Lennox GHR32Q, GHR32V Unit Information

Page 1
Service Literature
GHR32Q/V SERIES UNITS
Units are factory equipped for use with natural gas. A kit is available for conversion to LPG operation. GHR32−1 through −4 units are equipped with the Lennox SureLight silicon nitride ignition system. GHR32−5 units are equipped with the two stage (V models will have the vari­able speed control) integrated control board. Each GHR32 unit meets the California Nitrogen Oxides (NOx) Standards and California Seasonal Efficiency require­ments. The gas valve is redundant to assure safety shut−off as required by A.G.A. and C.G.A.
The heat exchanger, burners and manifold assembly can be removed for inspection and service. The maintenance section gives a detailed description on how this is done.
Information contained in this manual is intended for use by qualified service technicians only. All specifica-
tions are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
TABLE OF CONTENTS
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications Q Models 2. . . . . . . . . . . . . . . . . . . . . . . .
Blower performance Q Models 3. . . . . . . . . . . . . . . . . .
Specifications V Models 4. . . . . . . . . . . . . . . . . . . . . . . .
Blower performance V Models 5. . . . . . . . . . . . . . . . . . .
Parts Arrangement 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
I Unit Components 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Placement and Installation 41. . . . . . . . . . . . . . . . . . . .
III Start Up 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating System Service Checks 47. . . . . . . . . . . . . .
V Typical Operating Characteristics 49. . . . . . . . . . . . . .
VI Maintenance 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32Q/V
Corp. 0001−L2
Revised 08−2004
DOWN FLOW
POSITION
GHR32Q MODEL SHOWN
VII Wiring Diagram and Sequence of Operation 54. . . .
GHR32Q−1 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32Q−3 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32Q−5 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−1 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−3 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−4 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GHR32V−5 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII Operating Flow Charts 65. . . . . . . . . . . . . . . . . . . . . .
IX Troubleshooting 76. . . . . . . . . . . . . . . . . . . . . . . . . . . .
X Blower Control Board Jumper Summary 87. . . . . . . .
Page 1
© 2000 Lennox Industries Inc.
Litho U.S.A.
Page 2
SPECIFICATIONS GHR32Q MODELS
I
(kW)
O
(kW)
Temperature rise
Blower wheel nominal
Nominal cooling
Intake
Kit
()
()
()
10.0 (2.49)
10.0 (2.49)
10.0 (2.49)
Kit #67K27
Model No. GHR32Q2/3-50 GHR32Q3-75 GHR32Q4/5-100 GHR32Q4/5-120
nput  Btuh
utput  Btuh
A.F.U.E. 90.0%
California Seasonal Efficiency 83.7% 83.9% 85.3% 84.0%
Exhaust pipe connection (PVC) diameter  in. (mm) 2 (51)
Intake pipe connection (PVC) diameter  in. (mm) 2 (51)
Condensate drain connection (PVC)  in. (mm) 1/2 (12.7)
Temperature rise range  _F (_C)
High static certified by (A.G.A./C.G.A.)  in wg. (Pa) .50 (125)
Gas Piping Size I.P.S.  in. (mm) 1/2 (12.7)
Blower wheel nominal
diameter x width
Number and size of filters − in. (mm) (1) 14 x 25 x 1 (356 x 635 x 25) (1) 20 x 25 x 1 (508 x 635 x 25)
Blower motor output  hp (W) 1/3 (249) 1/2 (373) 3/4 (560)
Nominal cooling
that can be added
Shipping weight  lbs. (kg) 1 package 147 (67) 155 (70) 196 (89) 205 (93)
Electrical characteristics 120 volts  60 hertz  1 phase (less than 12 amps)
High Fire 50,000 (14.7) 72,000 (21.1) 100,000 (29.3) 118,000 (34.6)
Low Fire 34,000 (10.0) 51,000 (14.9) 68,000 (19.9) 81,600 (23.9)
High Fire 47,000 (13.8) 67,000 (19.6) 93,000 (27.2) 111,000 (32.5)
Low Fire 31,600 (9.3) 47,000 (13.8) 63,000 (18.4) 75,900 (22.2)
High Fire 30 − 60 (17 − 33) 40 − 70 (22 − 39) 45 − 75 (25 − 42)
Low Fire 25 − 55 (14 − 31) 35 − 65 (20 − 36) 40 − 70 (22 − 39)
in. 10 x 8 11-1/2 x 9
mm 254 x 203 292 x 229
Tons 2 to 3 2 to 3.5 3.5 to 5
kW 7.0 to 10.6 7.0 to 12.3 12.3 to 17.6
Optional Accessories (Must Be Ordered Extra)
LPG/Propane kit 59L81 (−1 and −2 models) 11M57 (−3 and later models)
Down-Flow Additive Base 32K52 32K53
Horizontal Support Frame Kit  Ship. Wt. − lbs. (kg.) 56J18  18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits 60G77 − For 1 1/2 inch (38 mm) venting
Roof
Vent/
Intake
Kits
Twinning Kit 15L38 (all models)
Condensate Drain Heat Cable 26K68 6 ft. (1.8 m)  26K69 24 ft. (7.3 m)  26K70 50 ft. (15.2 m)
Heat Cable Tape 39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.Determine from venting tables proper intake and exhaust pipe size and termination kit required.Cleanable polyurethane frame type filter.
Termination
Kits
Wall
Termination
s
For 2 inch (51 mm) venting 15F75 Not Available
For 3 inch (76 mm) venting Not Available 44J41
For 2 inch (51 mm) venting
15F74 (ring kit) − 22G44 (close couple) − 30G28 (WTK Close Cou-
30G79 (WTKX close couple with extension riser)
For 3 inch (76 mm) venting Not Available 44J40 (close couple)  81J20 (WTK close couple)
ple)
33K97 − For 2 inch
(51 mm) venting
60L46 − For 3 inch
(76 mm) venting
Not Available
HIGH ALTITUDE
No gas pressure adjustment is needed when operating from 0 to 4500 ft. (0 to 1372m). See table below for correct manifold pressure and prove switch for altitudes greater than 4500 ft. (1372m).
Model No. Prove Switch
GHR32−50 nat no change 3.5 (0.87) 3.5 (0.87) 3.5 (0.87)
GHR32−75 nat
GHR32−100 nat
GHR32−120 L.P.
GHR32−50 L.P.
GHR32−75 L.P.
GHR32−100 L.P.
HGR32−120 L.P.
Kit #67K27 3.4 (0.85) 3.3 (0.82) 3.2 (0.80)
no change
Manifold Pressure (outlet) in. w.g. (kPa)
4501 to 5500 ft.
(1373 to 1676m)
10.0 (2.49) 10.0 (2.49) 10.0 (2.49)
9.6 (2.39) 9.3 (2.31) 9.0 (2.24)
5501 to 6500 ft.
(1677 to 1981m)
6501 to 7500 ft.
(1982 to 2286m)
Page 2
Page 3
BLOWER PERFORMANCE DATA Q MODELS
External Static
External Static
External Static
External Static
GHR32Q2/3-50 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 1480 700 640 1330 630 520 1070 505 435 900 425 355 .10 25 1430 675 615 1290 610 500 1050 495 420 880 415 346 .20 50 1380 650 595 1240 585 480 1040 490 400 870 410 330 .30 75 1320 625 570 1200 565 455 1010 475 380 850 400 320 .40 100 1260 595 545 1140 540 430 980 460 370 820 385 300 .50 125 1200 565 520 1080 510 410 930 440 320 790 375 280 .60 150 1100 520 500 1000 470 385 860 405 300 740 350 265 .70 175 1000 470 470 890 420 370 750 355 290 660 310 250 .80 200 800 380 440 700 330 340 590 280 280 550 260 240
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium-Low Low
GHR32Q3-75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 1650 780 720 1540 725 585 1450 685 540 1230 580 450 .10 25 1590 750 660 1490 705 550 1400 660 505 1200 565 420 .20 50 1520 715 645 1430 675 520 1350 635 485 1170 550 405 .30 75 1440 680 630 1370 645 490 1300 615 450 1130 535 390 .40 100 1370 645 610 1300 615 470 1240 585 430 1090 515 370 .50 125 1300 615 590 1240 585 450 1170 550 410 1040 490 330 .60 150 1210 570 560 1170 550 430 1100 520 375 970 460 320 .70 175 1120 530 540 1080 510 410 1020 480 350 890 420 280 .80 200 1020 480 515 980 460 380 900 425 325 750 355 260 .90 225 880 415 500 820 385 350 750 355 300 600 285 240
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium-Low Low
GHR32Q4/5-100 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 2530 1195 1360 2300 1085 1210 2030 960 1050 1780 840 885 1540 725 745 .10 25 2460 1160 1290 2250 1060 1140 2010 950 1010 1760 830 850 1530 720 730 .20 50 2380 1125 1270 2200 1040 1100 1990 940 990 1740 820 830 1520 715 720 .30 75 2310 1090 1250 2150 1015 1080 1950 920 970 1720 810 805 1510 715 710 .40 100 2250 1060 1200 2090 985 1060 1910 900 950 1690 800 790 1500 710 690 .50 125 2180 1030 1150 2020 955 1020 1870 880 910 1660 785 780 1480 700 670 .60 150 2100 990 1100 1960 925 980 1810 855 870 1620 765 760 1430 675 650 .70 175 2010 950 1070 1880 885 940 1750 825 855 1570 740 730 1380 650 630 .80 200 1910 900 1040 1800 850 920 1680 795 840 1500 710 710 1320 625 615 .90 225 1800 850 1010 1700 800 890 1580 745 800 1420 670 690 1240 585 600
1.00 250 1700 800 980 1600 755 870 1500 710 780 1320 625 670 1120 530 590
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium Medium-Low Low
Air Volume and Motor Watts at Specific Blower Taps
Air Volume and Motor Watts at Specific Blower Taps
Air Volume and Motor Watts at Specific Blower Taps
GHR32Q4/5-120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0 0 2400 1135 1250 2270 1070 1140 2060 970 1010 1800 850 860 1560 735 720 .10 25 2350 111 0 1220 2220 1050 1100 2040 965 980 1780 840 830 1550 730 705 .20 50 2290 1080 1200 2170 1025 1080 2000 945 960 1750 825 815 1540 725 685 .30 75 2220 1050 1180 2120 1000 1060 1960 925 940 1720 810 800 1520 715 675 .40 100 2150 1015 1130 2050 965 1020 1900 895 920 1680 795 770 1500 710 660 .50 125 2080 980 1100 1980 935 980 1850 875 880 1640 775 750 1460 690 650 .60 150 2000 945 1050 1910 900 940 1780 840 840 1590 750 720 1420 670 630 .70 175 1900 895 1010 1830 865 920 1710 805 810 1530 720 690 1380 650 610 .80 200 1800 850 980 1740 820 900 1630 770 790 1460 690 675 1320 625 595 .90 225 1700 800 960 1630 770 860 1540 725 770 1380 650 660 1250 590 580
1.00 250 1600 755 940 1530 720 840 1430 675 750 1300 615 640 1150 545 560
NOTE  All air data is measured external to unit with air filter in place.
High Medium-High Medium Medium-Low Low
Air Volume and Motor Watts at Specific Blower Taps
Page 3
Page 4
SPECIFICATIONS GHR32V MODELS
Temperature rise
Blower wheel nominal
g
Nominal cooling
Vent/
Kits
Model No. GHR32V3-75 GHR32V5-100
High Fire 72,000 (21.1) 100,000 (29.3)
Input  Btuh (kW)
Output  Btuh (kW)
A.F.U.E. 90.0% 90.0%
California Seasonal Efficiency 83.9 85.3
Exhaust pipe connection (PVC) diameter  in. (mm) 2 (51)
Intake pipe connection (PVC) diameter  in. (mm) 2 (51)
Condensate drain connection (PVC)  in. (mm) 1/2 (12.7)
Low Fire 51,000 (14.9) 68,000 (19.9)
High Fire 67,000 (19.6) 93,000 (27.2)
Low Fire 47,000 (13.8) 63,000 (18.4)
Te mperature rise range  _F (_C)
High static certified by (A.G.A./C.G.A.)  in wg. (Pa) .80 (200)
Gas Piping Size I.P.S.  in. (mm) 1/2 (12.7)
Blower wheel nominal
diameter x width
Blower motor output  hp (W) 1/2 (373) 1 (746)
Number and size of filters − in. (mm) (1) 14 x 25 x 1 (356 x 635 x 25) (1) 20 x 25 x 1 ( 508 x 635 x 25)
Nominal coolin
that can be added
Shipping weight  lbs. (kg) 1 package 160 (73) 201 (91)
Electrical characteristics 120 volts  60 hertz  1 phase (less than 12 amps)
High Fire 40 − 70 (22 − 39)
Low Fire 35 − 65 (19 − 36)
in. 10 x 8 11-1/2 x 9
mm 254 x 203 292 x 229
Tons 2 to 3.5 3.5 to 5
kW 7.0 to 12.3 12.3 to 17.6
Optional Accessories (Must Be Ordered Extra)
LPG/Propane kit 59L81
Down-Flow Additive Base 32K52 32K53
Horizontal Support Frame Kit  Ship. Wt. − lbs. (kg.) 56J18  18 lbs. (8 kg)
Concentric Roof/Wall Termination Kits 60G77 − For 1 1/2 inch (38 mm) venting 33K97 − For 2 inch (51 mm) venting
Roof
Termination
Vent/
Intake
Kits
Condensate Drain Heat Cable 26K68 6 ft. (1.8 m)  26K69 24 ft. (7.3 m)  26K70 50 ft. (15.2 m)
Heat Cable Tape 39G04 1/2 inch (13 mm) wide or 39G03 2 inch (51 mm) wide
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.Determine from venting tables proper intake and exhaust pipe size and termination kit required.Cleanable polyurethane frame type filter.
Kits
Wall
Termination
Kits
For 2 inch (51 mm) venting 15F75
For 3 inch (76 mm) venting 44J41
15F74 (ring kit)
For 2 inch (51 mm) venting
30G79 (WTKX close couple w/ extension riser)
For 3 inch (76 mm) venting 44J40 (close couple)  81J20 (WTK close couple)
22G44 (close couple)
30G28 (WTK Close Couple)
22G44 (close couple)
Page 4
15F74 (ring kit)
Page 5
BLOWER PERFORMANCE DATA −1 through −3 V MODELS
p
Jumper
g
g
Setting
ADJUST
Jumper
s
Positions
ADJUST
Jumper
s
Positions
GHR32V3-75 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP2−1 Blower Control Low Speed  3 Factory Settings High Speed  4
ADJUST"
Jum
Setting
NORM 875 415 940 445 985 465
minus 15%
less motor
speed
NOTE  The effect of static pressure and filter resistance is included in the air volumes listed.
(Cool, Low Heat Or Continuous Fan)
er
1 2 3 4 1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
750 355 795 375 850 400 915 430 900 425 940 445
LOW" Speed
GHR32V5-100 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP2−1 Blower Control Low Speed  2 Factory Settings High Speed  4
ADJUST"
Jumper
Settin
NORM 1100 520 1260 595 1445 680 1635 770 1670 790 1960 925 2165 1020 2285 1075 1640 775 1825 860 2150 1015 2315 1090
minus 15%
less motor
speed
NOTE  The effect of static pressure and filter resistance is included in the air volumes listed.
LOW" Speed (Cool Or Continuous Fan) HIGH" Speed (Cool) HEAT" Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
935 440 1015 480 1195 565 1355 640 1335 630 1495 705 1690 800 1800 850 1360 640 1465 690 1770 835 1905 900
GHR32V3-75 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP3−1 Blower Control Factory Settings ADJUST − NORM
ADJUST"
Jumper
Positions
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
NORM (Normal) 875 415 940 445 985 465 1060 500 1090 515 1175 555 1285 605 1330 630
" (Minus) 15% 750 355 795 375 850 400 915 430 940 445 995 470 1095 515 1180 555
ADJUST"
Jumper
Position
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
NORM (Normal) 875 415 940 445 985 465 1060 500 1070 505 1130 535 1270 600 1290 610
" (Minus) 15% 750 355 795 375 850 400 915 430 900 425 940 445 1055 500 1120 530
15% lower motor speed than NORM jumper setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 875 cfm (415 L/s) for all positions.
GHR32V5−100 BLOWER PERFORMANCE
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range
VSP3−1 Blower Control Factory Settings ADJUST − NORM
ADJUST"
Jumper
Positions
NORM (Normal) 1100 520 1260 595 1445 680 1635 770 1640 775 1825 860 2150 1015 2315 1090
" (Minus) 15% 935 440 1015 480 1195 565 1355 640 1360 640 1465 690 1770 835 1905 900
ADJUST"
Jumper
Position
NORM (Normal) 1100 520 1260 595 1445 680 1635 770 1670 790 1960 925 2165 1020 2285 1075
" (Minus) 15% 935 440 1015 480 1195 565 1355 640 1335 630 1495 705 1690 800 1800 850
15% lower motor speed than NORM jumper setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL jumper placement with a minimum of approximately 1100 cfm (520 L/s) for all positions.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Heat Speed  3
VSP Jumper Speed Positions
HIGH" Speed (Cool) HEAT" Speed
106
0
500
107
505 113 0 535
0
127
105
0
5
129
600
0
500 112 0 530 940 445 995 470
610
109
515 117 5 555
0
Heat Speed  1
VSP Jumper Speed Positions
BLOWER PERFORMANCE DATA −4 V MODELS
Heat Speed − 3 Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low Speed High Speed
COOL"
Low Speed High Speed
Heat Speed − 2 Cool Speed − 4
VSP Jumper Speed Positions
HEAT"
Low Speed High Speed
COOL"
Low Speed High Speed
Page 5
128
605
5
109
515 118 0 555
5
133
630
0
Page 6
GHR32V3−75−5 Blower Motor Performance
Adjust
Jumper
g
Adjust"
Jumper
g
Adj
"
Jumper
Jumper
g
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
"
Jumper
Setting
Norm 875 415 940 445 985 465 1060 500 1070 505 1130 535 1270 600 1290 610
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
750 355 795 375 850 400 915 430 900 425 940 445 1055 500 1120 530
Low High
Cooling
Blower Speed Adjustment Settings (Switches 7 and 8)
 Jumper
Setting
"
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Low High
Norm 945 446 1025 484 1125 531 1270 599 1080 510 1172 533 1286 607 1452 685
803 379 871 411 956 451 1080 510 918 433 996 470 1093 516 1234 582
15% lower motor speed than NORM switch setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 825 cfm (390 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 875 cfm (415 L/s) for all positions.
Heating
GHR32V5−100/125−5 Blower Motor Performance
(For Static Pressure 0.0" to 0.8" w.g.)
Blower Speed Adjustment Settings (Switches 5 and 6)
"
ust
Jumper
Setting
Norm 1100 520 1260 595 1445 680 1635 770 1670 790 1960 925 2165 1020 2285 1075
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
935 440 1015 480 1195 565 1355 640 1335 630 1495 705 1690 800 1800 850
Low High
Cooling
Blower Speed Adjustment Settings (Switches 7 and 8)
"
Adjust"
Setting
Norm 1100 520 1260 595 1445 680 1635 770 1640 775 1825 860 2150 1015 2315 1090
1* 2 3 4 1* 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
935 440 1015 480 1195 565 1355 640 1360 640 1465 690 1770 835 1905 900
Low High
15% lower motor speed than NORM switch setting.
NOTE − The effect of static pressure and filter resistance is included in air volumes shown. NOTE − Continuous Fan only speed is approximately 1050 cfm (495 L/s) − non adjustable. NOTE − Lennox Harmony IIt zone control applications − MAX CFM is determined by COOL switch setting with a minimum of approximately 1100 cfm (520 L/s) for all positions.
Heating
Page 6
Page 7
GHR32Q−5 PARTS IDENTIFICATION
(Downflow Application Shown)
CONTROL VOLTAGE
CIRCUIT BREAKER
CONTROL TRANSFORMER
CONTROL BOX COVER
DOOR INTERLOCK SWITCH
COLD END HEADER
(COLLECTOR) BOX
COMBUSTION AIR
BLOWER MOUNTING
COMBUSTION
AIR INDUCER
EXHAUST TEE
PATCH PLATE
WITH BARBED
FITTING
BURNER BOX
COVER
FLAME SIGHT
GLASS
FLAME SENSOR
INTAKE AIR
GASKET
BRACKET
FRESH AIR
INTAKE FITTING
IGNITOR
SURELIGHT TWO−STAGE
INTEGRATED CONTROL
CORBELS
BURNER BOX
TOP
BURNER BOX
ASSEMBLY
ORIFICE
GAS VALVE
AND MANIFOLD
FIGURE 1
SUPPLY AIR
BLOWER
TOP CAP
CONTROL
BOX
GASKET
PRIMARY LIMIT
AUTO−RESET
(ALTERNATE STYLES)
BURNER BOX
GASKET
FLAME ROLL−OUT SWITCH
(MANUAL RESET)
SECONDARY LIMIT
AUTO−RESET
(Located on Backside
of Blower Wrapper)
CABINET
COMBUSTION AIR
PROVING (PRES-
SURE) SWITCH
HOT END HEADER
(COLLECTOR) BOX
CONDENSER
COIL
DuralokPlus
HEAT EXCHANGER
ASSEMBLY
CONDENSATE
TRAP
BACK FILTER
CLIP
FLUE
COLLAR
CONDENSATE
COLLAR
TM
Page 7
Page 8
I−UNIT COMPONENTS
GHR32 unit components are shown in figure 1. The com­bustion air blower, gas valve and burners can be accessed by removing the burner access panel. The blower and con­trol box can be accessed by removing the blower access door.
INTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
WARNING
Before attempting to perform any service or mainte­nance, turn the electrical power to unit OFF at dis­connect switch
A−Make-Up Box (Figure 2)
WARNING
Unit must be grounded in accordance with national and local codes. Electric Shock Hazaed. Can cause injury or death.
A field make−up box (see figure 2) is provided for line voltage wiring. Line voltage wiring to unit is done through the J96 jack from the field make−up box to plug P96 from the control box. The box may be installed inside or outside the unit (see figures 3 and 4) and may be installed on the unit left or right side.
MAKE-UP BOX
POWER ENTRY KNOCKOUT
BOX
UNIT
GROUND
JACK J96
Box may be installed inside or outside unit.
FIGURE 2
120V LINE VOLTAGE
PIGTAIL CONNECTIONS
COVER
J96
BUSHING
P96
FIGURE 3
EXTERIOR MAKE−UP BOX INSTALLATION
MAKE−UP
BOX
BUSHING
J96
(Shown with
accessory
wire connected)
P96
FIGURE 4
An accessory (brown) output wire is provided with the make­up box. The wire provides a 120V connection for optional ac­cessories such as electronic air cleaner or humidifier. If used, the wire is field installed in J96 jack plug by inserting the pin of the brown wire into the open socket of the jack. See fig­ure 5. 120V accessories rated up to 4 amps total may be con­nected to this wire. The neutral leg of the accessory is con­nected to the neutral white wire in the make-up box. The acces-
INSTALLING BROWN
ACCESSORY WIRE TO J96
WHITE
NEUTRAL
BROWN
sory terminal is energized whenever the indoor blower is in operation.
BLACK
J96
FIGURE 5
Page 8
Page 9
B−Control Box (Figure 6)
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CIRCUIT BREAKER CB8
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the techni­cian at the same electrostatic potential. Neutral­ize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
GHR32−1 through −4 CONTROL BOX
TWO−STAGE
CONTROL
CIRCUIT
BREAKER
TRANSFORMER
FIGURE 6
Unit transformer (T1), circuit breaker (CB8), SureLight control (A92), VSP−2 control (A24) and Two−stage control (A86) are located in the control box. In addition, a door in­terlock switch (S51) is located in the control box. Jackplugs and a snap-off" terminal strip allow the control box to be easily removed for blower service.
1. Control Transformer (T1)
A transformer located in the control box provides power to the low voltage 24 volt section of the unit. Transformers on all models are rated 40VA with a 120V primary and a 24V secondary.
2. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the transformer (T1). The breaker is rated 3 amps at 32V. If the current ex­ceeds this limit the breaker will trip and all unit operation will shut down. The breaker can be manually reset by pressing the button on the face (figure 7).
VSP−2
CONTROL
(v models only)
SURELIGHT
CONTROL
DOOR INTERLOCK
SWITCH
PRESS TO RESET
FIGURE 7
3.Door Interlock Switch (S51)
A door interlock switch rated 14 amps at 125VAC is located on the control box. The switch is wired in series with line voltage. When the blower door is removed the unit will shut down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
4. SureLight Ignition System A92
All GHR32−1 through −4 units are equipped with the Len­nox SureLight ignition system. The system consists of ig­nitor (figure 8) and ignition control board (figure 9 and table 3 ). The board and ignitor work in combination to en­sure furnace ignition and ignitor durability. The SureLight integrated board controls all major furnace operations. Table 1 and 2 show jack plug terminal designations. shows control board terminations. The board also features two LED lights for troubleshooting and two accessory termi­nals rated at (1) one amp. See table 4 for troubleshooting diagnostic codes. Units equipped with the SureLight board can be used with either electronic or electro−me­chanical thermostats without modification. The SureLight ignitor is made of durable silicon nitride. Ignitor longevity is also enhanced by voltage ramping by the control board. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor.
NOTE − Do not remove blower access panel to read Surelight LED lights. A sight glass is provided on the access panel for viewing.
Page 9
Page 10
13/32’
SURELIGHT IGNITOR
MEASUREMENT IS TO I.D.
5/8"
OF RETENTION RING
FRONT VIEW
TABLE 1
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN # FUNCTION
1 Ignitor
2
3
4
Combustion Air Blower Line Voltage
5
6
Combustion Air Blower Neutral
Not Used
Ignitor Neutral
Not Used
TABLE 2
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
5/16"
TOP VIEW
FIGURE 8
SURELIGHT INTEGRATED CONTROL BOARD
GHR32−1 through −4 units
PIN # FUNCTION
1 Primary Limit In
2
3
4
5
6
Pressure Switch and Primary Limit Out
7
8
9
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Not Used
Roll Out Switch In
Ground
TABLE 3
ACB COOL ACB HEAT PARK ACB LOW ACC TX HOT HTG ACC NEUTRALS 24VAC HOT 24VAC RTN FLAME SENSE
TERMINAL DESIGNATIONS
Blower − Cooling Speed (Line Volt) Blower − Heating Speed (Line Volt) Alternate Blower Speeds (Dead) Continuous Low Speed Blower Accessory Terminal (Line Volt) 120VAC Hot to Transformer 120VAC Hot Input Heat Only Accessory (Line Volt) 120VAC Neutrals 24VAC Hot from Transformer 24VAC Return from Transformer Flame Sense Terminal
FIGURE 9
Page 10
Page 11
TABLE 4
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1 LED #2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASH ON
OFF SLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASH OFF
ON SLOW FLASH
ON ON
OFF
FAST FLASH SLOW FLASH
SLOW FLASH FAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Limit must close within 3 minutes or board goes
Watchguard pressure switch − 5 minutes. Pressure switch open or has opened 5 times during a single call for heat; OR: Blocked inlet/exhaust vent; OR: Conden-
sate line blocked; OR: Pressure switch closed prior to activation of combustion
Watchguard 60 minute delay − burners fail to ignite.
Flame sensed without gas valve energized.
Rollout switch open. OR: 9 pin connector improperly attached.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .61 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
into one hour limit Watchguard.
air blower.
Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.21 microAmps
a−Electronic Ignition Figures 12 and 13
On a call for heat the SureLight control monitors the com­bustion air blower pressure switch. The control will not be­gin the heating cycle if the pressure switch is closed (by− passed). Once the pressure switch is determined to be open, the combustion air blower is energized. When the differential in the pressure switch is great enough, the pres­sure switch closes and a 15−second pre−purge begins. If the pressure switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. Units with control 97L48: ig­nitor stays energized during the trial or until flame is sensed. Units with control 56L83: ignitor stays energized for the first second of the 4−second trial. If ignition is not
The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
b−Fan Time Control Q Models Only
The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 10.
proved during the 4−second period, the control (97L48 or 56L83) will try four more times with an inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control
FAN-OFF TIME ADJUSTMENT
60sec. 90sec. 120sec. 180sec.
goes into Watchguard−Flame Failure mode. After a 60−min­ute reset period, the control will begin the ignition sequence again.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 10
Page 11
Page 12
c−Flame Sensor
ЙЙЙЙЙЙЙЙЙ
A flame sensor is located on the left side of the burner sup­port. See figure 11. The sensor is mounted on a bracket in the burner support and the tip protrudes into the flame en­velope of the left−most burner. The sensor is fastened to burner supports and can be removed for service without re­moving any part of the burners. During operation, flame is sensed by current passed through the flame and sensing electrode. The SureLight control allows the gas valve to re­main open as long as flame signal is sensed.
SENSOR
3/8"
IGNITOR
FIGURE 11
NOTE − The GHR32 furnace contains electronic com­ponents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
5. Two−Stage Control (A86)
All GHR32−1 through −4 units are equipped with a two− stage control board. Two different boards have been used. Boards 43K9001 and 29M9201 (figure 14) are identical, except the 9 pin connector on 43K9001 is replaced by two relays with quick connect terminals on board 29M9201. The two−stage board acts as a go between from the indoor thermostat to the SureLight ignition board. The board can be utilized in three modes: with a SINGLE−STAGE thermo­stat, a TWO−STAGE thermostat or with a second−stage (high fire) delay called W2 TIMED. The two−stage board is equipped with a jumper (see figure 14) which changes op­erating modes and a jumper which adjusts second−stage heat delay during W2 TIMED mode.
NOTE−The mode of operation jumper on the two−stage control board is factory set in the TWO−STAGE" position.
While in the single−stage thermostat mode (one−stage jumper setting), the unit will always operate on second− stage heat. The combustion air blower (B6) will operate on high speed and indoor blower (B3) will operate on heating speed. While in the two−stage thermostat mode the unit will operate on first−stage heat (low fire). The combustion air blower (B6) and indoor blower will operate on low speed. The unit will switch to second−stage heat (high fire) on call from the indoor thermostat W2. While in the W2 TIMED mode (factory setting 8 minutes) the unit will fire on first− stage heat (low fire) with the combustion air blower (B6) and indoor blower (B3) operating on low speed. After a set time delay the unit switches to second−stage heat (high fire). The combustion air blower and indoor blower also switch to second−stage heat mode.
SureLight Control Ignition Sequence Board 56L8301
15
ON
OFF
DEMAND
CAB IGNITOR GAS VALVE INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −Purge Ignitor Warmup Trial for
341
35
Ignition
38
Blower On"
Delay
FIGURE 12
SureLight Control Ignition Sequence Board 97L4801
15
ON
OFF
DEMAND
CAB IGNITOR GAS VALVE INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
Pre −Purge Ignitor Warmup
341
Trial for Ignition
38
Blower On"
Delay
FIGURE 13
5 SEC80
Post
Purge
5 SEC80
Post
Purge
Page 12
Page 13
MODE OF
OPERATION
JUMPER
TWO−STAGE CONTROL BOARD
G32(V) −1 through −4 units
W2 TIMED DELAY JUMPER
6.VSP2−1 Blower Control Board (A24)
−1 through −3 V Models only
GHR32V−1 through −3 units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. The unit uses the VSP2−1 variable speed control board, located in the blow­er compartment, which controls the blower speed and provides diagnostic LEDs. The control has a non−adjust­able, factory preset ON" fan timing delay and an adjustable OFF" fan timing delay (see figure 17).
The VSP2−1 also senses limit trip condition and turns on the blower. The GHR32 primary limit switch is located in the middle of the vestibule wall and the secondary limit switch is located int ehblower compartment. When excess heat is sensed in the heat exchanger, or blower compartment, the respective switch will open and interrupt the current to the gas valve, while at the same time the VSP2−1 energizes the blower on heating speed. The limit automatically resets when the unit temperature returns to normal and the blower is de−energized.
FIGURE 14
HIGH SPEED
SELECTOR PINS
(COOLING ONLY)
LOW SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG (BOARD TO VARIOUS POINTS IN FURNACE)
Diagnostic LEDs located on the VSP2−1 control board are pro­vided to aid in identifying the unit’s mode of operation. Certain scenarios will arise depending on the jumper positions. Refer to figure 15 for identification.
VSP2−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP 2
HIGH LOW ADJUST HEAT
270
1
2
3
4
DS4
CFM
210
90
150
JP 1
1
1
2
3
4
HTG.
BLOWER
12
1
2
3
4
HEAT
DS2
TEST
+
NORM
DS3
ON/OFF
HI/LOW
DS1
JP46
13 PIN PLUG
(BOARD TO MOTOR)
HEATING SPEED
SELECTOR PINS
See table 5 for VSP2
factory settings
OPERATIONAL
SELECTOR PINS
(Affects both heating and
cooling modes)
DIAGNOSTIC
DS LEDS
FAN OFF"
TIMING PINS
FIGURE 15
Page 13
Page 14
IMPORTANT
24 VAC half wave rectified (DC pulse), when mea­sured with a meter, may appear as a lower or higher voltage depending on the make of the meter. Rather than attempting to measure the output voltage of the VSP2 board, see GHR32 BLOWER & VSP2 BLOWER CONTROL BOARD TROUBLESHOOTING FLOW CHART in the TROUBLESHOOTING section of this manual.
VSP2−1 BLOWER CONTROL BOARD (A24)
1
J46
HIGH LOW ADJUST HEAT
1 2 3 4
HTG.
BLOWER
1 2 3 4
HEAT
DS3
TEST
− + NORM
HI/LOW
1 2 3 4
DS4
Diagnostic LED Lights
a − DS3 ON/OFF"
ON/OFF−DS3 indicates there is a demand for the blower mo-
tor to run. When the ON/OFF LED−DS3 is lit, a demand is be­ing sent to the motor. In heating mode only, there is a 45 sec­ond fan ON" delay in energizing ON/OFF LED−DS3. The light will not go off until adjustable fan OFF" delay has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1 & HEAT LED−DS2 are off, the motor will operate in low speed.
b − DS2 HEAT"
If HEAT LED−DS2 is on, the blower is running in the heat speed according to the HEAT" jumper setting. The HEAT LED−DS2 comes on instantaneous and switches off when the call for heat is satisfied.
NOTE−When the blower is in OFF" delay mode, the mo­tor runs at low speed, therefore the HEAT LED−DS2 is off. It switches off when the call for heat is satisfied.
c − DS1 HI/LOW"
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control. PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output. PIN 13 - 24V - Input 24 VAC power for the VSP2-1. PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 1 - Heat - Heat speed input signal to the ICM2 motor.
PIN 4 - High Tap - High Speed programming input.
PIN 5 - Low Tap - Low speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 8 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor.
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common. PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
DS1
270
CFM
210
90
150
HIGH/LOW LED−DS1 indicates whether the blower is op­erating in high or low speed. When the light is off, the blow­er is running in low speed according to the LOW" jumper setting. When HIGH/LOW LED−DS1 is on, the blower is op- erating in high speed according to the HIGH" jumper set­ting.
d − DS4 CFM"
CFM LED−DS4 indicates the CFM the unit is operating,
according to the jumper settings. The light flashes once for approximately every 100 CFM. For example, if the unit is operating at 1000 CFM, CFM LED−DS4 will flash 10 times. If the CFM is 2050, CFM LED−DS4 will flash 20 full times plus one fast or half flash. At times the light may appear to flicker or glow. This takes place when the control is communicating with the motor be­tween cycles. This is normal operation.
The appropriate speed according to application and CFM need is selected by moving jumper pins.
Page 14
VOLTAGES INTO VSP2−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0 volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage) if CCB
is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP2−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx.
34 volts
0 volts
Voltage across J46 pins 8 and 9 to 3, is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pins 8 and 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
24VAC Half-Rectified (DC Pulse)
a voltage of 0−25VDC should be present.
@ 60Hz.
FIGURE 16
Page 15
NOTE−On Harmony II zoning applications in the heating mode, the highest speed obtainable is the same as the highest cooling speed selection. Also, the heating speed (heat jumper position) is only used when the primary limit has been tripped. In non−zoning applications, refer to the section on the VSP2−1 control.
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
not operable. Notice in the GHR32V5−100 table, that the normal adjustment setting for heat speed position #3 is 2150 CFM (1015L/s). After the adjustment setting has been determined, c hose th e re main ing speed jumper settings from those offered in the table.
The TEST pin is available to bypass the VSP2−1 control and run the motor at approximately 70% to test that the moto r i s operational. This is beneficial primarily in troubleshoot­ing. G must be energized for motor to run.
b−HEATING BLOWER"
IMPORTANT
Before changing jumper setting, make sure the motor has completely stopped. Any jumper set­ting change will not take place while the motor is running.
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and condi­tions associated with each one. Refer to figure 15 for identifica­tion.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in the tables in the blower performance section. Using the tables, determine which row of CFM volumes most closely matches the desired CFM. Once a specific row has been chosen (NORMAL or −), CFM volumes from other rows cannot be used. Below are the descriptions of each of the jumper selections.
Refer to table 5 for factory settings. Refer to the blower perfor­mance tables for the approximate air volume for each setting.
VSP2−1 FACTORY SETTINGS
MODEL HIGH LOW ADJUST HEAT
GHR32V−75−
1, −2, −3 units
GHR32V−100
−1, −2, −3 units
a−ADJUST"
The ADJUST pins allow the motor to run at normal speed or approximately 15% lower than normal speed. The blower performance tables give two rows (NORMAL and −) with their respective CFM volumes. The + adjustment setting i s
TABLE 5
4 3 NORM 2
4 2 NORM 1
For GHRV32 units, place the HEATING BLOWER jumper across the second and third pins (position #2).
When W1 is energized, the LOW jumper selections are ac­tivated. The HEAT jumper selections are activated when W2 is energized.
NOTE−In Harmony II zoning applications, HEATING BLOWER jumper must be in position #2.
c−HEAT"
The HEAT jumper is used to set the blower speed to ob- tain the required CFM as outlined in HEAT SPEED in the blower performance tables.
The HEAT jumper selections are activated with a call for second-stage heating (W2).
d−HIGH"
The HIGH jumper is used to determine the CFM during cooling speed. These jumper selections are activated when G and DS terminals are energized.
e−LOW"
The LOW jumper is used to determine CFM during low speed cooling. These jumper selections are activated when G is energized. The LOW jumper may also be used for low speed heating. See the HEAT" section for details.
f−FAN OFF"
Fan OFF" timings (time that the blower operates after the heat demand has been satisfied) are determined by the ar­rangement of a jumper on the VSP2−1 board. See figure
17. To adjust fan OFF" timings, gently disconnect the jumper and reposition it across pins corresponding with the new timing. Fan OFF" time is adjustable from 90 to 330 seconds. The control has a non−adjustable, factory preset on" fan timing (45 seconds).
WARNING − MAKE SURE TO DISCONNECT POWER BEFORE CHANGING FAN OFF" TIMINGS.
Page 15
Page 16
FAN-OFF TIME ADJUSTMENT
NOTEIf fan OFF" time is too low, residual heat in heat exchanger may cause primary limit S10 to trip resulting
TIMING
JUMPER
To adjust fan−off timings:
Remove jumper from VSP2−1 and select
one of the other pin combinations to
achieve the desired time.
in frequent cycling of blower. If this occurs, adjust blow­er to longer time setting.
Table 6 outlines the operation of the variable speed motor in relation to specific modes of operation. Some informa-
270
150 90
210
Leave jumper off to achieve
330 second fan−off timing.
TIMING PINS (seconds)
Fan-off timing is factory
set at 90 seconds
tion has been repeated from the previous section to provide an example. Refer to each diagnostic LED or jumper settings section for more information.
FIGURE 17
TABLE 6
VSP2−1 GHR32−1 through −3 units OPERATION
HEATING MODE COOLING MODE
UNITS WITH
SINGLE−STAGE HEATING
NON−ZONED
APPLICATIONS
Using a single−stage thermostat with one−stage" heating, the HEAT LED− DS2 is lit when the thermostat calls for heat. The ON/OFF LED−DS3 is lit after 110 seconds (65 seconds pre−purge and 45 seconds fan ON" time) from the time a call for heat is made. This in­dicates the blower is operating in heat­ing speed.
Using a single−stage thermostat with W2 TIMED," and W1 calling, the ON/ OFF LED−DS3 is lit to indicate the blower is operating on low speed.
When the HEAT LED−DS2 is lit, the blower is operating in heating speed, and second−stage (W2) heating is call­ing.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zon­ing system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/ OFF LED−DS3 are lit to indicate the blower is operating.
NOTE−In Harmony II zoning applica­tions, HTG. BLOWER jumper must be in position #2.
NOTE: For zone applications with Harmony, remove the wire from the pin #3 of the J73 terminal on the VSP control board, insulate the end, and secure it to prevent from shorting.
Using a two−stage thermostat with first−stage (W1) calling, the ON/OFF LED−DS3 is lit to indicate the blower is operating in low speed.
When the ON/OFF LED−DS3 and HEAT LED−DS2 are lit, the blower is operating in heating speed and sec­ond−stage (W2) heating is calling.
HEAT LED−DS2 is lit with a call for heat from the thermostat. ON/OFF LED− DS3 is lit after 110 seconds from the time a call for heat is made.
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zon­ing system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/ OFF LED−DS3 are lit to indicate the blower is operating.
NOTE−In Harmony II zoning applica­tions, HTG. BLOWER jumper must be in position #2.
UNITS WITH
TWO−STAGE HEATING
NON−ZONED
APPLICATIONS
HARMONY ZONED
APPLICATIONS
UNITS WITH SINGLE−
SPEED COMPRESSOR
NON−ZONED
APPLICATIONS
The terminals DS and Y must be jumpered together. With a call for cooling, terminals G, Y and DS on the unit control board are energized from the thermostat. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indi­cate the blower is operating on high speed.
NOTEY and DS are factory jump­ered for single−stage cooling, non− zoned applications.
NOTEFor low speed during single− stage cooling remove jumper from Y to DS.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
UNITS WITH TWO−SPEED
COMPRESSOR
NON−ZONED
APPLICATIONS
The ON/OFF LED−DS3 is lit to indicate the blower is operating in first stage cooling. This LED is energized on when a 24VAC thermostat demand is supplied to the control (terminal G" on the control board terminal strip).
In second stage, the ON/OFF LED− DS3 and HI/LOW LED−DS1 are lit to indicate the blower is operating on high speed (24VAC is supplied to the unit terminal strip Y2 from Y2 on the thermostat).
NOTE Jumper must be moved from Y1 to Y2 In two−speed, non−zoned ap­plications.
HARMONY ZONED
APPLICATIONS
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zon­ing system to the terminal strip’s DS terminal. HI/LOW LED−DS1 and ON/ OFF LED−DS3 are lit to indicate the blower is operating.
Page 16
Page 17
7.VSP3−1 Blower Control Board (A24) GHR32V−4 Units
GHR32V−4 units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. The unit uses the VSP3−1 vari­able speed control board, located in the blower compart­ment, which controls the blower speed and provides diagnostic LEDs. The control has both a non−adjustable, factory preset ON" fan timing delay and an adjustable OFF" fan timing delay (see figure 17).
VSP3−1 VARIABLE SPEED CONTROL BOARD SELECTIONS
1
JP2
DELAY PROFILE SELECTOR PINS
(COOLING ONLY)
DELAY COOL ADJUST HEAT
1
2
3
4
The VSP3−1 also senses limit trip condition and turns on the blower. The GHR32V limit switch is located in the middle of the vestibule wall. When excess heat is sensed in the hea t ex­changer, the limit switch will open and interrupt the current to the gas valve, while at the same time the VSP3−1 energizes the blower on heating speed. The limit automatically resets when the unit temperature returns to normal and the blower is de−energized.
Diagnostic LEDs located on the VSP3−1 control board are pro­vided to aid in identifying the unit’s mode of operation. Certain scenarios will arise depending on the jumper positions. Refer to figure 18 for identification.
JP46
13 PIN PLUG
(BOARD TO MOTOR)
1
2
3
4
TEST
+
NORM
1
2
3
4
HEATING SPEED SELECTOR PINS
See table 7 for VSP3−1
factory settings
COOL SPEED
SELECTOR PINS
(COOLING, HEATING and
CONTINUOUS FAN)
HEATING STAGE
JUMPER SELECTOR PINS
JP73
15 PIN PLUG (BOARD TO VARIOUS POINTS IN FURNACE)
JP1
1
HTG.
BLOWER
12
HEAT
DS2
ON/OFF
FIGURE 18
DS3
HI/LOW
DS1
270
210
150
DS4
CFM
OPERATIONAL
SELECTOR PINS
(Affects both heating
and cooling modes)
DIAGNOSTIC
DS LEDS
90
FAN OFF"
TIMING PINS
Page 17
Page 18
VSP3−1 BLOWER CONTROL BOARD (A24)
1
J46
DELAY COOL ADJUST HEAT
1 2 3 4
HTG.
BLOWER
1 2 3 4
HEAT
DS3
TEST
− + NORM
HI/LOW
1 2 3 4
DS4
IMPORTANT
24 VAC half wave rectified (DC pulse), when measured with a meter, may appear as a lower or higher voltage depending on the make of the meter. Rather than attempting to measure the output voltage of A24, see GHR32V BLOWER & VSP3 BLOWER CONTROL BOARD TROUBLE­SHOOTING FLOW CHART in the TROUBLE­SHOOTING section of this manual.
ON/OFF
12
J73
1
PIN 2 - G - Input signal from thermostat’s fan signal.
PIN 3 - W2 - Input signal for second stage heat from the thermostat.
PIN 4 - DS - Input signal for the blower speed regulation.
PIN 5 - Limit - Input signal from the external limit.
PIN 6 - R - 24 VAC power to the thermostat.
PIN 9 - CI - Input signal from the fan limit control. PIN 10 - CO - Output signal to the burner control.
PIN 11 - HT - Input signal from the fan limit control.
PIN 12 - ACC - 24 VAC accessory output. PIN 13 - 24V - Input 24 VAC power for the VSP2-1. PIN 14 - 24V - Input 24 VAC power for the VSP2-1.
PIN 15 - V - Input signal from the gas line.
PIN 4 - Delay Tap - Delay profile programming input.
PIN 5 - Cooling blower speed programming input.
PIN 6 - On / Off - On / off output signal to the ICM2 motor.
PIN 7 - Adjust Tap - ICM2 mode selection.
PIN 9 - Hi / Low - Speed regulate input signal to the ICM2 motor with CCB1 and
PIN 10 - Ref. V - ICM2 reference voltage.
PIN 11 - Heat Tap - Heating blower speed programming.
PIN 13 - cfm - Motor speed diagnostic signal.
DS2
PIN 1 - C - 24 VAC common.
PIN 7 - C - 24 VAC common.
Pin 8 - C - 24 VAC common.
PIN 2 - C - 24 VAC common. PIN 3 - C - 24 VAC common.
PIN 12 - C - 24 VAC common.
J73
J46
PIN 1 - Not Used.
PIN 8 - NOT USED
HARMONY only
DS1
270
CFM
210
90
150
Diagnostic LED Lights
DS3 ON/OFF
ON/OFF−DS3 indicates there is a demand for the blower
motor to run. When the ON/OFF LED−DS3 is lit, a demand is being sent to the motor. In heating mode only, there is a 45−second fan ON" delay in energizing ON/OFF LED− DS3. Light will not go off until adjustable fan OFF" delay has expired.
If ON/OFF LED−DS3 is on and both HIGH/LOW LED−DS1 & HEAT LED−DS2 are off, the motor will operate in low speed (heating).
DS2 HEAT
If HEAT LED−DS2 is on, the blower is running in second− stage heat speed according to the HEAT" jumper setting. In heating mode only, there is a 45 second delay in energiz­ing HEAT LED−DS2. Light will not go off until adjustable fan OFF" delay has expired.
DS1 HI/LOW
HIGH/LOW LED−DS1 indicates the blower is operating in
the cooling mode.
DS4 CFM
CFM LED−DS4 indicates the CFM the blower is providing,
according to the jumper settings.
VOLTAGES INTO VSP3−1
Voltage across J73 pins 13 to 1 and 6 to 1 is 24VAC as shown here.
34 volts
0
volts
−34 volts
Voltage across J73 pins 4 to 1 is approximately 15-20VDC (straight voltage) if CCB is used. If Harmony is used a voltage of 0−25VDC should be present.
If CCB or Harmony is not used, pin 4 to 1 voltage is 21VAC.
Refer to unit wiring diagram.
24VAC @ 60Hz.
VOLTAGES FROM VSP3−1 TO ELECTRONICALLY
CONTROLLED BLOWER MOTOR
Voltage across J46 pins 6 to 3 and 1 to 3 is half-rectified AC as shown here.
Approx. 34 volts
0
volts
Voltage across J46 pin 9 to 3 is approximately 15-20VDC if CCB is used. If CCB or
Harmony is not used, pin 9 to 3 voltage is approximately 21VAC. If Harmony is used
Refer to unit wiring diagram.
a voltage of 0−25VDC should be present.
24VAC Half-Rectified (DC
FIGURE 19
Pulse)
@ 60Hz.
Page 18
Page 19
Jumper Settings
SEE BLOWER PERFORMANCE TABLES AT FRONT
OF MANUAL FOR ANY REFERENCE TO CFM.
IMPORTANT
Before changing jumper setting, make sure the motor has completely stopped. Any jumper set­ting change will not take place while the motor is running.
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and condi­tions associated with each one. Refer to figure 18 for identifica­tion.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in the blower performance tables. Using the tables, determine which row of CFM volumes most closely matches the desired CFM. Once a specific row has been chosen (NORMAL or −), CFM volumes from other rows cannot be used. Below are the descriptions of each of the jumper selections.
Refer to table 7 for factory settings.
TABLE 7
VSP FACTORY SETTINGS FOR GHR32V−4 UNITS
MODEL DELAY COOL ADJUST HEAT
GHR32V3−75 4 4 NORM 3
GHR32V5−100 4 4 NORM 2
NOTE − In Harmony II zoning applications in the heating mode, the highest cooling speed selected is the highest blower speed obtainable. Also, the fan−only speed is used when the primary lim­it has been tripped. In non−zoning applications, refer to the section on the VSP3−1 control.
ADJUST
The ADJUST pins allow the motor to run at normal speed or approximately 15% lower than normal speed. The blow­er performance tables two rows (NORMAL and −) with their respective CFM volumes. The + adjustment setting is not operable. Notice that the normal adjustment setting for heat speed position #3 is 2150 CFM (1015 L/s) . After the adjustment setting has been determined, choose the re­mainder speed jumper settings from those in the table.
The TEST pin is available to bypass the VSP3−1 control and run the motor at approximately 70% to test that the motor is operational. This is beneficial primarily in troubleshooting. G must be energized for motor to run.
HTG. BLOWER
For GHR32V−4 units only, place the HTG. BLOWER jump­er across the second and third pins (position #2).
NOTE − In Harmony II zoning applications, HTG. BLOWER jumper must be in position #2.
HEAT
The HEAT jumper is used to set the blower speed to obtain the required CFM as outlined in HEAT SPEED section of the blower performance tables. The HEAT jumper selec- tions are activated with a call for first−stage heating (W1) and second−stage heating (W2).
DELAY
The DELAY jumper is used to set the specific motor fan mode of operation during cooling. Depending on the ap­plication, one of four fan options may be chosen by moving the jumper to the appropriate set of pins.
Options 1, 2, 3, or 4 will have an increased dehumidification effect on the system. Option 1 will have the least effect and option 4 will have the greatest effect.
#1 PIN JUMPERED
A − Motor runs at 100% until demand is satisfied. B − Once demand is met, motor ramps down to off.
A B
100% CFM
COOLING DEMAND
OFFOFF
#2 PIN JUMPERED
A − Motor runs at 82% for approximately 7−1/2 minutes. B − If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
C − Once demand is met, motor ramps down to off.
C
OFF
OFF
A
7 1/2 MIN
82%CFM
B
100% CFM
COOLING DEMAND
#3 PIN JUMPERED A − Motor runs at 50% for 1/2 minute. B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor ramps down to off.
C D
100% CFM
OFF
OFF
A
1/2 MIN 50% CFM
B
7 1/2 MIN 82% CFM
COOLING DEMAND
Page 19
Page 20
#4 PIN JUMPERED A − Motor runs at 50% for 1/2 minute. B − Motor then runs at 82% for approximately 7−1/2 min-
utes.
C − If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D − Once demand is met, motor runs at 50% for 1/2 min-
ute.
E − Motor ramps down to off.
C D
100% CFM
1/2 MIN 50% CFM
E
OFF
OFF
A
1/2 MIN 50% CFM
B
7 1/2 MIN 82% CFM
COOLING DEMAND
COOL
The cool jumper is used to set the blower speed to obtain the required CFM as outlined in the blower performance tables.
VSP Operation
Table 8 outlines the operation of the variable speed motor in relation to specific modes of operation. See table 9 for GHR32V with CCB1 and a two speed outdoor unit. Some information has been repeated from the previous section to provide an example. Refer to each diagnostic LED or jump­er settings section for more information.
Heating Mode Cooling Mode
Units With
Single−Stage Heating
Non−Zoned Applications
Using a single−stage thermostat with "one−stage" heating, the HEAT LED−DS2 is lit when the thermostat calls for heat. The ON/OFF LED− DS3 is lit after 110 seconds (65 sec­onds prepurge and 45 seconds fan "ON" time) from the time a call for heat is made. This indicates the blower is operating in high speed heat.
Using a single−stage thermostat with "W2 TIMED" and W1 calling, the ON/OFF LED−DS3 is lit to indi­cate the blower is operating on low speed heat.
When HEAT LED−DS2 is lit, the blower is operating in high speed heat and second−stage (W2) is call­ing.
Harmony Zoned Applications
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED− DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
Note − In Harmony II zoning ap­plications, HTG BLOWER jumper must be in position #2.
GHR32V−4 Units with VSP3−1
TABLE 8
Units With
Two−Stage Heating
Non−Zoned Applications
Using a two−stage thermostat with first−stage (W1) calling, the ON/ OFF LED−DS3 is lit to indicate the blower is operating in low speed heat.
When the ON/OFF LED−DS3 and HEAT LED−DS2 are lit, the blower is operating in high speed heat and second−stage (W2) is calling.
HEAT LED−DS2 is lit with a call for heat from the thermostat. ON/OFF LED−DS3 is after 110 seconds from the time a call for heat is made.
Harmony Zoned Application
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED− DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
Note − In Harmony II zoning applica­tions, HTG BLOWER jumper must be in position #2.
Units With
Single−speed Compressor
Non−Zoned Applications
Y1−DS and Y1−Y2 must be jump­ered together. With a call for cool­ing, G, Y1, Y2 and DS on the unit control board are energized from the thermostat. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to in­dicate a call for cooling.
Note − Y1 to DS and Y1 to Y2 are factory jumpered for single−stage cooling, non−zoned applications.
Harmony Zoned Application
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the termi­nal strip’s DS terminal. HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate the blower is oper­ating.
Units With
Two−speed Compressor
Non−Zoned Applications
Y1−DS must be jumpered together. With a call for single−stage cooling, G, Y1, and DS on the unit control board are energized from the Ther­mostat. With a call for second−stage cooling, G, Y1, Y2, and DS on the unit control board are energized from the thermostat. In both cases, HI/LOW LED−DS1 and ON/OFF LED−DS3 are lit to indicate a call for cooling.
Note − Jumper Y1−Y2 must be re­moved for units with two−speed compressor.
Harmony Zoned Application
The blower speed is controlled by the PWM (pulse width modulation) signal sent from the control center of the zoning system to the terminal strip’s DS terminal. HI/LOW LED− DS1 and ON/OFF LED−DS3 are lit to indicate the blower is operating.
NOTE − For zone applications with Harmony, remove the wire from pin #2 and pin #13 of the J49 terminal at the motor and the wire from pin #3 of the J73 terminal on the VSP control board, insulate the ends and secure to prevent shorting.
Page 20
Page 21
TABLE 9
p
Normal operation
blower speed follow thermostat
removal during 1st
ifi
ill i
,
When humidity demand is satisfied
satisfied during
th
gp p
Call f
idit
g
Call for 1st stage
Call for 2nd stage
Reduced blower speed (dehumidifi-
mostat demand), slide switch is
GHR32V−4 UNITS WITH CCB1 & TWO−SPEED OUTDOOR UNIT OPERATING SEQUENCE
Operating Sequence System Demand System Response
System
Condition
Step
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
***Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Call for humidity
removal during 1st
stage thermostat
demand
Significant increase
in humidity during
thermostat demand.
Humidity demand
satisfied during
thermostat demand.
or hum
removal during 2nd
stage thermostat
demand
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase
in humidity
Humidity demand satisfied between
thermostat demands
(unit off cycle).
y
1 Y1 Acceptable (None) Low
2 Y2 Acceptable (None) High HIGH COOL
1 Y1 Acceptable (None) Low
2 Y1
Demand
3
satisfied
4 Y1 Slightly over setpoint (1) High
1 Y1 Acceptable (None) Low
2 Y1
1 Y1 Over Setpoint High
2 Y1
3 None Acceptable (None) Off Off
4 Y1 Acceptable (None) Low
1 Y2 Acceptable (None) High HIGH COOL
2 Y2
3 Y2 Acceptable (None) High HIGH COOL
1 None Slightly over setpoint (1) Off Off Dehumidification mode (high speed
2 Y1 Slightly over setpoint (1) Low
1 None Slightly over setpoint (1) Off Off
2 Y2 Slightly over setpoint (1) High
1 None
2 Y1 or Y2
1 None Over setpoint (1 or more) Off Off
2 Y1 or Y2
Change to slightly
over setpoint (1)
Slightly over setpoint (1) Off Off
Change to significantly
over setpoint (2 or more)
Change to Acceptable
(None)
Change to slightly
over setpoint (1)
Significantly over setpoint
(2 or more)
Significantly over
setpoint (2 or more
Change to
acceptable (None)
Low
High
High HIGH COOL
High
Off Off
High
High HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
Compressor demand and indoor
blower s
Dehumidification mode begins with
next thermostat demand, after initial
thermostat demand is satisfied.
If humidity increases significantly
over setpoint, or if slide switch is
moved sign
ately go into dehumidification mode
(in presence of thermostat demand).
When humidity demand is satisfied
blower immediately shifts to the
HIGH COOL CFM in order to hasten
e end of the cycle. Unit can only
shift out of high speed compressor
operation at beginning of next cycle.
Blower immediately changes speed
in response to thermostat demand.
compressor) begins with next ther-
mostat demand after initial demand is
Reduced blower speed (dehumidifi-
cation speed) begins immediately
If humidity increases significantly
over setpoint, or if slide switch is
moved, unit immediately goes into
dehumidification mode (in presence
While unit is not operating (no ther-
mostat demand), slide switch is
moved down and back up. Blower
and compressor operate at high
speed until next thermostat demand.
eed follow thermostat
demand
cantly, u nit w
satisfied.
with thermostat demand
of thermostat demand).
mmedi-
,
Note − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther­mostat heating demand.
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed indefinitely. To reset, move humidity slide switch all the way down then back up to desired setpoint (with unit running) ** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5. ***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compres­sor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 21
Page 22
8.Two Stage Integrated Control (A92) GHR32Q−5 Units
DANGER
Shock hazard.
Disconnect power before servicing. Control is not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
All GHR32Q units are equipped with the Lennox two− stage integrated SureLight control board. The system consists of a ignition control board (figure 20 with control terminal designations in tables 12, 13 and 14) and ignitor (figure 8). The board and ignitor work in combination to en­sure furnace ignition and ignitor durability. The board con­trols all major furnace operations. The board features two LED lights, DS1 and DS2 for troubleshooting. The board also has two accessory terminals rated at (1) one amp each. See table 15 for troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heat cycle, SureLight control mon­itors the first stage and second stage combustion air induc­er prove switch. The control will not begin the heating cycle if the first stage prove switch is closed (by−passed). Like­wise the control will not begin the second stage heating cycle if the second stage prove switch is closed and will al­low first stage heat only. However if the second stage prove switch closes during the first stage pre−purge, the control will still respond to second stage heat. Once the first stage prove switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−min­ute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. The ignitor energizes during the trial until flame is sensed. If ignition is not proved during the 4−second period, the control will try four more times with an inter purge and warm−up time between trials of 35 sec­onds. After a total of five trials for ignition (including the ini­tial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE thermostat or TWO−STAGE thermostat. The thermostat selection jumper E20, located just below dip switches 1 through 4 (figure 20), must be positioned for the particular application. The jumper is factory set on TWO" for use with a two−stage thermostat with two stage heat. Re−posi­tion jumper to SINGLE" for use with a single stage thermo­stat with two stage heat. While in the single−stage thermostat mode (single jumper setting), the burners will always fire on first−stage heat. The combustion air inducer will operate on low speed and in­door blower will operate on low heat speed. After a field se­lectable 10 or 15 minute delay (dip switch 3), the unit will switch to second stage heat. While in the two−stage ther­mostat mode (two jumper setting) the burners will fire on first−stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second−stage heat on call from the indoor thermostat. If there is a simultaneous call for W1 and W2 (first and second stage heat) the unit will fire on first stage heat and will switch to second stage heat after 30 seconds of operation. See Sequence of Operation flow charts in the back of this manual for more detail.
Dip Switch Settings
Dip Switches 1 and 2 − Heating Fan off Delay − The fan on
time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satis­fied) can be adjusted by flipping the dip switches 1 and 2 located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. For customized comfort, monitor the supply air temperature once the heat demand is satisfied. Note the supply air temperature at the instant the blower is de−ener­gized. Adjust the fan−off delay to achieve a supply air tem­perature between 90° − 110° at the instant the blower is de− energized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher air tem­perature). See table 10 for dip switch settings.
TABLE 10
Heating Fan Off Delay
Delay (Seconds)
60 Off Off
90 Off On 120 On Off 180 On On
Switch 3 − Second Stage Delay (Used with Single−Stage Thermostat Only) −− This switch is used to determine the
second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the ON position, which provides a 10−minute delay before second−stage heat is initiated. If the switch is toggled to the OFF position,
Switch 1 Switch 2
Page 22
Page 23
it will provide a 15−minute delay before second−stage heat is initiated. This switch is only activated when the thermo­stat selector jumper is positioned for SINGLE−stage ther­mostat use.
Switch 4 − Cooling Fan off Delay − The fan on delay time of 2 seconds is not adjustable. Fan off time (time that the blower operates after the cool demand has been satisfied) can be adjusted by flipping dip switch 4. The unit is shipped with a factory fan off setting of 45 seconds. Fan off time will affect comfort and is adjustable to satisfy individual ap­plications. See table 11 for cool fan off time settings.
TABLE 11
Cooling Fan Off Delay
Delay (Seconds) Switch 4
2 Off
45 On
Diagnostic LED’s (DS1 and DS2)
Two diagnostic LED’S are located on the two−stage inte­grated control board. See figure 20. These light flashes correspond with the codes detailed in table 15.
Factory Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the integrated control board terminal strip must be removed for two−stage cooling.
TABLE 12
Integrated Control Board Terminals
120VAC Neutral
LINE Line
XFMR Transformer
EAC Electronic Air Cleaner
CIRC Indoor Blower
HUM Humidifier
120VAC Line
HUM Humidifier
XMFR Transformer
LINE Line
PARK For Unused Leads
COOL Cooling Speed
EAC Electronic Air Cleaner
HI HEAT High Heat Speed
LO HEAT Low Heat, Low Cool and Continuous Fan
Speed
TWO−STAGE INTEGRATED CONTROL BOARD
SWITCHES
SENSOR
FACTORY−
INSTALLED
JUMPER
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH(ES) FUNCTION
1 and 2 Blower Off Delay (Heating Mode)
3 Second Stage ON Delay (Single−stage t’stat) 4 Blower Off Delay (Cooling Mode)
FIGURE 20
LEDs
DIP
1 − 4
Page 23
Page 24
TABLE 13
ONONON
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
Integrated Control Board 5 Pin Terminal
PIN # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
Integrated Control Board 12Pin Terminal
PIN # Function
1 Gas Valve 2nd Stage (High Fire)
2 Second Stage Prove Switch
3 Not Used
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve 1st stage (Low Fire)
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Out
12 1st Stage Prove Switch
TABLE 14
TABLE 15
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 20 for location of diagnostic LEDs.
DS1 DS2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH ON
OFF SLOW FLASH
OFF FAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH OFF Flame sensed without gas valve energized.
ON ON
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation. Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes or unit goes into 1 hour Watchguard. Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes; OR lost flame sense 5 times in one heating cycle; OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts. (If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Minimum flame sense current = 0.17−0.22 microAmps.
Page 24
Page 25
9.Two Stage Variable Speed Integrated Control (A92) GHR32V−5 Units
All GHR32V−5 units are equipped with the Lennox two− stage, variable speed integrated SureLight control board. The system consists of a ignition / blower control board (figure 21 with control terminal designations in tables 16 through 19) and ignitor (figure 8). The board and ignitor work in combination to ensure furnace ignition and ignitor durability. The SureLight integrated board controls all ma­jor furnace operations. The board features two LED lights, DS1 and DS2 for troubleshooting and four LED lights (DS3, DS6, DS7 and DS8) to show furnace status. The board also has two accessory terminals rated at (1) one amp each. See table 20 for status code and table 21 for troubleshooting diagnostic codes.
Electronic Ignition
At the beginning of each heating cycle, the SureLight con­trol monitors the first stage and second stage combustion air inducer prove switch. The control will not begin the heat­ing cycle if the first stage prove switch is closed (by− passed). Likewise the control will not begin the second stage heating cycle if the second stage prove switch is closed, and will allow first stage heat only. However if the second stage prove switch closes during the first stage pre− purge, the control WILL respond to second stage heat call. Once the first stage prove switch is determined to be open, the combustion air inducer is energized on low (first stage) heat speed. When the differential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re−set period. After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve opens for a 4−second trial for ignition. The ignitor energizes during the trial until flame is sensed. If ignition is not proved during the 4−second period, the control will try four more times with an inter purge and warm−up time between trials of 35 sec­onds. After a total of five trials for ignition (including the ini­tial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that pro­longs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
Two Stage Operation / Thermostat Selection Jumper
The control can be utilized in two modes: SINGLE−STAGE thermostat or TWO−STAGE thermostat. The thermostat selection jumper E20, located just below dip switches 1 through 3 (figure 21), must be positioned for the particular application. The jumper is factory set on TWO" for use with a two−stage thermostat with two stage heat. Re−posi­tion jumper to SINGLE" for use with a single stage thermo­stat with two stage heat. While in the single−stage thermostat mode (single jumper setting), the burners will always fire on first−stage heat. The combustion air inducer will operate on low speed and in­door blower will operate on low heat speed. After a field se­lectable 10 or 15 minute delay (dip switch 3), the unit will switch to second stage heat. While in the two−stage ther­mostat mode (two jumper setting) the burners will fire on first−stage heat. The combustion air inducer will operate on low speed and indoor blower will operate on low heat speed. The unit will switch to second−stage heat on call from the indoor thermostat. If there is a simultaneous call for W1 and W2 (first and second stage heat) the unit will fire on first stage heat and switch to second stage heat after 30 seconds of operation. See Sequence of Operation flow charts in the back of this manual for more detail.
TABLE 16
Two Stage Ignition / Blower Control Terminals
120VAC Neutral
LINE Line 120VAC Neutral
XFMR Transformer 120VAC Neutral
EAC Electronic Air Cleaner 120VAC Neutral
CIRC Indoor Blower 120VAC Neutral
HUM Humidifier 120VAC Neutral
120VAC Line
HUM Humidifier 120VAC Hot
XMFR Transformer 120VAC Hot
LINE Line 120VAC Hot
CIRC Indoor Blower 120VAC Hot
EAC Electronic Air Cleaner 120VAC Hot
TABLE 17
SureLight Board 5 Pin Terminal Designation
PIN # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
Page 25
Page 26
TW0−STAGE, VARIABLE SPEED INTEGRATED
CONTROL BOARD
DIAGNOSTIC
LEDs
LEDs
DS8
DS7
ON−BOARD
JUMPER W914
(cut when CCB1 or
Harmony II are used)
FACTORY−
INSTALLED
DS3
JUMPER
16 PIN BLOWER
CONTROL TERMINALS
(cut when heat pump
THERMOSTAT CONNECTIONS (TB1)
DIP SWITCH FUNCTIONS
DIP SWITCH(ES) FUNCTION
1 and 2 Blower Off Delay
3 Second Stage ON Delay (Single−stage t’stat)
4 Not used 5 and 6 Cooling Mode Blower Speed 7 and 8 Blower Speed Adjustment
9 and 10 Cooling Mode Blower Ramping Profile
11 and 12 Heating Mode Blower Speed
SWITCHES
SWITCHES
ON−BOARD
JUMPER W951
is used with FM21)
DIP
1 − 3
E20
JUMPER
DIP
5 − 12
LED DS6
TABLE 18
SureLight Board 12Pin Terminal Designation
PIN # Function
1 Gas Valve 2nd. Stage (High Fire)
2 Second Stage Pressure Switch
3 Not Used
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve 1st. Stage (Low Fire)
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Out
12 1st Stage Pressure Switch
TABLE 19
SureLight Board 16 Pin Blower Control Terminals
PIN # Function
1 Ground
2 Low Heat Speed
3 Ground
4 DELAY" Dip Switch Selection
5 COOL" Dip Switch Selection
6 Y1" Signal
7 ADJUST" Dip Switch Selection
8 Ground
9 O" From Thermostat
10 DS" Output Signal
11 HEAT" Dip Switch Selection
12 24 VAC
13 HIGH HEAT Speed
14 Y2" Signal
15 G"
16 CFM LED
FIGURE 21
Page 26
Page 27
TABLE 20
ONONON
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
STATUS CODES
STATUS LED COLOR FUNCTION
DS3
ON / OFF ’
DS6
CFM"
DS7
HI / LO"
DS8
HEAT"
GREEN
GREEN
YELLOW
YELLOW DS8−ON indicates the sytem is in HEAT mode.
DS3−ON indicates that the motor has a demand to operate. (This LED must be on in all modes).
DS6−blinking indicates the airflow (CFM) demand in the motor. The air flow is determined by counting blinks between two (2) second pauses. One blink equals roughly 100 CFM.
DS7−ON indicaties the DS to R" jumper has not been cut. When the jumper is cut the system will be operating with LENNOX HARMONY IIt (See Harmony Installation Instructions) or with the CCB1 Efficiency Plus control. CCB1: When ON, a 24 VAC is being applied and when OFF, it has been removed. This on/off operation varies the indoor blower’s performance so dehumidification can be enhanced.
TABLE 21
DIAGNOSTIC CODES
Diagnostic LEDs are labeled DS1 and DS2. See figure 21 for location of diagnostic LEDs.
DS1 DS2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH ON
OFF SLOW FLASH
OFF FAST FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH OFF Flame sensed without gas valve energized.
ON ON
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below 0.23 microAmps. Replace flame sense rod.
ALTERNATING
FAST FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
ALTERNATING
SLOW FLASH
OFF
ALTERNATING
FAST FLASH
Power on − Normal operation. Also signaled during cooling and continuous fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary, secondary or rollout limit switch open. Limits must close within 3 minutes or unit goes into 1 hour Watchguard. Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Pressure switch open; OR: Blocked inlet/exhaust vent; OR: Pressure switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite; OR limit open more than 3 minutes; OR lost flame sense 5 times in one heating cycle; OR pressure switch opened 5 times in one heating cycle.
Circuit board failure or control wired incorrectly. Check 24 and 115 volts to board.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
2) Broken ignitor; OR: Open ignitor circuit;
3) Line voltage below 75 volts. (If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on call from thermostat, and will not respond.
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second). Minimum flame sense current = 0.17−0.22 microAmps.
Page 27
Page 28
Dip Switch Settings Switches 1 and 2 − Blower Off Delay The blower−on delay
of 45 seconds is not adjustable. The blower−off delay (time that the blower operates after the heating demand has been satisfied) can be adjusted by moving switches 1 and 2 on the integrated control board. The unit is shipped from the factory with a blower−off delay of 90 seconds. The blower off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve a supply air temperature between 90° and 110°F at the exact moment that the blower is de−energized. Longer off delay settings provide lower supply air temperatures; shorter settings provide higher supply air temperatu­res.The table below provides the blower off timings that will result from different switch settings.
TABLE 22
Blower Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 1 Switch 2
60 Off Off
90 Off On 120 On Off 180 On On
Switch 3 − Second Stage Delay (Used with Single−Stage Thermostat Only) This switch is used to determine the
second stage on delay when a single−stage thermostat is being used. The switch is factory−set in the ON position, which provides a 10−minute delay before second−stage heat is initiated. If the switch is toggled to the OFF position, it will provide a 15−minute delay before second−stage heat is initiated. This switch is only activated when the thermo­stat selector jumper is positioned for SINGLE−stage ther­mostat use.
Switch 4 − Not used
Switches 5 and 6 − Cooling Mode Blower Speed
Switches 5 and 6 are used to select cooling blower motor speed. The unit is shipped from the factory with the dip switches positioned for high speed (4) indoor blower motor operation during the cooling mode. The table below pro­vides the cooling mode blower speeds that will result from different switch settings. Refer to blower data tables at the front of this manual for corresponding cfm values.
Cooling Mode Blower Speeds
TABLE 23
Speed Switch 5 Switch 6
1 − Low On On
2 − Medium Low Off On
3 − Medium High On Off
4 − High (Factory) Off Off
Switches 7 and 8 − Blower Speed Adjustment Switches 7 and 8 are used to select blower speed adjustment set­tings. The unit is shipped from the factory with the dip switches positioned for NORMAL (no) adjustment. The dip switches may be positioned to adjust the blower speed by +10% or −10% to better suit the application. The table be­low provides blower speed adjustments that will result from different switch settings. Refer to blower data tables at the front of this manual for corresponding cfm values.
TABLE 24
Blower Speed Adjustment
Adjustment Switch 7 Switch 8
+10% (approx.) On Off
NORMAL (Factory) Off Off
−10% (approx.) Off On
Switches 9 and 10 − Cooling Mode Blower Speed Ramping −− Switches 9 and 10 are used to select cooling
mode blower speed ramping options. Blower speed ramp­ing may be used to enhance dehumidification perfor­mance. The switches are factory set at option A which has the greatest effect on blower motor performance. The table below provides the cooling mode blower speed ramping options that will result from different switch settings. The cooling mode blower speed ramping options are detailed on the next page. See unit nameplate for manufacturing date.
TABLE 25
Cooling Mode Blower Speed Ramping
Ramping Option Switch 9 Switch 10
A (Factory) Off Off
B On Off C Off On
D* On On
*Only option for CCB1
Page 28
Page 29
GHR32V units manufactured before April 2003
Ramping Option A (Factory Selection)
D Motor runs at 50% for 1/2 minute. D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor runs at 50% for 1/2 min-
ute.
D Motor ramps down to off.
GHR32V units manufactured April 2003 and later
Ramping Option A (Factory Selection)
S Motor runs at 50% for 30 seconds. S Motor then runs at 82% for approximately 7−1/2 min-
utes. If demand has not been satisfied after 7−1/2 min­utes.
S Motor runs at 100% until demand is satisfied. S Once demand is met, motor runs at 50% for 30 sec-
onds then −
S ramps down to stop.
OFF
1/2 MIN 50% CFM
7−1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
D Motor runs at 50% for 1/2 minute. D Motor then runs at 82% for approximately 7−1/2 min-
utes.
D If demand has not been satisfied after 7−1/2 minutes,
motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
1/2 MIN 50% CFM
7−1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
D Motor runs at 82% for approximately 7−1/2 minutes. D If demand has not been satisfied after 7−1/2 minutes,
the motor runs at 100% until demand is satisfied.
D Once demand is met, motor ramps down to off.
OFF
7−1/2 MIN
82%CFM
COOLING DEMAND
100% CFM
OFF
OFF
1/2 MIN 50% CFM
7 1/2 MIN 82% CFM
COOLING DEMAND
100% CFM
1/2 MIN 50% CFM
OFF
Ramping Option B
S Motor runs at 82% for approximately 7−1/2 minutes. If
demand has not been satisfied after 7−1/2 minutes −
S motor runs at 100% until demand is satisfied. S Once demand is met, motor ramps down to stop.
OFF
7 1/2 MIN 82%CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option C
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor runs at 100% for 60 sec-
onds. Then,
S ramps down to stop.
OFF
100% CFM
COOLING DEMAND
100% CFM
OFF
Ramping Option D
D Motor runs at 100% until demand is satisfied. D Once demand is met, motor ramps down to off.
100% CFM
COOLING DEMAND
Ramping Option D
SMotor runs at 100% until demand is satisfied.
SOnce demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING DEMAND
OFFOFF
Page 29
Page 30
Switches 11 and 12 − Heating Mode Blower Speed
idi
Dehumidification mode begins when rela
satisfied between
d
lid
d
Switches 11 and 12 are used to select heating mode blower motor speed. The unit is shipped from the factory with the dip switches positioned for medium low (2) speed indoor blower motor operation during the heating mode. The table below provides the heating mode blower speeds that will result from different switch settings. Refer to blower data tables at the front of this manual for corresponding cfm val­ues.
TABLE 26
Heating Mode Blower Speeds
Speed Switch 11 Switch 12
1 − Low On On
2 − Medium Low
(Factory)
Off On
3 − Medium High On Off
4 − High Off Off
On−Board Jumper W914
On−board jumper W914, which connects terminals DS and R on the integrated control board, must be cut when the fur­nace is installed with either the Harmony II zone control board or the CCB1 EfficiencyPlus humidity control. Refer to table 27 for operation sequence in applications including a GHR32V, CCB1 and single−speed outdoor unit. Table 28 gives the operation sequence in applications with a two− speed outdoor unit.
On−Board Jumper W951
On−board jumper W951, which connects terminals R and O on the integrated control board, must be cut when the fur­nace is installed in applications which include a heat pump unit and the FM21 FuelMaster control board.
Factory−Installed Jumper Y1 to Y2
A factory−installed jumper from Y1 to Y2 terminals on the integrated control board terminal strip must be removed if two−stage cooling will be used.
Diagnostic LEDs (DS1 and DS2)
Two diagnostic LEDs are located on the two−stage, vari­able speed integrated control just to the left of the first bank of dip switches. These lights’ flashes correspond with diag­nostic codes detailed on in table 15.
Status LEDs (HEAT, HI/LO, ON/OFF and CFM)
The integrated control includes four LEDs which indicate operating status. The green ON/OFF LED is lit any time the blower is operating. The green CFM LED indicates the blower motor speed. Count the number of blinks between the two−second pauses to determine the CFM. Each blink represents approximately 100 CFM. The yellow HI/LO LED is lit when the W914 (DS to R) jumper has not been clipped for CCB1 or Harmony operation. The yellow HEAT LED is lit when the indoor blower is operating at the HEATING speed.
Table 27
Operating Sequence
GHR32V−5, CCB1 and Single−Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System Condition
Normal operation Y1
*Call for humidity
removal during
cooling demand Dehumidification demand satisfied
during cooling demand.
Call for cooling after
call for hum
removal.
Humidity demand satisfied between
thermostat demands
(unit off cycle).
NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther­mostat heating demand. * Reduced blower speed is 77% of COOL for V3 units and 74% of COOL for the V5 units.
ty
Thermostat
Demand
Y1
Y1
None
Y1
None Over setpoint (1 or more) Off
Y1 Change to acceptable COOL
*Relative Humidity
(EfficiencyPlus Lights)
No demand. Humidity
level is acceptable
Humidity level rises
above setpoint. Demand
initiated.
Humidity level falls below
setpoint. No demand
Humidity level above set-
point. Demand initiated.
Humidity level above set-
point. Demand initiated.
Blower
CFM
(COOL)
COOL
77%/74% of COOL
COOL
Off
77%/74%
of COOL
Comments
Compressor demand and indoor blower speed controlled by thermostat demand.
Call for dehumidification initiated by CCB1 control. Indoor blower speed reduced by CCB1 control. When humidity demand is satisfied, blow­er speed immediately increases to the COOL CFM to hasten the end of the cycle.
Dehumidification mode begins when rela­tive humidity is greater than setpoint.
While unit is not operating (no thermostat
emand), s
back up. Blower operates at COOL CFM.
e switch is moved down an
Page 30
Page 31
Table 28
Normal operation
blower speed controlled by
removal during
until after initial thermostat demand is
humidity duri
point, or if slide switch is moved signifi
g
When humidity demand is satisfied
satisfied during
speed compressor operation at begin
d
d
compressor) begins with next thermo
satisfied between
Operating Sequence
GHR32V−5, CCB1 and Two−Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
****Compressor
Speed
Blower CFM
(COOL)
Comments
Normal operation
Call for humidity
1st−stage cooling
demand
Significant increase in
ng
thermostat cooling
demand.
Humidity demand
satisfied durin
thermostat demand.
Call for humidity
removal during 2nd
stage thermostat
eman
*Call for 1st stage
cooling after call for
humidity removal.
Call for 2nd stage
cooling after call for
humidity removal
Call for cooling after
significant increase in
humidity
Humidity demand satisfied between
thermostat demands
(unit off cycle).
Y1 No demand. Acceptable Low
Y2 No demand. Acceptable High HIGH COOL
Y1 No demand. Acceptable Low
Y1
Demand satisfied
Y1
Y1
Y1
Y1
Y1
None
Y1
Y2
Y2
Y2
None
Y1
None
Y2
None
Y1 or Y2
None
Y1 or Y2
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
Humidity level remains
slightly (1) above setpoint.
Demand continues.
Humidity level remains
slightly (1) above setpoint.
Demand continues.
No demand. Acceptable
Humidity level rises signifi-
cantly (2 or more) above
setpoint. Demand initiated.
Humidity level
above setpoint.
Humidity level falls below
setpoint. No demand.
No demand. Acceptable
No demand. Acceptable
No demand. Acceptable
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
No demand. Acceptable
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is slightly (1)
above setpoint.
Humidity level is significantly
above setpoint (2 or more).
Humidity level is significantly
above setpoint (2 or more).
Humidity level is slightly (1)
above setpoint.
Humidity level falls below
setpoint. No demand.
Low
Off
High
Low
High
High
High
Off
Low
High
High
High
Off
Low
Off
High
Off
High
Off
High
55% of
HIGH COOL
55% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
55% of
HIGH COOL
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
55% of
HIGH COOL
**77%/74% of
HIGH COOL
**77%/74% of
HIGH COOL
HIGH COOL
Off
Off
Off
Off
Off
Off
Compressor demand and indoor
blower speed controlled by
thermostat demand
Dehumidification mode does not begin
satisfied and new cooling demand is
initiated.
If humidity rises significantly above set­point, or if slide switch is moved signifi-
cantly, unit will immediately go into de-
humidification mode (in presence of
thermostat demand).
When humidity demand is satisfied,
blower immediately shifts to the COOL
CFM in order to hasten the end of the
cycle. Unit can only shift out of high
speed compressor operation at begin-
ning of next cycle.
Blower immediately changes speed in
response to thermostat demand.
Dehumidification mode (high speed
compressor) begins with next thermo-
stat demand after initial demand is sat-
isfied.
Reduced blower speed (dehumidifica-
tion speed) begins immediately with
thermostat demand
If humidity increases significantly over
setpoint, or if slide switch is moved,
unit immediately goes into dehumidifi-
cation mode (in presence of thermostat
demand).
While unit is not operating (no thermo-
stat demand), slide switch is moved
down and back up. Blower and com-
pressor operate at high speed until
next thermostat demand.
Note − During mode of operation change from cooling to heating, indicating lights will not change until the first thermostat heating demand.
,
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed indefinitely. To reset, move the humidity slide switch all the way down then back up to desired setpoint while the unit is running. ** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5. ***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compres­sor will latch into high speed after a Y1 demand has occurred for that period of time.
Page 31
Page 32
HEAT EXCHANGER
SUPPORT
HOT END HEADER
(COLLECTOR) BOX
GHR32 HEAT EXCHANGER
CONDENSER COIL
COMBUSTION
AIR BLOWER
COMBUSTION AIR
BLOWER MOTOR
COLD HEADER
(COLLECTOR)
BOX
PRIMARY LIMIT
CONTROL (S10)
LENNOX DURALOKPlust
HEAT EXCHANGER
(Assembly)
CLAMSHELL
(Each Segment)
CORBEL ORIFICE
CUPS
FLAME SENSOR
ASSEMBLY
GAS VALVE
MANIFOLD
BURNER
BOX
BURNERS
FIGURE 22
Page 32
BURNER ORIFICE
FLAME SIGHT
(VIEWING) GLASS
SURELIGHT
IGNITOR
Page 33
C−Heating Components (Figure 22)
Combustion air blower (B6), primary limit control (S10), Sur­eLight ignitor, flame sensor, burners, flame rollout switch (S47), gas valve (GV1), combustion air blower switch (S18), and clamshell heat exchangers are located in the heating compartment. The heating compartment can be accessed by removing the burner access panel.
1.Combustion Air Inducer Blower (B6)
All GHR32 units use a two−stage combustion air inducer blow­er to move air through the burners and heat exchanger during heating operation. The blower uses a 120VAC motor. The mo­tor operates during all heating operation and is controlled by the SureLight integrated board (A92) and two−stage control board (A86). The combustion air inducer blower operates on low speed during first stage heat (low fire), then switches to high speed for second stage heat (high fie).
2.Combustion Air Blower Capacitor (C3) PSC Motors only
GHR32 units with a PSC combustion air blower motor, will have a thermally protected 3 MFD 300VAC capacitor. The capacitor is mounted on the combustion air blower housing.
3.Primary Limit Control (S10)
Figure 23 shows the primary limit (S10) used on GHR32 units. S10 is located in the middle of the heating vestibule panel. When excess heat is sensed in the heat exchanger, the limit will open. If the limit is tripped, the furnace control ener­gizes the supply air blower and closes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. See table 29 for limit set points.
SPADE CONNECTORS
GHR32 UNIT SIZE LIMiT SET POINT
GHR32-50 300°
GHR32-75 300°
GHR32Q3/4-100 220°
GHR32-120 175°
LIMIT CONTROL (S10)
LIMIT
INSULATING COVER (s)
FIGURE 23
TABLE 29
DETAIL VIEW OF BURNER CLUSTER MOUNTING
Burner Box
Raised
Toggle Locks
Burner Cluster
Flange
Screw
FIGURE 24
4.Burners
Figure 22 shows the arrangement of the burner box. Table 30 shows how many burners are used per unit. See figure 24 for a more detailed view. Notice the position of the raised toggle lockets.
TABLE 30
NUMBER OF HEAT
GHR32 UNIT SIZE
GHR32-50 2 GHR32-75 3
GHR32Q3/4-100 4
GHR32-120 5
All units use inshot burners Burners are factory set and do not require adjustment. A sight glas s is fu rnis hed in the burn er box assembly for flame viewing. Always operate the unit wit h the burne r box cover in place. Burners can be removed as an assembly for service. Burner maintenance and service is detailed in the SERVICE CHECKS sections of this manu­al. Each burner uses an orifice which is precisely matched to the burner input. The orifice is threaded into the burner man­ifold. The burner is supported by the orifice and will easily slide off for service. Each orifice and burner are sized specif­ically to the unit. Refer to Lennox Repair Parts Listing for cor­rect sizing information. A flame retention ring in the end of each burner maintains correct flame length and shape and keeps the flame from lifting off the burner head. In addition, the burner entrance to each clamshell (Figure 22) is fitted with a corbel cup (orifice) used to direct the flow of combustion prod­ucts.
NOTE−Do not use thread-sealing compound on the ori­fices. Thread-sealing compound may plug the orifices.
EXCHANGER CLAMSHELLS /
BURNERS
Page 33
Page 34
5.Clamshell Heat Exchanger
GHR32 units use an aluminized steel primary and stain­less steel secondary heat exchanger assembly. Table 30 shows how many heat exchanger clamshells are used per unit. Heat is transferred to the air stream from all sur­faces of the heat exchanger. The shape of the heat ex­changer ensures maximum efficiency.
The combustion air blower pulls fresh air through the air in­take box. This air is mixed with gas in the burner venturi and at the corbel orifices. The gas / air mixture is then burned at the entrance of each clamshell. Combustion gases are then pulled through the primary and secondary heat exchangers and exhausted out the exhaust vent pipe.
6.Flame Rollout Switch (S47)
Flame rollout switch S47 is a SPST N.C. high temperature limit located behind the burner air intake fitting on the burner box assembly (see figure 25). S47 is wir ed to the burne r ign itio n control A3. When S47 senses flame rollout (indicating a blockage in the combustion air passages), the flame rol­lout switch trips, and the ignition control immediately closes the gas valve.
Switch S47 in all GHR32 units is factory preset to open at 320_F + 12_F (160_C + 6.7_C) on a temperature rise. All flame rollout switches are manually reset.
7.Gas Valve
The GHR32 uses a gas valve manufactured by White Rodgers or Honeywell. The valve is two-stage internally redundant to assure safety shut−off. If the gas valve must be replaced, the same type valve must be used. The Honeywell valve can be field converted to LP and is adjust­able on both low and high fire. WhiteRodgers supplies two seperate valves for natural and LP and is adjustable for high fire ONLY.
24VAC terminals and gas control knob are located on top of the valve. Terminals on the gas valve are connected to wires from the SureLight integrated control and the two−stage con­trol. 24V applied to the terminals energizes the valve.
Inlet and outlet pressure taps are located on the valve. A regu­lator adjustment screw is located on the side of the valve. Re­fer to figures 26, 27 , and 28 for location of valve features.
NOTE−WhiteRodgers valve is not adjustable on low fire. Do not attempt to regulate low fire manifold pressure.
WHITE RODGERS 36E SERIES GAS VALVE
NATURAL GAS
(LOW HEAT MANIFOLD PRESSURE FACTORY SET.
DO NOT ADJUST.)
HIGH HEAT
MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
FLAME ROLLOUT SWITCH (S47)
FLAME ROLLOUT
SWITCH (S47)
FIGURE 25
HONEYWELL VR8205 Series Gas Valve
HIGH FIRE ADJUSTMENT
SCREW (UNDER CAP)
LOW FIRE
ADJUSTMENT
SCREW
(UNDER CAP)
INLET PRESSURE TAP
VALVE SHOWN IN OFF POSITION
FIGURE 26
MANIFOLD
PRESSURE
TAP
MANIFOLD
PRESSURE
OUTLET ON
SIDE
FIGURE 27
WHITE RODGERS 36E SERIES GAS VALVE
PROPANE GAS
(LOW HEAT MANIFOLD PRESSURE FACTORY SET.
DO NOT ADJUST.)
PM
HI
C
HIGH HEAT MANIFOLD
PRESSURE
ADJUSTMENT
ON SIDE
(under cap)
MANIFOLD
PRESSURE
OUTLET ON
SIDE
FIGURE 28
100% Sealed Combustion
The burner box is completely sealed and operates under a negative pressure. A pressure hose is connected from the burner box to the gas valve regulator. The gas valve senses the pressure in the burner box and changes gas valve outlet (manifold) pressure based on changes in bu rner box pr es­sure. The intent is to compensate for different vent con­figurations which can greatly affect the firing rate of the unit.
Page 34
Page 35
NORMAL OPERATION (Natural Gas Units)
3.5
3.4
3.3
3.2
3.1
3.0
2.9
2.8
GAS VALVE OUTPUT
2.7
2.6
MANIFOLD PRESSURE (positive inches water gauge)
2.5
Gray area indicates normal operating range + 10% of manifold pressure The purpose of this chart is to explain unit operation . Each unit may vary depending on installation, altitude, intake/exhaust configuration and other factors.
OPERATION AT THIS EXTREME
MAY INDICATE A BLOCKED
INLET OR OTHER PROBLEM"
BURNER BOX PRESSURE
(Negative inches water gauge
measured on left side of burner box)
FIGURE 29
NORMAL OPERATION (L.P. Gas Units)
10.0
9.9
9.8
9.7
9.6
9.5
9.4
9.3
GAS VALVE OUTPUT
9.2
9.1
MANIFOLD PRESSURE (positive inches water gauge)
9.0
Gray area indicates normal operating range + 10% of manifold pressure The purpose of this chart is to explain unit operation . Each unit may vary depending on installation, altitude, intake/exhaust configuration and other factors.
OPERATION AT THIS EXTREME
MAY INDICATE A BLOCKED
INLET OR OTHER PROBLEM"
BURNER BOX PRESSURE
(Negative inches water gauge
measured on left side of burner box)
Figures 29 and 30 show how gas valve manifold pressure changes as burner box pressure changes. The GHR32 is a self adjusting unit to maintain a constant output.
8.Combustion Air Prove Switch (S18) GHR32−1/−4 Units & (S102) GHR32−5 Units
GHR32 series units are equipped with a differential pressure switch S18 or S102 located on either side of the heating compartment cabinet (factory installed on left side ).The switch monitors the differential pressure be­tween the downstream and upstream flue gas pressures. When the unit is installed for horizontal right-hand dis­charge, the air proving pressure switch must be moved to the opposite side of the unit. Any one of four different switches may be on the unit. One is manufactured by MPL. The other three switches are manufactured by TRIDELTA / HONEY­WELL. Each switch operates the same and can be replaced
−1.0−0.20 −0.4 −0.6 −0.8
−1.0−0.20 −0.4 −0.6 −0.8
with one another. See figure 31 for combustion air prove switch replacment. Hoses must be connected to correct taps for switch to operate safely and properly. GHR32 model units have color coded tubing to designate positive and negative sides of the pressure switch. Red/Square tubing should always be connected to the positive side of the pres­sure switch. Gray or Black /Round tubing should always be connected to the negative side of the pressure switch. See fig­ure 31.
The switch is a SPST N.O. pressure switch electrically con­nected to the integrated control. The purpose of the switch is to prevent burner operation if the combustion air blower is not moving enough air for proper combustion.
On start-up, the switch senses that the combustion air blower is operating. It closes a circuit to the ignition control when the difference in pressure across the pressure switch ex­ceeds 0.90" W.C. (223.78Pa). If the switch doe s no t s uc­cessfully sense the required differential, the switch can­not close and the furnace cannot operate. The switch is factory set and is not adjustable. If the flue or air inlet be­come obstructed during operation, the switch senses a loss of pressure differential and opens the circuit to the igni­tion control. If the condensate line is blocked, water will back up into the header box and reduce the pressure differential across the switch. The pressure switch will open if the differ­ential drops below 0.75" W.C. +
05" W.C. (186.48 Pa +
12.4 Pa).
FIGURE 30
Page 35
Page 36
NEGATIVE
PRESSURE
(Marked With "V")
TRIDELTA / HONEYWELL
(All Metal Construction)
NEGATIVE
PRESSURE (NO Markings) Hose Connec-
tion Side Only)
MPL
POSITIVE
PRESSURE
(Marked With "P")
POSITIVE PRESSURE (NO Markings Electrical Terminal
and Hose Connection Side)
NEGATIVE PRESSURE
(Marked With "−")
POSITIVE
PRESSURE
(Marked With "+")
TRIDELTA / HONEYWELL IS2
TRIDELTA / HONEYWELL
(Metal/Plastic Construction)
NEGATIVE PRESSURE
(gray side marked −")
HORIZONTAL LEFT HAND AIR DISCHARGE
Connect hose (red square) to POSITIVE side on pres-
sure switch and open tap on FRONT of collector box.
Pressure
Switch
AIR FLOW
Connect hose (gray or black
round) To "NEGATIVE"side on
pressure switch and open tap on
SIDE of collector box.
NEGATIVE PRESSURE CONNECTIONS
(Gray or Black round tubing beginning with −3 models)
SCALE1.000
POSITIVE PRESSURE
(black side marked +")
DOWN FLOW AIR DISCHARGE
Connect hose (gray or black round) To NEGATIVE side
on pressure switch and open tap on FRONT of collector
box.
AIR FLOW
Pressure
Switch
Connect hose
(red square) to
POSITIVE side
on pressure
switch and open
tap on FRONT
of collector box.
Collector Box
HORIZONTAL RIGHT HAND DISCHARGE
Connect the red square hose to the POSITIVE side on pressure
switch and the open tap on the FRONT of the collector box.
Pressure
Switch
must be
on top side
of unit.
Collector Box
BLANK STEMS EARLY MODEL
UNITS ONLY
POSITIVE PRESSURE CONNECTIONS
(Red tubing)
AIR FLOW
Connect the gray or black round hose to the NEGATIVE
side on the pressure switch and SIDE of the collector box.
FIGURE 31
Page 36
Page 37
To troubleshoot the pressure switch, temporarily jumper the
switch. The unit will not fire with pressure switch jumpered.
Therefore, the pressure switch must be bypassed after the
combustion air blower is activated. This will determine if the
pressure switch and furnace are operating properly. However,
this may not indicate if the sealed combustion system is oper-
ating properly. If the unit cannot attain 0.75" W.C. (186.48 Pa )
differential, the unit will not operate.
D−Blower Compartment (Figures 33 and 34)
Blower motor (B3), capacitor (C4), and secondary limit con­trol (S21) are located in the blower compartment shown in figure 33. Blower motor (B3), Coil choke (L13) and secon­dary limit (S21) are shown in figure 34. The blower compart­ment can be accessed by removing the blower access pan­el.
IMPORTANT
Unit will not operate with pressure switch bypassed upon start-up. To troubleshoot pressure switch, jumper pressure switch following activation of com­bustion air blower!!
Checks of pressure differential can aid in troubleshooting.
When measuring the pressure differential, readings should be
taken at the pressure switch. Lack of differential usually indi-
cates problems in the intake or exhaust piping, but may ind i-
cate problems in the heat exchanger, condensing coil,
header boxes, combustion blower or other compo-
nents.
Measuring pressure differential
The differential pressure is the difference in pressure mea-
sured on either side of the pressure switch:
1 − Remove thermostat demand and allow unit to cycle
off.
2 − Disconnect hose from front of pressure switch and
install tee as shown in figure 32. Repeat sequence for hose connected to back of switch.
BLOWER COMPARTMENT
Q MODELS
SECONDARY LIMIT
CONTROL (S21)
BLOWER MOTOR
(B3)
BLOWER MOTOR
CAPACITOR (C4)
FIGURE 33
TEE AND 1/4"i.d. RUBBER HOSE FIELD PROVIDED
TO PRESSURE
SENSING HOSE
TO PRESSURE
SWITCH
TO DRAFT GAUGE
FIGURE 32
3 − Install manometer (draft gauge) to open ends of tee’s.
The hose from the back side of the switch goes to the zero side of the gauge.
4 − Operate unit and observe draft gauge reading. Read-
ings will change as heat exchanger warms.
a. Take one reading immediately after startup. b. Take a second reading after unit has reached steady state (approximately 5 minutes).
Pressure differential should be greater than .75"
W.C. (186.48 Pa).
5 − Remove thermostat demand and allow to cycle off.
6 − Remove draft gauge and Tee’s. Reinstall combustion air
sensing hoses to the pressure switch.
BLOWER COMPARTMENT
V MODELS
SECONDARY
LIMITS (S21)
COIL
CHOKE
(L13)
To Remove Blower From Unit: Remove Bolts and
Wiring Jackplugs. Then Slide Out Front of Unit.
BLOWER
WHEEL
BLOWER
MOTOR (B3)
FIGURE 34
Page 37
Page 38
1.Blower Motor (B3) and Capacitor (C4) GHR32Q Models
All GHR32Q model units use single phase direct drive blow­er motors. All motors are 120V permanent split capacitor motors to ensure maximum efficiency. See motor name­plate or SPECIFICATIONS section for motor ratings. Rat­ings for capacitor will be on side.
2.Secondary Limit Control (S21)
The secondary limit (S21) on GHR32 units is mounted on the back side of the blower housing. When excess heat is sensed in the blower compartment, the limit will open. If the limit is tripped, the furnace control energizes the supply air blower and closes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch opens at 160_F + 5_F (71.1_C + 2.8_C) on a temperature rise and re­sets at 130_F + 8_F (54.4_C + 4.4_C) on a temperature fall. The switch is factory set and cannot be adjusted. The setpoint is printed on the face plate of the limit.
SECONDARY LIMIT CONTROL (S21)
SPADE CONNECTORS
LIMIT
INSULATING COVER (s)
GHR32V BLOWER MOTOR B3
J48
SHAFT
MOTOR
CONTROLLER
J49
FIGURE 36
GHR32V BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 37
A solid-state controller is attached to the motor. The controller is primarily an A.C. to D.C. converter. Con­verted D.C. power is used to drive the motor. The con­troller contains a microprocessor which monitors vary­ing conditions inside the motor (such as motor workload).
The controller uses sensing devices to sense what position the rotor is in at any given time. By sensing the position of the rotor and then switching the motor windings on and off in se­quence, the rotor shaft turns the blower.
FIGURE 35
3. Blower Motor (B3) GHR32V MODELS
GHR32V model units use a single−phase, electronically con­trolled D.C. brushless motor (controller converts single phase A.C. to three phase D.C.), with a permanent-magnet-type ro­tor (figure 36). Because this motor has a permanent magnet rotor it does not need brushes like conventional D.C. motors. Internal components are shown in figure 37. The stator wind­ings are split into three poles which are electrically connected to the controller. This arrangement allow s mot or windin gs to turn on and off in sequence by the controller.
DANGER
Disconnect power from unit and wait at least five minutes to allow capacitors to discharge before at­tempting to adjust motor speed tap settings. Failure to wait may cause personal injury or death.
GHR32V series blower motor ratings are listed in the SPECIFICATIONS section. All GHR32V blower motors use single phase power. An external run capacitor is not used. The motor uses permanently lubricated ball-type bearings. The VSM is a two part component; the motor and the control module. If motor fails, it is quite possible the control module only, will need to be replaced. Len­nox provides a replacement kit for the control module.
Internal Operation
Each time the controller switches a stator winding (figure 37) on and off, it is called a pulse." The length of time each pulse stays on is called the pulse width." By varying the pulse width (figure 38), the controller varies motor speed (called pulse­width modulation"). This allows for precise control of motor speed and allows the motor to compensate for varying load conditions as sensed by the controller. In this case, the control­ler monitors the static workload on the motor and varies motor rpm in order to maintain constant airflow (cfm).
The motor is equipped with 11 incremental taps which are driv­en by the integral controller. The controller is capable of con­trolling three of the 11 taps.
Page 38
Page 39
The motor controller is driven by the VSP2−1, VSP3−1 or two stage integrated SureLight control The VSP re­ceives its demand (PWM signal or fixed 24 VAC or VDC signal) from optional controls such as the Harmony zone con­trol system, Efficiency Plus Humidity Control (CCB1) or a con­ventional thermostat.
Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel. The control­ler monitors the static work load on the motor and motor amp­draw to determine the amount of rpm adjustment. Blower rpm may be adjusted any amount in order to maintain a constant cfm as shown in Blower Ratings Tables. The amount of adjust­ment is determined by the incremental taps which are used and the amount of motor loading sensed internally. The cfm remains relatively stable over a broad range of static pressure. Since the blower constantly adjusts rpm to maintain a specified cfm, motor rpm is not rated. Hence, the terms blower speed" and speed tap" in this manual, on the unit wiring diagram and on blower B3 refer to blower cfm regardless of motor rpm.
When Harmony is used, speed taps are overridden and a PWM signal generated by the Harmony controller continuous­ly varies motor speed based upon zone demands.
Initial Power Up
When line voltage is applied to B3, there will be a large inrush of power lasting less than 1/4 second. This in rush charges a bank of DC filter capacitors inside the controller. If the discon­nect switch is bounced (rapid turning on and off) when the dis­connect is closed, the disconnect contacts may become welded. Try not to bounce the disconnect switch when apply­ing power to the unit.
Motor Start-Up
When B3 begins start-up, the motor gently vibrates back and forth for a moment. This is normal. During this time the elec­tronic controller is determining the exact position of the rotor. Once the motor begins turning, the controller slowly eases the motor up to speed (this is called soft-start"). The motor may take as long as 10-15 seconds to reach full speed. If the motor does not reach 200rpm within 13 seconds, the motor shuts down. Then the motor will immediately attempt a re­start. The shutdown feature provides protection in case of a frozen bearing or blocked blower wheel. The motor may at­tempt to start eight times. If the motor does not start after the eighth try, the controller locks out. Reset controller by momen­tarily turning off power to unit.
The DC filter capacitors inside the controller are connected electrically to the speed tap wires. The capacitors take
approximately 5 minutes to discharge when the dis­connect is opened. For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempting to change speed taps.
Page 39
Page 40
MOTOR SPEED CONTROL WITH D.C. PULSE-WIDTH MODULATION
Motor speed is determined by the size of the electrical pulse sent to the
motor windings. The longer the pulse, the faster the motor.
OUTPUT FROM CONTROLLER TO MOTOR WINDINGS
WINDINGS TURNED OFF
The frequency of the pulses to the windings is 20KHz.
DO NOT ATTEMPT TO MEASURE THESE VOLTAGES.
LOW SPEED HEAT/COOL (output from controller to motor windings)
One
Pulse
One revolution
325VDC
O volts
WINDING #1
325VDC
O volts
WINDING #2
325VDC
O volts
WINDING #3
HIGH SPEED HEAT (output from controller to motor windings)
One revolution
325VDC
O volts
WINDING #1
325VDC
O volts
WINDING #2
325VDC
O volts
WINDING #3
WINDINGS TURNED ON
ON PULSE
OFF PULSE
HIGH SPEED COOL (output from controller to motor windings)
One revolution
325VDC
O volts
WINDING #1
325VDC
O volts
WINDING #2
325VDC
O volts
WINDING #3
FIGURE 38
Page 40
Page 41
External Operation (Speed Tap Priority)
Figure 39 shows the two quick-connect jacks (J48 and J49) which connect the motor to the GHR32V. Jack J48 is the power plug and jack J49 connects the unit controls to the motor.
Line voltage must be applied to J48 pin 5 in order for the motor to operate. When using 120VAC pins 1 and 2 must be jumpered. When control voltage is applied to J49 pin 3 and 15 (single stage heating and cooling), the motor is en­ergized on the low speed heat/cool tap.
4.Choke Coil (L13)
A choke coil is used on all GHR32V units. The choke is located on the blower housing and is used to block radio fre­quency interference.
Precautions
If the GHR32 V or its electronically controlled blower motor is improperly or inadequately grounded, it may cause television interference (commonly known as RFI or radio frequency in­terference).
When voltage is applied to J49 pin 2 in addition to pin 3 and 15 (second stage heating), the blower is energized on the high speed heating tap. When voltage is applied to J49 pin 10 in addition to pin 3 and 15 (second stage cooling), the blower is energized on the high speed cooling tap. The mo­tor assigns priority to J49 pin 2 so that if a call for cooling and a call for heating are concurrent, heating call overrides and the blower operates on high speed heating tap.
ICM2 with VSP3 or Two stage Variable Speed Control
The ICM2 operates slightly different than stated above when matched with the VSP3 or Two stage variable speed control. When control voltage is applied to J49 pin 3 and 15, the motor is energized on continuous fan. When voltage is applied to J49 pin 2 in addition to pin 3 and 15 (first stage heating), the blower is energized on the low speed heating tap. When voltage is applied to J49 pin 13 in addition to pin 3 and 15 (second stage heating), the blower is energized on the high speed heating tap. The motor assigns priority to J49 pin 2 so that if a call for cooling and a call for heating are concurrent, heating call overrides and the blower operates on high speed heating tap.
BLOWER B3 HARNESS CONNECTORS
POWER
CONNECTOR J48
J48
PIN 1 - Jumper PIN 1 to PIN2 for 120VAC line input only. PIN 2 - Jumper PIN 1 to PIN2 for 120VAC line input only. PIN 3 - Ground PIN 4 - AC Line PIN 5 - AC Line
CONTROL
CONNECTOR J49
1
J49
PIN 1 - C1 PIN 2 - W / W1 PIN 3 - C2
1
PIN 4 − Delay PIN 5 - Cool PIN 6 - Y1 PIN 7 - Adjust PIN 8 - 0ut PIN 9 - 0 PIN 10 - BK / PWM PIN 11 - Heat PIN 12 - R PIN 13 - EM / W2 PIN 14 - Y / Y2 PIN 15 - G PIN 16 - Out +
FIGURE 39
This interference is caused by internal switching fre­quencies of the motor controller (see figure 40). TV in­terference may show up as small specks or lines which randomly appear on the TV screen accompanied by pops or clicks in the sound. Before attempting any service, make sure the indoor unit is causing the interference. To check, discon­nect power to indoor unit then check TV for continued signs of interference.
TV interference may be stopped by making sure the mo­tor is solidly grounded to the cabinet (metal to metal) and by making sure the cabinet is solidly grounded. If TV in­terference persists, make sure the television (and all af­fected RF appliances) are moved away from the GHR32V. Also make sure affected appliances are connected to a sepa­rate electrical circuit.
ECM SWITCHING FREQUENCY
The electrical pulses to the windings cycle on and off at a rate of
20,000 cycles per second (20Khz, this is called the switching
frequency). The effective D.C. voltage can be varied by chang-
ing the pulse width. The switching frequency is necessary in
order to vary the speed of the motor. If the motor is not securely
grounded to the cabinet and if the cabinet is not securely
grounded, the switching frequency may cause television inter-
OUTPUT FROM CONTROLLER TO MOTOR WINDINGS
One Pulse
325VDC
O volts
325VDC
O volts
325VDC
O volts
PULSE ON
PULSE OFF
WINDING OFF
WINDING #1
WINDING #2
WINDING #3
One cycle
ference.
ELECTRICAL
325VDC
PULSE
O volts
Switching Frequency
20Khz
ONE
FIGURE 40
Page 41
Page 42
II−PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation in­structions and applicable codes.
A−PVC Joint Cementing Procedure
WARNING
DANGER OF EXPLOSION! Fumes from PVC glue may ignite during system check. Remove spark plug wire from ignition control before 120V power is applied. Reconnect wire after two minutes.
B−Venting Considerations
All GHR32 furnaces must be vented independently as shown in figure 42 and must not be connected to a com­mon venting system. If a GHR32 furnace replaces a less efficient furnace which was vented with other gas ap­pliances into a common vent, the size of the common vent pipe must be appropriate for gas appliances which remain connected. Without the heat of the original furnace flue prod­ucts, the vent pipe is probably oversized for the single water heater or other appliance(s). The common vent should be checked for proper draw for all appliance(s) which remain connected.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any
ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of
pipe.
5 − Uniformly apply liberal coat of PVC primer for PVC or
ABS cleaner for ABS to inside socket surface of fitting and male end of pipe to depth of fitting socket.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.
NOTE−Time is critical at this stage. Do not allow primer to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn pipe 1/4 turn during assembly (but not after pipe is fully inserted) to dis­tribute cement evenly. Once joint is made, PVC may swell. Hold joint together until bonded (approxi­mately 20 seconds).
NOTE−Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
Checks of Common Venting System for Other Gas Appliances (Water Heater, etc...)
1 − Unused openings in the common venting system must be
sealed.
2 − The venting system should be visually checked for proper
size and horizontal pitch. You should also check and de­termine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an un­safe condition.
3 − Close all building doors and windows and all doors
between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common vent­ing system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance will operate continuously.
5 − Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use match or candle flame, or smoke from a cigarette or cigar.
6 − After it has been determined that each appliance re-
maining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
8 − After assembly, wipe excess cement from pipe at
end of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may in­dicate a defective assembly due to insufficient sol­vent.
9 − Handle joints carefully until completely set.
7 − If improper venting is observed during any of the tests, the
common venting system must be corrected. The com­mon venting system should be resized to approach the minimum size as determined by using the appropriate tables in appendix G in the current standards of the Na­tional Fuel Gas Code in the U.S.A. or category 1 in the Natural Gas and Propane Installation Code in Canada.
Page 42
Page 43
GHR32 Intake and Exhaust Piping Considerations
If the GHR32 venting system must be altered or repaired, use the following as a guide. Intake and exhaust pipes may be routed either horizontally through an outside wall or verti­cally through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 42 through 45 show typical terminations.
1 − Use only recommended piping materials for both in-
take and exhaust piping.
2 − Secure permanent joints gas tight using approved ce-
ment.
3 − Piping diameters should be determined according to
length of pipe run. See table 31. Locate intake piping upwind (prevailing wind) from exhaust piping. To avoid recirculation of exhaust gas on roof terminations, end of exhaust pipe must be higher than intake pipe.
Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one through the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.
4 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il­lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina­tions.
NOTE−If winter design temperature is below 32_ F (0_C), exhaust piping must be insulated with 1/2" (13mm) Ar­maflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to outside air; exterior exhaust pipe must be insu­lated with 1/2" (13mm) Armaflex or equivalent. In ex­treme cold climate areas, 3/4" (19mm) Armaflex or equivalent is recommended. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect insulation from deterioration.
5 − Exhaust piping must terminate straight out or up as
shown. On roof terminations, the intake piping should terminate straight down using two 90_ elbows (See figure 42). In rooftop applications, a 2" X 1−1/2" (51mm X 38mm) reducer for 2" (51mm) venting, 3" x 2" (76mm X 51mm) reducer for 3" (76mm) venting must be used on exhaust piping at the point where it exits the structure to improve the velocity of exhaust and force flue products away from intake piping.
NOTE-Care must be taken to avoid recirculation of ex­haust back into intake pipe.
6 − On side wall exits, exhaust piping should extend a
maximum of 12" (395mm) beyond the outside wall. Intake piping should be as short as possible. See figure 44.
7 − Minimum separation distance between the end of
the exhaust pipe and the end of the intake pipe is 8" (203mm).
8 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob­structions, refer to figure 45 for proper piping method. Piping must be supported every 3 ft. (.91m) as shown in figure 41 and must be insulated. When exhaust and intake piping must run up an outside wall, the exhaust piping is reduced accordingly after the final elbow.
9 − Position termination ends so they are free from any ob-
structions and above snow accumulation level (where ap­plicable). Termination ends must be a minimum of 12" (305mm) above grade level. Do not point into window wells, stairwells, alcoves, courtyard areas or other re­cessed areas. Do not position termination ends directly below roof eaves.
10− Suspend piping using hangers at a minimum of every
5 feet (1.52m) for schedule 40 PVC and every 3 feet (.91m) for ABS−DWV, PVC−DWV, SDR−21 PVC, and SDR−26 PVC piping. A suitable hanger can be fabri­cated by using metal or plastic strapping or a large wire tie. See figure 41.
Page 43
Page 44
METAL OR PLASTIC
S
T
STRAPPING
FIGURE 41
60G77  For 2 inch (51 mm) Venting 33K97  For 3 inch (76 mm) Venting
2 x 1-1/2 in. (51 x 38 mm) 60G77
3 x 2 in. (76 x 51 mm) 33K97
REDUCER BUSHING (Furnished)
37
(940)
INTAKE AIR
11− In areas where piping penetrates joists or interior walls,
hole must be large enough to allow clearance on all sides of pipe through center of hole using support straps.
12− Isolate piping at the point where it exits the outside wall
or roof.
13− Unit should not be installed in areas normally sub-
ject to freezing temperatures.
14− When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining exhaust tee, cold end header collector box, condensate collection trap and lines.
Intake Piping Requirements
Piping must be routed to outside of structure.
IMPORTANT
Combustion air intake inlet and exhaust outlet should not be located within 6 ft. (1.8m) of dryer vent or combustion air inlet or outlet of another ap­pliance. Piping should not exit less than 3 ft. (.91m) from opening into another building.
3 (76)
ELBOW
(Furnished)
CLAMP
(Furnished)
INTAKE AIR
TERMINATION ASSEMBLY
EXHAUST
AIR
(Furnished)
60L46  For 3 inch (76 mm) Venting
46−3/4 (1187)
6−1/2 (165)
4−1/2 (114)
INTAKE AIR
ELBOW
(Field Supplied)
TERMINATION ASSEMBLY
(Furnished)
EXHAUST
AIR
CONCENTRIC WALL TERMINATION APPLICATIONS
Cat. No. A
60G77 10-1/2 (267) max. 33K97 10-1/2 (267) max. 60L46 7−1/2 (191) max.
EXHAUST
AIR
A
INTAKE
AIR
EXHAUS
AIR
INTAKE PIPE
Not Furnished)
12 (305)
Minimum
Above
Average
Snow
Accumulation
ROOF TERMINATION KITS 15F75  For 2 inch (51 mm) Venting 44J41  For 3 inch (76 mm) Venting
3 in. MAX.
(76 mm)
FLASHING
(2)
(Furnished)
INSULATION SLEEVES (2)
(Furnished)
8 (203)
Minimum
2 x 1-1/2 in.
(51 x 38 mm) 15J75
or
(76 x 51 mm) 44J41
REDUCER BUSHING
(Not Furnished)
EXHAUST PIPE (Not Furnished)
ARMAFLEX
INSULATION
(Not Furnished)
3 x 2 in.
FIGURE 42
INTAKE
AIR
OUTSIDE
WALL
INTAKE
AIR
GRADE
12 (305)
Minimum
Above Grade
CONCENTRIC ROOF TERMINATION APPLICATION
FLASHING
12 (305)
Minimum
Above Average
Snow
Accumulation
CLAMP
SHEET METAL STRAP
(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)
FIGURE 43
Page 44
Page 45
8 in. (203 mm)
5
u
R
minimum
(2 Furnished 1 for intake and 1 for exhaust)
NOTE  12 in. (305 mm) minimum height above
average snow accumulation.
12 in. (305 mm) maximum
6 in. (152 mm)
maximum
Typical Application
GALVANIZED STEEL INSIDE SEAL CAP
PVC COUPLING
(Not Furnished)
WALL TERMINATION KIT (RING KIT) 15F74  For 2 inch (51 mm) Venting
NOTE  Not for use with 3 inch (76 mm) Venting
NOTE  EXHAUST PIPE SHOWN
INSULATION SLEEVE
(2 Furnished 1 for intake and 1 for exhaust)
STAINLESS STEEL OUTSIDE SEAL CAP
(2 Furnished 1 for intake and 1 for exhaust)
2 in. (51 mm) PVC
(Not Furnished)
ARMAFLEX INSULATION
(Not Furnished)
INDOOR
EXHAUST ASSEMBLY
(Furnished)
INDOOR
INTAKE ASSEMBLY
(Furnished)
2 in. (51 mm) COUPLING
(Furnished)
*Bushing outside on plate for 44J40 kit.
SEAL RINGS (4 Furnished
2 for intake and 2 for exhaust)
2 x 1-1/2 in. (51 x 38 mm) 22G44
3 x 2 in. (76 x 51 mm) 44J40
*REDUCER BUSHING
FACE PLATE
(Furnished)
(Furnished)
INTAKE
AIR
GASKET
(Furnished)
12
(305)
FIGURE 44
OUTDOOR
EXHAUST ASSEMBLY
(Furnished)
EXHAUST
AIR
2 x 1-1/2 in. (51 x 38 mm)
REDUCER BUSHING
(Not Furnished)
WALL TERMINATION KITS (CLOSE-COUPLE)
22G44  For 2 inch (51 mm) Venting
44J40  For 3 inch (76 mm) Venting
If Intake and Exhaust Pipe is less than 12 in. (305 mm) above snow accumula­tion or other obstructions, field fabri­cated piping must be installed.
EXHAUST
AIR
INTAKE
AIR
5 (127)
5-1/2 (140)
EXHAUST
AIR
INSULATION
(Not Furnished)
FIGURE 45
Page 45
12
(305)
2
(51)
INTAKE
AIR
12
(305)
GRADE
12 (30
Minim
ABOVE G
Page 46
TABLE 31
3 in. (76 mm)
2 in. (51 mm) 2 i
(51
)
3 in. (76 mm)
Maxi
l
aust
run, either intake or exhaust
3 i
(76
)
Not Available
3 in. (76 mm)
N
Acceptable
()
A
A
N
NOTE Exhaust pipe
Termination Kits
NOTE Intake
12 in. (305 mm) in length
A
A
N
N
pp
Kits f
(76
)
Venting
must be terminated with
A
)pp,
VENTING REQUIREMENTS
Model No. GHR32−50 GHR32−75 GHR32−100 GHR32−120
Vent Pipe Minimum Equivalent Length with Accelerator − Exhaust pipe should terminate with an accelerator. See Termination Kits, below.
feet (m) Minimum Vent Pipe Diameter Required
15 (4.6) Not Recommended 2 in. (51 mm) 20 (6.1) 25 (7.6) 30 (9.1)
Maximum Equivalent Vent Length
mum length is for one individua
run, either intake or exh
.
.
35 (10.7) 40 (12.2) 45 (13.7) 50 (15.2) 55 (16.8) 60 (18.3) 70 (21.3) 80 (24.4) 90 (27.4) 100 (30.5)
VENT/INTAKE AIR TERMINATION KIT USAGE
Cat. No.
Kits for 2 in. (51 mm)
Venting
NOTE − Exhaust pipe
must be terminated with
an accelerator; 1−1/2 in.
(38.1 mm) diameter pipe,
NOTE − Intake
and Exhaust
pipes must be the
same
diameter.
2 in. (51 mm) pipe may be used to adapt terminations and intake/exhaust furnace connections. The TOTAL of 2 in. (51 mm) pipe that can be used CANNOT exceed 3 feet (1 m).
Equivalent Vent Lengths:
10 ft. (3 m) and two 90° elbows of 2 in. (51 mm) pipe equals 20 ft. (6.1 m).5 ft. (1.5 m) and two 90° elbows of 2 in. (51 mm) pipe equals 15 ft. (4.6 m).5 ft. (1.5 m) and two 90° elbows of 3 in. (76 mm) pipe equals 15 ft. (4.6 m).One 90_elbow equals 5 feet (1.5 m) of straight vent pipe. One 45_ elbow equals 2.5 feet (.75 m) of straight vent pipe.When additional/field supplied venting is used to clear average snow accumulation, the additional length of pipe and elbows must be figured into
the Maximum Equivalent Vent Length/Minimum Vent Pipe Diameter Requirements.
90° intake elbow CANNOT be used in this application.12 feet (3.6 m) of additional vent must be figured into the Maximum Equivalent Vent Length/Minimum Vent Pipe Diameter Requirements if this kit is
used. Only used with minimum vent length.
12 in. (305 mm) in length.
or 3 in.
Venting
NOTE − Exhaust pipe
an accelerator; 2 in. (51
mm) diameter pipe, 12 in.
(305 mm) in length.
mm
Roof Kit (15F75) Wall Ring Kit (15F74) Closed Couple Wall Kit
(22G44) Concentric Roof/Wall Kit (60G77) Not Available Closed Couple Wall Kit
(30G28)
.
Closed Couple Wall Kit with extension riser (30G79)
Cat. No.
Concentric Roof/Wall Kit (60L46) Not Available Acceptable Vent/Intake Air Roof Kit
(44J41)
Closed Couple Wall Kit (44J40)
Concentric Roof/Wall Kit (33K97) Acceptable
20 ft. (6.1 m) 20 ft. (6.1 m) 15 ft. (4.6 m) 15 ft. (4.6 m)
3 in. (76 mm)
2 in. (51 mm)
n.
mm
n.
3 in. (76 mm)
cceptable
cceptable
Acceptable Acceptable Acceptable
cceptable
cceptable
mm
3 in. (76 mm)
ot Available
Acceptable
Acceptable
ot Available
Not Available
ot Available
ot Available
cceptable
Exhaust Piping Requirements
This unit is designed for left or right air exhaust piping for the down-flow configuration. In horizontal applications, flue piping must exit the top side of the unit.
All horizontal runs of exhaust pipe must slope toward unit. A minimum of 1/4" (6mm) drop for every 12" (305mm) of horizontal run is mandatory for drainage. Horizontal runs of exhaust piping must be supported every 5 ft. (1.5m) [3 ft. (0.9m) for ABS and SDR] using hangers.
NOTE−Exhaust piping must be installed on the same side as the condensate trap.
NOTE−Exhaust piping should be checked carefully to make sure there are no sags or low spots.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is above the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pressure and must be completely sealed to pre­vent leakage of combustion products into the living space.
Page 46
Page 47
Condensate Piping Requirements
The GHR32 unit is designed for either left or right con­densate plumbing in the down-flow configuration. In the horizontal position, trap should extend below unit; pro­vide for a 3-3/4" (92mm) service clearance. Condensate drain line should be routed only within the conditioned space to avoid freezing of condensate and blockage of drain line. An electric heat cable should be used where condensate piping is exposed to unconditioned areas. If condensate piping needs to be relocated to another position or removed for service, use the following procedure to reinstall.
CAUTION
Do not use copper tubing or existing copper condensate lines for drain line.
1 − Determine the side the condensate trap is to be installed.
Remove temporary plugs from condensate collar on which the condensate trap is to be installed.
CONDENSATE ASSEMBLY
(Right Side Installation Shown)
CONDENSATE
STEMS
DRAIN
PLUG CAP
FIGURE 46
COLLAR
DRAIN PLUG
CONDENSATE
DRAIN LINE
CONNECTION
(route line to one side
glue cap to unused side)
CONDENSATE
TRAP
CAUTION
5 − Install a tee and vent pipe in the drain line near the trap.
Top of vent pipe should be 7" (178mm) above drain level on trap.
6 − Condensate line must be sloped downward away from
trap (a minimum of 1/4" [6mm] drop for each 12" [305mm] of horizontal line) to drain. If drain level is above condensate trap, condensate pump must be used in condensate line.
III−START-UP A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be with-
in range listed on the nameplate. If not, consult th e pow er company and have voltage condition corrected be­fore starting unit.
3 − Inspect condition of condensate traps and drain as-
sembly. Disassemble and clean seasonally.
B−Heating Start-Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been under­water. Inspect the furnace and replace any part of the control system and any gas control which has been under water.
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
Condensate trap must be installed on the same side as exhaust piping in downflow applica­tions and on bottom of unit in horizontal ap­plications.
2 − Apply glue to condensate trap stems and insert trap
into holes provided in condensate collar. Make sure condensate trap is completely sealed to avoid any leaks. Use the provided 1/2" screw to secure the top of the condensate trap to the side of the unit. See figure 46.
3 − For downflow applications only, remove plugs from the
unused condensate collar on the opposite side of the unit. Apply glue to the plugs and place them back into the condensate collar.
4 − Glue the drain line (field provided) to the trap. Route
drain line to an open drain. Glue 1" (25mm) cap (pro­vided on trap) on unused condensate drain line con­nection.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, do not force. Force or attempted repair may result in a fire or explosion.
GHR32 units are equipped with a hot surface ignition system. Do not attempt to manually light burners on these furnaces. Each time thermostat calls for heat, the burners will be automatically lit.
Page 47
Page 48
How To Operate Gas Valve
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set thermostat to lowest setting.
3 − Turn off all electrical power to furnace.
4 − This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to light the burner by hand.
5 − Remove unit access panel.
6 − Natural valve, move lever to OFF. Propane valve,
turn knob to OFF. Do not force.
7 − Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instruc­tions. If you do not smell gas go to next step.
8 − Natural valve, move lever to ON. Propane valve, turn
knob to ON. Do not force.
9 − Replace access panel.
10− Turn on all electrical power to unit.
11− Set thermostat to desired setting.
12− If the appliance will not operate, follow the instructions
To Turn Off Gas To Unit" and call your service techni­cian or gas supplier.
Turning Off Gas To Unit
1 − Set thermostat to lowest setting.
2 − Turn off all electrical power to unit if service is to be per-
formed.
3 − Remove access panel. 4 − Natural valve, move lever to OFF. Propane valve, turn
knob to OFF. Do not force.
5 − Replace access panel.
NOTE−On initial start−ups and when condensate trap is dry, unit may turn itself off and on to allow condensate trap to fill. This is normal operation.
C−Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
D−Extended Period Shutdown
Turn off thermostat or set to UNOCCUPIED" mode. Close all gas valves (both internal and external to unit) to guaran­tee no gas leak into combustion chamber. Turn off power to unit. All access panels, covers and vent caps must be in place and secured.
Refer to Maintenance" section of this manual for instruc­tions on how to prepare condensate assembly for ex­tended period shutdown.
IV−HEATING SYSTEM SERVICE CHECKS
A−A.G.A./C.G.A. Certification
All units are A.G.A. and C.G.A. design certified without modifications. Refer to the GHR32 Operation and Installa­tion Instruction Manual Information.
B−Gas Piping
Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
When pressure testing gas lines, the gas valve must be dis­connected and isolated. Gas valves can be damaged if subjected to more than 0.5psig (14" W.C.). See figure 47. If the pressure is equal to or less than 0.5psig (14"W.C.), use the manual shut−off valve before pressure testing to isolate furnace from gas supply.
GAS PIPING TEST PROCEDURE (Typical)
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8" N.P.T.
PLUGGED TAP
CAP
FIGURE 47
FURNACE
ISOLATE
GAS VALVE
IMPORTANT
In case emergency shutdown is required, turn off the main shut-off valve and disconnect the main power to unit. These controls should be properly labeled by the installer.
When checking piping connections for gas leaks, use preferred means. Kitchen detergents can cause harmful corrosion on various metals used in gas piping. Use of a spe­cialty Gas Leak Detector is strongly recommended. It is available through Lennox under part number 31B2001.
Do not use matches, candles, flame or any other source of ignition to check for gas leaks.
Page 48
Page 49
TOP
SIDE
PIPING
1/8" NPT
PLUGGED
TAP
MANUAL MAIN
SHUT−OFF
GAS VALVE
BOTTOM
SIDE
PIPING
MANUAL
MAIN
SHUT−OFF
VALV E
1/8" NPT PLUGGE
D
TAP
LEFT SIDE
PIPING
GAS VALVE
RIGHT
SIDE
PIPING
FIGURE 48
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to inlet pressure tap (field provided). See figure 48. Check gas line pressure with unit firing at maximum rate. Low pres­sure may result in erratic operation or underfire. High pressure can result in permanent damage to gas valve or overfire. For natural gas units, operating pressure at unit gas connection must be a minimum of 4.5" W.C. (1.12kPa). For L.P. gas units, operating pressure at unit gas connection must be a minimum of 11.0" W.C. (2.74kPa). For both natural and L.P. gas units, operating pressure must not exceed 13" W.C. (3.23 kPa).
On multiple unit installations, each unit should be checked separately, with and without the other units operating. Sup­ply pressure minimum and maximum must be the same as listed in previous paragraph.
E−Check Manifold Pressure
Manifold Operating Pressure is the manifold pressure mea­sured during normal operation (sensing burner box pressure). Manifold Absolute Pressure is manifold pressure measured when the gas valve regulator is operating at factory preset lev­el (sensing atmospheric pressure).
After line pressure has been checked and adjusted, check manifold absolute pressure. Move pressure gauge to outlet pressure tap located on unit gas valve (GV1). Checks of manifold absolute pressure are made as verification of proper regulator adjustment. Manifold operating pressure for the GHR32 can be mea­sured at any time the gas valve is open and is supplying
VALV E
MANUAL MAIN
SHUT−OFF
VALV E
1/8" NPT
PLUGGED
TAP
SHUT−OFF
PLUGGE
MANUAL
MAIN
VALV E
1/8" NPT
D
TAP
Page 49
gas to the unit. Normal manifold operating pressure for natural gas units is 2.5 to 3.5" W.C. (621 to 870 Pa). See figure 29. For LP/propane gas the correct manifold operat­ing pressure is 9.0 to 10.0" W.C. (2.24 to 2.49 Pa). See fig­ure 30.
IMPORTANT
For safety, connect a shut-off valve between the manometer and the gas tap to permit shut off of gas pressure to the manometer.
TABLE 32
GAS VALVE REGULATION*
Unit (Fuel)
Natural L.P.
Absolute Pressure (outlet) in. W.C.
3.5
10.0
The gas valve is factory set and should not require adjustment. See table 32. Also, gas valve regulation varies with burner box pressure (figures 29 and 30).
*Manifold Absolute Pressure Measurement and Adjust­ment
1 − Connect test gauge to outlet tap on gas valve. 2 − Disconnect pressure sensing hose from gas valve
and plug hose by covering opening with tape or equivalent. Leave hose barb on valve open to atmo­sphere.
3 − Start unit and allow 5 minutes for unit to reach steady
state.
4 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue. L.P. gas should burn mostly blue with some orange streaks.
5 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to values given in table 32. If values are different, adjust to table 32.
IMPORTANT
For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
NOTE−During this test procedure, the unit will be overfir­ing:
D Operate unit only long enough to obtain accurate read-
ing to prevent overheating heat exchanger.
D Attempts to clock gas valve during this procedure will
be inaccurate. Measure gas flow rate only during nor­mal unit operation.
6 − When test is complete remove obstruction from hose
and return hose to gas valve barb.
F− Proper Gas Flow
Furnace should operate at least 5 minutes before check­ing gas flow. Determine time in seconds for two revolu­tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 33 below. Adjust manifold on gas valve to match time needed.
NOTE−To obtain accurate reading, shutoff all other gas appliances connected to meter.
Page 50
TABLE 33
GHR32
18M34
63K89
GAS METER CLOCKING CHART
Seconds for One Revolution
GHR32
Unit
−50 72 144 180 360
−75 48 96 120 240
−100 36 72 90 180
−120 30 60 75 150
Natural−1000 btu/cu ft LP−2500 btu/cu ft
Natural LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
G−Flame Signal
A microamp DC meter is needed to check the flame signal on the SureLight control. Use a flame signal transducer (part number 78H5401) available from Lennox to measure the flame signal, if meter used will not read microamp signal. Flame (microamp) signal is an electrical current which
passes from the ignition control through the sensor elec­trode during unit operation. Current passes from the sen­sor through the flame to ground to complete a safety circuit.
To Measure Flame Signal:
1 − Set the volt meter to the DC voltage scale. Insert trans-
ducer into the VDC and common inputs. Observe cor­rect polarities. Failure to do so results in negative (−)
values. 2 − Turn off supply voltage to control. 3 − Disconnect flame sensor lead from terminal of ignition
control. 4 − Connect (+) lead of transducer to ignition control sen-
sor connection. 5 − Connect (−) lead of the transducer to sensor wire. 6 − Turn supply voltage on and close thermostat contacts
to cycle system. 7 − When unit lights, read voltage on meter display. Re-
member 1 DC volt = 1 DC microamp.
TABLE 34
FLAME SIGNAL MICROAMPS
Boards
Normal u0.23
V−TYPICAL OPERATING CHARACTERISTICS A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat con-
trol system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower operates continuously. With fan switch in AUTO position, blower cycles with demand.
3 − In all cases, blower and entire unit will be off when the
system switch is in OFF position.
B−Temperature Rise
Temperature rise for GHR32 units depends on unit input, blow­er speed, blower horsepower and static pressure as marked on the unit rating plate. The blower speed must be set for unit operation within the range of AIR TEMP. RISE °F" listed on the unit rating plate.
To Measure Temperature Rise:
1 − Place plenum thermometers in the supply and return air
plenums. Locate supply air thermometer in the first hori­zontal run of the plenum where it will not pick up radiant heat from the heat exchanger.
2 − Set thermostat to highest setting. 3 − After plenum thermometers have reached their high-
est and steadiest readings, subtract the two readings. The difference should be in the range listed on the unit rating plate. If the temperature is too low, decrease blower speed. If temperature is too high, first check the firing rate. Provided the firing rate is acceptable, increase blower speed to reduce temperature. To change blower speed taps see the Blower Speed Taps section in this manual.
46M99 18M99 49M59
Boards
24L85 56L83 97L48
Low 0.17 to 0.22
Drop Out 0.16
Normal u0.61
Low 0.21 to 0.60
Drop Out 0.20
H− Variable Speed Motor
To check out the VSM blower and blower control board, begin with the ICM2 motor and follow the procedures outlined in section IX−TROUBLESHOOTING. The ICM2 consists of a control module and motor. The control module can be re­placed separately form the the motor if necessary. However, if the motor fails the motor/control module assembly will have to be replaced.
Page 50
Page 51
C−External Static Pressure
1 − Measure tap locations as shown in figure 49. 2 − Punch a 1/4" diameter hole in
supply and return air ple­nums. Insert manometer hose flush with inside edge of hole or insulation. Seal around the hose with perma­gum. Connect the zero end of the manometer to the dis­charge (supply) side of the system. On ducted systems, connect the other end of manometer to the return duct as above. For systems with non−ducted returns, leave the other end of the manometer open to the atmo­sphere.
3 − With only the blower motor running and the evapo-
rator coil dry, observe the manometer reading. Ad­just blower motor speed to deliver the air desired ac­cording to the job requirements.
4 − Pressure drop must not exceed 0.5" W.C.
5 − Seal around the hole when the check is complete.
GHR32 BLOWER REMOVAL
STATIC PRESSURE
TEST
MANOMETER
FIGURE 49
D−Blower Speed Taps GHR32Q Motors
Blower speed tap changes are made on the SureLight con­trol board. See figure 9. Unused taps must be secured on dummy terminals "PARK M1" and or "PARK M2" on the SureLight board. The heating tap is connected to the "ACB HEAT " terminal and the cooling tap is connected to the "ACB COOL" terminal. The continuous blower tap is con­nected to the "ACB LOW" terminal. To change existing heat tap, turn off power then switch out speed tap on "ACB HEAT" with tap connected to "PARK M1" or "PARK M2". See wiring diasgrams for blower motor tap colors for each speed.
To Remove Blower:
1. Turn off line voltage power. Unplug the following jack/plugs: J96/P96 power interface, J135/P135 secondary limit, J58/P58 control, J98/P98 CAB.
2. Remove screws (2) and remove control box cover. Disconnect thermostat wiring connections by re­moving low voltage terminal strip. Disconnect spark wire and grommet.
3. Loosen screws (2) and remove control box from unit. Holes are slotted so screws do not need to be re­moved.
4. Remove bolts (2) and remove blower from unit.
J69/P69
J98/P98
FIGURE 50
J96/P96
J135/P135
4
3
2
Page 51
Page 52
VI−MAINTENANCE
Retainers for factory supplied return air filter are shown in figure 51.
CABINET
WRAPPER
FILTER
SIDE FILTER CLIP DETAIL
Press up on side filter clip to release filter
(One on each side of cabinet)
BACK FILTER CLIP
FILTER CLIP
Press up on side filter clip to release filter
(One on each side of cabinet)
FILTER
FILTER
CLIP
FIGURE 51
A−Filters
At the beginning of each heating season, the system should be checked as follows:
1 − Filters should be inspected monthly and must be
cleaned or replaced when dirty to ensure proper fur­nace operation.
2 − Reusable foam filters used with the GHR32 can be
washed with water and mild detergent. When dry, they should be sprayed with filter handicoater prior to rein­stallation. Filter handicoater is RP Products coating no. 418 and is available as Lennox part no. P-8-5069.
3 − If replacement is necessary, order Lennox part no. 31J81
for 14 X 25 inch (356 X 635mm) filter for GHR32-50 and
-75 units and P-8-7831 for 20 X 25 inch (508 X 635mm) filter for GHR32-100 and -120 units.
B−Cleaning Heat Exchanger and Burners
NOTE−Use papers or protective covering in front of fur­nace while cleaning furnace.
Cleaning the heat exchanger is not recommended; but, if it be­comes necessary, follow the procedures outlined below and refer to figure 1 for parts arrangement. Pay close attention to wire routing and plumbing connections. If at all possible, the unit should be removed and placed on its back. Tools needed are: slotted screwdriver, extra long 1/4" nut driver, extra long 5/16" nut driver, and duck­bill pliers.
CABINET
WRAPPER
Heat Exchanger
1 − Turn off electrical and gas power supplies to furnace. 2 − Remove upper and lower furnace access panels. 3 − Remove 3/8" rubber cap from condensate drain plug
and drain. Replace cap after draining.
4 − Disconnect and remove intake pipe from air intake fit-
ting.
5 − Mark all gas valve wires and disconnect them from
valve.
6 − Remove gas supply line connected to gas valve.
Disconnect gas valve sensing hose from side of burner box. Remove burner box cover by removing six (four on some units) securing screws. Remove gas valve/ manifold assembly.
7 − Detach burner box from vestibule panel by removing four
securing screws. Take care to avoid damaging the glass fiber gasket.
8 − Mark and disconnect spark and sensor electric wires
from the ignitor and flame sensor.
9 − Disconnect wires from flame roll−out switch. Remove
wires from patch plates. Remove side plates on burner box holding sensor and spark electrode. Set burner burn­er box assembly aside.
NOTE− If burner cleaning is needed, do so at this time. Refer to burner cleaning procedure.
10− Remove flexible exhaust tee by loosening three
clamps.
11− Disconnect drain line attached to condensate trap. Re-
move screws that secure both condensate collars to ei­ther side of the unit and remove collars. It may be neces­sary to cut the pipe to allow for removal of the condensate trap. Remove drain tubes from cold end header collector box.
12− Disconnect condensate drain tubing from exhaust
pipe. Remove screws that secure both flue collars into place. Remove flue collars. It may be neces­sary to cut the exiting exhaust pipe to allow for re­moval of the fittings.
13− Disconnect 2−pin plug from combustion air blower.
Remove combustion air blower from bracket by re­moving four securing screws. Remove ground wire from bundle.
14− Remove combustion air blower bracket by removing two
screws from collector box and two screws from ves­tibule panel.
15− Disconnect combustion air pressure and condensate
sensing hoses from cold end header collector box. Re­move pressure hose from two blank stems on cold end header collector box.
16− Mark and remove wires from pressure switch. Re-
move pressure switch/bracket assembly. Keep hoses attached to pressure switch. Remove pres­sure switch installation screws from both sides of the unit.
17− Disconnect 9−pin and 3− pin plugs at blower deck. Re-
move both plugs from the heat exchanger side of the blower deck.
18− Remove the primary limit from vestibule panel.
Page 52
Page 53
19− Remove two (2) screws from the front cabinet flange at
the blower deck. Remove front screws from cabinet at blower deck on left and right sides. Cabinet sides must be slightly spread apart to clear heat exchanger pas­sage.
NOTE−To protect insulation in horizontal applications, slide a piece of sheet metal between the coil sec tion of the heat exchanger and the cabinet when removing and replacing heat exchanger. Remove indoor blower for horizontal installations. Remove sheet metal when complete.
20− Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as­sembly to cabinet.
21− With a pair of duck bills, carefully bend bottom flange
straight. Use caution not to damage the cabinet. Re­move heat exchanger.
22− Back wash heat exchanger with soapy water solu-
tion or steam. If steam is used it must be below
275_F (135_C).
23− Thoroughly rinse and drain the heat exchanger. Soap
solution can be corrosive so take care that entire as­sembly is completely rinsed.
24− Re−install heat exchanger into cabinet (blower deck end
first) making sure that the clamshells of the heat ex­changer assembly are resting on the supports at the rear of the cabinet. This can be viewed by re­moving the indoor blower and examining through the blower opening.
25− Re−secure the supporting screws along the vestibule
sides and bottom to the cabinet. Carefully bend bot­tom flange back to a 90 degree angle with a pair of duck bills. Once again, use caution not to damage the cabinet.
26− Re−install cabinet screws on sides and front flange at
blower deck.
27− Re−install primary limit to vestibule panel.
28− Re−install 9−pin plug to blower deck and connect it to the
9−pin plug from below the blower deck. Re−install 3−pin plug to blower deck and connect it to the 3−pin plug from below the blower deck.
29− Re−install pressure switch/bracket assembly and re-
place pressure switch screws on both sides of unit from installed pressure switch. Reconnect wires to pressure switch.
30− Connect combustion air pressure and condensate
sensing hoses from pressure switch to cold end header collector box. See figure 31to confirm hose location.
31− Re−install the combustion air bracket.
32− Re−install the combustion air blower to bracket. Re-
connect the 2−pin plug to the wire harness.
33− Replace flue collars with securing screws to either side of
the unit. Reconnect exhaust piping and exhaust drain tubing.
34− Replace condensate collars with securing screws to
either side of the unit. Reconnect drain line to conden­sate trap. Reconnect drain tubing from cold end head­er collector box. Reconnect condensate drain tubing from exhaust pipe.
35− Replace flexible exhaust tee to combustion air
blower and exhaust pipes and secure with three clamps.
36− Align burner box gasket to securing holes closest to
the end of the unit. Use a small piece of tape to secure gasket to vest panel. Make sure glass fiber gasket has not been damaged so it will provide a continuous seal between the burner box and the vestibule panel.
37− Move burner box assembly to vestibule area.
38− Reconnect flame roll−out switch wires. Re−install
patch plates to side of burner box. Connect wires to patch plates.
39− Reconnect sensor and spark electrode or SureLight
ignitor wires through provided openings in the burner plate.
40− Replace four screws to secure reassembled burner
box assembly to vestibule panel. Make sure burn-
ers line up in center of burner ports.
41− Re−install gas valve manifold assembly. Replace
burner box cover. Re−install gas supply line to gas valve. Attach gas valve pressure sensing hose to burner box.
42− Reconnect gas valve wires to gas valve.
43− Re−install intake vent pipe to rubber connector on in-
take fitting with hose clamp.
44− Replace both upper and lower access panels.
45− Refer to instruction on verifying gas and electrical con-
nections when re−establishing supply.
46− Following lighting instructions, light and run unit for 5
minutes to ensure heat exchanger is clean, dry and operating safely.
Page 53
Page 54
Cleaning the Burner Assembly
1 − Turn off electrical and gas power supplies to furnace.
2 − Remove upper and lower furnace access panels.
3 − Disconnect and remove intake pipe from air intake fit-
ting.
4 − Mark all gas valve wires and disconnect them from
valve.
5 − Remove gas supply line connected to gas valve.
Disconnect gas valve sensing hose from valve. Re­move burner box cover (4 to 6 screws). Remove gas valve/manifold assembly.
18− Re−install gas valve/manifold assembly. Re−install
burner box cover. Reconnect gas valve sensing hose to side of burner box. Re−install gas supply line to gas valve.
19− Reconnect gas valve wires to gas valve.
20− Replace both upper and lower access panels.
21− Refer to instruction on verifying gas and electrical con-
nections when re−establishing supply.
22− Following lighting instructions, light and run unit for 5
minutes to ensure heat exchanger is clean, dry and operating safely.
6 − Loosen hose clamp holding the air intake pipe to the
no−hub connector on the top of the burner box. Re­move pipe from no−hub connector and set aside.
7 − Mark and disconnect spark or SureLight ignitor and
sensor electrical wires from the ignitor and flame sen­sor.
8 − Detach burner box from vestibule panel by remov-
ing four securing screws. Take care to avoid dam­aging the glass fiber gasket.
9 − On GHR32−50 and −75 units, remove air intake fitting from
burner box top.
10 − Remove burner box top from burner box assembly.
11− Using 1/4" nut driver, remove two screws holding
burners in place. Slide burner assembly out of burn­er box.
12− Clean burner by running a vacuum with a soft brush at-
tachment over face of burners. Visually inspect inside of burners and crossovers for any blockage caused by foreign matter. Remove any blockage.
13− Re−install burner assembly so that protruding side (not
cavity side) of metal buttons are toward the burner box top (intake side).
14− Replace top and air intake piece to burner box.
C−Supply Air Blower
1 − Check and clean blower wheel.
2 − Motors are prelubricated for extended life; no further lu-
brication is required.
D−Electrical
1 − Check all wiring for loose connections.
2 − Check circuit breaker located in unit control box.
3 − Check for correct voltage at unit (unit operating).
4 − Check amp-draw on blower motor.
Motor Nameplate_________Actual_________
5 − Check to see that heat (if applicable) is operating.
E−Intake and Exhaust Lines
Check intake and exhaust lines and all connections for tightness and make sure there is no blockage. Also check condensate line for free flow during operation.
F−Insulation
Outdoor piping insulation should be inspected yearly for deteri­oration. If necessary, replace with same materials.
15− Reconnect sensor and spark electrode or SureLight
ignitor wires.
16− Align burner box gasket to securing holes closest to
the end of the unit. Use a small piece of tape to secure gasket to vest panel. Make sure glass fiber gasket has not been damaged so it will provide a continuous seal between the burner box and the vestibule panel.
17− Replace four screws to secure reassembled burner
box assembly to vestibule panel. Make sure burn-
ers line up in center of burner ports.
G−Winterizing and Condensate Trap Care
If the unit is to be shut down for an extended period of time and will be exposed to sub-freezing temperatures, the unit should be winterized by draining water from the conden­sate trap.
To drain condensate trap remove the 3/8" cap located on the bottom corner of the condensate trap (see figure 46). Periodically drain condensate trap to insure proper drain­age and check for blockage.
Page 54
Page 55
VII−WIRING DIAGRAM AND SEQUENCE OF OPERATION
GHR32Q −1 UNIT DIAGRAM
Page 55
Page 56
GHR32Q −3 UNIT DIAGRAM
Page 56
Page 57
Sequence of Operation GHR32Q −1, −3 Units
Ignitor operation will vary between SureLight boards. Board 56L83 will energize ignitor for the first second of the 4 second ignition trial. Board 97L48 will energize ignitor during the entire ignition trial until flame is sensed.
1 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the furnace control with 24VAC.
2 − SureLight control runs self−check for S10 primary limit
switch normally closed contacts and S18 combustion air prove switch normally open contacts. Follow steps 4 through 8 per respective thermostat.
Single−stage Mode, Single−stage Thermostat
3 − SureLight control energizes combustion air inducer
B6 on high speed. Combustion air inducer runs until S18 prove switch closes (switch will close within 2−1/2 minutes or control goes into Watchguard−Prove Switch mode). A 15−second pre−purge follows after S18 closes.
4 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve is energized on first stage heat (low). Gas
valve opens for a 4−second trial for ignition.
6 − Flame is sensed, After 8 seconds from when gas valve
opens, valve energizes on second stage (high heat).
7 After 45−second delay, indoor blower B3 is energized
on heating speed.
Two−stage Mode, Single−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until combustion air proving switch S18 closes (switch will close within 2−1/2 minutes or control goes into Watch­guard−Prove Switch mode). A 15−second pre−purge follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 Gas valve is energized on first stage. Gas valve opens
for a 4−second trial for ignition. Signal is sent from con­trol module to two−stage control board to begin W2 (second−stage) ON delay.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Second stage time on delay complete (8, 12, or 15
minutes). Combustion air inducer B6 switches to high speed, indoor blower B3 switches to heating speed and gas valve opens on high heat (second stage.)
Two−stage Mode, Two−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until combustion air inducer switch S18 closes. Switch will close within 2−1/2 minutes or control goes into Watch­guard−Proving Switch mode). A 15−second pre−purge follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 Gas valve is energized on first stage only. Gas valve
opens for a 4−second trial for ignition.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Call for second stage heat comes from indoor thermo-
stat (W2).
Page 57
Page 58
GHR32Q −5 & −6 UNIT DIAGRAM
Page 58
Page 59
Sequence of Operation. GHR32Q with SureLight Two Stage Control
Sequence depends on type thermostat used. Units are applicable for single stage or two stage thermostats. Both type thermostats are described below. Thermo­stat jumper E20 dictates which mode unit will operate in. See flow chart for more sequence detail.
SureLight Control Self Check
When there is a call for heat, the SureLight integrated con­trol runs a self check. The control checks for S10 primary limit, S21 secondary limit (s) and S47 rollout switch nor­mally closed contacts. The control also checks for S102 prove switch normally open contacts. Once self check is complete and all safety switches are operational, heat call can continue.
Two−Stage Thermostat, Two Stage Heat. Jumper E20
set at TWO".
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until S102 closes (switch must close within 2 1/2 minutes or control goes into Watchguard Pressure Switch mode. A 15 second pre−purge follows once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until first stage de­mand is satisfied OR a second stage heat demand is initiated.
6− Second stage heat demand initiated. A 30 second sec-
ond stage recognition period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Single−Stage Thermostat, Two Stage Heat. Jumper
E20 set at SINGLE"
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until S102 prove switch contacts close (switch must close within 2 1/2 minutes or control goes into Watchguard Pressure Switch mode. A 15 second pre−purge follows once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
6− A 10 minute (factory set) or 15 minute (field set) second
stage heat delay period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Page 59
Page 60
GHR32V −1 UNIT DIAGRAM
Page 60
Page 61
GHR32V −3 UNIT DIAGRAM
Page 61
Page 62
GHR32V −4 UNIT DIAGRAM
Page 62
Page 63
Sequence of Operation GHR32V −1 / −4 Units
Ignitor operation will vary between SureLight boards. Board 56L83 will energize ignitor for the first second of the 4 second ignition trial. Board 97L48 will energize ignitor during the entire ignition trial until flame is sensed.
1 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the furnace control with 24VAC.
2 − SureLight control runs self−check for S10 primary limit
switch normally closed contacts and S18 combustion air prove switch normally open contacts. Follow steps 4 through 8 per respective thermostat.
Single−stage Mode, Single−stage Thermostat
3 − SureLight control energizes combustion air inducer
B6 on high speed. Combustion air inducer runs until S18 prove switch closes (switch will close within 2−1/2 minutes or control goes into Watchguard−Prove Switch mode). A 15−second pre−purge follows after S18 closes.
4 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve is energized on first stage heat (low). Gas
valve opens for a 4−second trial for ignition.
6 − Flame is sensed, After 8 seconds from when gas valve
opens, valve energizes on second stage (high heat).
7 After 45−second delay, indoor blower B3 is energized
on heating speed.
Two−stage Mode, Single−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until combustion air proving switch S18 closes (switch will close within 2−1/2 minutes or control goes into Watch­guard−Prove Switch mode). A 15−second pre−purge follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 Gas valve is energized on first stage. Gas valve opens
for a 4−second trial for ignition. Signal is sent from con­trol module to two−stage control board to begin W2 (second−stage) ON delay.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Second stage time on delay complete (8, 12, or 15
minutes). Combustion air inducer B6 switches to high speed, indoor blower B3 switches to heating speed and gas valve opens on high heat (second stage.)
Two−stage Mode, Two−stage Thermostat
1 − SureLight control energizes combustion air inducer
B6 on low speed. Combustion air inducer runs until combustion air inducer switch S18 closes. Switch will close within 2−1/2 minutes or control goes into Watch­guard−Proving Switch mode). A 15−second pre−purge follows once S18 closes.
2 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
3 Gas valve is energized on first stage only. Gas valve
opens for a 4−second trial for ignition.
4 − Flame is sensed, gas valve remains open for the heat
call.
5 After 45−second delay, indoor blower B3 is energized
on low speed.
6 − Call for second stage heat comes from indoor thermo-
stat (W2).
Page 63
Page 64
GHR32V −5 & −6 UNIT DIAGRAM
Page 64
Page 65
Sequence of Operation GHR32V with SureLight Two Stage Variable Speed Control
Sequence depends on type thermostat used. Units are applicable for single stage or two stage thermostats. Both type thermostats are described below. Thermo­stat jumper E20 dictates which mode unit will operate in. See flow chart for more sequence detail.
SureLight Control Self Check
When there is a call for heat, the SureLight integrated con­trol runs a self check. The control checks for S10 primary limit, S21 secondary limit (s) and S47 rollout switch nor­mally closed contacts. The control also checks for S102 prove switch normally open contacts. Once self check is complete and all safety switches are operational, heat call can continue.
Two−Stage Thermostat, Two Stage Heat. Jumper E20
set at TWO".
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until S102 prove switch contacts close (switch must close within 2 1/2 minutes or control goes into Watchguard Pressure Switch mode. A 15 second pre−purge follows once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until first stage de­mand is satified OR a second stage heat demand is initiated.
6− Second stage heat demand initiated. A 30 second sec-
ond stage recognition period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Single−Stage Thermostat, Two Stage Heat. Jumper
E20 set at SINGLE"
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until S102 prove switch contacts close (switch must close within 2 1/2 minutes or control goes into Watchguard Pressure Switch mode. A 15 second pre−purge follows once S102 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
6− A 10 minute (factory set) or 15 minute (field set) second
stage heat delay period begins.
7− The combustion air inducer ramps up to high heat
speed.
8− B3 indoor blower ramps up to high heat speed.
Page 65
Page 66
VIII−Sequence of Operation Flow Charts GHR32Q −1 & −3 GHR32V−1 / −4
HEATING SEQUENCE OF OPERATION
NOTE: LED REFERS TO SURELIGHT CONTROL . LED−DS REFERS TO VSP CONTROL.
NORMAL HEATING MODE ABNORMAL HEATING MODE
POWER ON
CONTROL SELF−CHECK OKAY?
COMBUSTION AIR BLOWER ON FOR 1 SECOND.
POLARITY OKAY?
LED#1 AND #2
ALTERNATING FAST
FLASH. SIGNAL
HOLDS UNTIL UNIT IS
PROPERLY GROUND.
NO YES
YES
IS THERE A
PROPER GROUND?
IS VOLTAGE
ABOVE 75 VOLTS?
YES
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON. LED #1 AND #2 ALTERNATING FAST FLASH. CHECK FOR BROKEN IGNITOR OR OPEN IGNITOR CIRCUIT.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
(RESET CONTROL BY TURNING MAIN POWER OFF.)
INDOOR BLOWER DELAY OFF.
LED #1 AND #2 ALTERNATING FAST FLASH.
NO
SIGNAL HOLDS UNTIL VOLTAGE RISES
LED #1 ON LED #2 ON
POLARITY REVERSED.
LED #1 −− FAST FLASH
LED #2 −− SLOW FLASH
ABOVE 75 VOLTS.
LED #1 −− SIMULTANEOUS SLOW FLASH LED #2 −− SIMULTANEOUS SLOW FLASH
PRESSURE SWITCH CONTACTS OPEN?
ENERGIZE COMBUSTION AIR BLOWER.
IS LINE VOLTAGE ABOVE 75 VOLTS?
TWO−STAGE MODE
CALL FOR 1ST STAGE HEAT
ROLLOUT SWITCH CLOSED?
YES
(CONTINUOUS FLAME CHECK)
THERMOSTAT CALLS FOR HEAT:
PRIMARY LIMIT SWITCH CLOSED?
IS UNIT PROPERLY GROUNDED?
BURNER OFF?
YES
NORMAL OPERATION:
LED #1 −− FAST FLASH LED #2 −− FAST FLASH
YES
YES
(HIGH AND LOW HEAT)
YES
ENERGIZE HTG ACC. TERM.
YES
YES
W2 TIMED MODE
SINGLE STAGE T’STAT
NO
NO
NO
NO
NO
SINGLE−STAGE MODE
HIGH HEAT ONLY
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF DELAY.
LED #1 −− ON
LED #2 −− SLOW FLASH
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
LED #1 −− SLOW FLASH
LED #2 −− OFF
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON.
LED #1 −− SLOW FLASH
LED #2 −− ON
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF DELAY.
LED #1 OFF
LED #2 SLOW FLASH
(Sequence holds until pressure switch
closes or thermostat resets control.)
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. LED #1 −− ALTERNATING FAST FLASHES LED #2 −− ALTERNATING FAST FLASHES
COMBUSTION AIR BLOWER
ON LOW SPEED (t 2.5 MINUTES)
LOW−HEAT PRESSURE
SWITCH CLOSED?
YES YES
NO
PREPURGE
15 SECONDS
CONTINUED ON NEXT PAGE
COMBUSTION AIR BLOWER
ON HIGH SPEED (t 2.5 MINUTES)
HIGH−HEAT PRESSURE
SWITCH CLOSED?
NO
Page 66
PRESSURE SWITCH WATCHGUARD
(5 MINUTES)
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
LED #1 OFF
LED #2 SLOW FLASH
WATCHGUARD 60-MINUTE DELAY
(SIGNAL LIMIT OR IGNITION FAILURE)
GAS VALVE OFF. COMBUSTION AIR
AND INDOOR BLOWER OFF.
LED #1 AND LED #2
ALTERNATING SLOW FLASHES
Page 67
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODE ABNORMAL HEATING MODE
PREPURGE
15 SECONDS
IGNITION SEQUENCE BEGINS
(Ignition trial counter initiated.)
IGNITOR WARM−UP
(20 SECONDS)
WATCHGUARD 60-MINUTE DELAY
(SIGNAL LIMIT OR IGNITION FAILURE)
GAS VALVE OFF. COMBUSTION AIR
AND INDOOR BLOWER OFF.
LED #1 AND LED #2
ALTERNATING SLOW FLASHES
WATCHGUARD −− FLAME FAILURE.
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
LED #1 & LED #2 ALTERNATE FLASH.
TWO−STAGE MODE
CALL FOR 1st STAGE HEAT
MAIN GAS VALVE OPEN
LOW HEAT ONLY
W2 TIMED MODE
SINGLE STAGE T’STAT
MAIN GAS VALVE OPEN
LOW HEAT ONLY
SECOND STAGE
TIME ON BEGINS
4 SECONDS
SINGLE−STAGE MODE
HIGH HEAT ONLY
GAS VALVE OPEN ON LOW HEAT.
WITHIN 8 SEC. VALVE OPENS HIGH HEAT.
8 SECONDS
FLAME RECTIFICATION CURRENT CHECK
(u0.20 microamps)
FLAME PRESENT?
NO
(Response time −− 2 seconds maximum.)
45 SECOND INDOOR BLOWER DELAY BEGINS. AFTER DELAY ACC. TERMINAL IS
ENERGIZE. Q" MODELS: ACB HEAT SPEEDIS ENERGIZED. V" MODELS: HEAT"
LED−DS2 LIT. BLOWER ON HEAT SPEED.
TWO−STAGE MODE
CALL FOR 1st STAGE HEAT
W2 TIMED MODE
SINGLE STAGE T’STAT
Q" MODELS: INDOOR BLOWER ON LOW
SPEED. V" MODELS: CFM" LED−DS4
BLINKS ONCE FOR EVERY 100CFM.
Q" MODELS: INDOOR BLOWER ON
SINGLE−STAGE MODE
HIGH HEAT ONLY
HIGH HEATING SPEED. V"
MODELS: CFM" LED−DS4 BLINKS
ONCE FOR EVERY 100CFM.
FLAME PRESENT?
(Continuous flame check)
FLAME SIGNAL
NO
(u0.61 microamps)
COMBUSTION AIR INDUCER DE−ENERGIZED.
NO
PRIMARY LIMIT SWITCH CLOSED?
NO
CONTROL CHECKS RETRY
FOR IGNITION COUNT. HAVE FOUR RE-TRIES
BEEN COMPLETED?
GAS VALVE
DE−ENERGIZED
YES
LIMIT SWITCH WATCHGUARD MODE. GAS VALVE OFF. COMB. AIR INDUCER OFF. INDOOR BLOWER OFF AFTER DELAY. LED#1−SLOW FLASH LED#2−ON. IS 60 MINUTE
NO
RESET PERIOD COMPLETE?
LOW FLAME SIGNAL
LED #1 −− SLOW FLASH
LED #2 −− FAST FLASH
GAS VALVE DE−ENERGIZED.
INDOOR BLOWER ON.
LED #1 − SLOW FLASH; LED #2 − ON.
YES
ROLLOUT SWITCH CLOSED?
PRESSURE SWITCH CLOSED?
(CONTINUED ON NEXT PAGE)
CONTINUED ON NEXT PAGE
NO
Page 67
HAS PRIMARY/SECODARY LIMIT
CLOSED (RESET) WITHIN 3 MINUTES?
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER DE−ENERGIZED.
INDOOR BLOWER OFF DELAY (Selected time)
LED #1 −− ON
LED #2 −− SLOW FLASH
NO
YES
Page 68
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODE ABNORMAL HEATING MODE
PREPURGE
PRESSURE SWITCH CLOSED?
NO
(See top of previous page.)
YES YES
TWO−STAGE MODE
CALL FOR 1st STAGE HEAT
CALL FOR 2nd STAGE
HEAT (HIGH HEAT)
FROM THERMOSTAT
W2 TIMED MODE
SINGLE STAGE T’STAT
2nd STAGE ON DELAY ON CONTROL BOARD
COMPLETE
(8, 12 OR 15 MIN.)
Q" MODELS: INDOOR BLOWER SWITCHES TO HEATING SPEED. V" MODELS: CFM" LED−DS4 BLINKS ONCE FOR
EVERY 100 CFM.
COMBUSTION AIR INDUCER SWITCHES TO
HIGH SPEED?
HIGH HEAT PRESSURE SWITCH CLOSED?
YES
HIGH HEAT GAS VALVE OPEN? (8 SEC. DELAY)
YES
TWO−STAGE MODE
CALL FOR 1st STAGE HEAT
W2 TIMED MODE
SINGLE STAGE T’STAT
CONTROL CHECKS: FLAME PRESENCE, CLOSED PRIMARY
LIMIT, CLOSED PRESSURE SWITCHES, CONTINUOUSLY
CLOSED ROLLOUT SWITCH (during heating cycle).
SEE PREVIOUS SEQUENCES FOR FAILURE MODES.
DEMAND FOR HEAT SATISFIED.
THERMOSTAT OPENS.
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER POST−PURGE 5
SECONDS. HTG ACC. TERM. DE−ENERGIZED
COMBUSTION AIR INDUCER ON FOR 2.5 MINUTES.
¦ 2.5
MINUTES
NO
SINGLE−STAGE MODE
HIGH HEAT ONLY
SLOW FLASH
SLOW FLASH
SLOW FLASH
FAST FLASH
FAST FLASH
SLOW FLASH
ALTERNATING SLOW FLASH
ALTERNATING FAST FLASH
GAS VALVE DE−ENERGIZED.
INDOOR BLOWER DE−ENERGIZED.
PRESSURE SWITCH
CLOSED?
PRESSURE SWITCH WATCHGUARD
COMBUSTION AIR INDUCER
DE−ENERGIZED.
5−MINUTE DELAY
COMBUSTION AIR
BLOWER ON.
DIAGNOSTIC CODES
LED #1 LED #2 DESCRIPTION
Primary or secondary limit open
ON
ON
OFF
ON
SLOW FLASH
OFF
SLOW FLASH
SLOW FLASH
FAST FLASH
SLOW FLASH
FAST FLASH
ON
Rollout switch open
Flame sensed without gas valve energized
Pressure switch open
Power on
Heating demand
Polarity reversed
Low flame signal
Circuit board failure
Watchguard −− burners failed to ignite
Watchguard −− low voltage, below 75V or improper main ground.
INDOOR BLOWER AND ACC TERMINAL OFF AFTER SELECTED
TIME OFF DELAY.
Page 68
Page 69
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE ABNORMAL COOLING MODE
POWER ON
IGNITION CONTROL MAIN POWER ON.
SIGNAL IMPROPER
GROUND AT LED.
SIGNAL HOLDS
UNTIL UNIT IS
PROPERLY
GROUNDED.
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
CHECK FOR MAIN BURNER FLAME SENSE.
LED: SLOW FLASH RATE REMAINS UNCHANGED
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
TURN INDUCER ON FOR 1 SECOND.
IS POLARITY REVERSED?
NO
NO
IS ROLLOUT SWITCH CLOSED?
IS MAIN BURNER FLAME OFF?
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
IS THERE
PROPER GROUND?
YES
YES
NO
YES
IS VOLTAGE
ABOVE 75 VOLTS?
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
SIGNAL POLARITY REVERSED AT LED.
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SEQUENCE HOLDS UNTIL FLAME IS NOT SENSED.
LOW VOLTAGE SIGNAL AT LED HOLDS
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
COMPRESSOR CONTACTOR AND INDOOR
BLOWER ENERGIZED WITH 0-SECOND DELAY
Q" MODELS: ACB COOL AND ACC TERMINAL ENERGIZED. V" MODELS: HI/LO" LED−DS1 IS
LIT. CFM" LED−DS4 BLINKS ONCE FOR EVERY
INDOOR BLOWER AND ACC TERMINAL OFF
WITH 0−SECOND DELAY.
100CFM.
THERMOSTAT OPENS.
COMPRESSOR OFF.
Page 69
Page 70
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT. CONTROL
(G)ENERGIZING ACC TERMINAL. Q" MODELS: ACB LOW
SPEED ENERGIZED. V" MODELS: ON/OFF" LED−DS3 LIT.
INDOOR BLOWER ENERGIZED ON LOW SPEED.
THERMOSTAT CALLS FOR HEAT (W).
NO YES
THERMOSTAT CALLS FOR COOLING.
YES
Q" MODELS: INDOOR BLOWER SWITCHED TO ACB
COOL SPEED. V" MODELS: HI/LO LED−DS1 LIT.
THERMOSTAT OPENS.
Q" MODELS − INDOOR BLOWER SWITCHES TO ACB
LOW SPEED. V" MODELS − ON/OFF" LED−DS3 LIT.
INDOOR BLOWER ON LOW SPEED.
HTG ACC TERMINAL ENERGIZES
WITH COMB. AIR INDUCER.
45 SECOND INDOOR BLOWER DELAY BEGINS. AFTER DELAY − Q"
MODELS: ACB HEAT SPEED ENERGIZED. V" MODELS: HEAT"
LED−DS2 LIT. BLOWER ON HEAT SPEED.
THERMOSTAT OPENS.
INDOOR BLOWER TIME OFF DELAY BEGINS. HTG ACC TERMINAL
DE−ENERGIZED WITH COMBUSTION AIR INDUCER. ACC TERMINAL
REMAINS ENERGIZED. AFTER DELAY − "Q" MODELS: ACB HEAT
SPEED DE−ENERGIZED. V" MODELS: INDOOR BLOWER HEAT
SPEED DE−ENERGIZED.
(blower remains energized during continuous fan mode)
Page 70
Page 71
GHR32Q with Two Stage Control and GHR32V with Two Stage Variable Speed Control
HEATING SEQUENCE OF OPERATION
NORMAL AND ABNORMAL HEATING MODE
POWER ON
CONTROL SELF−CHECK OKAY?
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CHECK FOR BROKEN IGNITOR OR OPEN IGNITER CIRCUIT. DS 1 AND DS 2 ALTERNATING FAST FLASH.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF. (RESET CONTROL BY
TURNING MAIN POWER OFF.) DS1 ON, DS2 ON
NO
POLARITY OKAY?
YES
IS THERE A
PROPER GROUND?
YES
IS VOLTAGE
ABOVE 75 VOLTS?
YES
BURNER OFF?
(CONTINUOUS FLAME CHECK)
YES
A
NORMAL OPERATION:
DS 1 −− SIMULTANEOUS SLOW FLASH DS 2 −− SIMULTANEOUS SLOW FLASH
B
THERMOSTAT CALLS FOR HEAT:
DS 1 −− SIMULTANEOUS FAST FLASH DS 2 −− SIMULTANEOUS FAST FLASH
YES
PRIMARY LIMIT
SWITCH CLOSED?
YES
ROLLOUT SWITCH CLOSED?
YES
PRESSURE SWITCH CONTACTS OPEN?
NO
NO
NO
NO
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
DS1 AND DS2 ALTERNATING FAST FLASH.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
NO
NO
NO
DS1 AND DS2 ALTERNATING FAST FLASH.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
INDOOR BLOWER ON. HAS PRIMARY LIMIT
60−MINUTE LIMIT WATCHGUARD MODE.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF, INDOOR BLOWER OFF WITH DELAY.
DS1 AND DS2 ALTERNATING SLOW FLASH,
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
HAS MANUAL ROLLOUT SWITCH(ES) BEEN
RESET (CLOSED) WITHIN 3 MINUTES?
POLARITY REVERSED.
DS 1 −− FAST FLASH
DS 2 −− SLOW FLASH
DS1 SLOW FLASH, DS2 OFF,
ON/OFF LED OFF
COMBUSTION AIR INDUCER OFF.
RESET WITHIN 3 MINUTES?
DS1 SLOW FLASH, DS2 ON,
ON/OFF LED ON, HEAT LED ON.
NO
ON/OFF LED OFF, HEAT LED ON.
DS1 SLOW FLASH, DS2 ON,
ON/OFF LED ON, HEAT LED ON.
YES
NO
YES
YES
TWO−STAGE OR SINGLE−STAGE THERMOSTAT
CALL FOR HEAT
COMBUSTION AIR INDUCER ON LOW SPEED.
DS1 AND DS2 SIMULTANEOUS FAST FLASH
CONTINUED ON NEXT PAGE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CONTROL REMAINS UNTIL
PRESSURE SWITCH IS DETECTED OPEN.
DS1 OFF, DS2 SLOW FLASH,
ON/OFF LED OFF, HEAT LED OFF.
Page 71
Page 72
HEATING SEQUENCE OF OPERATION
CONTINUED
PRESSURE SWITCH CLOSED WITHIN
2.5 MINUTES?
YES
15−SECOND COMBUSTION AIR INDUCER
PRE−PURGE INITIATED BY CLOSED PRESSURE
SWITCH (or 15 SECOND INTER−PURGE PERIOD.)
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
IGNITOR WARM−UP (20 SECONDS)
DS1 AND DS2 SIMULTANEOUS FAST FLASH
IS VOLTAGE ABOVE 75 VOLTS?
YES
IS THERE A PROPER GROUND?
IS IGNITOR INTACT AND CONNECTED?
YES
NO
NO
NO
NO
THERMOSTAT CALLS FOR HEAT
DS1 AND DS2 SIMULTANEOUS FAST FLASH
(Refer to box A on previous page)
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF. INDOOR BLOWER OFF. UNIT WILL RETRY
AFTER 5−MINUTE WAIT PERIOD.
DS1 OFF, DS2 SLOW FLASH,
ON/OFF LED OFF, HEAT LED OFF.
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
DS1 AND DS2 ALTERNATING FAST FLASH.
COMBUSTION AIR INDUCER OFF, IGNITER OFF.
SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.
DS1 AND DS2 ALTERNATING FAST FLASH.
COMBUSTION AIR INDUCER OFF, IGNITOR OFF.
SIGNAL HOLDS UNTIL IGNITOR IS REPLACED
OR RECONNECTED.
DS1 AND DS2 ALTERNATING FAST FLASH.
AT END OF IGNITOR 20 SECOND WARM UP
PERIOD, 4−SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS, IGNITOR ENERGIZED DURING
4−SECOND TRIAL UNTIL FLAME SENSED.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
YES
4−SECOND FLAME STABILIZATION PERIOD.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(u0.16 microamps)
FLAME PRESENT?
YES
CONTINUED ON NEXT PAGE
NO
GAS VALVE OFF. COMBUSTION AIR
INDUCER ON. INDOOR BLOWER OFF.
NO
DS1 SLOW FLASH, DS2 FAST FLASH,
ON/OFF LED OFF, HEAT LED 0N.
HAS CONTROL FAILED TO SENSE
FLAME FOR FIVE CONSECUTIVE TRIES
DURING A SINGLE HEAT DEMAND?
YES
WATCHGUARD MODE. GAS VALVE OFF,
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF.
DS1 AND DS2 ALTERNATING SLOW FLASH.
ON/OFF LED 0FF, HEAT LED OFF.
IS 60−MINUTE RESET PERIOD COMPLETE?
YES
HAS CONTROL RESET IGNITION SEQUENCE
FOUR (4) TIMES?
DS1 SLOW FLASH, DS2 FAST FLASH,
ON/OFF LED OFF, HEAT LED ON .
NO
YES
NO
Page 72
Page 73
CONTINUED
FLAME SIGNAL ABOVE
0.23 microamps)
(u
YES
HEATING SEQUENCE OF OPERATION
THERMOSTAT CALLS FOR HEAT.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
YES
NO
DS1 SLOW FLASH, DS2 FAST FLASH.
LOW FLAME SIGNAL
(Does not affect control operation)
SEE BOX A.
SINGLE−STAGE THERMOSTAT MODE
(E20 SET AT SINGLE")
YES
START SECOND−STAGE RECOGNITION
ON DELAY (10 OR 15 MINUTES).
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
PRESSURE SWITCH CLOSED?
YES
NO
FIRST−STAGE HEAT DEMAND SATISFIED?
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF FOLLOWING POST PURGE.
INDOOR BLOWER OFF WITH DELAY
DS1 AND DS2 SIMULTANEOUS SLOW FLASH
SECOND−STAGE HEAT DEMAND.
SECOND−STAGE HEAT DEMAND REQUIRED?
DS1 AND DS2 SIMUTANEOUS SLOW FLASH.
SECOND−STAGE 30−SECOND DELAY ON BEGINS.
DS1 AND DS2 SIMULTANEOUS FAST FLASH
SECOND−STAGE COMBUSTION AIR INDUCER
ON. SECOND−STAGE GAS VALVE ON. HIGH
HEAT INDOOR BLOWER SPEED ON.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
PRESSURE SWITCH CLOSED
IN LESS THAN TEN (10) SECONDS?
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
C
YES
YES
YES
ON/OFF LED ON.
YES
YES
CONTINUED ON NEXT PAGE
TWO STAGE THERMOSTAT MODE
(E20 SET AT TWO")
YES
45−SECOND INDOOR BLOWER ON DELAY BEGINS.
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
YES
NO
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF, INDOOR BLOWER ON. DS1 SLOW FLASH, DS2 ON,
SWITCH CLOSED WITHIN 3 MINUTES?
(Indoor blower on low speed during 3−minute period)
GAS VALVE OFF, COMBUSTION AIR INDUCER OFF,
DS1 AND DS2 ALTERNATING SLOW FLASH,
IS 60−MINUTE RESET PERIOD COMPLETE?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF AFTER DELAY.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
NO
INDOOR BLOWER OFF AFTER DELAY.
YES
PRIMARY LIMIT AND
ROLLOUT SWITCH CLOSED?
NO
ON/OFF LED ON, HEAT LED ON.
HAS PRIMARY LIMIT OR ROLLOUT
NO
LIMIT SWITCH WATCHGUARD MODE.
INDOOR BLOWER OFF WITH DELAY.
ON/OFF LED OFF, HEAT LED OFF.
DS1 OFF, DS 2 SLOW FLASH,
ON/OFF LED OFF, HEAT LED ON.
DS1 OFF, DS 2 SLOW FLASH,
ON/OFF LED OFF, HEAT LED ON.
YES
YES
Page 73
Page 74
CONTINUED
HEATING SEQUENCE OF OPERATION
SEE BOX A
NORMAL OPERATION
DS1 AND DS2 SIMULTANEOUS SLOW FLASH.
ARE PRIMARY LIMIT AND ROLLOUT
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
SINGLE−STAGE THERMOSTAT MODE
SWITCH CLOSED?
YES
PRESSURE SWITCH CLOSED?
YES
HEAT DEMAND SATISFIED?
YES
(E20 SET AT SINGLE")
YES
THERMOSTAT CALLS FOR HEAT
DS 1 AND DS 2 SIMULTANEOUS FAST
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
NO
HAS PRIMARY LIMIT OR ROLLOUT SWITCH
LIMIT SWITCH WATCHGUARD MODE. GAS VALVE
OFF. COMBUSTION AIR INDUCER OFF. INDOOR
BLOWER OFF WITH DELAY. IS 60−MINUTE RESET
PERIOD COMPLETE? DS SLOW FLASH, DS2 ON,
GAS VALVE OFF, COMBUSTION AIR INDUCER
OFF AFTER 15 SECOND POST PURGE, INDOOR
NO
TWO STAGE THERMOSTAT MODE?
(E20 SET AT TWO")
INDOOR BLOWER ON.
DS1 SLOW FLASH, DS2 ON,
ON/OFF LED ON, HEAT LED 0N.
CLOSED WITHIN 3 MINUTES?
ON/OFF LED OFF, HEAT LED OFF.
BLOWER OFF AFTER DELAY.
DS1 OFF, DS2 FAST FLASH,
ON/OFF LED ON, HEAT LED ON.
RETURN TO HEAT DEMAND?
SEE BOX B
FLASH.
YES
NO
YES
YES
YES
HEAT DEMAND SATISFIED?
DS1 AND DS2
SIMULTANEOUS FAST FLASH.
YES
GAS VALVE OFF, COMBUSTION AIR
INDUCER OFF AFTER 5−SECOND
LOW SPEED POST PURGE PERIOD,
INDOOR BLOWER OFF DELAY
INITIATED ON LOW HEAT SPEED.
DS1 AND DS2
SIMULTANEOUS FAST FLASH
DEMAND FOR HEAT SATISFIED.
POWER ON STAND BY.
DS1 AND DS2
SIMULTANEOUS SLOW FLASH
YES
FIRST AND SECOND STAGE HEAT
DEMAND SATISFIED SIMULTANEOUSLY.
DS1 & DS2 SIMULTANEOUS FAST FLASH.
YES
GAS VALVE, COMBUSTION AIR INDUCER
AND INDOOR BLOWER RETURN TO FIRST−
DS1 AND DS2 SIMULTANEOUS FAST FLASH.
FIRST STAGE HEAT DEMAND SATISFIED?
GAS VALVE OFF. COMBUSTION AIR INDUCER
OFF AFTER 5−SECOND LOW SPEED POST−
PURGE PERIOD. INDOOR BLOWER OFF. DELAY INITIATED ON LOW HEAT SPEED. DS1 & DS2 SIMULTANEOUS FAST FLASH.
SECOND STAGE HEAT
NO
DEMAND SASTISFIED?
DS1 AND DS2
SIMULTANEOUS FAST FLASH.
YES
STAGE OPERATION.
YES
Page 74
Page 75
COOLING SEQUENCE OF OPERATION
POWER ON
SIGNAL IMPROPER
GROUND AT DS.
SIGNAL HOLDS
UNTIL UNIT IS
PROPERLY
GROUNDED.
(V MODELS ONLY)
THERMOSTAT CALLS FOR FIRST−STAGE COOL.
INDOOR BLOWER ENERGIZED ON FIRST STAGE
FIRST−STAGE DEMAND FOR COOL SATISFIED?
THERMOSTAT CALLS FOR SECOND−STAGE COOL.
IS POLARITY REVERSED?
NO
NO
COMPRESSOR AND CONDENSER FAN
COOL SPEED AFTER 2 SECOND DELAY.
IS THERE
PROPER GROUND?
ENERGIZED.
NO
YES
YES
IS VOLTAGE
ABOVE 75 VOLTS?
YES
YES
SIGNAL POLARITY REVERSED.
DS1 FAST FLASH, DS2 SLOW FLASH.
NO
COMPRESSOR AND CONDENSER FAN DE−ENERGIZED.
LOW VOLTAGE SIGNAL AT DS HOLDS
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
INDOOR BLOWER DE−ENEGIZED.
INDOOR BLOWER RAMPS UP TO SECOND−STAGE COOL SPEED.
SECOND−STAGE DEMAND FOR COOL SATISFIED?
YES
UNIT RETURNS TO FIRST STAGE COOL
Page 75
Page 76
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
GHR32V−5 UNITS
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED.
YES YES
YES
INDOOR BLOWER RAMPS TO FIRST STAGE
COOLING SPEED AFTER A 2−SECOND DELAY.
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST STAGE COOL.
YES
AFTER 45−SECOND DELAY, INDOOR BLOWER
SWITCHES TO LOW HEAT SPEED.
YES
FIRST−STAGE COOL DEMAND SATISFIED?
NO
SECOND STAGE COOL DEMAND
INDOOR BLOWER RAMPS TO SECOND
STAGE COOL SPEED
SECOND STAGE COOL DEMAND SATISFIED?
YES
INDOOR BLOWER RAMPS DOWN TO FIRST STAGE
COOL SPEED.
NOTE − Continuous low speed fan and cooling low speed are equal to the low heat fan speed.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
AFTER 2 SECOND DELAY, INDOOR BLOWER IS
ENERGIZED ON CONTINUOUS FAN SPEED
FIRST−STAGE HEAT DEMAND SATISFIED.
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
SECOND−STAGE HEAT DEMAND SATISFIED.
INDOOR BLOWER RAMPS DOWN TO LOW
GHR32Q−5 UNITS
(LOW HEAT / LOW COOL).
YES YES
YES
NO
YES
YES
YES
HEAT SPEED.
YES
COMPRESSOR IS ENERGIZED AND INDOOR
BLOWER CONTINUES TO OPERATE IN LOW
YES
FIRST−STAGE COOL DEMAND SATISFIED?
SECOND−STAGE COOL DEMAND
INDOOR BLOWER SWITCHES TO
SECOND−STAGE COOL SPEED
SECOND−STAGE COOL DEMAND SATISFIED?
INDOOR BLOWER SWITCHES TO FIRST−STAGE
COOL SPEED.
NO
YES
COOL SPEED.
Page 76
THERMOSTAT CALLS FOR FIRST−STAGE HEAT.THERMOSTAT CALLS FOR FIRST−STAGE COOL.
YES
BURNERS IGNITE AND INDOOR BLOWER
CONTINUES TO OPERATE IN CONTINUOUS
LOW (LOW HEAT / LOW COOL) MODE.
FIRST−STAGE HEAT DEMAND SATISFIED.
NO
THERMOSTAT CALLS FOR SECOND−STAGE HEAT.
YES
INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED
AFTER 30−SECOND RECOGNITION PERIOD.
YES
SECOND−STAGE HEAT DEMAND SATISFIED.
YES
INDOOR BLOWER SWITCHES TO LOW HEAT
SPEED.
YES
Page 77
IX− Troubleshooting
Diagnostic lights flash the roll out
LED#1−On
ACTION 1
blower does not energize
blower does not energize
120V field connection
SureLight Control UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT Unless otherwise noted, condition applies to all GHR32Q/V units.
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Condition Possible Cause Corrective Action / Comments
1.1
Both diagnostic lights fail to light up.
Main voltage 120V not supplied to unit.
1.1.1
ACTION 1 − Check 120V main voltage.
Determine cause of main power failure.
LED#1−Off LED#2−Off
1.2
GHR32Q/V−1 through −4 Units Only
Diagnostic lights flash the roll−out
code.
,
LED#2−Slow Flash
1.3
− On initial power−up the comb. air .
.
− Diagnostic lights flash the reverse
polarity code.
1.1.2
Miswiring of furnace or improper con­nections.
1.1.3
Circuit breaker tripped or fails to close.
1.1.4
Door interlock switch failure.
1.1.5
Transformer Failure.
1.1.6
Failed control board.
1.2.1
Roll−out switch open.
1.2.2
Roll−out switch failure.
1.2.3
Miswiring or improper connections at roll−out switch.
1.2.4
Nine pin connector failure
1.3.1
120V main power polarity reversed.
ACTION 1 − Check for correct wiring of 120V to power make up box and transformer.
ACTION 2 − Check 24V wiring to control board.
ACTION 1 − Replace circuit breaker if it is reset
but does not have continuity. ACTION 2 − If circuit breaker still trips, check for short.
ACTION 1 − Check that door switch is activated when door is closed. ACTION 2 − Check wire connections to switch, re­place loose connectors. ACTION 3 − Check continuity of switch in closed position. Replace if malfunctioning
ACTION 1 − Check that transformer output is 24V. Replace if malfunctioning
ACTION 1 − If all the above items have been checked, replace board.
ACTION 1 − Manually reset the roll−out switch by pushing the top button. ACTION 2 − Determine the cause of the roll−out switch activation before leaving furnace.
ACTION 1 − Check continuity across roll−out switch. Replace roll−out switch if switch is reset but does not have continuity.
− Check wiring connections to switch.
ACTION 1 − Check 9−pin connector for proper
connection to control board. ACTION 2 − Check continuity of the multi plug pin.
ACTION 1 − Check the 120V has line and neutral correctly input into control. ACTION 2 − Reverse the line and neutral at the 120V field connection.
.
LED#1−Fast Flash, LED#2−Slow Flash.
1.4
GHR32Q/V−1 through −4 Units Only
− On initial power up the combustion
air blower does not energize.
− Diagnostic lights flash normal power
on operation.
LED#1−Slow Flash LED#2−Slow Flash
1.4.1
Open combustion air blower motor cir­cuit.
1.4.2
Failed combustion air blower motor.
Page 77
ACTION 1 − Check for 120V to combustion air blower. If no power, check wire and connec­tions.
ACTION 1 − If power is present at blower, replace blower.
Page 78
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
g
Diagnostic lights flash the pressure
Condition Possible Cause Corrective Action / Comments
1.5
On initial power−up the combustion
air blower remains energized.
Diagnostic lights flash the improper main ground.
LED#1−Alternating Fast Flash LED#2−Alternating Fast Flash
1.5.1
Improper ground to the unit.
1.5.2
6−Pin connector is improperly at-
tached to the circuit board.
1.5.3
Line voltage is below 75V.
ACTION 1 − Check that the unit is properly grounded. ACTION 2 − Install a proper main ground to the unit
ACTION 1 − Check 6−pin connector for proper installation. Correctly insert connector into con­trol.
ACTION 1 − Check that the line voltage is above 75V. Determine cause of voltage drop and supply correct voltage to the control.
PROBLEM 2: UNIT FAILS TO OPERATE IN THE COOLING OR HEATING MODE, BUT COMBUSTION
AIR BLOWER OPERATES CONTINUOUS. GHR32Q/V−1 through −4 UNITS WITH CONTROL BOARDS DATE CODED AFTER NOV.1 1997, WILL OPERATE IN COOLING WITH COMBUSTION AIR BLOWER
CYCLING 5 SECONDS ON 55 SECONDS OFF, BUT NOT IN THE HEATING MODE.
Condition Possible Cause Corrective Action / Comments
2.1
On initial power−up the combustion
air blower remains energized.
Diagnostic lights flash the improper main ground.
− G32V−1 to −4 Units with control boards date coded after Nov.1 1997; combustion air blower will cycle 5 seconds on 55 seconds off.
LED#1−Alternating Fast Flash LED#2−Alternating Fast Flash
2.1.1
Open ignitor circuit.
2.1.2
Broken or failed ignitor.
ACTION 1 − Check for correct wiring and loose connections in the ignitor circuit. Check multi − plug connections for correct installation.
ACTION 1 − Unplug ignitor and read resistance across ignitor. If resistance does not read be­tween 10.9 and 19.7 ohms, replace the ignitor.
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES NOT
ENERGIZE
Condition Possible Cause Corrective Action / Comments
3.1
Unit operates with a cooling or contin-
uous fan demand.
Combustion air blower will not start with a Heating demand.
− Diagnostic lights flash the limit failure mode.
LED#1−Slow Flash, LED#2−On
3.2
− Unit operates with a cooling and con­tinuous fan demand.
− Combustion air blower will not start with a Heating demand.
Diagnostic lights flash the pressure
switch failure code.
LED#1−Off, LED#2−Slow Flash
3.1.1
Primary or secondary (if equipped) or
rollout limit switch open.
3.1.2
Miswiring of furnace or improper con-
nections at limit switch(es).
3.2.1
Miswiring of furnace or improper con-
nections to combustion air blower.
3.2.2
Pressure switch stuck closed.
ACTION 1 − Check continuity across switch(es). Switches reset automatically upon cool down.
Rollout switch must be reset manually. ACTION 2 − Check for restrictions on blower inlet
air (including filter) and outlet air. Determine cause for limit activation before placing unit back in operation.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − Check that the pressure switch is open without the combustion air blower operat­ing. Replace if malfunctioning
Page 78
Page 79
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES NOT
g
LED#1 Off
ENERGIZE (CONT.).
Condition Possible Cause Corrective Action/Comments
3.3
− Unit operates with a cooling and con-
tinuous fan demand.
Combustion air blower will not start
with a Heating demand.
Miswiring of furnace or improper con-
nections to combustion air blower.
3.3.1
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any loose connections.
Diagnostic lights flash the pressure
switch failure code 2.5 minutes after heating demand.
ACTION 1 − If there is 120V to combustion air blower and it does not operate, replace combus­tion air blower.
LED#1−Off,
3.3.2
Combustion air blower failure.
LED#2−Slow Flash
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
Condition Possible Cause Corrective Action/Comments
4.1
Unit operates with a cooling and
continuous fan demand.
Combustion air blower energizes
with a heating demand.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after heating demand.
LED#1−Off LED#2−Slow Flash
Pressure switch does not close due
to incorrect routing of the pressure
Pressure switch does not close due
to obstructions in the pressure tubing.
Pressure switch tubing damaged
Condensate in pressure switch tub-
Pressure switch does not close due to a low differential pressure across
the pressure switch.
Wrong pressure switch installed in the
unit, or pressure switch is out of cal-
Miswiring of furnace or improper con-
nections at pressure switch.
Pressure switch failure.
4.1.1
switch tubing.
4.1.2
4.1.3
4.1.4
ing.
4.1.5
4.1.6
ibration.
4.1.7
4.1.8
ACTION 1 − Check that the pressure switch tub-
ing is correctly routed. Correctly route pressure switch tubing.
ACTION 1 − Remove any obstructions from the pressure tubing and/or taps.
ACTION 1 − Check pressure switch tubing for leaks. Replace any broken tubing.
ACTION 1 − Check pressure switch tubing for condensate. Remove condensate from tubing. Check that the condensate tubing is located cor­rectly.
ACTION 1 − Check the differential pressure across the pressure switch. This pressure should exceed the set point listed on the switch. ACTION 2 − Check for restricted inlet and ex­haust vent. Remove all blockage. ACTION 3 − Check for proper vent sizing and run length. See installation instructions.
ACTION 1 − Check that the proper pressure switch is installed in the unit. Replace pressure switch if necessary.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − If all the above modes of failure have been checked, the pressure switch may have failed. Replace pressure switch and determine if unit will operate.
Page 79
Page 80
PROBLEM 5: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
rners light but unit shuts off prior
ignite code
ENERGIZES, IGNITOR IS ENERGIZED. (CONT.)
Condition Possible Cause Corrective Action/Comments
5.1
− Unit operates with a cooling and continuous fan demand.
− Combustion air blower energizes with Heating demand.
Ignitor is energized but unit fails to light.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
5.1.1
Check that gas is being supplied to
the unit.
5.1.2
Miswiring of gas valve or loose con-
nections at multi−pin control amp
plugs or valve.
5.1.3
Malfunctioning gas valve or ignition
control.
ACTION 1 − Check line pressure at the gas valve. Pressure should not exceed 13" WC for both nat­ural and propane. Line pressure should read a minimum 4.5" WC for natural and 8.0"WC for pro­pane.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − Check that 24V is supplied to the gas valve approximately 35 seconds after heat de­mand is initiated. ACTION 2 − Replace the valve if 24V is supplied but valve does not open (check for excessive gas line pressure before replacing gas valve). ACTION 3 − Replace the control board if 24V is not supplied to valve.
PROBLEM 6: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY
Condition Possible Cause Corrective Action/Comments
6.1
− Burners fire with a heating demand.
− Bu to satisfying T−stat demand.
− Diagnostic lights flash the pressure switch code.
LED#1−Off LED#2−Slow Flash
6.2
− Combustion air blower energizes with a heating demand.
− Burners light but fail to stay lit.
− After 5 tries the control diagnostics flash the watchguard burners failed to ignite code.
.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
6.1.1
Wrong concentric vent kit used for
terminating the unit.
6.1.2
Condensate drain line is not draining
properly.
6.1.3
Low pressure differential at the pres-
sure switch.
6.2.1
Sensor or sense wire is improperly
installed.
6.2.2
Sensor or sense wire is broken.
6.2.3
Sensor or sensor wire is grounded to
the unit.
6.2.4
Control does not sense flame.
ACTION 1 − Check vent termination kit installed. 1−1/2" dia. concentric vent (kit60G77) for 50 and 75 inputs and 2" dia. concentric vent (kit 33K97) for 100 &125 inputs.
ACTION 1 − Check condensate line for proper vent slope, and any blockage. Condensate should flow freely during operation of furnace. Repair or replace any improperly installed con­densate lines.
ACTION 1 − Check for restricted vent inlet or ex­haust. Remove all blockage. ACTION 2: Check for proper vent sizing. See installation instructions.
ACTION 1 − Check that sensor is properly lo­cated (page 10) and that the sense wire is properly attached to both the sensor and the control.
ACTION 1 − Check for a broken sensor. ACTION 2 − Test continuity across the sense
wire. If wire or sensor are damaged replace the component.
ACTION 1 − Check for resistance between the sensor rod and the unit ground. ACTION 2 − Check for resistance between the sensor wire and the unit ground.
ACTION 3 − Correct any shorts found in circuit.
ACTION 1 − Check the microamp signal from
the burner flame. If the microamp signal is be­low normal, check the sense rod for proper location or contamination. ACTION 2 − Replace, clean, or relocate flame sense rod. If rod is to be cleaned, use steel wool or replace sensor. DO NOT CLEAN ROD WITH SAND PAPER. SAND PAPER WILL CONTRIBUTE TO THE CONTAMINATION PROBLEM. NOTE: Do not attempt to bend sense rod.
Page 80
Page 81
PROBLEM 6: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
ure.
LED#2−Sl
h
flame failure.
Condition Possible Cause Corrective Action/Comments
6.3
− Combustion air blower energizes
with a heating demand.
− Burners light.
− Roll−out switch trips during the
heating demand.
− Diagnostic lights flash roll−out fail-
ure.
GHR32Q/V−1 through −4 Units Only
LED#1−On
ow Flas
GHR32Q/V−5 Units
LED#1−Slow Flash LED#2−On
6.4
Combustion air blower energizes
with a heating demand.
− Burners light roughly and the unit
fails to stay lit.
− Diagnostic lights flash watchguard
flame failure.
PREMATURELY (CONT.)
6.3.1
Unit is firing above 100% of the
nameplate input.
6.3.2
Gas orifices leak at the manifold con-
nection.
6.3.3
Air leakage at the connections be-
tween the primary heat exchanger,
secondary heat exchanger, and com-
bustion air blower.
6.3.4
Insufficient flow through the heat ex-
changer caused by a sooted or re-
stricted heat exchanger.
6.3.5
Burners are not properly located in
the burner box.
6.4.1
Recirculation of flue gases. This con-
dition causes rough ignitions and op-
eration. Problem is characterized by
nuisance flame failures.
ACTION 1 − Check that the manifold pressure matches value listed on nameplate. See installa­tion instructions for proper procedure. ACTION 2 − Verify that the installed orifice size match the size listed on the nameplate or installa­tion instructions. ACTION 3 − Check gas valve sensing hose to in­sure no leaks are present. ACTION 4 − Check the input rate to verify rate matches value listed on nameplate.
ACTION 1 − Tighten orifice until leak is sealed. NOTE: Be careful not to strip orifice threads. ACTION 2 − Check for gas leakage at the
threaded orifice connection. Use approved meth­od for leak detection (see unit instructions).
ACTION 1 − Check for air leakage at all joints in the heat exchanger assembly. Condition may cause high CO2 with high CO. ACTION 2 − Seal leakage if possible (high tem­perature silicon is recommended), replace heat exchanger if necessary, tag and return heat ex­changer to proper Lennox personnel.
ACTION 1 − Check for sooting deposits or other restrictions in the heat exchanger assembly. Clean assembly as outlined in instruction manu­al. ACTION 2 − For GHR32 gas furnaces, check for proper combustion and flow. CO2 should mea­sure between 6.0% and 8.0% for NAT and 7.0% and 9.0% for LP. CO should measure below .04% (400PPM) in an air−free sample of flue gases.
ACTION 1 − Check that the burners are firing into the center of the heat exchanger openings. Cor­rect the location of the burners if necessary.
ACTION 1 − Check for proper flow of exhaust gases away from intake vent. Remove any ob­stacles in front of the intake and exhaust vent which would cause recirculation. ACTION 2 − Check for correct intake and exhaust vent installation.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
6.4.2
Improper burner cross−overs
Page 81
ACTION 1 − Remove burner and inspect the cross−overs for burrs, or any restriction or if crossover is warped. Remove restriction or re­place burners.
Page 82
PROBLEM 6: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
6.5
− Combustion air blower energizes with a heating demand.
− Burners light.
− Diagnostic lights flash watch guard flame failure.
− NOTE" Unit might go into 60 minute Watchguard mode depending on in­termittent nature of sensor signal.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
PROBLEM 7: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE
Condition Possible Cause Corrective Action/Comments
7.0
− Unit operates correctly but the diag­nostic lights flash low flame sense code.
LED#1−Slow Flash LED#2−Fast Flash
PREMATURELY (CONT.)
6.5.1
Loose sensor wire connection causes
intermittent loss of flame signal.
7.1.1
Sense rod is improperly located on
the burner.
7.1.2
Sense rod is contaminated.
ACTION 1 − Check that the sensor is properly lo­cated. ACTION 2 − Check that the sense wire is properly attached to both the sensor and the control. Pay extra attention to the pin connectors.
ACTION 1 − Check the sense rod for proper loca­tion on the burner. Properly locate the sense rod or replace if rod cannot be located correctly.
ACTION 1 − Check sense rod for contamination or coated surface. Clean the sense rod with steel wool or replace sensor. DO NOT USE SAND PA­PER TO CLEAN ROD. SAND PAPER WILL CONTRIBUTE TO THE CONTAMINATION PROBLEM.
PROBLEM 8: RF STATIC DURING TIME FOR IGNITION
Condition Possible Cause Corrective Action/Comments
8.0
− AM radio interference
8.1.1
Ignitor operation
ACTION 1 Call Technical Support, Dallas
Page 82
Page 83
VSP2−1 Blower Control Board GHR32V−1 / −3 Units
DOES UNIT OPERATE?
YES
IS 24VAC ACROSS
COOLING MODE
PLACE JUMPER ACROSS R AND G.
IS BLOWER ON LOW SPEED AND IS
ON/OFF" LED−DS3 LIT? CFM" LED−DS4
LIGHT SHOULD BLINK ONCE FOR EV-
ERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2.
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP2 BOARD?
IN ADDITION TO R AND G,
JUMPER R AND DS.
NO
R AND C?
YES
YES
YES
NO
CHECK: 1−UNIT POWER 2−INTERLOCK SWITCH 3−TRANSFORMER 4−LIMIT SWITCH
NO
CHECK UNIT WIRING
AND IF CORRECT,
REPLACE VSP2−1.
NO
REPLACE VSP2−1.
END OF COOLING TEST
HEATING MODE
YES
IS BLOWER ON HIGH SPEED AND ARE DS1 AND
DS3 LIT? DOES THE CFM" LED−DS4 LIGHT BLINK
ONCE FOR EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2?
DOES UNIT OPERATE?
YES
IS 24VAC ACROSS
R AND C?
YES
PLACE HTG. BLOWER" JUMPER IN POSITION #2.
PLACE JUMPER ACROSS R AND W1. WAIT 75
SECOND FOR PREPURGE AND FANON" DELAY.
IS BLOWER ON LOW SPEED AND IS ON/OFF" LED−
DS3 LIT? CFM" LED−DS4 LIGHT SHOULD BLINK
ONCE FOR EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2.
YES
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP2 BOARD?
YES
PLACE HTG. BLOWER"
JUMPER IN POSITION #1.
R AND W1 REMAIN JUMPERED.
NO
NO
NO
NO
CHECK UNIT WIRING
AND IF CORRECT
REPLACE THE
VSP2−1.
CHECK: 1−UNIT POWER 2−INTERLOCK SWITCH 3−TRANSFORMER 4−LIMIT SWITCH
1−CHECK UNIT WIRING AND IF
CORRECT, REPLACE
2−BREAK AND REMAKE JUMPER
VSP2−1. (R TO W1).
3−AFTER 30−35 SECOND
PURGE, IS 24VAC PRESENT AT GAS VALVE?
REPLACE VSP2−1.
END OF TEST
DOES BLOWER SHIFT TO HEAT SPEED
AND IS HEAT" LED−DS2 ON? DOES THE
CFM" LED−DS4 LIGHT BLINK ONCE
FOR EVERY 100 CFM SELECTED IN
THE TABLES ON PAGE 2?
YES
REMOVE JUMPERS
YES
AFTER THE SELECTED
TIME, DOES BLOWER
TURN OFF?
Page 83
NO
NO
CHECK UNIT WIRING
AND IF CORRECT, REPLACE VSP2−1.
REPLACE THE VSP2−1.
Page 84
VSP3−1 Blower Control Board GHR32V−4 Units
DOES UNIT OPERATE?
YES
IS 24VAC ACROSS
COOLING MODE
PLACE JUMPER ACROSS R, G, AND Y1.
IS BLOWER ON LOW SPEED AND IS ON/
OFF LED−DS3 AND HI/LOW LED−DS1 LIT?
CFM LED−DS4 LIGHT SHOULD BLINK ONCE
FOR EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2.
NO
R AND C?
YES
YES
NO
CHECK: 1−UNIT POWER 2−INTERLOCK SWITCH 3−TRANSFORMER 4−LIMIT SWITCH
NO
CHECK UNIT WIRING AND IF
CORRECT, REPLACE VSP3−1.
END OF COOLING TEST
HEATING MODE
YES
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP3 BOARD?
YES
IN ADDITION TO R G, AND Y1
JUMPER R AND Y2.
IS BLOWER ON HIGH SPEED AND ARE DS1 AND DS3 LIT? DOES THE CFM LED−DS4 LIGHT BLINK
ONCE FOR EVERY 100 CFM SELECTED IN THE
YES
PLACE HTG. BLOWER JUMPER IN POSITION #2.
PLACE JUMPER ACROSS R AND W1. WAIT 75 SEC-
OND FOR PREPURGE AND FAN ON DELAY.
IS BLOWER ON LOW SPEED AND IS ON/OFF"
LED−DS3 LIT? CFM" LED−DS4 LIGHT SHOULD
BLINK ONCE FOR EVERY 100 CFM SELECTED IN
TABLES ON PAGE 2?
DOES UNIT OPERATE?
IS 24VAC ACROSS
R AND C?
YES
THE TABLES ON PAGE 2.
YES
IS 24 VOLTS PRESENT AT J73
PIN 12 ON VSP3 BOARD?
NO
NO
NO
REPLACE VSP3−1.
NO
NO
CHECK UNIT WIRING
AND IF CORRECT
REPLACE THE
VSP3−1.
CHECK: 1−UNIT POWER 2−INTERLOCK SWITCH 3−TRANSFORMER 4−LIMIT SWITCH
1−CHECK UNIT WIRING AND IF
CORRECT, REPLACE VSP3−1.
2−BREAK AND REMAKE JUMPER
(R TO W1).
3−AFTER 30−35 SECOND PURGE,
IS 24VAC PRESENT AT GAS VALVE?
REPLACE VSP3−1.
CFM" LED−DS4 LIGHT BLINK ONCE FOR
END OF TEST
YES
YES
PLACE HTG. BLOWER
JUMPER IN POSITION #1.
R AND W1 REMAIN JUMPERED.
DOES BLOWER SHIFT TO HIGH SPEED
AND IS HEAT" LED−DS2 ON? DOES THE
EVERY 100 CFM SELECTED IN THE
TABLES ON PAGE 2?
YES
REMOVE JUMPERS
AFTER THE SELECTED
TIME, DOES BLOWER
TURN OFF?
Page 84
NO
NO
CHECK UNIT WIRING
AND IF CORRECT, REPLACE VSP3−1.
REPLACE THE VSP3−1.
Page 85
ICM−2 WITH VSP2
120V to the motor must not be interupted. All connections for check out will be from the voltage source below (battery or 24V) to plug J46, after disconnectiong from blower control board VSP2.
J46
1
13
1
CHECK−OUT PROCEDURE USING BATTERY
An ordinary 9 volt battery with maximum DC 20volts is recommended. A 9 volt battery will last for about one day of normal operation.
LOW SPEED CHECK−OUT
12345678 910111213
J46
1− Disconnect power to unit. 2− Disconnect plug J46 from P46 located on the
blower control board. 3− Connect voltage source as shown above. 4− Turn on power to unit. Blower should operate
at low speed.
HIGH SPEED CHECK−OUT
12345678 910111213
J46
13
CHECK−OUT PROCEDURE USING 24V SOURCE
Unit transformer T1 with a maximum AC 30 volts may be used in lieu of a battery. If transformer T1 is used, double check all wiring connections be­fore placing unit back in operation.
LOW SPEED CHECK−OUT
12345678 910111213
J46
C
R
1− Disconnect power to unit. 2− Disconnect plug J46 from P46 located on the
blower control board. 3− Disconnect C and R from control board. 4− Connect voltage source as shown above. 5− Turn on power to unit. Blower should operate
at low speed.
HIGH SPEED CHECK−OUT
12345678 910111213
J46
C
5− Disconnect power to unit. 6− Connect voltage source as shown above. 7− Turn on power to unit. Blower should operate
at high speed.
HEATING SPEED CHECK−OUT
12345678 910111213
J46
8− Disconnect power to unit. 9− Connect voltage source as shown above.
10−Turn on power to unit. Blower should operate
at heating speed.
R
6− Disconnect power to unit. 7− Connect voltage source as shown above. 8− Turn on power to unit. Blower should operate
at high speed.
HEATING SPEED CHECK−OUT
12345678 910111213
J46
C
R
9− Disconnect power to unit. 10− Connect voltage source as shown above. 11− Turn on power to unit. Blower should operate
at heating speed.
A kit is available from the Lennox parts center to use in testing the variable speed motor. The kit 70J11 includes a test plug harness to facilitate ICM−2 check−out. Follow testing procedures outlined in the instructions provided with the kit.
The testing procedures are different than those listed above.
Page 85
Page 86
ICM−2 WITH VSP3
120V to the motor must not be interupted. All connections for check out will be from the voltage source below (battery or 24V) to plug J46, after disconnectiong from blower control board.
CHECK−OUT PROCEDURE USING BATTERY
An ordinary 9 volt battery with maximum DC 20volts is recommended. A 9 volt battery will last for about one day of normal operation.
LOW COOL SPEED
1 2 3 4 5 6 7 8 9 10111213
J46
1− Disconnect power to unit. 2− Disconnect plug J46 from P46 located on the
blower control board. 3− Connect voltage source as shown above. 4− Turn on power to unit. Blower should operate
at low cool speed.
HIGH COOL SPEED
12345678 910111213
5− Disconnect power to unit. 6− Connect voltage source as shown above.
7− Disconnect Y" on ignition control AND re-
move connection from Y2" on TB1 in control box. Connect a seperate wire between the − side of the battery and BOTH Y" on the igni­tion control and Y2" on TB1.
8− Turn on power to unit. Blower should operate
at high cool speed.
LOW HEAT SPEED
12345678 910111213
J46
To W" on ignition control board. !
9− Disconnect power to unit. 10− Connect voltage source as shown above. 11− Disconnect W" terminal on ignition control
board and connect a seperate wire between
W" and + side of battery. 12− Turn on power to unit. Blower should oper-
ate at low heat speed.
To Y2" on TB1.!
To Y" on ignition control. !
CHECK−OUT PROCEDURE USING 24V SOURCE
Unit transformer T1 with a maximum AC 30 volts may be used in lieu of a battery. If transformer T1 is used, double check all wiring connections be­fore placing unit back in operation.
LOW COOL SPEED
12345678 910111213
J46
C
1− Disconnect power to unit.
R
2− Disconnect plug J46 from P46 located on the
blower control board.
3− Disconnect C and R from ignition control
board.
4− Disconnect Y" from ignition control and con-
nect a seperate wire between R" on the
transfomer and Y" on the ignition control. 5− Connect voltage source as shown above. 6− Turn on power to unit. Blower should operate
at low cool speed.
To Y" on ignition control. !
HIGH COOL SPEED
1 2 3 4 5 6 7 8 9 1011 1213
J46
C
R
7− Disconnect power to unit. 8− Connect voltage source as shown above. 9− Disconnect Y2" on TB1 in control box and
connect a seperate wire between R" on transformer and Y2" on TB1.
10− Turn on power to unit. Blower should oper-
ate at high cool speed.
LOW HEAT SPEED
12345678910111213
J46
C
R
11− Disconnect power to unit. 11− Connect voltage source as shown above. 12− Disconnect W" from ignition control and
connect a seperate wire between R" on transformer and W" on the ignition control.
13− Turn on power to unit. Blower should operate
at low heat speed.
To W" on on ignition control. !
To Y2" on TB1.!
HIGH HEAT SPEED
12345678 910111213
J46
To W2" on TB1 !
13− Disconnect power to unit. 14− Connect voltage source as shown above.
15−Disconnect W2" on TB1 in control box and
connect a seperate wire between W2" and + side of battery.
16−Turn on power to unit. Blower should operate
at high heat speed.
Page 86
HIGH HEAT SPEED
12345678 910111213
J46
C
R
14− Disconnect power to unit. 15− Connect voltage source as shown above. 16− Disconnect W2" from TB1and connect a
seperate wire between R" on transformer and W2" on TB1.
17− Turn on power to unit. Blower should operate
at low heat speed.
To W2" on TB1 !
Page 87
ICM−2 WITH TWO STAGE VARIABLE SPEED CONTROL BOARD
120V to the motor must not be interrupted. All connections for check out will be from the volt­age source below (battery or 24V) to plug J46, after disconnecting from blower control board.
REMOVE PLUG FROM BOARD
1
CHECK−OUT PROCEDURE USING BATTERY
An ordinary 9 volt battery with maximum DC 20volts is recommended. A 9 volt battery will last for about one day of normal operation.
LOW
COOL
J46
SPEED
1− Disconnect power to unit. 2− Disconnect plug J46 from P46 located on the blower control board. 3− Connect voltage source as shown above. 4− Turn on power to unit. Blower should operate at low cool speed.
HIGH
COOL
SPEED
J46
16
CHECK−OUT PROCEDURE USING 24V SOURCE
Unit transformer T1 with a maximum AC 30 volts may be used in lieu of a battery. If transformer T1 is used, double check all wiring connections be­fore placing unit back in operation.
C
LOW
COOL
R
J46
SPEED
1− Disconnect power to unit. 2− Disconnect plug J46 from P46 located on the blower control board. 3− Connect voltage source as shown above. 4− Turn on power to unit. Blower should operate at low cool speed.
HIGH
C
R
COOL
SPEED
J46
5− Disconnect power to unit. 6− Connect voltage source as shown above.
7− Turn on power to unit. Blower should operate at high cool speed.
LOW
HEAT
J46
SPEED
8− Disconnect power to unit. 9− Connect voltage source as shown above.
10− Turn on power to unit. Blower should operate at low heat speed.
HIGH
HEAT
SPEED
11− Disconnect power to unit. 12− Connect voltage source as shown above.
13− Turn on power to unit. Blower should operate at high heat speed.
5− Disconnect power to unit. 6− Connect voltage source as shown above.
7− Turn on power to unit. Blower should operate at high cool speed.
C
LOW
HEAT
R
J46
SPEED
8− Disconnect power to unit. 9− Connect voltage source as shown above.
10− Turn on power to unit. Blower should operate at low heat speed.
C
HIGH
HEAT
SPEED
11− Disconnect power to unit. 12− Connect voltage source as shown above.
13− Turn on power to unit. Blower should operate at high heat speed.
R
J46J46
Page 87
Page 88
Page 88
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (HEATING)
MATCH UP COMMENTS OR SEQUENCE
Single-Stage Heating
with Single−Stage
Thermostat
Blower operates on the high
speed heat tap during the
heating mode.
Two-Stage Heating
With Single−Stage
Thermostat
No
Jumpers
Blower operates on the low
speed heat/cool tap during the
first stage of heating. Blower
operates on the high speed
heat tap during second stage
heating.
Harmony Heating No
Jumpers
Blower operates on PWM
signal generated by Har-
mony. Harmony overrides blower speed taps. Blower
speed varies according to
zone demand.
TABLE 35
FOR COOLING JUMPERS
SEE COOLING SECTION
BELOW
T−Strip Jumper
Mode of
Operation
No
Jumpers
One−Stage
W2 Timed
Two−Stage
Remove pin #3 of the J73
plug on the VSP control.
See fig. 16. Insulate end to
prevent it from shorting.
Low and high fire controlled by temperature modulating switch.
(continued on following page)
Jumper
Page 89
Page 89
MATCH UP COMMENTS OR SEQUENCE
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (COOLING)
Two-Speed Compressor,
no CCB1, no Harmony
Blower operates on low
speed heat/cool tap when
compressor is in first stage cooling. Blower op­erates on high speed cool
tap when compressor is in
second stage cooling.
DS" to Y2"
Single-Speed Com-
pressor, no CCB1,
no Harmony
Blower operates on high speed
cool tap during cooling.
(continued on following page)
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (HEATING CONTINUED)
Two−Stage Heating
With Two−Stage
Thermostat
No
Jumpers
Two−Stage Blower operates on the low
speed heat/cool tap during first
stage heating. Blower operates
on high speed heat tap during
second stage heating.
MATCH UP
COMMENTS OR SEQUENCE
T−STRIP JUMPER
T−Strip Jumper
Mode of Operation
DS to Y1"
Move factory
wired jumper from
Y1 to Y2".
(continued from previous page)
(factory wired)
Jumper
Y1
Y2
Remove Jumper
DS to Y1"
Blower operates on low speed
heat/cool during cooling
Page 90
Page 90
MATCH UP COMMENTS OR SEQUENCE
GHR32V−1 / −3UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (COOLING CONTINUED)
CCB1 with Two-Speed
Compressor, no Harmony
Blower speed is controlled by
the DC signal from CCB1. Blower operates on low speed heat/cool tap during dehumidi-
fication. Otherwise, blower op-
erates on high speed cool tap during high speed compressor operation and low speed heat/
cool tap during low speed
compressor operation.
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
CCB1 with Single-Speed
Compressor, no Harmony
Blower speed is controlled by
the DC signal from CCB1.
Blower operates on low speed heat/cool tap during dehumidifi­cation. Otherwise, blower oper-
ates on high speed cool tap
during cooling cycle.
No Jumpers
(Remove jumper
from Y1 to DS")
T−STRIP JUMPER
No Jumpers
(Remove jumper
from Y1 to DS")
(continued from previous page)
(continued on following page)
Y1
Y2
Page 91
Page 91
MATCH UP COMMENTS OR SEQUENCE WIRING CONNECTIONS
GHR32V−1 / −3 UNITS OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP2−1 (COOLING CONTINUED)
Harmony and Two-
Speed Compressor
Harmony and Single-
Speed Compressor
No Jumpers
(Remove
jumper from
Y1 to DS").
Remove pin #3 of the J73
terminal on the VSP con-
trol. Insulate end to pre-
vent shorting. Blower oper-
ates on PWM signal gener-
ated by Harmony. Harmony
overrides blower speed
taps. Blower speed varies
according to zone demand.
(continued from previous page)
FOR HEATING JUMPERS
SEE SEE HEATING SECTION
ABOVE
T−STRIP JUMPER
No Jumpers
(Remove
jumper from
Y1 to DS").
Remove pin #3 of the J73
terminal on the VSP con-
trol. Insulate end to pre-
vent shorting. Blower oper-
ates on PWM signal gener-
ated by Harmony. Harmony
overrides blower speed
taps. Blower speed varies
according to zone demand.
Page 92
Page 92
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (HEATING)
MATCH UP
COMMENTS OR SEQUENCE
Single-Stage Heating
with Single−Stage
Thermostat
Blower operates on
high speed during the
heating mode.
Two-Stage Heating
With Single−Stage
Thermostat
No
Jumpers
Blower operates on low
speed during the first stage
of heating. Blower operates
on high speed during
second−stage heating.
Harmony Heating No
Jumpers
Blower operates on PWM signal
generated by Harmony. Harmo-
ny overrides blower speed taps.
Blower speed varies according
to zone demand.
TABLE 36
WIRING CONNECTIONS
FOR COOLING JUMPERS
SEE COOLING SECTION
BELOW
T−Strip Jumper
Mode of
Operation
No
Jumpers
One−Stage
W2 Timed
Two−Stage
Remove pin #3 of the J73 plug on
the VSP control, and pins #2 and 13 of the J49 plug at the
motor. See fig 19 and 39. Insulate
ends to prevent them from shorting.
Low and high fire controlled by
temperature modulating switch.
(continued on following page)
Jumper
TEMPERATURE
SWITCH
MODULATING
Page 93
Page 93
MATCH UP
COMMENTS OR SEQUENCE
WIRING CONNECTIONS
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (COOLING)
Two-Speed Compressor,
no CCB1, no Harmony
Blower operates on low speed
cool when compressor is in
first stage cooling.
Blower operates on high
speed cool when compressor
is in second stage cooling.
DS to Y1
and
O to R
Remove factory−wired
jumper Y1 to Y2.
Single-Speed Com-
pressor, no CCB1,
no Harmony
Blower operates on high speed
during cooling.
(continued on following page)
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (HEATING CONTINUED)
MATCH UP
COMMENTS OR SEQUENCE
WIRING CONNECTIONS
T−STRIP JUMPER
T−Strip Jumper
Mode of Operation
DS to Y1
and Y1 to Y2
and O to R
(continued from previous page)
(factory wired)
Jumper
Two−Stage Heating
With Two−Stage
Thermostat
No
Jumpers
Two−Stage
Blower operates on low speed during first stage
heating. Blower operates on
high speed during second
stage heating.
Y1
Y2
Blower operates on low speed
during cooling.
Remove jumper
DS to Y1
Page 94
Page 94
MATCH UP COMMENTS OR SEQUENCE
WIRING CONNECTIONS
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (COOLING CONTINUED)
CCB1 with Two-Speed
Compressor, no Harmony
See table 9.
FOR HEATING JUMPERS
SEE HEATING SECTION
ABOVE
CCB1 with Single-Speed
Compressor, no Harmony
Blower speed is controlled
by the DC signal from
CCB1. Blower operates on
low speed during
dehumidification.
Otherwise, blower operates
on high speed during
cooling cycle.
Y1 to Y2
and
O to R
Remove the
factory−wired
jumper
Y1 to DS.
T−STRIP JUMPER
O to R
Remove jumper
from Y1 to DS
and
Y1 to Y2.
(continued from previous page)
(continued on following page)
Y 1
Y
2
Page 95
Page 95
MATCH UP COMMENTS OR SEQUENCE
WIRING
GHR32V−4 OPERATION SEQUENCE AND JUMPERS SUMMARY WITH VSP3−1 (COOLING CONTINUED)
Harmony and
Two-Speed Compressor
Y1 to Y2
and
O to R
(Remove
jumper from
Y1 to DS.)
Remove the wire from Pin #2 and
Pin #13 of the J49 harness connec-
tor at the motor and the wire from
Pin #3 of the J73 harness connec-
tor on the VSP control board.
Insulate the wire ends and secure
them to prevent shorting. Blower operates on PWM signal generated by the Harmony control board con-
trol board. The Harmony control
board overrides blower speed taps.
Blower speed varies according to
the zone’s demand.
(continued from previous page)
FOR HEATING JUMPERS
SEE SEE HEATING SECTION
ABOVE
T−STRIP JUMPER
O to R
(Remove jumper
from Y1 to DS
and Y1 to Y2.)
Remove the wire from Pin #2 and Pin
#13 of the J49 harness connector at
the motor and the wire from Pin #3 of
the J73 harness connector on the
VSP control board.
Insulate the wire ends and secure
them to prevent shorting. Blower op-
erates on PWM signal generated by
the Harmony control board.
The Harmony control board overrides
blower speed taps. Blower speed
varies according to zone’s demand.
CONNECTIONS
Harmony and
Single-Speed
Compressor
Page 96
Thermostat
1 Heat / 1 Cool
NOTE − Use dip switch 3 to set second−stage heat ON delay. ON−10 minutes. OFF−15 min­utes.
Table 37
GHR32V−5 Units Field Wiring Applications
Jumper Settings (See figure 21)
E20
Term. Strip
Y1 to Y2
W914 W951
SINGLE Ye s Intact Intact
Wiring Connections
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 1 Cool with CCB1
NOTE − Use dip switch 3 to set second−stage heat ON delay. ON−10 minutes. OFF−15 min­utes.
SINGLE Ye s Cut Intact
S1
T’STAT
CCB1
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 96
Page 97
Thermostat
1 Heat / 2 Cool
NOTE − Use dip switch 3 to set second−stage heat ON delay. ON−10 minutes. OFF−15 min­utes.
Table 37
GHR32V−5 Units Field Wiring Applications (Continued)
Jumper Settings (See figure 21)
E20
Term. Strip
Y1 to Y2
W914 W951
SINGLE No Intact Intact
Wiring Connections
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
1 Heat / 2 Cool
SINGLE No Cut Intact
with CCB1
NOTE − Use dip switch 3 to set second−stage heat ON delay. ON−10 minutes. OFF−15 min­utes.
2 Heat / 2 Cool TWO No Intact Intact
S1
T’STAT
S1
T’STAT
CCB1
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
2 Heat / 2 Cool
TWO No Cut Intact
with CCB1
Page 97
S1
T’STAT
CCB1
CONTROL
TERM. STRIP
OUTDOOR
UNIT
Page 98
Table 37
GHR32V−5 Units Field Wiring Applications (Continued)
Jumper Settings (See figure 21)
Thermostat
E20
Term. Strip
Y1 to Y2
W914 W951
2 Heat / 1 Cool TWO Yes Intact Intact
Wiring Connections
S1
T’STAT
CONTROL
TERM. STRIP
OUTDOOR
UNIT
FM21 Heat Pump / 1 Cool
Harmony Application* 2 Heat / 1 Cool
SINGLE Ye s Intact Cut
TWO Yes Cut Intact
*Disconnect existing furnace transformer and replace with 75VA, 24V transformer if de­frost option to be used.
75VA, 24V
TRANSFORMER*
NOTE − Wiring connec­tions to outdoor unit and thermostat made at FM21 control board per FM21 instructions.
TEMP.
MOD.
SWITCH
FAN LO
FAN LINE
HARMONY
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
FM21
NOTE − Remove Y1/Y2 jumper for two−stage cooling.
OUT-
DOOR
UNIT
Harmony
TWO No Cut Intact Application* 2 Heat / 2 Cool
*Cut wires at pin positions 2 and 13 of J/P46. Insulate ends to prevent a short. Blower operates on PWM signal generated by Harmony. Harmony overrides blower speed taps. Blower speed varies according to zone demand. Low and high−fire controlled by temperature modulating switch.
Page 98
TEMP.
MOD.
SWITCH
FAN LO
FAN LINE
HARMONY
CONTROL
TERM. STRIP
OUT-
DOOR
UNIT
Page 99
SERVICE NOTES
Page 99
Loading...