Improper installation, adjustment, alteration, service or
maintenance can cause personal injury, loss of life, or
damage to property.
Installation and service must be performed by a licensed
professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
INSTRUCTIONS
Merit® CBX25UHV (-10) Series
Units
AIR HANDLERS
507616-02
7/2018
Shipping and Packing List
Package 1 of 1 contains the following:
1 - Assembled air handler unit factory-equipped for up-flow or
horizontal air discharge application (includes up-flow and
horizontal drain pans and pre-installed air filter).
Check equipment for shipping damage. If found, immediately
report damage to the last carrier. Check the unit rating plate to
confirm that delivered unit matches order.
General
The Merit® CBX25UHV air handler is designed for indoor
installation only. As shipped, the unit is ready for installation in
either up-flow or horizontal left-hand air discharge applications.
Horizontal drain pan may be repositioned in the field to allow
installation in the horizontal right-hand air discharge position.
Various accessories are listed in the CBX25UHV Product
Specification bulletin.
All units are equipped with a factory-installed check/expansion
valve.
Page 1
Merit® CBX25UHV Unit Dimensions – Up-flow – inches (mm)
NOTE - Unit is shipped configured for horizontal left-hand air discharge. Unit may be converted to horizontal right-
hand air discharge by repositioning horizontal drain pan.
Dimensions remain the same in all configurations.
Page 2
Requirements
WARNING
Excessive Weight Hazard - Use two or more people
when moving and installing the unit. Failure to do so can
result in back or other type of injury.
Do not remove the cabinet knockouts until it has been
determined which knockouts will need to be removed for
the installation.
Select the air discharge position which best suits the site
conditions. Consider required clearances, space, routing
requirements for refrigerant line, condensate disposal,
filters, duct system, wiring, and accessibility for service.
Refer to the rating plate on the air handler for specific
information.
IMPORTANT
Merit® CBX25UHV units include a factory-installed
check/expansion valve which provides optimal refriger
ant control and system performance with outdoor units
of varying capacities. These units must be installed as
part of a matched system as outlined in the CBX25UHV
Product Specification bulletin.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
These instructions are intended as a general guide and do
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation.
Compliance with all local, state, or national codes
pertaining to this type of equipment should be determined
prior to installation. Read this instruction manual, as well
as the instructions supplied in separate equipment, before
starting the installation.
In addition to conforming to manufacturer's installation
instructions and local municipal building codes, installation
of Lennox air handler units (with or without optional electric
heat), MUST conform with National Fire Protection
Association (NFPA) standards: “Standard for Installation
of Air Conditioning and Ventilation Systems” (NFPA No.
90A) and “Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems” (NFPA
No. 90B).
All models are designed for indoor installation only. The
installation of the air handler, field wiring, duct system, etc.
must conform to the requirements of the National Electrical
Code, ANSI/NFPA No. 70 (latest edition) in the United
States, and any state laws, and local ordinances (including
plumbing or wastewater codes). Local authorities having
jurisdiction should be consulted before installation is
made. Such applicable regulations or requirements take
precedence over the general instructions in this manual.
Install the conditioned air plenum, ducts and air filters
(provided) in accordance with NFPA 90B Standard for the
Installation of Warm Air Heating and Air-Conditioning
Systems (latest edition).
The air handler is shipped from the factory completely
assembled. This unit is provided with flanges for
connecting the supply plenum.
WARNING
Danger of explosion. Keep flammable ma
terials and vapors, such as gasoline, away
from air handler. Place air handler so that
heating elements are at least 18 inches (46
cm) above the floor for a garage installa
tion. Failure to follow these instructions
can result in death, explosion, or fire.
IMPORTANT
Excessive condensation may occur if the unit is installed
in a warm, humid place. When the unit is installed in an
unconditioned space, apply sealant around electrical
wires, refrigerant piping and condensate lines at the
point where they enter the cabinet.
Apply sealant on the inside of the cabinet at the point
where the electrical wires exit through the conduit open
ing. Sealing the cabinet in this way prevents warm,
moist, unconditioned air from entering the cabinet.
Warm, moist air in the cabinet forms condensate on the
cooler control box and electrical controls.
IMPORTANT
This unit is approved for installation clearance to com
bustible material as stated on the unit rating plate. Ac
cessibility and service clearances must take precedence
over combustible material clearances.
The air handler must be installed so that free access is
allowed to the coil/filter compartment and blower/control
compartment.
Installation Clearances
NON-DUCTED RETURN CLOSET INSTALLATION
The air handler can be installed in a closet with a false
bottom to form a return air plenum. It may also be installed
with a return air plenum under the air handler.
Louvers or return air grilles are field‐supplied. Local codes
may limit application of systems without a ducted return to
single-story buildings.
When a Merit® CBX25UHV unit is installed in a closet with
a louvered return opening, the minimum open area for the
louvers will be:
●320 square inches for -018 and -024 models;
●360 square inches for -030 and -036 models;
●450 square inches for -042 thru -060 models.
Page 3
MERIT® CBX25UHV SERIES
If the free area is not known, assume a 25% free area for
wood or a 75% free area for metal louvers or grilles. Using
the louver dimensions and the 25% or 75% assumption,
determine if the open area meets the minimum open area
listed above.
If a return air plenum is used, the return air grille should be
immediately in front of the opening in the plenum to allow
for the free flow of return air. When not installed in front of
the opening, there must be adequate clearance around the
air handler to allow for the free flow of return air.
Installation
Each unit consists of a blower assembly, refrigerant coil
and controls in an insulated, galvanized steel factoryfinished enclosure. Knockouts are provided for electrical
wiring entrance.
For ease in installation, it is best to make any necessary
coil configuration changes before setting air handler in
place.
REFRIGERANT METERING DEVICE
CBX25UHV units are equipped with a check/expansion
valve, which is factory-installed internal to the cabinet.
UP-FLOW APPLICATION
1 - The air handler must be supported on the bottom only
and set on a solid floor or a field‐supplied support
frame. Securely attach the air handler to the floor or
support frame.
2 - If installing a unit in an up-flow application, remove the
horizontal drain pan.
IMPORTANT - The horizontal drain pan is not required in
up-flow air discharge installations. It must be removed
to provide the best efficiency and air flow.
3 - Place the unit in the desired location and properly
slope the unit (see page 8). Connect the return and
supply air plenums as required using sheet metal
screws.
4 - In applications that do not include a return air plenum,
install units on a stand that is raised at least 14” above
the floor. This ensures proper air return.
HORIZONTAL APPLICATIONS
IMPORTANT
When removing the coil, there is a possibility of equip
ment damage and personal injury. Be careful when re
moving the coil assembly from a unit installed in right- or
left-hand applications. The coil may tip into the drain pan
once it is clear of the cabinet. Support the coil when re
moving it.
NOTE - When the unit is installed in horizontal
applications, a secondary drain pan is recommended.
Refer to local codes.
NOTE - This unit may be installed in left-hand or right-hand
air discharge horizontal applications. Adequate support
must be provided to ensure cabinet integrity. Ensure that
there is adequate room to remove service and access
panels if installing in the horizontal position.
LEFT-HAND DISCHARGE
1 - Determine which plugs are required for drain line
connections.
2 - With access door removed, remove drain line plugs to
install drain lines.
3 - Set unit so that it is sloped toward the end of the unit with
the drain pan (see figure 14).
4 - A typical horizontal configuration is shown in figure 2.
AIR FLOW
Drains
PLUGS
Figure 2. Left‐Hand Discharge Configuration
LEFT‐HAND DRAINS
HORIZONTAL DRAIN PAN
IMPORTANT - REMOVE PAN
FOR BEST EFFICIENCY
AND AIR FLOW.
UP-FLOW
DRAIN PAN
UP-FLOW DRAIN
CONNECTIONS (BOTH
SIDES; USE ONE SIDE
OR OTHER)
Figure 1. Up-flow Configuration
HORIZONTAL DRAIN
CONNECTIONS
(BOTH SIDES; NOT
USED)
Page 4
5 - If the unit is suspended, the entire length of the cabinet
must be supported. If you use a chain or strap, use a
piece of angle iron or sheet metal attached to the unit
(either above or below) to support the length of the
cabinet. Use securing screws no longer than 1/2 inch
to avoid damaging the coil or filter. See figure 3. Use
sheet metal screws to connect the return and supply
air plenums as required.
3 - Remove coil assembly, bottom drain pan and
horizontal drain pan as one unit from the air handler.
ANGLE IRON OR SHEET METALELECTRICAL INLET CLEAR
MAXIMUM 1/2”
LONG SCREW
AIR FLOW
FRONT VIEWEND VIEW
ANCE 4 IN. (102 MM)
Figure 3. Suspending Horizontal Unit
RIGHT-HAND AIR DISCHARGE
For horizontal right-hand air discharge, the following field
modifications are required.
1 - Remove and set aside blower and coil access panels.
2 - Remove brackets securing pans to unit. See figure 4.
Figure 5. Remove Coil Assembly, Bottom Drain Pan
and Horizontal Drain Pan As A Unit
Figure 4. Remove Main Drain Pan Mounting
Brackets
4 - Remove the blow-off prevention brackets, top cap and
drip pan between slabs. Move the horizontal drain pan
to the opposite side of the coil.
Figure 6. Remove Blow-Off Prevention Brackets,
Top Cap and Drip Pan
5 - Rotate drip pan 180º and reinstall on coil as shown by
the arrow above. Reinstall the top cap. Rotate the
blow-off prevention brackets 180º and reinstall using
the same screws. Use the correct mounting holes; the
brackets must cover the hairpins. See figure 7.
Page 5
MERIT® CBX25UHV SERIES
Figure 7. Reinstall the Top Cap. Brackets Must
Cover the Hairpins
6 - Slide coil assembly, bottom drain pan and horizontal
drain pan as one unit back into the air handler.
Figure 9. Reinstall Brackets that Hold the Coil and
Horizontal Drain Pan in Place
Repositioning Black Box on Motor Module – -018,
-024 and -030 Units
When the horizontal drain pan is moved to the right side of
the air handler, the black box on the back of the supply fan
motor will prevent the insertion of the blower assembly
back into the cabinet. The black box must be repositioned
to overcome this issue.
Tools and Material Required:
1" or 2" putty knife and 1" wide double-sided tape.
8 - Arrange the blower assembly on a stable surface with
the motor facing up.
MOTOR
MODULE
Figure 8. Slide Coil Assembly, Bottom Drain Pan
and Horizontal Drain Pan Back Into the Air Handler
as a Unit
7 - Reinstall the brackets that hold the coil and horizontal
drain pan in place. See figure 9.
BLACK
BOX
Figure 10. Black Box in Factory Position on Motor
Module
Page 6
9 - The black box is fastened to the motor module at each
end with a strip of black double-sided tape. Starting at
one end, slide the putty knife between the black box
and the motor module. Carefully separate the black
box from the motor module. Clean off any
double-sided tape remaining on the motor module.
Figure 11. Black Box Separated from Motor Module
11 - Slide the blower assembly into the cabinet to confirm
clearance between the horizontal drain pan and the
black box. Remove the blower assembly and relocate
the black box if necessary to achieve clearance. Make
note of the new position. Apply two new strips of
double-sided tape to the black box and affix it to the
module in the confirmed position.
12 -Slide the blower assembly back into the air handler
cabinet and install the two screws to secure the
assembly to the cabinet. Plug the motor wires back
into the motor and black box.
13 -Confirm that the black box is not touching the
horizontal drain pan.
10 - Cut a small piece of tape and apply it to the back of the
black box. This will be used to test the position of the
black box. The goal is to raise the position of the box
on the module. Position the black box onto the module
higher than the original position.
Figure 12. Black Box Repositioned on Motor Module
Figure 13. Blower Assembly Installed in Air Handler
Cabinet with Required Clearance Between
Horizontal Drain Pan and Motor Black Box
Page 7
MERIT® CBX25UHV SERIES
Condensate Drain
IMPORTANT
A field-fabricated secondary drain pan, with a drain pipe
to the outside of the building, is required in all installa
tions over a finished living space or in any area that may
be damaged by overflow from the main drain pan. In
some localities, local codes may require a secondary
drain pan for any horizontal installation.
The air handler is provided with ¾” NPT condensate drain
connections.
SLOPING THE UNIT
Make sure the unit is sloped (similar to the slope shown in
figure 14) (horizontal or up-flow) so that the drain pan will
empty completely without water standing in the pan.
THIS CORNER SHOULD BE 5/8” (+/- 1/8”) HIGHER
THAN DRAIN CORNER
THIS CORNER SHOULD BE
5/8” (+/- 1/8”) HIGHER THAN
DRAIN CORNER
INSTALL CONDENSATE DRAIN
The air handler is equipped with ¾” NPT condensate drain
connections.
IMPORTANT
On some pans, the primary and secondary drain holes
have knockouts.
Confirm primary and secondary drains are open.
1 - CB25UHV units are equipped with a drain pan, which
includes green (main drain) and red (secondary drain)
plugs. Unscrew the plugs to remove them before
inserting condensate drain fittings.
ALL CBX25UHV MODELS
UNSCREW PLUGS
AND CONNECT
PROPERLY SIZED
FIELD-PROVIDED
FITTINGS AND
DRAIN LINES.
DRAIN PAN
GREEN MAIN
DRAIN PLUG
RED SECONDARY
DRAIN PLUG
DRAIN CORNER
Figure 14. Sloping the Unit for Proper Drainage
Figure 15. Drain Line Connections
Page 8
IMPORTANT
On units of this type, the blower “draws” rather than “blows” air through the coil. A trap must be installed in the primary
(main) condensate drain line. The trap prevents the blower from drawing air through the drain lines into the air supply.
ABOVE
FINISHED
SPACE?
YES
NOTE- WHEN AN AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE, THE SECONDARY
DRAIN PAN MUST HAVE A LARGER FOOTPRINT
THAN THE AIR HANDLER.
SECONDARY
DRAIN PAN
ALWAYS RUN A SECONDARY (OVERFLOW) DRAIN LINE. IF NOT
POSSIBLE, INSTALL LOW VOLTAGE OVERFLOW SWITCH KIT.
WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.
USE TWO-PART 3/4” FEMALE SLIP INLET AND MALE ADAPTER
NO
WHEN OBSTRUCTIONS PREVENT DIRECT THREADING OF
OVERFLOW SWITCH.
SECONDARY (OVERFLOW) DRAIN LINE
LENNOX #
X3169
AIR HANDLER DRAIN PAN
MAIN DRAIN
WHEN A COIL IS LOCATED ABOVE A FINISHED
SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE
MUST BE:
●CONNECTED TO SECONDARY DRAIN PAN
OR
●CONNECTED TO THE SECONDARY
(OVERFLOW) DRAIN OUTLET OF THE AIR
HANDLER DRAIN PAN.
CLEAN OUT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
LENNOX1 P-TRAP
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4”
VENT
2”
(51MM)
TRAP MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES — GENERALLY,
TWO INCHES (51MM).
1
LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE
fittings and connect primary drain line to the main drain
pan connection.
NOTE - When installing drain line connection fittings to
the drain pan, hand tighten the fitting and use a thread
sealant. Over-tightening the fittings can split
connections on the drain pan.
3 - If the secondary drain line is to be used, remove the
plug or the knockout and route the drain line so that
water draining from the outlet will be easily noticed by
the homeowner. Refer to local codes for drain trap
requirements on the secondary drain line.
4 - Check again to ensure drain ports and drain pan are
free of all debris.
5 - Plug and check any unused drain pan openings for
tightness. Torque plugs to 30 in. lb. to prevent water
leaks or seepage from the drain pan.
6 - Install a 2” trap in the main (primary) drain lines as
close to the unit as practical (see figure 16). Make sure
TO APPROVED
DRAIN
DRAIN LINE SHOULD
SLOPE A MINIMUM OF
ONE INCH PER 10 FEET
(25MM PER 3 METERS)
FOR NEGATIVE PRESSURE COILS (BLOWER
AFTER COIL), A TRAP IS REQUIRED ON THE
MAIN DRAIN LINE CONNECTED TO COIL.
SEE LOCAL CODES FOR TRAP REQUIRE
MENTS ON SECONDARY DRAINS.
TRAP DEPTH
the top of the trap is below the connection to the drain
pan to allow complete drainage of the pan.
NOTE - Horizontal runs must have an anti-siphon air
vent (standpipe) installed ahead of the horizontal run.
See figure 16. An extremely long horizontal run may
require an oversized drain line to eliminate air traps.
NOTE - Do not operate air handler without a trap in the
main (primary) drain. The condensate drain is on the
negative pressure side of the blower; therefore, air
being pulled through the condensate line will not allow
positive drainage without a proper trap.
7 - Route the drain line to the outside or to an appropriate
drain. Drain lines must be installed so they do not block
service access to the front of the air handler. A 24”
clearance is required for filter, coil, or blower removal
and service access.
NOTE - Check local codes before connecting the drain
line to an existing drainage system.
Insulate the drain lines where sweating could cause water
damage.
Page 9
MERIT® CBX25UHV SERIES
TEST CONDENSATE DRAIN
Test the drain pan and drain line after installation:
1 - Pour several quarts of water into drain pan. Use
enough water to fill both the drain trap and the line.
2 - Check the installed drain pan. Drain pan must drain
completely. Drain line fittings must not leak. Water
must drain from the end of the primary drain line.
3 - Correct any leaks found.
Duct System and Filters
DUCT SYSTEM
The air handler is provided with flanges for the connection
of the supply plenum.
Supply and return duct system must be adequately sized
to meet the system's air requirements and static pressure
capabilities. The duct system should be insulated with a
minimum of 1” thick insulation with a vapor barrier in
conditioned areas or 2” minimum in unconditioned areas.
Supply plenum should be the same size as the flanged
opening provided around the blower outlet and should
extend at least 3 ft. from the air handler before turning or
branching off plenum into duct runs. The plenum forms an
extension of the blower housing and minimizes air
expansion losses from the blower.
FILTERS
A filter is provided. Table 1 lists the filter size for each unit.
Table 1. Unit Air Filter Size Chart
ModelFilter Size
-01812” x 20” x 111.50” x 19.50” x .75”
-024 and -03015” x 20” x 114.50” x 19.50” x .75”
-03618” x 20” x 117.50” x 19.50” x .75”
-042, -048 and -06018” x 24” x 117.50” x 23.50” x .75”
Actual Minimum
Filter Size
INSTALLING DUCT SYSTEM
Connect supply air duct to the flange on top of the air handler. If an
isolation connector is used, it must be nonflammable.
FIELD-FABRICATED RETURN AIR DUCT FLANGE
FOR HORIZONTAL APPLICATIONS
A return air duct system is recommended, but not
factory-provided. If the unit is installed in a confined space or
closet, run a full-size return connection to a location outside the
closet.
Cabinet and Duct Flange
CABINET
DOOR FLANGE
1−1/2
(38)
DUCT
FLANGE
3/4
(19)
1−1/2(38)
3/4
(19)
”A”
BRAKE DOWN 90 DEGREES
1/2
(13)
UNIT SIZE
−01814−7/8 (378)
−024 & −030 18−3/8 (467)
−036 to −060 21−3/4 (552)
3/4
(19)
1/4 (6) DIA.
2−HOLES
”A”
BOTTOM OF
CABINET
DUCT
ADAPTER
3/4
(19)
1−1/2
(38)
IMPORTANT
If a highefficiency filter is being installed as part of this
system to ensure better indoor air quality, the filter must
be properly sized. Highefficiency filters have a higher
static pressure drop than standardefficiency glass/foam
filters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop
may also cause the limit to trip more frequently during the
winter and the indoor coil to freeze in the summer, result
ing in an increase in the number of service calls.
Before using any filter with this system, check the spe
cifications provided by the filter manufacturer against the
data given in the appropriate Lennox Product Specifica
tions bulletin. Additional information is provided in Ser
vice and Application Note ACC002 (August 2000).
Figure 17. Cabinet and Duct Flange
Brazing Refrigerant Lines
Refrigerant lines must be connected by a qualified technician in
accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dry, refrigerant-grade
copper lines. Air handler coils should be installed only
with specified line sizes for approved system combina
tions.
Handle the refrigerant lines gently during the installation
process. Sharp bends or kinks in the lines will cause a
restriction.
Page 10
WARNING
Polyol ester (POE) oils used with HFC-410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or
service valve stub caps until you are ready to make
connections.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in the low side shell and suction tubing
being pressurized. Application of a
brazing torch while pressurized may
result in ignition of the refrigerant and oil
mixture - check the high and low
pressures before unbrazing.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration
or air conditioning system, use a
regulator that can control the pressure
down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
IMPORTANT
To prevent the build-up of high levels of nitrogen when
purging, be sure it is done in a well ventilated area. Purge
low pressure nitrogen (1 to 2 psig) through the refrigerant
piping during brazing. This will help to prevent oxidation
and the introduction of moisture into a system.
NOTE - When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, CORP. 9351-L9, or contact
Lennox Technical Support Product Applications for
assistance. To obtain the correct information from Lennox,
be sure to communicate the following information: Model
and capacity.
1 - Route the suction and liquid lines from the fittings on the
indoor coil to the fittings on the outdoor unit. Run the lines in
a direct path, avoiding unnecessary turns and bends.
2 - Make sure that the suction line is insulated over the entire
exposed length and that neither suction nor liquid lines are
in direct contact with floors, walls, duct system, floor joists, or
other piping.
3 - To avoid damaging the rubber grommets in the cabinet while
brazing, slide the rubber grommets over the refrigerant lines
until they are away from the heat source.
NOTE - Place wet rags against piping plate and around
suction line connections.
4 - Connect the suction and liquid lines to the evaporator coil.
Take care to protect the cabinet and internal components as
detailed in figure 18.
5 - Braze using an alloy of silver or copper and phosphorus with
a melting point above 1,100°F (593°C).
NOTE - Do not use soft solder.
6 - Allow refrigerant pipes to cool to room temperature.
7 - Reinstall the rubber grommets into the refrigerant piping
panel.
NOTE - Make sure expansion valve capillary tube is not
touching metal edges or copper tubing.
8 - Make sure outdoor unit has been placed according to the
Installation Instructions and is connected to the refrigerant
lines.
Page 11
MERIT® CBX25UHV SERIES
PLEASE READ IMPORTANT ISSUES CONCERNING BRAZING
OPERATIONS ON PREVIOUS PAGES BEFORE PROCEEDING.
NOTE - REFER TO OUTDOOR UNIT INSTALLATION
INSTRUCTIONS FOR REFRIGERANT PIPING SIZE
REQUIREMENTS.
NOTE - Use silver alloy brazing rods with five or six percent
minimum silver alloy for copper-to-copper brazing, 45
percent alloy for copper-to-brass and copper-to-steel
brazing.
REMOVE ACCESS PANEL
A
REMOVE RUBBER PLUG FROM BOTH LIQUID
B
AND SUCTION LINES
NOTE - CBX25UHV SERIES UNITS USE NITROGEN OR DRY AIR
AS A HOLDING CHARGE. IF THERE IS NO PRESSURE WHEN
THE RUBBER PLUGS ARE REMOVED, CHECK THE COIL FOR
LEAKS BEFORE INSTALLING.
EITHER REMOVE OR PUSH PIPE WRAPPING BACK
C
THROUGH HOLE IN PIPING PLATE BEFORE LINE
SET CONNECTION AND BRAZING.
PIPING
PLATE
LOW
HIGH
CONNECT PIPES
D
NOTE - REFRIGERANT LINE SETS
SHOULD BE ROUTED TO ALLOW
FILTER ACCESSIBILITY.
PLACE A WET RAG AGAINST PIPING
F
PLATE AND AROUND THE SUCTION
LINE CONNECTION. A
BRAZE CONNECTION. ALLOW PIPE TO
G
COOL BEFORE REMOVING WET RAG
FROM CTXV SENSING BULB AND PIPING
PANEL AREA.
REPEAT PREVIOUS PROCEDURE FOR
H
LIQUID LINE.
CONNECT GAUGES AND
E
START NITROGEN FLOW
FLOW REGULATED NITROGEN (AT 1 TO 2 PSIG)
THROUGH THE REFRIGERATION GAUGE SET INTO THE
VALVE STEM PORT CONNECTION ON THE OUTDOOR
UNIT LIQUID LINE SERVICE VALVE AND OUT OF THE
VALVE STEM PORT CONNECTION ON THE SUCTION
SERVICE VALVE.
REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR
UNIT FOR LEAK TESTING, EVACUATING AND CHARGING
PROCEDURES
NITROGEN
Figure 18. Brazing Connections
Page 12
Sealing the Unit
Seal the unit so that warm air is not allowed into the cabinet. Warm
air introduces moisture, which results in water blow-off problems.
This is especially important when the unit is installed in an
unconditioned area.
If installed in an unconditioned space, sealant should be applied
around the electrical wires, refrigerant tubing, and condensate
lines where they enter the cabinet.
WARNING
There must be an air-tight seal between the bottom of the
air handler and the return air plenum. Use fiberglass
sealing strips, caulking, or equivalent sealing method
between the plenum and the air handler cabinet to
ensure a tight seal. Return air must not be drawn from a
room where this air handler or any gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing
device (i.e., wood fireplace) is installed.
IMPORTANT
Use duct tape and/or Permagum to seal closed any
space around the holes where the drain lines exit the
cabinet. Warm air must not be allowed to enter through
any gaps or holes in the cabinet.
Electrical Connections
WARNING
Electric Shock Hazard.
Can cause injury or death.
Foil‐faced insulation has conductive characteristics sim
ilar to metal. Be sure there are no electrical connections
within a ½” of the insulation. If the foil‐faced insulation
comes in contact with electrical voltage, the foil could
provide a path for current to pass through to the outer
metal cabinet. While the current produced may not be
enough to trip existing electrical safety devices (e.g.
fuses or circuit breakers), the current can be enough to
cause an electric shock hazard that could cause person
al injury or death.
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be
grounded in accordance with national
and local codes.
Line voltage is present at all
components when unit is not in
operation on units with single‐pole
contactors. Disconnect all remote
electric power supplies before
opening access panel. Unit may have
multiple power supplies.
WARNING
Electric shock hazard! - Disconnect all
power supplies before servicing.
Replace all parts and panels before op
erating.
Failure to do so can result in death or elec
trical shock.
WARNING
Run 24V Class II wiring only through specified low
voltage opening. Run line voltage wiring only
through specified high voltage opening. Do not
combine voltage in one opening.
WARNING
Electrically ground air handler. Connect
ground wire to ground terminal marked
“GND”.
Failure to do so can result in death or elec
trical shock.
●Wiring must conform to the current National Electric
Code ANSI/NFPA No. 70, or Canadian Electric Code
Part I, CSA Standard C22.1, and local building codes.
Refer to following wiring diagrams. See unit
nameplate for minimum circuit ampacity and
maximum over-current protection size.
Page 13
MERIT® CBX25UHV SERIES
●Electrical wiring, disconnect means and over-current
protection are to be supplied by the installer. Refer to
the air handler rating plate for maximum over-current
protection, minimum circuit ampacity, as well as
operating voltage.
Select the proper supply circuit conductors in
accordance with tables 310-16 and 310-17 in the
National Electric Code, ANSI/NFPA No. 70 or tables
1 through 4 in the Canadian Electric Code, Part I,
CSA Standard C22.1.
●The power supply must be sized and protected
according to the specifications supplied on the
product.
●This air handler is factory-configured for 240 volt,
single phase, 60 cycles. For 208-volt applications, see
“208 Volt Conversion” later in this section.
●Separate openings have been provided for 24V low
voltage and line voltage. Refer to the dimension
illustration of specific location.
●This unit is provided with holes for conduit. Use
provided caps to seal holes not used.
●Typical unit wiring (as well as wiring of optional
field-installed electric heat) is given in figure 21. Refer
to the instructions provided with the electric heat
section for proper installation.
●See figure 22 for typical low voltage field wiring
connections.
WARNING
USE COPPER CONDUCTORS ONLY
LOW VOLTAGE TERMINAL STRIP
Figure 19. Electrical Connections
(Upflow Configuration)
208 VOLT CONVERSION
1 - Disconnect all power supplies.
2 - Remove the air handler access panel.
3 - Using the wiring diagram located on the unit access
panel as a reference, move the black transformer
leads from the 240-volt terminal on the transformer to
the 208-volt terminal on the transformer.
See figure 20.
208 / 240 VOLT TRANSFORMER
PRIMARYSECONDARY
1 - Disconnect all power supplies.
2 - Remove the air handler access panel.
3 - Route the field supply wires to the air handler electrical
connection box.
4 - Use UL-listed wire nuts to connect the field supply
conductors to the unit black and yellow leads, and the
ground wire to ground terminal marked GND.
5 - Replace the air handler access panel.
240 Volts
208 Volts
Figure 20. Converting Unit from 240 VAC to 208 VAC
Page 14
SYSTEMFIELD JUMPERS
SINGLE STAGE AIR CONDITIONER NEED ALL
TWO−STAGE AIR CONDITIONERREMOVE Y1 TO Y2
SINGLE STAGE HEAT PUMPREMOVE R TO O
TWO−STAGE HEAT PUMPREMOVE Y1 TO Y2 AND R TO O
TWO−STAGE ELECTRIC HEATREMOVE W1 TO W2
TO ACTIVATE DEHUMIDIFICATION REMOVE R TO DS
POWER (FACTORY WIRED)
POWER (FIELD WIRED)
CONTROL (FACTORY WIRED)
CONTROL (FIELD WIRED)
CONTROL CIRCUIT WIRING TO
BE 24 VOLT, N.E.C. CLASS 2
PLUG PIN
LOCATION
2
2
4156
**
TD = TIME DELAY (OPT .)
TR = TRANSFORMER
1
2
3
4
5
6
7
8
9
10
11
12
BR = BLOWER RELAY
MTR = BLOWER MOTOR
CAP = MOTOR CAPACITOR
GND = GROUND CONNECTION
*** SEQUENCER USED: WIRED AS SHOWN
RELAY USED: WIRED PER RELAY POLE
TO BREAK CIRCUIT
NO DEVICE PRIOR TO 10−15−2014
WIRING DIAGRAM: NO HEAT
WIRE NUTS
BY OTHERS
CIRCUIT BOARD
13
14
15
14 BLK
1
6−PIN
PLUG
14 YEL(240V)
14 WHT(120V)
2
THREE POLE SEQUENCER
TIMING − SEC
ON
1−20
20−60
20−60
TWO POLE SEQUENCER
3
3
TIMING − SEC
ON
30−90
6514
30−90
L1
L2 OR
NEUT.
14 GRN
GRD
(OPT.)
(OPT.)
OFF
40−110
1−30
1−30
OFF
1−30
1−30
15 AMP
SUPPLY
VOLTAGE
W2
W1
W2
Figure 21. Typical Wiring Diagram — CBX25UHV Air Handler with Electric Heat
GND
G
W1
G
OR
O
DS
R
DS
C
Y1
C
Y1
Y2
Y2
Page 15
MERIT® CBX25UHV SERIES
Figure 22. Low Voltage Connections (Variable-Speed Motor)
WARNING
USE COPPER CONDUCTORS ONLY
Page 16
BDC3 Blower Control
JP1 15 PIN
PLUG (BOARD
TO MOTOR)
QC1
24V ACCESSORY
CONTACTS –
RATED FOR 1 AMP
OR LESS
OPERATIONAL
SELECTOR PINS
(AFFECTS BOTH
HEATING AND
COOLING MODES)
Figure 23. BDC3 Variable Speed Control Selections
SERVICE
24V/1A
QC2
ADJUSTHEATCOOLDELAY CFM RUN
HEATING SPEED
SELECTOR PINS
COOLING SPEED
SELECTOR PINS
Merit® CBX25UHV units are equipped with a
variable-speed motor that is capable of maintaining a
specified CFM throughout the external static range. A
particular CFM can be obtained by positioning jumpers
(COOL, HEAT, and ADJUST) on the BDC3 control.
The jumpers are labeled 1, 2, 3, and 4. This indicates the
selected air volume (CFM). The ADJUST jumper is
labeled Test, -, +, and Norm. The - and + pin settings are
used to add or subtract a percentage of the CFM selected.
The Test jumper is used to operate the motor in the test
mode. The delay jumper controls the timing pattern in
which the fan delay occurs.
Figure 23 illustrates the BDC3 control. Use either table 5
on page 19, or table 6 on page 19, to determine the correct
air volume for heat and cool speed taps.
Diagnostic LEDs located on the BDC3 control to assist in
servicing the unit. Read the jumper settings section before
adjusting blower speed. Refer to figure 23 on page 17 for
identification.
NORM
+
TEST
JP1
4
3
2
1
4
3
2
1
FAN DELAY
SELECTOR PINS
4
3
2
1
DIAGNOSTIC
LEDS
Adjusting the Blower Speed
Diagnostic LEDs
1 - RUN LED indicates there is a demand for the blower
motor to run.
2 - CFM LED indicates the cubic feet per minute at which
the unit is operating. The light flashes once for
approximately every 100 CFM. For example, if the unit
is operating at 1000 CFM, CFM LED will flash 10
times. If the CFM is 1150, CFM LED will flash 11 full
times plus one fast or half flash.
At times, the light may appear to flicker or glow. This is
normal and occurs when the control is communicating with
the motor between cycles.
Move the jumper pins to select the blower speed needed to
meet application CFM requirements.
Page 17
JUMPER SETTINGS
IMPORTANT
Before changing jumper setting, make sure the
motor has completely stopped. Any jumper setting
change will not take place while the motor is
running.
Table 2 lists the recommended factory blower speed tap
selections for Merit® CBX25UHV series units. These
settings are for nominal tonnage match-ups with the Merit
CBX25UHV. When matched with other sizes, it is
recommended that the CFM be adjusted to provide
approximately 400 CFM per ton.
Table 2. Recommended Blower Speed Taps
Speed Tap Selection
Air Handler
CBX25UHV018
CBX25UHV024
CBX25UHV030
CBX25UHV036
CBX25UHV042
CBX25UHV048
CBX25UHV060
NOTES -
1 - Condensing Unit
2 - Heat Pump
3 - Condensing Unit with electric heat only
4 - Heat Pump with electric heat
* Minimum setting for heat
To change jumper positions, gently pull the jumper off the
pins and insert it onto the desired set of pins. The following
section outlines the different jumper selections available
and conditions associated with each one as illustrated in
figure 23.
After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in the appropriate tables on the following pages. From the
tables, determine which row of CFM volumes most closely
matches the desired CFM. Once a specific row has been
chosen (+, NORMAL, or -), CFM volumes from other rows
cannot be used. Below are descriptions of the jumper
selections.
ADJUST JUMPER
The ADJUST pins allow the motor to run at normal speed,
slightly higher (approximately 10%) than normal speed, or
slightly lower (approximately 10%) than normal speed. The
tables on the following pages list three rows (+, NORMAL,
and -) with their respective CFM volumes. Notice in table 3,
for example, that the normal adjustment setting for heat
CoolingHeating*
Note 1 -Note 2 -Note 3 -Note 4 -
COOL
PIN #2
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3-
COOL
PIN #3-
COOL
PIN #2
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3
COOL
PIN #3-
COOL
PIN #3-
HEAT
PIN #2
HEAT
PIN #2+
HEAT
PIN #2+
HEAT
PIN #2
HEAT
PIN #2
HEAT
PIN #2
HEAT
PIN #2
MERIT® CBX25UHV SERIES
HEAT
PIN #2
HEAT
PIN #2+
HEAT
PIN #2+
HEAT
PIN #2
HEAT
PIN #2
HEAT
PIN #2
HEAT
PIN #2
®
speed position #4 is 1000 CFM. The + adjustment setting for
that position is 1080 CFM and for the - adjustment setting is
910 CFM. After the adjustment setting has been determined,
choose the remaining speed jumper settings from those
offered in the table in that row.
The TEST pin is available to bypass the BDC3 control and
run the motor at approximately 70% to test that the motor is
operational. This is beneficial primarily in troubleshooting.
G must be energized for motor to run.
COOL JUMPER
The COOL jumper is used to determine the CFM during
either cooling or heat pump operation without a call for
electric heat. These jumper selections are activated for
cooling when Y2 and DS terminals in the Merit
CBX25UHV are energized. The are activated for heating
when Y2 is energized.
Applications without the Lennox ComfortSense® 7000
thermostat will provide 70% of the COOL CFM during
first-stage cooling for two-stage outdoor units. 100% of
COOL speed is provided for systems with a single-stage
outdoor unit.
Applications with the Lennox ComfortSense® 7000
Table 3. Merit® CBX25UHV‐018 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
thermostat, but no demand for de-humidification will
operate as follows: during a first-stage cooling call
(two-stage outdoor unit), the air volume is 70% of the
COOL jumper selection. This arrangement provides for
additional dehumidification during standard first-stage
cooling. See the tables that follow for various scenarios
concerning use of the ComfortSense® 7000 thermostat
and the Merit® CBX25UHV series unit.
For applications with Harmony III® zone control, the air
handler CFM volume is determined by the Harmony III
control center. The minimum blower speed is
predetermined at 250 CFM for -018, -024, -030 and -036
units and 450 CFM for -042, -048 and -060 units. This
®
speed is not adjustable. See footnotes in the blower
performance tables.
With the thermostat set for Continuous Fan and without a
call for heating or cooling, the Merit® CBX25UHV provides
50% of the COOL CFM selected.
NOTE - For two-stage heat pumps, air handler will operate
at 70% of the COOL selection until supplemental electric
heat is demanded. At that time, the air handler will operate
at the selected HEAT speed. This arrangement provides
warmer supply air during second-stage heating.
Jumper Speed Positions
“ADJUST”
Jumper
Setting
cfmcfmcfmcfmcfmcfmcfmcfmcfmcfmcfmcfm
+47067089010803504706207604706758901090
NORM44061581010003504505607004356108151020
–400560730910350420520650400575725915
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Table 4. Merit® CBX25UHV‐024 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Page 18
Table 5. Merit® CBX25UHV‐030 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Table 6. Merit® CBX25UHV‐036 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 250 cfm.
Table 7. Merit® CBX25UHV‐042 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 450 cfm.
Page 19
MERIT® CBX25UHV SERIES
Table 8. Merit® CBX25UHV‐048 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 450 cfm.
Table 9. Merit® CBX25UHV‐060 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
NOTES
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications minimum blower speed is 450 cfm.
Table 10. Merit® CBX25UHV, Thermostat and Single-Stage Outdoor Unit Operating Sequence
Operating SequenceSystem DemandSystem Response
System
Condition
NO CALL FOR DEHUMIDIFICATION
Normal Operation1OnOn OnAcceptable24 VACHigh100%
BASIC MODE (only active on a Y1 thermostat demand)
Normal
Operation
Dehumidification Call2OnOn OnDemand0 VACHigh
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1OnOn OnAcceptable24 VACHigh100%
Dehumidification Call2OnOn OnDemand0 VACHigh
Dehumidification Call
ONLY
* During dehumidification, cooling air handler speed is as follows: 70% of COOL cfm for 018, 024, 030; 65% for 036; 60% for 042, 048 and 060 units.
** Thermostat will maintain the room temperature up to 2°F (1.2°C) cooler than the room thermostat setting in precision mode.
Step
1OnOn OnAcceptable24 VACHigh100%
1OnOn OnDemand0 VACHigh
Jumpers at indoor unit with a single stage outdoor unit
With Condensing unit - Y1 to Y2 and R to O
With Heat Pump - Y1 to Y2
Thermostat DemandRelative Humidity
Y1Y2OGW1 W2StatusD
Com
pressor
Air
Handler
CFM
(COOL)
60%/65
70%*
60%/65%
70%*
60%/65%
70%*
Comments
Compressor and indoor air handler fol
low thermostat demand
Thermostat energizes Y1 and de-ener
gizes D on a call for dehumidification
Dehumidification mode begins when hu
midity is greater than set point
Thermostat will try to maintain room hu
midity setpoint by allowing the room
space to maintain a cooler room ther
mostat setpoint**
Page 20
Table 11. Merit® CBX25UHV, Thermostat and Two‐Stage Outdoor Unit Operating Sequence
F
Operating SequenceSystem DemandSystem Response
Thermostat DemandRelative Humidity
System
Condition
NO CALL FOR DEHUMIDIFICATION
Normal Operation
- Y1
Normal Operation
- Y2
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation1OnOnOnAcceptable24 VACLow70%
Dehumidification
Call
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1OnOnOnAcceptable24 VACLow70%
Dehumidification
Call
Dehumidification
Call ONLY
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation1OnOnOnOnAcceptable24 VACHigh100%
Dehumidification
Call
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation1OnOnOnOnAcceptable24 VACHigh100%
Dehumidification
Call
Dehumidification
Call ONLY
* During dehumidification, cooling air handler speed is as follows: 70% of COOL cfm for 018, 024, 030; 65% for 036; 60% for 042, 048 and 060 units.
** Thermostat will maintain the room temperature up to 2°F (1.2°C) cooler than the room thermostat setting in precision mode.
Step
1OnOnOnAcceptable24 VACLow70%
2OnOnOnOnAcceptable24 VACHigh100%
Room Thermostat Calls for First-Stage Cooling
2OnOnOnOnDemand24 VACHigh
2OnOnOnOnDemand0 VACHigh
1OnOnOnOnDemand0 VACHigh
Room Thermostat Calls for First- and Second-Stage Cooling
2OnOnOnOnDemand0 VACHigh
2OnOnOnOnDemand0 VACHigh
1OnOnOnOnDemand0 VACHigh
Jumpers at indoor unit with a two-stage outdoor unit
With Condensing unit - Y2 and R to O
With Heat Pump - none
Com
pressor
Air
Handler
CFM
(COOL)CommentsY1Y2OGW1 W2StatusD
60%/65%
70%*
60%/65%
70%*
60%/65%
70%*
60%/65%
70%*
60%/65%
70%*
60%/65%
70%*
Compressor and indoor air handler follow
thermostat demand
Thermostat energizes Y2 and de-ener
gizes D on a call for dehumidification
Dehumidification mode begins when hu
midity is greater than set point
Thermostat will try to maintain room hu
midity setpoint by allowing the room
space to maintain a cooler room thermo
stat setpoint**
Thermostat energizes Y2 and de-ener
gizes D on a call for dehumidification
Dehumidification mode begins when hu
midity is greater than set point
Thermostat will try to maintain room hu
midity setpoint by allowing the room
space to maintain a cooler room thermo
stat setpoint**
HEAT JUMPER
The HEAT jumper is used to determine CFM during
electric heat operation only. These jumper selections are
activated only when W1 is energized.
DELAY JUMPER
The DELAY jumper is used to set the specific motor fan
operation during cooling mode. Depending on the
application, one of four options may be chosen by moving
the jumper to the appropriate set of pins.
#1 Pins Jumpered
A- Motor runs at 100% until demand is satisfied.
B- Once demand is met, motor ramps down to stop.
AB
100% CFM
COOLING
DEMAND
OFFOFF
#2 Pins Jumpered
A- Motor runs at 100% until demand is satisfied.
Page 21
B- Once demand is met, motor runs at 100% for 60
seconds.
C- Motor ramps down to stop.
B
100% CFM
(60 seconds)
C
OF
OFF
A
100% CFM
COOLING DEMAND
#3 Pins Jumpered
A- Motor runs at 82% for approximately 7-1/2 minutes. If
demand has not been satisfied after 7-1/2 minutes -
B- Motor runs at 100% until demand is satisfied.
C- Once demand is met, motor ramps down to stop.
C
OFF
OFF
A
7 1/2 MIN
82%CFM
B
100% CFM
COOLING DEMAND
MERIT® CBX25UHV SERIES
#4 Pins Jumpered
A- Motor runs at 50% for 30 seconds.
B- Motor then runs at 82% for approximately 7-1/2
minutes. If demand has not been satisfied after 7-1/2
minutes,
C- Motor runs at 100% until demand is satisfied.
D- Once demand is met, motor runs at 50% for 30
seconds.
E- Motor ramps down to stop.
CD
100%
CFM
1/2 MIN
50% CFM
E
OFF
OFF
A
1/2 MIN
50% CFM
B
7 1/2 MIN
82% CFM
COOLING DEMAND
Check-Out Procedures
NOTE - Refer to outdoor unit installation instructions for
system start-up instructions and refrigerant charging
instructions.
PRE‐START‐UP CHECKS
●Is the air handler properly and securely installed?
●If horizontally configured, is the unit sloped up to 5/8”
toward drain lines?
●Will the unit be accessible for servicing?
●Has a secondary (auxiliary) pan been provided under
the unit with separate drain for units installed above a
finished ceiling or in any installation where condensate
overflow could cause damage?
●Have ALL unused drain pan ports been properly
plugged?
●Has the condensate line been properly sized, run,
trapped, pitched and tested?
●Is the duct system correctly sized, run, sealed and
insulated?
●Have all cabinet openings and wiring been sealed?
●Is the indoor coil factory‐installed TXV properly sized
for the outdoor unit being used?
●Have all unused parts and packaging been disposed
of properly?
●Is the filter clean, in place and adequately size?
●Is the wiring neat, correct and in accordance with the
wiring diagram?
●Is the unit properly grounded and protected (fused)?
●Is the thermostat correctly wired and in a good
location?
●Are all access panels in place and secure?
CHECK BLOWER OPERATION
●Set thermostat to FAN ON.
●The indoor blower should come on.
CHECK COOLING OPERATION
●Set thermostat to force a call for cooling
(approximately 5ºF lower than the indoor ambient
temperature).
●The outdoor and indoor units should come on
immediately.
●Check the airflow from a register to confirm that the
system is moving cooled air.
●Set the thermostat 5ºF higher than the indoor
temperature. The indoor blower and outdoor unit
should cycle off. Air handler should cycle off 45
seconds after the outdoor unit shuts off.
CHECK ELECTRIC HEATER (IF USED)
●Set thermostat to call for auxiliary heat (approximately
5°F above ambient temperature). The indoor blower
and auxiliary heat should come on together. Allow a
minimum of 3 minutes for all sequencers to cycle on.
●Set the thermostat so that it does not call for heat.
Allow up to 5 minutes for all sequencers to cycle off.
Maintenance
IMPORTANT
Do not operate system without a filter. A filter is required
to protect the coil, blower, and internal parts from exces
sive dirt and dust. The filter is placed in the return duct
by the installer.
●Inspect air filters at least once a month and replace or
clean as required. Dirty filters are the most common
cause of inadequate heating or cooling performance.
●Replace disposable filters. Cleanable filters can be
cleaned by soaking in mild detergent and rinsing with
cold water.
●Install new/clean filters with the arrows on the side
pointing in the direction of airflow. Do not replace a
cleanable (high velocity) filter with a disposable (low
velocity) filter unless return air system is properly sized
for it.
●If water is seen dripping from the secondary drain line,
contact a qualified service technician. This is a sign of
a problem which must be investigated and corrected.
Cabinet Insulation
IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR
REPLACED before the unit is put back into operation. In
sulation loses its insulating value when wet, damaged,
separated or torn.
Matt‐ or foil-faced insulation is installed in indoor
equipment to provide a barrier between outside air
conditions (surrounding ambient temperature and
humidity) and the varying conditions inside the unit. If the
insulation barrier is damaged (wet, ripped, torn or
Page 22
separated from the cabinet walls), the surrounding
ambient air will affect the inside surface temperature of the
cabinet. The temperature/humidity difference between the
inside and outside of the cabinet can cause condensation
on the inside or outside of the cabinet which leads to sheet
metal corrosion and subsequently, component failure.
REPAIRING DAMAGED INSULATION
Areas of condensation on the cabinet surface are an
indication that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good
condition, the insulation should be cut in an X pattern,
peeled open, glued with an appropriate all-purpose glue
and placed back against the cabinet surface, being careful
to not overly compress the insulation so the insulation can
retain its original thickness. If such repair is not possible,
replace the insulation. If using foil‐faced insulation, any
cut, tear, or separations in the insulation surface must be
taped with a similar foil-faced tape.
GLUE - Make sure there is
full coverage of glue on the
metal or insulation so there
are no areas where air
pockets may form which
can lead to sweating.
Use of Air Handler During Construction
Lennox does not recommend the use of its air handler unit
during any phase of construction. Very low return air
temperatures, harmful vapors and operation of the unit
with clogged or misplaced filters will damage the unit.
Air handler units may be used for heating (heat pumps) or
cooling of buildings under construction, if the following
conditions are met:
●A room thermostat must control the air handler. The
use of fixed jumpers is not allowed.
●Air filter must be installed in the system and must be
maintained during construction.
●Air filter must be replaced upon construction
completion.
●The air handler evaporator coil, supply fan assembly
and duct system must be thoroughly cleaned following
final construction clean-up.
●All air handler operating conditions must be verified
Installing Date_______________________________
Air Handler Model #___________________________
Thermostat
SUPPLY
AIR
9
Disconnect
Switch
2
Line Voltage
3
Integrated Control
Blower Motor Amps
6
Electric Heat Amps
7
RETURN
AIR
DUCT SYSTEM
1
SUPPL Y AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLT AGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
Installing Date_______________________________
Air Handler Model #___________________________
Disconnect
Switch
Line Voltage
3
1
Duct System
RETURN
AIR
4
Drain Line
DUCT SYSTEM
1
SUPPL Y AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLT AGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight