Lennox G24-200 User Manual

Page 1
INSTALLATION
PRODUCT LITERATURE
2005 Lennox Industries Inc.
Dallas, Texas
RETAIN THESE INSTRUCTIONS
INSTRUCTIONS
G24-200
UPFLOW GAS FURNACE Direct Spark Ignition
503,613M 8/2005
Supersedes 7/2003
Table of Contents
G24−200 Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . .
G24−200 Parts Arrangement 4. . . . . . . . . . . . . . . . . . . .
G24−200 Gas Furnace 6. . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 6. . . . . . . . . . . . . . . . . . . . . .
Safety 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 8. . . . . . . . . . . .
Setting Equipment 11. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Return Air Plenum / Filter Box Installation 11. . . . . . . .
Duct System 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor and Drive Installation 13. . . . . . . . . . . . .
Venting 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−up 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 34. . . . . . . . . . . . . . . .
Gas Pressure Adjustment 35. . . . . . . . . . . . . . . . . . . . .
High Altitude Information 35. . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments and Operation 35. . . . . . . . . . .
Setting Blower CFM 37. . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G24−200 Start−up & Performance Check List 39. . . . .
Troubleshooting 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Litho USA
Failure to follow safety warnings exact­ly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be per­formed by a qualified installer, ser­vice agency or the gas supplier.
08/05
*2P0805*
WARNING
FIRE OR EXPLOSION HAZARD.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.Extinguish any open flame.Do not touch any electrical switch; do not
use any phone in your building.
Leave the building immediately.Immediately call your gas supplier from a
neighbor’s phone. Follow the gas suppli­er’s instructions.
If you cannot reach your gas supplier, call
the fire department.
503,613M
*P504613M*
Page 2
G24−200 Unit Dimensions − inches (mm)
52-1/2 (1334)
10-1/2
(267)
VENT
OUTLETS
17
(432)
5/8
(16)
VENT
OUTLETS
5-1/2 (140)
9 (229)
Either Side
29-1/4
(743)
17
(432)
HEAT
EXCHANGER
SUPPLY
AIR
OPENING
2
(51)
7/8
(22)
1-1/16
(27)
CONTROL
BOX
4-1/4 (108)
50-3/4 (1289)
Bottom Return
Air Opening
53
(1346)
7/8
(22)
Either Side
GAS
PIPING
INLET
Either Side)
ELECTRICAL
INLET
(Either Side)
BLOWER
MOTOR
(25)
1
26
(660)
FLOW
Bottom Return
Air Opening
FRONT VIEW SIDE VIEW
52-1/2 (1334)
50-3/8 (1280)
Supply Air
Opening
1-1/16
(27)
AIR
2-1/4
(57)
1
(25)
REAR RETURN
AIR OPENING
BACK VIEW
50-1/2 (1283)
27
(686)
1
(25)
1
(25)
Page 2
Page 3
G24−200 Filter Box Dimensions − inches (mm)
5
(127)
AIR
FLOW
1
(25)
4-3/4 (121)
26-1/4
(667)
AIR
FLOW
50-1/2 (1283)
OPENING SAME
BOTH SIDES
1
(25)
32
(813)
5 (127)
1
(25)
5
(127)
4-3/4
(121)
26-1/4
(667)
*OPTIONAL FILTER BOX
*NOTE  Return air filter box may be installed at back or bottom of furnace.
50-1/2 (1283)
(127)
32
(813)
5
(25)
1
(25)
BACK VIEWSIDE VIEW
TOP VIEW
4-3/4 (121)
1
50-1/2 (1283)
26-1/4
(667)
1
*NOTE  Return air filter box may be
(25)
installed at back or bottom of furnace.
OPENING SAME
BOTH SIDES
1
(25)
FRONT VIEW
1
(25)
OPENING SAME
BOTH SIDES
32
(813)
Page 3
Page 4
G24−200 Parts Arrangement
LIMIT CONTROL*
LEFT SIDE PANEL
FLUE BOX GASKET*
COMBUSTION AIR BLOWER*
FLUE BOX*
BURNER RETENTION
BRACKET*
FLAME ROLLOUT
SWITCH*
G24−200 HEAT SECTION AND CABINET
*
(THIS UNIT CONTAINS TWO HEAT SECTIONS. EACH HEAT SECTION CONTAINS ONE OF THESE ITEMS.)
CABINET TOP
PRESSURE SWITCH*
HEAT EXCHANGER ASSEMBLY*
FLEXIBLE CONNECTOR
PRESSURE SWITCH*
IGNITION CONTROL*
REAR PANEL − TOP
BURNER MTG
BRACKET*
SENSOR*
IGNITOR*
GAS VALVE*
(two-stage)
CONTROL BOX
REAR PANEL − BOTTOM
RIGHT SIDE PANEL
MAKE−UP BOX*
HEATING COMPARTMENT ACCESS
PANEL*
BLOWER COMPARTMENT AC-
CESS PANEL
CENTER MULLION
Page 4
Page 5
G24−200 Parts Arrangement Continued
G24−200 BLOWER SECTION
DRIVE BELT
(Drive Kit)
ADJUSTMENT ARM
BLOWER
PULLEY
MOTOR PULLEY
(Drive Kit)
MOTOR BASE
SHAFT
MOTOR
(Drive
Kit)
CUT−OFF PLATE
BLOWER HOUSING
BEARING
WHEEL
BASE ASSEMBLY
MOTOR BASE
VIBRATION ISOLATOR
LOCATING ROD
Page 5
Page 6
G24−200 Gas Furnace
CLEARANCE
The G24−200 upflow gas furnace is for use with natural gas only.
Each G24−200 requires the installation of a separately or­dered drive kit. The available drive kits are listed in tables 10 and 15. Provided in each drive kit is the following: the fur­nace’s blower motor, its 24 volt control transformer, and (in non-208/230 volt models) an autotransformer for each of the furnaces’s induced draft blowers. Also available for order separately is a filter box kit for rear or bottom return air applications. This furnace has two independently controlled heat sections, each with an input of 100MBH and each operating in a two­stage (low heat/high heat) mode. The C17−090/120 cooling coil has been designed for use with this furnace and can be connected to either a single condensing unit or to two con­densing units. (See C17 coil installation instructions.)
Shipping and Packing List
Package 1 of 3 contains:
1 − Assembled unit (vent adapters are factory-installed) 1 − Flexible gas connector
Package 2 of 3 contains:
1 − Filter box assembly
Package 3 of 3 contains:
1 − Blower drive kit consisting of:
1 − Blower motor
1 − Motor pulley
1 − Belt
1 or 3 − Transformer(s)
1 − Bag assembly containing wiring parts
1 − Bag assembly containing securing hardware
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Safety
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
Lennox G24−200 units are CSA international certified to ANSI Z21.47 and CSA 2.3 standard.
In the USA, installation of Lennox gas central furnaces must conform with local building codes. In the absence of local codes, units must be installed in accordance with the current National Fuel Gas Code (ANSI−Z223.1/NFPA54). The National Fuel Gas Code is available from:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA−B149.1 Natural Gas and Pro­pane Installation Codes", local plumbing or waste water codes and other applicable local codes.
Adequate clearance must be made around the air open­ings into the vestibule area. Provisions must be made for proper operation and for combustion air and ventilation air supply according to the current National Fuel Gas Code or CSA-B149 standards.
In the U.S.A, vent installations shall be in accordance with the venting tables provided in this manual and the applica­ble provisions of local building codes. In Canada, vent installations shall be in accordance with the venting tables in the current editions of the CSA B149 codes and the applicable provisions of local building codes.
This furnace is CSA international certified for installation clearances to combustible material as listed on unit rating plate and in table 1. Accessibility and service clearances must take precedence over fire protection clearances.
TABLE 1
INSTALLATION CLEARANCES INCHES (mm)
VENT CONNECTOR TYPE
TYPE C TYPE B1
TOP 1 (25) 1 (25)
FRONT* 3 (76) 3 (76)
BACK 0 0
SIDES 0 0
VENT 6 (152) 1 (25)
FLOOR 0** 0**
* Front clearance must be 24 inches (610mm) minimum for service access.
** For installation on combustible floors, appliance shall not be installed directly on carpeting, tile, or other combustible materi­al other than wood flooring.
Maintain adequate clearance for filter access. See section on Return Air Plenum/Filter Box Installation."
Page 6
Page 7
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are lo­cated no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical dam­age by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149.1 standard.
The furnace must be adjusted to obtain a temperature rise range and within the allowable external static pressure on furnaces with a duct system as listed on unit nameplate.
Installation in parking structures must be in accordance with the Standard for Parking Structures (ANSI/NFPA No. 88A−1991). Installation in repair garages must be in accor­dance with the Standard for Repair Garages (ANSI/NFPA No. 88B−1991).
The G24−200 furnace must be installed so that electrical components are protected from water.
When the furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually oper­ated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT" or COOL" setting.
When installed, the furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
Never test for gas leaks with an open flame. Check all con­nections with a commercially available soap solution made specifically for leak detection.
NOTE − Furnace must be adjusted to obtain a tempera­ture rise (high and low fire) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit operation.
Field wiring connection must meet or exceed specifications of type T wire and withstand a maximum temperature rise of 180°F (82°C).
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside of the space con­taining the furnace, return air shall be handled by a duct(s) sealed to the furnace casing and terminating outside space containing furnace.
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit­tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
Use of this unit as a construction heater or air conditioner is not recommended during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will damage the unit.
If this unit has been used for heating or cooling of buildings or structures under construction, the following conditions must be met or the warranty will be void:
The vent hood must be installed per these installation
instructions.
A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or cooling is not allowed.
A pre−filter must be installed at the entry to the return air
duct.
The return air duct must be provided and sealed to the
unit.
Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.
Air filters must be replaced and pre−filters must be re-
moved upon construction completion.
The input rate and temperature rise must be set per the
unit rating plate.
The heat exchanger, components, duct system, air fil-
ters and evaporator coil must be thoroughly cleaned following final construction clean−up.
The unit operating conditions (including airflow, cool-
ing operation, ignition, input rate, temperature rise and venting) must be verified according to these installa­tion instructions.
NOTE − The Commonwealth of Massachusetts stipu­lates these additional requirements:
Gas units shall be installed by a licensed plumber
or gas fitter only.
The gas cock must be T handle" type.
The Lennox G24−200 furnace may be installed in alcoves, closets, basements, garages and utility rooms.
Page 7
Page 8
This furnace design has not been CSA international certi­fied for installation in mobile homes, recreational vehicles, or outdoors.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements indicated previously, the fol­lowing general recommendations should be considered when installing the Lennox G24−200 furnace.
The furnace should be placed as close to the center of the air distribution system as possible. The furnace should also be located close to the chimney or vent termination point.
Do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.
Do not block furnace combustion air openings with cloth­ing, boxes, doors, etc. Combustion air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900 USA
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, ap­pliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Un­less outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combus­tion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install G24−200 furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with per­mission from the National Fuel Gas Code (ANSI-Z223.1/NFPA54). This reprinted material is not the complete and official position of the ANSI on the refer­enced subject, which is represented only by the standard in its entirety.
In Canada, refer to the standard CSA B149.1 installation code.
CAUTION
Do not install furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
Combustion Air Requirements
Page 8
Page 9
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combus­tion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When fire­places, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to en­sure proper combustion and to prevent a downdraft. Insuf­ficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contami­nants may include bleaches, adhesives, detergents, sol­vents and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Confined Space
A confined space is an area with a volume less than 50 cu­bic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain­ing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 1.
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate di­rectly or by ducts with the outdoors or spaces (crawl or at­tic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the en­closure. See figures 2 and 3. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 4.
Page 9
Page 10
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM INSIDE
CHIMNEY
OR GAS
VENT
G24−200
FURNACE
OPENINGS
(To Adjacent
Room)
NOTE−Each opening shall have a free area of at least one square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of the total input rat­ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm2).
FIGURE 1
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec­tive covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
EQUIPMENT IN CONFINED SPACE ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
CHIMNEY OR
GAS VENT
VENTILATION LOUVERS
(Each end of attic)
G24−200
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
OUTLET
AIR
INLET
AIR
FIGURE 2
Page 10
Page 11
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
CHIMNEY
OR GAS
VENT
OUTLET
AIR
G24−200
FURNACE
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip­ment in the enclosure.
VENTILATION LOUVERS
(Each end of attic)
INLET AIR
(Ends 12 in.
above bottom)
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do­ing so will adversely affect the operation of the safety control devices, which could result in personal inju­ry or death.
The Lennox G24−200 upflow gas furnace can be installed with rear or bottom return air. If unit is installed on a platform with bottom return air, furnace/filter box must be sealed airtight at the platform to ensure proper and safe operation.
Select a location that allows for required clearances listed on unit rating plate. Also consider gas supply connections, electrical supply, vent connection, installation and service clearances [24 inches (610mm) at unit front] and filter ac­cessibility.
The furnace must be leveled using shims or leveling bolts (field provided). The corner gussets provided in the furnace base will accept leveling bolts.
FIGURE 3
EQUIPMENT IN CONFINED SPACE
(ALL AIR FROM OUTSIDE)
CHIMNEY
OR GAS
VENT
G24−200
FURNACE
NOTE−Each air duct opening shall have a free area of at least one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each open­ing shall have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.
OUTLET AIR
INLET AIR
FIGURE 4
Return Air Plenum / Filter Box Installation
Return air openings are provided at rear and in bottom of unit. A return air closure panel is shipped secured to the rear opening.
A − Bottom Return Air (Refer to figure 5)
1 − Determine the location of the furnace/filter box.
2 − Cut 50-5/8 x 26-1/8 (128.6cm x 66.4cm) opening in the
return air platform.
3 − Fabricate the return air plenum with right angle flanges
and insert into the floor opening.
4 − Remove filter box access door and filters.
5 − Apply adhesive-backed foam tape to the bottom of the
filter box all around the opening. Position the filter box over the return air plenum. Fasten as required using self-tapping screws provided.
Make sure there is an air tight seal between the platform/return air plenum and filter box.
6 − Apply adhesive-backed foam to the top of the filter box
all around the opening. Place furnace over the filter box with sides and rear of furnace and filter box flush. Fas­ten as required.
Make sure there is an air tight seal between the fur­nace and the filter box.
Page 11
Page 12
7 − Install the filters and the filter access door.
BOTTOM RETURN AIR FILTER BOX INSTALLATION
2-3/4
(70)
1
(25)
4-3/4 (121)
ADHESIVE­BACKED FOAM TAPE
RETURN AIR PLENUM
29-1/4 (743)
27-1/4 (692)
26-1/4 (667)
26-1/8 (664) x 50-5/8 (1286)
Floor Opening
Furnace
Opening
Filter Box
Opening
AIR
FLOW
UNIT
1
(25)
FILTER BOX
PLATFORM
INCHES (mm)
SIDE VIEW
FIGURE 5
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace. In platform installations with bottom return air, the furnace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or proper­ty damage could result.
Page 12
Page 13
B − Rear Return Air (Refer to figure 6)
Duct System
REAR RETURN AIR FILTER BOX INSTALLATION
UNIT
FILTER
ACCESS
PANEL
REPOSITION REAR PANEL WITH FLANGES AS SHOWN.
(Seal air-tight with adhesive-backed foam tape.)
FOUR FILTERS (Filters may be also installed through top of frame)
ADHESIVE-BACKED
FOAM TAPE
(Apply to filter box)
FILTER
ACCESS
PANEL
RETURN AIR FILTER BOX
FIGURE 6
1 − Determine the location of the furnace/filter box.
NOTE − Filter box can be installed with right or left side filter access or top-rear filter access. Allow enough room when positioning the furnace for filter access.
2 − Remove the bottom-rear panel from the furnace and
re-install on the bottom of the furnace as shown. Seal
air-tight with adhesive-backed foam tape.
3 − Apply adhesive-backed foam tape to the filter box (side
facing furnace) all around the opening. Refer to figure 6.
4 − Position the filter box over the furnace return air open-
ing. The top of the filter box should be in the up" posi­tion and the filter box and the furnace edges flush at the sides and bottom.
5 − Fasten using self-drilling self-tapping screws provided
with the filter box. Use the frame clearance holes as a guide.
6 − Install the four filters and the filter access door.
7 − Size the return air plenum to fit the filter box and then
seal the joint air tight.
Size and install supply and return air duct system using in­dustry-approved standards that result in a quiet and low­static system with uniform air distribution.
Supply Air Plenum
Furnaces installed without a cooling coil require the installa­tion of a removable access panel in the supply air duct. The access panel should be large enough to permit inspection (ei­ther by smoke or reflected light) of the heat exchanger for leaks after installation. The furnace access panel must al­ways be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
In applications requiring air conditioning, see installation instructions provided with C17-090/120 evaporator coil for supply air plenum size and connection.
Return Air Plenum
Return air must not be drawn from a room where this furnace, or any other gas appliance (i.e., a water heat­er), is installed. When return air is drawn from a room, a
negative pressure is created in the room. If a gas ap­pliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
Size and install return air plenum as indicated in previous section.
Blower Motor / Drive Installation
A − Motor Installation
Refer to figure 7.
1 − Check the box on the rating plate to indicate which of
the drive kits are being installed.
2 − Secure the blower motor to the motor base with the
hardware provided.
3 − Slide the motor pulley onto the motor shaft and align
with the blower pulley.
4 − Install the belt.
5 − Refer to Setting Blower CFM Section" to determine
blower RPM setting and the following section for ad­justing belt tension.
Page 13
Page 14
TYPICAL MOTOR/DRIVE INSTALLATION
MOTOR PULLEY
MOTOR
MOTOR SECURING HARDWARE
MOTOR BASE
Example: Deflection distance of a 400mm span would be 6mm.
3 − Measure the belt deflection force. For a used belt, the
deflection force should be 5 lbs. (35kPa). A new belt deflection force should be 7 lbs. (48kPa).
A force below these values indicates an under-ten­sioned belt. A force above these values indicates an over-tensioned belt.
MEASURE BELT TENSION
BELT TENSION ADJUSTING HARDWARE
PULLEY ALIGNMENT
BLOWER PULLEY
MOTOR PULLEY
FIGURE 7
B − Blower Belt Adjustment
Maximum life and wear can be obtained from belts only if the proper pulley alignment and belt tension are main­tained. Tension new belts after a 24 to 48 hour period of op­eration. This will allow the belt to stretch and seat in the grooves.
1 − Loosen belt adjusting hardware. See figure 7.
2 − To increase belt tension −
Move the motor base away from the blower housing.
To loosen belt tension −
Move the motor toward the blower housing.
3 − Tighten the belt adjusting hardware.
C − Check Belt Tension
Over-tensioning a belt shortens belt and bearing life. Check belt tension as follows:
1 − Measure span length X. See figure 8.
2 − Apply perpendicular force to the center of span (X)
with enough pressure to deflect belt 1/64 inch for ev­ery inch of span length or 1.5mm per 100mm of span length.
Example: Deflection distance of a 40 inch span would be 40/64 inch or 5/8 inch.
FORCE
DEFLECTION 1/64 INCH PER INCH OF SPAN
OR 1.5 mm PER 100 mm OF SPAN
FIGURE 8
Venting
A vent adapter is factory-installed on each of the combus­tion air blower outlets. Modification of, or removal of the
adapter(s) will cause unsafe unit operation and will void CSA unit certification. The vent adapter does not re-
quire insulation.
The G24−200 units are classified as fan assisted Category I type furnaces when vertically vented according to the latest edition of ANSI Z21.47 Gas-fired Central Furnace Standard in the USA and the current standard CSA 2.3 Gas-fired Cen­tral Furnace in Canada. The definition of a fan assisted fur­nace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger.
NOTE − Use these instructions as a guide. They do not su­persede local codes.
The vent sizing tables in this manual have been extracted from the Current edition of the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper application, termination, construction and location of vents must conform to local codes having jurisdiction. In the absence of local codes, the NFGC serves as the defining document in the U.S.A., while the CSA−B149 codes serve as the defining docu­ments in Canada.
Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.
Install the first vent connector elbow a minimum of 6 in. (152mm) from the furnace vent outlet.
Page 14
Page 15
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent a G24−200 furnace:
Masonry chimneys used to vent Category I central fur­naces must be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 9 and 10 for common venting.
A Category I appliance must never be connected to a chim­ney that is servicing a solid−fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed.
A fan−assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:
1 − The chimney is currently serving at least one drafthood
equipped appliance.
2 − The vent connectors and chimney are sized according
to the provided venting tables for the USA, and the ap­propriate venting tables in the standards of CSA B149.1 of the Natural Gas and Propane Installation Code in Canada.
A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof assembly ac­cording to the terms of their respective listings and the vent manufacturer’s instructions.
Do not install a manual damper, barometric draft regula­tor, or flue restrictor between the furnace and the chimney.
If type B1 double-wall vent is used inside a chimney, no oth­er appliance can be vented into the chimney. Outer wall of type B1 vent pipe must not be exposed to flue products.
Insulation for the flexible vent pipe must be an encapsu­lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 9.
The space between the liner and the chimney wall should NOT be insulated with puffed mica or any other loose granular insulating material.
If B1 vent or an insulated flexible vent pipe cannot be used as liners, the chimney must be rebuilt to accommodate one of these methods or some alternate approved method must be found to vent the appliance.
IMPORTANT
SINGLE appliance venting of a fan-assisted furnace into a tile-lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system, sized according to the provided venting tables.
COMMON VENTING USING METAL−LINED MASONRY CHIMNEY
NOTE 1 − Refer to the provided venting tables for installations in the USA and the venting tables in CSA−B149.1 for installations Canada.
NOTE 2 − Either single-walled or double-walled vent connector may be used. Refer to the ca­pacity requirements shown in the provided venting tables for installations in USA and the venting tables in current CSA−B149.1 for installations in Canada.
5 FT.
(1.5m)
MIN.
VENT
CONNECTOR
SEE NOTE 2
MIN. LENGTH − AS SHORT
When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials or replaced with a gas vent or chimney suitable for venting G24−200 units. The chimney passage­way must be checked periodically to ensure that it is clear and free of obstructions.
MAX. LENGTH − SEE
NOTE 1 BELOW.
AS PRACTICAL
G24−200
SEALED
EXTERIOR CHIMNEY WITH
B1" VENT OR INSULATED
FLEXIBLE VENT PIPE
PERMANENTLY
SEALED FIRE-
PLACE OPENING
JOIN HEAT
SECTIONS
WITH A ’TEE−Y’
FIGURE 9
Page 15
Page 16
COMMON VENTING USING TILE−LINED INTERIOR MASONRY CHIMNEY AND COMBINED VENT CONNECTOR
NOTE 1 − Refer to provided venting tables for installations in the USA and the vent­ing tables in current CSA−B149.1 for installations in Canada.
VENT
CONNECTOR
SEE NOTE 2
Note 2 − Either single-walled or double-walled vent connector may be used. Refer to the capacity re­quirements as shown in the provided venting tables for installations in USA and the venting tables in cur­rent CSA−B149.1 for installations in Canada.
MIN. LENGTH = AS SHORT AS PRACTICAL.
FOR MAX. LENGTH SEE NOTE 1
JOIN HEAT SECTIONS
WITH A ’TEE−Y’
G24−200
INTERIOR TILE−LINED
MASONRY CHIMNEY
NOTE − The chimney must be properly sized per provided vent­ing tables and lined with a listed metal lining system.
PERMANENTLY SEALED
FIREPLACE OPENING
FIGURE 10
General Venting Requirements
All G24−200 furnaces must be vented according to these instructions.
1 − Vent diameter recommendations and maximum al-
lowable piping runs are found in the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149.1 of the Natural Gas and Propane Installation Code for Canada.
2 − In no case should the vent or vent connector diameter
be less than the diameter specified in the provided venting tables for the USA, and the appropriate vent­ing tables in the standards of CSA B149.1 of the Natu­ral Gas and Propane Installation Code for Canada.
3 − Single Appliance Vent − If the vertical vent or tile-lined
chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to de­termine the minimum vent capacity and the vent
connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, how-
ever, shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood out­let area or flue collar area unless designed according to approved engineering methods.
4 − Multiple Appliance Vents − The flow area of the largest
section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, flue collar area or drafthood outlet area unless designed according to engineering methods.
5 − The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning, and replacement.
6 − Single appliance venting configurations with zero lat-
eral lengths, see tables 3 and 4, are assumed to have no elbows in the vent system. For all other vent config­urations, the vent system is assumed to have two 90 elbows. For each additional 90 elbow or equivalent (for example two 45 elbows equal one 90 elbow) be­yond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi­mum listed capacity).
7 − The common venting tables 5, 6, 7, and 8 were gener-
ated using a maximum horizontal vent connector length of 1-1/2 feet (18 inches) for each inch of con­nector diameter as follows:
TABLE 2
Connector
Diameter
inches (mm)
3 (76) 4−1/2 (1.37)
4 (102) 6 (1.83)
5 (127) 7−1/2 (2.29)
6 (152) 9 (2.74)
7 (178) 10−1/2 (3.20)
Maximum Horizontal
Connector Length
feet (m)
8 − If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90 elbows (0.80 x maximum common vent ca­pacity). The horizontal length of the offset shall not ex­ceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.
9 − The vent pipe should be as short as possible with
the least number of elbows and angles to do the job. The vent connector should be routed to the vent using the shortest possible route.
Page 16
Page 17
10− A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance. See local and national installation codes for support intervals and methods. National installation code in the U.S.A is current edition of National fuel Gas Code (ANSI−Z223.1/NFPA54). National installation codes in Canada are current editions of CSA−B149 codes.
11− Vent connectors shall be firmly attached to furnace flue
collars by sheet metal screws or other approved means, except vent connectors of listed Type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by sheet metal screws or other approved means.
15− Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
16− If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10 percent, the equivalent of one 90 elbow (0.90 x maximum common vent capacity).
17− The common vent diameter must always be at least as
large as the largest vent connector diameter.
18− In no case, shall the vent connector be sized more than
two consecutive table size diameters over the size of the flue collar outlet.
12− When the vent connector used for Category I ap-
pliances must be located in or pass through a crawl space or other areas which may be cold, that portion of the vent connector shall be constructed of listed double−wall Type B vent material or material having equivalent insulation qualities.
13− All venting pipe passing through floors, walls, and ceil-
ings must be installed with the listed clearance to com­bustible materials and be fire stopped according to local codes. In absence of local codes, refer to NFGC (Z223.1/NFPA54).
14− No portion of the venting system can extend into, or pass
through any circulation air duct or plenum.
19− Do not install a manual damper, barometric draft regu-
lator or flue restrictor between the furnace and the chimney.
20− When connecting this appliance to an existing dedicated
or common venting system, the venting system must be inspected for signs of corrosion and general condition. The sizing of the vent system must be reviewed and must conform to these instructions and the provided venting tables for the USA, and the appropriate venting tables in the standards of CSA B149.1 of the Natural Gas and Propane Installation Code for Canada. If the ex­isting system is in conflict with these requirements, the venting system must be resized.
Page 17
Page 18
TABLE 3
(
)L(
)
(feet)
(feet)
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH TYPE B DOUBLE-WALL CONNECTORS
SERVING A SINGLE CATEGORY I APPLIANCE
Vent and Connector Diameter − D (inches)
Height
H
feet
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90 elbows. For each additional 90 elbow or equivalent (for example two 45 elbows equal one 90 elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
feet
0 0 78 0 152 0 251 0 375
2 13 51 18 97 27 157 32 232
4 21 49 30 94 39 153 50 227
6 25 46 36 91 47 149 59 223
0 0 84 0 165 0 276 0 415
2 12 57 16 109 25 178 28 263
5 23 53 32 103 42 171 53 255
8 28 49 39 98 51 164 64 247
0 0 88 0 175 0 295 0 447
2 12 61 17 11 8 23 194 26 289
5 23 57 32 11 3 41 187 52 280
10 30 51 41 104 54 176 67 267
0 0 94 0 191 0 327 0 502
2 11 69 15 136 20 226 22 339
5 22 65 30 130 39 219 49 330
10 29 59 40 121 51 206 64 315
15 35 53 48 112 61 195 76 301
0 0 97 0 202 0 349 0 540
2 10 75 14 149 18 250 20 377
5 21 71 29 143 38 242 47 367
10 28 64 38 133 50 229 62 351
15 34 58 46 124 59 217 73 337
20 48 52 55 116 69 206 84 322
0 0 100 0 213 0 374 0 587
2 9 81 13 166 14 283 18 432
5 21 77 28 160 36 275 45 421
10 27 70 37 150 48 262 59 405
15 33 64 44 141 57 249 70 389
20 56 58 53 132 66 237 80 374
30 NR NR 73 11 3 88 214 104 346
3 Inch 4 Inch 5 Inch 6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MIN MAX MIN MAX MIN MAX MIN MAX
Page 18
Page 19
TABLE 4
(
)L(
)
(feet)
(feet)
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH SINGLE-WALL METAL CONNECTORS
SERVING A SINGLE CATEGORY I APPLIANCE
Vent and Connector Diameter − D (inches)
Height
H
feet
6
8
10
15
20
30
NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent configurations, the vent system is assumed to have two 90 elbows. For each additional 90 elbow or equivalent (for example two 45 elbows equal one 90 elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
feet
0 38 77 59 151 85 249 126 373
2 39 51 60 96 85 156 123 231
4 NR NR 74 92 102 152 146 225
6 NR NR 83 89 11 4 147 163 220
0 37 83 58 164 83 273 123 412
2 39 56 59 108 83 176 121 261
5 NR NR 77 102 107 168 151 252
8 NR NR 90 95 122 161 175 243
0 37 87 57 174 82 293 120 444
2 39 61 59 11 7 82 193 119 287
5 52 56 76 111 105 185 148 277
10 NR NR 97 100 132 171 188 261
0 36 93 56 190 80 325 116 499
2 38 69 57 136 80 225 115 337
5 51 63 75 128 102 216 144 326
10 NR NR 95 11 6 128 201 182 308
15 NR NR NR NR 158 186 220 290
0 35 96 54 200 78 346 114 537
2 37 74 56 148 78 248 113 375
5 50 68 73 140 100 239 141 363
10 NR NR 93 129 125 223 177 344
15 NR NR NR NR 155 208 216 325
20 NR NR NR NR 186 192 254 306
0 34 99 53 211 76 372 110 584
2 37 80 55 164 76 281 109 429
5 49 74 72 157 98 271 136 417
10 NR NR 91 144 122 255 171 397
15 NR NR 115 131 151 239 208 377
20 NR NR NR NR 181 223 246 357
30 NR NR NR NR NR NR NR NR
3 Inch 4 Inch 5 Inch 6 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MIN MAX MIN MAX MIN MAX MIN MAX
Page 19
Page 20
TABLE 5
V
C
Height
Rise
6
V
Height
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH TYPE B DOUBLE-WALL CONNECTORS
SERVING TWO OR MORE CATEGORY I APPLIANCES
VENT CONNECTOR CAPACITY
ent
Height
H
(feet) (feet)
6
8
10
15
20
30
onnector
Rise
4 Inch 5 Inch 6 Inch 7 Inch
R
MIN MAX MIN MAX MIN MAX MIN MAX
1 35 66 46 106 58 164 77 225
2 37 75 48 121 60 183 79 253
3 38 81 49 132 62 199 82 275
1 35 72 49 11 4 64 176 84 243
2 36 80 51 128 66 195 86 269
3 37 87 53 139 67 210 88 290
1 34 78 49 123 65 189 89 257
2 36 86 51 136 67 206 91 282
3 37 92 52 146 69 220 94 303
1 33 89 47 142 64 220 88 298
2 35 96 49 153 66 235 91 320
3 36 102 51 163 68 248 93 339
1 33 99 46 157 62 246 86 334
2 34 105 48 167 64 259 89 354
3 35 11 0 50 176 66 271 91 371
1 31 11 3 45 181 60 288 83 391
2 33 11 8 47 190 62 299 85 408
3 34 123 48 198 64 309 88 423
Vent and Connector Diameter − D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 6
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH TYPE B DOUBLE-WALL CONNECTORS
SERVING TWO OR MORE CATEGORY I APPLIANCES
COMMON VENT CAPACITY
ent
Height
H
(feet)
6 92 81 140 11 6 204 161 309 248
8 101 90 155 129 224 178 339 275
10 110 97 169 141 243 194 367 299
15 125 112 195 164 283 228 427 352
20 136 123 215 183 314 255 475 394
30 152 138 244 210 361 297 547 459
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
4 Inch 5 Inch 6 Inch 7 Inch
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter − D (inches)
Page 20
Page 21
TABLE 7
V
C
Height
Rise
6
V
Height
CAPACITY OF TYPE B DOUBLE-WALL VENT WITH SINGLE-WALL METAL CONNECTORS
SERVING TWO OR MORE CATEGORY I APPLIANCES − VENT CONNECTOR CAPACITY
ent
Height
H
(feet) (feet)
6
15
30
onnector
Rise
4 Inch 5 Inch 6 Inch 7 Inch
R
MIN MAX MIN MAX MIN MAX MIN MAX
1 NR NR NR NR NR NR 207 223
2 NR NR NR NR 168 182 215 251
3 NR NR 121 131 174 198 222 273
1 79 87 11 6 138 177 214 238 291
2 83 94 121 150 185 230 246 314
3 87 100 127 160 193 243 255 333
1 77 11 0 11 3 175 169 278 226 380
2 81 11 5 11 7 185 177 290 236 397
3 85 11 9 122 193 185 300 244 412
Vent and Connector Diameter − D (inches)
Appliance Input Rating in Thousands of Btu Per Hour
TABLE 8
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH SINGLE-WALL METAL CONNECTORS
SERVING TWO OR MORE CATEGORY I APPLIANCES − COMMON VENT CAPACITY
ent
Height
H
(feet)
6 89 78 136 11 3 200 158 304 244
8 98 87 151 126 218 173 331 269
10 106 94 163 137 237 189 357 292
15 121 108 189 159 275 221 416 343
20 131 118 208 177 305 247 463 383
30 145 132 236 202 350 286 533 446
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
4 Inch 5 Inch 6 Inch 7 Inch
Appliance Input Rating in Thousands of Btu Per Hour
Common Vent Diameter − D (inches)
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas ap­pliances, the venting system is likely to be too large to prop­erly vent the remaining attached appliances. The following test should be conducted while each appliance in operation and the other appliances not in operation remain con­nected to the common venting system. If the venting sys­tem has been installed improperly, the system must be corrected as indicated in the general venting requirements section.
1 − Seal any unused openings in the common venting
system.
2 − Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re­striction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − To the extent that it is practical, close all building doors
and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the build­ing. Turn on clothes dryers and any appliances not con­nected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom ex-
hausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance will operate continuously.
5 − Test for spillage of the flue gases at the draft hood relief
opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6 − After determining that each appliance remaining con-
nected to the common venting system properly vents when tested as indicated instep 3, return doors, windows, exhaust fans, fireplace dampers and any other gas−burn­ing appliance to their previous condition of use.
7 − If improper venting is observed during any of the
above tests, the common venting system must be cor­rected. The common venting system should be re­sized to approach the minimum size as determined by using the appropriate tables in appendix G in the cur­rent standards of the National Fuel Gas Code ANSI Z223.1 /NFPA54 in the USA, and the appropriate Category 1 Natural Gas appliances venting sizing tables in the current standards of the CSA−B149.1 Natural Gas Installation Code in Canada.
Page 21
Page 22
Testing for Proper Venting and Sufficient Combustion Air (Non−Direct Vent Applications Only)
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monox­ide poisoning or death. The following steps shall be followed for each ap­pliance connected to the venting system being placed into operation, while all other appliances con­nected to the venting system are not in operation.
After the furnace has been started, the following test should be conducted to ensure proper venting and suffi­cient combustion air has been provided to the furnace, as well as to other gas-fired appliances which are separately vented. The test should be conducted while all appliances (both in operation and those not in operation) are con­nected to the venting system being tested.
1 − Seal any unused openings in the venting system.
2 − Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or re­striction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − To the extent that it is practical, close all building doors
and windows and all doors between the space in which the appliances connected to the venting system are lo­cated and other spaces of the building.
4 − Close fireplace dampers.
5 − Turn on clothes dryers and any appliances not con-
nected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
6 − Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so appliance will operate continuously.
7 − Test for spillage of flue gases at the draft hood relief
opening after 5 minutes of main burner operation. Use the flame of match or candle, or smoke from a ciga­rette, cigar.
8 − If improper venting is observed during any of the
above tests, the venting system must be corrected or sufficient combustion/make-up air must be provided. The venting system should be re-sized to approach the minimum size as determined by using the ap­propriate tables in appendix G in the current stan­dards of the National Fuel Gas Code ANSI−Z223.1/NPFA 54 in the U.S.A., and the ap­propriate Natural Gas and Propane appliances vent­ing sizing tables in the current standard of the CSA−B149.1 Natural Gas and Propane Installation Code in Canada.
9 − After determining that each appliance remaining
connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their pre­vious condition of use.
General Guidelines for Vent Terminations for Non-Direct Vent Installations.
In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the out­doors. The furnace is then classified as a non-direct vent, Category IV gas furnace. In Non-Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and cur­rent standards CSA−B149.1 of the Natural Gas and Pro­pane Installation Codes in Canada for details.
Position termination end according to location given in fig­ure 11. In addition, position termination end so it is free from any obstructions and above the level of snow accu­mulation (where applicable). The termination should be at least 12 inches (305mm) from any opening through which flue products could enter the building.
Page 22
Page 23
VENT TERMINATION CLEARANCES
FOR INSTALLATIONS IN THE USA AND CANADA*
VENT TERMINATION
C
A − Clearance above grade − 12 in. (305mm) minimum. B − Clearance to window or door
for vent installations in USA − 48 in. (1219mm) minimum horizontal and below, 12 in. (305mm) minimum above. for vent installations in Canada − 12 in. (305mm) minimum for appliances 100,000 Btuh (30 kW); 36 in. (0.9m) minimum for appliances > 100,000 Btuh (30
kW). C − Do not position terminations directly under roof eaves. D − Clearance to electric meters, gas meters, regulators, and
relief equipment
for vent installations in USA − 48 in (1219mm) minimum.
for vent installations in Canada − see current edition of
CSA B149 Code.
AIR INLET OF OTHER APPLIANCE
less than 10 ft (3.048M)
D
D
E
E − Clearance to non−mechanical air supply inlet
for vent installations in USA − 48 in. (1219mm) minimum hor­izontal and below, 12 in. (305mm) minimum above. for vent installations in Canada − 12 in. (305mm) minimum for appliances 100,000 Btuh (30 kW); 36 in. (0.9m) minimum for appliances > 100,000 Btuh (30 kW).
F − Clearance to mechanical air supply inlet −−
for vent installations in USA − 36 in. minimum (914mm).
G − Clearance to mechanical air supply inlet −−
for vent installations in Canada − 72 in. (1829mm) minimum.
H − Do not point terminations into recessed areas such as window
wells, stairwells or alcoves.
J − Do not position terminations directly above a walkway.
F
G
* Note −
(I) Dimensions are from the current edition of The National Fuel Gas Code − ANSI-Z223.1/NFPA 54 for USA installations. In Canada, refer to current edition of CSA building code. Local codes or regulations may require different clearances.
(II) In Non-Direct Vent installations, combustion air is taken from indoors and the flue gases are discharged to the outdoors.
FIGURE 11
Page 23
Page 24
Horizontal Venting
This furnace design is certified by CSA international for horizontal venting through an outside wall, only with the use of two Field Controls Company Model SWG-4L side­wall venting kits, available from any Lennox Dealer Service Center. No other Field brand venting kits or any other manufacturer’s venting kits are acceptable. Horizontal venting of this furnace without the use of the above stated kits is prohibited.
NOTE − Each heat section of the G24−200 unit re­quires its own sidewall venting kit. The two venting systems shall be completely separate starting at the outlet of each heat section and ending with the vent terminal of each Field Controls Venting Kit. (See fig- ure 12 for field wiring of the two sidewall horizontal venting kits.)
WIRING FOR SIDEWALL VENTING KITS
(Two kits are required − one for each heat section.)
24 VAC
THERMOSTAT
W2 R Y2 GCW1 Y1
When horizontally vented, the minimum clearance for terminations from electric meters, gas meters, regula­tors and relief equipment is 4 ft. (1.2m) for US installa­tions. Refer to the current CSA−B149.1 for installations in Canada or with authorities having local jurisdiction.
At vent terminations, care must be taken to maintain pro­tective coatings over building materials (prolonged expo­sure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8 m) of a condensing unit be­cause the condensate can damage the painted coating.
FIELD INSTALLED WIRING
FACTORY INSTALLED WIRING
CK−43 CONTROL BOX
PRESSURE
SWITCH
C
NO
L1 MN
2
1
354
RELAY
T1 T2 T3
M
SWG
POWER
VENTER
MOTOR
W2 R Y2 G
W1 Y1
CONNECTIONS IN FURNACE JUNCTION BOX
C
C
TERMINAL STRIP FOR THERMOSTAT
L2
L1
120VAC
CK−43 CONTROL BOX
PRESSURE
SWITCH
NO
L1 MN
2
1
354
RELAY
T1 T2 T3
M
SWG
POWER
VENTER
MOTOR
FIGURE 12
Page 24
Page 25
Gas Piping
NOTE − The flexible connector supplied with the unit must not be modified and must be installed between the two combination gas controls.
1 − Piping can be installed to enter either side of cabinet.
Refer to figure 13. Left-Side Installation − Install flexible connector (supplied with unit) between gas valves and connect supply piping as shown.
Right-Side Installation −
a − Remove tee and 1/2 in. NPTx1/2 in. male brass
fitting from left side gas valve.
b − Remove 1/2 in. elbow and nipple from right side
gas valve and re-install on left side gas valve fac­ing toward right side cabinet entry.
c − Re-install tee and 1/2 in. NPTx1/2 in. male brass
fitting on right side gas valve with 3/4 in. side of tee facing the right side cabinet entry.
d − Install flexible connector (supplied with unit) be-
tween gas valves and connect supply piping as shown.
NOTE − Flexible gas connector must be routed so that connector does NOT come in contact or interfere with any wiring.
2 − When connecting the gas supply, factors such as
length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 9 lists recommended pipe sizes for typical ap­plications.
3 − The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumbwaiters or elevator shafts.
4 − The piping should be sloped 1/4 inch (6.4 mm) per 15
feet (4.57 m) upward toward the meter from the fur­nace. The piping must be supported at proper inter­vals [every 8 to 10 feet (2.44 to 3.01 m) using suitable hangers or straps. A drip leg should be installed in ver­tical pipe runs to the unit.
5 − In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by the installer) external to the unit. Union must be of the ground joint type.
6 − A 1/8" N.P.T. plugged tap is located on gas valve for
test gauge connection. See figure 20 for tap location.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­leum gases.
LEFT SIDE GAS LINE INSTALLATION
MANUAL MAIN SHUT-OFF VALVE
1/2 in. NPT X 1/2 in. MALE
BRASS FITTING
(Provided with flex connector)
DRIP LEG
TEE
AUTOMATIC GAS VALVE
(WITH MANUAL SHUT-OFF VALVE)
FIELD PROVIDED AND
(3/4 in. X 1/2 in. X 1/2 in.)
GROUND JOINT UNION
FLEXIBLE CONNECTOR
SHIPPED WITH UNIT
AND FIELD INSTALLED
INSTALLED
1/2 in. STREET
ELBOW
RIGHT SIDE GAS LINE INSTALLATION
(See item # 1 on previous page for installation instructions)
FLEXIBLE CONNECTOR SHIPPED WITH UNIT AND FIELD INSTALLED
1/2 in. STREET
ELBOW
AUTOMATIC GAS VALVE
(WITH MANUAL SHUT-OFF VALVE)
1/2 in. NPT X 1/2 in. MALE
FIELD PROVIDED AND
INSTALLED
BRASS FITTING
(Provided with
flex connector)
MANUAL MAIN SHUT-OFF VALVE
(3/4 in. X 1/2 in. X 1/2in. )
DRIP LEG
GROUND JOINT UNION
TEE
FIGURE 13
Page 25
Page 26
TABLE 9
Nominal
Internal
GAS PIPE CAPACITY − FT3/HR (KL/HR)
Nominal Internal
Iron Pipe Size
Inches(mm)
1/4
(6.35)
3/8
(9.53)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1−1/4
(31.75)
1−1/2
(38.1)
2
(50.8)
2−1/2
(63.5)
3
(76.2)
4
(101.6)
Diameter
Inches(mm)
.364
(9.246)
.493
(12.522)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
10
(3.048)20(6.096)30(9.144)40(12.192)50(15.240)60(18.288)70(21.336)80(24.384)90(27.432)
43
(1.13)
95
(2.69)
175
(4.96)
360
(10.19)
680
(919.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
29
(.82)
65
(1.84)
120
(3.40)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
24
(.68)
52
(1.47)
97
(2.75)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.
Length of Pipe - Feet (m)
20
(.57)
45
(1.27)
82
(2.32)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
18
(.51)
40
(1.13)
73
(2.07)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
(121.76)
(249.18)
16
(.45)
36
(1.02)
66
(1.87)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
8800
15
(.42)
33
(.73)
61
(1.73)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
14
(.40)
31
(.88)
57
(1.61)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
13
(.37)
29
(.82)
53
(1.50)
110
(3.11)
205
(5.80)
430
(12.18)
650
(18.41)
1220
(34.55)
1950
(55.22)
3450
(97.69)
7200
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
Leak Check
After gas piping is completed, carefully check all piping connections (factory- and field-installed) for gas leaks. Use a leak detecting solution or other preferred means.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi­cally for the detection of leaks to check all connec­tions. A fire or explosion may result causing proper­ty damage, personal injury or loss of life.
NOTE − In case emergency shutdown is required, shut off the main manual gas valve and disconnect the main power to the furnace. These devices should be properly labeled by the installer.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures equal to or less than 1/2 psig (3.48 kPa).
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 14. Gas valves can be damaged if subjected to more than 1/2 psig (3.48 kPa).
MANUAL MAIN
SHUT−OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
FIGURE 14
ISOLATE
GAS
VALVES
FURNACE
Page 26
Page 27
Electrical
CAUTION
Electrostatic discharge can affect electronic com­ponents. Take precautions during furnace installa­tion and service to protect the furnace’s electronic controls. Precautions will help to avoid control ex­posure to electrostatic discharge by putting the fur­nace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an un­painted unit surface, such as the gas valve or blow­er deck, before performing any service procedure.
Refer to figure 15, 16, and 17 for field wiring and figures 18 and 19 for schematic wiring diagram and troubleshooting.
1 − Select circuit protection and wire size according to re-
quirements listed on unit rating plate.
2 − Install a separate disconnect switch (protected by ei-
ther fuse or circuit breaker) near the unit so power can be turned off for servicing.
3 − Make power supply wire connections at unit make-up
boxes (both left and right side boxes are provided).
4 − Install the room thermostat according to the instruc-
tions provided with the thermostat and make connec­tions according to the appropriate field wiring diagram. Install a field-provided 150 ohm, 10 watt re­sistor (Lennox part number P−8−6256) in two-stage applications when using an electro-mechanical ther­mostat.
5 − All applications require a control transformer to power
the furnace’s 24 volt circuit. In all applications except
TABLE 10
DRIVE KIT TRANSFORMER VOLTAGES AND PART NUMBERS
Drive Kit
Model No.
Furnace
Supply
Voltage,
Phase,
Frequency
**Induced Draft Blower Autotransformers Control Circuit Transformer
Transformer Part Number & (Quantity)
Wiring
Diagram
Designation
Input
Voltage
those where a 208/230 volt power supply is used, an autotransformer is required to power each of the in­duced draft blowers. These transformer(s) are pro­vided in the drive kit which has been selected for use with the furnace. Transformer part numbers and volt­ages are given in table 10. Install the transformer(s) in the control box using the holes pre-drilled for them. Select a field wiring diagram according to the power supply voltage and phase being used (see figure 15, 16, or 17), and make the wiring connections between the transformers and the furnace.
6 − Select a field wiring diagram according to the power
supply voltage and phase being used (see figure 15, 16, or 17), and make wiring connections between the blower motor and the furnace. The connecting wires are provided in the drive kit.
7 − An accessory relay (K109) is provided with the
G24−200 furnace. Any accessory with a rated voltage equal to the supply voltage can be connected to termi­nal 5" of this relay. The relay is energized with the blower.
8 − To add an accessory which is energized on a heating
demand (such as a humidifier), a relay with coil wired to terminal W1" of the TB1 terminal strip must be add­ed.
9 − The TB1" terminal strip includes a terminal for econo-
mizer connection. See the field wiring diagrams.
10 −Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA or current Canadian Electric Code part 1 (CSA standard C22.1) for Canada.
Output
Voltage
Transformer
Part Number
Wiring
Diagram
Designation
Primary
Voltage
Secondary-
Voltage
DKG24−200−1
DKG24−200−2
DKG24S−200−3,
DKG24−200−6
DKG24S−200−4,
DKG24−200−7
DKG24S−200−5,
DKG24−200−8
*Note − This transformer has a nominal 230 volt output rating and a 460 volt input rating; however, when wired to the furnace as shown in figure 15, a 115 volt input will produce a 230 volt output. **Note − The induced draft blowers are rated at 230 volts, single phase, 60 hz.
120v,
1ph, 60hz
208/230v,
1ph, 60hz
208/230v,
3ph, 60hz
460v,
3ph, 60hz
575v,
3ph, 60hz
54G5201*
(2)
− − − − − − − − − − − − − − − −
− − − − − − − − − − − − − − − −
54G5201
(2)
54G3101
(2)
T3, T13 115* 230*
T3, T13 460 230
T3, T13 575 230
LB−66256G
(99K0601)
LB−66256G
(99K0601)
LB−66256K
(13H2801)
LB−66256H
(51H7901)
LB−66256J
(66J5401)
T1 120 24
T1 208 or 240 24
T1 208 or 240 24
T1 480 24
T1 600 24
Page 27
Page 28
G24−200 FIELD WIRING DIAGRAM (120V SINGLE PH 60HZ)
COMBUSTION
AIR BLOWER
(Alternate make-up box right side)
MAKE-UP BOX
T3 TRANSFORMER
TERMINAL STRIP
See Note 1
RELAY
K109
RELAY
K105
RELAY
K13
CONTROL BOX
RED
L1
RED
L3
RED
See Note 3
5
7
7
4
PRIMARY
LIMIT
GAS
VALV E
PRESSURE
IGNITION
CONTROL
DOOR
INTERLOCK
RED
TB34
1 1
2
2
YELLOW YELLOW
BLUE
BLUE
GROUND LUG
BLACK
K3 CONTACTOR
T1 TRANSFORMER
24v: blue − yellow
120v: black − white
SWITCH
BOARD
BLACK
RED
WHITE
WHITE
COMBUSTION
AIR BLOWER
FLAME ROLLOUT
DOOR
INTERLOCK
J84
31 2 4
PLUG
BLUE
WHITE
BLACK
BLUE
L3
L1
L2
T1
T3T2
PRIMARY
LIMIT
GAS
VALV E
SWITCH
T13 TRANSFORMER
See Note 3
RED
C
W1
G
W2
Y1
Y2
R
ECON
TB1 TERMINAL STRIP
PRESSURE
IGNITION
CONTROL
BOARD
RED
L1
RED
L3
MAKE−UP BOX
SWITCH
BLOWER DECK
R3
See Note 2
FUSED OR CIRCUIT BREAKER
DISCONNECT
(Furnished by
installer)
L1 N
GND
(Alternate make-up box left side)
REMOVE FACTORY­INSTALLED JUMPER IN TWO-STAGE MODE
THERMOSTAT
C
W1
G
W2
Y1
Y2
R
ECONOMIZER
NOTES :
BLOWER MOTOR
1 − Relay K109 can be used for an accessory rated at the same voltage as power supply. 2 − Field installed and supplied resistor (R3), is required in two-stage applications when using electro-mechanical thermo-
stat. (Use a 150 ohm, 10 watt resistor − Lennox part number P−8−6256.) 3 − The T3 and T13 transformers (54G5201) are marked as follows: 230v between white and black leads and 460v between
white and red leads. However, in this application, each transformer has been used to supply 230v (available between the white and red leads) to an induce draft blower when 115v is applied between the white and black leads of each transformer.
FIELD-INSTALLED DRIVE KIT COMPONENT
FACTORY INSTALLED
LINE VOLTAGE FIELD INSTALLED 24 VOLTS FIELD INSTALLED
FIGURE 15
Page 28
Page 29
COMBUSTION
AIR BLOWER
PRIMARY
LIMIT
GAS
VALV E
G24-200 FIELD WIRING DIAGRAM
P UNITS − 208/230V 1PH 60 HZ
Y UNITS − 208/230V 3PH 60HZ
PRESSURE
SWITCH
IGNITION
CONTROL
BOARD
COMBUSTION
AIR BLOWER
GAS
VALV E
PRIMARY
LIMIT
PRESSURE
IGNITION
CONTROL
BOARD
SWITCH
Three phase shown. L2 not used
in single phase applications
FUSED OR CIRCUIT BREAKER
DISCONNECT (Furnished by
installer)
L1
GND
L3L2
RELAY
K109
RELAY
K105
FLAME ROLLOUT
SWITCH
BLOWER DECK
RED
RED
RED
MAKE−UP BOX
L1
L2
L3
(Alternate make−up box right side)
TERMINAL STRIP
SEE NOTE 1
5
7
7
T1 TRANSFORMER
24v: blue − yellow
208v: red − black
240v: orange − black
TB34
1 1
2
2
YELLOW YELLOW
BLUE
BLUE
Three phase shown.
This lead not used in
single phase applications
FLAME ROLLOUT
SWITCH
31 2 4
DOOR
INTERLOCK
J84
PLUG
DOOR
INTERLOCK
Three phase shown. L2 not used
in single phase applications
REMOVE JUMPER IN TWO-STAGE MODE
GROUND LUG
BLACK
K3 CONTACTOR
RED
ORANGE
BLOWER MOTOR
L1
T1
L2
L3
T3T2
RED
L1
RED
L2
RED
L3
MAKE−UP BOX
C
W1
G
W2
Y1
Y2
R
ECON
TB1
TERMINAL STRIP
CONTROL BOX
R3 See Note 2
(Alternate make−up box left side)
THERMOSTAT
C
W1
G
W2
Y1
Y2
R
ECONOMIZER
NOTES :
1 − Relay K109 can be used for an accessory rated at the same voltage as power sup­ply.
2 − Field installed and supplied re­sistor (R3), is required in two-stage applications when using electro­mechanical thermostat. (Use a 150 ohm, 10 watt resistor − Lennox part number P−8−6256.)
FIELD-INSTALLED DRIVE KIT COMPONENT
FACTORY INSTALLED
LINE VOLTAGE FIELD INSTALLED 24 VOLTS FIELD INSTALLED
FIGURE 16
Page 29
Page 30
COMBUSTION
AIR BLOWER
(Alternate make-up box right side)
RED
RED
RED
PRIMARY
LIMIT
GAS
VALV E
DOOR
INTERLOCK
L1
L2
L3
G24−200 FIELD WIRING DIAGRAM
G UNITS − 460V 3PH 60HZ
J UNITS − 575V 3PH 60HZ
PRESSURE
SWITCH
IGNITION
CONTROL
BOARD
RED
COMBUSTION
AIR BLOWER
FLAME ROLLOUT
SWITCH
PLUG
J84
31 2 4
GAS
VALV E
DOOR
INTERLOCK
BLUE
PRIMARY
LIMIT
IGNITION
CONTROL
BOARD
L1
L2
L3
PRESSURE
SWITCH
BLOWER DECK
RED
RED
RED
FUSED OR
CIRCUIT BREAKER
DISCONNECT
(Furnished by
installer)
L1 L2
L1
L3
GND
MAKE-UP BOX
RELAY
K109
RELAY
K105
RELAY
K13
RED
T3 TRANSFORMER
460v: white − red
230v: white − black
TERMINAL STRIP
TB34
SEE NOTE 1
1
5
1
2
7
7
2
YELLOW YELLOW
BLUE
BLUE
4
T1 TRANSFORMER
24v: blue − yellow
460v: black − black
RED
BLACK
WHITE
GROUND LUG
BLACK
BLACK
BLACK
BLACK
K3 CONTACTOR
WHITE
RED
BLUE
L3
L1
L2
T1
T3T2
BLOWER MOTOR
T13 TRANSFORMER
BLACK
460v: white − red
230v: white − black
C
W1
G
W2
Y1
Y2
R
ECON
TB1 TERMINAL STRIP
CONTROL BOX
MAKE−UP BOX
R3
See Note 2
(Alternate make-up box left side)
REMOVE JUMPER IN TWO-STAGE MODE
THERMOSTAT
C
W1
G
W2
Y1
Y2
R
ECONOMIZER
NOTES :
1 − Relay K109 can be used for an accessory rated at the same voltage as power supply.
2 − Field installed and supplied resistor (R3), is required in two­stage applications when using electro-mechanical thermostat. (Use a 150 ohm, 10 watt resistor
− Lennox part number P−8−6256.)
FIELD-INSTALLED DRIVE KIT COMPONENT
FACTORY INSTALLED
LINE VOLTAGE FIELD INSTALLED 24 VOLTS FIELD INSTALLED
FIGURE 17
Page 30
Page 31
SCHEMATIC WIRING DIAGRAM FOR G24−200 UNITS (120V SINGLE PHASE 60HZ )
FIGURE 18
Page 31
Page 32
WIRING SCHEMATIC DIAGRAM FOR G24−200
P UNITS − 208/230V 1PH 60 HZ
Y UNITS − 208/230V 3PH 60HZ
G UNITS − 460V 3PH 60HZ
J UNITS − 575V 3PH 60HZ
FIGURE 19
Page 32
Page 33
Unit Start−Up
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING
Do not use this furnace if any part has been under water. A flood−damaged furnace is extremely dan­gerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, elec­trical parts that have been wet or the furnace if deemed necessary.
WARNING
Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
WARNING
SMOKE POTENTIAL
The heat exchanger in this unit could be a source of smoke on initial firing. Take precautions with respect to building occupants and property. Vent initial sup­ply air outside when possible.
Placing Furnace Into Operation
G24−200 units are equipped with two direct spark ignition systems − one for each heat section. Do not attempt to manually light burners on these furnaces. Each time ther­mostat calls for heat, the burners will automatically light.
WARNING
Danger of explosion and fire. Can cause injury or product or property damage. You must follow these instructions exactly.
Gas Valve Operation − White Rodgers 36E Two-Stage Gas Valve (Figure 20)
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit.
3 − This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to light the burners by hand.
4 − Remove the control access panels.
WHITE RODGERS 36E GAS VALVE
LOW HEAT MANIFOLD PRESSURE FACTORY-SET, NOT FIELD-ADJUSTABLE.
HIGH HEAT MANIFOLD
PRESSURE ADJUSTMENT
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
WARNING
Danger of explosion. Can cause injury or death. Do not attempt to light manually. Unit has a direct spark ignition system.
BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
MANIFOLD
PRESSURE
OUTLET ON SIDE.
GAS VALVE KNOB SHOWN IN OFF" POSITION
FIGURE 20
5 − Perform the following to both gas valves − Turn knob
on gas valve 180 either way to OFF. Do not force.
6 − Wait five minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from your neighbor’s phone. Follow the gas supplier’s instructions. If you don’t smell gas go to next step.
7 − Perform the following to both gas valves − Turn knob
on gas valve 180 either way to ON position.
8 − Replace the control access panels.
9 − Turn on all electrical power to the unit.
10 −Set the thermostat to desired setting.
11 −Both combustion air blowers will start. The burners
in both heat sections will light after a 45-second pre­purge.
Page 33
Page 34
12 −If the furnace does not light the first time (the gas line
may not be fully purged), it will attempt up to two more ignitions before locking out.
13 −If lockout occurs, repeat steps 1 through 10.
14 −If the appliance will not operate, follow the instructions
Turning Off Gas To Unit" and call your service techni­cian or gas supplier.
B − Turning Off Gas To Unit
1 − Set the thermostat to the lowest setting.
7 − For troubleshooting purposes, an ignition attempt after
lockout may be re-established manually. Move thermo­stat from Heat" to OFF" then back to Heat." The heat­ing sequence then restarts at step 1.
B − Applications with Two-Stage Thermostat
1 − When the thermostat calls for heat, the K13 relay con-
tacts close (W1 and W2 not jumpered on furnace ter- minal strip) and both combustion air blowers (B6 and B16) start.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the control access panels.
4 − Perform the following to both gas valves − Turn knob on
gas valve 180 either way to OFF. Do not force.
5 − Replace the control access panels.
Heating Sequence of Operation
A − Applications with Single-Stage Thermostat
1 − When the thermostat calls for heat, the K13 and K19
relay contacts close (W1 and W2 jumpered on furnace terminal strip) and both combustion air blowers (B6 and B16) start.
2 − The combustion air pressure switches (S18 and S45)
prove blower operation, then ignition controls (A3 and A12) are energized. The pressure switches are factory set and require no adjustment.
3 − After a pre-purge of 30 seconds, the two spark ignitors
energize and the gas valves (GV1 and GV3) open on
low heat and after approximately 3 seconds open on high heat.
4 − The sparks ignite the gas, the ignition sensors prove
the flames and the combustion process continues.
5 − In the event that the flames are not detected after the
first trial for ignition (8 seconds trial duration), the igni­tion controls will repeat steps 3 and 4 two more times before locking out. (The two ignition controls operate independently. If one control locks out its gas valve, the other control maintains its gas valve in operation.)
2 − The combustion air pressure switches (S18 and S45)
prove blower operation, then the ignition controls (A3 and A12) are energized. The pressure switches are factory set and require no adjustment.
3 − After a pre-purge of 30 seconds, the two spark ignitors
energize and the gas valves (GV1 and GV3) open on low heat.
4 − The sparks ignite the gas, the ignition sensors prove
the flames and the combustion process continues.
5 − In the event that the flames are not detected after the
first trial for ignition, the ignition controls will repeat steps 3 and 4 two more times before locking out. (The two ignition controls operate independently. If one con­trol locks out its gas valve, the other control maintains its gas valve in operation.)
6 − If the temperature of the conditioned space continues
to drop, the thermostat’s second-stage contacts close (W2 powered).
7 − The K19 relay contacts close and the gas valves (GV1
and GV3) open on high heat after approximately 3 seconds.
8 − When the W2 heating demand is satisfied, the K19
relay contacts open and both gas valves (GV1 and GV3) close second-stage after 3 seconds and then re­turn to low heat operation. When the W1 heating de­mand is satisfied, the K13 relay contacts open and both gas valves (GV1 and GV3) close first-stage.
6 − When W1 heating demand is satisfied, the K13 and
K19 relay contacts open and both gas valves (GV1 and GV3) close on second-stage after 3 seconds and then close on first-stage.
9 − For troubleshooting purposes,an ignition attempt after
lock-out may be re-established manually. Move the thermostat from Heat" to OFF" then back to Heat." The heating sequence then restarts at step 1.
Page 34
Page 35
Gas Pressure Adjustment
Unit
Input
High Altitude Information
Gas Flow (Approximate)
1− Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for two revolu- tions of gas through the meter. (Two revolutions as­sures a more accurate time.) A portable LP gas meter (17Y44) is available for LP applications.
2− Divide the number of seconds by two and compare
to the time in table 11. If manifold pressure is correct and rate is incorrect, check gas orifices for proper size and restriction.
3− Remove temporary gas meter if installed.
NOTE− To obtain accurate reading, shut off all other gas appliances connected to meter.
TABLE 11
GAS METER CLOCKING CHART
Unit
Input
Rate
(Btuh)
Seconds for One Revolution
Natural LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
75,000 48 96 120 240 125,000 29 58 72 144 130,000 28 55 69 138 235,000 15 31 38 77 260,000 14 28 35 69 470,000 8 15 19 38
Natural−1000 btu/cu ft LP−2500 btu/cu ft
Note: Table assumes standard temperature (60°F), pressure (30in.Hg.), and fuel heating values (Btuh/Ft. corrections in altitudes above 2000 ft.
3
). Apply pressure
Gas Pressure
1 − Check the gas line pressure with the unit (both heat sec-
tions) firing at the high heat input rate. A minimum of 4.5 in. w.c. for natural gas should be maintained.
2 − After the line pressure has been checked and ad-
justed, check the high heat regulator pressure on both gas valves. See figure 20 for gas pressure adjustment screw location. The low heat setting is factory-set and is not field-adjustable. The high heat manifold pres­sure settings are given in table 12.
TABLE 12
MANIFOLD GAS PRESSURES (HIGH HEAT)
ALTITUDE
feet (m)
0 − 2000 (0 − 610) Natural 3.5 (0.87)
2000 − 4500 (610 − 1372) Natural 3.5 (0.87)
4500 − 7500* (1372 −
2286)
GAS
FUEL
Natural 3.2 (0.80)
MANIFOLD PRESSURE
in. w.c. (kPa)
*In Canada, certification for installation at altitudes over 4500 feet (1372m) above sea level is the jurisdiction of the local authorities.
In Canada, certification for installation at altitudes over 4500 feet (1372m) above sea level is the jurisdiction of the local authorities.
See table 12 for the correct high heat manifold pressures to be maintained for natural gas.
Check the gas line pressure with the unit (both heat sections) firing at high heat input rate The minimum pressure as shown on the nameplate for natural gas must be main­tained.
No orifice change is required. No pressure switch change is required.
Other Unit Adjustments and Operation
Primary (S10 and S99) Limits
Each heat sec tion ha s a pr imary limit locat ed on the heat­ing compartment vestibule panel. These limits are facto­ry set and do not require field adjustment.
Flame Rollout Switches (S47 and S69)
Each heat section has a manually reset flame rollout switch. Each switch is located on the burner top plate. If tripped, a check for adequate combustion air should be made before resetting. The switches are non-adjustable.
Combustion Air Pressure Switches (S18 and S45)
Each heat section has a combustion air pressure switch lo­cated on the heating compartment vestibule panel. Each switch checks for proper combustion air blower operation before allowing ignition trial. The switches are factory set and require no field adjustment.
Blower Motor Controls (K25 Circuit Board), (K20 Relay), (K123 Relay) and (K36 Relay)
When the gas valves are powered, the blower motor starts after a delay of 45 seconds. When the gas valves lose pow­er because the thermostat demand is satisfied, the blower motor remains running for 150 seconds. These timings are programmed into the K25 control board and are non-ad­justable. The board is located in the control box. If abnormal furnace operation causes either high limit (S10 or S99) to open, the relays K20, K123 and K36 maintain blower operation until the limit(s) is reset.
Page 35
Page 36
Temperature Rise
Burner Flame Adjustment
Check the temperature rise and, if necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit rating plate.
Electro-mechanical Thermostat Heat Anticipation
In single-stage heat applications, set the heat anticipation to 0.2 amps. In two-stage heat applications, set the heat anticipation to
0.26 amps and install a field-provided resistor (150 ohm, 10 watt rating −Lennox part number P−8−6256) in parallel with K13 relay coil.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on blower motor.
Motor service factor amps Nameplate __________Actual__________
Flue And Chimney
The G24−200 burner flame is not adjustable; however, the flame should be inspected at the beginning of each heating season. If necessary, clean the burners. Burner flame should be blue when burning natural gas. See figure 21.
BURNER FLAME
FLAME APPEARS
BLUE IF BURNING
NAT. GAS.
BURNER
FLAME
HEAT
EXCHANGER
TUBE
VEST
PANEL
FIGURE 21
Failure To Operate
If unit fails to operate check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
1 − Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage.
2 − Check unit for proper draft.
3 − Are pressure switches closed? Obstructed flue will
open pressure switches and cause unit to shut down. Check flue and outlet for blockages.
4 − Reset manual flame rollout switches on burner box
covers.
4 − Is there a blown fuse or tripped circuit breaker?
5 − Are the filters dirty or plugged? Dirty or plugged filters
will cause the limit controls to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Are the internal manual shut-off valves open?
9 − Are the unit ignition systems in lock out mode? If unit
locks out again, call serviceman to inspect unit for block­ages.
Page 36
Page 37
Setting blower CFM
Vol um e
Note − Turn electrical power off when adjusting mo­tor pulley. Blower RPM adjustment is accomplished by
changing the motor pulley opening. Loosen Allen screw and turn pulley clockwise to increase RPM or turn coun­terclockwise to decrease. Re-tighten Allen screw. (See Blower motor/drive installation section for the pulley alignment and belt tensioning method.)
1 − Enter table 13 at design CFM and total external static
pressure. (Design total external static pressure equals the sum of all pressure drops across all acces­sories which are installed external to furnace and all ductwork/accessories. See table 14 for external filter box with filters pressure drops, C17 coil pressure drops and EMD17M economizer pressure drops.)
TABLE 13
CFM vs TOTAL EXTERNAL STATIC PRESSURE
Air
Vol um e
cfm
(L/s)
.10 (25) .20 (50) .30 (75) .40 (100) .50 (125) .60 (150) .70 (175) .80 (200) .90 (225) 1.00 (250) 1.10 (275)
RPM BHP
(kW)
RPM BHP
(kW)
RPM BHP
(kW)
Total External Static Pressure − in. w.g. (Pa)
RPM BHP
(kW)
RPM BHP
(kW)
2 − The table yields a value for design BHP and RPM.
3 − Select drive kit so that motor maximum BHP (as
shown in table 15) exceeds the value from table13.
4 − Run the blowers and measure the actual blower shaft
RPM and total external static pressure.
5 − Adjust RPM to the value in table13 which will result in the
design CFM. From design CFM and actual Total Exter­nal Static Pressure reading, Table 13 gives required BHP. This value should still be lower than the maximum BHP delivered by the motor as shown in table 15.
6 − As a final check, measure the motor’s current draw and
compare it to the motor’s nameplate service factor amps rating (SFA). If the current draw is not less than or equal to the SFA rating, reduce the motor’s load until it is.
RPM BHP
(kW)
RPM BHP
(kW)
RPM BHP
(kW)
RPM BHP
(kW)
RPM BHP
(kW)
RPM BHP
(kW)
2400
(1135)
2600
(1225)
2800
(1320)
3000
(1415)
3200
(1510)
3400
(1605)
3600
(1700)
3800
(1795)
4000
(1890)
4200
(1980)
4400
(2075)
- - - - - - - -
- - - - - - - -
- - - - - - - -
- - - - - - - -
- - - - - - - -
- - - -
- - - -
- - - -
- - - -
550 0.70
(0.52)
570 0.80
(0.60)
535 0.50
(0.37)
550 0.55
(0.41)
570 0.60
(0.45)
585 0.70
(0.52)
605 0.80
(0.60)
625 0.90
(0.67)
535 0.30
(0.22)
545 0.35
(0.26)
560 0.40
(0.30)
570 0.45
(0.34)
585 0.50
(0.37)
595 0.55
(0.41)
610 0.65
(0.48)
625 0.70
(0.52)
645 0.80
(0.60)
660 0.90
(0.67)
675 1.00
(0.75)
600 0.35
(0.26)
610 0.40
(0.30)
620 0.45
(0.34)
630 0.55
(0.41)
640 0.85
(0.45)
655 0.65
(0.48)
665 0.75
(0.56)
680 0.80
(0.60)
695 0.90
(0.67)
710 1.00
(0.75)
725 1.10
(0.82)
665 0.45
(0.34)
670 0.50
(0.37)
680 0.55
(0.41)
690 0.60
(0.45)
685 0.70
(0.52)
710 0.75
(0.56)
720 0.85
(0.63)
730 0.90
(0.67)
745 1.00
(0.75)
760 1.10
(0.82)
770 1.20
(0.90)
720 0.55
(0.41)
725 0.60
(0.45)
735 1.05
(0.48)
740 0.70
(0.52)
750 0.80
(0.60)
760 0.85
(0.63)
770 0.95
(0.71)
780 1.05
(0.78)
790 1.10
(0.82)
805 1.25
(0.93)
815 1.35
(1.01)
755 0.65
(0.48)
780 0.70
(0.52)
785 0.75
(0.56)
790 0.90
(0.60)
800 0.90
(0.67)
805 0.95
(0.71)
815 1.05
(0.78)
825 1.15
(0.86)
835 1.25
(0.93)
850 1.35
(1.01)
860 1.45
(1.08)
825 0.75
(0.56)
830 0.80
(0.60)
835 0.85
(0.63)
840 0.90
(0.67)
845 1.00
(0.75)
855 1.05
(0.78)
860 1.15
(0.86)
870 1.25
(0.93)
880 1.35
(1.01)
890 1.45
(1.08)
900 1.60
(1.19)
875 0.85
(0.63)
875 0.90
(0.67)
880 0.95
(0.71)
865 1.00
(0.75)
890 1.10
(0.82)
895 1.20
(0.90)
905 1.25
(0.93)
910 1.35
(1.01)
920 1.45
(1.08)
930 1.60
(1.19)
940 1.70
(1.27)
920 0.95
(0.71)
920 1.00
(0.75)
925 1.05
(0.78)
930 1.15
(0.86)
935 1.20
(0.90)
940 1.30
(0.97)
945 1.40
(1.04)
955 1.50
(1.12)
960 1.60
(1.19)
970 1.70
(1.27)
- - - - - - - -
965 1.05
(0.78)
965 1.10
(0.82)
965 1.15
(0.86)
970 1.25
(0.93)
975 1.35
(1.34)
- - - -
- - - -
- - - -
- - - -
- - - -
4600
(2170)
4800
(2265)
5000
(2360)
NOTE − All air data is measured external to furnace using rear return air opening without air filters in place.
Bold text indicates 2 H.P. (1.5 kW) drive kits.
590 0.90
(0.67)
610 1.00
(0.75)
630 1.10
(0.82)
645 1.00
(0.75)
660 1.10
(0.82)
680 1.25
(0.93)
695 1.10
(0.82)
710 1.25
(0.93)
730 1.35
(1.01)
740 1.25
(0.93)
755 1.35
(1.01)
775 1.50
(1.12)
785 1.35
(1.01)
800 1.45
(1.08)
815 1.60
(1.19)
830 1.45
(1.08)
845 1.60
(1.19)
860 1.75
(1.31)
870 1.60
885 1.75
900 1.90
Page 37
(1.19)
(1.31)
(1.42)
915 1.75
(1.31)
925 1.85
(1.38)
940 2.00
(1.49)
950 1.85
(1.38)
965 2.00
(1.49)
975 2.15
(1.60)
- - - - - - - -
- - - - - - - -
- - - - - - - -
Page 38
TABLE 14
Circuit
Belt
Weight
(
)
(35.2)
ACCESSORY AIR RESISTANCE
Model C17−090/120 Coil
cfm L/s in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa
2400 1135 0.14 35 0.17 42 0.05 12 .04 10 −−−− −−−−
2600 1225 0.16 40 0.18 45 0.06 15 .05 12 −−−− −−−−
2800 1320 0.19 47 0.20 50 0.07 17 .06 15 −−−− −−−−
3000 1415 0.22 55 0.22 55 0.08 20 .07 17 .03 7
3200 1510 0.24 60 0.23 57 0.09 22 .08 20 .04 10
3400 1605 0.27 67 0.25 62 0.10 25 .09 22 .05 12
3600 1700 0.30 75 0.27 67 0.10 25 .10 25 .06 15
3800 1795 0.33 82 0.29 72 0.11 27 .11 27 .07 17
4000 1890 0.36 90 0.31 77 0.12 30 .12 30 .07 17
4200 1980 0.38 95 0.34 85 0.13 32 −−−− −−−− .08 20
4400 2075 0.42 104 0.36 90 0.14 35 −−−− −−−− .09 22
4600 2170 0.45 11 2 0.39 97 0.16 40 −−−− −−−− .10 25
4800 2265 0.48 11 9 0.42 104 0.17 42 −−−− −−−− .11 27
5000 2360 0.51 127 0.44 109 0.18 45 −−−− −−−− .11 27
* Furnished with filter box.
Pleated Filter −
1 in. (25 mm)
*Disposable Filter −
1 in. (25 mm)
EMD17M−95 EMD17M−135
TABLE 15
DRIVE KIT SPECIFICATIONS
Additive
Cooling
Tons
(kW)
Drive Kit
Model No. & Phase
Voltage
Motor Output
hp (kW)
min. max.
Minimum
Circuit
Ampacity
Motor Pulley
(in.) & Groove (in.) & Groove Range
Blower Pulley
RPM
Belt
Shipping
Weight
lbs. (kg)
DKG24−200−1 115v−1ph 25 42 (19)
DKG24−200−2 230v−1ph 14 42 (19)
7.5 or 10 (26.4 or
35.2)
10
35.2
Maximum usable output of motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, keep within the service factor limitations specified on motor nameplate. At rated voltages shown. NOTE − All drive kits include matching 24 volt control transformer. All kits (except 208/230v) include matching auto−transformer for combustion air blower operation.
DKG24S−200−3 208/230v−3ph
DKG24S−200−4 460v−3ph 4 48 (22)
DKG24S−200−5 575v−3ph 3 48 (22)
DKG24−200−6 208/230v−3ph 9 57 (26)
DKG24−200−7 460v−3ph
DKG24−200−8 575v−3ph 3 57 (26)
1.5 (1.1) 1.7 (1.3)
2 (1.5) 2.3 (1.7)
9
4
7/8 x 4−3/4 − A 1 x 10 − A 535 − 772 A − 52
7/8 x 6 − A 1 x 10 − A 802 − 977 A − 52
48 (22)
57 (26)
Page 38
Page 39
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete fur­nace model number listed on the CSA international. rating plate  Example: G24−200. Refer to page 4 and 5 for parts identifi­cation.
Cabinet Parts Electrical Parts Heating Parts Blower Parts
Front louver door (2) Transformer(s) Heat exchanger (2) Wheel (2)
Blower access panel (2) Ignition control board (2) Main burners Motor
Cabinet cap Door interlock (2) Main burner orifices Cut-off plate (2)
Cabinet top-rear Ignition cable (2) Gas manifold/burner
box assembly (2)
Cabinet bottom-rear Ignitor (2) Gas valve (2) Motor pulley
Flue adapter (2) Flame sensor (2) Flue box (2) Wheel pulley
Roll-out switch (2) Combustion air blower (2) Belt
Primary limit (2) Flexible gas connector Bearing (2)
Pressure switch (2) Vibration isolators (4)
Blower timing control board Locating rods (2)
Accessory relay
Blower operation relays
Contactor
Combustion air blower
operation relays
Shaft
G24−200 Start−up and Performance Check List
Job Name Job Number Date Job Location City State/Province Installer
City State/Province
Unit Model No. Serial Number Serviceman
HEATING SECTION
Electrical Connections Tight? Supply Voltage
Blower Motor Amps Blower Motor Horsepower/Kw
Blower Motor Lubrication OK? Blower Shaft Lubrication OK?
Gas Piping Connections Tight & Leaks Tested?
Fuel Type: Natural Gas?
Furnace Btu (kw) Input Line Pressure w.c./Pa − Nat.
Regulator Pressure w.c./Pa −− Nat.
Connections Tight? Proper Draft?
Temperature Rise Filter Clean & Secure? Vent Clear?
THERMOSTAT
Calibrated? Heat Anticipator Properly Set? Level?
Page 39
Page 40
Troubleshooting
HEATING SEQUENCE OF OPERATION WITH TWO-STAGE THERMOSTAT
NOTE − THIS FURNACE FUNCTIONS WITH TWO INDEDPENDENTLY CONTROLLED HEAT SECTIONS.
THE GRAY BOXES INDICATE COMPONENTS WHICH EFFECT BOTH HEAT SECTIONS SIMULTANEOUSLY.
NORMAL HEATING MODE
POWER ON
THERMOSTAT CALLS FOR HEAT
(W1 ENERGIZED)
K13 RELAY ENERIZED.
A3 (A12) IGNITION CONTROL LED ON.
IS THE S10 (S99) HIGH LIMIT CLOSED?
YES
IS THE S47 (S69) ROLLOUT SWITCH CLOSED?
YES
IS THE B6 (B15) COMBUSTION
AIR BLOWER ON?
YES
IS THE S18 (S45) COMBUSTION AIR
BLOWER PROVING SWITCH CLOSED?
YES
NO
NO
NO
NO
ABNORMAL HEATING MODE
DETERMINE WHY AUTOMATIC-RESET
S10 (S99) HIGH LIMIT OPEN.
CHECK VENTING SYSTEM
OPERATION/BLOCKAGE BEFORE
RESETTING THE MANUALLY-RESET S47
(S69) ROLLOUT SWITCH.
CHECK K13−1 CONTACT OPERATION AND
WIRING TO B6 (B15) COMBUSTION AIR
BLOWER?
CHECK SENSING TUBE FOR BLOCKAGE
AND S18 (S45) SWITCH FOR PROPER
OPERATION.
B6 (B15) COMBUSTION AIR BLOWER
PREPURGE FOR 30 SECS.
8 SEC TRIAL FOR IGNITION − START IGNITION
TRAIL, GV1 (GV3) GAS VALVE OPENS ON LOW
HEAT. IS FLAME SENSED WITHIN 8 SECS?
YES
K56 (K57) RELAY ENERGIZED. K25 CIRCUIT
BOARD ENERGIZED. SYSTEM BLOWERS ON
AFTER 45 SEC DELAY.
YES
FLAME SENSE OK?
YES
CONTINUED NEXT PAGE
NO
NO
Page 40
NO
NO
GV1 (GV3) GAS VALVE CLOSED, SPARK
OFF. INCREMENT TRAIL REGISTER.
(DURING RETRY PERIOD LED FLASHES
.5 SEC. ON AND 2.5 SEC. OFF. ARE THE
THREE TRIALS COMPLETE?
YES
LOCKOUT OCCURS. TO RESET A3 (A12)
IGNITION CONTROL MOVE THERMOSTAT
SWITCH FROM HEAT TO OFF TO HEAT.
CHECK BELT.
CHECK RELAYS.
Page 41
HEATING SEQUENCE OF OPERATION WITH TWO-STAGE THERMOSTAT CONTINUED
NORMAL HEATING MODE
IS THE S10 (S99) HIGH LIMIT CLOSED?
YES
HAS ROOM AIR TEMPERATURE CONTINUED
TO DROP BELOW THE THERMOSTAT"S
W2 SET POINT?
YES
POWER FROM W2
ENERGIZES K19 RELAY
SECOND-STAGE OF GV1 (GV3)
GAS VALVE ENERGIZED (HIGH HEAT)
AFTER APPROXIMATELY 3 SEC.
IS W2 DEMAND SATISFIED?
NO
NO
IS W1 DEMAND SATISFIED?
YES
A3 (A12) LED OFF
FIRST-STAGE OF GV1 (GV3)
GAS VALVE CLOSES.
B6 (B15) COMBUSTION
AIR BLOWER OFF.
ABNORMAL HEATING MODE
DETERMINE WHY AUTOMATIC-RESET
S10 (S99) HIGH LIMIT OPEN. K20, (K123), K36
RELAYS MAINTAIN BLOWER OPERATION.
YES
CLOSE SECOND-STAGE OF
GV1 (GV3) GAS VALVE AFTER
APPROXIMATELY 3 SEC. AND THEN
RETURN TO LOW HEAT OPERATION.
NOTE − IF ECONOMIZER INSTALLED, ECONOMIZER OPERATES WHEN BLOWER POWERED.
1 − ON NORMAL OPERATION WITH THERMOSTAT CALLING FOR HEAT. 2 − 0.5 SEC ON AND 2.5 SECS OFF IN IGNITION RETRY PERIOD. 3 − OFF NO POWER OR DETECTED FAULT.
B3 SYSTEM BLOWERS OFF
AFTER 150 SEC DELAY.
LED CODES
Page 41
Page 42
HEATING SEQUENCE OF OPERATION WITH SINGLE-STAGE THERMOSTAT
NOTE − THIS FURNACE FUNCTIONS WITH TWO INDEPENDENTLY CONTROLLED HEAT SECTIONS.
THE GRAY BOXES INDICATE COMPONENTS WHICH EFFECT BOTH HEAT SECTIONS SIMULTANEOUSLY.
NORMAL HEATING MODE
POWER ON
THERMOSTAT CALLS FOR HEAT
(W1 ENERGIZED)
K13 AND K19 RELAY ENERIZED.
(W1 AND W2 OF FURNACE
TERMINAL STRIP JUMPERED.)
A3 (A12) IGNITION CONTROL LED ON.
IS THE S10 (S99) HIGH LIMIT CLOSED?
YES
IS THE S47 (S69) ROLLOUT SWITCH CLOSED?
YES
IS THE B6 (B15) COMBUSTION
AIR BLOWER ON?
YES
IS THE S18 (S45) COMBUSTION AIR
BLOWER PROVING SWITCH CLOSED?
YES
NO
NO
NO
NO
ABNORMAL HEATING MODE
DETERMINE WHY AUTOMATIC-RESET
S10 (S99) HIGH LIMIT OPEN.
CHECK VENTING SYSTEM
OPERATION/BLOCKAGE BEFORE
RESETTING THE MANUALLY-RESET S47
(S69) ROLLOUT SWITCH.
CHECK K13−1 CONTACT OPERATION AND
WIRING TO B6 (B15) COMBUSTION AIR
BLOWER?
CHECK SENSING TUBE FOR BLOCKAGE
AND S18 (S45) SWITCH FOR PROPER
OPERATION.
B6 (B15) COMBUSTION AIR BLOWER
PREPURGE FOR 30 SECS.
8 SEC TRIAL FOR IGNITION − START IGNITION
TRAIL, GV1 (GV3) GAS VALVE OPENS ON LOW
HEAT AND AFTER A 3 SEC. DELAY OPENS ON
HIGH HEAT. IS FLAME SENSED WITHIN 8 SECS?
YES
K56 (K57) RELAY ENERGIZED. K25 CIRCUIT
BOARD ENERGIZED. SYSTEM BLOWERS ON
AFTER 45 SEC DELAY.
YES
FLAME SENSE OK?
YES
CONTINUED NEXT PAGE
Page 42
NO
NO
NO
NO
GV1 (GV3) GAS VALVE CLOSED, SPARK
OFF. INCREMENT TRAIL REGISTER.
(DURING RETRY PERIOD LED FLASHES
.5 SEC. ON AND 2.5 SEC. OFF. ARE THE
THREE TRIALS COMPLETE?
YES
LOCKOUT OCCURS. TO RESET A3 (A12) IGNITION
CONTROL MOVE THERMOSTAT SWITCH FROM
HEAT TO OFF TO HEAT.
CHECK BELT.
CHECK RELAYS.
Page 43
HEATING SEQUENCE OF OPERATION WITH SINGLE-STAGE THERMOSTAT CONTINUED
NORMAL HEATING MODE
IS THE S10 (S99) HIGH LIMIT CLOSED?
YES
IS W1 DEMAND OF
THERMOSTAT SATISFIED?
YES
A3 (A12) LED OFF
SECOND-STAGE OF GV1 (GV3)
GAS VALVE CLOSES AFTER
APRROXIMATELY 3 SEC. AND
THEN FIRST-STAGE CLOSES.
B6 (B15) COMBUSTION
AIR BLOWER OFF.
B3 SYSTEM BLOWERS OFF
AFTER 150 SEC DELAY.
NO
ABNORMAL HEATING MODE
DETERMINE WHY AUTOMATIC-RESET
S10 (S99) HIGH LIMIT OPEN. K20, (K123), K36
RELAYS MAINTAIN BLOWER OPERATION.
NOTE − IF ECONOMIZER INSTALLED, ECONOMIZER OPERATES WHEN BLOWER POWERED.
LED CODES
1 − ON NORMAL OPERATION WITH THERMOSTAT CALLING FOR HEAT. 2 − 0.5 SEC ON AND 2.5 SECS OFF IN IGNITION RETRY PERIOD. 3 − OFF NO POWER OR DETECTED FAULT.
Page 43
Page 44
COOLING SEQUENCE OF OPERATION
FOR TWO CONDENSING UNITS
THERMOSTAT CALLS FOR COOLING
(Y1 POWERED)
COOLING CONTACTOR OF FIRST-STAGE
CONDENSING UNIT CLOSES AND SYSTEM
BLOWERS START.
HAS ROOM AIR TEMPERATURE CONTINUED
TO RISE ABOVE THE THERMOSTAT"S
Y2 SET POINT?
YES
COOLING CONTACTOR OF SECOND-STAGE
CONDENSING UNIT CLOSES.
IS Y2 DEMAND SATISFIED?
YES
FOR A SINGLE CONDENSING UNIT
THERMOSTAT CALLS FOR COOLING
(Y1 POWERED)
COOLING CONTACTOR OF CONDENSING UNIT
CLOSES AND SYSTEM BLOWERS START.
IS Y1 DEMAND SATISFIED?
YES
COOLING UNIT CONTACTOR
OPENS AND B3 SYSTEM
BLOWERS OFF.
SECOND-STAGE COOLING
UNIT CONTACTOR OPENS
IS Y1 DEMAND SATISFIED?
YES
FIRST-STAGE COOLING UNIT
CONTACTOR OPENS AND B3
SYSTEM BLOWERS OFF.
MANUAL FAN OPERATION
MANUAL FAN SELECTION MADE AT THERMOSTAT.
THE BLOWERS RUN CONTINUOUSLY WITH OR
WITHOUT A CALL FOR HEATING OR COOLING.
Page 44
Loading...