Lennox CBX25UH User Manual

Page 1
INSTALLATION
E2012 Lennox Industries Inc.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
Dallas, Texas, USA
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
WARNING
The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects, or reproductive harm.
INSTRUCTIONS
Merit® CBX25UH Series Units
AIR HANDLERS
506757-01 (0659371-80) 10/2012
Table of Contents
Shipping and Packing List 1......................
CBX25UH Series Units 1.........................
Requirements 3.................................
Installation Clearances 3.........................
Installation 4....................................
Condensate Drain 6.............................
Duct System and Filters 7........................
Connecting Refrigerant Lines 8...................
Sealing the Unit 8...............................
Electrical Connections 9.........................
Airflow - Cooling Blower Speed 10..................
Check-Out Procedures 12.........................
Operation 12....................................
Maintenance 13..................................
Cabinet Insulation 13.............................
Shipping and Packing List
Package 1 of 1 contains the following:
1 - Assembled air handler unit for upflow or horizontal air
discharge application (includes upflow and horizontal drain pans and pre-installed air filter).
Check equipment for shipping damage. If found, immediately report damage to the last carrier. Check the unit rating plate to confirm that delivered unit matches order.
General
The CBX25UH air handler is designed for indoor installation only. As shipped, the unit is ready for installation in either upflow, horizontal left-hand and right-hand air discharge applications. Electric heat, down flow air discharge application kits, air filters and other various accessories are available and listed in the CBX25UH Product Specification bulletin for ordering.
All units come with a factory installed check/expansion valve.
Litho U.S.A.
10/2012 506757-01 (0659371-80)
Page 1
*2P102012* *P506757-01*
Page 2
CBX25UH Unit Dimensions - inches (mm)
CB
F
AIR FLOW
SUCTION LINE
LIQUID LINE
3/4 (19)
A
CONDENSATE DRAIN PIPING PLATE (4) (21/4 x 33/4)
FILTER ACCESS
LINE VOLTAGE
Right, Left and Top
LOW VOLTAGE
Right Side Only
J
E
3/4
D
G
21/2
(64)
(Opening)
21/2 (64)
FRONT VIEW
(19)
13/4
(44)
H
(Opening)
SIDE VIEW
21/2 (64)
Dimension
A
B
C
D
E
F
G
H
J
Supply Air
Opening
Return Air
Opening
018
inches mm
38 965
15 381
22 559
6 152
11 279
35/8 92
10 254
173/4 451
35/8 92
Depth 17 432
Width 13 330
Depth 203/4 527
Width 121/2 318
024
inches mm
401/2 1029
181/2 470
22 559
6 152
14 357
51/2 140
131/2 343
173/4 451
51/2 140
17 432
161/2 419
203/4 527
16 406
43 1092
181/2 470
22 559
6 152
16 406
51/2 140
131/2 343
173/4 451
51/2 140
17 432
161/2 419
203/4 527
16 406
inches mm
48 1219
217/8 556
22 559
121/4 311
187/8 479
53/4 146
167/8 429
173/4 451
53/4 146
17 432
197/8 505
203/4 527
193/8 492
inches mminches mm
48 1219
217/8 556
26 660
61/4 159
177/8 454
31/4 83
167/8 429
213/4 552
45/8 117
21 533
197/8 505
243/4 629
193/8 492
048 / 060−042−036−030
inches mm
521/2 1334
217/8 556
26 660
63/8 162
151/4 387
31/4 83
167/8 429
213/4 552
63/8 162
21 533
197/8 505
243/4 629
193/8 492
Page 2
Page 3
Requirements
WARNING
Excessive Weight Hazard - Use two or more people when moving and installing the unit. Failure to do so can result in back or other type of injury.
IMPORTANT
The CBX25UH units are designed to match, and must be used with, outdoor units as rated. The indoor sections are manufactured with a check/expansion valve (TXV) to provide optimum refrigerant control and system performance with a variety of different capacities of out door units.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation. Read this instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.
In addition to conforming to manufacturer's installation instructions and local municipal building codes, installation of Lennox air handler units (with or without optional electric heat), MUST conform with National Fire Protection Association (NFPA) standards: “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA No. 90A) and “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA No. 90B).
All models are designed for indoor installation only. The installation of the air handler, field wiring, duct system, etc. must conform to the requirements of the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or wastewater codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
Install the conditioned air plenum, ducts and air filters (provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).
The air handler is shipped from the factory completely assembled. The unit is provided with flanges for the connection of the duct system.
Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation.
Select the final air discharge position which best suits the site conditions. Consider required clearances, space, routing requirements for refrigerant line, condensate disposal, filters, duct system, wiring, and accessibility for service. Refer to the air handler rating plate on the air handler for specific information.
WARNING
Danger of explosion. Keep flammable ma terials and vapors, such as gasoline, away from air handler. Place air handler so that heating elements are at least 18 inches (46 cm) above the floor for a garage installa tion. Failure to follow these instructions can result in death, explosion, or fire.
NOTES — During cooling operation, excessive sweating may occur if
the air handler is installed in a warm and humid space.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
Electrical wires should be sealed on the inside where they exit the conduit opening. Sealant is required to prevent air leakage into, and condensate from forming inside of, the air handler, the control box, and on the electrical controls.
This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances.
The air handler must be installed so that free access is allowed to the coil/filter compartment and blower/control compartment.
Installation Clearances
NON-DUCTED RETURN CLOSET INSTALLATION
The air handler can be installed in a closet with a false bottom to form a return air plenum. It may also be installed with a return air plenum under the air handler.
Louvers or return air grilles are field‐supplied. Local codes may limit application of systems without a ducted return to single story buildings.
When a CBX25UH unit is installed in a closet with a louvered return opening, the minimum open area for the louvers will be:
S 320 square inches for -018 and -024 models; S 360 square inches for -030 and -036 models; S 450 square inches for -042 thru -060 models.
If the free area is not known, assume a 25% free area for wood or a 75% free area for metal louvers or grilles. Using the louver dimensions and the 25% or 75% assumption, determine if the open area meets the minimum open area listed above.
Page 3
CBX25UH SERIES
Page 4
If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow for the free flow of return air. When not installed in front of the opening, there must be adequate clearance around the air handler to allow for the free flow of return air.
Installation
Each unit consists of a blower assembly, refrigerant coil, and controls, in an insulated galvanized steel factory finished enclosure. Knockouts are provided for electrical wiring entrance.
For ease in installation, it is best to make any necessary coil configuration changes before setting air handler in place.
REFRIGERANT METERING DEVICE
CB25UH units are equipped with a factory-installed check expansion valve.
UPFLOW APPLICATION
1. The air handler must be supported on the bottom only and set on solid floor or field‐supplied support frame. Securely attach the air handler to the floor or support frame.
2. If installing a unit in an upflow application, remove the horizontal drain pan. IMPORTANT - The horizontal drain pan
is not required in upflow air discharge installations; its removal provides the best efficiency and air flow.
3. Place the unit in the desired location and slope unit as previously mentioned. Connect return and supply air plenums as required using sheet metal screws.
4. Install units that have no return air plenum on a stand that is at least 14” from the floor. This will allow proper air return.
HORIZONTAL DRAIN PAN
IMPORTANT! REMOVE PAN
FOR BEST EFFICIENCY
AND AIR FLOW.
HORIZONTAL DRAIN
UPFLOW
DRAIN PAN
UPFLOW DRAIN CON
NECTIONS (BOTH
SIDES; USE ONE SIDE
OR OTHER)
CONNECTIONS (BOTH SIDES; NOT USED)
HORIZONTAL APPLICATIONS
IMPORTANT
When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right­or left-hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.
ANGLE IRON OR SHEET METAL
MAXIMUM 1/2” LONG SCREW
AIR FLOW
FRONT VIEW END VIEW
Figure 2. Suspending Horizontal Unit
NOTE — When the unit is installed in horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE — This unit may be installed in left-hand or right-hand air discharge horizontal applications. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove service and access panels if installing in the horizontal position.
LEFT-HAND DISCHARGE
1. Determine knockouts required for drain line connections.
2. With access door removed, knock out drain line opening for installing drain lines.
3. Set unit so that it is sloped toward the drain pan end of the unit (see figure 10).
4. The horizontal configuration is shown in figure 3.
AIR FLOW
KNOCKOUT
ELECTRICAL INLET CLEAR
ANCE 4 IN. (102 MM)
Drains
LEFT‐HAND DRAINS
Figure 1. Upflow Configuration
Figure 3. Left‐Hand Discharge Configuration
Page 4
Page 5
5. If the unit is suspended, the entire length of the cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2 inch to avoid damaging the coil or filter. See figure 2. Use sheet metal screws to connect the return and supply air plenums as required.
RIGHT-HAND AIR DISCHARGE
For horizontal right-hand air discharge, the following field modifications are required.
1. Remove and set aside blower and coil access covers.
2. Remove bracket(s) securing pan(s) to unit as illustrated in figures 4 and 5.
3. Remove coil assembly, bottom drain pan and horizontal drain pan as one assembly from the air handler.
4. Move the horizontal drain pan to the opposite side of the coil. Be sure drain holes toward the back of the unit are plugged. Remove the plugs from the front drain pan ports.
5. Re-install modified coil/drain pan assembly in air handler in the same orientation as before (figures 6 and 7).
REMOVE BRACKET
SECURING MAIN
DRAIN PAN TO UNIT.
Figure 4. Remove Main Drain Pan Mounting Bracket
(-018 through -036)
REMOVE BRACKETS
SECURING BOTH
DRAIN PANS TO UNIT.
INSTALL BRACKET SECURING MAIN DRAIN PAN TO UNIT.
Figure 6. Install Main Drain Pan Mounting Bracket
(-018 through -036)
REMOVE BRACKETS SECURING BOTH DRAIN PANS TO UNIT.
Figure 5. Remove Horizontal and Main Drain Pan
Mounting Brackets (-042 through -060)
Figure 7. Install both Horizontal and Main Drain Pan
Brackets (-042 through -060)
6. Remove two screws securing the blow-off prevention bracket. Rotate the brackets 180º and reinstall using the same screws. See figure 8.
Page 5
CBX25UH SERIES
Page 6
HORIZONTAL RIGHT
HORIZONTAL LEFT
(FACTORY DEFAULT)
REMOVE 2 SCREWS SECURING BLOW OFF PREVENTION BRACKET
ROTATE BRACKET TO THIS POSITION AND REINSTALL
Figure 8. Blow-Off Prevention Plate
Condensate Drain
IMPORTANT
On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the con densate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.
ABOVE
FINISHED
SPACE?
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.
LENNOX #
COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
NO
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING
OVERFLOW DRAIN LINE
X3169
CLEAN OUT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
VENT
AIR HANDLER DRAIN PAN
OVERFLOW
DRAIN
YES
NOTE — WHEN A AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:
MAIN
DRAIN
S CONNECTED TO SECONDARY DRAIN PAN
SECONDARY
DRAIN PAN
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES — GENERALLY, TWO INCHES (51MM).
1
LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE
IN HALF AND USE IT TO ROUTE THE MAIN DRAIN.
OR
S CONNECTED TO THE OVERFLOW DRAIN
OUTLET OF THE AIR HANDLER DRAIN PAN.
Figure 9. Typical Main and Overflow Drain
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
LENNOX1 P-TRAP
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4”
TRAP DEPTH
FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL) TRAPS ARE REQUIRED ON ALL DRAIN LINES CONNECTED TO COIL.
2”
(51MM)
DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)
TO APPROVED
DRAIN
Page 6
Page 7
IMPORTANT
A field-fabricated secondary drain pan, with a drain pipe to the outside of the building, is required in all installa tions over a finished living space or in any area that may be damaged by overflow from the main drain pan. In some localities, local codes may require a secondary drain pan for any horizontal installation.
The air handler is provided with ¾” NPT condensate drain connections.
SLOPING THE DRAIN
Make sure the unit is sloped (similar to the slope shown in figure 10) (horizontal or upflow) so that the drain pan will empty completely without water standing in the pan.
THIS CORNER SHOULD BE 5/8” (+/- 1/8”) HIGHER THAN DRAIN CORNER
THIS CORNER SHOULD BE 5/8” (+/- 1/8”) HIGHER THAN DRAIN CORNER
DRAIN CORNER
Figure 10. Sloping the Drain
INSTALL CONDENSATE DRAIN
1. Remove the appropriate drain knockouts. If necessary, remove the indoor coil assembly from the cabinet.
2. Connect primary drain line connection to the primary drain pan connection. The primary drain connection is flush with the bottom of the inside of the pan. Secondary connection is raised above the bottom of the inside of the pan.
NOTE — When making drain fitting connections to the drain pan, hand tighten the fitting and use a thread sealant. Over-tightening the fittings can split connections on the drain pan.
3. If the auxiliary drain line is to be used, remove the plug and route the drain line so that water draining from the outlet will be easily noticed by the homeowner. The auxiliary drain line does not require venting or a trap. Refer to local codes.
4. After removal of drain pan plugs, check the drain port to see if holes have been drilled. If not drilled, use a 19/32” bit to drill out the primary drain hole; use a 3/8” drill bit for the secondary drain hole. Remove all drill shavings.
5. Make sure drain ports and drain pan are free of all debris.
6. Plug and check any unused drain pan openings for tightness. Torque plugs to 30 in. lb. to prevent water leaks or seepage from the drain pan.
7. Install a 2” trap in the primary drain lines as close to the unit as practical (see figure 9). Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.
NOTE — Horizontal runs must have an anti-siphon air vent (standpipe) installed ahead of the horizontal run (See figure 9). An extremely long horizontal run may require an oversized drain line to eliminate air trapping.
NOTE — Do not operate air handler without a drain trap. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will prevent positive drainage without a proper trap.
8. Route the drain line to the outside or to an appropriate drain. Drain lines must be installed so they do not block service access to the front of the air handler. A 24” clearance is required for filter, coil, or blower removal and service access.
NOTE — Check local codes before connecting the drain line to an existing drainage system.
Insulate the drain lines where sweating could cause water damage.
TEST CONDENSATE DRAIN
Test the drain pan and drain line after installation:
1. Pour several quarts of water into drain pan, enough to fill drain trap and line.
2. Check to make sure the drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the end of the primary drain line.
3. Correct any leaks found.
Duct System and Filters
DUCT SYSTEM
The air handler is provided with flanges for the connection of the plenum and ducts. The air handler is equipped with flanges that can form a filter rack for the installation of the air filter, or the filter may be installed as part of the return air duct system.
Supply and return duct system must be adequately sized to meet the system's air requirements and static pressure capabilities. The duct system should be insulated with a minimum of 1” thick insulation with a vapor barrier in conditioned areas or 2” minimum in unconditioned areas.
Table 1. Unit Air Filter Size Chart
Model Filter Size Actual Minimum
Filter Size
-018 12” x 20” x 1 11.50” x 19.50” x .75”
-024 and -030 15” x 20” x 1 14.50” x 19.50” x .75”
-036 18” x 20” x 1 17.50” x 19.50” x .75”
-042, -048 and -060 18” x 24” x 1 17.50” x 23.50” x .75”
Page 7
CBX25UH SERIES
Page 8
IMPORTANT
If a highefficiency filter is being installed as part of this system to ensure better indoor air quality, the filter must be properly sized. Highefficiency filters have a higher static pressure drop than standardefficiency glass/foam filters. If the pressure drop is too great, system capacity and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, result ing in an increase in the number of service calls.
Before using any filter with this system, check the spe cifications provided by the filter manufacturer against the data given in the appropriate Lennox Product Specifica tions bulletin. Additional information is provided in Ser vice and Application Note ACC002 (August 2000).
Supply plenum should be the same size as the flanged opening provided around the blower outlet and should extend at least 3 ft. from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.
INSTALLING DUCT SYSTEM
Connect supply air duct to the flange on top of the air handler. If an isolation connector is used, it must be nonflammable.
A return air duct system is recommended. If the unit is installed in a confined space or closet, a return connection must be run, full size, to a location outside the closet.
Connecting Refrigerant Lines
Refrigerant lines must be connected by a qualified technician in accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dehydrated, refrig erant-grade copper lines. Air handler coils should be installed only with specified line sizes for approved sys tem combinations.
Handle the refrigerant lines gently during the installation process. Sharp bends or possible kinking in the lines will cause a restriction.
Do not remove the caps from the lines or system connec tion points until connections are ready to be completed.
1. Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit. Run the lines in as direct a path as possible avoiding unnecessary turns and bends.
2. Make sure that the suction line is insulated over the entire exposed length and that neither suction nor liquid lines are in direct contact with floors, walls, duct system, floor joists, or other piping.
3. Connect the suction and liquid lines to the evaporator coil.
4. To avoid damaging the rubber grommets in the cabinet while brazing, slide the rubber grommets over the refrigerant lines until they are away from the heat source.
5. Braze using an alloy of silver or copper and phosphorus with a melting point above 1,100°F (593°C).
NOTE — Do not use soft solder.
6. Reinstall the rubber grommets after brazing is finished.
7. Make sure outdoor unit has been put in place according to the Installation Instructions and is connected to the refrigerant lines.
Sealing the Unit
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow-off problems. This is especially important when the unit is installed in an unconditioned area.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
WARNING
There must be an airtight seal between the bottom of the air handler and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide-producing device (i.e., wood fireplace) is installed.
IMPORTANT
When sealing the cabinet, be sure to seal closed any space around the holes where the drain lines exit the cabinet using duct tape and/or Permagum. Warm air must not be allowed to enter through any gaps or holes in the cabinet.
Make sure the liquid line and suction line entry points are sealed with either ARMAFLEX material or with Permagum. Permagum may also be used to seal around the main and auxiliary drains and around open areas of electrical inlets.
Page 8
Page 9
Electrical Connections
WARNING
Electric shock hazard! - Disconnect all power supplies before servicing.
Replace all parts and panels before op erating.
Failure to do so can result in death or elec trical shock.
WARNING
Electric Shock Hazard.
Can cause injury or death.
Foil‐faced insulation has conductive characteristics sim ilar to metal. Be sure there are no electrical connections within a ½” of the insulation. If the foil‐faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g. fuses or circuit breakers), the current can be enough to cause an electric shock hazard that could cause person al injury or death.
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Route the field supply wires to the air handler electrical connection box.
4. Use UL-listed wire nuts to connect the field supply conductors to the unit black and yellow leads, and the ground wire to ground terminal marked GND.
5. Replace the air handler access panel.
CONNECT BLACK AND YELLOW WIRES TO FIELD-PROVIDED CONDUCTORS.
S All field wiring must be done in accordance with
National Electrical Code, applicable requirements of UL and local codes, where applicable.
S Electrical wiring, disconnect means and over-current
protection are to be supplied by the installer. Refer to the air handler rating plate for maximum over-current protection, minimum circuit ampacity, as well as operating voltage.
S The power supply must be sized and protected
according to the specifications supplied on the product.
S This air handler is factory-configured for 240 volt,
single phase, 60 cycles. For 208-volt applications, see “208 Volt Conversion” later in this section.
S For optional field‐installed electric heat applications,
refer to the instructions provided with the accessory for proper installation.
WARNING
USE COPPER CONDUCTORS ONLY
CONNECT GROUND WIRE TO GROUND TERMINAL MARKED “GND”
Figure 11. Making Electrical Connections
208 VOLT CONVERSION
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Using the wiring diagram located on the unit access panel as a reference, move the 2 connected black transformer leads from the 240 volt terminal on the transformer to the 208 volt terminal on the transformer.
WARNING
Electrically ground air handler. Connect ground wire to ground terminal marked “GND”.
Failure to do so can result in death or elec trical shock.
Page 9
CBX25UH SERIES
Page 10
SEE
NOTE
AIR HANDLERTHERMOSTAT
R
G
BU
Y
AIR
CONDITIONER
UNIT
COOLING‐ONLY APPLICATION
NOTE
THERMOSTAT
SEE
AIR HANDLERTHERMOSTAT
R
G
BU
W
HEAT‐ONLY APPLICATION
AIR HANDLER
R
HEAT PUMP
UNIT
AIR HANDLERTHERMOSTAT
G
R
SEE
NOTE
G
W
BK
BU
Y
AIR CONDITIONER
UNIT
COOLING APPLICATION WITH
ELECTRIC HEAT
CONNECT COMMON
WIRE ONLY IF
REQUIRED
(REFER TO THE
APPROPRIATE
THERMOSTAT
INSTALLATION
INSTRUCTIONS)
HEAT PUMP APPLICATION WITH
ELECTRIC HEAT
BU
BK
W
NOTE - Connect common wire only if required (Refer to the appropriate thermostat installation instructions)
Figure 12. Low Voltage Connections (3-Speed PSC Motor) - Field Wiring
Airflow — Cooling Blower Speed
CHANGE BLOWER SPEED
1. Disconnect all power supplies.
The cooling blower speed is factory configured to provide correct airflow for an outdoor unit that matches the cooling capacity rating of the air handler.
If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler, the cooling blower speed may need to be changed. Refer to blower performance chart, table 2 on page 11 .
2. Remove the air handler access panel.
3. Locate pin number 2 on the blower relay. Two black wires are connected to this terminal pin. One connects to pin number 5 on the blower relay, one connects to an in-line splice connecting to a red wire.
4. Remove the wire going to the 4-pin blower motor connector from the splice.
WARNING
Electric shock hazard! - Disconnect all power supplies before servicing.
Replace all parts and panels before op erating.
Failure to do so can result in death or elec trical shock.
5. Connect the blower lead [Red (LO), Black (HI)] onto the splice from the 4-pin blower motor connector.
NOTE — Reuse the factory-installed plastic cap on whichever wire is not used.
6. Replace all panels.
7. Reconnect power.
Page 10
Page 11
BLOWER RELAY
CHANGING BLOWER SPEED
5
BLOWER RELAY HARNESS
BLUE (MED)
PLASTIC CAPS
RED (L0)
2
BLACK (HI)
YELLOW (COM)
4-PIN
BLOWER CONNECTOR
Figure 13. Changing Blower Speed
NOTE — Refer to wiring diagram located on the unit access panel (or figure 13 above) and blower performance (table 2).
S All air data measured external to unit with 1 inch non-pleated air filter in place. S All factory settings are medium speed except the -48 which is set to low speed from the factory. S All data given while air handler is operating with a dry DX coil.
Table 2. CBX25UH Blower Performance (3-Speed PSC) - 240V (CFM @ ESP. - in. W. C.)
Air Handler
Model
18
24
30
36
42
48
60
Blower Speed .10” WC .20” WC .30” WC .40” WC .50” WC
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
510 670 905
630 885
1130
900 1075 1240
1160 1500 1660
1325 1490 1820
1775 1995 2070
1675 1965 2140
495 650 865
625 875
1100
865 1060 1210
1140 1445 1575
1315 1465 1770
1710 1895 1970
1630 1925 2085
475 630 820
615 850
1070
830 1030 1170
1115 1385 1495
1300 1440 1690
1645 1800 1850
1580 1875 2000
420 595 770
610 820
1010
780 985
1135
1085 1300 1405
1275 1395 1600
1565 1685 1719
1520 1800 1895
325 505 705
580 780 950
740 940
1085
990 1200 1390
1225 1315 1500
1470 1560 1595
1450 1695 1795
S Blower Performance (CFM vs. ESP inches H2O) S Cooling speeds should not be reduced below factory setting. S Units with electric heat approved at 0.5” maximum and medium blower speed minimum.
Page 11
CBX25UH SERIES
Page 12
Check-out Procedures
NOTE - Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging instructions.
PRE‐START‐UP CHECKS
S Is the air handler properly and securely installed? S If horizontally configured, is the unit sloped up to 5/8
inch toward drain lines?
S Will the unit be accessible for servicing? S Has an auxiliary pan been provided under the unit with
separate drain for units installed above a finished ceiling or in any installation where condensate overflow could cause damage?
S Have ALL unused drain pan ports been properly
plugged?
S Has the condensate line been properly sized, run,
trapped, pitched, and tested?
S Is the duct system correctly sized, run, sealed, and
insulated?
S Have all cabinet openings and wiring been sealed? S Is the indoor coil factory‐installed TXV properly sized
for the outdoor unit being used?
S Have all unused parts and packaging been disposed
of?
S Is the filter clean, in place, and of adequate size? S Is the wiring neat, correct, and in accordance with the
wiring diagram?
S Is the unit properly grounded and protected (fused)? S Is the thermostat correctly wired and in a good
location?
S Are all access panels in place and secure?
CHECK BLOWER OPERATION
S Set thermostat to FAN ON. S The indoor blower should come on.
CHECK COOLING OPERATION
S Set thermostat to force a call for cooling
(approximately 5ºF lower than the indoor ambient temperature).
S The outdoor and indoor units should come on
immediately.
S Check the airflow from a register to confirm that the
system is moving cooled air.
S Set the thermostat 5ºF higher than the indoor
temperature. The indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.
CHECK ELECTRIC HEATER (IF USED)
S Set thermostat to call for auxiliary heat (approximately
5°F above ambient temperature). The indoor blower and auxiliary heat should come on together. Allow a minimum of 3 minutes for all sequencers to cycle on.
S Set the thermostat so that it does not call for heat.
Allow up to 5 minutes for all sequencers to cycle off.
Operation
TIME DELAY RELAY
Blower time delay operation:
1. When cooling demand is initiated, there is a 1 second motor-on delay.
2. After the motor-on delay expires, motor ramps up to 100% and runs at 100% until cooling demand is satisfied.
3. Once demand is met, motor runs at 100% for 45 seconds.
4. Motor ramps down to stop.
34
100%
2
1
1
SECOND
DELAY
COOLING (COOLING ONLY OR HEAT PUMP)
When the thermostat calls for cooling, 24 volts is put on the blower time-delay relay coil and then the indoor blower relay energizes. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
On heat pumps, circuit R and O energizes the reversing valve, switching the valve to the cooling position. (The reversing valve remains energized as long as the thermostat selector switch is in the COOL position.)
At the completion of the cooling demand the indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.
HEATING (ELECTRIC HEAT ONLY)
When the thermostat calls for heat, the circuit between R and W is completed, and the heat sequencer is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat sequencer can be connected with the first sequencer to W on the thermostat subbase, or they may also be connected to a second stage on the subbase.
HEATING (HEAT PUMP)
When the thermostat calls for heating, 24 volts is put on the blower time-delay relay coil. Then normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
If the room temperature should continue to fall, the circuit between R and W1 is completed by the second‐stage heat room thermostat. Circuit R-W1 energizes a heat sequencer. The completed circuit will energize supplemental electric heat (if applicable). Units with a
CFM
COOLING
DEMAND
Figure 14. Blower Time Delay
100%
CFM
45
SECS
OFF
Page 12
Page 13
second heat sequencer can be connected with the first sequencer to W1 on the thermostat. They may also be connected to a second heating stage W2 on the thermostat subbase.
EMERGENCY HEAT (HEATING HEAT PUMP)
If the selector switch on the thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat (if applicable). A jumper should be placed between W2 and E on the thermostat subbase so that the electric heat control will transfer to the first‐stage heat on the thermostat. This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position.
Maintenance
Matt‐ or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet. The temperature/humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and subsequently, component failure.
REPAIRING DAMAGED INSULATION
Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair.
IMPORTANT
Do not operate system without a filter. A filter is required to protect the coil, blower, and internal parts from exces sive dirt and dust. The filter is placed in the return duct by the installer.
S Inspect air filters at least once a month and replace or
clean as required. Dirty filters are the most common cause of inadequate heating or cooling performance.
S Replace disposable filters. Cleanable filters can be
cleaned by soaking in mild detergent and rinsing with cold water.
S Install new/clean filters with the arrows on the side
pointing in the direction of airflow. Do not replace a cleanable (high velocity) filter with a disposable (low velocity) filter unless return air system is properly sized for it.
S If water should start coming from the secondary drain
line, a problem exists which should be investigated and corrected. Contact a qualified service technician.
Cabinet Insulation
IMPORTANT
If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil‐faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape.
GLUE -make sure there is full coverage of glue on the metal or insulation so there are no areas where air pockets may form which can lead to sweating.
1. CUT INSULATION IN X PATTERN
2. APPLY GLUE
3. PRESS GLUED TABS AGAINST CABINET
Figure 15. Repairing Insulation
Page 13
CBX25UH SERIES
Page 14
Installing Contractor’s Name_______________________ Installing Contractor’s Phone_______________________ Job Address____________________________________
8
1
Temperature
Duct
System
5
Duct Static
Installing Date_______________________________ Air Handler Model #___________________________
Thermostat
SUPPLY
AIR
9
Disconnect
Switch
2
Line Voltage
3
Integrated Control
Blower Motor Amps
6
Electric Heat Amps
7
RETURN
AIR
DUCT SYSTEM
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLTAGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
4
DRAIN LINE
Leak Free
Filter
TOTAL EXTERNAL STATIC (dry coil)
5
Supply External Static ______ ______
Return External Static ______ ______
Total External Static = ______ ______
6
ELECTRIC HEAT AMPS____________
7
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
TEMPERATURE DROP (Cooling Mode)
8
Return Duct Temperature ___________
Supply Duct Temperature − ___________
8
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature __________
9
THERMOSTAT
Adjusted and Programmed
Operation Explained to Owner
4
Drain Line
dry coil wet coil
Temperature Drop = ___________
Temperature Rise = __________
Explained Operation of System to Homeowner
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Figure 16. Start-Up and Performance Checklist (Upflow Configuration)
Page 14
Page 15
Installing Contractor’s Name_______________________ Installing Contractor’s Phone_______________________ Job Address____________________________________
Thermostat
9
1
Duct System
2
Integrated
Control
Filter
Installing Date_______________________________ Air Handler Model #___________________________
Disconnect
Switch
Line Voltage
3
1
Duct System
RETURN
AIR
4
Drain Line
DUCT SYSTEM
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLTAGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
4
DRAIN LINE
Leak Free
5
Duct Static
8
Temperature
SUPPLY
AIR
Electric Heat Amps
6
Blower motor Amps
7
TOTAL EXTERNAL STATIC (dry coil)
5
dry coil wet coil
Supply External Static ______ ______
Return External Static ______ ______
Total External Static = ______ ______
6
ELECTRIC HEAT AMPS____________
7
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
TEMPERATURE DROP (Cooling Mode)
8
Return Duct Temperature ___________
Supply Duct Temperature − ___________
Temperature Drop = ___________
8
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature __________
Temperature Rise = __________
9
THERMOSTAT
Adjusted and Programmed
Operation Explained to Owner
Explained Operation of System to Homeowner
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Figure 17. Start-Up and Performance Checklist (Horizontal Configuration)
Page 15
CBX25UH SERIES
Page 16
Loading...