The CBX32MV is a high efficiency residential split system
blower/coil featuring a variable speed motor controlled by an
electronic blower drive control (BDC).
CBX32MV series units are designed to be matched with
Lennox two-speed or single-speed HFC−410A condensing
units and heat pumps. Several models are available in sizes
ranging from 1.5 through 5 tons. All units are equipped with
factory installed check and expansion valve for cooling or heat
pump applications.
Electric heat is available in several voltages and KW sizes,
and can be field installed in the cabinet.
Some CBX32MV applications may include the optional
Lennox ComfortSense
Efficiency Plus Comfort Management Control (CCB1). The
purpose of both controls is to vary indoor blower speed in
response to indoor dehumidification demand. When a
two-speed outdoor unit is used, compressor speed can
also be controlled by the SignatureStat or CCB1 in
response to indoor dehumidification demand.
Information contained in this manual is intended for use by
experienced HVAC service technicians only. All
specifications are subject to change. Procedures outlined
in this manual are presented as a recommendation only
and do not supersede or replace local or state codes.
®
7000, SignatureStatt or
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect switch(es). Unit may have multiple
power supplies.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during unit installation and service to protect the unit’s electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the unit, the control and the technician at the
same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an
unpainted unit surface before performing any
service procedure.
NOTES − The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
Low speed cooling air volume is 70% of COOL speed setting. Production units September 2005 and later; continuous blower speed for is approximately 38% of
COOL speed setting. Earlier production units continuous blower speed is approximately 50% of COOL speed setting.
Harmony Zone Control applications − Low speed cooling is approximately 250 cfm (118 L/s).
Lennox Harmony IIIt Zone Control applications − Low speed cooling is 300 cfm (145 L/s)
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
CBX32MV-018/024 BLOWER MOTOR WATTS AT +" (Plus) BDC3 SETTING (Adjust" Jumper at +" Setting)
BDC3 Jumper
Speed Positions
HEAT" Speed
COOL" Speed
Tap 1100113126142154172190206230
Tap 2155176197221237260278295310
Tap 3237260289305314337356373390
Tap 4338361379409433457447426406
Tap 1364761718195106118135
Tap 28910311 8129143163177197207
Tap 3183198229248266290307327343
Tap 4266294315330349373390411401
HEAT" SpeedCOOL" Speed
Motor Watts @ Various External Static Pressures − in. wg. (Pa)
NOTES − The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
Low speed cooling air volume is 70% of COOL speed setting. Production units September 2005 and later; continuous blower speed for is approximately 38% of
COOL speed setting. Earlier production units continuous blower speed is approximately 50% of COOL speed setting.
Harmony Zone III Control applications − Low speed cooling is approximately 300 cfm (145 L/s).
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
HEAT" SpeedCOOL" Speed
CBX32MV-024/030 BLOWER MOTOR WATTS AT +" (Plus) BDC3 SETTING (Adjust" Jumper at +" Setting)
Motor Watts @ Various External Static Pressures − in. wg. (Pa)
NOTES − The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
Low speed cooling air volume is 70% of COOL speed setting (65% COOL speed for production prior to August 2002). Production units September 2005 and later;
continuous blower speed for is approximately 38% of COOL speed setting. Earlier production units continuous blower speed is approximately 50% of COOL
speed setting.
Harmony Zone Control applications − Low speed cooling is approximately 380 cfm (178 L/s).
Lennox Harmony IIIt Zone Control applications − minimum blower speed is 442 cfm (210 L/s).
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
HEAT" SpeedCOOL" Speed
CBX32MV-036 BLOWER MOTOR WATTS AT +" (Plus) BDC3 SETTING (Adjust" Jumper at +" Setting)
Motor Watts @ Various External Static Pressures − in. wg. (Pa)
NOTES − The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
Low speed cooling air volume is 70% of COOL speed setting (60% of COOL speed for production prior to August 2002). Production units September 2005 and
later;continuous blower speed for is approximately 38% of COOL speed setting. Earlier production units continuous blower speed is approximately 50% of COOL
speed setting.
Harmony Zone Control applications − Low speed cooling is approximately 400 cfm (190 L/s).
Lennox Harmony IIIt Zone Control applications − minimum blower speed is 442 cfm (210 L/s)
12341234
cfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/scfmL/s
HEAT" SpeedCOOL" Speed
CBX32MV-048 AND CBX32MV-060 BLOWER MOTOR WATTS AT +" (Plus) BDC3 SETTING (Adjust" Jumper at +" Setting)
NOTES − The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 60% of COOL speed setting. Production units September 2005 and later;continuous blower speed for is approximately 38% of
COOL speed setting. Earlier production units continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony IIIt Zone Control applications − minimum blower speed is 442 cfm (210 L/s).
CBX32MV-068 BLOWER MOTOR WATTS AT +" (Plus) BDC3 SETTING (Adjust" Jumper at +" Setting)
Motor Watts @ Various External Static Pressures − in. wg. (Pa)
Tap 3295330375395445495555600660
Tap 4335370400445505550600660705
COOL"
Speed
Tap 1125150170210245270300340370
Tap 2160185225255300335365415450
Tap 3225245280320370420460510545
Tap 4290325355400445490545595650
Page 8
Parts Arrangement
ELECTRIC HEAT
SECTION
CBX32MV
BLOWER ACCESS
PANEL
COIL ACCESS
PANEL
CONTROL BOX
BLOWER
COMPARTMENT
HORIZONTAL
DRAIN PAN
COIL
CHECK AND EXPANSION VALVE
(COMPLETE WITH SCREEN)
UPFLOW/DOWNFLOW
DRAIN PAN
FIGURE 1
SMALL ELECTRIC HEAT
KNOCK OUT FOR
2.5 − 15 kW
GROUNDING
LUGS
CBX32MV CONTROL BOX
LARGE ELECTRIC HEAT
ADDITIONAL KNOCK
OUT FOR
20 − 30 kW
BDC3 BLOWER
CONTROL (A15)
TERMINAL
STRIP
(TB2)
BLOWER
RELAY (K20)
TRANSFORMER
(T1)
TERMINAL
STRIP (TB1)
R
W3
W2
W1
G
C
0Y1Y2DS
FIGURE 2
Page 9
I−APPLICATION
CBX32MV blower coils are designed for R410A
applications only. All major blower coil components
must be matched according to Lennox
recomme n d ations fo r the unit to be covered under
warranty. Refer to the Engineering Handbook for approved
system matchups. A misapplied system will cause erratic
operation and can result in early unit failure. The units come
with factory installed check and expansion valve for all
applications. It has been installed internally and is accessible if
required.
II−UNIT COMPONENTS
A−Control Box
The CBX32MV control box is shown in figure 2. Line voltage
and electric heat connections are made in the control box.
Optional electric heat fits through an opening located in the
center of the control box. When electric heat is not used,
knockout plates cover the opening. The electric heat control
arrangement is detailed in the electric heat section of this
manual.
B−Terminal Strips (TB1 and TB2)
All CBX32MV units are equipped with two low voltage
terminal strips (TB1 and TB2) located in the control box.
See figure 2. The strips are used for making up all indoor
thermostat wires.
All CBX32MV units have factory installed jumpers
connecting DS to Y1, R to O and Y1 to Y2. These jumpers
will have to be removed in certain unit application. See table
1.
TABLE 1
Application
Harmony II, CCB1,
SignatureStatt
Remove Jumpers
DS to Y1
Heat PumpR to O
Two−Stage CoolingY1 to Y2
C−Transformer (T1)
All CBX32MV series units use a single line voltage to
24VAC transformer mounted in the control box. The
transformer supplies power to the control circuits in the
indoor and outdoor unit.
D−Blower Relay (K20)
All units use SPDT relay to energize the blower motor in
response to heating demand. The relay coil is energized
when the 1st stage electric heat relay closes. When K20 is
energized, its N.O. contacts close to energize jack plug
JP46 pin 2 (located on blower drive control A15). When
JP46−2 is energized, the blower drive control immediately
energizes the blower on heating speed. Heating speed will
override cooling speed. K20−2 will energize the
economizer if used ( refer to wiring diagram.)
208 / 240 VOLT TRANSFORMER
PRIMARY
ORANGE
240 VOLTS
RED
208 VOLTS
BLACK
FIGURE 3
E−Circuit Breaker (CB8)−1 units & Fuse (F1)
All transformers used in the CBX32MV−1 series units are
equipped with internal secondary voltage overcurrent
protection. Each transformer uses a manual re−set circuit
breaker (CB8) located on the transformer. The circuit
breaker is connected in series with the blue secondary
voltage wire and is rated at 3.5 Amps. CBX23MV−2 units
and later are equipped with a fuse (F1) rated at 3 amps. F1
is connected in series with the blue secondary voltage wire
and like CB8 provides overcurrent protection.
SECONDARY
BLUE
YELLOW
CB8
F−Plastic Drain Pans
Both upflow/downflow and horizontal drain pans are
provided and installed on the CBX32MV units. The drain
pans are made from fiberglass-filled plastic. The drain hole
is used for right-hand air discharge only, and must be
plugged when the unit is configured for left-hand air
discharge (see page 24 for horizontal left-hand
application). Each pan has a set of connections, one for a
primary drain and one for an auxiliary drain.
G−Coil
All CBX32MV series units have dual slab coils arranged in
an "A" configuration. Each coil has two or three rows of
copper tubes fitted with ripple-edge aluminum fins. A check
and expansion valve complete with screen feeds multiple
parallel circuits through the coils. The coil is designed to
easily slide out of the unit cabinet.
Optional electric heating elements are sequenced so
blower relay K20 operates on a first on/last off basis.
H−Variable Speed Blower Motor (B3)
CBX32MV series units use a single-phase variable-speed
motor. See figure 4. A solid-state controller is attached to
the motor.
Page 10
CBX32MV MOTOR BLOWER HOUSING
ARROW MUST
BE UP
MOTOR
BLOWER HOUSING
CBX32MV BLOWER MOTOR
B3
SHAFT
MOTOR
CONTROLLER
J48
J49
CBX32MV BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 4
I−BDC3 Blower Control Board (A15)
CFM on the CBX32MV unit is controlled by the BDC3 board
(A15) located in the control box. CFM can be obtained by
positioning jumpers (COOL, HEAT and ADJUST) on the
BDC3 board. The jumpers are labeled 1,2,3, and 4. Each
enables a different air volume. Diagnostic LEDs are
provided as an aid in identifying the unit’s mode of
operation. The LEDs are labeled RUN and CFM. See
figure 5.
BLOWER SPEED ADJUSTMENTS
Diagnostic LEDs
RUN"
RUN indicates there is a demand for the blower motor to
run.
CFM"
CFM LED indicates the CFM the unit is operating according to
the jumper settings. The light flashes once for approximately
every 100 CFM. For example, if the unit is operating at 1000
CFM, CFM LED will flash 10 times. If the CFM is 1150, CFM
LED will flash 11 full times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes
place when the control is communicating with the motor
between cycles. This is normal operation.
The appropriate speed according to application and CFM
need is selected by moving jumper pins.
Jumper Settings
IMPORTANT
Before changing jumper setting, make sure the
motor has completely stopped. Any jumper setting change will not take place while the motor is
running.
Table 2 shows the recommended factory blower speed tap
selections for CBX32MV series units. These settings are
for nominal tonnage match−ups with the CBX32MV. When
matched with other sizes, it is recommended that the CFM
be adjusted to approximately 400 CFM per ton.
FACTORY BLOWER SPEED TAP SELECTION
UNIT
−018/
024
−024/
−030
−036
−048
−060
−068
*Minimum setting for heat.
COOL"HEAT"
Condensing
Unit
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3
COOL
PIN #2
COOL
PIN #3
COOL
PIN #3
To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and
conditions associated with each one. Refer to figure 5 for
identification.
After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in the blower data tables at the front of this manual. From
the tables determine which row of CFM volumes most
closely matches the desired CFM. Once a specific row has
been chosen (+, NORMAL, or −), CFM volumes from other
rows cannot be used. Below are the descriptions of each of
the jumper selections.
TABLE 2
SPEED TAP SELECTION
*Condensing Unit
Heat
PIN
#3
PIN
#3
PIN
#3
PIN
#2
PIN
#3
PIN
#3
with Electric Heat
Only
HEAT
PIN #4
HEAT
PIN #4
HEAT
PIN #4
HEAT
PIN #1
HEAT
PIN #1
HEAT
PIN #4
Pump
COOL
COOL
COOL
COOL
COOL
COOL
*Heat Pump
with Electric
Heat
HEAT
PIN #4
HEAT
PIN #4
HEAT
PIN #4
HEAT
PIN #1
HEAT
PIN #1
HEAT
PIN #4
Page 11
BDC3 VARIABLE SPEED CONTROL SELECTIONS
JP1 15 PIN PLUG
(BOARD TO MOTOR)
15
15
4
3
2
1
DIAGNOSTIC
4
3
2
1
CFM RUN
DS LEDS
ACCESSORY RELAY
CONTACTS
(DRIVES OPTIONAL
ACCESSORY
RELAY)
OPERATIONAL
SELECTOR PINS
(Affects both heating
and cooling modes)
11
JP1
ACC
24V/1A
NORM
4
+
3
−
2
TEST
ADJUSTHEAT COOLDELAY
1
NOTE − For two speed heat pump units blower will operate at
60%, 65% or 70% of COOL CFM. For single speed heat pump
units blower will operate at 100% COOL CFM until
supplemental electric heat is demanded. At that time, the
blower will operate at HEAT speed selected. This arrangement
provides for warmer supply air during heat pump operation
only.
HEAT"
The HEAT jumper is used to determine CFM during a W1
demand for electric heat operation. These jumper
selections are activated when W1 is energized with or
without a Y1 demand for heat pump compressor.
DELAY"
HEATING SPEED
SELECTOR PINS
COOLING SPEED
SELECTOR PINS
FAN DELAY
SELECTOR PINS
FIGURE 5
ADJUST"
The ADJUST pins allow the motor to run at normal speed,
approximately 10% higher, or approximately 10% lower than
normal speed. The blower tables give three rows (+,
NORMAL, and −) with their respective CFM volumes. Notice
that the normal adjustment setting for heat speed position #3
is 1315 CFM. The + adjustment setting for that position is
1445 CFM and for the − adjustment setting is 1185 CFM.
After the adjustment setting has been determined, chose the
remainder speed jumper settings from those offered in the
table in that row.
The TEST pin is available to bypass the BDC3 control and
run the motor at approximately 70% to test that the motor is
operational. This is beneficial primarily in troubleshooting.
G must be energized for motor to run.
COOL"
The COOL jumper is used to determine the CFM during
either 1) cooling or 2) heat pump operation without a call for
electric heat. These jumper selections are activated for
cooling when Y2 and DS terminals in the CBX32MV are
energized and for heating when Y2 is energized.
Applications without the Lennox SignatureStatt or
TM
EfficiencyPlus
CCB1 humidity control will provide 70% of
the COOL CFM during first−stage cooling for two−speed
outdoor units. Units built prior to August 2002, will provide
either 60% (−048, −060 series units) or 65% (−036 series
units) of the COOL CFM during first stage cooling for two
stage outdoor units. 100% of COOL speed is provided for
systems with a single−speed outdoor units.
The DELAY jumper is used to set the specific motor fan
mode of operation during cooling. Depending on the
application, one of four fan options may be chosen by
moving the jumper pins to the appropriate set of pins.
Options 1, 2, 3, or 4 will have an increased dehumidification
effect on the system. Option 1 will have the least effect and
option 4 will have the greatest effect.
Applications with the EfficiencyPlus CCB1 humidity
control create different CFM volumes. For example,
during a first−stage cooling call (two−speed outdoor unit)
with no demand from the CCB1, the air volume is 40% of
the COOL jumper selection. For a normal COOL (Pin #2
setting for CBX32MV−036), the CFM is 1125; the reduced
speed is 450 CFM (1125 x 40% = 450). This arrangement
provides for additional dehumidification during standard
first stage cooling. See tables 10 and 11 for various
scenarios concerning use of the CCB1 humidity control
and the CBX32MV series unit.
Applications with the Lennox SignatureStat but no
demand for de−humidification will operate as follows:
during a first−stage cooling call (two−stage outdoor unit),
the air volume is 70% of the COOL jumper selection. For a
normal COOL (Pin #2 setting for CBX32MV−036), the
CFM is 1125; the reduced speed is 788 CFM (1125 x 70% =
788). This arrangement provides for additional
dehumidification during standard first stage cooling. See
tables 12 and 13 for various scenarios concerning use of
the SignatureStat and the CBX32MV series unit.
For applications with Harmonyr zone control, the blower
CFM volume is determined by the Harmony control center.
This speed is not adjustable. See footnotes in the blower
tables (table of contents).
Page 12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.