 furnaces must be vented independently as
shown in figure 42 and must not be connected to a common venting system. If a GHR32 furnace replaces a less
efficient furnace which was vented with other gas appliances into a common vent, the size of the common vent
pipe must be appropriate for gas appliances which remain
connected. Without the heat of the original furnace flue products, the vent pipe is probably oversized for the single water
heater or other appliance(s). The common vent should be
checked for proper draw for all appliance(s) which remain
connected.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any
ridges or rough edges. If end is not chamfered, edge
of pipe may remove cement from fitting socket and
result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of
pipe.
5 − Uniformly apply liberal coat of PVC primer for PVC or
ABS cleaner for ABS to inside socket surface of fitting
and male end of pipe to depth of fitting socket.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take care
to keep excess cement out of socket. Apply second
coat to end of pipe.
NOTE−Time is critical at this stage. Do not allow primer
to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn pipe 1/4 turn during
assembly (but not after pipe is fully inserted) to distribute cement evenly. Once joint is made, PVC may
swell. Hold joint together until bonded (approximately 20 seconds).
NOTE−Assembly should be completed within 20 seconds after last application of cement. Hammer blows
should not be used when inserting pipe.
Checks of Common Venting System
for Other Gas Appliances (Water Heater, etc...)
1 − Unused openings in the common venting system must be
sealed.
2 − The venting system should be visually checked for proper
size and horizontal pitch. You should also check and determine that there is no blockage or restriction, leakage,
corrosion and other deficiencies which could cause an unsafe condition.
3 − Close all building doors and windows and all doors
between the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers
and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
4 − Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance will
operate continuously.
5 − Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use match or candle
flame, or smoke from a cigarette or cigar.
6 − After it has been determined that each appliance re-
maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and any
other gas-burning appliance to their previous condition of
use.
8 − After assembly, wipe excess cement from pipe at
end of fitting socket. A properly made joint will show
a bead around its entire perimeter. Any gaps may indicate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
7 − If improper venting is observed during any of the tests, the
common venting system must be corrected. The common venting system should be resized to approach the
minimum size as determined by using the appropriate
tables in appendix G in the current standards of the National Fuel Gas Code in the U.S.A. or category 1 in the
Natural Gas and Propane Installation Code in Canada.
Page 42
Page 43
GHR32 Intake and Exhaust Piping Considerations
If the GHR32 venting system must be altered or repaired, use
the following as a guide. Intake and exhaust pipes may be
routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical
termination through the roof is preferred. Figures 42 through
45 show typical terminations.
1 − Use only recommended piping materials for both in-
take and exhaust piping.
2 − Secure permanent joints gas tight using approved ce-
ment.
3 − Piping diameters should be determined according to
length of pipe run. See table 31. Locate intake piping
upwind (prevailing wind) from exhaust piping. To avoid
recirculation of exhaust gas on roof terminations, end of
exhaust pipe must be higher than intake pipe.
Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one
through the side. Also, do not exit the intake on one
side and the exhaust on another side of the house or
structure.
4 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to illustrations). Maximum separation is 3" (76mm) on roof
terminations and 6" (152mm) on side wall terminations.
NOTE−If winter design temperature is below 32_ F (0_C),
exhaust piping must be insulated with 1/2" (13mm) Armaflex or equivalent when run through unheated
space. Do not leave any surface area of exhaust pipe
open to outside air; exterior exhaust pipe must be insulated with 1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or
equivalent is recommended. Insulation on outside
runs of exhaust pipe must be painted or wrapped to
protect insulation from deterioration.
5 − Exhaust piping must terminate straight out or up as
shown. On roof terminations, the intake piping
should terminate straight down using two 90_ elbows
(See figure 42). In rooftop applications, a 2" X 1−1/2"
(51mm X 38mm) reducer for 2" (51mm) venting, 3" x 2"
(76mm X 51mm) reducer for 3" (76mm) venting must be
used on exhaust piping at the point where it exits the
structure to improve the velocity of exhaust and force flue
products away from intake piping.
NOTE-Care must be taken to avoid recirculation of exhaust back into intake pipe.
6 − On side wall exits, exhaust piping should extend a
maximum of 12" (395mm) beyond the outside wall.
Intake piping should be as short as possible. See
figure 44.
7 − Minimum separation distance between the end of
the exhaust pipe and the end of the intake pipe is 8"
(203mm).
8 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other obstructions, refer to figure 45 for proper piping method.
Piping must be supported every 3 ft. (.91m) as shown in
figure 41 and must be insulated. When exhaust and intake
piping must run up an outside wall, the exhaust piping is
reduced accordingly after the final elbow.
9 − Position termination ends so they are free from any ob-
structions and above snow accumulation level (where applicable). Termination ends must be a minimum of 12"
(305mm) above grade level. Do not point into window
wells, stairwells, alcoves, courtyard areas or other recessed areas. Do not position termination ends directly
below roof eaves.
10− Suspend piping using hangers at a minimum of every
5 feet (1.52m) for schedule 40 PVC and every 3 feet
(.91m) for ABS−DWV, PVC−DWV, SDR−21 PVC, and
SDR−26 PVC piping. A suitable hanger can be fabricated by using metal or plastic strapping or a large wire tie.
See figure 41.
Page 43
Page 44
METAL OR PLASTIC
S
T
STRAPPING
FIGURE 41
60G77 For 2 inch (51 mm) Venting
33K97 For 3 inch (76 mm) Venting
2 x 1-1/2 in. (51 x 38 mm) 60G77
3 x 2 in. (76 x 51 mm) 33K97
REDUCER BUSHING (Furnished)
37
(940)
INTAKE AIR
11− In areas where piping penetrates joists or interior walls,
hole must be large enough to allow clearance on all
sides of pipe through center of hole using support
straps.
12− Isolate piping at the point where it exits the outside wall
or roof.
13− Unit should not be installed in areas normally sub-
ject to freezing temperatures.
14− When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining exhaust
tee, cold end header collector box, condensate collection
trap and lines.
Intake Piping Requirements
Piping must be routed to outside of structure.
IMPORTANT
Combustion air intake inlet and exhaust outlet
should not be located within 6 ft. (1.8m) of dryer
vent or combustion air inlet or outlet of another appliance. Piping should not exit less than 3 ft. (.91m)
from opening into another building.
2 in. (51 mm) pipe may be used to adapt terminations and intake/exhaust furnace connections. The TOTAL of 2 in. (51 mm) pipe that can be used
CANNOT exceed 3 feet (1 m).
Equivalent Vent Lengths:
10 ft. (3 m) and two 90° elbows of 2 in. (51 mm) pipe equals 20 ft. (6.1 m).
5 ft. (1.5 m) and two 90° elbows of 2 in. (51 mm) pipe equals 15 ft. (4.6 m).
5 ft. (1.5 m) and two 90° elbows of 3 in. (76 mm) pipe equals 15 ft. (4.6 m).One 90_elbow equals 5 feet (1.5 m) of straight vent pipe.One 45_ elbow equals 2.5 feet (.75 m) of straight vent pipe.
When additional/field supplied venting is used to clear average snow accumulation, the additional length of pipe and elbows must be figured into
the Maximum Equivalent Vent Length/Minimum Vent Pipe Diameter Requirements.
90° intake elbow CANNOT be used in this application.
12 feet (3.6 m) of additional vent must be figured into the Maximum Equivalent Vent Length/Minimum Vent Pipe Diameter Requirements if this kit is
used.
Only used with minimum vent length.
12 in. (305 mm) in length.
or 3 in.
Venting
NOTE − Exhaust pipe
an accelerator; 2 in. (51
mm) diameter pipe, 12 in.
(305 mm) in length.
mm
Roof Kit (15F75)
Wall Ring Kit (15F74)Closed Couple Wall Kit
(22G44)
Concentric Roof/Wall Kit (60G77)Not Available
Closed Couple Wall Kit
(30G28)
.
Closed Couple Wall Kit with
extension riser (30G79)
Cat. No.
Concentric Roof/Wall Kit (60L46)Not AvailableAcceptable
Vent/Intake Air Roof Kit
(44J41)
Closed Couple Wall Kit
(44J40)
Concentric Roof/Wall Kit (33K97)Acceptable
20 ft. (6.1 m) 20 ft. (6.1 m) 15 ft. (4.6 m)15 ft. (4.6 m)
3 in. (76 mm)
2 in. (51 mm)
n.
mm
n.
3 in. (76 mm)
cceptable
cceptable
AcceptableAcceptableAcceptable
cceptable
cceptable
mm
3 in. (76 mm)
ot Available
Acceptable
Acceptable
ot Available
Not Available
ot Available
ot Available
cceptable
Exhaust Piping Requirements
This unit is designed for left or right air exhaust piping for the
down-flow configuration. In horizontal applications, flue piping
must exit the top side of the unit.
All horizontal runs of exhaust pipe must slope toward unit.
A minimum of 1/4" (6mm) drop for every 12" (305mm) of
horizontal run is mandatory for drainage. Horizontal runs of
exhaust piping must be supported every 5 ft. (1.5m) [3 ft.
(0.9m) for ABS and SDR] using hangers.
NOTE−Exhaust piping must be installed on the same
side as the condensate trap.
NOTE−Exhaust piping should be checked carefully to
make sure there are no sags or low spots.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If
vertical discharge through an existing unused
stack is required, insert PVC pipe inside the stack
until the end is above the top or outlet end of the
metal stack.
CAUTION
The exhaust vent pipe operates under positive
pressure and must be completely sealed to prevent leakage of combustion products into the
living space.
Page 46
Page 47
Condensate Piping Requirements
The GHR32 unit is designed for either left or right condensate plumbing in the down-flow configuration. In the
horizontal position, trap should extend below unit; provide for a 3-3/4" (92mm) service clearance. Condensate
drain line should be routed only within the conditioned
space to avoid freezing of condensate and blockage of
drain line. An electric heat cable should be used where
condensate piping is exposed to unconditioned areas. If
condensate piping needs to be relocated to another position
or removed for service, use the following procedure to reinstall.
CAUTION
Do not use copper tubing or existing copper
condensate lines for drain line.
1 − Determine the side the condensate trap is to be installed.
Remove temporary plugs from condensate collar on
which the condensate trap is to be installed.
CONDENSATE ASSEMBLY
(Right Side Installation Shown)
CONDENSATE
STEMS
DRAIN
PLUG CAP
FIGURE 46
COLLAR
DRAIN PLUG
CONDENSATE
DRAIN LINE
CONNECTION
(route line to one side
glue cap to unused side)
CONDENSATE
TRAP
CAUTION
5 − Install a tee and vent pipe in the drain line near the trap.
Top of vent pipe should be 7" (178mm) above drain
level on trap.
6 − Condensate line must be sloped downward away from
trap (a minimum of 1/4" [6mm] drop for each 12"
[305mm] of horizontal line) to drain. If drain level is
above condensate trap, condensate pump must be
used in condensate line.
III−START-UP
A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be with-
in range listed on the nameplate. If not, consult th e pow er
company and have voltage condition corrected before starting unit.
3 − Inspect condition of condensate traps and drain as-
sembly. Disassemble and clean seasonally.
B−Heating Start-Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been underwater. Inspect the furnace and replace any part of
the control system and any gas control which has
been under water.
WARNING
If overheating occurs or if gas supply fails to shut
off, shut off the manual gas valve to the appliance
before shutting off electrical supply.
Condensate trap must be installed on the same
side as exhaust piping in downflow applications and on bottom of unit in horizontal applications.
2 − Apply glue to condensate trap stems and insert trap
into holes provided in condensate collar. Make sure
condensate trap is completely sealed to avoid any
leaks. Use the provided 1/2" screw to secure the top
of the condensate trap to the side of the unit. See
figure 46.
3 − For downflow applications only, remove plugs from the
unused condensate collar on the opposite side of the
unit. Apply glue to the plugs and place them back into
the condensate collar.
4 − Glue the drain line (field provided) to the trap. Route
drain line to an open drain. Glue 1" (25mm) cap (provided on trap) on unused condensate drain line connection.
CAUTION
Before attempting to perform any service or
maintenance, turn the electrical power to unit
OFF at disconnect switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
do not force. Force or attempted repair may result in a fire
or explosion.
GHR32 units are equipped with a hot surface ignition
system. Do not attempt to manually light burners on
these furnaces. Each time thermostat calls for heat, the
burners will be automatically lit.
Page 47
Page 48
How To Operate Gas Valve
WARNING
If you do not follow these instructions exactly, a
fire or explosion may result causing property
damage, personal injury or loss of life.
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set thermostat to lowest setting.
3 − Turn off all electrical power to furnace.
4 − This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.
5 − Remove unit access panel.
6 − Natural valve, move lever to OFF. Propane valve,
turn knob to OFF. Do not force.
7 − Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
8 − Natural valve, move lever to ON. Propane valve, turn
knob to ON. Do not force.
9 − Replace access panel.
10− Turn on all electrical power to unit.
11− Set thermostat to desired setting.
12− If the appliance will not operate, follow the instructions
To Turn Off Gas To Unit" and call your service technician or gas supplier.
Turning Off Gas To Unit
1 − Set thermostat to lowest setting.
2 − Turn off all electrical power to unit if service is to be per-
formed.
3 − Remove access panel.
4 − Natural valve, move lever to OFF. Propane valve, turn
knob to OFF. Do not force.
5 − Replace access panel.
NOTE−On initial start−ups and when condensate trap is
dry, unit may turn itself off and on to allow condensate
trap to fill. This is normal operation.
C−Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
D−Extended Period Shutdown
Turn off thermostat or set to UNOCCUPIED" mode. Close
all gas valves (both internal and external to unit) to guarantee no gas leak into combustion chamber. Turn off power to
unit. All access panels, covers and vent caps must be in
place and secured.
Refer to Maintenance" section of this manual for instructions on how to prepare condensate assembly for extended period shutdown.
IV−HEATING SYSTEM SERVICE CHECKS
A−A.G.A./C.G.A. Certification
All units are A.G.A. and C.G.A. design certified without
modifications. Refer to the GHR32 Operation and Installation Instruction Manual Information.
B−Gas Piping
Gas supply piping should not allow more than 0.5"W.C. drop
in pressure between gas meter and unit. Supply gas pipe
must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be
resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
When pressure testing gas lines, the gas valve must be disconnected and isolated. Gas valves can be damaged if
subjected to more than 0.5psig (14" W.C.). See figure 47. If
the pressure is equal to or less than 0.5psig (14"W.C.), use
the manual shut−off valve before pressure testing to isolate
furnace from gas supply.
GAS PIPING TEST PROCEDURE (Typical)
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8" N.P.T.
PLUGGED TAP
CAP
FIGURE 47
FURNACE
ISOLATE
GAS VALVE
IMPORTANT
In case emergency shutdown is required, turn off
the main shut-off valve and disconnect the main
power to unit. These controls should be properly
labeled by the installer.
When checking piping connections for gas leaks, use
preferred means. Kitchen detergents can cause harmful
corrosion on various metals used in gas piping. Use of a specialty Gas Leak Detector is strongly recommended. It is
available through Lennox under part number 31B2001.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.
Page 48
Page 49
TOP
SIDE
PIPING
1/8" NPT
PLUGGED
TAP
MANUAL MAIN
SHUT−OFF
GAS VALVE
BOTTOM
SIDE
PIPING
MANUAL
MAIN
SHUT−OFF
VALV E
1/8" NPT
PLUGGE
D
TAP
LEFT SIDE
PIPING
GAS VALVE
RIGHT
SIDE
PIPING
FIGURE 48
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
inlet pressure tap (field provided). See figure 48. Check gas
line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High
pressure can result in permanent damage to gas valve
or overfire. For natural gas units, operating pressure at
unit gas connection must be a minimum of 4.5" W.C.
(1.12kPa). For L.P. gas units, operating pressure at unit
gas connection must be a minimum of 11.0" W.C.
(2.74kPa). For both natural and L.P. gas units, operating
pressure must not exceed 13" W.C. (3.23 kPa).
On multiple unit installations, each unit should be checked
separately, with and without the other units operating. Supply pressure minimum and maximum must be the same as
listed in previous paragraph.
E−Check Manifold Pressure
Manifold Operating Pressure is the manifold pressure measured during normal operation (sensing burner box pressure).
Manifold Absolute Pressure is manifold pressure measured
when the gas valve regulator is operating at factory preset level (sensing atmospheric pressure).
After line pressure has been checked and adjusted, check
manifold absolute pressure. Move pressure gauge to outlet
pressure tap located on unit gas valve (GV1). Checks of
manifold absolute pressure are made as verification of proper
regulator adjustment.
Manifold operating pressure for the GHR32 can be measured at any time the gas valve is open and is supplying
VALV E
MANUAL MAIN
SHUT−OFF
VALV E
1/8" NPT
PLUGGED
TAP
SHUT−OFF
PLUGGE
MANUAL
MAIN
VALV E
1/8" NPT
D
TAP
Page 49
gas to the unit. Normal manifold operating pressure for
natural gas units is 2.5 to 3.5" W.C. (621 to 870 Pa). See
figure 29. For LP/propane gas the correct manifold operating pressure is 9.0 to 10.0" W.C. (2.24 to 2.49 Pa). See figure 30.
IMPORTANT
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of
gas pressure to the manometer.
TABLE 32
GAS VALVE REGULATION*
Unit (Fuel)
Natural
L.P.
Absolute Pressure (outlet) in. W.C.
3.5
10.0
The gas valve is factory set and should not require adjustment.
See table 32. Also, gas valve regulation varies with burner box
pressure (figures 29 and 30).
*Manifold Absolute Pressure Measurement and Adjustment
1 − Connect test gauge to outlet tap on gas valve.
2 − Disconnect pressure sensing hose from gas valve
and plug hose by covering opening with tape or
equivalent. Leave hose barb on valve open to atmosphere.
3 − Start unit and allow 5 minutes for unit to reach steady
state.
4 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue. L.P. gas should burn
mostly blue with some orange streaks.
5 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to values given in
table 32. If values are different, adjust to table 32.
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained. Take
care to replace pressure tap plug.
NOTE−During this test procedure, the unit will be overfiring:
D Operate unit only long enough to obtain accurate read-
ing to prevent overheating heat exchanger.
D Attempts to clock gas valve during this procedure will
be inaccurate. Measure gas flow rate only during normal unit operation.
6 − When test is complete remove obstruction from hose
and return hose to gas valve barb.
F− Proper Gas Flow
Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time
in table 33 below. Adjust manifold on gas valve to match
time needed.
NOTE−To obtain accurate reading, shutoff all other gas
appliances connected to meter.
Page 50
TABLE 33
GHR32
18M34
63K89
GAS METER CLOCKING CHART
Seconds for One Revolution
GHR32
Unit
−5072144180360
−754896120240
−100367290180
−120306075150
Natural−1000 btu/cu ft LP−2500 btu/cu ft
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
G−Flame Signal
A microamp DC meter is needed to check the flame signal on
the SureLight control. Use a flame signal transducer (part
number 78H5401) available from Lennox to measure the
flame signal, if meter used will not read microamp signal.
Flame (microamp) signal is an electrical current which
passes from the ignition control through the sensor electrode during unit operation. Current passes from the sensor through the flame to ground to complete a safety circuit.
To Measure Flame Signal:
1 − Set the volt meter to the DC voltage scale. Insert trans-
ducer into the VDC and common inputs. Observe correct polarities. Failure to do so results in negative (−)
values.
2 − Turn off supply voltage to control.
3 − Disconnect flame sensor lead from terminal of ignition
control.
4 − Connect (+) lead of transducer to ignition control sen-
sor connection.
5 − Connect (−) lead of the transducer to sensor wire.
6 − Turn supply voltage on and close thermostat contacts
to cycle system.
7 − When unit lights, read voltage on meter display. Re-
member 1 DC volt = 1 DC microamp.
TABLE 34
FLAME SIGNAL MICROAMPS
Boards
Normalu0.23
V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat con-
trol system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand.
3 − In all cases, blower and entire unit will be off when the
system switch is in OFF position.
B−Temperature Rise
Temperature rise for GHR32 units depends on unit input, blower speed, blower horsepower and static pressure as marked
on the unit rating plate. The blower speed must be set for unit
operation within the range of AIR TEMP. RISE °F" listed on
the unit rating plate.
To Measure Temperature Rise:
1 − Place plenum thermometers in the supply and return air
plenums. Locate supply air thermometer in the first horizontal run of the plenum where it will not pick up radiant
heat from the heat exchanger.
2 − Set thermostat to highest setting.
3 − After plenum thermometers have reached their high-
est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check the
firing rate. Provided the firing rate is acceptable, increase
blower speed to reduce temperature. To change blower
speed taps see the Blower Speed Taps section in this
manual.
46M99
18M99
49M59
Boards
24L85
56L83
97L48
Low0.17 to 0.22
Drop Out0.16
Normalu0.61
Low0.21 to 0.60
Drop Out0.20
H− Variable Speed Motor
To check out the VSM blower and blower control board, begin
with the ICM2 motor and follow the procedures outlined in
section IX−TROUBLESHOOTING. The ICM2 consists of a
control module and motor. The control module can be replaced separately form the the motor if necessary. However,
if the motor fails the motor/control module assembly will have
to be replaced.
Page 50
Page 51
C−External Static Pressure
1 − Measure tap locations as shown in figure 49.
2 − Punch a 1/4" diameter hole in
supply and return air plenums. Insert manometer
hose flush with inside edge of
hole or insulation. Seal
around the hose with permagum. Connect the zero end of
the manometer to the discharge (supply) side of the system. On ducted systems,
connect the other end of manometer to the return duct
as above. For systems with non−ducted returns, leave
the other end of the manometer open to the atmosphere.
3 − With only the blower motor running and the evapo-
rator coil dry, observe the manometer reading. Adjust blower motor speed to deliver the air desired according to the job requirements.
4 − Pressure drop must not exceed 0.5" W.C.
5 − Seal around the hole when the check is complete.
GHR32 BLOWER REMOVAL
STATIC PRESSURE
TEST
MANOMETER
FIGURE 49
D−Blower Speed Taps GHR32Q Motors
Blower speed tap changes are made on the SureLight control board. See figure 9. Unused taps must be secured on
dummy terminals "PARK M1" and or "PARK M2" on the
SureLight board. The heating tap is connected to the "ACB
HEAT " terminal and the cooling tap is connected to the
"ACB COOL" terminal. The continuous blower tap is connected to the "ACB LOW" terminal.
To change existing heat tap, turn off power then switch out
speed tap on "ACB HEAT" with tap connected to "PARK
M1" or "PARK M2". See wiring diasgrams for blower motor
tap colors for each speed.
To Remove Blower:
1. Turn off line voltage power. Unplug the following
jack/plugs: J96/P96 power interface, J135/P135
secondary limit, J58/P58 control, J98/P98 CAB.
2. Remove screws (2) and remove control box cover.
Disconnect thermostat wiring connections by removing low voltage terminal strip. Disconnect spark
wire and grommet.
3. Loosen screws (2) and remove control box from unit.
Holes are slotted so screws do not need to be removed.
4. Remove bolts (2) and remove blower from unit.
J69/P69
J98/P98
FIGURE 50
J96/P96
J135/P135
4
3
2
Page 51
Page 52
VI−MAINTENANCE
Retainers for factory supplied return air filter are shown in
figure 51.
CABINET
WRAPPER
FILTER
SIDE FILTER
CLIP DETAIL
Press up on side filter clip to release filter
(One on each side of cabinet)
BACK FILTER CLIP
FILTER CLIP
Press up on side filter clip to release filter
(One on each side of cabinet)
FILTER
FILTER
CLIP
FIGURE 51
A−Filters
At the beginning of each heating season, the system
should be checked as follows:
1 − Filters should be inspected monthly and must be
cleaned or replaced when dirty to ensure proper furnace operation.
2 − Reusable foam filters used with the GHR32 can be
washed with water and mild detergent. When dry, they
should be sprayed with filter handicoater prior to reinstallation. Filter handicoater is RP Products coating
no. 418 and is available as Lennox part no. P-8-5069.
3 − If replacement is necessary, order Lennox part no. 31J81
for 14 X 25 inch (356 X 635mm) filter for GHR32-50 and
-75 units and P-8-7831 for 20 X 25 inch (508 X 635mm)
filter for GHR32-100 and -120 units.
B−Cleaning Heat Exchanger and Burners
NOTE−Use papers or protective covering in front of furnace while cleaning furnace.
Cleaning the heat exchanger is not recommended; but, if it becomes necessary, follow the procedures outlined below and
refer to figure 1 for parts arrangement. Pay close attention to
wire routing and plumbing connections.
If at all possible, the unit should be removed and placed
on its back. Tools needed are: slotted screwdriver, extra
long 1/4" nut driver, extra long 5/16" nut driver, and duckbill pliers.
CABINET
WRAPPER
Heat Exchanger
1 − Turn off electrical and gas power supplies to furnace.
2 − Remove upper and lower furnace access panels.
3 − Remove 3/8" rubber cap from condensate drain plug
and drain. Replace cap after draining.
4 − Disconnect and remove intake pipe from air intake fit-
ting.
5 − Mark all gas valve wires and disconnect them from
valve.
6 − Remove gas supply line connected to gas valve.
Disconnect gas valve sensing hose from side of
burner box. Remove burner box cover by removing six
(four on some units) securing screws. Remove gas valve/
manifold assembly.
7 − Detach burner box from vestibule panel by removing four
securing screws. Take care to avoid damaging the glass
fiber gasket.
8 − Mark and disconnect spark and sensor electric wires
from the ignitor and flame sensor.
9 − Disconnect wires from flame roll−out switch. Remove
wires from patch plates. Remove side plates on burner
box holding sensor and spark electrode. Set burner burner box assembly aside.
NOTE− If burner cleaning is needed, do so at this time.
Refer to burner cleaning procedure.
10− Remove flexible exhaust tee by loosening three
clamps.
11− Disconnect drain line attached to condensate trap. Re-
move screws that secure both condensate collars to either side of the unit and remove collars. It may be necessary to cut the pipe to allow for removal of the condensate
trap. Remove drain tubes from cold end header collector
box.
12− Disconnect condensate drain tubing from exhaust
pipe. Remove screws that secure both flue collars
into place. Remove flue collars. It may be necessary to cut the exiting exhaust pipe to allow for removal of the fittings.
13− Disconnect 2−pin plug from combustion air blower.
Remove combustion air blower from bracket by removing four securing screws. Remove ground wire from
bundle.
14− Remove combustion air blower bracket by removing two
screws from collector box and two screws from vestibule panel.
15− Disconnect combustion air pressure and condensate
sensing hoses from cold end header collector box. Remove pressure hose from two blank stems on cold end
header collector box.
16− Mark and remove wires from pressure switch. Re-
move pressure switch/bracket assembly. Keep
hoses attached to pressure switch. Remove pressure switch installation screws from both sides of
the unit.
17− Disconnect 9−pin and 3− pin plugs at blower deck. Re-
move both plugs from the heat exchanger side of the
blower deck.
18− Remove the primary limit from vestibule panel.
Page 52
Page 53
19− Remove two (2) screws from the front cabinet flange at
the blower deck. Remove front screws from cabinet at
blower deck on left and right sides. Cabinet sides must
be slightly spread apart to clear heat exchanger passage.
NOTE−To protect insulation in horizontal applications,
slide a piece of sheet metal between the coil sec tion of
the heat exchanger and the cabinet when removing
and replacing heat exchanger. Remove indoor
blower for horizontal installations. Remove sheet
metal when complete.
20− Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger assembly to cabinet.
21− With a pair of duck bills, carefully bend bottom flange
straight. Use caution not to damage the cabinet. Remove heat exchanger.
22− Back wash heat exchanger with soapy water solu-
tion or steam. If steam is used it must be below
275_F (135_C).
23− Thoroughly rinse and drain the heat exchanger. Soap
solution can be corrosive so take care that entire assembly is completely rinsed.
24− Re−install heat exchanger into cabinet (blower deck end
first) making sure that the clamshells of the heat exchanger assembly are resting on the supports at
the rear of the cabinet. This can be viewed by removing the indoor blower and examining through
the blower opening.
25− Re−secure the supporting screws along the vestibule
sides and bottom to the cabinet. Carefully bend bottom flange back to a 90 degree angle with a pair of
duck bills. Once again, use caution not to damage the
cabinet.
26− Re−install cabinet screws on sides and front flange at
blower deck.
27− Re−install primary limit to vestibule panel.
28− Re−install 9−pin plug to blower deck and connect it to the
9−pin plug from below the blower deck. Re−install 3−pin
plug to blower deck and connect it to the 3−pin plug from
below the blower deck.
29− Re−install pressure switch/bracket assembly and re-
place pressure switch screws on both sides of unit
from installed pressure switch. Reconnect wires to
pressure switch.
30− Connect combustion air pressure and condensate
sensing hoses from pressure switch to cold end
header collector box. See figure 31to confirm hose
location.
31− Re−install the combustion air bracket.
32− Re−install the combustion air blower to bracket. Re-
connect the 2−pin plug to the wire harness.
33− Replace flue collars with securing screws to either side of
the unit. Reconnect exhaust piping and exhaust
drain tubing.
34− Replace condensate collars with securing screws to
either side of the unit. Reconnect drain line to condensate trap. Reconnect drain tubing from cold end header collector box. Reconnect condensate drain tubing
from exhaust pipe.
35− Replace flexible exhaust tee to combustion air
blower and exhaust pipes and secure with three
clamps.
36− Align burner box gasket to securing holes closest to
the end of the unit. Use a small piece of tape to secure
gasket to vest panel. Make sure glass fiber gasket has
not been damaged so it will provide a continuous seal
between the burner box and the vestibule panel.
patch plates to side of burner box. Connect wires to
patch plates.
39− Reconnect sensor and spark electrode or SureLight
ignitor wires through provided openings in the burner
plate.
40− Replace four screws to secure reassembled burner
box assembly to vestibule panel. Make sure burn-
ers line up in center of burner ports.
41− Re−install gas valve manifold assembly. Replace
burner box cover. Re−install gas supply line to gas
valve. Attach gas valve pressure sensing hose to
burner box.
42− Reconnect gas valve wires to gas valve.
43− Re−install intake vent pipe to rubber connector on in-
take fitting with hose clamp.
44− Replace both upper and lower access panels.
45− Refer to instruction on verifying gas and electrical con-
nections when re−establishing supply.
46− Following lighting instructions, light and run unit for 5
minutes to ensure heat exchanger is clean, dry and
operating safely.
Page 53
Page 54
Cleaning the Burner Assembly
1 − Turn off electrical and gas power supplies to furnace.
2 − Remove upper and lower furnace access panels.
3 − Disconnect and remove intake pipe from air intake fit-
ting.
4 − Mark all gas valve wires and disconnect them from
valve.
5 − Remove gas supply line connected to gas valve.
Disconnect gas valve sensing hose from valve. Remove burner box cover (4 to 6 screws). Remove gas
valve/manifold assembly.
18− Re−install gas valve/manifold assembly. Re−install
burner box cover. Reconnect gas valve sensing hose
to side of burner box. Re−install gas supply line to gas
valve.
19− Reconnect gas valve wires to gas valve.
20− Replace both upper and lower access panels.
21− Refer to instruction on verifying gas and electrical con-
nections when re−establishing supply.
22− Following lighting instructions, light and run unit for 5
minutes to ensure heat exchanger is clean, dry and
operating safely.
6 − Loosen hose clamp holding the air intake pipe to the
no−hub connector on the top of the burner box. Remove pipe from no−hub connector and set aside.
7 − Mark and disconnect spark or SureLight ignitor and
sensor electrical wires from the ignitor and flame sensor.
8 − Detach burner box from vestibule panel by remov-
ing four securing screws. Take care to avoid damaging the glass fiber gasket.
9 − On GHR32−50 and −75 units, remove air intake fitting from
burner box top.
10 − Remove burner box top from burner box assembly.
11− Using 1/4" nut driver, remove two screws holding
burners in place. Slide burner assembly out of burner box.
12− Clean burner by running a vacuum with a soft brush at-
tachment over face of burners. Visually inspect inside
of burners and crossovers for any blockage caused by
foreign matter. Remove any blockage.
13− Re−install burner assembly so that protruding side (not
cavity side) of metal buttons are toward the burner box
top (intake side).
14− Replace top and air intake piece to burner box.
C−Supply Air Blower
1 − Check and clean blower wheel.
2 − Motors are prelubricated for extended life; no further lu-
brication is required.
D−Electrical
1 − Check all wiring for loose connections.
2 − Check circuit breaker located in unit control box.
3 − Check for correct voltage at unit (unit operating).
4 − Check amp-draw on blower motor.
Motor Nameplate_________Actual_________
5 − Check to see that heat (if applicable) is operating.
E−Intake and Exhaust Lines
Check intake and exhaust lines and all connections for
tightness and make sure there is no blockage. Also check
condensate line for free flow during operation.
F−Insulation
Outdoor piping insulation should be inspected yearly for deterioration. If necessary, replace with same materials.
15− Reconnect sensor and spark electrode or SureLight
ignitor wires.
16− Align burner box gasket to securing holes closest to
the end of the unit. Use a small piece of tape to secure
gasket to vest panel. Make sure glass fiber gasket has
not been damaged so it will provide a continuous seal
between the burner box and the vestibule panel.
17− Replace four screws to secure reassembled burner
box assembly to vestibule panel. Make sure burn-
ers line up in center of burner ports.
G−Winterizing and Condensate Trap Care
If the unit is to be shut down for an extended period of time
and will be exposed to sub-freezing temperatures, the unit
should be winterized by draining water from the condensate trap.
To drain condensate trap remove the 3/8" cap located on
the bottom corner of the condensate trap (see figure 46).
Periodically drain condensate trap to insure proper drainage and check for blockage.
Page 54
Page 55
VII−WIRING DIAGRAM AND SEQUENCE OF OPERATION
GHR32Q −1 UNIT DIAGRAM
Page 55
Page 56
GHR32Q −3 UNIT DIAGRAM
Page 56
Page 57
Sequence of Operation GHR32Q −1, −3 Units
Ignitor operation will vary between SureLight boards.
Board 56L83 will energize ignitor for the first second of the
4 second ignition trial. Board 97L48 will energize ignitor
during the entire ignition trial until flame is sensed.
1 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the furnace control with 24VAC.
2 − SureLight control runs self−check for S10 primary limit
switch normally closed contacts and S18 combustion
air prove switch normally open contacts. Follow steps
4 through 8 per respective thermostat.
Single−stage Mode, Single−stage Thermostat
3 − SureLight control energizes combustion air inducer
B6 on high speed. Combustion air inducer runs until
S18 prove switch closes (switch will close within 2−1/2
minutes or control goes into Watchguard−Prove
Switch mode). A 15−second pre−purge follows after
S18 closes.
4 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve is energized on first stage heat (low). Gas
valve opens for a 4−second trial for ignition.
6 − Flame is sensed, After 8 seconds from when gas valve
opens, valve energizes on second stage (high heat).
7 − After 45−second delay, indoor blower B3 is energized
on heating speed.
Two−stage Mode, Single−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until
combustion air proving switch S18 closes (switch will
close within 2−1/2 minutes or control goes into Watchguard−Prove Switch mode). A 15−second pre−purge
follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 − Gas valve is energized on first stage. Gas valve opens
for a 4−second trial for ignition. Signal is sent from control module to two−stage control board to begin W2
(second−stage) ON delay.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 − After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Second stage time on delay complete (8, 12, or 15
minutes). Combustion air inducer B6 switches to high
speed, indoor blower B3 switches to heating speed
and gas valve opens on high heat (second stage.)
Two−stage Mode, Two−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until
combustion air inducer switch S18 closes. Switch will
close within 2−1/2 minutes or control goes into Watchguard−Proving Switch mode). A 15−second pre−purge
follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 − Gas valve is energized on first stage only. Gas valve
opens for a 4−second trial for ignition.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 − After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Call for second stage heat comes from indoor thermo-
stat (W2).
Page 57
Page 58
GHR32Q −5 & −6 UNIT DIAGRAM
Page 58
Page 59
Sequence of Operation. GHR32Q with
SureLight Two Stage Control
Sequence depends on type thermostat used. Units are
applicable for single stage or two stage thermostats.
Both type thermostats are described below. Thermostat jumper E20 dictates which mode unit will operate
in. See flow chart for more sequence detail.
SureLight Control Self Check
When there is a call for heat, the SureLight integrated control runs a self check. The control checks for S10 primary
limit, S21 secondary limit (s) and S47 rollout switch normally closed contacts. The control also checks for S102
prove switch normally open contacts. Once self check is
complete and all safety switches are operational, heat call
can continue.
Two−Stage Thermostat, Two Stage Heat. Jumper E20
set at TWO".
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 closes (switch must close within 2 1/2 minutes or
control goes into Watchguard Pressure Switch mode.
A 15 second pre−purge follows once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until first stage demand is satisfied OR a second stage heat demand is
initiated.
6− Second stage heat demand initiated. A 30 second sec-
ond stage recognition period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Single−Stage Thermostat, Two Stage Heat. Jumper
E20 set at SINGLE"
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
Pressure Switch mode. A 15 second pre−purge follows
once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
6− A 10 minute (factory set) or 15 minute (field set) second
stage heat delay period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Page 59
Page 60
GHR32V −1 UNIT DIAGRAM
Page 60
Page 61
GHR32V −3 UNIT DIAGRAM
Page 61
Page 62
GHR32V −4 UNIT DIAGRAM
Page 62
Page 63
Sequence of Operation GHR32V −1 / −4 Units
Ignitor operation will vary between SureLight boards.
Board 56L83 will energize ignitor for the first second of the
4 second ignition trial. Board 97L48 will energize ignitor
during the entire ignition trial until flame is sensed.
1 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the furnace control with 24VAC.
2 − SureLight control runs self−check for S10 primary limit
switch normally closed contacts and S18 combustion
air prove switch normally open contacts. Follow steps
4 through 8 per respective thermostat.
Single−stage Mode, Single−stage Thermostat
3 − SureLight control energizes combustion air inducer
B6 on high speed. Combustion air inducer runs until
S18 prove switch closes (switch will close within 2−1/2
minutes or control goes into Watchguard−Prove
Switch mode). A 15−second pre−purge follows after
S18 closes.
4 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve is energized on first stage heat (low). Gas
valve opens for a 4−second trial for ignition.
6 − Flame is sensed, After 8 seconds from when gas valve
opens, valve energizes on second stage (high heat).
7 − After 45−second delay, indoor blower B3 is energized
on heating speed.
Two−stage Mode, Single−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until
combustion air proving switch S18 closes (switch will
close within 2−1/2 minutes or control goes into Watchguard−Prove Switch mode). A 15−second pre−purge
follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 − Gas valve is energized on first stage. Gas valve opens
for a 4−second trial for ignition. Signal is sent from control module to two−stage control board to begin W2
(second−stage) ON delay.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 − After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Second stage time on delay complete (8, 12, or 15
minutes). Combustion air inducer B6 switches to high
speed, indoor blower B3 switches to heating speed
and gas valve opens on high heat (second stage.)
Two−stage Mode, Two−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until
combustion air inducer switch S18 closes. Switch will
close within 2−1/2 minutes or control goes into Watchguard−Proving Switch mode). A 15−second pre−purge
follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 − Gas valve is energized on first stage only. Gas valve
opens for a 4−second trial for ignition.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 − After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Call for second stage heat comes from indoor thermo-
stat (W2).
Page 63
Page 64
GHR32V −5 & −6 UNIT DIAGRAM
Page 64
Page 65
Sequence of Operation GHR32V with
SureLight Two Stage Variable Speed Control
Sequence depends on type thermostat used. Units are
applicable for single stage or two stage thermostats.
Both type thermostats are described below. Thermostat jumper E20 dictates which mode unit will operate
in. See flow chart for more sequence detail.
SureLight Control Self Check
When there is a call for heat, the SureLight integrated control runs a self check. The control checks for S10 primary
limit, S21 secondary limit (s) and S47 rollout switch normally closed contacts. The control also checks for S102
prove switch normally open contacts. Once self check is
complete and all safety switches are operational, heat call
can continue.
Two−Stage Thermostat, Two Stage Heat. Jumper E20
set at TWO".
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
Pressure Switch mode. A 15 second pre−purge follows
once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until first stage demand is satified OR a second stage heat demand is
initiated.
6− Second stage heat demand initiated. A 30 second sec-
ond stage recognition period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Single−Stage Thermostat, Two Stage Heat. Jumper
E20 set at SINGLE"
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
Pressure Switch mode. A 15 second pre−purge follows
once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
6− A 10 minute (factory set) or 15 minute (field set) second
stage heat delay period begins.
7− The combustion air inducer ramps up to high heat
Miswiring or improper connections at
roll−out switch.
1.2.4
Nine pin connector failure
1.3.1
120V main power polarity reversed.
ACTION 1 − Check for correct wiring of 120V to
power make up box and transformer.
ACTION 2 − Check 24V wiring to control board.
ACTION 1 − Replace circuit breaker if it is reset
but does not have continuity.
ACTION 2 − If circuit breaker still trips, check for
short.
ACTION 1 − Check that door switch is activated
when door is closed.
ACTION 2 − Check wire connections to switch, replace loose connectors.
ACTION 3 − Check continuity of switch in closed
position. Replace if malfunctioning
ACTION 1 − Check that transformer output is
24V. Replace if malfunctioning
ACTION 1 − If all the above items have been
checked, replace board.
ACTION 1 − Manually reset the roll−out switch
by pushing the top button.
ACTION 2 − Determine the cause of the roll−out
switch activation before leaving furnace.
ACTION 1 − Check continuity across roll−out
switch. Replace roll−out switch if switch is reset
but does not have continuity.
− Check wiring connections to switch.
ACTION 1 − Check 9−pin connector for proper
connection to control board.
ACTION 2 − Check continuity of the multi plug
pin.
ACTION 1 − Check the 120V has line and neutral
correctly input into control.
ACTION 2 − Reverse the line and neutral at the
120V field connection.
.
LED#1−Fast Flash,
LED#2−Slow Flash.
1.4
GHR32Q/V−1 through −4 Units Only
− On initial power up the combustion
air blower does not energize.
− Diagnostic lights flash normal power
on operation.
LED#1−Slow Flash
LED#2−Slow Flash
1.4.1
Open combustion air blower motor circuit.
1.4.2
Failed combustion air blower motor.
Page 77
ACTION 1 − Check for 120V to combustion air
blower. If no power, check wire and connections.
ACTION 1 − If power is present at blower, replace
blower.
Page 78
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
− Diagnostic lights flash the improper
main ground.
LED#1−Alternating Fast Flash
LED#2−Alternating Fast Flash
1.5.1
Improper ground to the unit.
1.5.2
6−Pin connector is improperly at-
tached to the circuit board.
1.5.3
Line voltage is below 75V.
ACTION 1 − Check that the unit is properly
grounded.
ACTION 2 − Install a proper main ground to the
unit
ACTION 1 − Check 6−pin connector for proper
installation. Correctly insert connector into control.
ACTION 1 − Check that the line voltage is above
75V. Determine cause of voltage drop and supply
correct voltage to the control.
PROBLEM 2: UNIT FAILS TO OPERATE IN THE COOLING OR HEATING MODE, BUT COMBUSTION
AIR BLOWER OPERATES CONTINUOUS. GHR32Q/V−1 through −4 UNITS WITH CONTROL BOARDS
DATE CODED AFTER NOV.1 1997, WILL OPERATE IN COOLING WITH COMBUSTION AIR BLOWER
CYCLING 5 SECONDS ON 55 SECONDS OFF, BUT NOT IN THE HEATING MODE.
− Combustion air blower will not start
with a Heating demand.
− Diagnostic lights flash the limit failure
mode.
LED#1−Slow Flash,
LED#2−On
3.2
− Unit operates with a cooling and continuous fan demand.
− Combustion air blower will not start
with a Heating demand.
− Diagnostic lights flash the pressure
−
switch failure code.
LED#1−Off,
LED#2−Slow Flash
3.1.1
Primary or secondary (if equipped) or
rollout limit switch open.
3.1.2
Miswiring of furnace or improper con-
nections at limit switch(es).
3.2.1
Miswiring of furnace or improper con-
nections to combustion air blower.
3.2.2
Pressure switch stuck closed.
ACTION 1 − Check continuity across switch(es).
Switches reset automatically upon cool down.
Rollout switch must be reset manually.
ACTION 2 − Check for restrictions on blower inlet
air (including filter) and outlet air. Determine
cause for limit activation before placing unit back
in operation.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check that the pressure switch is
open without the combustion air blower operating. Replace if malfunctioning
Page 78
Page 79
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES NOT
g
LED#1 Off
ENERGIZE (CONT.).
ConditionPossible CauseCorrective Action/Comments
3.3
− Unit operates with a cooling and con-
tinuous fan demand.
− Combustion air blower will not start
with a Heating demand.
Miswiring of furnace or improper con-
nections to combustion air blower.
3.3.1
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after
heating demand.
ACTION 1 − If there is 120V to combustion air
blower and it does not operate, replace combustion air blower.
LED#1−Off,
3.3.2
Combustion air blower failure.
LED#2−Slow Flash
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
ConditionPossible CauseCorrective Action/Comments
4.1
− Unit operates with a cooling and
continuous fan demand.
− Combustion air blower energizes
with a heating demand.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after
heating demand.
LED#1−Off
LED#2−Slow Flash
Pressure switch does not close due
to incorrect routing of the pressure
Pressure switch does not close due
to obstructions in the pressure tubing.
Pressure switch tubing damaged
Condensate in pressure switch tub-
Pressure switch does not close due
to a low differential pressure across
the pressure switch.
Wrong pressure switch installed in the
unit, or pressure switch is out of cal-
Miswiring of furnace or improper con-
nections at pressure switch.
Pressure switch failure.
4.1.1
switch tubing.
4.1.2
4.1.3
4.1.4
ing.
4.1.5
4.1.6
ibration.
4.1.7
4.1.8
ACTION 1 − Check that the pressure switch tub-
ing is correctly routed. Correctly route pressure
switch tubing.
ACTION 1 − Remove any obstructions from the
pressure tubing and/or taps.
ACTION 1 − Check pressure switch tubing for
leaks. Replace any broken tubing.
ACTION 1 − Check pressure switch tubing for
condensate. Remove condensate from tubing.
Check that the condensate tubing is located correctly.
ACTION 1 − Check the differential pressure
across the pressure switch. This pressure
should exceed the set point listed on the
switch.
ACTION 2 − Check for restricted inlet and exhaust vent. Remove all blockage.
ACTION 3 − Check for proper vent sizing and
run length. See installation instructions.
ACTION 1 − Check that the proper pressure
switch is installed in the unit. Replace pressure
switch if necessary.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − If all the above modes of failure have
been checked, the pressure switch may have
failed. Replace pressure switch and determine if
unit will operate.
Page 79
Page 80
PROBLEM 5: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
rners light but unit shuts off prior
ignite code
ENERGIZES, IGNITOR IS ENERGIZED. (CONT.)
ConditionPossible CauseCorrective Action/Comments
5.1
− Unit operates with a cooling and
continuous fan demand.
− Combustion air blower energizes
with Heating demand.
ACTION 1 − Check line pressure at the gas valve.
Pressure should not exceed 13" WC for both natural and propane. Line pressure should read a
minimum 4.5" WC for natural and 8.0"WC for propane.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check that 24V is supplied to the gas
valve approximately 35 seconds after heat demand is initiated.
ACTION 2 − Replace the valve if 24V is supplied
but valve does not open (check for excessive gas
line pressure before replacing gas valve).
ACTION 3 − Replace the control board if 24V is
not supplied to valve.
PROBLEM 6: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY
ConditionPossible CauseCorrective Action/Comments
6.1
− Burners fire with a heating demand.
−
− Bu
to satisfying T−stat demand.
− Diagnostic lights flash the pressure
switch code.
LED#1−Off
LED#2−Slow Flash
6.2
− Combustion air blower energizes with
a heating demand.
− Burners light but fail to stay lit.
− After 5 tries the control diagnostics
flash the watchguard burners failed to
ignite code.
ACTION 1 − Check vent termination kit installed.
1−1/2" dia. concentric vent (kit60G77) for 50 and
75 inputs and 2" dia. concentric vent (kit 33K97)
for 100 &125 inputs.
ACTION 1 − Check condensate line for proper
vent slope, and any blockage. Condensate
should flow freely during operation of furnace.
Repair or replace any improperly installed condensate lines.
ACTION 1 − Check for restricted vent inlet or exhaust. Remove all blockage.
ACTION 2: Check for proper vent sizing. See
installation instructions.
ACTION 1 − Check that sensor is properly located (page 10) and that the sense wire is
properly attached to both the sensor and the
control.
ACTION 1 − Check for a broken sensor.
ACTION 2 − Test continuity across the sense
wire. If wire or sensor are damaged replace the
component.
ACTION 1 − Check for resistance between the
sensor rod and the unit ground.
ACTION 2 − Check for resistance between the
sensor wire and the unit ground.
ACTION 3 − Correct any shorts found in circuit.
ACTION 1 − Check the microamp signal from
the burner flame. If the microamp signal is below normal, check the sense rod for proper
location or contamination.
ACTION 2 − Replace, clean, or relocate flame
sense rod. If rod is to be cleaned, use steel
wool or replace sensor. DO NOT CLEAN ROD
WITH SAND PAPER. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM. NOTE: Do not attempt to bend
sense rod.
Page 80
Page 81
PROBLEM 6: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
ure.
LED#2−Sl
h
flame failure.
ConditionPossible CauseCorrective Action/Comments
6.3
− Combustion air blower energizes
with a heating demand.
− Burners light.
− Roll−out switch trips during the
heating demand.
− Diagnostic lights flash roll−out fail-
ure.
GHR32Q/V−1 through −4 Units Only
LED#1−On
ow Flas
GHR32Q/V−5 Units
LED#1−Slow Flash
LED#2−On
6.4
− Combustion air blower energizes
with a heating demand.
− Burners light roughly and the unit
fails to stay lit.
− Diagnostic lights flash watchguard
flame failure.
PREMATURELY (CONT.)
6.3.1
Unit is firing above 100% of the
nameplate input.
6.3.2
Gas orifices leak at the manifold con-
nection.
6.3.3
Air leakage at the connections be-
tween the primary heat exchanger,
secondary heat exchanger, and com-
bustion air blower.
6.3.4
Insufficient flow through the heat ex-
changer caused by a sooted or re-
stricted heat exchanger.
6.3.5
Burners are not properly located in
the burner box.
6.4.1
Recirculation of flue gases. This con-
dition causes rough ignitions and op-
eration. Problem is characterized by
nuisance flame failures.
ACTION 1 − Check that the manifold pressure
matches value listed on nameplate. See installation instructions for proper procedure.
ACTION 2 − Verify that the installed orifice size
match the size listed on the nameplate or installation instructions.
ACTION 3 − Check gas valve sensing hose to insure no leaks are present.
ACTION 4 − Check the input rate to verify rate
matches value listed on nameplate.
ACTION 1 − Tighten orifice until leak is sealed.
NOTE: Be careful not to strip orifice threads.
ACTION 2 − Check for gas leakage at the
threaded orifice connection. Use approved method for leak detection (see unit instructions).
ACTION 1 − Check for air leakage at all joints in
the heat exchanger assembly. Condition may
cause high CO2 with high CO.
ACTION 2 − Seal leakage if possible (high temperature silicon is recommended), replace heat
exchanger if necessary, tag and return heat exchanger to proper Lennox personnel.
ACTION 1 − Check for sooting deposits or other
restrictions in the heat exchanger assembly.
Clean assembly as outlined in instruction manual.
ACTION 2 − For GHR32 gas furnaces, check for
proper combustion and flow. CO2 should measure between 6.0% and 8.0% for NAT and 7.0%
and 9.0% for LP. CO should measure below .04%
(400PPM) in an air−free sample of flue gases.
ACTION 1 − Check that the burners are firing into
the center of the heat exchanger openings. Correct the location of the burners if necessary.
ACTION 1 − Check for proper flow of exhaust
gases away from intake vent. Remove any obstacles in front of the intake and exhaust vent
which would cause recirculation.
ACTION 2 − Check for correct intake and exhaust
vent installation.
PROBLEM 7: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE
ConditionPossible CauseCorrective Action/Comments
7.0
− Unit operates correctly but the diagnostic lights flash low flame sense
code.
LED#1−Slow Flash
LED#2−Fast Flash
PREMATURELY (CONT.)
6.5.1
Loose sensor wire connection causes
intermittent loss of flame signal.
7.1.1
Sense rod is improperly located on
the burner.
7.1.2
Sense rod is contaminated.
ACTION 1 − Check that the sensor is properly located.
ACTION 2 − Check that the sense wire is properly
attached to both the sensor and the control. Pay
extra attention to the pin connectors.
ACTION 1 − Check the sense rod for proper location on the burner. Properly locate the sense rod
or replace if rod cannot be located correctly.
ACTION 1 − Check sense rod for contamination
or coated surface. Clean the sense rod with steel
wool or replace sensor. DO NOT USE SAND PAPER TO CLEAN ROD. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM.
PROBLEM 8: RF STATIC DURING TIME FOR IGNITION
ConditionPossible CauseCorrective Action/Comments
8.0
− AM radio interference
8.1.1
Ignitor operation
ACTION 1− Call Technical Support, Dallas
Page 82
Page 83
VSP2−1 Blower Control Board GHR32V−1 / −3 Units
DOES UNIT OPERATE?
YES
IS 24VAC ACROSS
COOLING MODE
PLACE JUMPER ACROSS R AND G.
IS BLOWER ON LOW SPEED AND IS
ON/OFF" LED−DS3 LIT? CFM" LED−DS4
LIGHT SHOULD BLINK ONCE FOR EV-
ERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2.
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP2 BOARD?
IN ADDITION TO R AND G,
JUMPER R AND DS.
NO
R AND C?
YES
YES
YES
NO
CHECK:
1−UNIT POWER
2−INTERLOCK SWITCH
3−TRANSFORMER
4−LIMIT SWITCH
NO
CHECK UNIT WIRING
AND IF CORRECT,
REPLACE VSP2−1.
NO
REPLACE VSP2−1.
END OF COOLING TEST
HEATING MODE
YES
IS BLOWER ON HIGH SPEED AND ARE DS1 AND
DS3 LIT? DOES THE CFM" LED−DS4 LIGHT BLINK
ONCE FOR EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2?
DOES UNIT OPERATE?
YES
IS 24VAC ACROSS
R AND C?
YES
PLACE HTG. BLOWER" JUMPER IN POSITION #2.
PLACE JUMPER ACROSS R AND W1. WAIT 75
SECOND FOR PREPURGE AND FANON" DELAY.
IS BLOWER ON LOW SPEED AND IS ON/OFF" LED−
DS3 LIT? CFM" LED−DS4 LIGHT SHOULD BLINK
ONCE FOR EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2.
YES
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP2 BOARD?
YES
PLACE HTG. BLOWER"
JUMPER IN POSITION #1.
R AND W1 REMAIN JUMPERED.
NO
NO
NO
NO
CHECK UNIT WIRING
AND IF CORRECT
REPLACE THE
VSP2−1.
CHECK:
1−UNIT POWER
2−INTERLOCK SWITCH
3−TRANSFORMER
4−LIMIT SWITCH
1−CHECK UNIT WIRING AND IF
CORRECT, REPLACE
2−BREAK AND REMAKE JUMPER
VSP2−1.
(R TO W1).
3−AFTER 30−35 SECOND
PURGE, IS 24VAC PRESENT
AT GAS VALVE?
REPLACE VSP2−1.
END OF TEST
DOES BLOWER SHIFT TO HEAT SPEED
AND IS HEAT" LED−DS2 ON? DOES THE
CFM" LED−DS4 LIGHT BLINK ONCE
FOR EVERY 100 CFM SELECTED IN
THE TABLES ON PAGE 2?
YES
REMOVE JUMPERS
YES
AFTER THE SELECTED
TIME, DOES BLOWER
TURN OFF?
Page 83
NO
NO
CHECK UNIT WIRING
AND IF CORRECT,
REPLACE VSP2−1.
REPLACE THE VSP2−1.
Page 84
VSP3−1 Blower Control Board GHR32V−4 Units
DOES UNIT OPERATE?
YES
IS 24VAC ACROSS
COOLING MODE
PLACE JUMPER ACROSS R, G, AND Y1.
IS BLOWER ON LOW SPEED AND IS ON/
OFF LED−DS3 AND HI/LOW LED−DS1 LIT?
CFM LED−DS4 LIGHT SHOULD BLINK ONCE
FOR EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2.
NO
R AND C?
YES
YES
NO
CHECK:
1−UNIT POWER
2−INTERLOCK SWITCH
3−TRANSFORMER
4−LIMIT SWITCH
NO
CHECK UNIT WIRING AND IF
CORRECT, REPLACE VSP3−1.
END OF COOLING TEST
HEATING MODE
YES
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP3 BOARD?
YES
IN ADDITION TO R G, AND Y1
JUMPER R AND Y2.
IS BLOWER ON HIGH SPEED AND ARE DS1 AND
DS3 LIT? DOES THE CFM LED−DS4 LIGHT BLINK
ONCE FOR EVERY 100 CFM SELECTED IN THE
YES
PLACE HTG. BLOWER JUMPER IN POSITION #2.
PLACE JUMPER ACROSS R AND W1. WAIT 75 SEC-
OND FOR PREPURGE AND FAN ON DELAY.
IS BLOWER ON LOW SPEED AND IS ON/OFF"
LED−DS3 LIT? CFM" LED−DS4 LIGHT SHOULD
BLINK ONCE FOR EVERY 100 CFM SELECTED IN
TABLES ON PAGE 2?
DOES UNIT OPERATE?
IS 24VAC ACROSS
R AND C?
YES
THE TABLES ON PAGE 2.
YES
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP3 BOARD?
NO
NO
NO
REPLACE VSP3−1.
NO
NO
CHECK UNIT WIRING
AND IF CORRECT
REPLACE THE
VSP3−1.
CHECK:
1−UNIT POWER
2−INTERLOCK SWITCH
3−TRANSFORMER
4−LIMIT SWITCH
1−CHECK UNIT WIRING AND IF
CORRECT, REPLACE VSP3−1.
2−BREAK AND REMAKE JUMPER
(R TO W1).
3−AFTER 30−35 SECOND PURGE,
IS 24VAC PRESENT AT GAS
VALVE?
REPLACE VSP3−1.
CFM" LED−DS4 LIGHT BLINK ONCE FOR
END OF TEST
YES
YES
PLACE HTG. BLOWER
JUMPER IN POSITION #1.
R AND W1 REMAIN JUMPERED.
DOES BLOWER SHIFT TO HIGH SPEED
AND IS HEAT" LED−DS2 ON? DOES THE
EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2?
YES
REMOVE JUMPERS
AFTER THE SELECTED
TIME, DOES BLOWER
TURN OFF?
Page 84
NO
NO
CHECK UNIT WIRING
AND IF CORRECT,
REPLACE VSP3−1.
REPLACE THE VSP3−1.
Page 85
ICM−2 WITH VSP2
120V to the motor must not be interupted. All connections for check out
will be from the voltage source below (battery or 24V) to plug J46, after
disconnectiong from blower control board VSP2.
J46
1
13
1
CHECK−OUT PROCEDURE USING BATTERY
An ordinary 9 volt battery with maximum DC
20volts is recommended. A 9 volt battery will
last for about one day of normal operation.
LOW SPEED CHECK−OUT
12345678 910111213
J46
1− Disconnect power to unit.
2− Disconnect plug J46 from P46 located on the
blower control board.
3− Connect voltage source as shown above.
4− Turn on power to unit. Blower should operate
at low speed.
HIGH SPEED CHECK−OUT
12345678 910111213
J46
13
CHECK−OUT PROCEDURE USING 24V SOURCE
Unit transformer T1 with a maximum AC 30 volts
may be used in lieu of a battery. If transformer T1
is used, double check all wiring connections before placing unit back in operation.
LOW SPEED CHECK−OUT
12345678 910111213
J46
C
R
1− Disconnect power to unit.
2− Disconnect plug J46 from P46 located on the
blower control board.
3− Disconnect C and R from control board.
4− Connect voltage source as shown above.
5− Turn on power to unit. Blower should operate
at low speed.
HIGH SPEED CHECK−OUT
12345678 910111213
J46
C
5− Disconnect power to unit.
6− Connect voltage source as shown above.
7− Turn on power to unit. Blower should operate
at high speed.
HEATING SPEED CHECK−OUT
12345678 910111213
J46
8− Disconnect power to unit.
9− Connect voltage source as shown above.
10−Turn on power to unit. Blower should operate
at heating speed.
R
6− Disconnect power to unit.
7− Connect voltage source as shown above.
8− Turn on power to unit. Blower should operate
at high speed.
HEATING SPEED CHECK−OUT
12345678 910111213
J46
C
R
9− Disconnect power to unit.
10− Connect voltage source as shown above.
11− Turn on power to unit. Blower should operate
at heating speed.
A kit is available from the Lennox parts center to use in testing the variable speed motor. The kit 70J11 includes a test plug
harness to facilitate ICM−2 check−out. Follow testing procedures outlined in the instructions provided with the kit.
The testing procedures are different than those listed above.
Page 85
Page 86
ICM−2 WITH VSP3
120V to the motor must not be interupted. All connections for check out
will be from the voltage source below (battery or 24V) to plug J46, after
disconnectiong from blower control board.
CHECK−OUT PROCEDURE USING BATTERY
An ordinary 9 volt battery with maximum DC
20volts is recommended. A 9 volt battery will
last for about one day of normal operation.
LOW COOL SPEED
1 2 3 4 5 6 7 8 9 10111213
J46
1− Disconnect power to unit.
2− Disconnect plug J46 from P46 located on the
blower control board.
3− Connect voltage source as shown above.
4− Turn on power to unit. Blower should operate
at low cool speed.
HIGH COOL SPEED
12345678 910111213
5− Disconnect power to unit.
6− Connect voltage source as shown above.
7− Disconnect Y" on ignition control AND re-
move connection from Y2" on TB1 in control
box. Connect a seperate wire between the −
side of the battery and BOTH Y" on the ignition control and Y2" on TB1.
8− Turn on power to unit. Blower should operate
at high cool speed.
LOW HEAT SPEED
12345678 910111213
J46
To W" on ignition control board. !
9− Disconnect power to unit.
10− Connect voltage source as shown above.
11− Disconnect W" terminal on ignition control
board and connect a seperate wire between
W" and + side of battery.
12− Turn on power to unit. Blower should oper-
ate at low heat speed.
To Y2" on TB1.!
To Y" on ignition control. !
CHECK−OUT PROCEDURE USING 24V SOURCE
Unit transformer T1 with a maximum AC 30 volts
may be used in lieu of a battery. If transformer T1
is used, double check all wiring connections before placing unit back in operation.
LOW COOL SPEED
12345678 910111213
J46
C
1− Disconnect power to unit.
R
2− Disconnect plug J46 from P46 located on the
blower control board.
3− Disconnect C and R from ignition control
board.
4− Disconnect Y" from ignition control and con-
nect a seperate wire between R" on the
transfomer and Y" on the ignition control.
5− Connect voltage source as shown above.
6− Turn on power to unit. Blower should operate
at low cool speed.
To Y" on ignition control. !
HIGH COOL SPEED
1 2 3 4 5 6 7 8 9 1011 1213
J46
C
R
7− Disconnect power to unit.
8− Connect voltage source as shown above.
9− Disconnect Y2" on TB1 in control box and
connect a seperate wire between R" on
transformer and Y2" on TB1.
10− Turn on power to unit. Blower should oper-
ate at high cool speed.
LOW HEAT SPEED
12345678910111213
J46
C
R
11− Disconnect power to unit.
11− Connect voltage source as shown above.
12− Disconnect W" from ignition control and
connect a seperate wire between R" on
transformer and W" on the ignition control.
13− Turn on power to unit. Blower should operate
at low heat speed.
To W" on on ignition control. !
To Y2" on TB1.!
HIGH HEAT SPEED
12345678 910111213
J46
To W2" on TB1 !
13− Disconnect power to unit.
14− Connect voltage source as shown above.
15−Disconnect W2" on TB1 in control box and
connect a seperate wire between W2" and +
side of battery.
16−Turn on power to unit. Blower should operate
at high heat speed.
Page 86
HIGH HEAT SPEED
12345678 910111213
J46
C
R
14− Disconnect power to unit.
15− Connect voltage source as shown above.
16− Disconnect W2" from TB1and connect a
seperate wire between R" on transformer
and W2" on TB1.
17− Turn on power to unit. Blower should operate
at low heat speed.
To W2" on TB1 !
Page 87
ICM−2 WITH TWO STAGE VARIABLE SPEED CONTROL BOARD
120V to the motor must not be interrupted. All connections for check out will be from the voltage source below (battery or 24V) to plug J46, after disconnecting from blower control board.
REMOVE PLUG FROM BOARD
1
CHECK−OUT PROCEDURE USING BATTERY
An ordinary 9 volt battery with maximum DC
20volts is recommended. A 9 volt battery will
last for about one day of normal operation.
LOW
COOL
J46
SPEED
1− Disconnect power to unit.
2− Disconnect plug J46 from P46 located on the blower control board.
3− Connect voltage source as shown above.
4− Turn on power to unit. Blower should operate at low cool speed.
HIGH
COOL
SPEED
J46
16
CHECK−OUT PROCEDURE USING 24V SOURCE
Unit transformer T1 with a maximum AC 30 volts
may be used in lieu of a battery. If transformer T1
is used, double check all wiring connections before placing unit back in operation.
C
LOW
COOL
R
J46
SPEED
1− Disconnect power to unit.
2− Disconnect plug J46 from P46 located on the blower control board.
3− Connect voltage source as shown above.
4− Turn on power to unit. Blower should operate at low cool speed.
HIGH
C
R
COOL
SPEED
J46
5− Disconnect power to unit.
6− Connect voltage source as shown above.
7− Turn on power to unit. Blower should operate at high cool speed.
LOW
HEAT
J46
SPEED
8− Disconnect power to unit.
9− Connect voltage source as shown above.
10− Turn on power to unit. Blower should operate at low heat speed.
HIGH
HEAT
SPEED
11− Disconnect power to unit.
12− Connect voltage source as shown above.
13− Turn on power to unit. Blower should operate at high heat speed.
5− Disconnect power to unit.
6− Connect voltage source as shown above.
7− Turn on power to unit. Blower should operate at high cool speed.
C
LOW
HEAT
R
J46
SPEED
8− Disconnect power to unit.
9− Connect voltage source as shown above.
10− Turn on power to unit. Blower should operate at low heat speed.
C
HIGH
HEAT
SPEED
11− Disconnect power to unit.
12− Connect voltage source as shown above.
13− Turn on power to unit. Blower should operate at high heat speed.
R
J46J46
Page 87
Page 88
Page 88
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (HEATING)
MATCH UPCOMMENTS OR SEQUENCE
Single-Stage Heating
with Single−Stage
Thermostat
Blower operates on the high
speed heat tap during the
heating mode.
Two-Stage Heating
With Single−Stage
Thermostat
No
Jumpers
Blower operates on the low
speed heat/cool tap during the
first stage of heating. Blower
operates on the high speed
heat tap during second stage
heating.
Harmony HeatingNo
Jumpers
Blower operates on PWM
signal generated by Har-
mony. Harmony overrides
blower speed taps. Blower
speed varies according to
zone demand.
TABLE 35
FOR COOLING JUMPERS
SEE COOLING SECTION
BELOW
T−Strip
Jumper
Mode of
Operation
No
Jumpers
One−Stage
W2 Timed
Two−Stage
Remove pin #3 of the J73
plug on the VSP control.
See fig. 16. Insulate end to
prevent it from shorting.
Low and high fire controlled by
temperature modulating switch.
(continued on following page)
Jumper
Page 89
Page 89
MATCH UPCOMMENTS OR SEQUENCE
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (COOLING)
Two-Speed Compressor,
no CCB1, no Harmony
Blower operates on low
speed heat/cool tap when
compressor is in first
stage cooling. Blower operates on high speed cool
tap when compressor is in
second stage cooling.
DS" to Y2"
Single-Speed Com-
pressor, no CCB1,
no Harmony
Blower operates on high speed
cool tap during cooling.
(continued on following page)
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (HEATING CONTINUED)
Two−Stage Heating
With Two−Stage
Thermostat
No
Jumpers
Two−StageBlower operates on the low
speed heat/cool tap during first
stage heating. Blower operates
on high speed heat tap during
second stage heating.
MATCH UP
COMMENTS OR SEQUENCE
T−STRIP JUMPER
T−Strip
Jumper
Mode of
Operation
DS to Y1"
Move factory
wired jumper from
Y1 to Y2".
(continued from previous page)
(factory wired)
Jumper
Y1
Y2
Remove Jumper
DS to Y1"
Blower operates on low speed
heat/cool during cooling
Page 90
Page 90
MATCH UPCOMMENTS OR SEQUENCE
GHR32V−1 / −3UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (COOLING CONTINUED)
CCB1 with Two-Speed
Compressor, no Harmony
Blower speed is controlled by
the DC signal from CCB1.
Blower operates on low speed
heat/cool tap during dehumidi-
fication. Otherwise, blower op-
erates on high speed cool tap
during high speed compressor
operation and low speed heat/
cool tap during low speed
compressor operation.
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
CCB1 with Single-Speed
Compressor, no Harmony
Blower speed is controlled by
the DC signal from CCB1.
Blower operates on low speed
heat/cool tap during dehumidification. Otherwise, blower oper-
ates on high speed cool tap
during cooling cycle.
No Jumpers
(Remove jumper
from Y1 to DS")
T−STRIP JUMPER
No Jumpers
(Remove jumper
from Y1 to DS")
(continued from previous page)
(continued on following page)
Y1
Y2
Page 91
Page 91
MATCH UPCOMMENTS OR SEQUENCEWIRING CONNECTIONS
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (COOLING CONTINUED)
Harmony and Two-
Speed Compressor
Harmony and Single-
Speed Compressor
No Jumpers
(Remove
jumper from
Y1 to DS").
Remove pin #3 of the J73
terminal on the VSP con-
trol. Insulate end to pre-
vent shorting. Blower oper-
ates on PWM signal gener-
ated by Harmony. Harmony
overrides blower speed
taps. Blower speed varies
according to zone demand.
(continued from previous page)
FOR HEATING JUMPERS
SEE SEE HEATING SECTION
ABOVE
T−STRIP JUMPER
No Jumpers
(Remove
jumper from
Y1 to DS").
Remove pin #3 of the J73
terminal on the VSP con-
trol. Insulate end to pre-
vent shorting. Blower oper-
ates on PWM signal gener-
ated by Harmony. Harmony
overrides blower speed
taps. Blower speed varies
according to zone demand.
Page 92
Page 92
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (HEATING)
MATCH UP
COMMENTS OR SEQUENCE
Single-Stage Heating
with Single−Stage
Thermostat
Blower operates on
high speed during the
heating mode.
Two-Stage Heating
With Single−Stage
Thermostat
No
Jumpers
Blower operates on low
speed during the first stage
of heating. Blower operates
on high speed during
second−stage heating.
Harmony HeatingNo
Jumpers
Blower operates on PWM signal
generated by Harmony. Harmo-
ny overrides blower speed taps.
Blower speed varies according
to zone demand.
TABLE 36
WIRING CONNECTIONS
FOR COOLING JUMPERS
SEE COOLING SECTION
BELOW
T−Strip
Jumper
Mode of
Operation
No
Jumpers
One−Stage
W2 Timed
Two−Stage
Remove pin #3 of the J73 plug on
the VSP control, and pins #2
and 13 of the J49 plug at the
motor. See fig 19 and 39. Insulate
ends to prevent them from shorting.
Low and high fire controlled by
temperature modulating switch.
(continued on following page)
Jumper
TEMPERATURE
SWITCH
MODULATING
Page 93
Page 93
MATCH UP
COMMENTS OR SEQUENCE
WIRING CONNECTIONS
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (COOLING)
Two-Speed Compressor,
no CCB1, no Harmony
Blower operates on low speed
cool when compressor is in
first stage cooling.
Blower operates on high
speed cool when compressor
is in second stage cooling.
DS to Y1
and
O to R
Remove factory−wired
jumper Y1 to Y2.
Single-Speed Com-
pressor, no CCB1,
no Harmony
Blower operates on high speed
during cooling.
(continued on following page)
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (HEATING CONTINUED)
MATCH UP
COMMENTS OR SEQUENCE
WIRING CONNECTIONS
T−STRIP JUMPER
T−Strip
Jumper
Mode of
Operation
DS to Y1
and Y1 to Y2
and O to R
(continued from previous page)
(factory wired)
Jumper
Two−Stage Heating
With Two−Stage
Thermostat
No
Jumpers
Two−Stage
Blower operates on low
speed during first stage
heating. Blower operates on
high speed during second
stage heating.
Y1
Y2
Blower operates on low speed
during cooling.
Remove jumper
DS to Y1
Page 94
Page 94
MATCH UPCOMMENTS OR SEQUENCE
WIRING CONNECTIONS
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (COOLING CONTINUED)
CCB1 with Two-Speed
Compressor, no Harmony
See table 9.
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
CCB1 with Single-Speed
Compressor, no Harmony
Blower speed is controlled
by the DC signal from
CCB1. Blower operates on
low speed during
dehumidification.
Otherwise, blower operates
on high speed during
cooling cycle.
Y1 to Y2
and
O to R
Remove the
factory−wired
jumper
Y1 to DS.
T−STRIP JUMPER
O to R
Remove jumper
from Y1 to DS
and
Y1 to Y2.
(continued from previous page)
(continued on following page)
Y
1
Y
2
Page 95
Page 95
MATCH UPCOMMENTS OR SEQUENCE
WIRING
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (COOLING CONTINUED)
Harmony and
Two-Speed Compressor
Y1 to Y2
and
O to R
(Remove
jumper from
Y1 to DS.)
Remove the wire from Pin #2 and
Pin #13 of the J49 harness connec-
tor at the motor and the wire from
Pin #3 of the J73 harness connec-
tor on the VSP control board.
Insulate the wire ends and secure
them to prevent shorting. Blower
operates on PWM signal generated
by the Harmony control board con-
trol board. The Harmony control
board overrides blower speed taps.
Blower speed varies according to
the zone’s demand.
(continued from previous page)
FOR HEATING JUMPERS
SEE SEE HEATING SECTION
ABOVE
T−STRIP JUMPER
O to R
(Remove jumper
from Y1 to DS
and Y1 to Y2.)
Remove the wire from Pin #2 and Pin
#13 of the J49 harness connector at
the motor and the wire from Pin #3 of
the J73 harness connector on the
VSP control board.
Insulate the wire ends and secure
them to prevent shorting. Blower op-
erates on PWM signal generated by
the Harmony control board.
The Harmony control board overrides
blower speed taps. Blower speed
varies according to zone’s demand.
CONNECTIONS
Harmony and
Single-Speed
Compressor
Page 96
Thermostat
1 Heat / 1 Cool
NOTE − Use dip
switch 3 to set
second−stage
heat ON delay.
ON−10 minutes.
OFF−15 minutes.
Table 37
GHR32V−5 Units Field Wiring Applications
Jumper Settings (See figure 21)
E20
Term. Strip
Y1 to Y2
W914W951
SINGLEYe sIntactIntact
Wiring Connections
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 1 Cool
with CCB1
NOTE − Use dip
switch 3 to set
second−stage
heat ON delay.
ON−10 minutes.
OFF−15 minutes.
SINGLEYe sCutIntact
S1
T’STAT
CCB1
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 96
Page 97
Thermostat
1 Heat / 2 Cool
NOTE − Use dip
switch 3 to set
second−stage
heat ON delay.
ON−10 minutes.
OFF−15 minutes.
Table 37
GHR32V−5 Units Field Wiring Applications (Continued)
Jumper Settings (See figure 21)
E20
Term. Strip
Y1 to Y2
W914W951
SINGLENoIntactIntact
Wiring Connections
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool
SINGLENoCutIntact
with CCB1
NOTE − Use dip
switch 3 to set
second−stage
heat ON delay.
ON−10 minutes.
OFF−15 minutes.
2 Heat / 2 CoolTWONoIntactIntact
S1
T’STAT
S1
T’STAT
CCB1
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
2 Heat / 2 Cool
TWONoCutIntact
with CCB1
Page 97
S1
T’STAT
CCB1
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 98
Table 37
GHR32V−5 Units Field Wiring Applications (Continued)
Jumper Settings (See figure 21)
Thermostat
E20
Term. Strip
Y1 to Y2
W914W951
2 Heat / 1 CoolTWOYesIntactIntact
Wiring Connections
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
FM21 Heat
Pump / 1 Cool
Harmony
Application*
2 Heat / 1 Cool
SINGLEYe sIntactCut
TWOYesCutIntact
*Disconnect existing
furnace transformer
and replace with 75VA,
24V transformer if defrost option to be used.
75VA, 24V
TRANSFORMER*
NOTE − Wiring connections to outdoor unit and
thermostat made at
FM21 control board per
FM21 instructions.
TEMP.
MOD.
SWITCH
FAN LO
FAN LINE
HARMONY
CONTROL
TERM. STRIP
CONTROL
TERM.
STRIP
FM21
NOTE −
Remove
Y1/Y2 jumper
for two−stage
cooling.
OUT-
DOOR
UNIT
Harmony
TWONoCutIntact
Application*
2 Heat / 2 Cool
*Cut wires at pin positions 2 and 13 of J/P46. Insulate ends to prevent a short. Blower operates on PWM signal generated by Harmony. Harmony
overrides blower speed taps. Blower speed varies according to zone demand. Low and high−fire controlled by temperature modulating switch.
Page 98
TEMP.
MOD.
SWITCH
FAN LO
FAN LINE
HARMONY
CONTROL
TERM.
STRIP
OUT-
DOOR
UNIT
Page 99
SERVICE NOTES
Page 99
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.