Lennox CBA25UH Installation Instructions Manual

INSTALLATION
©2017 Lennox Industries Inc. Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTRUCTIONS
Merit® Series CBA25UH Air Handler Units
MULTI-POSITION AIR HANDLERS 507751-01 12/2017
Table of Contents
Shipping and Packing List .............................................1
CBA25UH Unit Dimensions – Upow – Inches (mm) ..... 2
General Information ....................................................... 3
Requirements ................................................................3
Installation Clearances ..................................................4
Installation .....................................................................4
Condensate Drain...........................................................7
Duct System and Filters ...............................................8
Brazing Refrigerant Lines .............................................. 9
Sealing the Unit ...........................................................12
Electrical Connections ................................................. 12
Air Flow – Cooling Blower Speed ................................ 15
Check-out Procedures ................................................. 16
Operation .................................................................... 17
Homeowner Maintenance ............................................17
Repairing or Replacing Cabinet Insulation .................. 18
Professional Maintenance ...........................................18
Use of Air Handler During Construction .......................18
Shipping and Packing List
Package 1 of 1 contains:
1 – Assembled air handler unit factory-equipped for upow
or horizontal air discharge application (includes upow
and horizontal drain pans and preinstalled air lter).
Check the air handler for shipping damage; if found, im­mediately contact the last carrier. Check the unit rating
plate to conrm that delivered unit matches order.
IMPORTANT: Special procedures are required for clean­ing the all-aluminum coil in this unit. See page 18 in this instruction for information.
IMPORTANT INFORMATION FOR INSTALLER
This unit has a delay relay that delays the supply blower “ON” for 1 second and keeps the blower “ON” for 45
seconds on all fan and cooling demands. For more details, refer to page 17 for unit sequence of operation.
1
1
SECOND
DELAY
34
100%
2
CFM
COOLING
DEMAND
Page 1
100%
CFM
45
SECS
OFF
CBA25UH Unit Dimensions – Upow – Inches (mm)
(Top and Left Side)
8
1 (25)
DETAIL OF PIPING PLATE
1 (25)
LINE VOLTAGE
INLETS
3/4
(19)
14-1/2
(368)
TOP VIEW
CIRCUIT
BREAKER
COVER
SUPPLY AIR
OPENING
C
B
1 (25)
LOW VOLTAGE
INLETS
(Top and Right Side)
2-3/8
(60)
4-3/8 (111)
LINE VOLTAGE
INLETS
(Top and Right Side)
LOW VOLTAGE
INLETS
(Either Side)
3/4 (19)
SUCTION
LINE
LIQUID
LINE
2-3/4
(70)
1-3/4
(44)
4-3/4
(121)
CONDENSATE
DRAINS (2) (Horizontal)
CONDENSATE
DRAINS (2) (Upflow and
Downflow)
3-1/2
(89)
22
(559)
A
1-1/8
(29)
AIR FLOW
PIPING
PLATE
D
OPENING
CONDENSATE DRAIN
PIPING PLATE (3)
(2-1/4 x 3-3/4)
FILTER ACCESS
1-1/8
(29)
SUCTION
LINE
LIQUID
LINE
1/2
(13)
20-3/8
(518)
OPENING
FRONT VIEW SIDE VIEW
1-1/
(29)
Page 2
General Information
The CBA25UH series air handler with all-aluminum coil is designed for indoor installation only. As shipped,
the unit is ready for installation in either upow, horizontal
left-hand or right-hand air discharge applications. Electric heat, downow air discharge kits, air lters and other ac­cessories are available and listed in the CBA25UH Prod- uct Specication bulletin for ordering.
This instruction is intended as a general guide and does not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Requirements
Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instruc­tions in this manual.
Install the conditioned air plenum, ducts and air lters
(provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Sys­tems (latest edition).
The air handler is shipped from the factory completely as­sembled. The unit is provided with anges for the connec­tion of the duct system.
Do not remove the cabinet knockouts until it has been de­termined which knockouts will need to be removed for the installation.
Select the air discharge position which best suits the site conditions. Consider required clearances, space, routing requirements for refrigerant line, condensate disposal,
lters, duct system, wiring, and accessibility for service. Refer to the rating plate on the air handler for specic in-
formation.
WARNING
Excessive Weight Hazard - Use two or more people when moving and installing the unit. Failure to do so can result in back or other type of injury.
IMPORTANT
CBA25UH units include a factory-installed check/ expansion valve which will provide optimal refrigerant control and system performance with outdoor units of varying capacities. These units must be installed as a part of a matched system as outlined in the CBA25UH
Product Specication bulletin.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
Compliance with all local, state, or national codes pertain­ing to this type of equipment should be determined prior to installation. Read this instruction manual, as well as the instructions supplied in separate equipment, before start­ing the installation.
In addition to conforming to manufacturer’s installation in­structions and local municipal building codes, installation of Lennox air handler units (with or without optional elec­tric heat), MUST conform with National Fire Protection As­sociation (NFPA) standards: “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA No. 90A) and “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA No. 90B).
All models are designed for indoor installation only. The
installation of the air handler, eld wiring, duct system, etc.
must conform to the requirements of the National Electri­cal Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (includ­ing plumbing or waste water codes).
WARNING
Danger of explosion. Keep ammable
materials and vapors, such as gasoline, away from air handler. Place air handler so that heating elements are at least 18 inches (46
cm) above the oor for a garage installation.
Failure to follow these instructions can result
in death, explosion, or re.
IMPORTANT
Excessive condensation may occur if the unit is installed in a warm, humid place. When the unit is installed in an unconditioned space, apply sealant around electrical wires, refrigerant piping and condensate lines at the point where they enter the cabinet.
Apply sealant on the inside of the cabinet at the point where the electrical wires exit through the conduit opening. This will also keep warm and moist unconditioned air out of the air handler cabinet where it will form condensate on the cooler control box and electrical controls.
IMPORTANT
This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances.
The air handler must be installed so that free access is
allowed to the coil/lter compartment and blower/control
compartment.
Page 3
NOTES –
During cooling operation, excessive sweating may occur if the air handler is installed in a warm and humid space.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
Electrical wires should be sealed on the inside where they exit the conduit opening. Sealant is required to prevent air leakage into, and condensate from forming inside of, the air handler, the control box, and on the electrical controls.
This unit is approved for installation clearance to combus­tible material as stated on the unit rating plate. Accessi­bility and service clearances must take precedence over combustible material clearances.
The air handler must be installed so that free access is allowed to the coil/lter compartment and blower/control compartment.
Installation Clearances
NON-DUCTED RETURN CLOSET INSTALLATION
The air handler can be installed in a closet with a false bottom to form a return air plenum. It may also be installed with a return air plenum under the air handler.
Louvers or return air grilles are eld-supplied. Local codes
may limit application of systems without a ducted return to single-story buildings.
When a CBA25UH unit is installed in a closet with a lou­vered return opening, the minimum open area for the lou­vers will be:
• 320 square inches for -018 and -024 models;
• 360 square inches for -030 and -036 models;
• 450 square inches for -042 thru -060 models
If the free area is not known, assume a 25% free area for wood or a 75% free area for metal louvers or grilles. Using the louver dimensions and the 25% or 75% assumption, determine if the open area meets the minimum open area listed above.
If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow
for the free ow of return air. When not installed in front of
the opening, there must be adequate clearance around
the air handler to allow for the free ow of return air.
Installation
Each unit consists of a blower assembly, refrigerant coil, and controls in an insulated galvanized steel factory-n­ished enclosure. Knockouts are provided for electrical wir­ing entrance.
For ease in installation, it is best to make any necessary
coil conguration changes before setting air handler in
place.
REFRIGERANT METERING DEVICE
CBA25UH units are equipped with a factory-installed check/ expansion valve.
UPFLOW APPLICATION
1 - The air handler must be supported on the bottom
only and set on solid oor or eld-supplied support frame. Securely attach the air handler to the oor or
support frame.
2 - If installing a unit in an upow application, remove
the horizontal drain pan. IMPORTANT - The
horizontal drain pan is not required in upow
air discharge installations; its removal provides
the best efciency and air ow.
3 - Place the unit in the desired location and slope unit.
Connect return and supply air plenums as required using sheet metal screws.
4 - Install units that have no return air plenum on a
stand that is at least 14" from the oor. This will
allow proper air return.
HORIZONTAL DRAIN PAN (MUST BE REMOVED)
UP-FLOW / DOWN-FLOW DRAIN PAN
FIGURE 1. Upow Conguration
HORIZONTAL APPLICATIONS
IMPORTANT
When removing the coil, there is a possibility of danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right- or left-hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it..
NOTE - When the unit is installed in horizontal applica­tions, a secondary drain pan is recommended. Refer to local codes.
NOTE - This unit may be installed in left-hand or right­hand air discharge horizontal applications. Adequate sup­port must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove service and access panels if installing in the horizontal position.
Page 4
RIGHT-HAND DISCHARGE
FRONT WEIV DNEWEIV
ANGLE IRON OR SHEET
E
RE
1 - Determine which plugs are required for drain line
connections.
2 - With access door removed, remove drain line plugs
to install drain lines.
3 - Set unit so that it is sloped toward the upow drain
pan end of the unit and level from front to back of
unit (see gure 7).
4 - The horizontal conguration is shown in gure 2.
AIR FLOW
Drains
RIGHT‐HAND DRAINS
PLUGS
FIGURE 2. Right-Hand Discharge Conguration
5 - If the unit is suspended, the entire length of the
cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2 inch to avoid damaging
the coil or lter. See gure 3. Use sheet metal
screws to connect the return and supply air plenums as required.
METAL
MAXIMUM 1/2" LONG SCREW
ANCE 4 IN. (102 MM)
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into the drain pan during installation that may plug up the drain opening.
4 - Rotate drain pan 180º front-to-back and install it on
the opposite side of the coil.
5 - Remove screws from top cap. Remove horizontal
drip shield screw located in the center of the back
coil end seal as illustrated in gure 4.
6 - Rotate horizontal drip shield 180º front-to-back.
7 - Remove plastic plug from left hole on coil front
end seal and reinstall plug in back hole. Reinstall horizontal drip shield screw in front coil end seal. Drip shield should drain downward into horizontal drain pan inside coil.
TOP CAP ROTATED TO CORRECT POSITION
TOP CAP SCREWS
DRAIN PAN
SHIPPING
LOCATION
CABINET
SUPPORT
DRAIN PAN
INSTALLED
HERE
DRIP
SHIELD
90º
BEND
LEFT-HAND AIR DISCHARGE
For horizontal left-hand air discharge, the following eld modications are required.
1 - Remove access panels and the horizontal drip
2 - Pull the coil assembly from unit. Pull off the
3 - Remove the drain plugs from back drain holes on
AIR FLOW
FIGURE 3. Suspending Horizontal Unit
shield (-060 model) and the corrugated padding between the blower and coil assembly. Discard the corrugated padding.
horizontal drain pan.
horizontal drain pan and reinstall them on front holes.
REINSTALLED HERE REMOVED FROM HERE
COIL SHOWN IN UPLOAD POSITION FOR EASY CONVERSION
TOP CAP
90º
BEND
———— DRAIN PLUGS ————
ALIGN HOLES WITH HOLES IN COIL END PLATE. STARTING WITH THE ROUND HOLES ON THIS END.
BACK COIL END SEAL
FIGURE 4. Field Modication for
Left-Hand Discharge
8 - Rotate top cap 180º front-to-back and align with
unused screw holes. Holes must align with front and back coil end plates. The top cap has a 45º bend on one side and a 90º bend on the other.
The 90º bend must be on the same side as the
horizontal drain pan as illustrated in gure 4.
Page 5
HORIZONTAL DRIP SHIELD (-060 MODEL)
DOWN-FLOW RAIL FRONT EDGE OF HORIZONTAL
DRAIN PAN
FIGURE 5. Left-Hand Discharge Conguration
NOTE – Be very careful when reinstalling the screws into the coil end plate engaging holes. Misaligned screws may damage the coil.
9 - From the upow position, ip cabinet 90º to the
left and set into place. Replace blower assembly. Secure coil in place by bending down the tab on the cabinet support rail as illustrated.
10 - Install the horizontal shield (-060 model) on the
front edge of the horizontal drain pan as illustrated
in gure 5.
NOTE – For horizontal applications in high humidity ar- eas, remove the downow rail closest to the drain pan. To remove rail, remove screw from rail at back of unit and at cabinet support rail. Remove downow rail then replace screws. Also, seal around the exiting drain pipe, liquid and suction lines to prevent inltration of humid air.
11 - Knock out drain seal plate from access door. Secure
plate to cabinet front ange with screw provided.
12 - Flip access door and replace it on the unit.
13 - Set unit so that it is sloped 1/4ʺ toward the drain
pan end of the unit. Connect return and supply air plenums as required using sheet metal screws.
14 - If suspending the unit, it must be supported along the
entire length of the cabinet. If using chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) so that the full length of the cabinet is supported. Use securing
screws no longer than 1/2ʺ to avoid damage to coil or lter, as illustrated in gure 3. Connect return and
supply air plenums as required using sheet metal screws.
DOWNFLOW APPLICATION
NOTE – If downow application is required, separately order kit number 83M57 and install per kit’s instructions. Also use metal or class I supply and return air plenums.
Use the installation instruction provided with the downow kit.
IMPORTANT
If electric heat section with circuit breakers (ECB29/
ECB31) is installed in a CBA25UH unit in a downow
application, the circuit breakers must be rotated 180° to the UP position. See ECB29/ECB31 installation instructions for more details.
Page 6
Condensate Drain
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE MAIN DRAIN.
THIS CORNER SHOULD BE 5/8" (+/- 1/8") HIGHER
IMPORTANT
On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.
ABOVE
FINISHED
SPACE?
YES
NOTE — WHEN A AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE THE SECONDARY DRAIN PA N MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.
SECONDARY
DRAIN PAN
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE AIR HANDLER DRAIN PAN.
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES — GENERALLY, TWO INCHES (51MM).
1
LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.
LENNOX #
COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
NO
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING
AIR HANDLER DRAIN PA N
OVERFLOW
DRAIN
OVERFLOW DRAIN LINE
X3169
MAIN
DRAIN
MAIN
DRAIN
CUT TO
REQUIRED
LENGTH
PROVIDED
PIPE NIPPLE
SIDE VIEW
2
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
CLEAN OUT
PRESS IN
(DO NOT GLUE)
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
1
P-TRAP
LENNOX
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4”
FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL) TRAPS ARE REQUIRED ON ALL DRAIN LINES CONNECTED TO COIL.
VENT
2”
(51MM)
TRAP DEPTH
TO APPROVED
DRAIN
DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)
FIGURE 6. Typical Main and Overow Drain
IMPORTANT
THAN DRAIN CORNER
A eld-fabricated secondary drain pan, with a drain pipe
to the outside of the building, is required in all installations
over a nished living space or in any area that may be damaged by overow from the main drain pan. In some
localities, local codes may require a secondary drain pan for any horizontal installation.
SLOPING THE UNIT
Make sure the unit is sloped (similar to the slope shown in gure 7) so that the drain pan will empty completely with-
DRAIN CORNER
out water standing in the pan.
FIGURE 7. Sloping the Unit for Proper Drainage
Page 7
LEVEL PLANE
INSTALL CONDENSATE DRAIN
ALL CBA25UH MODELS
DRAIN PLUG
DRAIN PLUG
The air handler is provided with 3/4" NPT condensate drain connections.
IMPORTANT
On some pans, the primary and secondary drain holes have knockouts.
Conrm primary and secondary drains are open.
1 - CBA25UH units are equipped with a drain pan, which
includes green (main drain) and red (secondary drain) plugs. Unscrew the plugs to remove them
before inserting condensate drain ttings.
UNSCREW PLUGS
AND CONNECT PROPERLY SIZED FIELD-PROVIDED
FITTINGS AND
DRAIN LINES.
DRAIN PAN
GREEN MAIN
FIGURE 8. Drain Line Connections
2 - Install properly sized, eld-provided connection
ttings and connect primary drain line to the main
drain pan connection.
NOTE - When installing drain line connection ttings to the drain pan, hand tighten the tting and use a thread sealant. Over-tightening the ttings can split connections on the drain pan.
3 - If the secondary drain line is to be used, remove the
plug or the knockout and route the drain line so that water draining from the outlet will be easily noticed by the homeowner. Refer to local codes for drain trap requirements on the secondary drain line.
4 - Check again to ensure drain ports and drain pan
are free of all debris.
5 - Plug and check any unused drain pan openings for
tightness. Torque plugs to 30 in. lb. to prevent water leaks or seepage from the drain pan.
6 - Install a 2" trap in the main (primary) drain lines as
close to the unit as practical (see gure 6). Make
sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.
NOTE - Horizontal runs must have an anti-siphon air vent (standpipe) installed ahead of the horizontal run. See g­ure 6. An extremely long horizontal run may require an oversized drain line to eliminate air traps.
NOTE - Do not operate air handler without a trap in the main (primary) drain. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will not allow positive drainage without a proper trap.
7 - Route the drain line to the outside or to an
appropriate drain. Drain lines must be installed so they do not block service access to the front of the
air handler. A 24" clearance is required for lter, coil,
or blower removal and service access.
RED SECONDARY
NOTE - Check local codes before connecting the drain line to an existing drainage system. Insulate the drain lines where sweating could cause water damage.
TEST CONDENSATE DRAIN
Test the drain pan and drain line after installation:
1 - Pour several quarts of water into drain pan. Use
enough water to ll both the drain trap and the line.
2 - Check the installed drain pan. Drain pan must be
draining completely. Drain line ttings must not be
leaking. Water must be draining from the end of the primary drain line.
3 - Correct any leaks found.
Duct System and Filters
DUCT SYSTEM
The air handler is provided with anges for the connection
of the supply plenum. Supply and return duct system must be adequately sized
to meet the system’s air requirements and static pressure capabilities. The duct system should be insulated with a minimum of 1" thick insulation with a vapor barrier in con­ditioned areas or 2" minimum in unconditioned areas.
Supply plenum should be the same size as the anged
opening provided around the blower outlet and should ex­tend at least 3 ft. from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expan­sion losses from the blower.
FILTERS
A lter is provided. Table 1 lists the lter size for each unit.
TABLE 1. Unit Air Filter Size Chart
CBA25UH Filter Size – In.
-018, -024, -030 15" x 20" x 1"
-036, -042, -048, -060 18" x 20" x 1"
IMPORTANT
If a high efciency lter is being installed as part of this system to ensure better indoor air quality, the lter must be properly sized. High efciency lters have a higher static pressure drop than standard efciency glass/foam lters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service
calls. Before using any lter with this system, check the specications provided by the lter manufacturer
against the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002 (August 2000)..
Page 8
INSTALLING DUCT SYSTEM
Cabinet and Duct Flange
Connect supply air duct to the ange on top of the air han­dler. If an isolation connector is used, it must be nonam-
mable.
FIELD-FABRICATED RETURN AIR DUCT FLANGE
FOR HORIZONTAL APPLICATIONS
A return air duct system is recommended, but not facto-
ry-provided. If the unit is installed in a conned space or
closet, run a full-size return connection to a location out­side the closet.
CABINET DOOR FLANGE
1−1/2
(38)
WARNING
Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING
Danger of re. Bleeding the refrigerant
charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before applying heat.
DUCT FLANGE
3/4
(19)
1−1/2(38)
3/4
(19)
”A”
BRAKE DOWN 90 DEGREES
1/2
(13)
UNIT SIZE
-018, -024,
-030
-036, -042,
-048, -060
3/4
(19)
1/4 (6) DIA.
2−HOLES
"A"
18-3/8"
21-1/2"
BOTTOM OF CABINET
DUCT ADAPTER
3/4
(19)
1−1/2
(38)
FIGURE 9. Cabinet and Duct Flange
Brazing Refrigerant Lines
Refrigerant lines must be connected by a qualied techni­cian in accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dry, refrigerant-grade copper lines. Air handler coils should be installed
only with specied line sizes for approved system
combinations. Handle the refrigerant lines gently during the installation
process. Sharp bends or kinks in the lines will cause a restriction.
Do not remove the caps from the lines or system connection points until connections are ready to be completed.
WARNING
When using a high pressure gas such as nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and ux contain materials which are
hazardous to your health. Avoid breathing vapors or fumes from brazing operations.
Perform operations only in well-ventilated areas. Wear gloves and protective goggles or face shield to
protect against burns. Wash hands with soap and water after handling brazing
alloys and ux.
IMPORTANT
To prevent the build-up of high levels of nitrogen when purging, it must be done in a well-ventilated area. Purge low-pressure nitrogen (1 to 2 psig) through the refrigerant piping during brazing. This will help to prevent oxidation and the introduction of moisture into the system.
Page 9
NOTE - When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fab­rication Guidelines, CORP. 9351-L9, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following information: Model and capac­ity.
1 - Route the suction and liquid lines from the ttings
on the indoor coil to the ttings on the outdoor unit.
Run the lines in a direct path, avoiding unnecessary turns and bends.
2 - Make sure that the suction line is insulated over the
entire exposed length and that neither suction nor
liquid lines are in direct contact with oors, walls, duct system, oor joists, or other piping.
3 - To avoid damaging the rubber grommets in the
cabinet while brazing, slide the rubber grommets over the refrigerant lines until they are away from the heat source.
NOTE - Place wet rags against piping plate and around suction line connections.
4 - Connect the suction and liquid lines to the evaporator
coil. Take care to protect the cabinet and internal
components as detailed in gure 10.
5 - Braze using an alloy of silver or copper and
phosphorus with a melting point above 1,100°F (593°C).
NOTE - Do not use soft solder.
6 - Allow refrigerant pipes to cool to room temperature.
NOTE - Make sure to route copper refrigerant tubing away from sharp edges and make sure that it does not touch other metal surfaces. This prevents damage caused by vibration or metal-on-metal contact.
7 - Reinstall the rubber grommets into the refrigerant
piping panel.
NOTE - Make sure expansion valve capillary tube is not touching metal edges or copper tubing.
8 - Make sure outdoor unit has been placed according
to the Installation Instructions and is connected to the refrigerant lines
Page 10
PROCEDURES
PLEASE READ IMPORTANT ISSUES CONCERNING BRAZING
OPERATIONS ON PREVIOUS PAGES BEFORE PROCEEDING.
p
NOTE - REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR REFRIGERANT PIPING SIZE REQUIREMENTS.
NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing, 45
ercent alloy for copper-to-brass and copper-to-steel
brazing.
REMOVE ACCESS PANEL
A
REMOVE RUBBER PLUG FROM BOTH LIQUID
B
AND SUCTION LINES
NOTE - CBA25UH SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE. IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED, CHECK THE COIL FOR LEAKS BEFORE INSTALLING.
EITHER REMOVE OR PUSH PIPE WRAPPING BACK
C
THROUGH HOLE IN PIPING PLATE BEFORE LINE SET CONNECTION AND BRAZING.
LOW
HIGH
PIPING PLATE
CONNECT PIPES
D
NOTE - REFRIGERANT LINE SETS SHOULD BE ROUTED TO ALLOW FILTER ACCESSIBILITY.
PLACE A WET RAG AGAINST PIPING
F
PLATE AND AROUND THE SUCTION LINE CONNECTION.
BRAZE CONNECTION. ALLOW PIPE TO
G
COOL BEFORE REMOVING WET RAG FROM CTXV SENSING BULB AND PIPING PANEL AREA.
REPEAT PREVIOUS PROCEDURE FOR LIQUID
H
LINE.
CONNECT GAUGES AND
E
START NITROGEN FLOW
FLOW REGULATED NITROGEN (AT 1 TO 2 PSIG) THROUGH THE REFRIGERATION GAUGE SET INTO THE VALVE STEM PORT CONNECTION ON THE OUTDOOR UNIT LIQUID LINE SERVICE VALVE AND OUT OF THE VALVE STEM PORT CONNECTION ON THE SUCTION SERVICE VALVE.
REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING, EVACUATING AND CHARGING
NITROGEN
FIGURE 10. Brazing Connections
Page 11
Sealing the Unit
Seal the unit so that warm air is not allowed into the cabi­net. Warm air introduces moisture, which results in water blow-off problems. This is especially important when the unit is installed in an unconditioned area.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
WARNING
There must be an airtight seal between the bottom of
the air handler and the return air plenum. Use berglass
sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide-producing
device (i.e., wood replace) is installed.
IMPORTANT
Use duct tape and/ or Permagum to seal closed any space around the holes where the drain lines exit the cabinet. Warm air must not be allowed to enter through any gaps or holes in the cabinet.
Electrical Connections
WARNING
Electric Shock Hazard. Can cause injury or death. Foil-faced insulation has conductive
characteristics similar to metal. Be sure there
are no electrical connections within 1/2ʺ
of the insulation. If the foil-faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g., fuses or circuit breakers), the current can be enough to cause an electrical shock hazard that could cause personal injury or death.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single­pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
WARNING
Electric shock hazard! - Disconnect all power supplies before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
WARNING
Run 24V Class II wiring only through specied low
voltage opening. Run line voltage wiring only through
specied high voltage opening. Do not combine voltage
in one opening.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
• Wiring must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to following wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum over-cur­rent protection size.
• Electrical wiring, disconnect means and over-current pro­tection are to be supplied by the installer. Refer to the air handler rating plate for maximum over-current protection, minimum circuit ampacity, as well as operating voltage. Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.
• The power supply must be sized and protected accord-
ing to the specications supplied on the product.
This air handler is factory-congured for 240 volt, single phase, 60 cycles. For 208-volt applications, see “208 Volt Conversion” later in this section.
• Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension illustra-
tion of specic location.
• This unit is provided with holes for conduit. Use provid­ed caps to seal holes not used.
Typical unit wiring (as well as wiring of optional eld-in-
stalled electric heat) is given in gure 14. Refer to the
instructions provided with the electric heat section for proper installation.
Page 12
WARNING
208 / 240 VOLT TRANSFORMER
USE COPPER CONDUCTORS ONLY
1 - Disconnect all power supplies.
2 - Remove the air handler access panel.
3 - Route the eld supply wires to the air handler
electrical connection box.
4 - Use UL-listed wire nuts to connect the eld supply
conductors to the unit black and yellow leads, and the ground wire to ground terminal marked GND.
5 - 5. Replace the air handler access panel.
TOP
208 VOLT CONVERSION
1 - Disconnect all power supplies.
2 - Remove the air handler access panel.
3 - Using the wiring diagram located on the unit access
panel as a reference, move the 2 connected black transformer leads from the 240 volt terminal on the transformer to the 208 volt terminal on the transformer.
WARNING
Electrically ground air handler. Connect ground wire to ground terminal marked “GND”.
Failure to do so can result in death or electrical shock.
PRIMARY SECONDARY
240 Volts
208 Volts
SIDE
FIGURE 11. Electrical Connections
(Upow Conguration)
NOTE - To avoid the possibility of moisture damage to the control in some right-hand discharge congurations, the control panel can be relocated to the end panel as shown in gure 12.
TOP
FIGURE 13. Converting Unit from 240VAC to 208VAC
SIDE
FIGURE 12. Control Panel Relocated to End Panel
(Left-Hand Horizontal Conguration)
Page 13
FIGURE 14. Typical Wiring Diagram – CBA25UH Air Handler with Electric Heat
Page 14
AIR HANDLERTHERMOSTAT
NOTE - Connect common wire only if required (Refer to the appropriate thermostat installation instructions).
SEE
NOTE
R
G
BU
Y
AIR
CONDITIONER
UNIT
COOLINGONLY APPLICATION
NOTE
THERMOSTAT
SEE
AIR HANDLERTHERMOSTAT
R
G
BU
W
HEATONLY APPLICATION
AIR HANDLER
R
HEAT PUMP
UNIT
AIR HANDLERTHERMOSTAT
R
CONNECT COMMON
WIRE ONLY IF
REQUIRED
(REFER TO THE
APPROPRIATE
THERMOSTAT
INSTALLATION
INSTRUCTIONS)
SEE
NOTE
G
W
BK
BU
Y
AIR CONDITIONER
UNIT
COOLING APPLICATION WITH
ELECTRIC HEAT
FIGURE 15. Low Voltage Connections (3-Speed PSC Motor) – Field Wiring
Air Flow – Cooling Blower Speed
The cooling blower speed is factory congured to provide correct air ow for an outdoor unit that matches the cool-
ing capacity rating of the air handler. If the outdoor unit is smaller than the maximum cooling ca-
pacity rating for the air handler, the cooling blower speed may need to be changed. Refer to blower performance chart, table 2 on page 16 .
WARNING
Electric shock hazard! - Disconnect all power supplies before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
G
BU
BK
W
HEAT PUMP APPLICATION WITH
ELECTRIC HEAT
CHANGE BLOWER SPEED
1 - Disconnect all power supplies.
2 - Remove the air handler access panel.
3 - Locate pin number 2 on the blower relay. Two
black wires are connected to this terminal pin. One connects to pin number 5 on the blower relay, one connects to an in-line splice connecting to a blue wire.
4 - Select the required blower motor speed. Connect
red-LO or black-HI and plug it into the 4-pin blower relay harness connector.
NOTE - Reuse the factory-installed wire nut on the un­used wires.
5 - Replace all panels.
6 - Reconnect power.
Page 15
BLOWER RELAY
BLOWER CONNECTOR
NOTE - Refer to wiring diagram located on the unit ance (table 2).
All air data measured external to unit with 1 inch non-pleated air filter in place.
All factory settings are medium speed.
All data given while air handler is operating with a dry DX coil.
All downflow applications run on high speed when utilizing electric heat.
FIGURE 16. Changing Blower Speed
TABLE 2. CBA25UH Blower Performance (3-Speed PSC) – 240V (CFM @ ESP. – in. W. C.)
Air Handler
Model
-018
-024
-030
-036
-042
-048
-060
Blower Speed .10" WC .20" WC .30" WC .40" WC .50" WC
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
Low (Red) Med (Blue) High (Black)
510 670 905
630 885
1130
900 1075 1240
1075 1300 1510
1325 1490 1820
1775 1995 2070
1675 1965 2140
495 650 865
625 875
1100
865 1060 1210
1040 1250 1450
1315 1465 1770
1710 1895 1970
1630 1925 2085
5
BLOWER RELAY HARNESS
BLUE (MED)
PLASTIC CAPS
RED (L0)
2
BLACK (HI)
YELLOW (COM)
4-PIN
475 630 820
615 850
1070
830 1030 1170
1000 1205 1390
1300 1440 1690
1645 1800 1850
1580 1875 2000
420 595 770
610 820
1010
780 985
1135
950 1145 1320
1275 1395 1600
1565 1685 1719
1520 1800 1895
325 505 705
580 780 950
740 940
1085
900 1085 1245
1225 1315 1500
1470 1560 1595
1450 1695 1795
• Blower Performance (CFM vs. ESP inches H20)
• Cooling speeds should not be reduced below factory setting.
• All units with electric heat approved at 0.5" maximum and medium blower speed minimum.
All downow applications run on high speed when utilizing electric heat.
Check-out Procedures
NOTE – Refer to outdoor unit installation instructions for sys­tem start-up instructions and refrigerant charging instructions.
PRE-START-UP CHECKS
• Is the air handler properly and securely installed?
If horizontally congured, is the unit sloped up to 5/8 inch toward drain lines?
• Will the unit be accessible for servicing?
• Has an auxiliary pan been provided under the unit with
separate drain for units installed above a nished ceil­ing or in any installation where condensate overow
could cause damage?
• Have ALL unused drain pan ports been properly plugged?
• Has the condensate line been properly sized, run, trapped, pitched, and tested?
• Is the duct system correctly sized, run, sealed, and in­sulated?
• Have all cabinet openings and wiring been sealed?
• Is the indoor coil factory-installed TXV properly sized for the outdoor unit being used?
• Have all unused parts and packaging been disposed of?
Is the lter clean, in place, and of adequate size?
Page 16
• Is the wiring neat, correct, and in accordance with the
SECS
34
wiring diagram?
• Is the unit properly grounded and protected (fused)?
• Is the thermostat correctly wired and in a good location?
• Are all access panels in place and secure?
CHECK BLOWER OPERATION
• Set thermostat to FAN ON.
• The indoor blower should come on.
CHECK COOLING OPERATION
• Set thermostat to force a call for cooling (approximately 5ºF lower than the indoor ambient temperature).
• The outdoor unit should come on immediately and the indoor blower should start between 30 - 60 seconds lat­er.
Check the air ow from a register to conrm that the system is moving cooled air.
• Set the thermostat 5ºF higher than the indoor tempera­ture. The indoor blower and outdoor unit should cycle off.
CHECK ELECTRIC HEAT (IF USED)
• Set thermostat to call for auxiliary heat (approximate­ly 5°F above ambient temperature). The indoor blow­er and auxiliary heat should come on together. Allow a minimum of 3 minutes for all sequencers to cycle on.
• Set the thermostat so that it does not call for heat. Allow up to 5 minutes for all sequencers to cycle off.
Operation
TIME DELAY RELAY
Blower time delay operation:
1 - When cooling demand is initiated, there is a 1
second motor-on delay.
2 - After the motor-on delay expires, motor ramps up
to 100% and runs at 100% until cooling demand is
satised.
3 - Once demand is met, motor runs at 100% for 45
seconds.
4 - Motor ramps down to stop.
contactor in the outdoor unit, starting the compressor and outdoor fan motor.
On heat pumps, circuit R and O energizes the reversing valve, switching the valve to the cooling position. (The re­versing valve remains energized as long as the thermo­stat selector switch is in the COOL position.)
At the completion of the cooling demand the indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.
HEATING (ELECTRIC HEAT ONLY)
When the thermostat calls for heat, the circuit between R and W is completed, and the heat sequencer is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat
sequencer can be connected with the rst sequencer to W
on the thermostat sub-base, or they may also be connect­ed to a second stage on the sub-base.
HEATING (HEAT PUMP)
When the thermostat calls for heating, 24 volts is applied to the blower time-delay relay coil. Then, normally open contacts close, causing the indoor blower motor to oper­ate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
If the room temperature continues to decrease, the cir­cuit between R and W1 is completed by the second-stage heat room thermostat. Circuit R-W1 energizes a heat se­quencer. The completed circuit will energize supplemen­tal electric heat (if applicable). Units with a second heat
sequencer can be connected with the rst sequencer to
W1 on the thermostat. They may also be connected to a second heating stage W2 on the thermostat sub-base.
EMERGENCY HEAT (HEATING HEAT PUMP)
If the selector switch on the thermostat is set to the emer­gency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat (if applicable). A jumper should be placed between W2 and E on the thermostat sub-base so that the electric heat con-
trol will transfer to the rst-stage heat on the thermostat.
This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO po­sition.
Homeowner Maintenance
1
1
SECOND
DELAY
100%
2
CFM
COOLING
DEMAND
100%
CFM
45
FIGURE 17. Blower Time Delay
COOLING (COOLING ONLY OR HEAT PUMP)
When the thermostat calls for cooling, 24 volts is put on the blower time-delay relay coil and then the indoor blow­er relay energizes. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the
OFF
IMPORTANT
Do not operate system without a lter. A lter is required
to protect the coil, blower, and internal parts from
excessive dirt and dust. The lter is placed in the return
duct by the installer.
Inspect air lters at least once a month and replace or
clean as required. Dirty lters are the most common
cause of inadequate heating or cooling performance.
Replace disposable lters. Cleanable lters can be cleaned by soaking in mild detergent and rinsing with cold water.
Page 17
Install new/clean lters with the arrows on the side point-
ing in the direction of air ow. Do not replace a clean­able (high velocity) lter with a disposable (low velocity) lter unless return air system is properly sized for it.
• If water should start coming from the secondary drain line, a problem exists which should be investigated and
corrected. Contact a qualied service technician.
Repairing or Replacing Cabinet Insulation
IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation. Insulation loses its insulating value when wet, damaged, separated or torn.
Matte- or foil-faced insulation is installed in indoor equip­ment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabi­net walls), the surrounding ambient air will affect the inside surface temperature of the cabinet.
The temperature/humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and, subsequently, component failure.
REPAIRING DAMAGED INSULATION
Areas of condensation on the cabinet surface are an indi­cation that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good con­dition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape.
Professional Maintenance
NOTICE !
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum coils may be damaged by exposure to solutions with a pH below 5 or above 9. The alumi­num coil should be cleaned using potable water at a moderate pressure (less than 50psi). If the coil cannot be cleaned using water alone, Lennox recommends use of a coil cleaner with a pH in the range of 5 to 9. The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable water several times per year to avoid corro­sive buildup (salt).
Use of Air Handler During Construction
Lennox does not recommend the use of its air handler unit during any phase of construction. Very low return air tem­peratures, harmful vapors and operation of the unit with
clogged or misplaced lters will damage the unit.
Air handler units may be used for heating (heat pumps) or cooling of buildings under construction, if the following conditions are met:
• A room thermostat must control the air handler. The use
of xed jumpers is not allowed.
Air lter must be installed in the system and must be maintained during construction.
Air lter must be replaced upon construction comple- tion.
• The air handler evaporator coil, supply fan assembly and duct system must be thoroughly cleaned following
nal construction clean-up.
All air handler operating conditions must be veried ac- cording to these installation instructions.
GLUE - Make sure there is full coverage of glue on the metal or insulation so there are no areas where air pockets may form which can lead to sweating.
1. CUT INSULATION IN X PATTERN
2. APPLY GLUE
3. PRESS GLUED TABS AGAINST CABINET
FIGURE 18. Repairing Insulation
Page 18
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Installing Contractor’s Name_______________________ Installing
Contractor’s Phone_______________________
Job
Installing Date_______________________________
_
Address____________________________________
8
Temperature
1
Duct
System
5
Duct Static
Air Handler Model #__________________________
Thermostat
SUPPLY
AIR
9
Disconnect
Switch
2
Line Voltage
3
Integrated Control
Blower Motor Amps
6
Electric Heat Amps
7
RETURN
AIR
DUCT SYSTEM
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLTAGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
4
DRAIN LINE
Leak Free
Filter
TOTAL EXTERNAL STATIC (dry coil)
5
Supply External Static ______ ______
Return External Static ______ ______
Total External Static = ______ ______
6
ELECTRIC HEAT AMPS____________
7
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
TEMPERATURE DROP (Cooling Mode)
8
Return Duct Temperature ___________
Supply Duct Temperature − ___________
8
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature − __________
9
THERMOSTAT
Adjusted and Programmed
Operation Explained to Owner
4
Drain Line
dry coil wet coil
Temperature Drop = ___________
Temperature Rise = __________
Explained Operation of System to Homeowner
FIGURE 19. Start-up and Performance Checklist (Upow Conguration)
Page 19
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Installing Contractor’s Name_______________________ Installing
Contractor’s Phone_______________________
Job
Installing Date_______________________________
_
Address____________________________________
Thermostat
9
1
Duct System
2
Integrated
Control
Filter
Air Handler Model #__________________________
Disconnect
Switch
Line Voltage
3
1
Duct System
DUCT SYSTEM
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLTAGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
4
DRAIN LINE
Leak Free
RETURN
4
Drain Line
AIR
Duct Static
Electric Heat Amps
6
Blower motor Amps
7
5
8
Temperature
TOTAL EXTERNAL STATIC (dry coil)
5
Supply External Static ______ ______
Return External Static ______ ______
Total External Static = ______ ______
6
ELECTRIC HEAT AMPS____________
7
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
TEMPERATURE DROP (Cooling Mode)
8
Return Duct Temperature ___________
Supply Duct Temperature − ___________
Temperature Drop = ___________
8
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature − __________
Temperature Rise = __________
9
THERMOSTAT
Adjusted and Programmed
Operation Explained to Owner
SUPPLY
AIR
dry coil wet coil
Explained Operation of System to Homeowner
FIGURE 20. Start-Up and Performance Checklist (Horizontal Conguration)
Page 20
Loading...