Lennox CBWMV User Manual

INSTALLATION
E2006 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
CAUTION
Unit is designed to be used with non−potable boiler systems only.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Introduction
The multi−positional Dave Lennox Signaturet Collection CBWMV air handler/hot water coil unit is designed to be used with non-potable boiler systems for warm air heating. A variety of Lennox air conditioning systems may be ap­plied to the CBWMV unit for optional cooling.
INSTRUCTIONS
CBWMV Series Units
AIR HANDLERS
505,047M 09/06 Supersedes 02/06
Table of Contents
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
CBWMV Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . .
General 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CBWMV Unit Parts Arrangement 3. . . . . . . . . . . . . . . .
CBWMV Unit Parts Description 3. . . . . . . . . . . . . . . . . .
CBWMV Unit Optional Accessories 3. . . . . . . . . . . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation − Setting Equipment 4. . . . . . . . . . . . . . . . . .
Duct System 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Return Air Opening Guidelines 6. . . . . . . . . . . . . . . . . .
Filter Assembly & Filters 8. . . . . . . . . . . . . . . . . . . . . . .
Plumbing 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Freezestat Operation 12. . . . . . . . . . . . . . . . . . . . . . . . . .
BDC3 Variable Blower Control Board 12. . . . . . . . . . . . .
Blower Speed Adjustments 12. . . . . . . . . . . . . . . . . . . . .
Initial Air System Purging 16. . . . . . . . . . . . . . . . . . . . . . .
System Adjustments 17. . . . . . . . . . . . . . . . . . . . . . . . . . .
Annual Service 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Filters 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Winterizing the CBWMV Unit 17. . . . . . . . . . . . . . . . . . . .
Repair Parts List 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting:
Continuous Fan Sequence of Operation 18. . . . . . . . . .
Cooling Sequence of Operation 19. . . . . . . . . . . . . . . . .
Heating Sequence of Operation 20. . . . . . . . . . . . . . . . .
Shipping & Packing List
1 − CBWMV Air Handler [NOTE − Includes freezestat mounted to the manifold.]
1 − Bag assembly containing:
1 − Electrical make−up box 1 − Copper fitting 1 − Snap bushing 2 − Water line grommets 3 − Wire nuts 2−7/8" cabinet plugs
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Litho U.S.A.
09/06 505,047M
Page 1
*2P0906* *P505047M*
CBWMV Unit Dimensions − inches (mm)
*NOTE − Single side inlet applications result in approximately 4 percent reduction of CFM on B−size units and approximately 5 percent reduction of CFM on C−size units.
OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT (Either Side) − Not for use with optional Return Air Base.
WATER INLET
G
SUPPLY AIR OPENING
F
D
E
WATER OUTLET
23-3/4 (603)
25 (635)
TOP VIEW
3/4 (19)
A
B
AIR FLOW
C
*Bottom Return
Air Opening
FRONT VIEW SIDE VIEW
3/4 (19)
9/16
(14)
OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT (Either Side)
14−3/4
(375)
16
(406)
5/8
(16)
40
(1016)
ALTERNATE WATER INLET (far side)
1−1/4" (32)
1−3/4" (44)
ALTERNATE WATER OUTLET
2"
(51)
4
(102)
RETURN CUTOUT
4−1/4
*Bottom Return Air Opening
(108)
28−1/2
(724)
19−7/16
(494)
10−1/2"
(267)
ELECTRICAL INLET (Either Side)
23
(584)
*OPTIONAL
(Either Side)
23−1/2
(597)
9/16
(14)
14
(356)
1−15/16 (49)
CBWMV Model No. A B C D E F G
−24B−040
−36B−070
17−1/2 (445) 16−3/8 (416) 16 (406) 1−1/2 (38) 1−3/4 (44) 8 (203) 2 (51)
−36C−090
−60C−100
21 (533) 19−7/8 (454) 19−1/2 (495) 2 (51) 2−1/2 (64) 9−1/2 (241) 1−1/2 (38)
−60C−120
Page 2
505047 09/06
General
CBWMV Unit Parts Description
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. Only qualified ser­vice technicians or installers may install and service this unit.
CBWMV Unit Parts Arrangement
CBWMV Unit
HOT WATER
COPPER
TUBE COIL
INSULATED STEEL CABINET
Blower
The CBWMV is equipped with a variable speed motor that provides separate cooling and heating CFM selections and low continuous fan speeds.
Hot Water Coil
The copper tube coil is equipped with aluminum fins which provide excellent heat transfer. Manual air bleed ports are located in the copper tubing to release trapped air in the water circuit in all unit configurations.
Blower Control
The control provides a fixed blower delay of 45 seconds ON / 30 seconds OFF on a W call.
Thermostat and accessory connections are made to the terminal strips in the control box.
CBWMV Unit Optional Accessories
Accessory Circulators (53J76, 99K69)
An accessory circulator should be used in long line ap­plications. Two circulators are available with either 9 gal­lons per minute (99K69) or 14 gpm (53J76) flow rate. Both units have 7/8" soldering joints (inlet and outlet) . See pip­ing section for more information.
CBWMV
CONTROL BOX
Figure 1
SUPPLY AIR BLOWER
Downflow Base (68M03)
A downflow base kit is available for downflow applications without add−on cooling coils. The base provides clearance for routing the CBWMV unit’s inlet and outlet water lines.
NOTE − Downflow applications with an add−on cooling coil require field−fabricated transitions to provide adequate clearance for servicing/removing the cooling coil without cutting the water lines.
Page 3
CBWMV SERIES
Requirements
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a qualified installer or service agency.
Installation of Lennox CBWMV unit must conform with lo­cal building codes. Refer to the electrical section (Page 8) for US and Canadian electrical regulations.
When paired with a water heating device, refer to local building codes for special considerations. Refer to water heating device for agency and service clearances. Clear­ances to combustibles for the CBWMV unit only is zero inches on all sides. Table 1 lists recommended service clearances.
Table 1
CBWMV Unit Service Clearances
Clearances Location Inches (mm)
Recommended Service Access
NOTE − Service access clearance must be maintained.
Accessibility and service clearances must take prece­dence over fire protection clearances.
For installation in a residential garage, unit must be lo­cated or protected to avoid physical damage by vehicles.
The CBWMV unit must be installed so that its electrical components are protected from water.
When the CBWMV unit is used with an air conditioner, the air handler shall be installed on the upstream side of the cooling evaporator coil to avoid freeze−up of water system and condensation. With a parallel flow arrangement, a damper (or other means to control the flow of air) must ad­equately prevent chilled air from entering the air handler. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
NOTE − CBWMV series units must not be used in or for the following applications:
S construction heater − during any phase of construction S unit heater S mobile home heater S potable water applications
Front Access Panel
30 (762)
Application
The CBWMV unit is designed for use in non−potable water boiler systems. The water heating device must be ade­quate to provide enough heat according to the Engineering Handbook specifications. The water heating device must provide a minimum of 6 gallons/minute for small units (CBWMV−040, −070) and 9 gallons/minute for large units (CBWMV−090, −100, −120).
Installation − Setting Equipment
WARNING
This product contains fiberglass wool.
Disturbing the insulation during installation, main­tenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
The boiler installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest revision of the National Fuel Gas Code, ANSI Z223. (Available from the American Gas Association, 8501 E. Pleasant Valley Road, Cleveland, OH 44134). Reference should also be made to local gas utility regulations and other codes in effect in the same area in which the installation is to be made. When installed in Canada: The latest revision of the CAN1/CSA−B149.1 and/or B149.2 Installation Codes for Gas-Burning Equip­ment and/or local codes.
Determine the CBWMV unit installation location and posi­tion units so that door panels are accessible. Keep in mind routing of the water and plumbing lines and electrical con­nections.
The CBWMV unit is multi−positional. No adjustment is nec­essary to apply unit for upflow or horizontal discharge. A downflow base is available and provides clearance for routing the inlet/outlet water lines when the CBWMV unit is applied without an add−on cooling coil. Downflow applica-
505047 09/06
Page 4
tions with add−on cooling coils require field−fabricated tran­sitions that provide at least 6 inches of clearance for the CBWMV unit’s inlet/outlet water lines. See figure 2 for ex­amples.
CBWMV Multi−Positional Unit
AIR
FLOW
RIGHT HAND DISCHARGE*
AIR
FLOW
AIR
FLOW
UPFLOW
DOWNFLOW BASE
AIR
FLOW
Either suspend the unit from the roof rafters or floor joists or mount on a platform. The CBWMV unit must be level and well supported.
NOTE − 1/2 hp and 1 hp blower motors are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic wash­er (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be re-
moved before the air handler is placed into operation.
After the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Duct System
Use industry-approved standards (such as those pub­lished by Air Conditioning Contractors of America or Amer­ican Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
LEFT HAND DISCHARGE*
DOWNFLOW
* CBWMV units must not be installed horizontally on the front or back of the unit.
Figure 2
Units may be horizontally installed in either attic or crawl space.
CAUTION
CBWMV series units are shipped with an antifreeze thermostat to prevent the water coil from freezing. The freezestat is installed at the factory but must be field wired (see figures 12 and 13). Do not bypass this feature when you install or run the unit.
CAUTION
Use a drain pan for installations over finished living areas.
NOTE − Do not operate the air handler with an external static pressure that exceeds 0.8 inches w.c. Higher exter­nal static pressures may cause erratic operation.
Return Air Plenum
IMPORTANT
Return air must not be drawn from a room where any fossil fuel appliance (ie., a water heater) is installed.
When return air is drawn from a room, a negative pres­sure is created in the room. If a fossil fuel appliance is op­erating in a room with negative pressure, the flue prod­ucts can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in in­complete combustion and the formation of carbon mon­oxide gas. This toxic gas might then be distributed throughout the house by the air handler duct system.
Page 5
CBWMV SERIES
Return Air Opening Guidelines
Side Return Air With Transition And Filter
NOTE − Do not bring in air from the back of the unit. Return air can be brought in from the sides or bottom only.
Bottom Return
If the air handler is installed on a platform with bottom re­turn, make an airtight seal between the bottom of the air handler and the platform to ensure that the air handler op­erates properly and safely. Use aluminum tape or mastic between the plenum and the air handler cabinet to ensure a tight seal. The air handler is equipped with a removable bottom panel to facilitate installation.
Side Return
For side return air applications, cut the air handler cabinet at the maximum return air dimensions shown on page 2. See figure 3 for a typical side inlet arrangement with a tran­sition and filter.
NOTE − Single side inlet applications result in approxi­mately a 4 percent reduction of CFM on B−size units and approximately a 5 percent reduction of CFM on C−size units:
Optional Return Air Base and Unit Dimensions − Inches (mm)
20" X 25" X 1" (508MM X 635MM X 25MM) CLEANABLE FILTER
RETURN AIR PLENUM
TRANSITION
Figure 3
Return Air Base
For return air with the optional return air base (RAB), see figure 4 (and refer to installation instructions provided with Return Air Base kit).
*NOTE − Both unit and return air base openings must be connected to and entirely covered by a single plenum or IAQ accessory opening. Optional side return air filter kits cannot be used with RAB Return Air Base.
4
(102)
*23 (584) Overall (Max.)
AIR FLOW
RETURN AIR BASE
17 (432) RAB−B (98M60) 21 (533) RAB−C (98M58)
FRONT VIEW
NOTE − IN SIDE RETURN APPLICATIONS, THE RAB IS REQUIRED FOR 100% CFM CAPACITY.
Side Return
Air Openings
(Either Side)
7−1/4 (184)
7/8 (22)
Figure 4
*Unit
Opening
*Base
Opening
27−5/8 (702)
SIDE VIEW
23 (584)
*Minimum
11 (279)
*Maximum
14 (356)
5−5/8 (143)
*Height varies with plenum or IAQ accessory height.
3/4 (19)
505047 09/06
Page 6
Removing the Bottom Panel (bottom return or return air base configurations)Remove the two screws that
secure the bottom cap to the air handler. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See fig­ure 5.
Removing the Bottom Panel
BOTTOM CAP
SCREW
BOTTOM PANEL
through the bottom panel and the bottom flange of the cabinet.
2. Install one bolt and two nuts into each hole. Screw the first nut onto a bolt and then insert the bolt into a hole. A flat washer may be added between the nut and the bottom of the unit.
3. Screw another nut onto the bolt on the inside of the air handler base. A flat washer may be added between the nut and the bottom of the unit.
4. Adjust the outside nut to the appropriate height and tighten the inside nut to secure the arrangement.
Horizontal Applications
The CBWMV air handler can be installed in horizontal ap­plications. Refer to Engineering Handbook for additional in­formation. Allow for clearances to combustible materials as indicated on the unit nameplate.
This air handler may be installed in either an attic or a crawlspace. Either suspend the air handler from roof raf­ters or floor joists, as shown in figure 7. The unit must be supported at both ends and beneath the blower deck to prevent sagging.
Figure 5
Leveling an Upflow UnitWhen the side return air inlets
are used in an upflow application, it may be necessary to install leveling bolts on the bottom of the air handler. Use field−supplied corrosion−resistant 5/16 inch machine bolts (4) and nuts (8). See figure 6.
NOTE − Maximum leveling bolt length is 1−1/2 inches.
Leveling Bolt Installation
AIR HANDLER FRONT
3/8 (10)
1−3/4 (44)
LEVELING BOLT
LOCATIONS
3/8 (10)
3/8 (10)
AIR
HANDLER
BOTTOM
1−3/4 (44)
1−3/4 (44)
inches (mm)
1−3/4 (44)
LEVELING BOLT
LOCATIONS
3/8 (10)
Figure 6
1. Lay the air handler on its back and drill a 5/16 inch di­ameter hole in each corner of the air handler’s bottom. See figure 6 for the correct location of the holes. Drill
Unit Suspended in Attic or Crawlspace
1/4 IN. RODS
DRAIN
ALLOW SUFFICIENT CLEARANCE BETWEEN ROD AND UNIT TO REMOVE ACCESS PANEL.
ANGLE IRON
U−CHANNELS
PAN
Figure 7
NOTE − Heavy−gauge, perforated sheet metal straps (plumbers’ straps) may be used to suspend the unit from roof rafters or ceiling joists. When suspending the unit in this manner, support must be provided for both the ends and the middle of the air handler to prevent sagging. Straps must not interfere with plenum or water piping. Securing screws should be 1/2 inch from the top edge and 1−1/2 inch from the side edge in all cases. Cooling coils and supply
and return air plenums must be supported separately.
NOTE − When the air handler is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the optional evaporator coil to drain.
Horizontal and Downflow Applications
Return air can be brought in through the end of an air han­dler installed in the horizontal or downflow application. The air handler is equipped with a removable bottom panel to facilitate installation (see figure 5).
Page 7
CBWMV SERIES
Filter Assembly & Filters
Air Handler
This unit is not equipped with a filter or rack. A field−pro­vided high−velocity filter is required for the unit to operate properly. Table 2 lists recommended filter sizes. A filter must be in place any time the unit is operating.
Table 2
Recommended Filter Sizes
Air Handler
Cabinet Size
17−1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Plumbing
Pipe and Fitting Specifications
Refer to local building and plumbing codes for approved copper pipe and fittings.
Plumbing Procedures
Refer to the installation instructions of the water heating device to be used with the CBWMV unit. Follow the recom­mendations outlined in that instruction as well as govern­ing plumbing codes and practices.
Plumbing Checklist
S Flush water lines between the CBWMV unit and the
water heating device before start−up. Normal flushing procedures should be used to rid the system of con­taminants and foreign debris.
S CBWMV units are installed in non-potable systems.
Refer to figure 12 for schematic wiring diagram and trouble­shooting.
Line Voltage (120V)
Line voltage field supply conductors are terminated at the CBWMV unit. The unit is shipped with the line voltage con­nections secured to the lower left coil manifold for left side make−up box installations. For right side make−up box installations, remove the wire tie that holds the line voltage connections and pull excess wires into blower deck/control box area as shown in figure 8.
Install make−up box (provided for line voltage wiring in the unit’s bag assembly) as shown in figure 9.
Make−up Box Wiring
WIRES SHOWN AS SHIPPED, ROUTED FOR LEFT SIDE MAKE−UP BOX INSTALLATION
FOR RIGHT SIDE MAKE−UP BOX INSTALLATION 
REMOVE WIRE TIE,
PULL EXCESS WIRE INTO BLOWER DECK / CONTROL BOX AREA.
Electrical
Wiring and grounding must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to following wiring diagrams. See unit name­plate for minimum circuit ampacity and maximum overcur­rent protection size.
Select the proper supply circuit conductors in accor­dance with tables 310−16 and 310−17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.
CAUTION
USE COPPER CONDUCTORS ONLY.
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Figure 8
Interior Make−Up Box Installation
MAKE−UP
BOX
LEFT SIDE
Figure 9
MAKE−UP
BOX
RIGHT SIDE
505047 09/06
Page 8
Electrostatic Discharge (ESD) - Precautions And Procedures
National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box.
CAUTION
Electrostatic discharge can affect electronic com­ponents. Take precautions during air handler instal­lation and service to protect the air handler’s elec­tronic controls. Precautions will help to avoid con­trol exposure to electrostatic discharge by putting the air handler, the control and the technician at the same electrostatic potential. Neu tralize electrostatic charge by touching hand and all tools on an un­painted unit surface, such as the blower deck, be­fore performing any service procedure.
5. Install the room thermostat according to the instruc­tions provided with the thermostat. See table 3 for field wiring connections in varying applications. If the air handler is being matched with a heat pump, refer to the FuelMaster21® installation instruction.
Removeable Jumpers
Removeable Jumper DS to Y1The factory−installed
wire jumper that connects terminals DS and Y1 on the TB1 terminal strip in the control box must be removed when the air handler is installed in a system supporting dehumidifi­cation using a SignatureStatt thermostat (e.g., Humidi-
Refer to table 3 for field wiring.
1. Refer to the CBWMV unit’s nameplate for minimum circuit ampacity and maximum overcurrent protection size.
2. Install a separate disconnect switch (protected by ei­ther fuse or circuit breaker) near the air handler so that power can be turned off for servicing.
3. Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wir­ing diagrams shown in table 3. Use 18−gauge wire or larger that is suitable for Class II rating for thermostat connections.
4. Electrically ground the unit according to local codes or, in the absence of local codes, according to the current
trol® Enhanced Dehumidification Accessory or Harmony zone controls).
Removeable Jumper R to OThe factory−installed wire jumper that connects TB7 (24V) terminal R to TB1 termi­nal O must be removed when the air handler is installed in applications which include a heat pump unit and the Fuel­Master21® control board. If the jumper is left intact, termi­nal O will remain energized, eliminating the heat mode in the heat pump.
Removeable Jumper Y1 to Y2The factory−installed wire jumper that connects Y1 and Y2 on the TB1 terminal strip must be removed if two−stage cooling is used. If the jumper is not removed the outdoor unit will only operate in second−stage cooling.
Table 3
Field Wiring Application Jumper Settings (See figure 12)
Thermostat (Application) TB1 Y1 to Y2 TB1 DS to Y1 TB1 R to O Wiring Connections
1 Heat / 1 Cool with SignatureStatt Thermostat [Single-Stage Heat Pump]
Yes No
(Remove)
No
(Remove)
SignatureStatt CBWMV
TERMINALS
t
OUTDOOR
UNIT
2 Heat / 2 Cool with SignatureStatt Thermostat
(Remove) [Two-Stage Heat Pump (Refer to FM21 Instructions)]
O" terminal used only with heat pumps.
No
No
(Remove)
Page 9
No
(Remove)
SignatureStatt
CBWMV
TERMINALS
JUMPERS REMOVED
OUTDOOR
UNIT
ALL JUMPERS REMOVED
CBWMV SERIES
Indoor Blower Speeds
1. When the thermostat is set to FAN ON," the indoor blower will run continuously at approximately 38% of the second−stage cooling speed when there is no cool­ing or heating demand.
2. When the CBWMV is in the heating mode, the indoor blower will run on the heating speed designated by the position of the HEAT pin.
3. When there is a cooling demand, the indoor blower will run on the cooling speed designated by the position of the COOL pin.
Accessory Field Wiring (K212)
Accessory Field Wiring (TB66 & TB67)
Connect wires from accessories (e.g. powered air clean­ers, humidifiers) to terminal blocks TB66 and TB67 (see detail in figure 11).
CBWMV Control Box
TERMINAL BLOCKS
TB2 TB13
(HOT) (NEUTRAL)
TRANSFORMER T1
Connect field wiring to 3PDT relay K212 (Lennox part 67K66) as shown in figure 10.
Accessory Relay Field Wiring (K212)
1
2
3
4
5
6
7
8
9
AB
24V 125MA 1/4" QUICK CONNECT TERMINALS
RELAY CONTACTS RATING 8 AMPS @ 120V MAX. 24V COIL
ACCESSORY RELAY
Figure 10
DOOR INTERLOCK SWITCH
BDC3 VARIABLE SPEED CONTROL
ACCESSORY FIELD WIRING TERMINAL BLOCKS
TERMINAL BLOCK TB1
TB66
TB67
Figure 11
CB8 CIRCUIT BREAKER
WIRING STRAIN RELIEF BUSHING
TERMINAL BLOCK 24V
K212 RELAY
505047 09/06
Page 10
Typical CBWMV Wiring Diagram
Figure 12
Page 11
CBWMV SERIES
Freezestat Operation
IMPORTANT
Use of the freezestat feature is required in all instal­lations using CBWMV units.
The CBWMV unit is equipped with a field-wired freezestat. The freezestat protects the CBWMV system from freezing temperatures when the unit is installed in unconditioned areas.
The factory-provided freezestat must energize the circula­tor when water temperatures fall below 45ºF. Freezestat wiring is shown in figure 13.
Freezestat Field Wiring
Figure 13
BDC3 Variable Blower Control Board
CBWMV units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. A particular CFM can be obtained by positioning jumpers (COOL, HEAT, and ADJUST) on the BDC3 control board. The COOL and HEAT jumpers are labeled 1, 2, 3, and 4. Each of the numbers corre­sponds with an air volume (CFM) setting. The ADJUST jumper is labeled TEST, −, +, and NORM. The + and − pin settings are used to add or subtract a percentage of the CFM selected. The TEST jumper is used to operate the motor in the test mode. The DELAY jumper controls ramp- ing profiles.
Figure 14 shows the BDC3 control board. Use tables 5 through 9 to determine the correct air volume for heat and cool speed taps.
Diagnostic LEDs located on the BDC3 control board are provided to aid in identifying the unit’s mode of operation. Certain scenarios will arise depending on the jumper posi­tions. Read through the jumper settings sections before adjusting blower speed. Refer to figure 14 for identification.
Continuous Low Blower Option
Refer to the blower speed chart located on the CBWMV unit wiring diagram for factory set cooling, heating and low (continuous) blower speeds. Systems using a cooling ther­mostat subbase may operate continuous blower (factory­set to operate at 38% of second-stage cooling speed) through the FAN−ON switch of the thermostat. For continu­ous low blower with a system without a cooling subbase, a fan switching subbase may be used.
Heating or cooling demand will cause blower to go to heat or cool speed.
Blower Speed Adjustments
Diagnostic LEDs
RUN LED  Indicates a demand for blower operation in
either the heating mode or continuous fan−only mode. RUN LED will not illuminate during a cooling demand.
CFM LED  Indicates the CFM at which the unit is operat­ing. The light flashes once for approximately every 100 CFM. For example, if the unit is operating at 1000 CFM, CFM LED will flash 10 times. If the CFM is 1150, CFM LED will flash 11 full times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes place when the control is communicating with the motor between cycles. This is normal operation.
The appropriate speed according to application and CFM need is selected by moving jumper pins.
BDC3 Variable Speed Control Board
JP1
15 PIN PLUG
(BOARD TO
MOTOR)
ACCESSORY
RELAY CON-
TACTS
(DRIVES OP-
TIONAL
ACCESSORY
RELAY)
OPERATIONAL
SELECTOR
PINS
(AFFECTS
BOTH
HEATING AND
COOLING
MODES)
HEATING SPEED SELECTOR PINS
COOLING SPEED
SELECTOR PINS
Figure 14
FAN DELAY
SELECTOR PINS
DIAGNOSTIC
LEDS
505047 09/06
Page 12
Bl
Jumper Settings
IMPORTANT
Before changing jumper setting, make sure the mo­tor has completely stopped. Any jumper setting change will not take place while the motor is run­ning.
Table 4 shows the factory blower speed tap settings for CBWMV series units. These settings are for nominal ton­nage match−ups with the CBWMV. When matched with other sizes, it is recommended that the CFM be adjusted approximately to 400 CFM per ton.
Table 4
Factory Blower Speed Tap Settings
CBWMV
ower
Coil
−24B−040 1 2 NORM 4
−36B−070 3 4 NORM 4
−36C−090 3 4 NORM 4
−60C−100 4 4 NORM 4
−60C−120 4 4 NORM 4
Cool Pin Heat Pin Adjust Delay
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and conditions associated with each one. Refer to figure
14.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in tables 5 through 9. From the tables, determine which row of CFM volumes most closely matches the desired CFM. Once a specific row has been chosen (+, NORMAL, or −), CFM volumes from other rows cannot be used. Below are descriptions of the jumper selections.
ADJUST Pins  The ADJUST pins allow the motor to run
at normal speed, approximately 10% higher, or approxi­mately 10% lower than normal speed. Tables 5 through 9 gives three rows (+, NORMAL, and −) with their respective CFM volumes. Notice that the normal adjustment setting for heat speed position #3 is 1070 CFM. The + adjustment setting for that position is 1180 CFM and for the − adjust­ment setting is 940 CFM. After the adjustment setting has been determined, chose the remainder speed jumper set­tings from those offered in the table in that row.
The TEST pin is available to bypass the BDC3 control and run the motor at approximately 70% to test that the motor is operational. This is beneficial primarily in troubleshooting. G must be energized for motor to run.
COOL Pins  The COOL jumper is used to determine the
CFM during either 1) cooling or 2) heat pump operation without a W1 call for electric heat. These jumper selections are activated for cooling when Y1 and/or Y2 and DS termi­nals in the CBWMV unit are energized and for heating when Y1 and/or Y2 is energized.
Speed Tap Selection
Page 13
For applications with the Harmony
®
Zoning System, the blower CFM volume is determined by the Harmony control center. The minimum blower speed is predetermined at 400 CFM for −CBWMV−24B−040 and 36B−070 series units and 600 CFM for CBWMV−36C−090, 60C−100, and 60C−120 series units. This speed is not adjustable.
With the thermostat set for Continuous Fan" and without a call for heating or cooling, the CBWMV will provide 38% of the COOL CFM selected.
HEAT Pins 
The HEAT jumper is used to determine
CFM heating. These jumper selections are activated only when W1 is energized. (There is a fixed 45 seconds ON and 30 seconds OFF delay on a W call.)
DELAY Pins  The DELAY jumper is used to set the spe-
cific motor fan operation during cooling mode. Depending on the application, one of four options may be chosen by moving the jumper to the appropriate set of pins.
#1 Pins Jumpered 
A Motor runs at 100% until demand is satisfied.
A B
OFFOFF
B Once demand is met, motor ramps down to stop.
#2 Pins Jumpered 
A Motor runs at 100% until demand is satisfied.
A
OFF
B
C
OFF
B Once demand is met, motor runs at 100% for 45
seconds. Then,
C ramps down to stop.
NOTE − Blower OFF DELAY also applies during heat pump operation
#3 Pins Jumpered 
A Motor runs at 82% for approximately 7−1/2 min-
utes. If demand has not been satisfied after 7−1/2 minutes,
B motor runs at 100% until demand is satisfied.
AB C
OFFOFF
C Once demand is met, motor ramps down to stop.
#4 Pins Jumpered 
A Motor runs at 50% for 30 seconds. B Motor then runs at 82% for approximately 7−1/2
minutes. If demand has not been satisfied after 7−1/2 minutes.
C Motor runs at 100% until demand is satisfied. D Once demand is met, motor runs at 50% for 30
seconds. Then,
B
A
C D
E
OFFOFF
E ramps down to stop.
CBWMV SERIES
Table 5
J
Setting
Setting
ADJUST
p
J
Setting
ADJUST
p
CBWMV−24B−040 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 2, Cooling Speed − 1, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 4%.
ADJUST"
umper
+ 610 290 770 365 930 440 1010 475
NORM 560 265 700 330 830 390 910 430
510 240 630 295 750 355 810 380
ADJUST"
Jumper
Setting
+ 820 385 990 465 1180 555 1340 630 880 415 1120 530 1340 630 1440 680
NORM 750 355 900 425 1070 505 1230 580 800 375 1000 470 1200 565 1300 615
970 315 810 380 940 445 1080 510 720 340 900 425 1080 510 1170 550
The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position. Lennox Harmony zone control applications − Minimum blower speed is 400 cfm. Max cfm is the same as 2nd stage cool position.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed 2nd Stage COOL" Speed
BDC3 Jumper Speed Positions
1st Stage COOL" Speed
1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s
Table 6
CBWMV−36B−070 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 4%.
ADJUST"
umper
+ 590 280 745 350 895 420 975 460
NORM 545 255 680 320 805 380 890 420
490 230 600 280 725 340 780 370
ADJUST"
Jumper
Setting
+ 790 370 980 465 1140 540 1310 620 850 400 1090 515 1300 620 1430 675
NORM 730 345 870 410 1040 490 1190 560 775 365 990 465 1190 560 1280 605
640 300 770 360 920 435 1070 505 700 330 870 410 1065 500 1150 540
The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position. Lennox Harmony zone control applications − Minimum blower speed is 400 cfm. Max cfm is the same as 2nd stage cool position.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed 2nd Stage COOL" Speed
BDC3 Jumper Speed Positions
1st Stage COOL" Speed
1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s
Page 14
505047 09/06
Table 7
J
Setting
Setting
ADJUST
p
J
Setting
ADJUST
p
CBWMV−36C−090 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.
ADJUST"
umper
+ 620 290 770 365 930 440 1010 475
NORM 570 270 700 330 830 390 910 430
520 245 630 295 760 360 810 380
ADJUST"
Jumper
Setting
+ 820 385 1000 470 1180 555 1340 630 890 420 1130 535 1340 630 1450 685
NORM 760 360 900 425 1070 505 1220 575 800 380 1020 480 1220 575 1310 620
675 320 810 380 950 450 1100 520 720 340 900 425 1100 520 1180 555
The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position. Lennox Harmony zone control applications − Minimum blower speed is 400 cfm. Max cfm is the same as 2nd stage cool position.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed 2nd Stage COOL" Speed
BDC3 Jumper Speed Positions
1st Stage COOL" Speed
1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s
Table 8
CBWMV−60C−100 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.
ADJUST"
umper
+ 1110 525 1250 590 1380 650 1530 720
NORM 1000 470 1130 535 1250 590 1380 650
930 440 1040 490 1130 535 1260 595
ADJUST"
Jumper
Setting
+ 1500 710 1700 800 1880 885 2100 990 1540 725 1760 830 1970 930 2200 1040
NORM 1370 645 1540 725 1720 810 1920 905 1400 660 1600 755 1800 850 1980 935
1250 590 1380 650 1540 725 1720 810 1270 600 1420 670 1600 755 1780 840
The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position. Lennox Harmony zone control applications − Minimum blower speed is 600 cfm. Max cfm is the same as 2nd stage cool position.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed 2nd Stage COOL" Speed
BDC3 Jumper Speed Positions
1st Stage COOL" Speed
1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s
Page 15
CBWMV SERIES
Table 9
J
Setting
Setting
ADJUST
p
CBWMV−60C−120 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling Speed − 4, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.
ADJUST"
umper
+ 1100 520 1250 590 1400 660 1560 735
NORM 990 465 1130 535 1260 595 1400 660
930 440 1020 480 1130 535 1260 595
ADJUST"
Jumper
Setting
+ 1510 715 1720 810 1900 895 2120 1000 1570 740 1800 850 2000 945 2200 1040
NORM 1380 650 1560 135 1740 820 1920 905 1410 665 1620 765 1820 860 2020 955
1240 585 1380 650 1540 725 1720 810 1260 595 1440 680 1620 765 1810 855
The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position. Lennox Harmony zone control applications − Minimum blower speed is 600 cfm. Max cfm is the same as 2nd stage cool position.
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed 2nd Stage COOL" Speed
BDC3 Jumper Speed Positions
1st Stage COOL" Speed
1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s
Initial Air Purging
After all plumbing connections have been made, leak tested and flushed, the water heating device is ready to be filled with water and purged of air. Air bleeder valves are provided as a convenience for installations that are not equipped with purge manifolds.
1. Make sure electrical power and gas supply to system
are OFF.
2. Remove CBWMV coil section access panel.
3. Remove cap from highest air bleed valve and depress valve stem until water is released. This may be done with a refrigerant style hose. See figure 15.
4. Replace cap on valve and access panel.
5. Apply electrical power and gas supply to the system.
6. Follow the System Start−Up section to operate the sys­tem. Complete purging of air after unit has gone through initial start−up.
Air Bleed Valve Location
VALV E
SHOWN
WITH CAP ON
Figure 15
Page 16
505047 09/06
System Adjustments
Timed−ON and Timed−OFF Delays
The 45−second timed−ON delay and the 30−second timed− OFF delay for heating (time that the blower operates after the heat demand has been satisfied) is not adjustable.
Blower Speeds
Select the blower speed by moving the pins on the variable speed control board. See figure 14.
Refer to the speed selection chart on unit wiring diagram.
NOTE − To check for proper CFM, take the reading exter­nal to the unit. The coil must be dry when you take the reading.
Annual Service
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Electrical
1. Check all wiring for loose connections.
2. Check for correct voltage at CBWMV unit (unit operat­ing).
3. Check to see that blower is operating.
Blower
1. Check and clean blower wheel.
2. Motors are pre−lubricated for extended life; no further lubrication is required.
Freezestat
Verify that the freezestat functions.
Service Filters
Filters must be cleaned or replaced when dirty to assure proper unit operation.
Winterizing CBWMV Water Coil
If unit is installed in an unconditioned space, the piping be­tween the CBWMV unit and the water heating device should be insulated. If power is removed from the unit, wa­ter must be drained from the system to prevent freezing.
Repair Parts List
The following repair parts are available. When ordering parts, include the complete unit model number listed on the unit rating plate of each piece of equipment.
Cabinet Parts
Blower Access Panel
S S Coil Access Panel
Hot Water Coil Parts
Coil Replacement Kit
S
Blower Part
Blower Wheel
S S Blower Motor S Blower Housing
Electrical Parts
BDC3 Board
S S Transformer S Circuit Breaker, 24VAC S 3PDT Relay
Page 17
CBWMV SERIES
WARNING
WARNING TO SERVICE PERSONS! Electric shock hazard. When electrical power to the internal control box components must be available for troubleshooting, a common practice is to construct a by−pass" of the door interlock switch. When such a by−pass is in place, a potential shock hazard is present which can cause injury or death. Make sure any door interlock switch by−pass has been removed after troubleshooting is complete and BEFORE attempting any re­pairs to the control box components!
Troubleshooting: Continuous Fan Sequence of Operation
CONDITIONS: Power On Normal Operation LED: Steady Flash
Thermostat (S1) Calls for Continuous Fan, G−Only
YES
Blower Operates at the Continuous Fan Speed Selected by COOL Jumper and ADJUST Jumper Positions on the BDC3 Control (A52)
YES
RUN Light on BDC3 Control (A52) illuminates to Indi­cate a Continuous Fan Call
YES
CFM Light on A52 Indicates Blower CFM Selection with 100CFM / Blink
YES
Thermostat (S1) Continuous Fan Demand Satisfied
YES
Blower Off
NO
Check for 24 Volts Between ’G’ and C at A15 Terminal Strip
NO
Check for 24 Volts Between Pins 3 and 15 on J49
505047 09/06
Page 18
WARNING
WARNING TO SERVICE PERSONS! Electric shock hazard. When electrical power to the internal control box components must be available for troubleshooting, a common practice is to construct a by−pass" of the door interlock switch. When such a by−pass is in place, a potential shock hazard is present which can cause injury or death. Make sure any door interlock switch by−pass has been removed after troubleshooting is complete and BEFORE attempting any re­pairs to the control box components!
Troubleshooting: Cooling Sequence of Operation
CONDITIONS: Power On Normal Operation LED: Steady Flash
Thermostat (S1) Provides 24 Volt Cooling Call to In­door Blower (B3)
YES
2 Stage Condensing Unit?
YES
Blower (B3) Operates at the 1st Stage Cooling Speed Determined by COOL, DELAY and ADJUST Jumper Positions on the BDC3 Control (A52)
CFM Light on A52 Indicates Blower CFM Selection with 100CFM / Blink
YES
Check for 24 Volts Between Y and C on A15 Terminal Strip
Check for 24 Volts Between Pins 6 and 3 on J49
First Stage Demand for Cooling Satisfied?
YES
Blower Shuts Off According to the DELAY Jumper Position on the BDC3 Control (A52)
YES
Demand for Cooling Satisfied
NO
Check for 24 Volts Between Y and C at A15 Terminal Strip
NO
NO
NO
Blower (B3) Operates at the 2nd Stage Cooling Speed Determined by COOL, DELAY and ADJUST Jumper Positions on the BDC3 Control (A52)
YES
CFM Light on A52 Indicates Blower CFM Selection with 100CFM / Blink
YES
Thermostat (S1) Demand Satisfied
YES
Blower Shuts Off According to the DELAY Jumper Position on the BDC3 Control (A52)
YES
Demand for Cooling Satisfied
Thermostat (S1) Calls for 2nd Stage Cooling
YES
Blower Operates at the 2nd Stage Cooling Speed Deter­mined by COOL, DELAY and ADJUST Jumper Positions on the BDC3 Control (A52)
YES
CFM Light on A52 Indi­cates Blower CFM Selec­tion with 100CFM / Blink
YES
2nd Stage Thermostat (S1) Demand Satisfied
YES
Blower Returns to 1st Stage Cooling Speed
NO
NO
Check for 24 Volts Between Pins 14 and 3 on J49
NO
Check for 24 Volts Between Pins 14 and 3 on J49
Check for 24 Volts Between Y2 on TB1 and C on A15 Terminal Strip
Page 19
CBWMV SERIES
WARNING
WARNING TO SERVICE PERSONS! Electric shock hazard. When electrical power to the internal control box components must be available for troubleshooting, a common practice is to construct a by−pass" of the door interlock switch. When such a by−pass is in place, a potential shock hazard is present which can cause injury or death. Make sure any door interlock switch by−pass has been removed after troubleshooting is complete and BEFORE attempting any re­pairs to the control box components!
Troubleshooting: Heating Sequence of Operation
CONDITIONS: Power On Normal Operation LED: Steady Flash
Thermostat (S1) Calls for Heat
YES
Fixed blower−ON delay (45−second) complete
Blower Operates at the Heating Speed Selected by
HEAT Jumper and ADJUST Jumper Positions on
the BDC3 Control (A52)
YES
CFM Light on A52 Indicates Blower
Speed Selection with 100CFM / Blink
YES
Thermostat (S1) Demand Satisfied
YES
30 Second Blower Off Delay (Fixed) Complete
YES
Demand for Heat Satisfied
NO
NO
Check for 24 Volts Between
W and C at A52 Terminal Strip
Check for 24 Volts Between Pins 3 and 2 on J49
505047 09/06
Page 20
Loading...