Lennox CH33 User Manual

INSTALLATION
,t_2007 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
®
WARNING
INSTRUCTIONS
EVAPORATOR COILS 505,264M (65484504)
10/07 Supersedes 09/06
CH33 Series Coils ............................. 1
General ...................................... 1
Shipping and Packing List ...................... 1
Releasing Air Charge .......................... 2
Unit Installation ............................... 2
Refrigerant Line Set ........................... 3
Connections .................................. 4
Refrigerant Metering Device .................... 4
Leak Testing, Evacuating and Charging .......... 6
Blower Speed Connection ...................... 6
Condensate Drain Connection .................. 7
Maintenance .................................. 7
_puTeCh ical
n
blications
Litho U.S.A.
WARNING
CAUTION
IMPORTANT
CH33 horizontal evaporator coils are designed for use with air conditioner or heat pump units. Each coil is equipped
with a compression fitting that provides convenient field
installation of a refrigerant metering device. Either a refrigerant metering orifice (factory installed in coils and
provided with some Lennox air conditioner units) or a thermostatic expansion valve (ordered separately) may be
used in air conditioner unit applications. A check expansion valve (ordered separately) is the only metering
device approved for use in heat pump applications. Refer to the CH33 Engineering Handbook for proper use of
these coils with Lennox furnaces, air conditioner units, heat pumps and line sets.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult
authorities who have jurisdiction before installation.
Package 1 of 1 contains the following:
1 -- CH33 evaporator coil
Check the components for shipping damage. If you find any damage, immediately contact the last carrier.
10/07
[[IHHI[IIIII[HI[[III[IIIH[[II[[III
Page 1
505,264M (65484504)
[III[IHHIIII[IH[IHI[IIH[[IImHI[[III
Table 1. Orifice Size Shipped with CH33
Model Number. Orifice Size
CH33-18A-2F 0.053 CH33-19A-2F 0.053 CH33-24/30A-2F 0.062 CH33-25A-2F 0.062
CH33-25B-2F 0.062 CH33-31A-2F 0.071 CH33-31 B-2F 0.071 CH33-36A-2F 0.076 CH33-36B-2F 0.076 CH33-36C-2F 0.076
CH33-42B-2F 0.082 CH33-43B-2F 0.082 CH33-43C-2F 0.082 CH33-44/48-2F 0.082 CH33-48C-2F 0.091 CH33-49C-2F 0.091
CH33-50/60C-2F 0.091 CH33-60D-2F 0.099 CH33-62D-2F 0.099
1, Install the furnace per the installation instructions
provided with the unit.
2, Place a field-provided heat shield, such as a wet rag,
against the piping plate and around the piping stubs, and sweat in the suction line. The heat shield must be
in place to guard against heat damage to the paint.
NOTE - In areas of high humidity, the suction line section in the air stream in the cabinet should be insulated with foam
tape. See figure 1.
FOAM TAPE
CAUTION
The CH33 coil are shipped with a 15+ 3 psi dry air holding charge. Ensure that the coil is void of pressure by
performing the following procedure:
a WARNING
1. Remove valve stem cap,
2, Press the liquid line valve stem,
NOTE - If there is no pressure when the valve core is
pressed, check the coil for leaks before continuing with the
installation,
Figure 1. Discharge End of Coil
3, Left-Hand and Right-Hand Discharge--The coil
must have a 1/2" slope from the rear of the cabinet to the drain. Position the coil adjacent to the furnace cabinet and align the six screw clearance holes in the coil casing with the furnace engagement holes. Use
six field-provided #8 X 1" screws to secure the coil casing to the furnace (see figures 2 and 3),
4, Right-Hand Air Discharge with Field-Provided
Spacer--The coil must have a 1/2" slope from the rear of the cabinet to the drain. Position the coil in
I
the left-to-right configuration connection on the service access side of the furnace (see figure 4).
Position the field-provided spacer between the furnace and the coil. Use field-provided screws to secure the coil casing, spacer and the furnace
together. The spacer should be long enough to allow room for proper installation (approximately six inches minimum).
NOTE: When the coil is connected directly with a condensing furnace, the coil must be level from return end to supply end. The front (access side) of the furnace may be pitched down up to one-inch to accommodate a 1/2" pitched coil.
5, Secure the supply duct to the coil cabinet, 6, Refer to the instructions provided with the condensing
unit for leak testing, evacuating and charging procedures. Always check the entire system for
leaks before charging.
7, Applications using CH33-62 "D" width unit with
"C" width furnace--Figure 5 shows an application that includes a "D" width coil and a "C" width furnace.
This application requires an insulated, field-supplied block-off plate be constructed to cover the open space
on the coil housing,
505264M 10/07
Page 2
Coil _ "Air Unit
Back
Slope 112" (13 mm) Coil
_ Drain
_l (Supply Air End View)
Supply Test Hole Supply Air Unit Rear
Front
90% Gas
Furnace Drain
Figure 2. Left-Hand Air Discharge
Supply Air Unit Rear Plumbinq Connections Supply Air Unit _. [' Coil
Plumbing Connections
Supply Air b Unit Front
Slope 1/2"
Supply Air Unit Front
Coil Front
Supply Air Unit Front
Supply Air Unit Rear
iiiiiiiiiiiiiiii!!!!!!!!!!!!!!!!!_i!iii!i_iil;!i
\ /
Supply Air Unit Front
Field-fabricated insulated
block-of[ plate
Supply Air Unit Rear
Test Hole
II T/i
Test Hole
NOTE - Use of this orientation is acceptable for 80% AFUE furnaces. Do not use this orientation for 90% condensing furnaces.
Figure 3. Right-Hand Air Discharge
Test Hole
.....
Plumbing Connections
Spacer (6 in. 152 mm min.)
Figure 4. Right-Hand Air Discharge with Spacer
Sealing Ducts - Ensure ducts are secured and all joints properly sealed to either the coil cabinet flanges or the
furnace cabinet flanges.
Drain
(Supply Air End View)
IMPORTANT
Plumbing Connections
SupplyAir
Unit Front
Figure 5. "D" Width Coil wl"C" Width Furnace
Leak Testing, Evacuating,Charging - Refer to the instructions provided with the outdoor unit for leak testing,
evacuating and charging procedures. Always leak check entire system before charging.
The refrigerant line sets should be sized according to the recommendations given in the outdoor unit installation
instructions. See table 1 for sweat connection sizes. A
field-provided adapter may be required to match line set
connections.
Page 3
CH33 SERIES
Table . Refrigerant Line Connections
CH33 Model
-18-F
-19-F
-24/30-F
-25-F
-31-F
-36-F
-42-F
-43-F
-44/48-F
-48-F
-49-F
-50/60-F
-60-F
-62-F
Suction (Vapor) Liquid
Line Sweat Size -
314 Inch (19mm)
Line Sweat Size -
3/8 Inch (9.5mm)
Line Sweat Size -
7/8 Inch (22mm)
If replacement parts are necessary, order kit69J46. The kit includes:
10 -- Brass nuts for liquid line assemblies
20 -- Teflon rings
10 -- Liquid line orifice housings
10 -- Liquid line assemblies
LIQUID LINE ORIFICE HOUSINGS (10)
/ TEFLON RINGS (20) _/RETAINER
PISTON
4. Remove the heat shield after brazing and allow the connections to cool.
CONNECT LIQUID LINE
Use the following procedure to connect the liquid line to the
indoor coil unit:
1. Slide the liquid line compression nut onto the provided liquid line fitting (the liquid line fitting comes attached
to the front of the delta plate of the uncased coils).
2. Insert the field-supplied liquid line into the liquid line stub for brazing.
The CH33 coils are shipped with a factory-installed fixed orifice, CH33 coils are compatible with either HFC-410A
fixed orifice or TXV/CTXV metering devices. The previously reference TXV/CTXV metering devices will
be referred to in this instruction as TXV,
DETERMINING CORRECT FIXED ORIFICE
A properly sized fixed orifice may be provided with the outdoor unit. Refer to the outdoor unit instruction to ensure
proper sizing of the refrigerant flow control orifice. An improperly sized RFC orifice can lead to diminished
capacities and/or efficiencies, as well as potential damage to the unit, RFCs shipped with the units are identified in
table 1.
I/2TURN
! / BRASS NUTS (I0)
"_ _ _11111_1 L_ _ STRAINER
L,QU,DUNEASSEMBL,ES" O%ER
(INCLUDES STRAINER) (10) LIQUID LINE
Figure 6. 69J46 Kit Components
Use a silver alloy brazing rod (5 or 6 percent silver alloy for copper-to-copper connections or 45 percent silver alloy for
copper-to-brass or copper-to-steel connections). BRAZE SUCTION/VAPOR LINE
Use the following procedure to connect the vapor line to the indoor coil unit:
1. Remove rubber plug.
2. Place a field-provided heat shield, such as a wet rag, against the piping plate and around the piping stubs,
and sweat in the suction line. The heat shield must be in place to protect the paint from heat damage.
3. Braze connection.
ASSEMBLY
Figure 7. Tightening Distance
TYPICAL FIXED ORIFICE REMOVAL PROCEDURE
1. On fully cased coils, remove the coil access and plumbing panels.
2. Remove any shipping clamps holding the liquid line and distributor assembly.
3. Using two wrenches, disconnect liquid line from distributor. Take care not to twist or damage distributor tubes during this process.
4. Remove and discard orifice, valve stem assembly if present and Teflon ring as illustrated in figure 8.
5. Retain brass nut to be using later with the liquid line assembly.
505264M 10/07
Page 4
VALVE STEM
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING REMOVE AND DISCARD
VALVE STEM CAP
ORIFICE VALVE STEM ASSEMBLY
(IF PRESENT)
BRASS NUT
/
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
(Uncased Coil Shown)
TWO PIECE
PATCH PLATE
dNCASED COIL
)ISTRIBUTOR
TUBES
(Uncased Coil Shown)
LIQUID LINE
ORIFICE STUB END
HOUSING
TXV
RING
SENSING
LINE
Figure 8. Typical Fixed Orifice Removal
TYPICAL FIXED ORIFICE INSTALLATION PROCEDURE
1. Ensure that the orifice is installed with the nylon seat pointing toward the liquid line orifice housing,
2. Insert the Teflon ring securely into the liquid line orifice housing. Lightly lubricate the threads of the liquid line
orifice housing and the expose surface of the Teflon
ring,
3. Connect the liquid line assembly with the brass nut to the liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 7, or 20 ftqb,
4. Place the supplied fixed orifice sticker on the indoor cabinet after installation.
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
\
TEFLON RING
ORIFICE
J BRASS NUT
/
MALE EQUALIZER LINE FITTING (SEE FIGURE
12 FOR FURTHER DETAILS)
Sensing bulb insulation is
required if mounted external to
the coil casing. See figure 11 for bulb positioning.
Figure 10. Typical TXV Installation
LIQUID
LINE
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
(Uncased Coil Shown
Figure 9. Typical Fixed Orifice Installation
TYPICAL TXV INSTALLATION PROCEDURE
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field-provided plenum, install the TXV in a manner that will provide access for field servicing of the
TXV, Refer to figure 10 for reference during installation of TXV unit,
Figure 11. TXV Sensing Bulb Installation
1. Insert one of the provided Teflon rings into the stubbed end of the TXV. Lightly lubricate the threads of the stubbed end of the TXV and the expose surface of the Teflon ring.
2. Attach the stubbed end of the TXV to the liquid line orifice housing, Finger tighten and use an appropriately
sized wrench to turn an additional 1/2 turn clockwise as illustrated in figure 7, or 20 ft-lb,
3. Place the remaining Teflon ring around the other end of the TXV and lightly lubricate the threads of the that end of the TXV, and the expose surface of the Teflon ring,
Page 5
CH33 SERIES
4, Attach the liquid line assembly with brass nut to the
TXV. Finger tighten and use an appropriately sized
wrench to turn an additional 1/2 turn clockwise as
illustrated in figure 7, or 20 if-lb.
5, Attach the sensing bulb of the TXV in the proper
orientation as illustrated in figure 11 to the suction line using the clamp and screws provided in the TXV kit.
6, Connect the equalizer line from the TXV to the
equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated in figure 7,
A IMPORTANT
Refer to the outdoor unit instruction for leak testing,
evacuating and charging procedures, Always leak check entire system before charging,
Proper air volume must be provided over the evaporator
coil. Select a blower motor speed tap that will provide 400 _+ 50 CFM per 12,000 Btuh of cooling capacity (wet coil).
A static pressure reading must be taken to see if the pressure drops are within the proper range. See figure 14
to see for an example to obtain an accurate reading.
Left-HandAir Discharge(TopView)
TEST HOLE 1 Supply Air Unit Rear
FLARE SEAL ,miD,, [ "_'1 r 1
CAP
I I
]
[_ _ FLARE NUT
OR ._ FLARESEAL
_I (REMOVE)
I
COPPER
BONNET
,R SSE? ,ZER
SUCTION/VAPOR LINE
Figure 12. Copper Flare Seal Bonnet Removal
NOTE - To prevent any possibility of water damage,
properly insulate all parts of the TXV assembly that may
sweat due to temperature differences between the valve and its surrounding ambient temperatures.
See the CH33 Engineering Handbook for approved TXV match-ups and application information. Typically, the TXV kits include the following:
1 -- TXV 2 -- Teflon rings 1 -- 1 1/4" wide copper mounting strap for sensing bulb
2 -- #10 hex head bolts and nuts for securing sensing bulb
AND NUTS (2)
@ TEFLON %/'/
COPPER
MOUNTING
RINGS (2) /%
STRAP (1)
Figure 13. TXV Kit Components
AIR
AIR
RETURN DUCT
)
TEST
HOLE 2 Supply Air Unit Front
Figure 14. Static Pressure Test
To ensure accuracy, test the air on both sides of the coil (figure 14 exemplifies the two test hole locations).
CAUTION
Table 2. Air Volume/Static Pressure Drop
Model Cabinet Volume: Drop: in. w.g. (Pa)
CH33 Width in (mm) CFM (L/s) [Dry] [Wet]
-18-F 14-1/2 (394) 600 (285) .14 (35) .17 (42)
-19-F 14-1/2 (394) 800 (380) .15 (37) .17 (42)
-25-F 14-1/2 (394) 800 (380) .15 (37) .19 (47)
-25-F 17-1/2 (444) 800 (380) .09 (22) .11 (27)
-24/30-F 14-1/2 (394) 1000 (470) .22 (55) .30 (80)
-31-F 14-1/2 (394) 1000 (470) .24 (60) .27 (67)
-31-F 17-1/2 (444) 1000 (470) .14 (35) .16 (40)
-36-F 14-1/2 (394) 1200 (565) .27 (67) .30 (75)
-36-F 17-1/2 (444) 1200 (565) .17 (42) .21 (52)
-36-F 21 (533) 1200 (565) .17 (42) .21 (52)
-42-F 17-1/2 (444) 1400 (660) .22 (55) .28 (70)
-43-F 14-1/2 (394) 1400 (660) .26 (65) .31 (77)
-43-F 17-1/2 (444) 1400 (660) .18 (45) .21 (52)
-44/48-F 17-1/2 (444) 1400 (660) .18 (45) .23 (57)
-48-F 21 (533) 1600 (755) .17 (42) .21 (52) 49-F 21 (533) 1600 (755) .25 (62) .29 (72)
-50/60-F 21 (533) 1600 (755) .23 (57) .29 (72)
-60/62-F 24-1/2 (622) 2000 (945) .21 (52) .27 (67)
Across Coil
505264M 10/07
Page 6
1, Drilla5/16"(8mm)testholeinthecoilcase1"from
thefurnaceflange(figure14,testhole1).
2. Drilla5/16"(8mm)testholeintotheairsupplyduct connectedtothecoil.(testhole2infigure14),
3, Connectthezero end of the draft gauge scale to the
furnace end of the coil. Insert the hoses so that 1/4" (6
mm) extends inside the duct or end seal, Seal around holes with Permagum.
4, Turn on the electrical power to the furnace and set the
thermostat to initiate a cooling demand.
5, Table 2 lists the range of air volumes and equivalent
draft gauge readings for this unit. Observe the draft gauge reading and if below the required air volume,
increase the blower speed; if above the required air
volume, decrease the blower speed. Refer to the furnace wiring diagram for blower speed settings.
6. When the required draft gauge readings are obtained, remove the draft gauge lines and insert snaphole plugs into the test holes,
IMPORTANT
3. If the auxiliary drain line is to be used, remove the plug and route the drain line so that water draining from the outlet will be easily noticed by the homeowner.
4. After removal of drain pan plugs, check the drain port to see if holes have been drilled. If not drilled, use a
19/32" bit to drill out the primary drain hole; use a 3/8" drill bit for the secondary drain hole. Remove all drill shavings.
5. Make sure drain ports and drain pan are free of all debris.
6. Plug and check any unused drain pan openings for tightness. Torque plugs to 30 in. lb. to prevent water leaks or seepage from the drain pan.
XkIMPORTANT
Vent must extend above the height of the coil drain pan by 2 inches (51 mm). VENT
DRAIN PAN
Trap must be deep enough to offset k k _ maximum static difference (Generally, _v_
2 inches [51ram]).
Drain line should slope a minimum (49P66) _, 1 inch per 10 feet (25 mm per 3 m) TO APPROVED DRAIN
Figure 15. Typical Condensate Drain Connection
CH33 evaporator coils have both main and auxiliary drain connections, The auxiliary drain removes accumulated
condensate if the main drain becomes plugged,
1, Install a trap in both drain lines per local codes. Ifa vent
tee is required to reduce friction and static pressure, the trap should be installed between the unit outlet and the vent tee. See figure 15,
2. Make drain connections at the 3/4" female threaded pipe using condensate lines of the same size. Pitch the
main drain line down to an open drain or sump,
TRAP
A trained technician or service agency must perform
maintenance and service on equipment. At the beginning of each heating or cooling season, indoor coils should be
cleaned. Do not use hydrofluoric acid, alkaline, or similar chemicals
on all coils. These chemicals are not necessary to dissolve salt, and may damage the fin coating. Acid washes are
used to dissolve oils and greases, which generally are not present on most installations.
Alkaline washes are useful for dissolving oxides such as
zinc oxide, aluminum oxide, and iron oxide (rust). These three oxides are more corrosion resistant than base
metals, so dissolving or removing them will cause an increase in corrosion.
Xk CAUTION
Page 7
CH33 SERIES
CLEANING THE COIL:
1, Remove the coil from the cabinet or plenum, and take
the coil to an appropriate place to clean it,
2, Vacuum or brush the coil to remove matted and
surface debris from the fin. Use vacuum attachments and/or brushes that are non-destructive to fins,
3, If oil deposits are present, spray the coil with ordinary
household liquid detergent, Allow detergent to soften deposits, Wait 10 minutes,
NOTE - For units in coastal regions, fresh water will dissolve away any salt deposits. (Wash coils with fresh water at least every six months.)
4, Spray the coil at a vertical angle of 30 to 45 degrees
with a constant stream of water at moderate pressure. A pressure washer with a fan nozzle will work best, Do
not spray the coil from a horizontal direction,
5, Direct the spray so that any debris is washed out of the
coil and basepan, For most residential units, hot water is not necessary,
NOTE - Attempting to back flush from the inside of the coil
will require removing parts from the unit, and it may be very
difficult to flush the whole coil surface. Attempting to blow
water through a coil will slow the water stream and reduce
the flushing action of the outer fin surface.
6, Replace the coil into the cabinet or plenum. Ensure
that you have followed the proper procedure for routing and securing the refrigerant tubing,
A IMPORTANT
505264M 10/07
Page 8
Loading...