G24M series units are mid−efficiency gas furnaces manufactured with tubular steel heat exchangers formed of aluminized steel. G24M units are available in heating capacities of
45,000 to 140,000 Btuh and cooling applications up to 5
tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is
available for conversion to LPG operation. Early model G24M
units use electronic (direct spark) ignition. Late model G24M
model units feature the Lennox SureLight silicon−nitride
ignition system. The G24MX unit meets the California Nitrogen Oxides (NO
ciency requirements. All units use a redundant gas valve to
assure safety shut−off as required by A.G.A. or C.G.A.
Units may be installed in upflow, downflow or horizontal position. The heat exchanger is designed for upright or horizontal use only. When the unit is installed in the downflow position, the heat exchanger is field removed and reinstalled so it
is upright when the cabinet is inverted. No field conversion is
required when the unit is installed in the horizontal position.
The heat exchanger, burners and manifold assembly can
easily be removed for inspection and service by simply disconnecting gas, unplugging wiring harness and spark wires
and removing four screws holding the heat exchanger in
place. Then the heat exchanger slides out of the cabinet.
LPG/propane kitLB-69845L (38K84)
Twinning Kit96J69 5 lbs. (2 kg)
Up−Flow/Horizontal Filter and Filter Rack Kits
No. & sizeoffilters− in. (mm)
Down-flow Combustible Floor Base
Sidewall Power Venting Kit79J15 25 lbs. (11 kg)
Hanging Bracket Kit
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Polyurethane frame type filter is furnished with kit.
Filters are not furnished with kit and must be ordered extra.
diameter x width
Nominal coolin
that can be added
Down-flow
Filter Kit
) Standards and California Seasonal Effi-
x
Model No.G24M2(X)-45G24M2-60G24M3(X)-60G24M2-75G24M3(X)-75
in.9 x 710 x 79 x 710 x 7
mm229 x 178254 x 178229 x 178254 x 178
Tons1, 1-1/2 or 22, 2-1/2 or 31, 1-1/2 or 22, 2-1/2 or 3
kW3.5, 5.3 or 7.07.0, 8.8 or 10.63.5, 5.3 or7.07.0, 8.8 or 10.6
Optional Accessories (Must Be Ordered Extra)
Catalog No.
No. & Size of Filters in. (mm)
Revised 07−2001
All specifications in this manual are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommended only and do not constitute
code.
kW7.0, 8.8, 10.6, 12.3 or 14.112.3, 14.1, 17.6 or 21.1
Optional Accessories (Must Be Ordered Extra)
Single (32J02) Ten Pack (66K64)
(1) 16 x 20 x 1 (406 x 508 x 25)
(2) 16 x 20 x 1 (406 x 508 x 25)
Single (46J14) Ten Pack (66K65)
(1) 20 x 20 x 1 (508 x 508 x 25)
Sidewall Power Venting Kit79J15 25 lbs. (11 kg)
Hanging Bracket KitLB-69957 (46J66) 15 lbs. (8 kg)
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Polyurethane frame type filter is furnished with kit.
Filters are not furnished with kit and must be ordered extra.
Page 2
Page 3
SPECIFICATIONS
Blower wheel nominal
g
Nominal cooling
No. & Size
External Static
Model No.
Input Btuh (kW)
Output Btuh (kW)
A.F.U.E.
California Seasonal Efficiency
Flue size connection diameter in. (mm) round
Temperature rise range F (C)
High static certified by A.G.A./C.G.A. in wg. (Pa)
Gas Piping Size I.P.S. Natural or LPG/propane − in (mm)
Blower wheel nominal
diameter x width
Blower motor output hp (W)
Nominal coolin
that can be added
Shipping weight lbs. (kg) 1 package
Electrical characteristics
LPG/propane kit
Twinning Kit
Up−Flow/Horizontal Filter and Filter Rack Kits
No. and sizeoffilters − in. (mm)
Catalog No.
Down-flow
Filter Rack
Down-flow Combustible Floor Base
Sidewall Power Venting Kit
Hanging Bracket Kit
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Polyurethane frame type filter is furnished with kit.
2 in. x 5 in. (51 mm x127 mm) flue adaptor furnished with -140 input furnaces for connection to furnace induced draft blower.
Filters are not furnished with kit and must be ordered extra.
No. & Size
of Filters
in.
mm
Tons2, 2-1/2, 3, 3-1/2 or 4
kW7.0, 8.8, 10.6, 12.3 or 14.1
Optional Accessories (Must Be Ordered Extra)
in.
mm
G24M3/4-120G24M4/5(X)-120
120,000 (35.2)
98,400 (28.8)
80.0%80.1%
Not Available75.5%
4 (102)5 (127)
45 - 75 (25 - 42)
.50 (125).65 (162)
1/2 (13)
12 x 812 x 9
305 x 203305 x 229
1/2 (373)3/4 (560)
3-1/2, 4, 5 or 6
12.3, 14.1, 17.6 or 21.1
175 (79)
120 volts 60 hertz 1 phase (less than 12 amps) All models
LB-69845K (81J14)
96J69 5 lbs. (2 kg)
Single (46J14) Ten Pack (66K65)
(1) 20 x 20 x 1 (508 x 508 x 25)
LB-69843A (32J01) 3 lbs. (1 kg)
(2) 16 x 20 x 1
(2) 406 x 508 x 25
LB-79239B (67J92) 10 lbs. (4 kg)
79J15 25 lbs. (11 kg)
LB-69957 (46J66) 15 lbs. (8 kg)
Single (58J93) Ten Pack (66K66)
(1) 20 x 20 x 1 (508 x 508 x 25)
G24M4/5-140
140,000 (41.0)
114,800 (33.6)
80.0%
Not Available
190 (86)
LB-79239C (67J93)
12 lbs. (5 kg)
BLOWER DATA
G24M2-45, G24M2-60 AND G24M2-75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/scfmL/s
001270600980460770365570270
.05121245590975460770365565265
.10251220575975460770365565265
.15371195565965455765360560265
.20501170550960455760360560265
.25621140540950450760360555260
.30751110525940445760360550260
.401001060500910430750355545255
.50125990465880415740350540255
.60150900425810380690325530250
.70175800380740350630295520245
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
HighMedium-HighMedium-LowLow
Air Volume at Various Blower Speeds
Page 3
Page 4
BLOWER DATA
External Static
External Static
G24M3-60 AND G24M3-75 BLOWER PERFORMANCE
Air Volume at Various Blower Speeds
Pressure
in. w.g.PacfmL/scfmL/scfmL/scfmL/s
00142567012405851000470800380
.051214156701230580995470800380
.102514006601220575990465795375
.153713856551200565985465795375
.205013706451180555980460790375
.256213506351160545970460780370
.307513306301140540955450770365
.4010012806051095515925435750355
.5012512105701040490900425720340
.601501135535985465860405680320
.701751070505920435800380630300
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
HighMedium-HighMedium-LowLow
G24M4-75, G24M3/4-100 AND G24M3/4-120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/scfmL/scfmL/s
001830865160075513256251070505880415
.05121815855158575013206251070505880415
.10251800850157074013156201070505880415
.15371875885155073013106201065505875415
.20501750825153072013006151060500875415
.25621725815151571512906101050495870410
.30751700800150071012756001040490870410
.401001650780146069012455901020480860405
.501251600755142067012105701000470840395
.60150155073013806501170550980460820385
.70175148070013306301130535960455790375
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
HighMedium-HighMediumMedium-LowLow
Air Volume at Various Blower Speeds
Page 4
Page 5
BLOWER DATA
External Static
G24M4/5-100, G24M4/5-120 AND G24M4/5-140 BLOWER PERFORMANCE
External Static
Pressure
in. w.g.PacfmL/scfmL/scfmL/scfmL/scfmL/s
002450115521601020197093017008001500710
.05122440115021551015196592516958001500710
.10252430114521501015196092516908001495705
.15372415114021351010195092016857951495705
.20502400113521201000194091516807951490705
.2562238011252105995193091016757901480700
.3075236011152090985191590516707901470695
.40100231010902050965187088016507801440680
.50125226010652000945181085516107601410665
.60150218010301950920175082515607351370645
.7017521009901890890170080015207151330630
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
HighMedium-HighMediumMedium-LowLow
Air Volume at Various Blower Speeds
FILTER AIR RESISTANCE
cfm (L/s)in. w.g. (Pa)
0 (0)0.00 (0)
200 (95)0.01 (2)
400 (185)0.03 (7)
600 (280)0.04 (10)
800 (375)0.06 (15)
1000 (470)0.09 (22)
1200 (560)0.12 (30)
1400 (655)0.15 (37)
1600 (750)0.19 (47)
1800 (845)0.23 (57)
2000 (935)0.27 (67)
2200 (1030)0.33 (82)
2400 (1125)0.38 (95)
2600 (1220)0.44 (110)
Page 5
Page 6
G24M
PARTS IDENTIFICATION
COMBUSTION AIR
INDUCER
FRONT LOUVERED
PANEL
TRANSFORMER
HEAT EXCHANGER
FLUE BOX
PRESSURE
SWITCH
PRIMARY
LIMIT
LOW PRESSURE SWITCH
(Propane Only)
BURNER
ASSEMBLY
VENT ADAPTER
ASSEMBLY
NOx
TURBULATOR
SECONDARY
LIMITS
CABINET TOP
G24M
CABINET
CABINET
BOTTOM
ROLLOUT SWITCH (2)
COMBUSTION AIR
PROVE SWITCH
ORIFICES
MANIFOLD
BURNERS
CONTROL
BOARD
DOOR INTERLOCK SWITCH
BLOWER ASSEMBLY
FIGURE 1
HEATING COMPONENTS (shown in horizontal position)
PRIMARY LIMIT
Bottom
Front
Left
Back
To p
GAS VALVE
COLLECTOR
FIGURE 2
Page 6
Right
HEAT EXCHANGER
COMBUSTION AIR INDUCER
Page 7
(shown in upflow position with SureLight ignition system)
G24M BURNER ASSEMBLY
BURNER BOX
TOP
UPPER
BURNER
MOUNTING
RAIL
LOWER
BURNER
MOUNTING
RAIL
FLAME
SENSOR
ORIFICE
MANIFOLD
SURELIGHT
IGNITOR
ROLLOUT
SWITCHES
BURNER
VEST PANEL
GAS VALVE
BURNER BOX
PRIMARY LIMIT
Left
Front
HEAT EXCHANGER
To p
Back
Right
Bottom
FIGURE 3
G24M BLOWER DOOR COMPONENTS − BLOWER ACCESS
To Access Blower:
4
J135/
P135
J1/P1
1− Turn off power to unit and disconnect L1 and
L2 line voltage power.
2− Disconnect thermostat wiring connections
from furnace control board.
3− Remove screws (2) from blower panel.
4− Disconnect J135 from P135 from limit
control.
5− Disconnect J43 from blower motor.
6− Remove blower panel and lift from unit.
5
To p
Back
Right
6
2
Left
Front
Bottom
3
1
FIGURE 4
Page 7
Page 8
I−UNIT COMPONENTS (Figures 1, 2, 3)
G24M unit components are shown in figure 1. The blower
controls, gas valve and burners can be accessed by removing the front access panel. A separate blower access
door is located behind the front access panel. Electrical
control components are mounted to the blower access
door.
G24M units are factory equipped with bottom return air panels
in place. The panels are designed to be field removed as required for bottom air return. Indentations on side of units,
show where side return opening should be cut during installation.
A−Blower Door Components (Figure 4)
Electrical burner control and blower control components
are located on the outside surface of the blower access
door. Jackplugs allow the blower door to be easily removed for blower service.
Located on the blower door are the unit transformer (T1),
the furnace control (A3) and door interlock switch (S51).
Furnace control (A3) combines the function of a burner
ignition control and blower control.
1− Control Transformer (T1)
A transformer located on the blower door provides power
to the low voltage section of the unit. Transformers on all
models are rated 30VA with a 120V primary and a 24V secondary.
2−Door Interlock Switch (S51)
A door interlock switch rated 16A at 125VAC is located on
the blower access door. The switch is wired in series with
line voltage. When the blower door is removed the unit will
shut down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
3− SureLight Ignition System (A3)
Late Model G24M Units
Late model G24M units are equipped with the Lennox
SureLight ignition system. The system consists of ignitor
(figure 5) and ignition control board (figure 6 with control
terminal designations in table 1). The board and ignitor
work in combination to ensure furnace ignition and ignitor
durability. The SureLight integrated board controls all
major furnace operations. The board also features two
LED lights for troubleshooting and two accessory terminals rated at (4) four amps. See table 2 for troubleshooting diagnostic codes. Table 3 and 4 show jack plug terminal designations. Units equipped with the SureLight
board can be used with either electronic or electro−mechanical thermostats without modification. The SureLight
ignitor is made of durable silicon−nitride. Ignitor longevity
is also enhanced by voltage ramping by the control board.
The board finds the lowest ignitor temperature which will
successfully light the burner, thus increasing the life of the
ignitor.
a−flame sensor
The flame sensor uses flame rectification to sense combustion. During operation, flame is sensed by current
passed through the flame and sensing electrode. Figure 7
shows the gap between tip of the electrode and the burner
surface.
SURELIGHT IGNITOR
UPPER BURNER
MOUNTING RAIL
SURELIGHT IGNITOR BURNER ASSEMBLY
FLAME RETENTION RING
FIGURE 5
Page 8
ORIFICE
FLAME SENSOR
Page 9
SURELIGHT CONTROL BOARD
LATE MODEL G24M UNITS
TABLE 1
SURELIGHT CONTROL TERMINAL DESIGNATIONS
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VAC HOT
24VAC RTN
FLAME SENSE
Blower − Cooling Speed (Line Volt)
Blower − Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VAC Hot to Transformer
120VAC Hot Input
Heat Only Accessory (Line Volt)
120VAC Neutrals
24VAC Hot from Transformer
24VAC Return from Transformer
Flame Sense Terminal
NORMAL FLAME SIGNAL > 0.7 MICROAMPS
LOW FLAME SIGNAL <
MINIMUM FLAME SIGNAL <
FLAME SENSOR TO BURNER GAP
1/4 in. 7 mm
1/32 in. 0.79
BURNER
SIDE VIEWEND VIEW
FIGURE 6
TABLE 2
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1LED #2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASHON
OFFSLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASHOFF
ONSLOW FLASH
ON
ON
OFF
FAST FLASHSLOW FLASH
SLOW FLASHFAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continues fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Units with board 63K8901 or 24L85: Limit must
close within 5 trials for ignition or board goes into one hour limit Watchguard.
Units with board 56L83 or 97L48: Limit must close within 3 minutes or board
Pressure switch open or has opened 5 times during a single call for heat; OR:
Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .7 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
goes into one hour limit Watchguard.
Watchguard − burners fail to ignite.
Open ignitor circuit.
mm
3/16 in.
4.7 mm
FLAME
SENSOR
FIGURE 7
0.7 MICROAMPS
0.15 MICROAMPS
11/16 in. 18 mm
1/32 in. 0.79
mm
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.15 microAmps
Page 9
Page 10
TABLE 3
SureLight BOARD J156 (J2) TERMINAL
DESIGNATIONS
PIN #FUNCTION
1Ignitor
2
3
4
Combustion Air Blower Line Voltage
5
6
Combustion Air Blower Neutral
Not Used
Ignitor Neutral
Not Used
TABLE 4
SureLight BOARD J58 (J1) TERMINAL
DESIGNATIONS
PIN #FUNCTION
1Primary Limit In
2
3
4
5
6
Pressure Switch and Primary Limit Out
7
8
9
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Not Used
Roll Out Switch In
Ground
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s
electronic controls. Precautions will help to
avoid control exposure to electrostatic discharge by putting the furnace, the control and
the technician at the same electrostatic potential. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface,
such as the gas valve or blower deck, before performing any service procedure.
not proven within 2−1/2 minutes, the control goes into
Watchguard−Pressure Switch mode for a 5−minute re−set
period.
NOTE − The G24M furnace contains electronic components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
After the 15−second pre−purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve
opens for a 4−second trial for ignition. The ignitor stays energized for the first second of the 4−second trial. G24M
units with 63K89, 24L85 or 56L83: the ignitor stays energized the first second of the 4 second trial. G24M units with
board 97L48: ignitor stays energized during the 4−second
trial until flame is sensed. If ignition is not proved during the
4−second period, the control will try four more times with an
inter purge and warm−up time between trials of 35 seconds. After a total of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure
mode. After a 60−minute reset period, the control will begin
the ignition sequence again.
The SureLight control board has an added feature that
prolongs the life of the ignitor. After a successful ignition,
the SureLight control utilizes less power to energize the ignitor on successive calls for heat. The control continues to
ramp down the voltage to the ignitor until it finds the lowest
amount of power that will provide a successful ignition.
This amount of power is used for 255 cycles. On the 256th
call for heat, the control will again ramp down until the lowest power is determined and the cycle begins again.
c−Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 8.
NOTEIf fan off" time is set too low, residual heat in
heat exchanger may cause primary limit S10 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
b−Electronic Ignition
On a call for heat the SureLight control monitors the combustion air inducer prove switch. The control will not begin
the heating cycle if the prove switch is closed (by−passed).
Once the prove switch is determined to be open, the combustion air inducer is energized. When the differential in
the prove switch is great enough, the prove switch closes
and a 15−second pre−purge begins. If the prove switch is
FAN-OFF TIME ADJUSTMENT
60sec.90sec.120sec.180sec.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 8
Page 10
Page 11
4− Ram Control (A3)
Early Model G24M Units
The furnace control combines burner ignition functions
with blower control functions.
Early model G24M units utilize a furnace control manufactured by RAM Electronics Corporation. The RAM" board is a
printed circuit board which controls the blower, gas valve,
combustion air blower and ignition spark. It also monitors the
flame, limit and gas valve operation. The control has a non−
adjustable, factory preset on" fan timing (45 seconds). Fan
off" timings are adjustable. The board utilizes both 120 and
24VAC. See figure 9. The board is also equipped with a
diagnostic LED for use when troubleshooting the unit.
When the furnace is idle (blower off and no heating or cooling demand), the diagnostic LED flashes at a slow steady
rate. On a call for heat, the diagnostic LED begins flashing
at a fast rate and the combustion air blower is energized.
The LED flashes different codes to indicate problem conditions. The diagnostic LED lights red (not flashing) to indicate control board failure. Table 7 shows how to interpret the
other LED modes.
Pre-Purge
On a call for heat, the combustion air blower begins operating. If the combustion air prove switch closes, the combustion air blower continues to operate for 45 seconds
(pre-purge) before allowing ignition. Pre-purge allows the
heat exchanger to be cleared of combustion products and
to introduce fresh air for combustion. If the combustion air
prove switch does not close, the combustion air blower
continues to run indefinitely (until the prove switch closes).
Post-Purge
After a demand, the combustion air blower continues to
operate for 5 seconds (post-purge) before stopping. Postpurge allows the heat exchanger to be cleared of combustion products.
Ignition Control
The ignition control is a direct spark ignition control module
integral to the furnace control. See figure 9. When there is a
call for heat, the control delays ignition until combustion air
blower operation has been proved and pre-purge period
has elapsed. It then opens the gas valve and generates a
spark to ignite the burners. Trial for ignition lasts for 7 seconds. At the same time, the control begins monitoring the
flame sensor. If the flame current is too weak (less than 1
microamp) or if the burners do not ignite (within the 7 second ignition trial), the control will shut off the spark ignitor
and the combustion air blower and de-energize the gas
valve. Flame current should be between 1 and 5 microamps to keep the gas valve open. See figure 21.
The control will attempt to ignite the burners up to two more
times. Each time the control restarts the ignition sequence,
it begins with a 45 second pre-purge. If flame is not sensed
after the third trial, the control locks out. Lockout means that
the control shuts off the gas valve, spark and combustion air
blower for 60 minutes. At the end of 60 minutes the control
completely resets and will attempt ignition up to three times.
The control can be manually reset before the end of 60 minutes by momentarily turning off power to the unit.
DANGER
Shock hazard.
Spark related components contain high voltage.
Disconnect power before servicing. Control is
not field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
Page 11
Page 12
SPARK OUTPUT
LINE VOLTAGE
TERMINAL
CONNECTIONS
EARLY MODEL G24M FURNACE CONTROL (A3)
24VAC VOLT
TERMINAL
CONNECTIONS
See Table 6 for
Terminal Func-
tions
DIAGNOSTIC
LED
TABLE 5
Furnace Control A3 Limit Response During Operation
Response
Condition
Loss of Flame
Sensed Before
End of 45 second Blower On
Delay
(3 or Fewer
Trials
for Ignition)
Loss of Flame
Sensed After
45 second
Blower On
Delay (3 or
Fewer Trials
for Ignition)
Loss of Flame
Sensed (More
Than 3 Trials
for Ignition)
Flame Sensed
Without
Demand
Primary or Sec-
ondary Limit
Open
Rollout Switch
Open
Combustion Air
Prove Switch
Open
Combustion
Air
Blower
On
On
OffOffOff2 Flashes
OnOffOn5 Flashes
OnOffOn4 Flashes
OnOffOn4 Flashes
OnOffOn3 Flashes
Gas
Valve
On
(Spark
Starts
Within 0.8
seconds)
Off Then
On With
Spark
After Pre-
Purge
Supply
Air
Blower
OnFast Flash
OnFast Flash
Diagnostic
LED
PLUG
P20
FAN-OFF TIMING
SWITCHES
THERMOSTAT
CONNECTIONS
FIGURE 9
When flame is sensed, the indoor blower starts after a 45
second delay. Gas valve remains open and blower continues to run until demand stops, flame sensor senses loss of
flame, a limit opens or the prove switch opens. If any of
these events occur during a thermostat demand, the gas
valve closes and the diagnostic LED registers the error
condition (table 5).
Blower Control and Timings
DANGER
Electrical Shock Hazard.
This control contains field adjustable switches
and also contains line voltage. Make sure power
is disconnected before making any field adjustments or performing any service procedure.
NOTEIf fan off" time is set too low, residual heat in
heat exchanger may cause primary limit S10 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
Fan ON" timing (time that the burners operate before the
supply air blower starts) is fixed at 45 seconds and cannot
be adjusted.
Fan OFF" timings (time that the blower operates after a
heating or cooling demand has been satisfied) are determined by the arrangement of switches on the furnace control board. See figure 9. To adjust fan off " timings, gently
reposition the switches to a new timing position. Figure 10
Page 12
Page 13
shows the various fan off" timings and how switches should
be positioned. Unit is shipped with a factory fan off" setting of
180 seconds. Fan off" time will affect comfort and efficiency
and is adjustable to satisfy individual applications. The fan
off" timing is initiated after a heating or cooling demand but
not after a blower demand (that is, when indoor thermostat
switch is changed from ON to AUTO and heating/cooling demand is not present, the blower stops immediately).
TABLE 6
FURNACE CONTROL A3 TERMINAL DESIGNATIONS
TerminalTypeFunction
24VAC HOT1/4" Spade24VAC In From Transformer
GND1/4" SpadeTo Cabinet Ground
YScrew StripCooling Demand
GScrew StripBlower Demand
RScrew Strip24VAC to Thermostat
WScrew StripHeating Demand
CScrew Strip24VAC Common
120VAC HOT1/4" SpadeLine Voltage In
120VAC RTN1/4" SpadeLine Voltage Neutral
120VAC TX1/4" SpadeLine Voltage Out To Transformer
CMBJ20/P20 Pin 1
CMB RTNJ20/P20 Pin 2
ACB HEAT1/4" Spade
ACB LOW1/4" Spade
ACB COOL1/4" Spade
VLV HOTJ20/P20 Pin 1324VAC to Gas Valve
VLV RTNJ20/P20 Pin 9
PSW IN
HIL IN
HIL OUT
RO OUTJ20/P20 Pin 724VAC Out To Rollout Switches
RO INJ20/P20 Pin 1524VAC In From Rollout Switches
SPARK
ELECTRODE
FSJ20/P20 Pin 12Flame Microamp Sensing
J20/P20
Pin 10
J20/P20
Pin 11
J20/P20
Pin 14
Male Spark
Plug Type
FAN-OFF TIME ADJUSTMENT SWITCHES
LOCATED ON FURNACE CONTROL (A3)
Switched 120VAC to
Combustion Air Blower
120VAC Common
Combustion Air Blower
Switched 120VAC to
Blower Heating Tap
120VAC Output to Supply Air
Blower for Continuous Operation
During No Demand
Switched 120VAC to Blower
Cooling Tap
24VAC Common From
Gas Valve
24VAC In From Pressure Switch
Switch Open: Prohibits Ignition
Switch Closed: Allows Ignition
24VAC In From Limits
Limit Open: Closes Gas Valve
Limits Closed: Allows Ignition
24VAC to Limit Train
and Pressure Switch
High Voltage Out To
Spark Electrode
Fan-Off Timings
Switch
12
Off
OnOn
Off
OnOff
OffOn
Timing
Seconds
90
120
180
240
FIGURE 10
Diagnostic LED
The furnace control is equipped with a diagnostic LED
used for troubleshooting the unit and the control. LED
functions are shown in table 7.
TABLE 7
Furnace Control A3 Diagnostic LED
LED StateMeaningRemedy
Steady OnControl FailureReplace Control
Slow Flash
Fast Flash
Two
Flashes
Three
Flashes
Four
Flashes
Five
Flashes
Normal Operation and
No Call For Heat
Normal Operation with
Call For Heat
Control Lockout
Pressure Switch Open
Open Limit
Flame Sensed and Gas
Valve Not Energized.
- - - -
- - - -
Failed to Sense or Sustain
Flame. Check Gas Valve,
Burners, Spark Electrode
and Wire, Flame Sensor.
Replace Control If All OK.
Failed to Prove Combus-
tion Blower Operation or
Blocked Vent. Repair or
Replace as Necessary.
Check Primary Limit, Rol-
lout Switches and Secondary Limits. Find source of
Overtemperature. If all OK,
Reset or Replace Limits as
Necessary.
Check Gas Valve. If OK,
Check Flame Sensor.
B−Blower Motors and Capacitors
All G24M units use direct drive blower motors. All motors
used are 120V permanent split capacitor motors to ensure
maximum efficiency. See table8 for ratings.
All G24M units use a combustion air inducer to move air
through the burners and heat exchanger during heating
operation. Some early model G24M units are equipped
with a blower that uses a PSC (Permanent Split Capacitor)
120VAC motor. PSC motors use run capacitors. Other early and late model G24M units are equipped with a blower
that uses a shaded pole 120V motor. The motor operates
during all heating operation and is controlled by furnace
control A3. For G24M units equipped with the Ram ignition
system, the blower will operate for 45 seconds before
burner ignition (pre-purge) and for 5 seconds after the gas
valve closes (post-purge). For G24M units equipped with
the SureLight ignition system, the blower will operate for
15 seconds before burner ignition (pre purge) and for 5
seconds after the the gas valve closes (post purge).
A pressure switch connected to the combustion air blower
housing is used to prove combustion air blower operation.
The switch monitors air pressure in the blower housing. During normal operation, the pressure in the housing is negative. If pressure becomes less negative (signifying an obstruction) the pressure switch opens. When the pressure
switch opens, the furnace control (A3) immediately closes
the gas valve to prevent burner operation.
D−Flame Rollout Switches (S47)
Flame rollout switch is a high temperature limit located on
top of the burner box. Each furnace is equipped with two
identical switches. One switch is located over the leftmost
burner and the other switch is located over the rightmost
burner. The limit is a N.C. SPST manual-reset limit connected in series with the ignition control A3. When S47
senses rollout, the ignition control immediately stops ignition and closes the gas valve. If unit is running and flame
rollout is detected, the gas valve will close and ignition
control will be disabled. Rollout can be caused by a
blocked flue or lack of combustion air. The switch is factory set and cannot be adjusted. The setpoint will be printed
on the side of the limit. The switch can be manually reset.
To manually reset a tripped switch, push the reset button
located on the control.
ROLLOUT SWITCH (S47)
E−Primary Limit Control (S10)
LIMIT CONTROL FOR
G24M SERIES UNITS
THIS TYPE AUTO-RESET LIMIT
IS USED FOR THE PRIMARY LIMIT (S10) AND
RIGHT SECONDARY LIMIT (S21)
(see FIGURE 11)
FIGURE 13
The primary limit (S10) on G24M units is located in the middle
of the heating vestibule panel. When excess heat is sensed in
the heat exchanger, the limit will open. If the limit is tripped, the
furnace control energizes the supply air blower and closes the
gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot
be adjusted. The switch may have different setpoints for
each unit model number. However, the setpoint will be
printed on the side of the limit.
F−Secondary Limit Controls (S21)
The secondary limit (S21) on G24M units is located in the
blower compartment in the back side of the blower housing.
When excess heat is sensed in the blower compartment, the
limit will open. If the limit is tripped, the furnace control energizes the supply air blower and closes the gas valve. The limit
automatically resets when unit temperature returns to normal.
The switch is factory set and cannot be adjusted. Two limits
are supplied in each furnace and each limit is a different
style (figures 13 and 14). The setpoint will be printed on the
side of the limit. If stick limit (figure 14) suffers from nuisance
trips and the furnace is in the horizontal position, replace
with limit kit no. 50L98.
SECONDARY LIMIT CONTROL
(S21)
INSULATING COVER
LIMIT
FOR G24M SERIES UNITS
SPADE CONNECTORS
THIS TYPE AUTO-RESET LIMIT IS
USED FOR THE LEFT SECONDARY
LIMIT (S21) (see FIGURE 11)
INSULATING COVER (s)
FIGURE 14
LIMIT
FIGURE 12
MANUAL
RESET BUTTON
G−Spark Electrode and Flame Sensor
Early Model G24M Units
Figure 15 shows the arrangement of flame sensor, spark
electrode and burners. The ignition control uses direct
spark to ignite the rightmost burner and the burners crosslight to the left. The flame sensor uses flame rectification to
sense combustion. A flame retention ring in the end of
each burner is used to maintain correct flame length and
shape and to keep the flame from lifting off the burner
head.
Figure 16 shows the gap between tip of the electrodes and
the burner surface.
Page 14
Page 15
1/8"(+1/64")
TYPICAL BURNER/ELECTRODE ORIENTATION
UPPER BURNER
MOUNTING RAIL
view looking at flame end of burners
BURNER
MANIFOLDORIFICE
To p
RightLeft
Bottom
GROUND
SPARK ELECTRODE
FLAME RETENTION RING
FIGURE 15
SPARK ELECTRODE TO BURNER GAP
11/16 in. 18 mm
1/32 in. 0.79
mm
END VIEW
BURNER
SIDE VIEW
1/4 in. 7 mm
1/32 in. 0.79
mm
FLAME
SENSOR
3/16 in.
4.7 mm
FIGURE 16
H−Gas Valve
The G24M uses a gas valve manufactured by Honeywell
(figure 17) or White Rodgers (figure 18). The valve is internally redundant to assure safety shut−off. If the gas valve
must be replaced, the same type valve must be used.
24VAC terminals and gas control knob are located on top of
the valve. All terminals on the gas valve are connected to
wires from the electronic ignition control. 24V applied to the
terminals energizes the valve.
Inlet and outlet pressure taps are located on the valve. A regulator adjustment screw is located on the valve. Refer to figure
17 or 18 for location of valve features.
An LPG changeover kit is available from Lennox. The kit includes burner orifices and a regulator conversion kit.
I−Combustion Air Blower Prove
(Pressure) Switch (S64)
G24M series units are equipped with a combustion air
prove switch located on the vestibule panel. The switch is
connected to the combustion air blower housing by means
of a flexible silicone hose. It monitors air pressure in the
combustion air blower housing.
LOWER BURNER
MOUNTING RAIL
FLAME SENSOR
(SOME UNITS MAY HAVE
SENSOR LOCATED IN
MIDDLE OF BURNER)
TYPICAL ACCESS TO REGULATOR
FOR ADJUSTMENT AND L.P. CHANGEOVER
(Honeywell VR8205 series gas valve shown)
INLET
PRESSURE
TAP
GAS VALVE SHOWN IN OFF POSITION
PRESSURE
REGULATOR
ADJUSTING SCREW
(White)
ON
OFF
CAP SCREW
(Black)
SPRING
Tapered End
Down
(Red)
PRESSURE TAP
GAS INLET
FIGURE 17
WHITE RODGERS
GAS VALVE
KNOB SHOWN
IN OFF POSITION
GAS INLET
PRESSURE
TAP
36E GAS VALVE
REGULATOR
COVER SCREW
PRESSURE
OUTLET
PRESSURE
TAP
INLET
TAP
Page 15
FIGURE 18
Page 16
The switch is a single-pole single-throw pressure switch
electrically connected to the furnace control. The purpose
of the switch is to prevent burner operation if the combustion air blower is not operating.
PROVE SWITCH
COMBUSTION AIR BLOWER
PROVE SWITCH
Normally Open
Closes on Negative Pressure
Sensing Tube
Attaches to Top
Side Of Blower
III−START-UP
A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be
within range listed on the nameplate. If not, consult the
power company and have voltage condition corrected
before starting unit.
B−Heating Start-Up
1 − Set thermostat to OFF position. Close manual knob on
gas valve.
2 − Wait 5 minutes.
3 − Open manual knob on gas valve, replace burner ac-
cess door and turn on unit electrical supply.
To p
PROVE
SWITCH
Back
Left
Right
Front
Bottom
FIGURE 19
On start-up, the switch senses that the combustion air
blower is operating. It closes a circuit to the furnace control
when pressure inside the combustion air blower increases
above switch setting (negative) w.c. The pressure sensed
by the switch is relative to atmospheric pressure. If the flue
becomes obstructed during operation, the switch senses a
loss of negative pressure (pressure becomes more equal
with atmospheric pressure) and opens the circuit to the
furnace control and gas valve. The switch trip pressure is
different depending on unit model number. The trip pressure is printed on the side of the limit.
The switch is factory set and is not field adjustable. It is a
safety shut-down control in the furnace and must not be
bypassed for any reason.
II−PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation
instructions and applicable codes.
WARNING
Shock and burn hazard.
G24M units are equipped with either a direct spark
or hot surface ignition system. Do not attempt to
light manually.
4 − Set fan switch to AUTO or ON and move system selec-
tion switch to HEAT. Adjust thermostat to a setting
above room temperature.
5 − If unit does not light the first time, the SureLight control
will attempt four more ignitions, the Ram control will at-
tempt two more ignitions before locking out.
6 − If lockout occurs, repeat steps 1, 2, 3 and 4.
C−Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
IMPORTANT
In case emergency shutdown is required, turn off
the main shut-off valve and disconnect the main
power to unit. These controls should be properly
labeled by the installer.
D−Extended Period Shutdown
Turn off thermostat or set to UNOCCUPIED" mode. Close
all gas valves (both internal and external to unit) to guarantee no gas leak into combustion chamber. Turn off power
to unit. All access panels, covers and vent caps must be in
place and secured.
Page 16
Page 17
IV−HEATING SYSTEM SERVICE CHECKS
A−A.G.A./C.G.A. Certification
All units are A.G.A. design certified without modifications.
Refer to the G24M Operation and Installation Instruction
Manual for Information.
B−Gas Piping
Gas supply piping should not allow more than 0.5"W.C.
drop in pressure between gas meter and unit. Supply gas
pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be
resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
When pressure testing gas lines, the gas valve must be
disconnected and isolated. Gas valves can be damaged if
subjected to more than 0.5psig (14" W.C.). See figure 20. If
the pressure is equal to or less than 0.5psig (14"W.C.), use
the manual shut−off valve before pressure testing to isolate furnace from gas supply.
pressure can result in permanent damage to gas valve or
overfire. For natural gas units, operating pressure at unit
gas connection must be between 5.0" W.C. and 13.0" W.C.
For L.P. gas units, operating pressure at unit gas connection must be between 10.0" W.C. and 13.0" W.C.
On multiple unit installations, each unit should be checked
separately, with and without other units operating. Supply
pressure must fall within range listed in previous paragraph.
E−Check Manifold Pressure
After line pressure has been checked and adjusted, check
manifold pressure. Move pressure gauge to outlet pressure tap located on unit gas valve (GV1). Checks of manifold pressure are made as verification of proper regulator
adjustment. Manifold pressure for the G24M can be measured at any time the gas valve is open and is supplying gas
to the unit. Normal manifold pressure for natural gas units is
3.5 in. w.c. For LP/propane gas the correct manifold pressure is 9.5 in. w.c.
GAS PIPING TEST PROCEDURE
MANUAL MAIN SHUT−OFF VALVE
WILL NOT HOLD TEST PRESSURE
IN EXCESS OF 0.5 PSIG (14"W.C.)
GAS VALVE
FIELD PROVIDED
LINE PRESSURE
CAP
TAP
FIGURE 20
When checking piping connections for gas leaks, use preferred means. Kitchen detergents can cause harmful corrosion on various metals used in gas piping. Use of a specialty
Gas Leak Detector is strongly recommended. It is available
through Lennox under part number 31B2001. See Corp.
8411−L10, for further details.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
inlet pressure tap (field provided). See figure 20. Check
gas line pressure with unit firing at maximum rate. Low
pressure may result in erratic operation or underfire. High
IMPORTANT
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of
gas pressure to the manometer.
TABLE 9
GAS VALVE REGULATION
Unit (Fuel)
L.P.9.5 +
The gas valve is factory set and should not require adjustment. All gas valves are factory regulated. See table 9.
Manifold Adjustment Procedure:
1 − Connect a test gauge to outlet pressure tap on gas
valve. Start unit and allow 5 minutes for unit to reach
steady state.
2 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue. L.P. gas should burn
mostly blue with some orange streaks.
3 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to values given in
table 9.
NOTE−Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to
replace pressure tap plug.
Operating Pressure (outlet) in. W.C.
3.5 +0 −0.3Natural
0.5
Page 17
Page 18
F− Proper Gas Flow
0 4500
4500 5500
5500 6500
6500 7500
Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures
a more accurate time.) Divide by two and compare to time
in table 10 below. Adjust manifold pressure on gas valve
to match time needed.
NOTE− To obtain accurate reading, shut off all other
gas appliances connected to meter.
TABLE 10
GAS METER CLOCKING CHART
Seconds for One Revolution
G24M
Unit
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
−4580160200400
−6060120150300
−754896120240
−100367290180
−120306075150
−140265264128
Natural−1000 btu/cu ft LP−2500 btu/cu ft
NOTE− To obtain accurate reading, shut off all other
gas appliances connected to meter.
G−High Altitude Derate
NOTE−In Canada, certification for installation at altitudes over 4500 ft. (1372m) above sea level is the jurisdiction of the local authorities.
G24M−1 through −9 Models
This unit does not require gas pressure adjustment, or
pressure switch change when operating at elevations of 0
to 7500 ft. (0 to 2248m). Check gas line pressure with unit
firing. The minimum pressure as shown on the nameplate
for natural and propane gases must be maintained. No orifice change is required.
NOTE−This is the only permissible field derate for this
appliance.
G24M−10 and −11 Models
Table 11 shows manifold pressure settings for installations
at different altitudes. Refer to table 12 for pressure switch
replacement for models at elevations of 4500 feet (1372m)
and greater.
TABLE 11
ALTITUDE
feet (m)
0 − 4500
(0 − 1372)
4500 − 5500
(1372 − 1676)
5500 − 6500
(1676 − 1981)
6500 − 7500
(1372 − 2286)
GAS FUEL
Natural3.5 (0.87)
Propane/LP9.5 (2.36)
Natural3.4 (0.86)
Propane/LP9.2 (2.29)
Natural3.3 (0.82)
Propane/LP8.9 (2.21)
Natural3.2 (0.80)
Propane/LP8.6 (2.14)
MANIFOLD
PRESSURE
in. W.C. (kPa)
TABLE 12
Unit Model
Pressure Switch Part Number
G24M−45No Change
G24M−60No Change
G24M−7588J8001
G24M−10018L2401
G24M−12018L2401
G24M−140No Change
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
H−Flame Signal
A microamp DC meter is needed to check the flame signal
on the primary ignition control.
Flame (microamp) signal is an electrical current which
passes from the furnace control through the sensor electrode during unit operation. Current passes from the sensor through the flame to ground to complete a safety circuit.
To Measure Flame Signal:
1 − Place meter in series between furnace control and
sensor wire. Connect the positive (+) lead of meter to
the ignition control sensor connection and the nega-
tive (−) lead of the meter to the sensor wire. See figure
21.
2 − Set thermostat for a heating demand and check flame
signal with unit operating. For G24M series with a RAM
control, a reading of 1 to 5 microamps DC should occur.
The furnace control must see at least 1.0 microamps in
order to keep the gas valve energized. G24M units with
the SureLight control should read 0.7 microamps or
more.
Page 18
Page 19
FLAME SIGNAL TEST
D.C. MICROAMP
METER
FLAME
SENSOR
IGNITION
CONTROL
SENSOR
WIRE
RAM CONTROL
SHOWN
SENSE"
TERMINAL
FIGURE 21
Flame signal from the Ram control may rise above 5 microamps for the first few seconds after ignition then level off within
the range.
WARNING
Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.
V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat control
system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower
operates continuously on low speed. With fan switch in
AUTO position, blower cycles with demand or runs continuously while heating or cooling circuit cycles.
3 − In all cases, blower and entire unit will be off when the
system switch is in OFF position.
B−Temperature Rise
Temperature rise for G24M units depends on unit input,
blower speed, blower horsepower and static pressure as
marked on the unit rating plate. The blower speed must be
set for unit operation within the range of AIR TEMP. RISE
°F" listed in the unit rating plate.
To Measure Temperature Rise:
1 − Place plenum thermometers in the supply and return
air plenums. Locate supply air thermometer in the first
horizontal run of the plenum where it will not pick up ra-
diant heat from the heat exchanger.
2 − Set thermostat to highest setting.
3 − After plenum thermometers have reached their high-
est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check
the firing rate. Provided the firing rate is acceptable, in-
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.
C−External Static Pressure
1 − Measure tap locations as shown in figure 22.
2 − Punch a 1/4" diameter hole
in supply and return air ple-
nums. Insert manometer
hose flush with inside edge
of hole or insulation. Seal
around the hose with per-
magum. Connect the zero
end of the manometer to the
discharge (supply) side of the system. On ducted sys-
tems, connect the other end of manometer to the re-
turn duct as above. For systems with non−ducted re-
turns, leave the other end of the manometer open to
the atmosphere.
3 − With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow-
er motor speed to deliver the air desired according to
the job requirements.
4 − External static pressure drop must not be more than
0.5" W.C.
5 − Seal around the hole when the check is complete.
STATIC PRESSURE
TEST
MANOMETER
G24M UNIT
FIGURE 22
Page 19
Page 20
D−Blower Speed Taps Leadless Motors
Blower speed tap selection is accomplished by changing the
taps at the blower motor harness connector. Disconnect harness connector from motor to expose speed selectors.
Blower speed selections are listed in table 13.
To Change Blower Speed:
1 − Turn off electric power to furnace.
2 − Remove front panel and blower access door. See
figure 4.
3 − Disconnect blower motor harness from motor.
4 − Select desired speeds for heating and cooling (refer to
unit wiring diagram).
5 − Depress harness connector tab to release wire termi-
nal. Select connector location for new speed (refer to
unit wiring diagram). Insert wire terminal until it is securely in place. See figure 23.
6 − Replace harness connector to motor.
BLOWER SPEED TAP SELEC-
TION
LEADLESS MOTORS
HARNESS
CONNECTOR
SureLight board. The heating tap is connected to the "ACB
HEAT " terminal and the cooling tap is connected to the
"ACB COOL" terminal. The continuous blower tap is connected to the "ACB LOW" terminal.
To change existing heat tap, turn off power then switch out
speed tap on "ACB HEAT" with tap connected to "PARK
M1" or "PARK M2". See table 14 for blower motor tap colors for each speed.
TABLE 13
TABLE 14
DEPRESS TAB TO RELEASE
WIRE TERMINAL. SELECT
CONNECTOR LOCATION
FOR NEW SPEED (REFER TO
UNIT WIRING DIAGRAM). INSERT WIRE UNTIL IT IS SECURELY IN PLACE.
MOTOR
FIGURE 23
E−Blower Speed Taps Leaded Motors
Blower speed tap changes are made on the SureLight
control board. See figure 6. Unused taps must be secured
on dummy terminals "PARK M1" and or "PARK M2" on the
VI−MAINTENANCE
At the beginning of each heating season, the system
should be checked as follows:
A−Filters
A filter must be used in order to ensure long life and proper
operation. The filter is located in the return air duct or return
air register. Filters must be cleaned or replaced when dirty
to assure proper unit operation.
B−Heat Exchanger and Burners
NOTE−Use papers or protective covering in front of furnace while cleaning furnace.
Due to dimples designed in the heatexchanger, cleaning is
not recommended. Removal is for inspection only.
Page 20
Page 21
To clean burners:
1 − Turn off both electrical and gas power supplies to fur-
nace.
2 − Disconnect gas supply piping and remove gas man-
ifold.
3 −Disconnect ignitor and flame sensor leads.
4 −Remove burner tray and burners.
5 −Clean burner retention ring with wire brush.
6 −Use test tube brush to clean inside of each burner.
7 −Replace burners and burner tray, making sure burners
are properly seated in slots on tray and orifice in manifold.
8 −Reinstall burner box and gas supply piping. Reconnect
ignitor and flame sense leads.
9 − Carefully check all piping connections (factory and
field) for gas leaks. Use a leak detecting solution or other preferred means.
10 − Restore electrical power and gas supply. Follow light-
ing instructions on front of unit.
CAUTION
Potential for gas leaks, fire or explosion.
Some soaps used for leak detection are corrosive
to certain metals. Carefully clean piping thoroughly after leak detection has been completed.
Can cause damage to piping resulting in gas
leaks, fire or explosion.
C−Supply Air Blower
1 − Check and clean blower wheel.
2 − Motors used on the Lennox G24M series units are
permanently lubricated and need no further lu-
brication.
D−Flue and Chimney
Flue must conform to all AGA/GAMA venting requirements. Flue pipe deteriorates from the inside out and must
be disconnected in order to check thoroughly. Check flue
pipe, chimney and all connections for tightness and to
make sure there is no blockage or leaks.
E−Electrical
1 − Check all wiring for loose connections.
2 − Check for correct voltage.
3 − Check amp−draw on blower motor.
HEAT EXCHANGER REMOVAL (unit shown in horizontal position)
FIELD INSTALLED CLASS II 24V
FIELD INSTALLED LINE VOLTAGE
THERMOSTAT
TO COMPRESSOR
CONTACTOR
TYPICAL G24M FIELD WIRING DIAGRAM
COMBUSTION
PRESSURE SWITCH
GWRY
FLAME ROLLOUT SWITCHES
PRIMARY LIMIT
TRANSFORMER
GWYCR
SURELIGHT CONTROL
AIR BLOWER
GAS
VALV E
SECONDARY
LIMITS
DOOR
INTERLOCK
SWITCH
(FURNISHED BY INSTALLER)
BLACK
WHITE
L1 N
GND
FIGURE 25
G24M and CONDENSING UNIT
THERMOSTAT DESIGNATIONS
(Refer to specific thermostat and outdoor unit.)
G24M
Condensing UnitThermostat
Furnace
HS UNIT
Y
COOLING
COMPRESSOR
Y
COMPRESSOR
INDOOR BLOWER
G
G
HEAT
W
W
POWER
R
COMMON
C
R
C
COMMON
HS UNIT
COMMON
FIGURE 26
Page 22
Page 23
B−Early Model G24M Series With Ram Ignition Control
5
6
2
3
1
8
4
1 − When disconnect is closed, 120V is routed through
door interlock switch (S51) to feed the line voltage
side of the furnace control (A3) and transformer T1 primary. Door interlock switch must be closed for A3 and
T1 to receive voltage.
2 − T1 supplies 24VAC to terminal 24VAC" on A3. In turn,
terminal R" of A3 supplies 24VAC to terminal RC" of
the indoor thermostat (not shown).
3 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the furnace control with 24VAC.
4 − CMB BLWR of the blower control energizes the com-
bustion air blower (B6). When the combustion air
blower nears full speed, combustion air prove switch
(S18) closes.
5 − When S18 closes, assuming the flame rollout switch
7
(S47), primary limit (S10) and secondary limits (S21)
are closed, the furnace control begins a 45 second
time-delay (pre-purge).
6 − At the end of the pre-purge cycle, the furnace control
simultaneously opens the gas valve and sends high
voltage to the spark electrode.
7 − When flame is sensed, the furnace control begins a 45
second delay before energizing the indoor blower.
8 − When heat demand is satisfied, W1 of the thermostat
de-energizes W of the furnace control and the furnace
control immediately de-energizes the gas valve. The
combustion air blower runs for 5 seconds (post-purge)
before being de-energized. Also, the indoor blower
runs for a designated period (90−240 seconds) as set
by switches on furnace control.
Page 23
Page 24
C−Ram Ignition Control Troubleshooting Guide
RAM CONTROL
HEATING TROUBLE SHOOTING SEQUENCE
NORMAL HEATING MODEABNORMAL HEATING MODE
LED: SLOW FLASH RATE
THERMOSTAT CALLS FOR HEAT
LED: FAST FLASH RATE
FLAME OFF?
YES
CONTROL SELF−CHECK OKAY?
YES
HI LIMIT SWITCH CLOSED?
YES
PRESSURE SWITCH OPEN?
YES
COMBUSTION AIR BLOWER ON?
PRESSURE SWITCH CLOSED?
YES
PREPURGE (45 seconds)
IGNITION TRIAL (7 seconds) −− START IGNITION
SPARK, OPEN MAIN GAS VALVE. INCREMENT
TRIAL REGISTER. HAS FLAME BEEN
REGISTERED WITHIN 7 SECONDS?
YES
SYSTEM FAN ON.
(Fixed 45−second delay)
NO
NO
NO
NO
NO
NO
LOCKOUT: MAIN VALVE OFF
COMB. AIR AND SYSTEM FANS ON
RESET THERMOSTAT
LED: 5 flash if flame sensed with valve off
LED: Steady on if control board failure
CHECK TO SEE IF MAIN VALVE IS OFF.
SEQUENCE HOLDS UNTIL HI LIMIT CLOSES.
LED: 4 flashes.
CHECK TO SEE IF MAIN VALVE IS OFF.
SEQUENCE HOLDS UNTIL PRES. SWITCH OPENS.
LED: 3 flashes.
CHECK TO SEE IF MAIN VALVE IS OFF.
SEQUENCE HOLDS UNTIL PRES. SWITCH CLOSES.
LED: Fast flash rate.
MAIN VALVE AND SPARK ARE OFF.
INCREMENT TRIAL REGISTER
THREE TRIALS COMPLETED?
YES
IGNITION RESET PERIOD
COMBUSTION & SYSTEM FANS OFF.
IS 60 MIN. RESET PERIOD COMPLETE?
LED: Fast flash rate.
NO
YES
FLAME SENSE OKAY?
YES
FLAME CONTINUOUSLY CHECKED?
ROLLOUT SWITCHES CLOSED
YES
HI LIMIT SWITCH CLOSED?
YES
PRESSURE SWITCH CLOSED?
YES
THERMOSTAT OPENS
LED: SLOW FLASH RATE
COMB. AIR BLOWER OFF (5 sec. delay)
FAN OFF (After selected 90, 120,
180, or 240 delay)?
NO
NO
NO
NO
MAIN VALVE AND SPARK OFF.
NO
START IGNITION SPARK (IN 0.8 SEC. MAXIMUM).
HAS FLAME BEEN DETECTED WITHIN 7 SEC.?
YES
LOCKOUT. MAIN VALVE OFF.
COMBUSTION AND SYSTEM FANS ON.
RESET OR REPLACE ROLLOUT SWITCH.
LED: 4 flashes.
MAIN VALVE OFF. COMBUSTION & SYSTEM FANS ON.
SEQUENCE HOLDS UNTIL SWITCH CLOSES.
LED: 4 flashes for hi limit.
LED: 3 flashes for pressure switch.
SWITCH CLOSED
YES
COMBUSTION FAN ON. SYSTEM FAN OFF.
(AFTER DELAY TO OFF INTERVAL COMPLETED.)
LED: Fast flash rate.
Page 24
Page 25
RAM CONTROL
COOLING TROUBLE SHOOTING SEQUENCE
REMAINS UNCHANGED THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED AT COOLING SPEED AFTER
1 SECOND DELAY. ACC TERMINAL ENERGIZED.
SYSTEM FAN AND ACC TERMINAL OFF AFTER
COMPLETING SELECTED DELAY INTERVAL
LED: Slow flash rate.
THERMOSTAT OPENS.
COMPRESSOR OFF.
(At dip switches).
MANUAL FAN TROUBLESHOOTING SEQUENCE
REMAINS UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL ENERGIZES SYSTEM FAN AT CONTINUOUS
THERMOSTAT CALLS FOR COOLING.
YESNO
SYSTEM FAN SWITCHED TO COOLING
SPEED. ACC TERMINAL REMAINS ENERGIZED.
THERMOSTAT OPENS.
AND ENERGIZES ACC TERMINAL. BOTH REMAIN ON
UNTIL MANUAL FAN IS SWITCHED OFF AT THERMOSTAT.
SLOW FLASH
FAST FLASH
2 FLASH
3 FLASH
4 FLASH
5 FLASH
STEADY ON
SPEED. ACC TERMINAL ENERGIZED.
SYSTEM FAN SWITCHES TO CONTINUOUS SPEED
NORMAL OPERATION. NO CALL FOR HEAT.
NORMAL OPERATION. CALL FOR HEAT.
SYSTEM LOCKOUT. FAILURE TO DETECT OR SUSTAIN FLAME.
.
PRESSURE SWITCH OPEN OR CLOSED.
HIGH LIMIT OR ROLLOUT SWITCH OPEN.
FLAME SENSED AND GAS VALVE NOT ENERGIZED.
CONTROL BOARD FAILURE.
LED: Slow flash rate.
THERMOSTAT CALLS FOR HEAT.
NO
LED CODES
YES
SYSTEM FAN SWITCHES TO HEATING SPEED AFTER
SELECTED DELAY. ACC TERM. REMAINS ENERGIZED.
THERMOSTAT OPENS.
SYSTEM FAN SWITCHED OFF AFTER DELAY.
ACC TERMINAL DE−ENERGIZED.
Page 25
Page 26
D−Late Model G24M Series With SureLight Ignition Control
TYPICAL G24M DIAGRAM
(−11 MODEL SHOWN)
1 − When there is a call for heat, W1 of the thermostat ener-
gizes W of the furnace control with 24VAC.
2 − S10 primary limit switch and S47 rollout switch are closed.
Call for heat can continue.
3 − SureLight control energizes combustion air blower B6.
Combustion air blower runs until S18 combustion air prove
switch closes (switch must close within 2−1/2 minutes or
control goes into 5 minute Watchguard Pressure Switch
delay). Once S18 closes, a 15−second pre−purge follows.
4 − SureLight control energizes ignitor. A 20−second warm−up
period begins.
5 − Gas valve opens for a 4−second trial for ignition. Ignitor
stays energized the first second of trial. (Board 97L48 only:
ignitor energized during trial or until flame is sensed.
6 − Flame is sensed, gas valve remains open for the heat call.
7 − After 45−second delay, SureLight control energizes indoor
blower B3.
8 − When heat demand is satisfied, W1 of the indoor thermostat
de−energizes W of the SureLight control which de−ener-
gizes the gas valve. Combustion air blower B6 continues a
5−second post−purge period, and indoor blower B3 com-
pletes a selected OFF time delay.
Page 26
Page 27
SURELIGHT CONTROL HEATING
SEQUENCE OF OPERATION
NORMAL HEATING MODEABNORMAL HEATING MODE
COMBUSTION AIR BLOWER ON FOR 1 SECOND.
SIGNAL IMPROPER
GROUND AT LED.
SIGNAL HOLDS
UNTIL UNIT IS
PROPERLY
GROUNDED.
IS COMBUSTION AIR BLOWER ENERGIZED?
(HTG ACC TERMINAL IS ENERGIZED WITH C.A.B.)
15-SECOND COMBUSTION AIR BLOWER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
POWER ON
CONTROL SELF−CHECK OKAY?
TURN INDUCER ON FOR 1 SECOND.
IS POLARITY REVERSED?
NO
NO
ROLLOUT SWITCH CLOSED?
(CONTINUOUS FLAME CHECK)
THERMOSTAT CALLS FOR HEAT:
PRESSURE SWITCH OPEN?
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
CONTINUED NEXT PAGE
IS THERE
PROPER GROUND?
YES
BURNER OFF?
YES
NORMAL OPERATION:
LED #1 −− SLOW FLASH
LED #2 −− SLOW FLASH
LED #1 −− FAST FLASH
LED #2 −− FAST FLASH
YES
IS COMBUSTION AIR
YES
YES
YES
YES
YES
NO
YES
IS VOLTAGE
ABOVE 75 VOLTS?
YES
NO
NO
NO
GAS VALVE OFF. COMBUSTION AIR BLOWER ON.
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
(RESET CONTROL BY TURNING MAIN POWER OFF.)
NO
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
LED #1 −− ON. LED #2 −− SLOW FLASH.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR BLOWER ON.
INDOOR BLOWER ON HEATING SPEED.
NO
PRESSURE SWITCH IS IN WATCHGUARD MODE.
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 −− OFF. LED #2 −− SLOW FLASH.
IS 5-MINUTE RESET PERIOD COMPLETE?
INDOOR BLOWER ON.
LED #1 ALTERNATING FAST FLASH
LED#2 ALTERNATING FAST FLASH
CHECK FOR BROKEN IGNITOR OR
OPEN IGNITOR CIRCUIT
INDOOR BLOWER DELAY OFF.
LED #1 ON
LED #2 ON
POLARITY REVERSED.
LED #1 −− FAST FLASH
LED #2 −− SLOW FLASH
LOW VOLTAGE SIGNAL AT LED HOLDS
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
INDOOR BLOWER OFF WITH DELAY.
LED #1 −− SLOW FLASH
LED #2 −− OFF
GAS VALVE OFF.
COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 OFF
LED #2 SLOW FLASH
(Sequence holds until pressure switch
closes or thermostat resets control.)
Page 27
Page 28
NORMAL HEATING MODEABNORMAL HEATING MODE
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP −− 20 SECONDS.
YES
4-SECOND TRIAL FOR IGNITION. GAS VALVE OPENS.
IGNITOR ENERGIZED FOR 1 SECOND AFTER VALVE
OPENS. NO FLAME SENSED DURING THIS PERIOD.
BOARD 97L48: IGNITOR ENERGIZED DURING TRIAL OR
FLAME SIGNAL ABOVE 0.7 MICROAMPS?
UNTIL FLAME SENSED.
YES
FLAME STABILIZATION PERIOD.
4 SECONDS
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(u0.15 microamps)
YES
FLAME PRESENT?
YES
YES
INDOOR BLOWER ON DELAY BEGINS
(45 seconds.)
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
(See table 2 DIAGNOSTIC CODES for limit reset operation)
IS VOLTAGE ABOVE 75 VOLTS?
NO
IS THERE A PROPER GROUND?
YES
IS IGNITOR INTACT AND CONNECTED?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
NO
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
IGNITION WATCHGUARD MODE. GAS VALVE OFF.
LED 1 ALT. SLOW FLASH LED 2 ALT SLOW FLASH
IS 60-MINUTE RESET PERIOD COMPLETE?
NO
NO
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER
DE−ENERGIZED.INDOOR BLOWER
NO
ON UNTIL SWITCH CLOSES.LED #1
−− SLOW FLASH. LED #2 −− ON.
IS LIMIT SWITCH CLOSED?
HAS PRIMARY/SECONDARY LIMIT RESET.
YES
YES
INDOOR BLOWER OFF.
HEAT DEMAND?
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
LOW FLAME SIGNAL
(Does not affect operation of control)
LED #1 −− SLOW FLASH
LED #2 −− FAST FLASH
YES
NO
NO
LIMIT SWITCH WATCH GUARD
MODE. GAS VALVE OFF.
COMB. AIR INDUCER OFF. INDOOR BLOWER OFF WITH
DELAY. LED#1−SLOW FLASH
LED#2− ON. IS 60MINUTE RESET PERIOD COMPLETE.?
LEDS SIGNAL
ALTERNATING
FAST FLASH
NO
NO
YES
NO
YES
YES
NO
YES
NO
ROLLOUT SWITCH CLOSED?
YES
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
YES
THERMOSTAT DEMAND SATISFIED.
YES
LED #1 & #2 SIMULTANEOUS SLOW FLASHES.
YES
COMB. AIR INDUCER CONTINUES 5-SECOND POST PURGE
AFTER T’STAT DEMAND IS SATISFIED. INDOOR AIR BLOWER
COMPLETES SELECTED OFF" DELAY BEFORE SHUTTING OFF.
ACB.HEAT SPEED, HTG ACC TERM. AND ACC TERM. OFF.
NO
HAS CAB SWITCH CLOSED IN 2.5 MINUTES?
COMBUSTION AIR INDUCER POWER OFF.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− OFF. LED #2 −− SLOW FLASH.
5-MINUTE PRESSURE SWITCH
GAS VALVE POWER OFF.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− ON. LED #2 −− SLOW FLASH.
YES
NO
WATCHGUARD MODE.
YES
Page 28
Page 29
SURELIGHT CONTROL COOLING SEQUENCE
NORMAL COOLING MODEABNORMAL COOLING MODE
POWER ON
IGNITION CONTROL MAIN POWER ON.
SIGNAL IMPROPER
GROUND AT LED.
SIGNAL HOLDS
UNTIL UNIT IS
PROPERLY
GROUNDED.
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
CHECK FOR MAIN BURNER FLAME SENSE.
LED: SLOW FLASH RATE REMAINS UNCHANGED
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
TURN INDUCER ON FOR 1 SECOND.
IS POLARITY REVERSED?
NO
NO
IS ROLLOUT SWITCH CLOSED?
IS MAIN BURNER FLAME OFF?
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
IS THERE
PROPER GROUND?
YES
YES
NO
YES
IS VOLTAGE
ABOVE 75 VOLTS?
NO
NO
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
SIGNAL POLARITY REVERSED AT LED.
NO
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
SEQUENCE HOLDS UNTIL FLAME IS NOT SENSED.
LOW VOLTAGE SIGNAL AT LET HOLDS
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED WITH 0-SECOND DELAY
ACB COOL SPEED AND ACC. TERM. ENERGIZED.
THERMOSTAT OPENS.
COMPRESSOR OFF.
ACB COOL SPEED AND ACC. TERM. OFF
WITH 0-SECOND DELAY.
Page 29
Page 30
CONTINUOUS LOW SPEED FAN SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT ACB
LOW SPEED. ACC. TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
NOYES
THERMOSTAT CALLS FOR COOLING.
YES
SYSTEM FAN SWITCHED TO ACB COOL
SPEED. ACC. TERM. REMAINS ON.
THERMOSTAT OPENS.
NO
HTG ACC. TERM. ENERGIZES
WITH COMB. AIR BLOWER.
BOARD NO. 63K8901
SYSTEM FAN DE−ENERGIZED. SYSTEM FAN
ENERGIZES ON ACB HEAT SPEED AFTER
NORMAL DELAY.
BOARD NO. 24L85, 56L83, 97L48
SYSTEM FAN SWITCHES TO ACB HEAT SPEED
AFTER NORMAL DELAY (fan remains energized)
THERMOSTAT OPENS. COMBUSTION AIR
AND HTG ACC TERMINAL DE−ENERGIZE.
BOARD 63K89: SYSTEM FAN OFF. ACC. TERM.
OFF. (AFTER OFF DELAY COMPLETED).
BOARDS 24L85, 56L83 AND 97L48:
SYSTEM FAN SWITCHES TO
LOW SPEED AFTER NORMAL DELAY.
(fan remains energized)
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT ACB
LOW SPEED. ACC. TERM. ENERGIZED.
Page 30
Page 31
E−SureLight Ignition Control Troubleshooting Guide
code
LED#2 Slow Flash
ACTION 1
blower does not energize
blower does not energize
120Vfieldconnection.
p
on operation
UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Miswiring or improper connections at
roll−out switch.
Nine pin connector failure
120V main power polarity reversed.
1.1.1
1.1.2
1.1.3
1.1.4
1.1.5
1.1.6
1.2.1
1.2.2
1.2.3
1.2.4
1.3.1
ACTION 1 − Check 120V main voltage.
Determine cause of main power failure.
ACTION 1 − Check for correct wiring of 120V to
power make up box and transformer.
ACTION 2 − Check 24V wiring to control board.
ACTION 1 − Replace circuit breaker if it is reset
but does not have continuity.
ACTION 2 − If circuit breaker still trips, check for
short.
ACTION 1 − Check that door switch is activated
when door is closed.
ACTION 2 − Check wire connections to switch, replace loose connectors.
ACTION 3 − Check continuity of switch in closed
position. Replace if malfunctioning
ACTION 1 − Check that transformer output is
24V. Replace if malfunctioning
ACTION 1 − If all the above items have been
checked, replace board.
ACTION 1 − Manually reset the roll−out switch
by pushing the top button.
ACTION 2 − Determine the cause of the roll−out
switch activation before leaving furnace.
ACTION 1 − Check continuity across roll−out
switch. Replace roll−out switch if switch is reset
but does not have continuity.
− Check wiring connections to switch.
ACTION 1 − Check 9−pin connector for proper
connection to control board.
ACTION 2 − Check continuity of the multi plug
pin.
ACTION 1 − Check the 120V has line and neutral
correctly input into control.
ACTION 2 − Reverse the line and neutral at the
120V field connection.
LED#1−Fast Flash,
LED#2−Slow Flash.
− On initial power up the combustion
air blower does not energize.
− Diagnostic lights flash normal power
on o
eration.
.
LED#1−Slow Flash
LED#2−Slow Flash
1.4
1.4.1
Open combustion air blower motor
circuit.
1.4.2
Failed combustion air blower motor.
Page 31
ACTION 1 − Check for 120V to combustion air
blower. If no power, check wire and connections.
ACTION 1 − If power is present at blower, replace
blower.
Page 32
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
ACTION 1 − Check continuity across switch(es).
Switches reset automatically upon cool down.
ACTION 2 − Check for restrictions on blower inlet
air (including filter) and outlet air. Determine
cause for limit activation before placing unit back
in operation.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check that the pressure switch is
open without the combustion air blower operating. Replace if malfunctioning
Page 32
Page 33
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES
g
LED#1 Off
NOT ENERGIZE (CONT.).
ConditionPossible CauseCorrective Action/Comments
3.3
− Unit operates with a cooling and con-
tinuous fan demand.
− Combustion air blower will not start
with a Heating demand.
Miswiring of furnace or improper con-
nections to combustion air blower.
3.3.1
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after
heating demand.
ACTION 1 − If there is 120V to combustion air
blower and it does not operate, replace combustion air blower.
LED#1−Off,
3.3.2
Combustion air blower failure.
LED#2−Slow Flash
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
ConditionPossible CauseCorrective Action/Comments
4.1
− Unit operates with a cooling and
continuous fan demand.
− Combustion air blower energizes
with a heating demand.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after
heating demand.
LED#1−Off
LED#2−Slow Flash
Pressure switch does not close due
to incorrect routing of the pressure
Pressure switch does not close due
to obstructions in the pressure lines.
Pressure switch lines damaged
Pressure switch does not close due
to a low differential pressure across
the pressure switch.
Wrong pressure switch installed in
the unit, or pressure switch is out of
Miswiring of furnace or improper con-
nections at pressure switch.
Pressure switch failure.
4.1.1
switch lines.
4.1.2
4.1.3
4.1.4
4.1.5
calibration.
4.1.6
4.1.7
ACTION 1 − Check that the pressure switch lines
are correctly routed. Correctly route pressure
switch lines.
ACTION 1 − Remove any obstructions from the
the pressure lines and/or taps.
ACTION 1 − Check pressure switch lines for
leaks. Replace any broken lines.
ACTION 1 − Check the differential pressure
across the pressure switch. This pressure
should exceed the set point listed on the
switch.
ACTION 2 − Check for restricted inlet and exhaust vent. Remove all blockage.
ACTION 3 − Check for proper vent sizing and
run length. See installation instructions.
ACTION 4 − Check voltage to thre combustion
air blower.
ACTION 1 − Check that the proper pressure
switch is installed in the unit. Replace pressure
switch if necessary.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − If all the above modes of failure have
been checked, the pressure switch may have
failed. Replace pressure switch and determine if
unit will operate.
Page 33
Page 34
PROBLEM 5: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ACTION 1 − Check line pressure at the gas
valve. Pressure should not exceed 13" WC for
both natural and propane. Line pressure should
read a minimum 4.5" WC for natural and 8.0"WC
for propane.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
ACTION 1 − Check that 24V is supplied to the
gas valve approximately 35 seconds after heat
demand is initiated.
ACTION 2 − Replace the valve if 24V is supplied
but valve does not open (check for excessive
gas line pressure before replacing gas valve).
ACTION 3 − Replace the control board if 24V is
not supplied to valve.
PROBLEM 6: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY
ConditionPossible CauseCorrective Action/Comments
6.1
− Burners fire with a heating de-
mand.
− Burners light but unit shuts off prior
to satisfying T−stat demand.
− Diagnostic lights flash the pressure
switch code.
6.1.1
Low pressure differential at the pres-
sure switch.
ACTION 1 − Check for restricted vent inlet or exhaust. Remove all blockage.
ACTION 2: Check for proper vent sizing. See
installation instructions.
LED#1−Off
LED#2−Slow Flash
6.2
− Combustion air blower energizes
with a heating demand.
− Burners light but fail to stay lit.
− After 5 tries the control diagnostics
flash the watchguard burners failed to
ignite code.
ACTION 1 − Check that sensor is properly located (page 10) and that the sense wire is
properly attached to both the sensor and the
control.
ACTION 1 − Check for a broken sensor.
ACTION 2 − Test continuity across the sense
wire. If wire or sensor are damaged replace
the component.
ACTION 1 − Check for resistance between the
sensor rod and the unit ground.
ACTION 2 − Check for resistance between the
sensor wire and the unit ground.
ACTION 3 − Correct any shorts found in circuit.
ACTION 1 − Check the microamp signal from
the burner flame. If the microamp signal is below 0.70 microamps, check the sense rod for
proper location or contamination.
ACTION 2 − Replace, clean, or relocate flame
sense rod. If rod is to be cleaned, use steel
wool or replace sensor. DO NOT CLEAN ROD
WITH SAND PAPER. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM. NOTE: Do not attempt to bend
sense rod.
Page 34
Page 35
PROBLEM 6: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
ure.
flame failure
ConditionPossible CauseCorrective Action/Comments
6.3
− Combustion air blower energizes
with a heating demand.
− Burners light.
− Roll−out switch trips during the
heating demand.
− Diagnostic lights flash roll−out fail-
ure.
LED#1−On
LED#2−Slow Flash
6.4
− Combustion air blower energizes
with a heating demand.
− Burners light roughly and the unit
fails to stay lit.
− Diagnostic lights flash watchguard
flame failure.
.
PREMATURELY (CONT.)
6.3.1
Unit is firing above 100% of the
nameplate input.
6.3.2
Gas orifices leak at the manifold con-
nection.
6.3.3
Insufficient flow through the heat ex-
changer caused by a sooted or re-
stricted heat exchanger.
6.3.4
Burners are not properly located in
the burner box.
6.4.1
Recirculation of flue gases. This con-
dition causes rough ignitions and op-
eration. Problem is characterized by
nuisance flame failures.
ACTION 1 − Check that the manifold pressure
matches value listed on nameplate. See installation instructions for proper procedure.
ACTION 2 − Verify that the installed orifice size
match the size listed on the nameplate or installation instructions.
ACTION 3 − Check gas valve sensing hose to insure no leaks are present.
ACTION 4 − Check the input rate to verify rate
matches value listed on nameplate.
ACTION 1 − Tighten orifice until leak is sealed.
NOTE: Be careful not to strip orifice threads. AC-
TION 2 − Check for gas leakage at the threaded
orifice connection. Use approved method for
leak detection (see unit instructions).
ACTION 1 − Check for sooting deposits or other
restrictions in the heat exchanger assembly.
Clean assembly as outlined in instruction manual.
ACTION 2 − For G24M gas furnaces, check for
proper combustion and flow. CO2 should measure between 6.0% and 8.0% for NG and between 6.5% and 8.5% for LP. CO should measure below .04% (400PPM) in an air−free sample
of flue gases for either NG or LP.
ACTION 1 − Check that the burners are firing into
the center of the heat exchanger openings. Correct the location of the burners if necessary.
ACTION 1 − Check for proper flow of exhaust
gases away from intake vent. Remove any obstacles in front of the intake and exhaust vent
which would cause recirculation.
ACTION 2 − Check for correct intake and exhaust vent installation. See instructions
PROBLEM 7: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE
ConditionPossible CauseCorrective Action/Comments
7.0
− Unit operates correctly but the
diagnostic lights flash low flame
.
LED#1−Slow Flash
LED#2−Fast Flash
PREMATURELY (CONT.)
6.5.1
Loose sensor wire connection
causes intermittent loss of flame sig-
nal.
7.1.1
Sense rod is improperly located on
the burner.
7.1.2
Sense rod is contaminated.
ACTION 1 − Check that the sensor is properly located.
ACTION 2 − Check that the sense wire is properly attached to both the sensor and the control.
Pay extra attention to the pin connectors.
ACTION 1 − Check the sense rod for proper location on the burner. Properly locate the sense rod
or replace if rod cannot be located correctly.
ACTION 1 − Check sense rod for contamination
or coated surface. Clean the sense rod with steel
wool or replace sensor. DO NOT USE SAND PAPER TO CLEAN ROD. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM.
PROBLEM 8: INDOOR BLOWER FAILS TO OPERATE IN COOLING, HEATING, OR CONTINUOUS
FAN MODE
ConditionPossible CauseCorrective Action/Comments
8.0
− Indoor blower fails to operate in
continuous fan, cooling, or heating
mode.
Miswiring of furnace or improper con-
nections at control or indoor blower
120V is not being supplied to the in-
door air blower or blower motor fail-
Defective control board
8.1.1
motor.
8.1.2
ure.
8.1.3
ACTION 1− Correct wiring and/or replace any
loose connections. Check for correct wiring and
loose connections.
ACTION 1 − Check for 120V at the various calls
for indoor blower by energizing "Y", "G", and "W"
individually on the low voltage terminal strip.
Note that when "W’ is energized, the blower is
delayed 45 seconds. If there is 120V to each motor tap but the blower does not operate, replace
the motor.
ACTION 1 − If there is not 120V when "Y", "G", or
"W" is energized, replace the control.
PROBLEM 9: RF STATIC DURING TIME FOR IGNITION
ConditionPossible CauseCorrective Action/Comments
9.0
− AM radio interference.
9.1.2
Ignitor operation
ACTION 1 − Call Technical Support, Dallas.
Page 36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.