Do not store or use gasoline or oth
er flammable vapors and liquids in
the vicinity of this or any other ap
pliance.
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion
may result causing property damage,
personal injury or death.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Extinguish any open flames.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbor's phone. Follow the gas suppli
er's instructions.
If you cannot reach your gas supplier, call
the fire department.
Page 1
Page 2
G24M Unit Dimensions - inches (mm)
G24M3/4120
GAS PIPING
INLET
2 (51)
E
D
FLUE
OUTLET
*NOTE - The supply air opening is equipped with a 3/4 inch (19 mm)
scored flange that may be bent 90 for plenum connection. The dimen
sions shown were taken after the flange was bent.
The double scored flange at the front of the supply air open
ing may be bent for a total opening dimension (front to rear)
of either 191/2 inches (495 mm) or 19 inches (483 mm).
41/4
(105)
A
2 (51)
AIRFLOW
F Left Side
G Right Side
ELECTRICAL INLETS
(Top & Bottom)
*C
1
(25)
1
(25)
*191/2
(495)
*19
(483)
SUPPLY
AIR
OPENING
TOP VIEW
295/8
(752)
GAS PIPING
INLET
(Both Sides)
1
(25)
1
(25)
1
(25)
B
ELECTRICAL
INLETS
(Either Side)
**NOTE The return air opening is
Return Air
**C
Opening
FRONT VIEWSIDE VIEW
Model No.ABCDEFG
G24M245
G24M260
G24M360
G24M375
G24M475
G24M3/4100
G24M3/4120
G24M4/5100
G24M4/5120
G24M4/5140
in.17361/41563/427/16111/261/2
mm43292138117162293165
in.201/239181/283/841/4138
mm521991470213108331203
in.231/439211/49-3/441/412-31/3273/32
mm591991540248108329180
equipped with a 3/4 inch (19 mm) scored
flange that may be bent 90 for plenum
1
connection. The dimensions shown were
(25)
taken after the flange was bent.
15
(381)
**191/2
(495)
191/2
(495)
RETURN AIR
KNOCKOUT
(Either Side)
3/4 (19)
Return Air
Opening
1
(25)
1
(25)
Page 2
Page 3
G24M Parts Arrangement
G24M
PARTS IDENTIFICATION
COMBUSTION AIR
BLOWER
FRONT LOUVERED
PANEL
TRANSFORMER
CONTROL
BOARD
HEAT EXCHANGER
ASSEMBLY
FLUE BOX
PRESSURE
SWITCH
PRIMARY
LIMIT
LOW PRESSURE SWITCH
(Propane Only)
BURNER
ASSEMBLY
DOOR INTERLOCK SWITCH
VENT ADAPTER
NOx
TURBULATOR
SECONDARY
LIMITS
BLOWER ASSEMBLY
CABINET TOP
G24M
CABINET
CABINET
BOTTOM
G24M Gas Furnace
The G24M gas furnace is shipped ready for installation
in the upflow position. The unit can easily be converted
for installation in either downflow or horizontal applications. The furnace is shipped with a bottom seal
panel in place for side return air in upflow applications.
Shipping and Packing List
Package 1 of 1 contains:
1 - Assembled G24M unit (includes vent adapter except
for 140 kBtuh units)
1 - Vent adapter (140 kBtuh units only)
The following additional items may be ordered separately,
if required:
1 - Thermostat
1 - External filter rack kit
1 - Hanging bracket kit
1 - Propane/LP changeover kit
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Requirements
Lennox G24M units are American Gas Association (AGA)
and Canadian Gas Association (CGA) certified.
In the USA, installation of Lennox gas central furnaces must
conform with local building codes. In the absence of local
codes, units must be installed according to the current Na
tional Fuel Gas Code (ANSIZ223.1) in the United States.
The National Fuel Gas Code is available from the following
address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CAN/CGAB149.1 Installation Code
for Natural Gas Burning Appliances and Equipment" and
CAN/CGAB149.2 Installation Code for Propane Gas
Burning Appliances and Equipment," local plumbing or
waste water codes and other applicable local codes.
Page 3
Page 4
Adequate clearance must be made around the air open
ings into the vestibule area. Provisions must be made for
proper operation and for combustion air and ventilation air
supply according to the current National Fuel Gas Code or
CAN/CGAB149 standards.
Vent installations must be according to the provided vent
ing tables and applicable provisions of local building codes.
This furnace is AGA and CGA certified for installation clear
ances to combustible material as listed on the unit rating plate
and in the tables in figures 5, 7 and 9. Accessibility and ser
vice clearances must take precedence over fire protection
clearances.
NOTE - For installation on combustible floors, the furnace shall
not be installed directly on carpeting, tile, or other combustible
material other than wood flooring.
For installation in a residential garage, the furnace must be
installed so that the burner(s) and the ignition source are lo
cated no less than 18 inches (457 mm) above the floor. The
furnace must be located or protected to avoid physical dam
age by vehicles. When a furnace is installed in a public garage,
hangar, or other building that has a hazardous atmosphere,
the furnace must be installed according to recommended
good practice requirements and current National Fuel Gas
Code or CAN/CGA B149.1 and B149.2 standards.
The furnace must be adjusted to obtain a temperature rise
within the range specified on the unit rating plate.
The G24M furnace must be installed so that electrical com
ponents are protected from water.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Field wiring connections must meet or exceed specifica
tions of type T wire and withstand a maximum temperature
rise of 180°F (82°C) .
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside of the space con
taining the furnace, return air shall be handled by a duct(s)
sealed to the furnace casing and terminating outside space
containing furnace.
NOTE - G24M series units must not be used as a construc
tion heater during any phase of construction. Very low re
turn air temperatures, harmful vapors and misplacement of
the filters will damage the unit and lower its efficiency.
The Lennox G24M furnace may be installed in alcoves,
closets, attics, basements, garages and utility rooms in the
upflow, downflow, or horizontal position.
This furnace design has not been AGA or CGA certified for
installation in mobile homes, recreational vehicles, or out
doors.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal inju
ry or death.
When the furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
With a parallel flow arrangement, a damper (or other means
to control the flow of air) must adequately prevent chilled air
from entering the furnace. If the damper is manually oper
ated, it must be equipped to prevent operation of either the
heating or the cooling unit, unless it is in the full HEAT" or
COOL" setting.
When installed, the furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
General
These instructions are intended as a general guide and do not
supersede local codes in any way. Consult authorities having
jurisdiction before installation.
In addition to the requirements outlined previously, the fol
lowing general recommendations should be considered
when installing the Lennox G24M furnace.
The furnace should be placed as close to the center of the
air distribution system as possible. The furnace should also
be located close to the chimney or vent termination point.
Do not install the furnace where drafts might blow directly
into it. This could cause improper combustion and unsafe
operation.
Do not block furnace combustion air openings with cloth
ing, boxes, doors, etc. Combustion air is needed for proper
combustion and safe unit operation.
When the furnace is installed in an attic or other insulated
space, keep insulation away from the furnace.
Page 4
Page 5
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of
California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379-9900 USA
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient out
door air for combustion. Infiltration provided all the air that was
needed. In today's homes, tight construction practices make it
necessary to bring in air from outside for combustion. Take into
account that exhaust fans, appliance vents, chimneys, and
fireplaces force additional air that could be used for combus
tion out of the house. Unless outside air is brought into the
house for combustion, negative pressure (outside pressure is
greater than inside pressure) will build to the point that a down
draft can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a potentially
dangerous situation.
In the absence of local codes concerning air for combustion
and ventilation, use the guidelines and procedures in this
section to install G24M furnaces to ensure efficient and safe
operation. You must consider combustion air needs and re
quirements for exhaust vents and gas piping. A portion of this
information has been reprinted with permission from the Na
tional Fuel Gas Code (ANSIZ223.1). This reprinted material
is not the complete and official position of the ANSI on the ref
erenced subject, which is represented only by the standard in
its entirety.
In Canada, refer to the standard CAN/CGA B149.1 and
B149.2 installation codes.
CAUTION
Do not install furnace in a corrosive or contaminated
atmosphere. Meet all combustion and ventilation air
requirements, as well as all local codes.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of
California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379-9900 USA
All gasfired appliances require air for the combustion pro
cess. If sufficient combustion air is not available, the fur
nace or other appliance will operate inefficiently and un
safely. Enough air must be provided to meet the needs of all
fuelburning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, ex
haust fans, or clothes dryers are used at the same time as
the furnace, much more air is required to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air di
lutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace compo
nents.
The requirements for providing air for combustion and ven
tilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com
bined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be un
confined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Page 5
Page 6
Confined Space
A confined space is an area with a volume less than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com
bined input rating of all appliances installed in that space. This
definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air cir
culated by the furnace to areas outside the space containing
the furnace, the return air must be handled by ducts which are
sealed to the furnace casing and which terminate outside the
space containing the furnace. This is especially important
when the furnace is mounted on a platform in a confined space
such as a closet or small equipment room. Even a small leak
around the base of the unit at the platform or at the return air
duct connection can cause a potentially dangerous negative
pressure condition. Air for combustion and ventilation can be
brought into the confined space either from inside the building
or from outside.
EQUIPMENT IN CONFINED SPACE
CHIMNEY
OR GAS
VENT
G24M
FURNACE
NOTE-Each opening shall have a free area of at least one square
inch (645 mm2) per 1,000 Btu (.29 kW) per hour of the total input rat
ing of all equipment in the enclosure, but not less than 100 square
inches (64516 mm2).
ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 1
Air from Inside
If the confined space that houses the furnace adjoins a space
categorized as unconfined, air can be brought in by providing
two permanent openings between the two spaces. Each
opening must have a minimum free area of 1 square inch
(645 mm2) per 1,000 Btu (.29 kW) per hour of total input rat
ing of all gas-fired equipment in the confined space. Each
opening must be at least 100 square inches (64516 mm2).
One opening shall be within 12 inches (305 mm) of the top of
the enclosure and one opening within 12 inches (305 mm) of
the bottom. See figure 1.
Air from Outside
If air from outside is brought in for combustion and ventilation,
the confined space must have two permanent openings. One
opening shall be within 12 inches (305 mm) of the top of the
enclosure and one opening within 12 inches (305 mm) of the
bottom. These openings must communicate directly or by
ducts with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors or indirectly through vertical
ducts. Each opening shall have a minimum free area of 1
square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of
total input rating of all equipment in the enclosure. See figures
2 and 3. When communicating with the outdoors through hori
zontal ducts, each opening shall have a minimum free area
of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total
input rating of all equipment in the enclosure. See figure 4.
When ducts are used, they shall be of the same cross-sec
tional area as the free area of the openings to which they con
nect. The minimum dimension of rectangular air ducts shall
be no less than 3 inches (75 mm). In calculating free area,
the blocking effect of louvers, grilles, or screens must be
considered. If the design and free area of protective covering
is not known for calculating the size opening required, it may
be assumed that wood louvers will have 20 to 25 percent free
area and metal louvers and grilles will have 60 to 75 percent
free area. Louvers and grilles must be fixed in the open posi
tion or interlocked with the equipment so that they are opened
automatically during equipment operation.
Page 6
Page 7
CHIMNEY OR
GAS VENT
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(Inlet Air from Crawlspace and Outlet Air to Ventilated
Attic)
VENTILATION LOUVERS
(Each end of attic)
CHIMNEY
OR GAS
VENT
G24M
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
OUTLET
AIR
NOTE-The inlet and outlet air openings shall each have a free area of at least one
square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of
all equipment in the enclosure.
FIGURE 2
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
WATER
HEATER
INLET
AIR
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
CHIMNEY
OR GAS
VENT
WATER
HEATER
G24M
FURNACE
NOTE-The inlet and outlet air openings shall each have a
free area of at least one square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of the total input rating of all equip
ment in the enclosure.
FIGURE 3
INLET AIR
(Ends 12" above
bottom)
WATER
HEATER
Page 7
OUTLET AIR
G24M
FURNACE
INLET AIR
NOTE-Each air duct opening shall have a free area of at least
one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of
the total input rating of all equipment in the enclosure. If the
equipment room is located against an outside wall and the air
openings communicate directly with the outdoors, each open
ing shall have a free area of at least one square inch (645 mm2)
per 4,000 Btu (1.17 kW) per hour of the total input rating of all
other equipment in the enclosure.
FIGURE 4
Page 8
Setting Equipment
The Lennox G24M multiposition gas furnace can be
installed as shipped in upflow or horizontal position with
righthand or lefthand discharge. The furnace can easi
ly be converted for downflow applications.
Select a location that allows for required clearances
listed on the unit rating plate. Also consider gas supply
connections, electrical supply, vent connection and
installation and service clearances [24 inches (610 mm)
at unit front].
NOTE - 1/3 and 1/2 hp blower motors are equipped with ei
ther four flexible mounting legs or three flexible legs and
one rigid leg. The rigid leg is equipped with a shipping bolt
and a flat white plastic washer (rather than the rubber
mounting grommet used with a flexible mounting leg). This
shipping bolt and flat washer must be removed before the
furnace is put into operation. Once the shipping bolt and
washer are removed, the rigid leg will not touch the fan
housing.
Upflow Applications
The Lennox G24M furnace is shipped in a standard upflow
position. Level the furnace using shims or leveling bolts. Four
knockouts in the furnace base panel are factory-provided for
the installation of leveling bolts (field-provided). Allow for
clearances to combustible materials as indicated on the unit
rating plate. Minimum clearances for closet or alcove installa
tions are shown in figure 5.
In upflow applications, return air can be brought in through
the bottom or either side of the furnace. If a furnace with
bottom return air is installed on a platform, make an airtight
seal between the bottom of the furnace and the platform to
ensure proper and safe operation.
Knockouts are provided on both sides of the furnace cabi
net for installations with side return air. When side return air
is used, seal the bottom of the furnace using the panel pro
vided.
An upflow filter rack is available and must be ordered sepa
rately. The adjustable rack can be installed beneath the fur
nace (flush with cabinet edges) for bottom return air ap
plications or on the side of the furnace for side return air.
Upflow Application
Installation Clearances
TOP
LEFT
SIDE
BOTTOM
Vent
Connector
Type
TOP1 in. (25 mm)
*FRONT2 in. (51 mm)
BACK0
SIDES0
VENT1 in. (25 mm)
*Front clearance in alcove installation must be 24 in. (610
mm). Maintain a minimum of 24 in. (610 mm) for front service
access.
** For installations on a combustible floor, do not install the
furnace directly on carpeting, tile or other combustible mate
rials other than wood flooring.
Type CType B1
1 in. (25 mm)
2 in. (51 mm)
0
0
6 in. (152 mm)
0**FLOOR0**
RIGHT
SIDE
FIGURE 5
UNIT CONVERSION FOR DOWNFLOW APPLICATION
REMOVE
TOP CAP
REMOVE
FOUR
SCREWS
REMOVE
BOTTOM
UPFLOW CONFIGURATIONDOWNFLOW CONFIGURATION
SINGLE-WALLED VENT
PIPE FROM COMBUSTION
AIR BLOWER FLUE
ADAPTER TO FURNACE
FLUE OUTLET
(Furnished by installer)
WIRE HARNESS JACK
PLUGS AND SENSOR
LEAD AT CONTROL
DISCONNECT WIRE
HARNESS JACKPLUGS
AND SENSOR LEAD
FROM CONTROL
BOARD
FIGURE 6
Page 8
RECONNECT
BOARD
REINSTALL
TOP CAP ON
UNIT BOTTOM
ROTATE HEAT
EXCHANGER &
REINSTALL
REINSTALL
BOTTOM ON
UNIT TOP
Page 9
Downflow Applications
The Lennox G24M furnace is shipped in the upflow config
uration and must be converted for downflow installation.
Refer to figure 6 and the following steps to convert the unit
for downflow installation:
1 - Place unit on its back and remove access panel.
2 - Disconnect wire harness jackplugs from control
board.
3 - Disconnect sensor lead from control board.
4 - Remove four screws securing cabinet top cap to cabi
net.
5 - Remove four screws holding heat exchanger assem
bly in place. Slide heat exchanger out through top of
cabinet.
6 - Rotate heat exchanger 180o and slide back into cabi
net through top. Resecure using four screws.
7 - Remove four screws securing cabinet bottom piece
to cabinet. Replace with cabinet top cap.
8 - Use four screws to install cabinet bottom piece where
cabinet top was.
9 - Reconnect sensor lead to control board.
10- Reconnect wire harness jackplugs to control board.
11- Replace unit access panel.
12- Use cord clip located on right side of furnace to
hold wiring away from hot surfaces in heating
compartment. Install two #10 sheet metal screws in
cabinet top to provide a better air seal.
In downflow applications, the unit can be installed in three dif
ferent ways: on noncombustible flooring, on combustible
floor using an additive base, or on a reverseflow cooling cab
inet. Do not drag unit across floor.
Allow clearances to combustible materials as indicated on
unit rating plate. Minimum clearances for closet or alcove
installations are shown in figure 7.
DOWNFLOW INSTALLATION CLEARANCES
TOP
(60 Hz. only)
A separate downflow filter kit is available for use in down
flow applications.
A-Installation on Non-Combustible Flooring
1 - Cut floor opening keeping in mind the clearances
listed on the unit rating plate. Also, keep in mind gas
supply and electrical supply, vent connections and
sufficient installation and service clearances. See
table 1 for correct floor opening size.
TABLE 1
NONCOMBUSTIBLE FLOOR OPENING
UNIT
G24M-45/60/7519-3/450215-1/4388
G24M-100/12019-3/450218-3/4477
G24M-14019-3/450221-1/2546
NOTE - Floor opening dimensions listed are 1/4" (6mm) larger than unit
openings.
Front to RearSide to Side
inmminmm
2 - Flange warm air plenum and lower into opening.
3 - Set unit over plenum.
4 - Check to see that an adequate seal is made.
B-Installation on Combustible Flooring
1 - When unit is installed on a combustible floor, an addi
tive base (ordered separately) must be installed be
tween the furnace and the floor. See table 2 for open
ing size to cut in the floor.
TABLE 2
ADDITIVE BASE FLOOR OPENING
UNIT
G24M-45/60/7521-7/855617-5/16440
G24M-100/12021-7/855620-3/4528
G24M-14021-7/855623-1/2597
NOTE - Floor opening dimensions listed are 1/4" (6mm) larger than addi
tive base openings.
COMBUSTIBLE FLOORING INSTALLATION
Front to RearSide to Side
inmminmm
LEFT
SIDE
BOTTOM
VENT
CONNECTOR
TOP1" (25mm)1" (25mm)
*FRONT2" (51mm)2" (51mm)
BACK00
SIDES00
VENT6" (152mm)1" (25mm)
FLOORNC**NC**
NC - Non-combustible floor
*Front clearance in alcove installation must be a min. of 24" (610mm)
for front service access.
**With additive base on combustible floor.
TYPE CTYPE B1
FIGURE 7
RIGHT
SIDE
Page 9
G24M UNIT
ADDITIVE
BASE
1. Cut correct size floor opening
2. Set additive base into opening.
3. Set supply air plenum into additive base.
4. Set unit.
FIGURE 8
SUPPLY AIR
PLENUM
PROPERLY
SIZED FLOOR
OPENING
Page 10
2 - After opening is cut, set the additive base into opening.
3 - Check fiberglass strips on additive base to make sure
they are properly glued and positioned.
4 - Lower supply air plenum into additive base until ple
num flanges seal against fiberglass strips.
5 - Set unit on additive base so unit flanges drop into ple
num. Refer to figure 8.
NOTE – Be careful not to damage fiberglass strips.
Check for tight seal.
C-Installation on Cooling Cabinet
1 - Refer to reverseflow coil installation instructions for
correctly sized opening in floor and installation of cabi
net.
2 - When cooling cabinet is in place, install furnace so
flanges drop inside cabinet opening.
3 - Seal cabinet and check for air leakage.
Horizontal Applications
The Lennox G24M furnace can be installed in horizontal
applications in either upflow or downflow configuration
(See figure 6). It is preferable to install the unit in the stan
dard upflow configuration, if possible, because the vent
pipe will not interfere with service access for blower. Install
two #10 screws in the cabinet bottom (upflow configura
tion) or cabinet top (downflow configuration) to provide a
better air seal. The unit cannot be installed on its back.
Horizontal Application
Installation Clearances
LEFT
SIDE
Vent
Connector
Type
TOP00
*FRONT2 in. (51 mm) 2 in. (51 mm)
BACK00
SIDES2 in. (51 mm) 2 in. (51 mm)
VENT
FLOOR0**0**
TOP
BOTTOM
Type C
6 in. (152 mm)
RIGHT
SIDE
Type B1
1 in. (25 mm)
See figure 10 for furnace installations on a platform.
NOTE - When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the air conditioning coil to drain.
Horizontal Application
NOTE - Line contact is permissible. See the unit rating plate for clearances.
Unit Installed on Platform
GAS
ENTRY
VENT
PIPE
WORKING
PLATFORM
FIGURE 10
Anyone of the following methods may be used to suspend the
furnace from roof rafters or floor joists:
1 - Using Lennox hanging bracket kit catalog num
ber 46J66 Install as indicated in the installation instructions
provided with the hanging bracket kit.
2 - Using angle iron with at least 1/4 in. diameter
rods Install as shown in figure 11.
Note - Rods must not interfere with plenum or ex
haust piping; cooling coils and supply and return
air plenums must be supported separately.
Unit Suspended in Attic or Crawlspace
Level unit - side to side and end to end.
Leave sufficient clearance between rod and unit to
remove access panels.
Horizontal Application
Using Angle Iron and Rods
*Front clearance in alcove installation must be 24 in.
(610 mm). Maintain a minimum of 24 in. (610 mm) for
front service access.
** For installations on a combustible floor, do not install
the furnace directly on carpeting, tile or other combus
tible materials other than wood flooring.
FIGURE 9
Allow for clearances to combustible materials as indicated
on the unit rating plate. Minimum clearances for closet or
alcove installations are shown in figure 9.
Furnaces may be installed in either an attic or a crawlspace.
Page 10
1/4 in. ROD
ANGLE
SUPPORT TIES -
INSTALL TO PREVENT
SPREADING
Secure the angle iron to the unit with sheetmetal screws:
maximum screw length - 3/4 in. and minimum screw size - # 10.
IRON
FIGURE 11
Page 11
3 - Using heavy gauge perforated steel straps
(plumber's straps") Install as shown in figure 12.
Note - Straps must not interfere with plenum or ex
haust piping; cooling coils and supply and return
air plenums must be supported separately.
Unit Suspended in Attic or Crawlspace
Using Heavy Gauge Perforated Steel Straps
Level unit - side to side and end to end.
PLUMBER'S
STRAPS
Horizontal Application
(Plumber's Straps")
Inches (mm)
Use existing blower deck screws to secure
straps. Also use washers, if required.
11/2 (38)
213/16
(72)
WARNING
Improper installation of the furnace can result in per
sonal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or the living space. Use screws and joint tape to seal
the return air system to the furnace.
In platform installations with bottom return air, the
furnace should be sealed airtight to the return air ple
num. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Al
low absolutely no sagging, cracks, gaps, etc.
The return and supply air duct systems must never
be connected to or from other heating devices such
as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or proper
ty damage could result.
Duct System
101/4 (260)
At the unit's top corners, secure each strap to the furnace, positioned
as shown, using at least two sheetmetal screws:
maximum screw length - 3/4 in. and minimum screw size - # 10.
TOP OF UNIT
RETURN AIR
OPENING
END VIEW
11/2 (38)
1/2
(13)
1/2
(13)
TOP OF UNIT
SUPPLY AIR
OPENING
END VIEW
11/2 (38)
SUPPLY
AIR
11/2 (38)
1/2
(13)
1/2
(13)
FIGURE 12
Use industryapproved standards to size and install the
supply and return air duct system. This will result in a quiet
and lowstatic system that has uniform air distribution.
Supply Air Plenum
Furnaces installed without a cooling coil require the installa
tion of a removable access panel in the supply air duct. The
access panel should be large enough to permit inspection (ei
ther by smoke or reflected light) of the heat exchanger for
leaks after installation . The furnace access panel must al
ways be in place when the furnace is operating and it must
not allow leaks into the supply air duct system.
Return Air Plenum
Return air must not be drawn from a room where this
furnace, or any other gas appliance (ie., a water heat
er), is installed. When return air is drawn from a room,
a negative pressure is created in the room. If a gas ap
pliance is operating in a room with negative pressure, the
flue products can be pulled back down the vent pipe and
into the room. This reverse flow of the flue gas may result
in incomplete combustion and the formation of carbon
monoxide gas. This toxic gas might then be distributed
throughout the house by the furnace duct system.
In upflow applications, return air can be brought in through
the bottom or either side of the furnace. If a furnace with
bottom return air is installed on a platform, make an airtight
seal between the bottom of the furnace and the platform to
ensure proper and safe operation. Use fiberglass sealing
strips between the plenum and the furnace cabinet to en
sure a tight seal. If a filter is installed, size the return air duct
to fit the filter frame.
In downflow applications, use the following steps when instal
ling return air plenum:
1 - Flange bottom edge of plenum with a hemmed edge.
See figure 13.
2 - Use fiberglass sealing strips between plenum and the
unit cabinet to ensure a tight seal.
Page 11
Page 12
3 - In all cases, secure the plenum to the top flanges of the
furnace using sheet metal screws. See figure 13.
PLENUM
FIBERGLASS
SEALING STRIP
SECURE
HEMMED EDGE
CABINET
SIDE PANEL
FIGURE 13
4 - In closet installations, it may be necessary to install
sheet metal screws from the inside. If this is the case,
make plenum with a removable front to install screws
as shown in figure 14.
SECURE FROM
INSIDE
FIBERGLASS
SEALING STRIP
PLENUM
HEMMED EDGE
CABINET
SIDE PANEL
FIGURE 14
Venting
Venting Using a Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent an G24M furnace.
Masonry chimneys used to vent Category I central fur
naces must be either tilelined or lined with a listed metal
lining system or dedicated gas vent. Unlined masonry
chimneys are prohibited. See figures 15 and 16 for com
mon venting.
A Category I appliance must never be connected to a chim
ney that is servicing a solid-fuel appliance. If a fireplace
chimney flue is used to vent this appliance, the fireplace
opening must be permanently sealed.
A fan-assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
1 - The chimney is currently serving at least one draft
hood equipped appliance.
2 - The vent connectors and chimney are sized according
to the provided venting tables for the USA, and the ap
propriate venting tables in the standards of CAN/CGA
B149.1 and B149.2 of the Natural Gas and Propane
Installation Code in Canada.
A vent adapter is factoryinstalled on the combustion air
blower outlet of all models, except the G24M-140. On the
G24M-140, the flue adapter is supplied with the furnace,
and must be fieldinstalled, between the combustion air
blower flue outlet and the vent connector, using one or two
corrosionresistant screws. Modification of or failure to
install the adapter will cause unsafe unit operation and
will void AGA and CGA unit certification. The vent con
nector does not require insulation.
The G24M series units are classified as fan-assisted Cate
gory I furnaces when vertically vented according to the latest
edition of ANSI Z21.47 Central Furnace Standard in the
USA and the current standards of CAN/CGA B149.1 and
B149.2 of the Natural Gas and Propane Installation Code in
Canada. A fan-assisted Category I furnace is an appliance
equipped with an integral mechanical means to either draw
or force products of combustion through the combustion
chamber and/or heat exchanger.
NOTE - Use these instructions as a guide. They do not su
persede local codes.
The vent sizing tables in this manual were extracted from
the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and
are provided as a guide for proper vent installation. Proper
application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the ab
sence of local codes, the NFGC serves as the defining doc
ument.
Refer to the tables and the venting information contained in
these instructions to properly size and install the venting
system.
Install the first vent connector elbow a minimum of 6 inches
(152 mm) from the furnace vent outlet.
IMPORTANT
SINGLE appliance venting of a fanassisted furnace
into a tilelined masonry chimney (interior or outside
wall) is PROHIBITED. The chimney must first be lined
with either type B1 vent or an insulated single wall
flexible vent lining system, sized according to the
provided venting tables.
A type B1 vent or masonry chimney liner shall terminate above
the roof surface with a listed cap or a listed roof assembly ac
cording to the terms of their respective listings and the vent
manufacturer's instructions.
Do not install a manual damper, barometric draft regulator,
or flue restrictor between the furnace and the chimney.
If type B1 doublewall vent is used inside a chimney, no oth
er appliance can be vented into the chimney. Outer wall of
type B1 vent pipe must not be exposed to flue products.
Insulation for the flexible vent pipe must be an encapsu
lated fiberglass sleeve recommended by the flexible vent
pipe manufacturer. See figure 15.
The space between the liner and the chimney wall
should NOT be insulated with puffed mica or any other
loose granular insulating material.
If B1 vent or an insulated flexible vent pipe cannot be used
as liners, the chimney must be rebuilt to accommodate one
of these methods or some alternate approved method
must be found to vent the appliance.
When inspection reveals that an existing chimney is not safe
for the intended purpose, it shall be rebuilt to conform to na
tionally recognized standards, lined or relined with suitable
materials or replaced with a gas vent or chimney suitable for
venting G24M series units. The chimney passageway must
be checked periodically to ensure that it is clear and free of
obstructions.
Page 12
Page 13
Common Venting Using Metal-lined Masonry Chimney
SEALED
MAX. LENGTH
-- SEE NOTE 1
5 ft. (1.5 m)
minimum
4 in. (102 mm)
minimum
APPLIANCE
VENT CONNECTOR
SEE NOTE 2
OTHER
BELOW.
MIN. LENGTH -- AS
SHORT AS PRACTICAL
G24M
EXTERIOR
CHIMNEY WITH
B1 VENT OR
INSULATED
VENT PIPE.
PERMANENTLY
SEALED FIREPLACE
OPENING
FLEXIBLE
NOTE 1 - Refer to the provided venting tables for installations in the USA and the venting tables in CAN/CGA-B149.1 for installations Canada.
NOTE 2 - Either singlewalled or doublewalled vent connector may be used. Refer to the capacity requirements shown in the
provided venting tables for installations in USA and the venting tables in current CAN/CGA-B149.1 for installations in Canada.
FIGURE 15
Common Venting Using Tile-lined Interior Masonry
Chimney and Combined Vent Connector
NOTE- Refer to provided venting tables
for installations in the USA and the
venting tables in current CAN/CGAB149.1 for installations in Canada.
MINIMUM LENGTH = AS SHORT AS PRACTICAL.
FOR MAXIMUM LENGTH SEE NOTE TO LEFT
INTERIOR TILE-LINED
MASONRY CHIMNEY
NOTE - chimney must be properly
sized per provided venting tables
or lined with listed metal lining
system.
VENT
CONNECTOR
OTHER
APPLIANCE
G24M
SEE NOTE 1 BELOW
PERMANENTLY
SEALED FIREPLACE
OPENING
Note 1 - Either singlewalled or doublewalled vent connector may be used. Refer to the capacity requirements as shown in the pro
vided venting tables for installations in USA and the venting tables in current CAN/CGA-B149.1 for installations in Canada.
FIGURE 16
General Venting Requirements
All G24M furnaces must be vented according to these
instructions.
1 - Vent diameter recommendations and maximum al
lowable piping runs are found in the provided venting
tables for the USA, and the appropriate venting tables
2 - In no case should the vent or vent connector diameter
be less than the diameter specified in the provided
venting tables for the USA, and the appropriate vent
ing tables in the standards of CAN/CGA B149.1 and
B149.2 of the Natural Gas and Propane Installation
Code for Canada.
in the standards of CAN/CGA B149.1 and B149.2 of
the Natural Gas and Propane Installation Code for
Canada.
Page 13
Page 14
3 - For single appliance vents: If the vertical vent or tile
lined chimney has a larger diameter or flow area than
the vent connector, use the vertical vent diameter to
determine the minimum vent capacity and the vent
connector diameter to determine the maximum
vent capacity. The flow area of the vertical vent, how
ever, shall not exceed 7 times the flow area of the
listed appliance categorized vent area, drafthood out
let area or flue collar area unless designed according
to approved engineering methods.
4 - For multiple appliance vents: The flow area of the larg
est section of vertical vent or chimney shall not exceed
7 times the smallest listed appliance categorized vent
area, drafthood outlet area or flue collar area unless
designed according to approved engineering meth
ods.
5 - The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
6 - Single appliance venting configurations with zero lat
eral lengths, see tables 4 and 5, are assumed to have
no elbows in the vent system. For all other vent config
urations, the vent system is assumed to have two 90
elbows. For each additional 90 elbow or equivalent
(for example two 45 elbows equal one 90 elbow) be
yond two, the maximum capacity listed in the venting
table should be reduced by 10 percent (0.90 x maxi
mum listed capacity).
7 - The common venting tables 6, 7, 8, and 9 were gener
ated using a maximum horizontal vent connector
length of 1-1/2 feet (.46 m) for each inch (25 mm) of
connector diameter as follows:
TABLE 3
Connector
Diameter
inches (mm)
3 (76)4-1/2 (1.37)
4 (102)6 (1.83)
5 (127)7-1/2 (2.29)
6 (152)9 (2.74)
7 (178)10-1/2 (3.20)
Maximum Horizontal
Connector Length
feet (m)
8 - If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent of
two 90 elbows (0.80 x maximum common vent ca
pacity). The horizontal length of the offset shall not ex
ceed 11/2 feet (.46 m) for each inch (25 mm) of com
mon vent diameter.
9 - The vent pipe should be as short as possible with
the least number of elbows and angles required to
complete the job. The vent connector should be
routed to the vent using the shortest possible route.
10- A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4
mm) per linear foot (305 mm) of connector, back to
ward the appliance. See local and national installation
codes for support intervals and methods. National
installation code in the USA is current edition of Na
tional fuel Gas Code (ANSI-Z223.1). National installa
tion codes in Canada are current editions of CAN/
CGA-B149 codes.
11- Vent connectors shall be firmly attached to furnace
flue collars by screws or other approved means, ex
cept vent connectors of listed type B vent material
which shall be assembled according to the manufac
turer's instructions. Joints between sections of single
wall connector piping shall be fastened by screws or
other approved means.
12- When the vent connector used for Category I ap
pliances must be located in or pass through a crawl
space or other areas which may be cold, that portion of
the vent connector shall be constructed of listed
doublewall type B vent material or material having
equivalent insulation qualities.
13- All venting pipe passing through floors, walls, and ceil
ings must be installed with the listed clearance to com
bustible materials and be fire stopped according to lo
cal codes. In absence of local codes, refer to NFGC
(Z223.1).
14- No portion of the venting system can extend into, or pass
through any circulation air duct or plenum.
15- Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
16- If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10%, the equivalent of one 90 elbow (0.90 x maximum
common vent capacity).
17- The common vent diameter must always be at least as
large as the largest vent connector diameter.
18- In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or flue collar outlet.
19- Do not install a manual damper, barometric draft regu
lator or flue restrictor between the furnace and the
chimney.
20- When connecting this appliance to an existing dedicated
or common venting system, the venting system must be
inspected for signs of corrosion and general condition.
The sizing of the vent system must be reviewed and
must conform to these instructions and the provided
venting tables for the USA, and the appropriate venting
tables in the standards of CAN/CGA B149.1 and
B149.2 of the Natural Gas and Propane Installation
Code for Canada. If the existing system is in conflict with
these requirements, the venting system must be re
sized.
Page 14
Page 15
TABLE 4
(
)L(
)
(feet)
(feet)
5
30
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH TYPE B DOUBLE-WALL CONNECTORS
SERVING A SINGLE CATEGORY I APPLIANCE
Vent and Connector Diameter - D (inches)
Height
H
feet
6
8
10
15
20
30
NOTE: Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent
system is assumed to have two 90 elbows. For each additional 90 elbow or equivalent (for example two 45 elbows equal one 90 elbow) beyond two, the maximum
capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
feet
0078015202510375
2135118972715732232
4214930943915350227
6254636914714959223
0084016502760415
21257161092517828263
52353321034217153255
8284939985116464247
0088017502950447
21261171182319426289
52357321134118752280
103051411045417667267
0094019103270502
21169151362022622339
52265301303921949330
102959401215120664315
1535534811 26119576301
0097020203490540
21075141491825020377
52171291433824247367
102864381335022962351
153458461245921773337
2048525511 66920684322
00100021303740587
2981131661428318432
52177281603627545421
102770371504826259405
153364441415724970389
205658531326623780374
30NRNR7311388214104346
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 15
Page 16
TABLE 5
(
)L(
)
(feet)
(feet)
5
30
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH SINGLE-WALL METAL CONNECTORS
SERVING A SINGLE CATEGORY I APPLIANCE
Vent and Connector Diameter - D (inches)
Height
H
feet
6
8
10
15
20
30
NOTE: Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent
system is assumed to have two 90 elbows. For each additional 90 elbow or equivalent (for example two 45 elbows equal one 90 elbow) beyond two, the maximum
capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
feet
038775915185249126373
23951609685156123231
4NRNR7492102152146225
6NRNR8389114147163220
037835816483273123412
239565910883176121261
5NRNR77102107168151252
8NRNR9095122161175243
037875717482293120444
23961591178219311 9287
5525676111105185148277
10NRNR97100132171188261
03693561908032511 6499
23869571368022511 5337
5516375128102216144326
10NRNR95116128201182308
15NRNRNRNR158186220290
03596542007834611 4537
23774561487824811 3375
5506873140100239141363
10NRNR93129125223177344
15NRNRNRNR155208216325
20NRNRNRNR186192254306
034995321176372110584
237805516476281109429
549747215798271136417
10NRNR91144122255171397
15NRNR11 5131151239208377
20NRNRNRNR181223246357
30NRNRNRNRNRNRNRNR
3 Inch4 Inch5 Inch6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MINMAXMINMAXMINMAXMINMAX
Page 16
Page 17
V
ent
C
Height
Rise
6
8
0
5
0
30
V
Height
Height
H
(feet)(feet)
6
8
10
15
20
30
onnector
Rise
TABLE 6
VENT CONNECTOR CAPACITY
TYPE B DOUBLE-WALL VENTS WITH TYPE B DOUBLE-WALL CONNECTORS
SERVING TWO OR MORE CATEGORY I APPLIANCES
Vent and Connector Diameter - D (inches)
3 Inch4 Inch5 Inch6 Inch
R
MINMAXMINMAXMINMAXMINMAX
1223735664610658164
2234137754812160183
3244438814913262199
1224035724911464176
2234436805112866195
3244737875313967210
1224334784912365189
2234736865113667206
3245037925214669220
1215033894714264220
2225335964915366235
32455361025116368248
1215433994615762246
22257341054816764259
32360351105017666271
12062311134518160288
22164331184719062299
32266341234819864309
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 7
COMMON VENT CAPACITY
TYPE B DOUBLE-WALL VENTS WITH TYPE B DOUBLE-WALL CONNECTORS
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter - D (inches)
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap
pliances, the venting system is likely to be too large to
properly vent the remaining attached appliances. The fol
lowing test should be conducted while each appliance in
operation and the other appliances not in operation re
main connected to the common venting system. If the
venting system has been installed improperly, the system
must be corrected as indicated in the general venting re
quirements section.
1 - Seal any unused openings in the common venting
system.
2 - Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re
striction, leakage, corrosion, or other deficiencies which
could cause an unsafe condition.
3 - To the extent that it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other spaces
of the building. Turn on clothes dryers and any ap
pliances not connected to the common venting sys
tem. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at maxi
mum speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
4 - Follow the lighting instructions. Place the appliance
being inspected in operation. Adjust thermostat so ap
pliance will operate continuously.
5 - Test for spillage of flue gases at the draft hood relief
opening after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from a ciga
rette, cigar or pipe.
Page 18
Page 19
6 - After determining that each appliance remaining con
nected to the common venting system properly vents
when tested as indicated in step 3, return doors, win
dows, exhaust fans, fireplace dampers and any other
gasburning appliance to their previous condition of
use.
7 - If improper venting is observed during any of the
above tests, the common venting system must be cor
rected. The common venting system should be re
sized to approach the minimum size as determined by
using the appropriate tables in appendix G in the cur
rent standards of the National Fuel Gas Code ANSI
Z223.1 in the USA, and the appropriate Category 1
Natural Gas and Propane appliances venting sizing
tables in the current standards of the CAN/CGA
B149.1 and B149.2 in the Natural Gas and Propane
Installation Code in Canada.
Horizontal Venting
Side Wall Venting Kit Wiring
CK-43 CONTROL BOX
THERMOSTAT CONNECTIONS
TERMINAL IN FURNACE
JUNCTION BOX
WRYG
SWG
POWER
VENTER
MOTOR
FACTORY-INSTALLED WIRING
FIELD-INSTALLED WIRING
THERMOSTAT
R
24 VAC
T
G
W
Y
PRESSURE
SWITCH
C
L1
120VAC
L2
NO
L1MN
2
1
354
RELAY
T1 T2 T3
M
FIGURE 17
When horizontally vented, the minimum clearance for
termination from electric meters, gas meters, regulators
and relief equipment is 4 feet (1.2 m) for US installations.
Refer to the current CAN/CGA B149.1 and B149.2 for
installations in Canada or with authorities having local ju
risdiction.
At vent termination, care must be taken to maintain pro
tective coatings over building materials (prolonged expo
sure to exhaust condensate can destroy protective coat
ings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8 m) of a condensing unit because
the condensate can damage the painted coating.
Gas Piping
GAS SUPPLY
1 - This unit is shipped standard for left or right side instal
lation of gas piping (or top entry in horizontal applica
tions). Connect the gas supply to the piping assembly.
2 - When connecting the gas supply, factors such as
length of run, number of fittings and furnace rating
must be considered to avoid excessive pressure drop.
Table 10 lists recommended pipe sizes for typical ap
plications.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters
or elevator shafts.
4 - The piping should be sloped 1/4 inch (6.4 mm) per 15 feet
(4.57 m) upward toward the meter from the furnace. The
piping must be supported at proper intervals [every 8 to
10 feet (2.44 to 3.01 m) using suitable hangers or straps.
A drip leg should be installed in vertical pipe runs to the
unit.
5 - In some localities, codes may require installation of a
manual main shutoff valve and union (furnished by
the installer) external to the unit. Union must be of the
ground joint type.
This furnace design is certified by the American Gas
Association and the Canadian Gas Association for hori
zontal venting through an outside wall only with the use of a
Field Controls Company Model SWG4L side wall venting
kit available as Lennox part number 79J15. No other Field
brand venting kit or any other manufacturer's venting kit is
acceptable. Horizontal venting of this furnace without the
use of the above stated kit is prohibited. See figure 17 for
field wiring of side wall horizontal venting kit.
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro
leum gases.
NOTE - Install a 1/8 inch NPT plugged tap in the field piping
upstream of the gas supply connection to the unit. The tap
must be accessible for test gauge connection. See figure 18.
NOTE - In case emergency shutoff is required, shut off main
manual gas valve and disconnect main power to unit. These
devices should be properly labeled by the installer.
NOTE-Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
Length of Pipe - feet (m)
20
(.57)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95
5300
(150.07)
10900
(308.64)
18
(.51)
40
(1.13)
73
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
16
(.45)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
8800
(249.18)
15
(.42)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
14
(.40)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
13
(.37)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
7200
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Left Side Piping
(Standard)
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Tap Shown)
GROUND
JOINT
UNION
DRIP LEG
AUTOMATIC
GAS VALVE
(with manual
shut-off valve)
PROVIDED
AND INSTALLED
FIGURE 18
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and field-installed) for gas leaks. Use
a leak detecting solution or other preferred means.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly af
ter leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
NOTE - In case emergency shutoff is required, shut off the
main manual gas valve and disconnect the main power to
the furnace. These devices should be properly labeled by
the installer.
The furnace must be isolated from the gas supply system
by closing its individual manual shutoff valve during any
FIELD
AUTOMATIC
GAS VALVE
(with manual
shut-off valve)
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Tap
Shown)
GROUND
JOINT
UNION
DRIP LEG
Right Side Piping
(Alternate)
pressure testing of the gas supply system at pressures
equal to or less than 1/2 psig (3.48 kPa).
IMPORTANT
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 19. Gas
valves can be damaged if subjected to more than 1/2
psig (3.48 kPa).
MANUAL MAIN
SHUT-OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
FIGURE 19
ISOLATE
GAS VALVE
FURNACE
Page 20
Page 21
Electrical
CAUTION
Electrostatic discharge can affect electronic com
ponents. Take precautions during furnace installa
tion and service to protect the furnace's electronic
controls. Precautions will help to avoid control ex
posure to electrostatic discharge by putting the fur
nace, the control and the technician at the same
electrostatic potential. Neutralize electrostatic
charge by touching hand and all tools on an un
painted unit surface, such as the gas valve or blow
er deck, before performing any service procedure.
These units operate on 120 volt, single phase, 60 hz
electrical power. Refer to figure 20 for field wiring and
figure 22 for schematic wiring diagram and trouble
shooting.
1 - Select circuit protection and wire size according to the
unit rating plate.
2 - Knockouts are provided on both sides of the furnace
cabinet to facilitate wiring.
3 - Install the room thermostat according to instructions
provided with the thermostat.
4 - Install a separate disconnect switch (protected by ei
ther fuse or circuit breaker) near the unit so power can
be turned off for servicing.
5 - Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough to
facilitate servicing at a later date. Remove the blower
access panel and open the panel to check wire length
for access.
6 - Complete wiring connections to the equipment using
wiring diagram provided with unit and wiring diagrams
shown in figures 20 and 22. Use 18 gauge wire or larg
er for thermostat connections.
7 - Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70) for the
USA and current Canadian Electric Code part 1 (CSA
standard C22.1) for Canada.
NOTE - The G24M furnace contains electronic com
ponents that are polarity sensitive. Make sure that
the furnace is wired correctly and is properly
grounded.
8 - One line voltage accessory ACC" terminal is provided
on the furnace control board with a protective plastic
cap. Any accessory rated up to 4 amps can be con
nected to this terminal (after removing the protective
cap) with the neutral leg of the circuit being connected
to the line voltage neutral wire. See figure 21 for con
trol board configuration. This terminal is energized
whenever the blower is in operation.
9 - One line voltage heating accessory HTG ACC" termi
nal is provided on the furnace control board with a pro
tective plastic cap. Any accessory rated up to 4 amps
can be connected to this terminal (after removing the
protective cap) with the neutral leg of the circuit being
connected to the line voltage neutral wire. See figure
21 for control board configuration. This terminal is en
ergized in the heating mode whenever the blower is in
operation.
Indoor Blower Speeds (Refer to Figure 22)
1 - When the thermostat is set to FAN ON", the indoor
blower will run continuously on low speed when there
is no cooling or heating demand.
2 - When the G24M is running in the heating mode, the in
door blower will run on the heating speed.
3 - When there is a cooling demand, the indoor blower will
run on the cooling speed.
Page 21
Page 22
FIELD INSTALLED CLASS II 24V
FIELD INSTALLED LINE VOLTAGE
TYPICAL G24M FIELD WIRING DIAGRAM
(120V, 1PH, 60HZ)
COMBUSTION
PRESSURE SWITCH
PRIMARY LIMIT
AIR BLOWER
120V, 1PH, 60 HZ
L1 N
FUSED OR CIRCUIT BREAKER
(FURNISHED BY INSTALLER)
DISCONNECT
GND
THERMOSTAT
TO COMPRESSOR
CONTACTOR
GAS
GWRY
FLAME ROLLOUT SWITCHES
TRANSFORMER
GWYCR
SURELIGHT CONTROL
VALV E
SECONDARY
LIMITS
DOOR
INTERLOCK
SWITCH
BLACK
WHITE
FIGURE 20
50A62 SureLight INTEGRATED CONTROL BOARD
(Silicon Nitride Ignition System)
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
TERMINAL DESIGNATIONS
Blower - Cooling Speed (Line Volt)
Blower - Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
FIGURE 21
Page 22
Page 23
G24M Schematic Wiring Diagram
(120V, 1PH, 60HZ)
FIGURE 22
Page 23
Page 24
Unit Start-Up
WARNING
Do not use this furnace if any part has been underwa
ter. Immediately call a qualified service technician to
inspect the furnace and to replace any part of the
control system and any gas control which has been
under water.
WARNING
If overheating occurs or if gas supply fails to shut off,
shut off the manual gas valve to the appliance before
shutting off electrical supply.
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at dis
connect switch.
FOR YOUR SAFETY READ BEFORE LIGHTING
BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
Use only your hand to turn the gas control knob. Never use
tools. If the knob will not turn by hand, do not try to repair it, call
a qualified service technician. Force or attempted repair may
result in a fire or explosion.
Placing Furnace Into Operation
G24M furnaces are equipped with a SureLight ignition
system. Do not attempt to manually light burners on these
furnaces. Each time the thermostat calls for heat, the burn
ers will automatically light.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figures 23 and 24)
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 - Remove the access panel.
6 - White Rodgers 36E Gas Valve - Switch gas valve le
ver to OFF. See figure 23.Honeywell VR8205 Gas Valve - Turn knob on gas
valve clockwise to OFF. Do not force. See figure
24.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instructions.
If you do not smell gas go to next step.
WHITE RODGERS 36E Series Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
GAS VALVE SHOWN IN OFF POSITION
FIGURE 23
HONEYWELL VR8205 Series Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
ON
OFF
GAS VALVE SHOWN IN OFF POSITION
FIGURE 24
8 - White Rodgers 36E Gas Valve - Switch gas valve lever
to ON.
Honeywell VR8205 Gas Valve - Turn knob on gas valve
counterclockwise to ON. Do not force.
9 - Replace the access panel.
10 - Turn on all electrical power to the unit.
11 - Set the thermostat to desired setting.
MANIFOLD
PRESSURE
OUTLET
NOTE – When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12 - If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service techni
cian or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting.
2 - Turn off all electrical power to the unit if service is to be
performed.
3 - Remove the access panel.
4 - White Rodgers 36E Gas Valve - Switch gas valve le
ver to OFF.
Honeywell VR8205 Gas Valve - Turn knob on gas
valve clockwise to OFF. Do not force.
5 - Replace the access panel.
Page 24
Page 25
Heating Sequence Of Operation
NAT
3.5
3.5 (0.87)*
3.4 (0.85)
3.3 (0.82)
3.2 (0.80)
9.5
)*
1 - When thermostat calls for heat, combustion air blower
starts.
2 - Combustion air pressure switch proves blower opera
tion. Switch is factory set and requires no adjustment.
3 - After a 15 second prepurge, hot surface ignitor ener
gizes.
4 - After a 20 second ignitor warm-up period, gas valve
solenoid opens.
5 - Gas is ignited, ignition sensor proves the flame and
combustion process continues.
6 - If flame is not detected after first ignition trial, ignition
control will repeat steps 3 and 4 four more times before
locking out the gas valve (WATCHGUARD" flame fail
ure mode). Ignition control will then automatically re
peat steps 3, 4, 5 and 6 after 60 minutes.
7 - To interrupt the 60-minute WATCHGUARD" period,
move thermostat from Heat" to OFF" then back to
Heat." Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow
To check for proper gas flow to the combustion chamber, de
termine the Btu (kW) input from the unit rating plate. Divide this
input rating by the Btu (kW) per cubic foot (cubic meter) of
available gas. The result is the required number of cubic feet
(cubic meter) per hour. Determine the flow of gas through the
gas meter for two minutes and multiply by 30 to get the hourly
flow of gas.
Gas Pressure
1 - Check the gas line pressure with the unit firing at maxi
mum rate. A minimum of 4.5 in. w.c. for natural gas or
11.0 in. w.c. for LP/propane gas should be maintained.
2 - After the line pressure has been checked and ad
justed, check the regulator pressure. Manifold pres
sures are given in table 11. See figures 23 and 24 for
manifold pressure adjustment screw location.
Note - A natural gas to LP/propane gas changeover kit is
required to convert the unit.
High Altitude Information
Refer to table 11 for manifold pressure settings for installa
tions at different altitudes and for different fuels.
TABLE 11
MANIFOLD ABSOLUTE PRESSURE (OUTLET) IN. W.C. (KPA)
Altitude - feet (m) above sea level
FUEL
LP
0-2000
(0-610)
3.5
(0.87)
9.5
(2.36)
2000-4500
(610-1372)
9.5 (2.36
4500-5500
(1372-1676)
5500-6500
(1676-1981)
*
9.2 (2.29)8.9 (2.21)8.6 (2.14)
*
6500-7500
(1981-2286)
*No adjustment required.
NOTE - In Canada, certification for installations at eleva
tions over 4500 feet (1372 m) is the jurisdiction of local au
thorities.
The combustion air pressure switches are factory-set and
require no adjustment.
At elevations of 4500 feet (1372 m) or greater, replace the
factoryinstalled pressure switch with the switch listed in
table 12.
TABLE 12
Unit Model
G24M-45NO CHANGE
G24M-60NO CHANGE
G24M-7588J8001
G24M-10018L2401
G24M-12018L2401
G24M-140-7NO CHANGE
Pressure Switch
Part Number
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment ves
tibule panel. Two secondary limits are located in the blower
compartment, behind the blower. These limits are factory-set
and require no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located just above the
burner box. If tripped, a check for adequate combustion air
should be made before resetting.
Combustion Air Pressure Switch
The combustion air pressure switch is located on the heat
ing compartment vestibule panel. This switch checks for
proper combustion air blower operation before allowing
ignition trial. The switch is factory-set and requires no ad
justment.
Fan Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the Surelight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 25.
Page 25
Page 26
FANOFF TIME ADJUSTMENT
60sec.90sec.120sec.180sec.
To adjust fan-off timing, flip dip switch to desired setting.
FIGURE 25
Temperature Rise
Check the temperature rise and, if necessary, adjust the
blower speed to maintain the temperature rise within the
range shown on the unit rating plate.
Thermostat Heat Anticipation
Set the thermostat heat anticipation:
0.50 ampsWhite Rodgers gas valves
0.70 ampsHoneywell gas valves
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating).
3 - Check ampdraw on the blower motor.
Motor Nameplate__________Actual__________
Flue And Chimney
1 - Check flue pipe, chimney and all connections for tight
ness and to make sure there is no blockage.
2 - Check unit for proper draft.
3 - Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and out
let for blockages.
4 - Reset manual flame rollout switches on burner box
cover.
Burner Flame Adjustment
The G24M burner flame is not adjustable; however, the
flame should be inspected at the beginning of each heating
season. If necessary, clean the burners. The burner flame
should be blue when burning natural gas, and blue/yellow
when burning propane gas. See figure 26.
Burner Flame
FLAME APPEARS BLUE IF
BURNING NAT. GAS; BLUE/
YELLOW FOR PROPANE.
FLAME
HEAT
EXCHANGER
TUBE
Blower Speeds
NOTE - CFM readings are taken external to unit with a dry
evaporator coil and without accessories.
1 - Turn off electrical power to furnace.
2 - Remove unit access panel.
3 - Disconnect existing speed tap at control board speed
terminal.
NOTE - TERMINATION OF ANY UNUSED MOTOR
LEADS MUST BE INSULATED.
4 - Refer to blower speed selection chart on unit wiring dia
gram for desired heating or cooling speed.
5 - Connect selected speed tap at control board speed
terminal.
6 - Resecure unit access panel.
7 - Turn on electrical power to furnace.
Electronic Ignition
The SureLight integrated control has an added feature of
an internal watchguard control. The feature serves as an au
tomatic reset device for ignition controls lockedout because
the burner has failed to light. This type of nuisance lockout is
usually attributed to low gas line pressure. After one hour of
continuous thermostat demand for heat, the watchguard will
break and remake thermostat demand to the furnace and
automatically reset the control to relight the furnace.
BURNER
VEST
PANEL
FIGURE 26
Turbulator
G24M(X) series units include a ceramic fiber turbulator in
each heat exchanger inlet. The turbulators lower nitrogen
oxide emissions. Prior to unit startup, inspect the turbula
tors for shipping damage. The turbulators are fragile; they
should be removed only if it is necessary to replace them.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat?
2 - Are access panels securely in place?
3 - Is the main disconnect switch closed?
4 - Is there a blown fuse?
5 - Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 - Is gas turned on at the meter?
7 - Is the manual main shutoff valve open?
8 - Is the internal manual shutoff valve open?
9 - Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the unit
for blockages.
Page 26
Page 27
Service
WARNING
5 - Clean the inside of each burner with a bottle brush as
shown in figure 27.
BURNER
Cleaning Burners
Disconnect power before servicing unit.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger
ous operation. Verify proper operation after servicing.
At the beginning of each heating season, service items A
through E as described below:
A - Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating).
3 - Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
B - Blowers
Check the blower wheels for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
C - Filters
All G24M filters are installed external to the unit. Filters
should be inspected monthly. Clean or replace the filters
when necessary to ensure proper furnace operation. See
table 13 for filter sizes. Replacement filters for
G24M-45/60/75 units must have a minimum velocity rating
of 400 FPM. Replacement filters for G24M-100/120/140
units require a minimum velocity rating of 625 FPM.
TABLE 13
Model NumberFilter Size - inches (mm)
G24M-45/60/7516 X 20 X 1 (406 X 508 X 25)
G24M-100/120/14020 X 20 X 1 (508 X 508 X 25)
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
D - Flue And Chimney
Check the flue pipe, chimney and all connections for tight
ness and to make sure there is no blockage.
E - Burners
Inspect the burners and burner flame at the beginning of
each heating season. If necessary, clean the burners as in
dicated below:
1 - Turn off the electrical and gas supply to the furnace.
2 - Remove the burner box top.
3 - Remove the burner retaining bracket.
4 - Remove the burners.
BOTTLE
BRUSH
FIGURE 27
6 - Replace the burners and the burner retaining bracket.
Make sure the burners are properly seated in the slots
on the tray. The burner orifice must be aligned with the
manifold.
7 - Reinstall the burner box top.
8 - Restore electrical power and gas supply to the furnace.
Follow lighting instructions on the front of the unit.
Check the appearance of the burner flame, burner
pressure, gas flow, and temperature rise. If necessary,
make adjustments. See the other unit adjustments sec
tion.
Heat Exchanger
Periodically inspect the heat exchanger tubes and the flue
box for corrosion and soot deposits. If necessary, clean as
indicated below:
1 - Turn off the electrical and gas supply to the furnace.
2 - Disconnect the wiring to the combustion air fan.
3 - Remove the screws securing the flue box to the furnace.
Clean the flue box with a wire brush (brassbristle brush
recommended), and rags or a shop vacuum cleaner.
4 - Disconnect the gas supply piping and the ignitor and
sensor wires. Remove the burner assembly from the
furnace.
5 - Since the heat exchanger tubes are crimped in several
locations, a thorough cleaning of the entire length of
each tube is not possible. However, remove any soot
deposits which are accessible with a wire brush (brass
bristle brush recommended), and rags or a shop vacuum
cleaner.
6 - Reinstall the flue box using a new gasket.
7 - Reconnect the combustion air fan wiring.
8 - Reinstall the burner box, ignitor and sensor wires and
the gas supply piping.
9 - Carefully check all piping connections (factory and field)
for gas leaks. Use a leak detecting solution or other pre
ferred means.
IMPORTANT
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly af
ter leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
10 Restore electrical power and gas supply. Follow light
ing instructions on front of unit. Check burner flame
and adjust if necessary.
Page 27
Page 28
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the
A.G.A. or C.G.A. rating plate Example: G24M3-75. Refer to page 3 for parts identification.
CABINET PARTSBLOWER PARTSNOx turbulator (60 Hz. X units only)
Front access panelBlower wheelHot Surface Ignitor
Blower access panelMotorFlame rollout switch (two)
Cabinet capBlower housing cut-off plateFlame sensor
Cabinet bottomMotor capacitorPrimary limit
Vent adapterHEATING PARTSSecondary limit (two)ELECTRICAL PARTSHeat exchangerPressure switch
TransformerMain burnersWire harness plug / cap
Control board (Hot Surface Ignition)Main burner orificesFlue box
Door interlock switchGas manifold/Burner box assemblyCombustion air blower
Gas valveGaskets
Low gas pressure switch (propane only)
Ignition Control Board Diagnostic Codes
DIAGNOSTIC CODES
LED #1LED #2
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH
OFF
ALTERNATING
SLOW FLASH
SLOW FLASH
ON
ON
ONOFF
OFFON
FAST FLASH
SLOW FLASH
ALTERNATING
FAST FLASH
NOTE - Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second).
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH
ALTERNATING
SLOW FLASH
SLOW FLASH
SLOW FLASH
FAST FLASH
ALTERNATING
FAST FLASH
ON
OFF
ON
DESCRIPTION
Power on -- Normal operation.
Also signaled during cooling and continuous fan.
Normal operation - signaled when heating demand initiated at
thermostat.
Primary or secondary limit switch open.
Pressure switch open or has opened 5 times during a single call for heat;
OR: Blocked inlet/exhaust vent; OR: Condensate line blocked;
OR: Pressure switch closed prior to activation of combustion air blower.
Watchguard -- burners failed to ignite.
Flame sensed without gas valve energized.
Rollout switch open. OR: 9pin connector improperly attached.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .7 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts;
OR: Broken ignitor; OR: Open ignitor circuit.
Minimum flame sense current = 0.15 microAmps.
Page 28
Page 29
Troubleshooting
HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODEABNORMAL HEATING MODE
COMBUSTION AIR BLOWER ON FOR 1 SECOND.
SIGNAL IMPROPER
GROUND AT LED.
SIGNAL HOLDS
UNTIL UNIT IS
PROPERLY
GROUNDED.
POWER ON
CONTROL SELF-CHECK OKAY?
TURN INDUCER ON FOR 1 SECOND.
IS POLARITY REVERSED?
NO
NO
IS THERE
PROPER GROUND?
ROLLOUT SWITCH CLOSED?
YES
BURNER OFF?
(CONTINUOUS FLAME CHECK)
YES
NORMAL OPERATION:
LED #1 -- SLOW FLASH
LED #2 -- SLOW FLASH
YES
NO
YE
S
IS VOLTAGE
ABOVE 75 VOLTS?
NO
NO
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
(RESET CONTROL BY TURNING MAIN POWER OFF.)
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR BLOWER ON.
INDOOR BLOWER DELAY OFF.
NO
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
INDOOR BLOWER OFF WITH DELAY.
LED #1 -- ON. LED #2 -- SLOW FLASH.
INDOOR BLOWER ON HEATING SPEED.
LED #1 ON
LED #2 ON
POLARITY REVERSED.
LED #1 -- FAST FLASH
LED #2 -- SLOW FLASH
LOW VOLTAGE SIGNAL AT LED HOLDS
LED #1 -- SLOW FLASH
LED #2 -- OFF
THERMOSTAT CALLS FOR HEAT:
LED #1 -- FAST FLASH
LED #2 -- FAST FLASH
YES
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
YES
IS COMBUSTION AIR BLOWER ENERGIZED?
(HTG. ACC. ENERGIZED WITH CAB.)
YES
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
YES
15SECOND COMBUSTION AIR BLOWER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
CONTINUED NEXT PAGE
NO
NO
PRESSURE SWITCH WATCHGUARD MODE.
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
LED #1 -- OFF. LED #2 -- SLOW FLASH.
IS 5MINUTE RESET PERIOD COMPLETE?
COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH DELAY.
(Sequence holds until pressure switch
closes or thermostat resets control.)
INDOOR BLOWER OFF WITH DELAY.
GAS VALVE OFF.
LED #1 OFF
LED #2 SLOW FLASH
Page 29
Page 30
Troubleshooting
NORMAL HEATING MODEABNORMAL HEATING MODE
15SECOND COMBUSTION AIR BLOWER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARMUP -- 20 SECONDS.
YES
4SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITOR ENERGIZED FOR
1 SECOND AFTER VALVE OPENS.
NO FLAME SENSED DURING THIS PERIOD.
YES
FLAME STABILIZATION PERIOD.
4 SECONDS
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(0.15 microamps)
HEATING SEQUENCE CONTINUED
GAS VALVE OFF. COMBUSTION AIR BLOWER ON.
NO
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
IGNITION WATCHGUARD MODE. GAS VALVE OFF.
LED #1-- ALT. SLOW FLASH, LED #2 -- ALT. SLOW FLASH.