G24Mseriesunitsaremid-efficiencygasfurnacesmanufactured with tubular steel heat exchangers formed of aluminizedsteel.G24Munitsareavailableinheatingcapacitiesof
45,000 to 140,000 Btuh and cooling applications up to 5
tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is
availableforconversiontoLPGoperation.EarlymodelG24M
units use electronic (direct spark) ignition. Late model G24M
model units feature the Lennox SureLightT silicon-nitride
ignition system. The G24MX unit meets the California Nitrogen Oxides (NOx) Standards and California Seasonal Efficiency requirements. All units use a redundant gas valve to
assure safety shut-off as required by A.G.A. or C.G.A.
Unitsmaybeinstalledinupflow,downfloworhorizontalposition. The heat exchanger is designed for upright or horizontal use only. When the unit is installed in the downflow position,theheatexchangerisfieldremovedandreinstalled so it
isuprightwhen the cabinet is inverted.Nofield conversion is
required when the unit is installed in the horizontal position.
The heat exchanger, burners and manifold assembly can
easily be removed for inspection and service by simply disconnecting gas, unplugging wiring harness and spark wires
and removing four screws holding the heat exchanger in
place. Then the heat exchanger slides out of the cabinet.
Model No.G24M2(X)-45G24M2-60G24M3(X)-60G24M2-75G24M3(X)-75
Input Btuh (kW)45,000 (13.2)60,000 (17.6)75,000 (22.0)
Output Btuh (kW)36,900 (10.8)49,200 (14.4)61,700 (18.1)
lA.F.U.E.80.1%80.5%80.5%80.1%80.0%
California Seasonal Efficiency75.4%76.4%75.9%76.8%76.8%
Flue size connection diameter — in. (mm) round3 (76)4 (102)
Temperature rise range — _F (_C)30 - 60 (17 - 33)45 - 75 (25 - 42)
High static certified by A.G.A./C.G.A. — in wg. (Pa).50 (125)
Gas Piping Size I.P.S. Natural or LPG/propane1/2 (13)
in.9 x 710 x 79 x 710 x 7
Blower motor output — hp (W)1/4 (187)1/3 (224)1/4 (187)1/3 (224)
LPG/propane kitLB-69845L (38K84)
Twinning Kit96J69 — 5 lbs. (2 kg)
Up-Flow/Horizontal Filter and Filter Rack Kits
}No. & size of filters - in. (mm)
Catalog No.
Filter Kit
Down-flow Combustible Floor Base
Sidewall Power Venting Kit79J15 — 25 lbs. (11 kg)
Hanging Bracket Kit
lAnnual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
}Polyurethane frame type filter isfurnished with kit.
¡Filters arenot furnished with kitand must be ordered extra.
No. & Size of Filters — in. (mm)
mm229 x 178254 x 178229 x 178254 x 178
Tons1, 1-1/2 or 22, 2-1/2 or 31, 1-1/2 or 22, 2-1/2 or 3
kW3.5, 5.3 or 7.07.0, 8.8 or 10.63.5, 5.3 or7.07.0, 8.8 or 10.6
b Optional Accessories (Must Be Ordered Extra) b
Revised 07-2001
All specifications in this manual are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or
state codes. In the absence of local or state codes, the
guidelines and procedures outlined in this manual (except
where noted) are recommended only and do not constitute
code.
G24M unit components are shown in figure 1. The blower
controls, gas valve and burners can be accessed by reĆ
moving the front access panel. A separate blower access
door is located behind the front access panel. Electrical
control components are mounted to the blower access
door.
G24M units are factory equipped with bottom return air panels
in place. The panels are designed to be field removed as reĆ
quired for bottom air return. Indentations on side of units,
show where side return opening should be cut during installaĆ
tion.
A-Blower Door Components (Figure 4)
Electrical burner control and blower control components
are located on the outside surface of the blower access
door. Jackplugs allow the blower door to be easily reĆ
moved for blower service.
Located on the blower door are the unit transformer (T1),
the furnace control (A3) and door interlock switch (S51).
Furnace control (A3) combines the function of a burner
ignition control and blower control.
1- Control Transformer (T1)
A transformer located on the blower door provides power
to the low voltage section of the unit. Transformers on all
models are rated 30VA with a 120V primary and a 24V secĆ
ondary.
2-Door Interlock Switch (S51)
A door interlock switch rated 16A at 125VAC is located on
the blower access door. The switch is wired in series with
line voltage. When the blower door is removed the unit will
shut down.
DANGER
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply
replace entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
3- SureLight Ignition System (A3)
Late Model G24M Units
Late model G24M units are equipped with the Lennox
SureLight ignition system. The system consists of ignitor
(f igur e 5) and ignition control board (f igur e 6 wit h control
terminal designations in table 1). The board and ignitor
work in combination to ensure furnace ignition and ignitor
durability. The SureLight integrated board controls all
major furnace operations. The board also features two
LED lights for troubleshooting and two accessory termiĆ
nals rated at (4) four amps. See table 2 for troubleshootĆ
ing diagnostic codes. Table 3 and 4 show jack plug termiĆ
nal designations. Units equipped with the SureLight
board can be used with either electronic or electro-meĆ
chanical thermostats without modification. The SurĆ
eLight ignitor is made of durable silicon-nitride. Ignitor
longevity is also enhanced by voltage ramping by the
control board. The board finds the lowest ignitor temperaĆ
ture which will successfully light the burner, thus increasĆ
ing the life of the ignitor.
a-flame sensor
The flame sensor uses flame rectification to sense comĆ
bustion. During operation, flame is sensed by current
passed through the flame and sensing electrode. Figure 7
shows the gap between tip of the electrode and the burner
surface.
SURELIGHT IGNITOR
UPPER BURNER
MOUNTING RAIL
SURELIGHT IGNITOR BURNER ASSEMBLY
FLAME RETENTION RING
FIGURE 5
Page 8
ORIFICE
FLAME SENSOR
SURELIGHT CONTROL BOARD
LATE MODEL G24M UNITS
TABLE 1
SURELIGHT CONTROL TERMINAL DESIGNATIONS
ACB COOL
ACB HEAT
PARK
ACB LOW
ACC
TX
HOT
HTG ACC
NEUTRALS
24VACHOT
24VACRTN
FLAME SENSE
Blower - Cooling Speed (Line Volt)
Blower - Heating Speed (Line Volt)
Alternate Blower Speeds (Dead)
Continuous Low Speed Blower
Accessory Terminal (Line Volt)
120VACHot to Transformer
120VACHot Input
Heat Only Accessory (Line Volt)
120VACNeutrals
24VACHot from Transformer
24VACReturn from Transformer
Flame Sense Terminal
NORMAL FLAME SIGNAL > 0.7 MICROAMPS
LOW FLAME SIGNAL< 0.7 MICROAMPS
MINIMUM FLAME SIGNAL < 0.15 MICROAMPS
FLAME SENSOR TO BURNER GAP
1/4 in. 7 mm
¦ 1/32 in. 0.79
BURNER
SIDE VIEWEND VIEW
FIGURE 6
TABLE 2
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1LED #2DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASHON
OFFSLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASHOFF
ONSLOW FLASH
ON
ON
OFF
FAST FLASHSLOW FLASH
SLOW FLASHFAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continues fan.
Normal operation - signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Units with board 63K8901 or 24L85: Limit must
close within 5 trials for ignition or board goes into one hour limit Watchguard.
Units with board 56L83 or 97L48: Limit must close within 3 minutes or board
Pressure switch open or has opened 5 times during a single call for heat; OR:
Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below .7 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power - Normal operation
goes into one hour limit Watchguard.
Watchguard - burners fail to ignite.
Open ignitor circuit.
mm
3/16 in.
4.7 mm
FLAME
SENSOR
FIGURE 7
11/16in. 18 mm
¦ 1/32 in. 0.79
mm
NOTE - Slowflash equals1 Hz (oneflash persecond). Fast flashequals 3Hz (threeflashes per second).Drop outflame sense current< 0.15microAmps
Page 9
TABLE 3
SureLight BOARD J156 (J2) TERMINAL
PIN #FUNCTION
1Ignitor
2
3
4
5
6
DESIGNATIONS
Not Used
Ignitor Neutral
Combustion Air Blower Line Voltage
Not Used
Combustion Air Blower Neutral
TABLE 4
SureLight BOARD J58 (J1) TERMINAL
PIN #FUNCTION
1Primary Limit In
2
3
4
5
6
7
8
9
DESIGNATIONS
Gas Valve Common
Roll Out Switch Out
Gas Valve 24V
Pressure Switch In
Pressure Switch and Primary Limit Out
Not Used
Roll Out Switch In
Ground
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s
electronic controls. Precautions will help to
avoid control exposure to electrostatic discharge by putting the furnace, the control and
the technician at the same electrostatic potential. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface,
such as thegas valve or blower deck, before performing any service procedure.
not proven within 2-1/2 minutes, the control goes into
Watchguard-Pressure Switch mode for a 5-minute re-set
period.
NOTE - The G24M furnace contains electronic components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
After the 15-second pre-purge period, the SureLight ignitor warms up for 20 seconds after which the gas valve
opensfor a 4-secondtrial for ignition.The ignitor staysenergized for the first second of the 4-second trial. G24M
units with 63K89, 24L85 or 56L83: the ignitor stays energizedthefirstsecondofthe4secondtrial.G24Munitswith
board 97L48: ignitor stays energized during the 4-second
trialuntilflameissensed.Ifignitionisnotproved during the
4-secondperiod,thecontrolwill try four more times withan
inter purge and warm-up time between trials of 35 seconds.After a totalof five trialsfor ignition (including the initial trial), the control goes into Watchguard-Flame Failure
mode.Aftera 60-minute reset period, the control willbegin
the ignition sequence again.
The SureLight control board has an added feature that
prolongs the life of the ignitor. After a successful ignition,
theSureLightcontrolutilizeslesspower to energize the ignitoron successive callsfor heat. Thecontrol continues to
rampdown the voltageto the ignitor untilit finds the lowest
amount of power that will provide a successful ignition.
Thisamount of poweris used for255 cycles. Onthe 256th
callfor heat, thecontrol will againramp down until the lowest power is determined and the cycle begins again.
c-Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. See figure 8.
NOTE—If fan “off” time is set too low, residual heat in
heat exchanger may cause primary limit S10 to trip resulting in frequent cycling of blower. If this occurs, adjust blower to longer time setting.
b-Electronic Ignition
On a call for heat the SureLight control monitors the combustion air inducer prove switch. The control will not begin
theheatingcycle if the prove switchisclosed (by-passed).
Once the prove switch is determined to be open, the combustion air inducer is energized. When the differential in
the prove switch is great enough, the prove switch closes
and a 15-second pre-purge begins. If the prove switch is
FAN-OFF TIME ADJUSTMENT
60sec.90sec.120sec.180sec.
To adjust fan-off timing, flip dip switch to desired setting.
Furnace should operate at least 5 minutes bef ore ch eckĆ
ing gas flow. Determine time in seconds for two revoluĆ
tions of gas through the meter. (Two revolutions assures
a more accurate time.) Divide by two and compare to time
in tabl e 10 below. Adjust manifold pressure on gas valve
to match time needed.
NOTE- To obtain accurate reading, shut off all other
gas appliances connected to meter.
TABLE 10
GAS METER CLOCKING CHART
Seconds for One Revolution
G24M
Unit
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
-4580160200400
-6060120150300
-754896120240
-100367290180
-120306075150
-140265264128
Natural-1000 btu/cu ft LP-2500 btu/cu ft
NOTE- To obtain accurate reading, shut off all other
gas appliances connected to meter.
G-High Altitude Derate
NOTE-In Canada, certification for installation at altiĆ
tudes over 4500 ft. (1372m) above sea level is the jurisĆ
diction of the local authorities.
G24M-1 through -9 Models
This unit does not require gas pressure adjustment, or
pressure switch change when operating at elevations of 0
to 7500 ft. (0 to 2248m). Check gas line pressure with unit
firing. The minimum pressure as shown on the nameplate
for natural and propane gases must be maintained. No oriĆ
fice change is required.
NOTE-This is the only permissible field derate for this
appliance.
G24M-10 and -11 Models
Table 11 shows manifold pressure settings for installations
at different altitudes. Refer to table 12 for pressure switch
replacement for models at elevations of 4500 feet (1372m)
and greater.
TABLE 11
ALTITUDE
feet (m)
0 - 4500
(0 - 1372)
4500 - 5500
(1372 - 1676)
5500 - 6500
(1676 - 1981)
6500 - 7500
(1372 - 2286)
GAS FUEL
Natural3.5 (0.87)
Propane/LP9.5 (2.36)
Natural3.4 (0.86)
Propane/LP9.2 (2.29)
Natural3.3 (0.82)
Propane/LP8.9 (2.21)
Natural3.2 (0.80)
Propane/LP8.6 (2.14)
MANIFOLD
PRESSURE
in. W.C. (kPa)
TABLE 12
Unit ModelPressure Switch Part Number
G24M-45No Change
G24M-60No Change
G24M-7588J8001
G24M-10018L2401
G24M-12018L2401
G24M-140No Change
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
H-Flame Signal
A microamp DC meter is needed to check the flame signal
on the primary ignition control.
Flame (microamp) signal is an electrical current which
passes from the furnace control through the sensor elecĆ
trode during unit operation. Current passes from the senĆ
sor through the flame to ground to complete a safety cirĆ
cuit.
To Measure Flame Signal:
1 - Place meter in series between furnace control and
sensor wire. Connect the positive (+) lead of meter to
the ignition control sensor connection and the negaĆ
tive (-) lead of the meter to the sensor wire. See figure
21.
2 - Set thermostat for a heating demand and check flame
signal with unit operating. For G24M series with a RAM
control, a reading of 1 to 5 microamps DC should occur.
The furnace control must see at least 1.0 microamps in
order to keep the gas valve energized. G24M units with
the SureLight control should read 0.7 microamps or
more.
Page 18
FLAME SIGNAL TEST
D.C. MICROAMP
METER
FLAME
SENSOR
IGNITION
CONĆ
TROL
SENSOR
WIRE
RAM CONTROL
SHOWN
SENSE"
TERMINAL
FIGURE 21
Flame signal from the Ram control may rise above 5 microĆ
amps for the first few seconds after ignition then level off within
the range.
WARNING
Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.
V-TYPICAL OPERATING CHARACTERISTICS
A-Blower Operation and Adjustment
NOTE- The following is a generalized procedure and
does not apply to all thermostat controls.
1 - Blower operation is dependent on thermostat control
system.
2 - Generally, blower operation is set at thermostat subĆ
base fan switch. With fan switch in ON position, blower
operates continuously on low speed. With fan switch in
AUTO position, blower cycles with demand or runs conĆ
tinuously while heating or cooling circuit cycles.
3 - In all cases, blower and entire unit will be off when the
system switch is in OFF position.
B-Temperature Rise
Temperature rise for G24M units depends on unit input,
blower speed, blower horsepower and static pressure as
marked on the unit rating plate. The blower speed must be
set for unit operation within the range of AIR TEMP. RISE
°F" listed in the unit rating plate.
To Measure Temperature Rise:
1 - Place plenum thermometers in the supply and return
air plenums. Locate supply air thermometer in the first
horizontal run of the plenum where it will not pick up raĆ
diant heat from the heat exchanger.
2 - Set thermostat to highest setting.
3 - After plenum thermometers have reached their highĆ
est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check
the firing rate. Provided the firing rate is acceptable, inĆ
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.
C-External Static Pressure
1 - Measure tap locations as shown in figure 22.
2 - Punch a 1/4" diameter hole
in supply and return air pleĆ
nums. Insert manometer
hose flush with inside edge
of hole or insulation. Seal
around the hose with perĆ
magum. Connect the zero
end of the manometer to the
discharge (supply) side of the system. On ducted sysĆ
tems, connect the other end of manometer to the reĆ
turn duct as above. For systems with non-ducted reĆ
turns, leave the other end of the manometer open to
the atmosphere.
3 - With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blowĆ
er motor speed to deliver the air desired according to
the job requirements.
4 - External static pressure drop must not be more than
0.5" W.C.
5 - Seal around the hole when the check is complete.
STATIC PRESSURE
TEST
MANOMETER
G24M UNIT
FIGURE 22
Page 19
D-Blower Speed Taps Leadless Motors
Blower speed tap selection is accomplished by changing the
taps at the blower motor harness connector. Disconnect harĆ
ness connector from motor to expose speed selectors.
Blower speed selections are listed in table 13.
To Change Blower Speed:
1 - Turn off electric power to furnace.
2 - Remove front panel and blower access door. See
figure 4.
3 - Disconnect blower motor harness from motor.
4 - Select desired speeds for heating and cooling (refer to
unit wiring diagram).
5 - Depress harness connector tab to release wire termiĆ
nal. Select connector location for new speed (refer to
unit wiring diagram). Insert wire terminal until it is seĆ
curely in place. See figure 23.
6 - Replace harness connector to motor.
BLOWER SPEED TAP SELECĆ
TION
LEADLESS MOTORS
HARNESS
CONNECTOR
SureLight board. The heating tap is connected to the "ACB
HEAT " terminal and the cooling tap is connected to the
"ACB COOL" terminal. The continuous blower tap is conĆ
nected to the "ACB LOW" terminal.
To change existing heat tap, turn off power then switch out
speed tap on "ACB HEAT" with tap connected to "PARK
M1" or "PARK M2". See table 14 for blower motor tap colĆ
ors for each speed.
TABLE 13
TABLE 14
DEPRESS TAB TO RELEASE
WIRE TERMINAL. SELECT
CONNECTOR LOCATION
FOR NEW SPEED (REFER TO
UNIT WIRING DIAGRAM). INĆ
SERT WIRE UNTIL IT IS SEĆ
CURELY IN PLACE.
MOTOR
FIGURE 23
E-Blower Speed Taps Leaded Motors
Blower speed tap changes are made on the SureLight
control board. See figure 6. Unused taps must be secured
on dummy terminals "PARK M1" and or "PARK M2" on the
VI-MAINTENANCE
At the beginning of each heating season, the system
should be checked as follows:
A-Filters
A filter must be used in order to ensure long life and proper
operation. The filter is located in the return air duct or return
air register. Filters must be cleaned or replaced when dirty
to assure proper unit operation.
B-Heat Exchanger and Burners
NOTE-Use papers or protective covering in front of furĆ
nace while cleaning furnace.
Due to dimples designed in the heatexchanger, cleaning is
not recommended. Removal is for inspection only.
D-Late Model G24M Series With SureLight Ignition Control
TYPICAL G24M DIAGRAM
(-11 MODEL SHOWN)
1 - When there is a call for heat, W1 of the thermostat ener-
gizes W of the furnace control with 24VAC.
2 - S10 primary limit switch and S47 rollout switch are closed.
Call for heat can continue.
3 - SureLight control energizes combustion air blower B6.
Combustionairblower runs until S18 combustion air prove
switch closes (switch must close within 2-1/2 minutes or
control goes into 5 minute Watchguard Pressure Switch
delay). Once S18 closes, a 15-second pre-purge follows.
4 - SureLight control energizes ignitor. A 20-second warm-up
period begins.
5 - Gas valve opens for a 4-second trial for ignition. Ignitor
staysenergizedthefirstsecond of trial. (Board 97L48 only:
ignitor energized during trial or until flame is sensed.
6 - Flame is sensed, gas valve remains open for the heat call.
7 - After 45-second delay, SureLight control energizes indoor
de-energizes W of the SureLight control which de-ener-
gizes the gas valve. Combustion air blowerB6 continues a
5-second post-purge period, and indoor blower B3 com-
pletes a selected OFF time delay.
Page 26
SURELIGHTCONTROLHEATING
SEQUENCEOFOPERATION
NORMALHEATINGMODEABNORMALHEATINGMODE
COMBUSTIONAIRBLOWERONFOR1SECOND.
SIGNALIMPROPER
GROUNDATLED.
SIGNALHOLDS
UNTILUNITIS
PROPERLY
GROUNDED.
ISCOMBUSTIONAIRBLOWERENERGIZED?
(HTGACCTERMINALISENERGIZEDWITHC.A.B.)
15-SECONDCOMBUSTIONAIRBLOWERPREPURGE
INITIATEDBYCLOSEDPRESSURESWITCH.
POWERON
CONTROLSELF--CHECKOKAY?
TURNINDUCERONFOR1SECOND.
ISPOLARITYREVERSED?
NO
NO
ROLLOUTSWITCHCLOSED?
(CONTINUOUSFLAMECHECK)
THERMOSTATCALLSFORHEAT:
PRESSURESWITCHOPEN?
HASCOMBUSTIONAIRPRESSURESWITCHCLOSEDIN2.5MINUTES?
ISTHERE
PROPERGROUND?
YES
BURNEROFF?
YES
NORMALOPERATION:
LED#1----SLOWFLASHLED#2----SLOWFLASH
LED#1----FASTFLASHLED#2----FASTFLASH
YES
ISCOMBUSTIONAIR
YES
YES
YES
YES
CONTINUEDNEXTPAGE
YES
YES
NO
YES
ISVOLTAGE
ABOVE75VOLTS?
NO
NO
NO
NO
GASVALVEOFF.COMBUSTIONAIRBLOWERON.
GASVALVEOFF.COMBUSTIONAIRBLOWEROFF.
(RESETCONTROLBYTURNINGMAINPOWEROFF.)
NO
GASVALVEOFF.COMBUSTIONAIRBLOWEROFF.
INDOORBLOWEROFFWITHDELAY.
LED#1----ON.LED#2----SLOWFLASH.
SEQUENCEHOLDSUNTILROLLOUTSWITCHCLOSES.
GASVALVEOFF.COMBUSTIONAIRBLOWERON.
INDOORBLOWERONHEATINGSPEED.
PRESSURESWITCHISINWATCHGUARDMODE.
GASVALVEOFF.COMBUSTIONAIRBLOWEROFF.
INDOORBLOWEROFFWITHDELAY.
LED#1----OFF.LED#2----SLOWFLASH.
IS5-MINUTERESETPERIODCOMPLETE?
INDOORBLOWERON.
LED#1ALTERNATINGFASTFLASH
LED#2ALTERNATINGFASTFLASH
CHECKFORBROKENIGNITOROR
OPENIGNITORCIRCUIT
INDOORBLOWERDELAYOFF.
LED#1ONLED#2ON
POLARITYREVERSED.LED#1----FASTFLASH
LED#2----SLOWFLASH
LOWVOLTAGESIGNALATLEDHOLDS
UNTILVOLTAGERISESABOVE75VOLTS.
LED#1----SLOWFLASH
LED#2----OFF
GASVALVEOFF.
COMBUSTIONAIRBLOWEROFF.
INDOORBLOWEROFFWITHDELAY.
LED#1OFF
LED#2SLOWFLASH
(Sequenceholdsuntilpressureswitch
closesorthermostatresetscontrol.)
3DJH
NORMAL HEATING MODEABNORMAL HEATING MODE
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATEDBY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP -- 20 SECONDS.
YES
4-SECOND TRIAL FOR IGNITION. GAS VALVE OPENS.
IGNITOR ENERGIZED FOR 1 SECOND AFTER VALVE
OPENS. NO FLAME SENSED DURING THIS PERIOD.
BOARD 97L48: IGNITOR ENERGIZED DURING TRIAL OR
FLAME SIGNAL ABOVE 0.7 MICROAMPS?
UNTIL FLAME SENSED.
YES
FLAME STABILIZATION PERIOD.
4 SECONDS
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(>0.15 microamps)
YES
FLAME PRESENT?
YES
YES
INDOOR BLOWER ON DELAYBEGINS
(45 seconds.)
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
(See table 2 DIAGNOSTIC CODES for limit reset operation)
IS VOLTAGE ABOVE 75 VOLTS?
NO
IS THERE A PROPER GROUND?
YES
IS IGNITOR INTACT AND CONNECTED?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
NO
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
IGNITION WATCHGUARD MODE. GAS VALVE OFF.
LED 1 ALT. SLOW FLASH LED 2 ALT SLOW FLASH
IS 60-MINUTE RESET PERIOD COMPLETE?
NO
NO
GAS VALVE DE-ENERGIZED.
COMBUSTION AIR INDUCER
DE-ENERGIZED.INDOOR BLOWER
NO
ON UNTIL SWITCH CLOSES.LED #1
-- SLOW FLASH. LED #2 -- ON.
IS LIMIT SWITCH CLOSED?
HAS PRIMARY/SECONDARY LIMIT RESET.
YES
YES
INDOOR BLOWER OFF.
HEATDEMAND?
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
LOW FLAME SIGNAL
(Does not affect operation of control)
LED #1 -- SLOW FLASH
LED #2 -- FAST FLASH
YES
NO
NO
LIMIT SWITCH WATCHGUARD
MODE. GAS VALVE OFF.
COMB. AIR INDUCER OFF. INDOOR BLOWER OFF WITH
DELAY. LED#1-SLOW FLASH
LED#2- ON. IS 60MINUTE RESET PERIOD COMPLETE.?
LEDS SIGNAL
ALTERNATING
FAST FLASH
NO
NO
YES
NO
YES
YES
NO
YES
NO
ROLLOUT SWITCH CLOSED?
YES
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
YES
THERMOSTAT DEMAND SATISFIED.
YES
LED #1 & #2 SIMULTANEOUS SLOW FLASHES.
YES
COMB. AIR INDUCER CONTINUES 5-SECOND POST PURGE
AFTER T’STAT DEMAND IS SATISFIED.INDOOR AIR BLOWER