This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
INSTRUCTIONS
Elite® Series
CBA27UHE Air Handler Units
MULTI-POSITION AIR HANDLERS
507674-01
3/2017
Table of Contents
CBA27UHE Upow and Downow Unit Dimensions ..... 2
CBA27UHE Horizontal Left- and Right-Hand Discharge
Unit Dimensions .............................................................3
General Information ....................................................... 4
Shipping and Packing List .............................................4
IMPORTANT: Special procedures are required for cleaning the all-aluminum coil in this unit. See page 15 in this instruction
for information.
IMPORTANT INFORMATION FOR INSTALLER
CHECK FOR AND REMOVE THESE ITEMS BEFORE OPERATING UNIT.
TOP CAP SHIPPING
BRACKET (REPLACE
SCREWS IN TOP CAP
BLOWER HOUSING
SUPPORT PAD
HORIZONTAL DRAIN PAN (SEE PAGES 4
AND 6)
REFRIGERANT LINE PLUGS
D
(SEE PAGE 6)
AFTER REMOVAL)
DRIP SHIELD. (USED FOR -060 UNITS HORIZONTAL
APPLICATIONS ONLY.) (SEE PAGE 5.) SHOWN
INSTALLED ON DRAIN PAN IN -060 UNIT.
D
Page 1
CBA27UHE Upow and Downow Unit Dimensions – Inches (mm)
3/4 (19)
11‐1/16 (281)
LINE VOLTAGE
INLETS (TOP
AND LEFT SIDE)
TOP VIEW
FLOW
RETURN AIR
FRONT VIEW
SUPPLY AIR
D
AIR
F
OPENING
LOW VOLTAGE
INLETS (TOP AND
RIGHT SIDE)
5/8 (16)
3/4 (19)
5/8 (16)
G
ELECTRIC HEAT
(FIELD-INSTALLED)
A
H
FILTER ACCESS
UP-FLOW POSITION
OPTIONAL
SUCTION
LINE
LIQUID
LINE
FILTER
2
2‐3/4
(70)
PIPING PLAT E DETAIL
1‐3/4 (44)
4‐3/8 (111)
3‐1/2 (89)
(FOR UP-FLOW AND DOWN-FLOW POSITIONS)
1‐1/8 (29)
(51)
5‐3/8
(137)
CB
FILTER
SUCTION
BLOWER
COIL
RETURN AIR
)52( 1)61( 8/5
SIDE VIEW
E
5/8 (16)
LINE
LIQUID
LINE
OPTIONAL
ELECTRIC HEAT
(FIELD-INSTALLED)
LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)
SUCTION LINE
CONDENSATE DRAINS
(2) (HORIZONTAL)
LIQUID LINE
CONDENSATE DRAINS
(2) (UP-FLOW AND
DOWN-FLOW)
C
COIL
BLOWER
SUPPLY
11‐1/16 (281)
AIR
SIDE VIEW
5/8 (16)
5/8 (16)
5/8 (16)
DOWN-FLOW POSITION
5/8 (16)
F
Air Opening
E
1 (25)
TOP VIEW
B
AIR FLOW
SUPPLY AIR
D
FRONT VIEW
5/8 (16)
Return
FILTER ACCESS
H
A
G
5/8 (16)
CBA27UHE Common Dimensions - Inches (mm)
Dim.-018/-024-030/-036-042/-048-060
A
B
C
D
E
F
G
H
49-1/4 (1251)51 (1295)58-1/2 (1486)62‐1/2 (1588)
21-1/4 (540)21-1/4 (540)21‐1/4 (540)21‐1/4 (540)
20-5/8 (524)22‐5/8 (575)24-5/8 (625)24-5/8 (625)
19-3/4 (502)19-3/4 (502)19‐3/4 (502)19‐3/4 (502)
19 (483)21 (533)23 (584)23 (584)
20 (508)20 (508)20 (508)20 (508)
24-5/8 (625)26‐3/8 (670)27‐7/8 (708)27‐7/8 (708)
24-5/8 (625)24-5/8 (625)30-5/8 (778)34‐5/8 (879)
Page 2
CBA27UHE Horizontal Left- and Right-Hand Discharge Unit Dimensions – Inches (mm)
5‐3/8
(137)
CONDENSATE
DRAINS (2)
(UP-FLOW
AND
DOWN-FLOW)
CONDENSATE
DRAINS (2)
(HORIZONTAL)
PIPING PLAT E
DETAIL
5/8 (16)
5/8 (16)
5/8 (16)
5‐3/4
(46)
E
RETURN AIR
OPENING
F
END VIEW
Horizontal Position
(Left‐Hand Air
Discharge)
1‐3/4
(44)
(51)
2
1‐1/2
(38)
1 (25)
FILTER ACCESS
LIQUID
LINE
SUCTION
LINE
1‐1/8
(29)
4‐3/8
(111)
FILTER
Horizontal Position
(Right‐Hand Air
Discharge)
Coil
LIQUID
SUCTION
LINE
LINE
TOP VIEW
A
H
AIR
FLOW
FRONT VIEW
C
BLOWER
BLOWER
OPTIONAL ELECTRIC
HEAT (FIELD-INSTA LLED)
G
Coil
5/8 (16)
B
INLETS (BOTTOM
C
LINE VOLTAGE
INLETS (TOP
AND RIGHT
SIDE)
LOW VOLTAGE
AND RIGHT
SIDE)
FOR DIMENSIONS “A” THROUGH
“H”, SEE CHART ON PAGE 2.
11‐1/16
3/4 (19)
(281)
Supply
4‐3/8
(111)
1‐1/8
(29)
Air
Opening
END VIEW
D
3/4 (19)
3/4 (19)
3/4 (19)
3/4 (19)
LOW VOLTAGE
3/4 (19)
11‐1/16
(281)
Supply
D
Air Opening
LINE VOLTAGE INLETS
(BOTTOM AND LEFT SIDE)
END VIEW
INLETS (TOP AND
LEFT SIDE)
OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
5/8 (16)
B
CONDENSATE DRAINS (2)
(HORIZONTA L)
G
Air Flow
FILTER
TOP VIEW
A
FRONT VIEW
SUCTION
LINE
H
1‐3/4
(44)
LIQUID
LINE
5‐3/4
(146)
SUCTION LINE
PIPING PLAT E
DETAIL
FILTER ACCESS
1‐1/2 (38)
LIQUID
LINE
1 (25)
E
Return
Air Opening
END VIEW
(51)
2
5‐3/8
(137)
5/8 (16)
5/8 (16)
F
5/8 (16)
Page 3
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
General Information
The Elite® CBA27UHE series air handler with all-aluminum coil is designed for installation with optional eld-in-
stalled electric heat and a matching HFC-410A outdoor
unit.
This instruction is intended as a general guide and does
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation.
Shipping and Packing List
Package 1 of 1 contains:
1 – Assembled air handler unit
Check the air handler for shipping damage; if found, immediately contact the last carrier.
Requirements
IMPORTANT
This unit must be matched with an indoor coil as specied
in the Lennox Engineering Handbook. Coils previously
charged with HCFC-22 must be ushed.
In addition to conforming to manufacturer’s installation instructions and local municipal building codes, installation
of Lennox air handler units (with or without optional electric heat), shall conform with the following National Fire
Protection Association (NFPA) standards:
• NFPA No. 90A - Standard for Installation of Air Conditioning and Ventilation Systems
• NFPA No. 90B - Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning Systems
This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over
combustible material clearances.
To disassemble:
1 - Remove access panels.
2 - Remove both blower and coil assemblies. This will
lighten the cabinet for lifting.
3 - Remove one screw from the left and right posts
inside the unit. Remove one screw from each
side on the back of the unit. Unit sections will now
separate.
To reassemble:
1 - Align cabinet sections together.
2 - Reinstall screws.
3 - Replace blower and coil assemblies.
4 - Replace access panel.
UPFLOW APPLICATION
Use the following procedures to congure the unit for upow operations:
1 - Remove access panels.
2 - Remove and discard the horizontal drip shield (-060
model, used only on horizontal applications) and
the corrugated padding between the blower and coil
assembly.
3 - The horizontal drain pan must be removed when
the coil blower is installed in the upow position.
Removing the horizontal drain pain will allow proper
air ow and increased efciency.
4 - After removing the horizontal drain pan, place the
unit in the desired location. Set unit so that it is level.
Connect return and supply air plenums as required
using sheet metal screws as illustrated in gure 1.
5 - Install units that have no return air plenum on a
stand that is at least 14" from the oor to allow for
proper air return. Lennox offers an optional upow
unit stand as listed in table 1.
HORIZONTAL DRAIN PAN
(MUST BE REMOVED)
UP-FLOW /
DOWN-FLOW
DRAIN PAN
Installing the Unit
These units are factory-congured for upow and horizontal right-hand discharge installation. For downow or
horizontal left-hand discharge, certain eld modications
are required.
DISASSEMBLE/REASSEMBLE AIR HANDLER UNITS
The air handler units consists of two factory-assembled
sections. It may be necessary to disassemble the sections
when positioning the unit for installation.
FIGURE 1. Upow Conguration
TABLE 1. Optional Side-Return Unit Stand
(Upow Only)
ModelKit Number
All unit sizes45K32
Page 4
HORIZONTAL RIGHT-HAND DISCHARGE
UP-FLOW / DOWN-FLOW
DRAIN
HORIZONT
PA
FRONT VIEWEND VIEW
TOP CAP ROTATED TO
APPLICATION
Use the following procedures to congure the unit for horizontal right-hand discharge operations:
NOTE – For horizontal applications, a secondary drain
pan is recommended. Refer to local codes.
1 - Before operating the unit, remove access panels
and the horizontal drip shield (-060 model) and the
corrugated padding between the blower and coil
assembly. Discard the corrugated padding.
2 - Install the horizontal shield on the front edge of the
horizontal drain pan as illustrated in gure 2.
3 - No further adjustment is necessary. Set unit so that
it is sloped 1/4" towards the drain pan end of the
unit.
4 - If the unit is suspended, the entire length of the
cabinet must be supported. If you use a chain or
strap, use a piece of angle iron or sheet metal
attached to the unit (either above or below) to
support the length of the cabinet. Use securing
screws no longer than 1/2" to avoid damaging the
coil or lter as illustrated in gure 3. Use sheet
metal screws to connect the return and supply air
plenums as required.
HORIZONTAL DRIP SHIELD (-060 MODELS)
PAN
1/2" SCREWS MAXIMUM
ANGLE IRON OR
SHEET METAL
ELECTRICAL INLET CLEARANCE 4"
(102 mm)
FIGURE 3. Suspending Horizontal Unit
IMPORTANT
When removing the coil, there is possible danger of
equipment damage and personal injury. Be careful when
removing the coil assembly from a unit installed in rightor left-hand applications. The coil may tip into the drain
pan once it is clear of the cabinet. Support the coil when
removing it.
HORIZONTAL LEFT-HAND DISCHARGE
APPLICATION
NOTE – For horizontal applications, a secondary drain
pan is recommended. Refer to local codes.
CABINET
SUPPORT
DRIP
SHIELD
CORRECT POSITION
TOP CAP SCREWS
N
FIGURE 2. Right-Hand Discharge Conguration
HORIZONTAL RIGHT-HAND DISCHARGE
APPLICATION IN HIGH-HUMIDITY AREAS
For horizontal applications in high humidity areas, remove
the downow rail closest to the drain pan.
To remove rail:
1 - Remove the screws from the rail at the back of unit
and at the cabinet support rail.
2 - Remove the downow rail then replace screws.
3 - Seal around the exiting drain pipe, liquid line, and
suction line to prevent humid air from inltrating into
the unit.
AL DRAIN
NO ADJUSTMENT IS NECESSARY
DOWN-FLOW RAIL
90º
BEND
DRAIN PAN
REINSTALLED
HERE
REINSTALLED HERE REMOVED FROM HERE
COIL SHOWN IN UPLOAD POSITION FOR EASY CONVERSION
TOP
CAP
90º
BEND
———— DRAIN PLUGS ————
ALIGN HOLES WITH
HOLES IN COIL END
PLATE. STARTING WITH
THE ROUND HOLES ON
THIS END.
BACK COIL END SEAL
FIGURE 4. Field Modication for
Left-Hand Discharge
DRAIN PAN
SHIPPING
LOCATION
Page 5
Use the following procedures to congure the unit for hor-
HORIZONTAL DRIP SHIELD (-060 MODEL)
DRAIN PAN
izontal left-hand discharge operations:
1 - Before operating the unit, remove access panels
and the horizontal drip shield (-060 model) and the
corrugated padding between the blower and coil
assembly. Discard the corrugated padding.
2 - Pull the coil assembly from unit. Pull off the
horizontal drain pan.
3 - Remove the drain plugs from back drain holes on
horizontal drain pan and reinstall them on front
holes.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s)
to verify that drain opening is fully open and free of any
debris. Also check to make sure that no debris has fallen
into the drain pan during installation that may plug up the
drain opening.
4 - Rotate drain pan 180º front-to-back and install it on
the opposite side of the coil.
5 - Remove screws from top cap. Remove horizontal
drip shield screw located in the center of the back
coil end seal as illustrated in gure 4 on page 5.
7 - Remove plastic plug from left hole on coil front
end seal and reinstall plug in back hole. Reinstall
horizontal drip shield screw in front coil end seal.
Drip shield should drain downward into horizontal
drain pan inside coil.
10 - Install the horizontal shield (-060 model) on the
front edge of the horizontal drain pan as illustrated
in gure 5 on page 6.
NOTE – For horizontal applications in high humidity ar-
eas, remove the downow rail closest to the drain pan. To
remove rail, remove screw from rail at back of unit and at
cabinet support rail. Remove downow rail then replace
screws. Also, seal around the exiting drain pipe, liquid and
suction lines to prevent inltration of humid air.
11 - Knock out drain seal plate from access door. Secure
plate to cabinet front ange with screw provided.
12 - Flip access door and replace it on the unit.
13 - Set unit so that it is sloped 1/4ʺ toward the drain
pan end of the unit. Connect return and supply air
plenums as required using sheet metal screws.
14 - If suspending the unit, it must be supported along the
entire length of the cabinet. If using chain or strap,
use a piece of angle iron or sheet metal attached
to the unit (either above or below) so that the full
length of the cabinet is supported. Use securing
screws no longer than 1/2ʺ to avoid damage to coil
or lter, as illustrated in gure 3 on page 5. Connect
return and supply air plenums as required using
sheet metal screws.
DOWNFLOW APPLICATION
NOTE – If downow application is required, separately
order kit number 83M57 and install per kit’s instructions.
Also use metal or class I supply and return air plenums.
Use the installation instruction provided with the downow
kit.
DOWN-FLOW RAILFRONT EDGE OF HORIZONTAL
FIGURE 5. Left-Hand Discharge Conguration
8 - Rotate top cap 180º front-to-back and align with
unused screw holes. Holes must align with front and
back coil end plates. The top cap has a 45º bend on
one side and a 90º bend on the other. The 90º bend
must be on the same side as the horizontal drain
pan as illustrated in gure 4 on page 5.
NOTE – Be very careful when reinstalling the screws into
the coil end plate engaging holes. Misaligned screws may
damage the coil.
9 - From the upow position, ip cabinet 90º to the
left and set into place. Replace blower assembly.
Secure coil in place by bending down the tab on the
cabinet support rail as illustrated in gures 4 and 5.
IMPORTANT
If electric heat section with circuit breakers (ECB29) is
installed in a CBA27UHE unit in a downow application,
the circuit breakers must be rotated 180° to the UP
position. See ECB29 installation instructions for more
details.
Brazing Connections
IMPORTANT
To prevent the build-up of high levels of nitrogen when
purging, it must be done in a well-ventilated area. Purge
low-pressure nitrogen (1 to 2 psig) through the refrigerant
piping during brazing. This will help to prevent oxidation
and the introduction of moisture into the system.
All coils are equipped with a factory-installed, internally
mounted check/expansion valve.
The air handler’s coil line sizes are listed in table 2. Use
Lennox L15 (sweat) series line sets (refer to the outdoor
unit Product Specications (EHB) for proper size, type
and application). For eld-fabricated refrigerant lines, see
the piping section of the Lennox Unit Information Service
Manual.
Page 6
WARNING
Danger of explosion!
Can cause equipment damage, injury, or
death.
When using a high pressure gas such as dry
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9
to 13.8 kPa).
AIR HANDLER UNIT
LIQUID LINE
FIGURE 6. Brazing Connections
NOTE – CBA27UHE series air handlers use nitrogen or
dry air as a holding charge. If there is no pressure when
the rubber plugs are removed, check the coil for leaks
before installing. After installation, pull a vacuum on the
line set and coil before releasing the unit charge into the
system.
NOTE – See outdoor unit instructions on how to ow nitro-
gen through line sets.
1 - Remove access panel.
2 - Remove the refrigerant line caps from the refrigerant
lines.
3 - Use a wet rag to protect TXV sensing bulb (or
remove it) when brazing suction line connections.
4 - Place a wet rag against piping plate and around
the suction line connection. The wet rag must be in
place to guard against damage to the paint.
5 - With the wet rag in place, position a eld provided
elbow tting to the air handler’s suction line and line
set. Start nitrogen ow before brazing.
6 - After the procedure is completed then remove the
wet rag.
7 - Place wet rag against piping plate and around the
liquid line connection. Position liquid line elbow to air
handler’s suction line and to line set. Start nitrogen
ow and begin brazing both connections and after
procedure is completed then remove both wet rags.
8 - Refer to instructions provided with outdoor unit for
leak testing, evacuating and charging procedures.
9 - Install access panel.
TABLE 2. Refrigerant Line Sizes
Model
-018
-024
-030
-036
-042
-048
-060
Liquid
Line
3/8ʺ
(10mm)
3/8ʺ
(10mm)
3/8ʺ
(10mm)
Vapor
Line
3/4ʺ
(19mm)
7/8"
(22mm)
7/8"
(22mm)
Line Sets
L15 line set sizes are
dependant on unit
match-up. See Product
Specications (EHB) for
outdoor unit to determine
correct line set sizes
Field fabricated
Installing the Condensate Drain
MAIN DRAIN
Connect the main drain and route downward to drain line
or sump. Do not connect drain to a closed waste system.
See Figure 8 for typical drain trap conguration.
OVERFLOW DRAIN
It is recommended that the overow drain is connected to
an overow drain line for all units. If overow drain is not
connected, it must be plugged with provided cap.
For downow orientation, the overow drain MUST be
connected and routed to a overow drain line. See Figure 7 for main and overow drain locations based on coil
orientation.
LEFT-HAND AIR
DISCHARGE
OVERFLOW
DRAIN ON LEFT
UP-FLOW OR
DOWN-FLOW
FIGURE 7. Main and Overow Drain Locations
Based on Coil Orientation
BEST PRACTICES
The following best practices are recommended for the
condensate removal process:
• Main and overow drain lines should NOT be smaller
than both drain connections at drain pan.
• Overow drain line should run to an area where home-
owner will notice drainage.
• It is recommended that the overow drain line be vented
and a trap installed. Refer to local codes.
• Condensate drain lines must be congured or provided
with a cleanout to permit the clearing of blockages and
for maintenance without requiring the drain line to be
cut.
RIGHT-HAND AIR
DISCHARGE
MAIN DRAIN ON
RIGHT
Page 7
ABOVE
FINISHED
SPACE?
OVERFLOW DRAIN LINE
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO
ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE
OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN
COMPRESSOR PER INSTRUCTIONS.
NO
YES
LENNOX #
X3169
CLEAN OUT
VENT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
LENNOX
1
P-TRAP
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4”
OVERFLOW
DRAIN
AIR HANDLER DRAIN PA N
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A
3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF
THE AIR HANDLER DRAIN PAN.
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES —
GENERALLY, TWO INCHES (51MM).
DRAIN LINE SHOULD
SLOPE A MINIMUM OF
ONE INCH PER 10
FEET (25MM PER 3
METERS)
NOTE — WHEN A AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE THE SECONDARY
DRAIN PA N MUST HAVE A LARGER FOOTPRINT
THAN THE AIR HANDLER.
MAIN
DRAIN
TO APPROVED
DRAIN
FOR NEGATIVE PRESSURE COILS (BLOWER
AFTER COIL) TRAPS ARE REQUIRED ON ALL
DRAIN LINES CONNECTED TO COIL.
COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE
OBSTRUCTIONS PREVENT DIRECT THREADING
SECONDARY
DRAIN PAN
2”
(51MM)
TRAP DEPTH
1
LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE MAIN DRAIN.
MAIN
DRAIN
PROVIDED
PIPE NIPPLE
2
CUT TO
REQUIRED
LENGTH
SIDE VIEW
Inspecting and Replacing Filters
IMPORTANT
Filter access panel must be in place during unit operation.
Excessive warm air entering the unit may result in water
blow-off problems.
Filters may be duct-mounted or installed in the cabinet. A
lter is installed at the factory. Note that lter access door
ts over access panel. Air will leak if the access panel is
placed over the lter door.
Filters should be inspected monthly and must be cleaned
or replaced when dirty to assure proper air handler operation.
Reusable lters supplied with some units can be washed
with water and mild detergent. Some units are equipped
with standard throw-away type lters which should be replaced when dirty.
To replace lter:
1 - Loosen the thumbscrews holding the lter panel in
place. Remove the dirty lter.
2 - Insert new lter and replace panel.
FIGURE 8. Typical Main and Overow Drain
-018, -024, -030, -03620" x 20" (508mm x 508mm)
CBA27UHEFilter Size – In. (mm)
-042, -048, -06020" x 24" (508mm x 610mm)
Sealing the Unit
There must be an airtight seal between the bottom of
the air handler and the return air plenum. Use berglass
sealing strips, caulking, or equivalent sealing method
between the plenum and the air handler cabinet to
ensure a tight seal. Return air must not be drawn from a
room where this air handler or any gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing
device (i.e., wood replace) is installed.
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water
blow-off problems. This is especially important when the
unit is installed in an unconditioned area.
Page 8
TABLE 3. Filter Dimensions
WARNING
Make sure the liquid line and suction line entry points are
sealed with either the provided exible elastomeric thermal insulation, or eld provided material (e.g. Armaex,
Permagum or equivalent). Any of the previously mentioned materials may be used to seal around the main and
auxiliary drains, and around open areas of electrical inlets.
Measuring Static Pressure
1 - Measure tap locations as shown in gure 9.
MANOMETER
SUPPLY
RETURN
These settings are for nominal tonnage match-ups with
the CBA27UHE units. When matched with other sizes, it is
recommended that the CFM be adjusted to approximately
400 CFM per ton.
To change blower motor speed tap remove the speed tap
from Y2 on the terminal strip and insert the desired speed
tap. Use the Blower Data tables on pages 10 and 11 for
the desired CFM setting.
IMPORTANT
The high-efciency programmable motor features
programmed electronic braking. The integral control
brakes the motor near the end of the supply blower
operation, allowing the motor to maintain a more
controlled ramping shut-down.
HORIZONTAL DISCHARGE LEFT POSITION
UNIT SHOWN IN
FIGURE 9. Static Pressure Test
2 - Punch a 1/4ʺ (6mm) diameter hole in supply and
return air plenums. Insert manometer hose ush
with inside edge of hole or insulation. Seal around
the hose with permagum. Connect the zero end of
the manometer to the discharge (supply) side of
the system. On ducted systems, connect the other
end of manometer to the return duct as above. For
systems with non-ducted returns, leave the other
end of the manometer open to the atmosphere.
3 - With only the blower motor running and the
evaporator coil dry, observe the manometer reading.
Adjust blower motor speed to deliver the air desired
according to the job requirements.
4 - For best air performance external static pressure
drop must not exceed 0.5" W.C. (1.2 kPa). Refer to
blower data tables for CFM and external static.
5 - Seal around the hole when the check is complete.
Adjusting Blower Speed
MOTOR SPEED TAPS
NOTE – Motor is programmed for a 45-second delayed
OFF on all speed taps except TAP #1 (continuous fan
speed).
Table 4 lists the recommended factory blower speed tap
selections for CBA27UH series units.
TABLE 5. Motor Speed Taps
Tap OperationRemarks
Continuous fan speed is
Continuous or
low-speed fan (for
1
two-speed heat
pumps or AC units)
Low-speed
operation on
2
high-static
system
Cooling speed
3
setting
Heat pump with
4
electric heat
High-static
5
applications
energized (24volt input to G)
when either G or Y1 has a 24
volt signal (24 volt input from
Y1 passes through the room
thermostat’s Fan Automatic
contacts to the G terminal).
CFM set at 1/2 ton less than
nominal of unit (e.g. 3-ton set at
1000 CFM).
CFM set at 400 cfm per nominal
ton at ARI minimum static
allowed, as follows:
1.5 to 2.0 ton - 0.10
2.5 to 3.5 ton - 0.15
4 to 5 ton - 0.20
CFM set at 400 cfm per nominal
ton at .4 static. Energized when
electric heat element has a call
for heat.
Ground unit at disconnect switch or to an earth ground.
cuit connections are made in
t
Install room thermostat (ordered separately) on an inside wall
in the center of the conditioned area and 5 feet (1.5m)
It should not be installed on an outside wall or where it
WARNING
Run 24V Class II wiring only through specied low
voltage opening. Run line voltage wiring only through
specied high voltage opening. Do not combine voltage
in one opening.
NOTE – Connect conduit to the unit using a proper conduit tting. Units are approved for use only with copper
conductors. A complete unit wiring diagram is located on
the back side of the unit’s access panel.
3 - Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit.
NOTE – For proper voltages, select thermostat wire gauge
per the following chart:
CAUTION
USE COPPER CONDUCTORS ONLY.
This unit is provided with knock-outs for conduit. Refer
to gure 11 on page 13 for unit wiring diagram, which includes all eld wiring. Separate openings have been pro-
vided for 24V low voltage and line voltage. Refer to the
dimension illustration on page 2 or 3 for specic location.
Wiring must conform to the current National Electric Code
ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA
Standard C22.1, and local building codes. Refer to following wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
Select the proper supply circuit conductors in accordance
with tables 310-16 and 310-17 in the National Electric
Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.
The motor speed is set by the speed tap connection to
the low voltage terminal strip in the control section. The
speed can be increased by swapping wires as shown in
gure 11.
WIRING CONNECTIONS
1 - Install line voltage power supply to unit from a
properly installed circuit breaker.
2 - Ground unit at unit disconnect switch or to an earth
ground.
TABLE 6. Run Length (Class II Rated Wiring)
Wire Run LengthAWG # Insulation / Core Types
Less than 100' (30m)18
More than 100' (30m)16
approximately
from the floor.
can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
he control panel.
NOTE — Units are approved for use only with copper conductors.
Color coded, temperature
rating 95°F (35°C)
minimum, solid core
FIGURE 10. Thermostat Installation
Page 12
FIGURE 11. Typical System Wiring Diagram
Page 13
FIGURE 12. Typical System Wiring Diagram – 460V, Single- and Three-Phase Units (-036, -048 and -060 only)
Page 14
Repairing or Replacing Cabinet Insulation
IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR
REPLACED before the unit is put back into operation.
Insulation loses its insulating value when wet, damaged,
separated or torn.
Matte- or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air conditions
(surrounding ambient temperature and humidity) and the
varying conditions inside the unit. If the insulation barrier
is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet. The temperature/
humidity difference between the inside and outside of the
cabinet can cause condensation on the inside or outside
of the cabinet which leads to sheet metal corrosion and
subsequently, component failure.
REPAIRING DAMAGED INSULATION
Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled
open, glued with an appropriate all-purpose glue and
placed back against the cabinet surface, being careful to
not overly compress the insulation so the insulation can
retain its original thickness. If such repair is not possible,
replace the insulation. If using foil-faced insulation, any
cut, tear, or separations in the insulation surface must be
taped with a similar foil-faced tape.
GLUE - Make sure there is
full coverage of glue on the
metal or insulation so there
are no areas where air
pockets may form which
can lead to sweating.
WARNING
Electric Shock Hazard.
Can cause injury or death.
Foil-faced insulation has conductive
characteristics similar to metal. Be sure there
are no electrical connections within 1/2ʺ
of the insulation. If the foil-faced insulation
comes in contact with electrical voltage, the
foil could provide a path for current to pass
through to the outer metal cabinet. While
the current produced may not be enough to
trip existing electrical safety devices (e.g.,
fuses or circuit breakers), the current can be
enough to cause an electrical shock hazard
that could cause personal injury or death.
Homeowner Maintenance
IMPORTANT
Do not operate system without a lter. A lter is required
to protect the coil, blower, and internal parts from
excessive dirt and dust. The lter is placed in the return
duct by the installer.
• Inspect air lters at least once a month and replace or
clean as required. Dirty lters are the most common
cause of inadequate heating or cooling performance.
• Replace disposable lters. Cleanable lters can be
cleaned by soaking in mild detergent and rinsing with
cold water.
• Install new/clean lters with the arrows on the side point-
ing in the direction of air ow. Do not replace a cleanable (high velocity) lter with a disposable (low velocity)
lter unless return air system is properly sized for it.
• If water should start coming from the secondary drain
line, a problem exists which should be investigated and
corrected. Contact a qualied service technician.
Professional Maintenance
1. CUT INSULATION IN X PATTERN
2. APPLY GLUE
3. PRESS GLUED TABS AGAINST CABINET
FIGURE 13. Repairing Insulation
NOTICE !
Failure to follow instructions will cause damage to
the unit.
This unit is equipped with an aluminum coil.
Aluminum coils may be damaged by exposure to
solutions with a pH below 5 or above 9. The aluminum coil should be cleaned using potable water
at a moderate pressure (less than 50psi). If the
coil cannot be cleaned using water alone, Lennox
recommends use of a coil cleaner with a pH in the
range of 5 to 9. The coil must be rinsed thoroughly
after cleaning.
In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corrosive buildup (salt).
Page 15
Check-out Procedures
IMPORTANT
During installation, service or maintenance, make sure
that copper tubing does not rub against metal edges
or other copper tubing. Care should also be taken to
ensure that tubing does not become kinked. Use wire
ties to secure tubing to prevent movement.
Do not secure electrical wires to tubing that carries hot
refrigerant gas. Heat from the tubing may melt the wiring
insulation, causing a short circuit.
NOTE – Refer to outdoor unit installation instructions for
system start-up instructions and refrigerant charging instructions.
PRE-START-UP CHECKS
• Is the air handler properly and securely installed?
• If horizontally congured, is the unit sloped up to 1/4
inch toward drain lines?
• Will the unit be accessible for servicing?
• Has an auxiliary pan been provided under the unit with
separate drain for units installed above a nished ceiling or in any installation where condensate overow
could cause damage?
• Have ALL unused drain pan ports been properly
plugged?
• Has the condensate line been properly sized, run,
trapped, pitched, and tested?
• Is the duct system correctly sized, run, sealed, and insulated?
• Have all cabinet openings and wiring been sealed?
• Is the indoor coil factory-installed TXV properly sized for
the outdoor unit being used?
• Have all unused parts and packaging been disposed
of?
• Is the lter clean, in place, and of adequate size?
• Is the wiring neat, correct, and in accordance with the
wiring diagram?
• Is the unit properly grounded and protected (fused)?
• Is the thermostat correctly wired and in a good location?
• Are all access panels in place and secure?
CHECK BLOWER OPERATION
• Set thermostat to FAN ON.
• The indoor blower should come on.
CHECK COOLING OPERATION
• Set thermostat to force a call for cooling (approximately
5ºF lower than the indoor ambient temperature).
• The outdoor unit should come on immediately and the
indoor blower should start between 30 - 60 seconds later.
• Check the air ow from a register to conrm that the
system is moving cooled air.
• Set the thermostat 5ºF higher than the indoor temperature. The indoor blower and outdoor unit should cycle
off.
CHECK ELECTRIC HEAT (IF USED)
• Set thermostat to call for auxiliary heat (approximately 5°F above ambient temperature). The indoor blower and auxiliary heat should come on together. Allow a
minimum of 3 minutes for all sequencers to cycle on.
• Set the thermostat so that it does not call for heat. Allow
up to 5 minutes for all sequencers to cycle off.
Use of Air Handler During Construction
Lennox does not recommend the use of its air handler unit
during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with
clogged or misplaced lters will damage the unit.
Air handler units may be used for heating (heat pumps)
or cooling of buildings under construction, if the following
conditions are met:
• A room thermostat must control the air handler. The use
of xed jumpers is not allowed.
• Air lter must be installed in the system and must be
maintained during construction.
• Air lter must be replaced upon construction comple-
tion.
• The air handler evaporator coil, supply fan assembly
and duct system must be thoroughly cleaned following
nal construction clean-up.
• All air handler operating conditions must be veried ac-
cording to these installation instructions.