Lennox CBA38MV User Manual

©2019 Lennox Industries Inc. Dallas, Texas, USA
INSTALLATION INSTRUCTIONS
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
NOTICE
A thermostat is not included and must be ordered separately.
• A Lennox communicating thermostat must be used in communicating applications.
In non-communicating applications, the Lennox ComfortSense® thermostat may be used, as well as other non-communicating thermostats.
In all cases, setup is critical to ensure proper system operation.
Field wiring for both communicating and non­communicating applications is illustrated in diagrams, which begin on page 13.
IMPORTANT: Special procedures are required for cleaning the all-aluminum coil in this unit. See page 43 in this instruction for information.
Dave Lennox Signature® Collection CBA38MV Units
MULTI-POSITION AIR HANDLERS 507725-02 12/2019
Table of Contents
CBA38MV Upow and Downow Unit Dimensions ....... 2
CBA38MV Horiz. LH/RH Discharge Unit Dimensions ...3
General Information ....................................................... 4
Shipping and Packing List .............................................4
Installation Clearances ..................................................4
Requirements ................................................................5
Installing the Unit ........................................................... 5
Brazing Connections .....................................................9
Installing the Condensate Drain .................................. 11
Inspecting and Replacing Filters .................................12
Sealing the Unit ...........................................................12
Field Control Wiring ..................................................... 13
Air Handler Control Button, Display and Jumpers ....... 25
Target CFM Tables ......................................................30
Unit Operating Sequences ..........................................32
Unit Operating Sequences ..........................................34
Heat Pump Operation (Heating and Cooling) .............. 39
Cooling Operation ........................................................40
Error Code / Recall Mode ............................................ 41
Indoor Blower Test ....................................................... 42
Operation ..................................................................... 42
Repairing or Replacing Cabinet Insulation .................. 43
Homeowner Maintenance ............................................43
Professional Maintenance ...........................................43
IMPORTANT INFORMATION FOR INSTALLER
CHECK FOR AND REMOVE THE FOLLOWING ITEMS BEFORE OPERATING UNIT.
BLOWER HOUSING SUPPORT PAD.
A
Important Update: The CBA38MV Air Handler Control (AHC) has been enhanced to automatically configure (set-up) the electric heat when the ECBA38 electric heat harness is connected to CBA38MV air handler. Manual Configuration of the electric heat using the push button is no longer required. See page 32.
H
HORIZONTA L DRAIN PA N (SEE
B
UPFLOW APPLICATIONS ON PAGE 5 AND DOWNFLOW APPLICATIONS ON PAGE 8 )
CONFIGURE ELECTRIC HEAT
REFRIGERANT LINE PLUGS (SEE
C
BRAZING CONNECTION ON PAGE 9) .
H
ECB38
Page 1
CBA38MV Upow and Downow Unit Dimensions – Inches (mm)
3/4 (19)
11‐1/16 (281)
LINE VOLTAGE
INLETS (TOP
AND LEFT SIDE)
TOP VIEW
FLOW
RETURN AIR
FRONT VIEW
SUPPLY AIR
D
AIR
F
OPENING
LOW VOLTAGE
INLETS (TOP AND
RIGHT SIDE)
5/8 (16)
3/4 (19)
5/8 (16)
G
ELECTRIC HEAT
(FIELD-INSTALLED)
A
H
FILTER ACCESS
UP-FLOW POSITION
OPTIONAL
SUCTION
LINE
LIQUID
LINE
FILTER
2
23/4 (70)
PIPING PLAT E DETAIL
13/4 (44)
43/8 (111)
31/2 (89)
(FOR UP-FLOW AND DOWN-FLOW POSITIONS)
11/8 (29)
(51)
53/8
(137)
CB
FILTER
SUCTION
BLOWER
COIL
RETURN AIR
)52( 1)61( 8/5
SIDE VIEW
E
5/8 (16)
LINE
LIQUID
LINE
OPTIONAL
ELECTRIC HEAT
(FIELD-INSTALLED)
LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)
SUCTION LINE
CONDENSATE DRAINS (2) (HORIZONTAL)
LIQUID LINE
CONDENSATE DRAINS (2) (UP-FLOW AND DOWN-FLOW)
C
COIL
BLOWER
SUPPLY
11‐1/16 (281)
AIR
SIDE VIEW
5/8 (16)
5/8 (16)
5/8 (16)
DOWN-FLOW POSITION
5/8 (16)
F
Air Opening
E
1 (25)
TOP VIEW
B
AIR FLOW
SUPPLY AIR
D
FRONT VIEW
5/8 (16)
Return
FILTER ACCESS
H
A
G
5/8 (16)
CBA38MV Common Dimensions - Inches (mm)
Dim. -018/024 -030/-036 -042/-048 -060
A
B
C
D
E
F
G
H
49-1/4 (1251) 51 (1295) 58-1/2 (1486) 621/2 (1588)
21-1/4 (540) 21-1/4 (540) 211/4 (540) 211/4 (540)
20-5/8 (524) 225/8 (575) 24-5/8 (625) 24-5/8 (625)
19-3/4 (502) 19-3/4 (502) 193/4 (502) 193/4 (502)
19 (483) 21 (533) 23 (584) 23 (584)
20 (508) 20 (508) 20 (508) 20 (508)
24-5/8 (625) 263/8 (670) 277/8 (708) 277/8 (708)
24-5/8 (625) 24-5/8 (625) 30-5/8 (778) 345/8 (879)
Page 2
CBA38MV Horizontal Left- and Right-Hand Discharge Unit Dimensions – Inches (mm)
53/8 (137)
CONDENSATE
DRAINS (2)
(UP-FLOW
AND
DOWN-FLOW)
CONDENSATE
DRAINS (2)
(HORIZONTAL)
PIPING PLAT E
DETAIL
5/8 (16)
5/8 (16)
5/8 (16)
53/4
(46)
E
RETURN AIR
OPENING
F
END VIEW
Horizontal Position
(LeftHand Air
Discharge)
13/4
(44)
(51)
2
11/2
(38)
1 (25)
FILTER ACCESS
LIQUID
LINE
SUCTION
LINE
11/8
(29)
43/8 (111)
FILTER
Horizontal Position
(RightHand Air
Discharge)
Coil
LIQUID
SUCTION
LINE
LINE
TOP VIEW
A
H
AIR
FLOW
FRONT VIEW
C
BLOWER
BLOWER
OPTIONAL ELECTRIC
HEAT (FIELD-INSTA LLED)
G
Coil
5/8 (16)
B
INLETS (BOTTOM
C
LINE VOLTAGE
INLETS (TOP
AND RIGHT
SIDE)
LOW VOLTAGE
AND RIGHT
SIDE)
FOR DIMENSIONS “A” THROUGH
“H”, SEE CHART ON PAGE 2.
11‐1/16
3/4 (19)
(281)
Supply
43/8 (111)
11/8
(29)
Air
Opening
END VIEW
D
3/4 (19)
3/4 (19)
3/4 (19)
3/4 (19)
LOW VOLTAGE
3/4 (19)
11‐1/16
(281)
Supply
D
Air Opening
LINE VOLTAGE INLETS
(BOTTOM AND LEFT SIDE)
END VIEW
INLETS (TOP AND
LEFT SIDE)
OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
5/8 (16)
B
CONDENSATE DRAINS (2)
A
G
Air Flow
(HORIZONTA L)
FRONT VIEW
FILTER
TOP VIEW
SUCTION
LINE
H
13/4
(44)
LIQUID
LINE
53/4 (146)
SUCTION LINE
PIPING PLAT E
DETAIL
FILTER ACCESS
11/2 (38)
LIQUID
LINE
1 (25)
E
Return
Air Opening
END VIEW
(51)
2
53/8 (137)
5/8 (16)
5/8 (16)
F
5/8 (16)
Page 3
Model Number Identication
230CB 38 036-01
060 = 5 tons (17.6 kW)
-
--6
MV
A
Unit Type
CB = Air Handler
Coil Type
A = Aluminum Coil
Series
Configuration
MV = Multi-Position, Variable
speed blower motor
Nominal Cooling Capacity
018/024 = 1.5 to 2 tons (5.3 to 7 kW) 030 = 2.5 tons (8.8 kW) 036 = 3 tons (10.6 kW) 042 = 3.5 tons (12.3 kW)
048 = 4 tons (14.1 kW)
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
General Information
This indoor unit with all-aluminum coil is designed for
installation with optional eld-installed electric heat and a
matched outdoor unit that is charged with HFC-410A re­frigerant. These units, designed for indoor installation in
multiple positions, are completely assembled for upow
and horizontal right-hand discharge before being shipped from the factory.
All CBA38MV air handlers are equipped with a factory-in­stalled, internally mounted check / expansion valve, which is suitable for use in HFC-410A applications.
This air handler is compatible with the ComfortSense® non-communicating thermostat and non-communicating outdoor units. In addition, this unit has the enhanced ca­pability of communicating with the communicating thermo­stats and communicating outdoor units using the Lennox RSBus protocols.
NOTE - For downow or horizontal left-hand air discharge, certain eld modications are required.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
Minor Revision Number
Refrigerant Metering Device
2 = Fixed Orifice 3 = TXV - Bleed port (indoor unit)
4 = TXV - Non-bleed port (indoor unit) 5 = TXV - Non-bleed port (outdoor unit) 6 = TXV - R410A Non-bleed port (indoor unit)
Voltage
230 = 208/230V-60hz-1ph
Check the air handler for shipping damage; if found, im­mediately contact the last carrier.
Installation Clearances
Cabinet 0 inch (0 mm)
To Plenum 0 inch (0 mm)
To Outlet Duct within 3 feet (914 mm) 0 inch (0 mm)
Floor See Note #1
Service / Maintenance See Note #2
1
Units installed on combustible oors in the downow position with
electric heat require optional downow additive base.
2
Front service access – 24 inches (610 mm) minimum.
NOTE - If cabinet depth is more than 24 inches (610 mm), allow a minimum of the cabinet depth plus 2 inches (51 mm).
IMPORTANT
This unit must be matched with an indoor coil as
specied in the Lennox Product Specications (EHB). Coils previously charged with HCFC-22 must be ushed.
WARNING
During blower operation, the ECM motor emits energy that may interfere with pacemaker operation. Interference is reduced by both the sheet metal cabinet and distance.
Shipping and Packing List
Package 1 of 1 contains: 1 – Assembled air handler unit
1 – Pipe nipple (Sch80, 3/4" I.D. x 5")
1 – Downow shields and foam tapes (required for down-
ow conguration only)
1 – Horizontal drip shield (CBA38MV-060 only)
1 – Warranty card
Page 4
WARNING
Improper installation of the air handler can result in personal injury or death.
Do not allow external combustion products or other contaminants to enter the return air system or to be mixed with air that will be supplied to the living space. Use sheet metal screws and joint tape or duct mastic to
seal return air system to air handler. In platform installations, the air handler should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the air handler. Allow absolutely no sagging, cracks, gaps. etc.
For no reason should return and supply air duct systems ever be connected to or from other heating devices
such as a replace or stove. etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property damage could result.
Requirements
In addition to conforming to manufacturer’s installation in­structions and local municipal building codes, installation of Lennox air handler units (with or without optional elec­tric heat), shall conform with the following National Fire Protection Association (NFPA) standards:
• NFPA No. 90A - Standard for Installation of Air Condi­tioning and Ventilation Systems
• NFPA No. 90B - Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems
This unit is approved for installation clearance to combus­tible material as stated on the unit rating plate. Accessi­bility and service clearances must take precedence over combustible material clearances.
4 - Replace access panel.
UPFLOW APPLICATION
Use the following procedures to congure the unit for up­ow operations:
1 - Remove access panels.
2 - Remove and discard the horizontal drip shield (-060
model, used only on horizontal applications) and the corrugated padding between the blower and coil assembly.
3 - The horizontal drain pan must be removed when
the coil blower is installed in the upow position.
Removing the horizontal drain pain will allow proper
air ow and increased e󰀩ciency.
4 - After removing the horizontal drain pan, place the
unit in the desired location. Set unit so that it is level. Connect return and supply air plenums as required
using sheet metal screws as illustrated in gure 1.
5 - Install units that have no return air plenum on a
stand that is at least 14" from the oor to allow for proper air return. Lennox o󰀨ers an optional upow
unit stand as listed in table 1.
HORIZONTAL DRAIN PAN (MUST BE REMOVED)
UP-FLOW / DOWN-FLOW DRAIN PAN
Installing the Unit
These units are factory-congured for upow and hori­zontal right-hand discharge installation. For downow or horizontal left-hand discharge, certain eld modications
are required.
DISASSEMBLE/REASSEMBLE AIR HANDLER UNITS
The air handler units consists of two factory-assembled sections. It may be necessary to disassemble the sections when positioning the unit for installation.
To disassemble:
1 - Remove access panels.
2 - Remove both blower and coil assemblies. This will
lighten the cabinet for lifting.
3 - Remove one screw from the left and right posts
inside the unit. Remove one screw from each side on the back of the unit. Unit sections will now separate.
To reassemble:
1 - Align cabinet sections together.
2 - Reinstall screws.
3 - Replace blower and coil assemblies.
FIGURE 1. Upow Conguration
TABLE 1. Optional Side-Return Unit Stand
(Upow Only)
Model Kit Number
All unit sizes
45K32
HORIZONTAL RIGHT-HAND DISCHARGE APPLICATION
Use the following procedures to congure the unit for hor­izontal right-hand discharge operations:
NOTE – For horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE – When air handler is located above a nished space, the secondary drain pan must have a larger foot­print than the air handler. In addition, a 3/4" (19.1mm) overow drain line must be:
• Connected to secondary drain pan
or
• Connected to the overow drain outlet of the air handler drain pan.
Page 5
NOTE - (-060 Model Only) Before operating the unit, re-
UP-FLOW / DOWN-FLOW DRAIN
HORIZONT PA
FRONT VIEW END VIEW
move access panels and the horizontal drip shield and the corrugated padding between the blower and coil assem­bly. Discard the corrugated padding and the downow drip shields.
NOTE - (-060 Model Only) Install the horizontal shield on the front edge of the horizontal drain pan as illustrated in gure 2.
1 - No further adjustment is necessary. Set unit so that it
is sloped 1/4" towards the drain pan end of the unit.
2 - If the unit is suspended, the entire length of the
cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2" to avoid damaging the
coil or lter as illustrated in gure 3. Use sheet
metal screws to connect the return and supply air plenums as required.
HORIZONTAL DRIP SHIELD (-060 MODELS)
PAN
2 - Remove the downow rail then replace screws.
3 - Seal around the exiting drain pipe, liquid line, and
suction line to prevent humid air from inltrating into
the unit.
1/2" SCREWS MAXIMUM
ANGLE IRON OR
SHEET METAL
ELECTRICAL INLET CLEARANCE 4" (102 mm)
FIGURE 3. Suspending Horizontal Unit
IMPORTANT
When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right­or left-hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.
N
FIGURE 2. Right-Hand Discharge Conguration
HORIZONTAL RIGHT-HAND DISCHARGE APPLICATION IN HIGH-HUMIDITY AREAS
For horizontal applications in high humidity areas, remove
the downow rail closest to the drain pan.
To remove rail:
1 - Remove the screws from the rail at the back of unit
and at the cabinet support rail.
AL DRAIN
NO ADJUSTMENT IS NECESSARY
DOWN-FLOW RAIL
HORIZONTAL LEFT-HAND DISCHARGE APPLICATION
NOTE – For horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE - (-060 Model Only) Before operating the unit, re- move access panels and the horizontal drip shield and the corrugated padding between the blower and coil assem­bly. Discard the corrugated padding and the downow drip shields. (The shields are used for downow applications only.)
Page 6
HORIZONTAL DRIP SHIELD (-060 MODEL)
DRAIN PAN
CABINET
SUPPORT
DRAIN PAN
REINSTALLED
HERE
TOP CAP ROTATED TO
CORRECT POSITION
90º
BEND
TOP CAP SCREWS
3/16” PLASTIC PLUG (REAR COIL END SEAL)
HORIZONTA L DRIP SHIELD SCREW (FRONT COIL END SEAL)
DRAIN PAN SHIPPING LOCATION
INSTALL DRAIN PAN
BETWEEN TA B AND
EXTERIOR INNER WALL.
DETAIL C
REINSTALLED HERE REMOVED FROM HERE
———— DRAIN PLUGS ————
FRONT VIEW
COIL SHOWN IN UPFLOW POSITION FOR EASY
CONVERSION (LEFT-HAND AIR DISCHARGE )
DETAIL A
FIGURE 4. Field Modication for Left-Hand Discharge
Use the following procedures to congure the unit for hor­izontal left-hand discharge operations:
1 - Pull the coil assembly from unit. Pull o󰀨 the horizontal
drain pan.
2 - Remove the drain plugs from back drain holes on
horizontal drain pan and reinstall them on front holes.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into the drain pan during installation that may plug up the drain opening.
3 - Rotate drain pan 180º front-to-back and install it on
the opposite side of the coil.
4 - Remove screws from top cap. Remove horizontal
drip shield screw located in the center of the back
coil end seal as illustrated in gure 4 on page 5.
5 - Rotate horizontal drip shield 180º front-to-back.
6 - Remove plastic plug from left hole on coil front
end seal and reinstall plug in back hole. Reinstall horizontal drip shield screw in front coil end seal. Drip shield should drain downward into horizontal drain pan inside coil.
NOTE – Be very careful when reinstalling the screws into the coil end plate engaging holes. Misaligned screws may damage the coil.
7 - From the upow position, ip cabinet 90º to the
left and set into place. Replace blower assembly. Secure coil in place by bending down the tab on the
cabinet support rail as illustrated in gures 4 and 5.
TOP CAP
DETAIL B
BEND
90º
DOWN-FLOW RAIL FRONT EDGE OF HORIZONTAL
ALIGN HOLES WITH HOLES IN COIL END PLATE. STARTING WITH THE ROUND HOLES ON THIS END.
BACK COIL END SEAL
FIGURE 5. Left-Hand Discharge Conguration
8 - Install the horizontal shield (-060 model) on the
front edge of the horizontal drain pan as illustrated
in gure 5.
NOTE – For horizontal applications in high humidity ar- eas, remove the downow rail closest to the drain pan. To remove rail, remove screw from rail at back of unit and at cabinet support rail. Remove downow rail then replace screws. Also, seal around the exiting drain pipe, liquid and suction lines to prevent inltration of humid air.
9 - Knock out drain seal plate from access door. Secure
plate to cabinet front ange with screw provided.
10 - Flip access door and replace it on the unit.
11 - Set unit so that it is sloped 1/4ʺ toward the drain
pan end of the unit. Connect return and supply air plenums as required using sheet metal screws.
Page 7
AN
DOWNFLO
1” WIDE FOAM TAPE (LONGER PIECE)
12 - If suspending the unit, it must be supported along the
entire length of the cabinet. If using chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) so that the full length of the cabinet is supported. Use securing
screws no longer than 1/2ʺ to avoid damage to coil or lter, as illustrated in gure 3 on page 6. Connect
return and supply air plenums as required using sheet metal screws.
DOWNFLOW APPLICATION
Use the following procedures to congure the unit for downow operations:
IMPORTANT
If electric heat section with circuit breakers (ECB29/
ECB31) is installed in a CBA38MV unit in a downow
application, the circuit breakers must be rotated 180° to the UP position. See ECB29/ECB31 installation instructions for more details.
HORIZONTA L DRAIN P
(REMOVE FROM UNIT)
UP-LOAD /
W
DRAIN PAN
FIGURE 6. Downow Discharge Position
Table 2 outlines the sizes of the various drip shields.
NOTE - (-060 Model Only) Remove access panels and horizontal drip shield from the corrugated padding be­tween the blower and coil assembly.
1 - Remove the coil assembly from the unit.
2 - For best e󰀩ciency and air ow, remove the
horizontal drain pan from the units in downow positions as illustrated in gure 6.
3 - Rotate cabinet 180º from the upright position. See
gure 6. You may need to rst remove the blower
assembly to lighten the cabinet for lifting.
4 - Foam tape that is provided creates a seal between
the drip shield and the coil so that water does not leak into the air stream. The foam tape pieces are precut. Apply the tape to the drip shields as
illustrated in gure 7 and specied as follows:
• Apply two pieces of foam tape provided down both ends of each shield. The tape should measure
4-3/4ʺ X 2ʺ (120 X 25 mm). Ensure that the tape
covers both sides of the shield equally.
• Apply the longer piece of 1 inch wide foam tape be­tween the end pieces of tape.
5 - From the underside of the coil, install the downow
drip shield rmly in place as illustrated in gure 8.
TABLE 2. Downow Drip Shields (Tape Required)
Units Length Width
-018/024 Not Required Not Required
-030 15-7/8ʺ 4-11/16ʺ
-036, -042 17-7/8ʺ 4-11/16ʺ
-048, -060 19-7/8ʺ 4-11/16ʺ
DRIP SHIELD
SIDE
VIEW
2” WIDE FOAM TAPE
FIGURE 7. Applying Foam Tape to Drip Shield
COIL
DRIP SHIELD
DRIP PAN
FIGURE 8. Downow Drip Shields
6 - Replace the coil assembly and blower if you have
removed it. Replace the coil access panel.
7 - Set the unit so that it is level. Using sheet metal
screws, connect the return and supply air plenums as required.
NOTE - For downow application, metal or Class I supply and return air plenums must be used.
Page 8
AIR
HANDER
UNIT
COMBUSTIBLE FLOOR
PROPERLY SIZED
FLOOR OPENING
ADDITIVE BASE
FIGURE 9. Downow Combustible Flooring Base
8 - For downow installation on combustible ooring,
an additive base must be used as illustrated in gure 9 on page 9. See CBA38MV Product Specications (EHB) for downow combustible ooring base kits
available for this air handler.
9 - Cut an opening appropriately sized for combustible
base. Base dimensions are illustrated in gure 10.
After opening has been cut, set the additive base into opening. Connect outlet air plenum to the additive base. Set the unit on the additive base so
anges of the unit drop into the base opening and
seal against the insulation strips. The unit is now locked in place. Install return air plenum and secure with sheet metal screws.
Brazing Connections
WARNING
Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING
Danger of re. Bleeding the refrigerant
charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.
WARNING
Danger of explosion! Can cause equipment damage, injury, or
death. When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
15/8 (41)
15/8 (41)
20 (508)
15/8 (41)
5/8 (16)
TOP VIEW
113/8
(289)
SUPPLY AIR OPENING
225/8 (575) -018/024
245/8 (625) -030, 036
265/8 (676) -042, 048, 060
131/2 (343)
OPENING
SIDE VIEW
23-1/4 (591)
INCHES (MM)
3 (76)
FIGURE 10. Downow Combustible Base Dimensions
CAUTION
Brazing alloys and ux contain materials which are
hazardous to your health. Avoid breathing vapors or fumes from brazing operations.
Perform operations only in well ventilated areas. Wear gloves and protective goggles or face shield to
protect against burns. Wash hands with soap and water after handling brazing
alloys and ux.
IMPORTANT
To prevent the build-up of high levels of nitrogen when purging, it must be done in a well-ventilated area. Purge low-pressure nitrogen (1 to 2 psig) through the refrigerant piping during brazing. This will help to prevent oxidation and the introduction of moisture into the system.
Page 9
LINE.
PLEASE READ IMPORTANT ISSUES CONCERNING BRAZING
NOTE — REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR REFRIGERANT PIPING SIZE REQUIREMENTS .
NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing, 45 percent alloy for copper-to-brass and copper-to-steel brazing.
REMOVE ACCESS PANEL
A
REMOVE RUBBER PLUG FROM BOTH LIQUID
B
AND SUCTION LINES
NOTE — CBA38MV SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE. IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED, CHECK THE COIL FOR LEAKS BEFORE INSTALLING.
EITHER REMOVE OR PUSH PIPE WRAPPING BACK
D
THROUGH HOLE IN PIPING PLATE BEFORE LINE SET CONNECTION AND BRAZING.
OPERATIONS ON PAGE 10 BEFORE PROCEEDING.
USE A WET RAG TO PROTECT CTXV
C
SENSING BULB WHEN BRAZING SUCTION LINE CONNECTIONS.
LOW
HIGH
PIPING PLATE
CONNECT PIPES
E
NOTE — REFRIGERANT LINE SETS SHOULD BE ROUTED TO ALLOW FILTER ACCESSIBILITY.
REPEAT PREVIOUS PROCEDURE FOR LIQUID
I
FLOW REGULATED NITROGEN (AT 1 TO 2 PSIG)
THROUGH THE REFRIGERATION GAUGE SET INTO THE VALV E STEM PORT CONNECTION ON THE OUTDOOR UNIT LIQUID LINE SER VICE VALVE AND OUT OF THE VALV E STEM PORT CONNECTION ON THE SUCTION SERVICE VALVE.
PLACE A WET RAG AGAINST PIPING
G
PLATE AND AROUND THE SUCTION LINE CONNECTION. A
BRAZE CONNECTION. ALLOW PIPE TO
H
COOL BEFORE REMOVING WET RAG FROM CTXV SENSING BULB AND PIPING PANEL AREA.
FIGURE 11. Brazing Connections
CONNECT GAUGES AND
F
START NITROGEN FLOW
REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING, EVACUATING AND CHARGING PROCEDURES
NITROGEN
Page 10
TABLE 3. CBA38MV Refrigerant Connections and
LEFT-HAND AIR
UP-FLOW OR
RIGHT-HAND AIR
Line Set Requirements
Model
-018/ 024
-030
-036
-042
-048
-060
NOTE - Some applications may require a eld-provided 7/8ʺ to 1-1/8ʺ adapter.
Liquid
Line
3/8ʺ
(10mm)
3/8ʺ
(10mm)
3/8ʺ
(10mm)
3/8ʺ
(10mm)
Vapor
Line
3/4ʺ
(19mm)
3/4ʺ
(19mm)
7/8"
(22mm)
7/8"
(22mm)
L15 Line Sets
L15 line set sizes are dependant on unit match-up. See Product
Specications (EHB) for
outdoor unit to determine correct line set sizes
Field fabricated
NOTE - When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fab­rication Guidelines, CORP. 9351-L9, or contact Lennox Technical Support Product Applications for assistance.
Installing the Condensate Drain
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into the drain pan during installation that may plug up the drain opening.
MAIN DRAIN
Connect the main drain and route downward to drain line or sump. Do not connect drain to a closed waste system.
See Figure 13 for typical drain trap conguration.
OVERFLOW DRAIN
It is recommended that the overow drain is connected to an overow drain line for all units. If overow drain is not
connected, it must be plugged with provided cap.
For downow orientation, the overow drain MUST be connected and routed to a overow drain line. See Fig­ure 12 for main and overow drain locations based on coil
orientation.
DISCHARGE
OVERFLOW
DRAIN ON LEFT
DOWN-FLOW
DISCHARGE
MAIN DRAIN ON
RIGHT
FIGURE 12. Main and Overow Drain Locations
Based on Coil Orientation
BEST PRACTICES
The following best practices are recommended for the condensate removal process:
Main and overow drain lines should NOT be smaller than both drain connections at drain pan.
Overow drain line should run to an area where home- owner will notice drainage.
It is recommended that the overow drain line be vented and a trap installed. Refer to local codes.
Condensate drain lines must be congured or provided with a cleanout to permit the clearing of blockages and for maintenance without requiring the drain line to be cut.
Page 11
ABOVE
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE MA IN DRAIN.
FINISHED
SPACE?
OVERFLOW DRAIN LINE
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO ROUTE OVERFLOW DRAIN LINE, INSTA LL LOW VOLTAGE OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.
LENNOX #
X3169
COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
NO
AND MALE ADAPTER, TWO PA RT DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING
CLEAN OUT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
VENT
MAIN
MAIN
DRAIN
PIPE NIPPLE
AIR HANDLER DRAIN PA N
OVERFLOW
DRAIN
YES
NOTE — WHEN A AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE THE SECONDARY DRAIN PA N MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.
DRAIN
SECONDARY
DRAIN PAN
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE AIR HANDLER DRAIN PAN.
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES — GENERALLY, TWO INCHES (51MM).
1
LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
FIGURE 13. Typical Main and Overow Drain Installations
CUT TO
REQUIRED
LENGTH
PROVIDED
SIDE VIEW
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
1
P-TRAP
LENNOX
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4”
2
FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL) TRAPS ARE REQUIRED ON ALL DRAIN LINES CONNECTED TO COIL.
2”
(51MM)
TRAP DEPTH
TO APPROVED
DRAIN
DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)
Inspecting and Replacing Filters
IMPORTANT
Filter access door must be in place during unit operation. Excessive warm air entering the unit from unconditioned
space may result in water blow-o󰀨 problems.
Filters may be duct-mounted or installed in the cabinet. A
lter is installed at the factory. Note that lter access door ts over access panel. Air will leak if the access panel is placed over the lter door.
Filters should be inspected monthly and must be cleaned or replaced when dirty to assure proper furnace operation.
To replace lter:
1 - Loosen the thumbscrews holding the lter panel in
place.
2 - Slide the lter out of the guides on either side of
cabinet.
3 - Insert new lter.
4 - Replace panel.
See table 4 for replacement lter sizes.
TABLE 4. Filter Dimensions
CBA38MV Filter Size – In. (mm)
-018/024, -030, -036 20 x 20 x 1 (508 x 508 x 25)
-042, -048, -060 20 x 24 x 1 (508 x 610 x 25)
Sealing the Unit
WARNING
There must be an airtight seal between the bottom of
the air handler and the return air plenum. Use berglass
sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide-producing
device (i.e., wood replace) is installed.
Seal the unit so that warm air is not allowed into the cabi­net. Warm air introduces moisture, which results in water
blow-o󰀨 problems. This is especially important when the
unit is installed in an unconditioned area.
Page 12
Make sure the liquid line and suction line entry points are
sealed with either the provided exible elastomeric ther­mal insulation, or eld provided material (e.g. Armaex,
Permagum or equivalent). Any of the previously men­tioned materials may be used to seal around the main and auxiliary drains, and around open areas of electrical inlets.
Field Control Wiring
WARNING
Electric Shock Hazard. Can cause injury or death. Foil-faced insulation has conductive characteristics
similar to metal. Be sure there are no electrical
connections within a ½ʺ of the insulation. If the foil-faced
insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g. fuses or circuit breakers), the current can be enough to cause an electric shock hazard that could cause personal injury or death.
Wiring must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to follow­ing wiring diagrams. See unit nameplate for minimum cir­cuit ampacity and maximum over-current protection size.
WARNING
Run 24V Class II wiring only through specied low
voltage opening. Run line voltage wiring only through
specied high voltage opening. Do not combine voltage
in one opening
Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Ca­nadian Electric Code, Part I, CSA Standard C22.1.
Separate openings have been provided for 24V low volt­age and line voltage. Refer to the dimension illustration of
specic location.
CAUTION
USE COPPER CONDUCTORS ONLY.
WIRING CONNECTIONS
1 - Install line voltage power supply to unit from a
properly installed circuit breaker.
2 - Ground unit at unit disconnect switch or to an earth
ground.
NOTE – Connect conduit to the unit using a proper con­duit tting. Units are approved for use only with copper conductors. A complete unit wiring diagram is located on the back side of the unit’s access panel.
3 - Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit.
NOTE – For proper voltages, select thermostat wire gauge per the following chart:
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
CAUTION
Electrostatic discharge can a󰀨ect
electronic components. Take care during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge.
Page 13
Cut Size: 7" wide x 10" tall
FIGURE 14. CBA38MV Air Handler Unit Typical Wiring Diagram
Page 14
Loading...
+ 32 hidden pages