INSTALLATION
,t_2007 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
®
WARNING
INSTRUCTIONS
CH33 Series Units
EVAPORATOR COILS
505,264M (65484504)
10/07
Supersedes 09/06
CH33 Series Coils ............................. 1
General ...................................... 1
Shipping and Packing List ...................... 1
Releasing Air Charge .......................... 2
Unit Installation ............................... 2
Refrigerant Line Set ........................... 3
Connections .................................. 4
Refrigerant Metering Device .................... 4
Leak Testing, Evacuating and Charging .......... 6
Blower Speed Connection ...................... 6
Condensate Drain Connection .................. 7
Maintenance .................................. 7
_puTeCh ical
n
blications
Litho U.S.A.
WARNING
CAUTION
IMPORTANT
CH33 horizontal evaporator coils are designed for use with
air conditioner or heat pump units. Each coil is equipped
with a compression fitting that provides convenient field
installation of a refrigerant metering device. Either a
refrigerant metering orifice (factory installed in coils and
provided with some Lennox air conditioner units) or a
thermostatic expansion valve (ordered separately) may be
used in air conditioner unit applications. A check
expansion valve (ordered separately) is the only metering
device approved for use in heat pump applications.
Refer to the CH33 Engineering Handbook for proper use of
these coils with Lennox furnaces, air conditioner units,
heat pumps and line sets.
These instructions are intended as a general guide and do
not supersede local or national codes in any way. Consult
authorities who have jurisdiction before installation.
Package 1 of 1 contains the following:
1 -- CH33 evaporator coil
Check the components for shipping damage. If you find
any damage, immediately contact the last carrier.
10/07
[[IHHI[IIIII[HI[[III[IIIH[[II[[III
Page 1
505,264M (65484504)
[III[IHHIIII[IH[IHI[IIH[[IImHI[[III
Table 1. Orifice Size Shipped with CH33
Model Number. Orifice Size
CH33-18A-2F 0.053
CH33-19A-2F 0.053
CH33-24/30A-2F 0.062
CH33-25A-2F 0.062
CH33-25B-2F 0.062
CH33-31A-2F 0.071
CH33-31 B-2F 0.071
CH33-36A-2F 0.076
CH33-36B-2F 0.076
CH33-36C-2F 0.076
CH33-42B-2F 0.082
CH33-43B-2F 0.082
CH33-43C-2F 0.082
CH33-44/48-2F 0.082
CH33-48C-2F 0.091
CH33-49C-2F 0.091
CH33-50/60C-2F 0.091
CH33-60D-2F 0.099
CH33-62D-2F 0.099
1, Install the furnace per the installation instructions
provided with the unit.
2, Place a field-provided heat shield, such as a wet rag,
against the piping plate and around the piping stubs,
and sweat in the suction line. The heat shield must be
in place to guard against heat damage to the paint.
NOTE - In areas of high humidity, the suction line section in
the air stream in the cabinet should be insulated with foam
tape. See figure 1.
FOAM
TAPE
CAUTION
The CH33 coil are shipped with a 15+ 3 psi dry air holding
charge. Ensure that the coil is void of pressure by
performing the following procedure:
a WARNING
1. Remove valve stem cap,
2, Press the liquid line valve stem,
NOTE - If there is no pressure when the valve core is
pressed, check the coil for leaks before continuing with the
installation,
Figure 1. Discharge End of Coil
3, Left-Hand and Right-Hand Discharge--The coil
must have a 1/2" slope from the rear of the cabinet
to the drain. Position the coil adjacent to the furnace
cabinet and align the six screw clearance holes in the
coil casing with the furnace engagement holes. Use
six field-provided #8 X 1" screws to secure the coil
casing to the furnace (see figures 2 and 3),
4, Right-Hand Air Discharge with Field-Provided
Spacer--The coil must have a 1/2" slope from the
rear of the cabinet to the drain. Position the coil in
I
the left-to-right configuration connection on the
service access side of the furnace (see figure 4).
Position the field-provided spacer between the
furnace and the coil. Use field-provided screws to
secure the coil casing, spacer and the furnace
together. The spacer should be long enough to allow
room for proper installation (approximately six inches
minimum).
NOTE: When the coil is connected directly with a
condensing furnace, the coil must be level from return end
to supply end. The front (access side) of the furnace may
be pitched down up to one-inch to accommodate a 1/2"
pitched coil.
5, Secure the supply duct to the coil cabinet,
6, Refer to the instructions provided with the condensing
unit for leak testing, evacuating and charging
procedures. Always check the entire system for
leaks before charging.
7, Applications using CH33-62 "D" width unit with
"C" width furnace--Figure 5 shows an application
that includes a "D" width coil and a "C" width furnace.
This application requires an insulated, field-supplied
block-off plate be constructed to cover the open space
on the coil housing,
505264M 10/07
Page 2
Coil _ "Air Unit
Back
Slope 112"
(13 mm) Coil
_ Drain
_l (Supply Air End View)
Supply Test Hole Supply Air Unit Rear
Front
90% Gas
Furnace Drain
Figure 2. Left-Hand Air Discharge
Supply Air Unit Rear Plumbinq Connections Supply Air Unit _. [' Coil
Plumbing
Connections
Supply Air b
Unit Front
Slope 1/2"
Supply Air Unit Front
Coil
Front
Supply Air Unit Front
Supply Air Unit Rear
iiiiiiiiiiiiiiii!!!!!!!!!!!!!!!!!_i!iii!i_iil;!i
\ /
Supply Air Unit Front
Field-fabricated
insulated
block-of[ plate
Supply Air
Unit Rear
Test
Hole
II T/i
Test Hole
NOTE - Use of this orientation is acceptable for 80% AFUE
furnaces. Do not use this orientation for 90% condensing furnaces.
Figure 3. Right-Hand Air Discharge
Test Hole
.....
Plumbing Connections
Spacer
(6 in. 152 mm min.)
Figure 4. Right-Hand Air Discharge with Spacer
Sealing Ducts - Ensure ducts are secured and all joints
properly sealed to either the coil cabinet flanges or the
furnace cabinet flanges.
Drain
(Supply Air End View)
IMPORTANT
Plumbing
Connections
SupplyAir
Unit Front
Figure 5. "D" Width Coil wl"C" Width Furnace
Leak Testing, Evacuating,Charging - Refer to the
instructions provided with the outdoor unit for leak testing,
evacuating and charging procedures. Always leak check
entire system before charging.
The refrigerant line sets should be sized according to the
recommendations given in the outdoor unit installation
instructions. See table 1 for sweat connection sizes. A
field-provided adapter may be required to match line set
connections.
Page 3
CH33 SERIES