For downflow application, kit number 83M57
(LB−109844A) is required. Kit is not provided with
coil blower; order separately.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of
California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact
your supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
The Lennox CB29M and CB30M Elite® series blower coil
units are designed for installation with a matched remote
outdoor unit and optional field−installed electric heat. The
blower coil units are for indoor installation only.
The CB29M and CB30M units, designed for multi−positional installations, are completely assembled at the factory
and shipped ready for upflow or horizontal right−hand discharge installation.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installing the unit
Check equipment for shipping damage; if found, immediately contact the last carrier.
Shipping and Packing List
Each CB29M and CB30M unit package contains:
1 − Assembled blower coil unit
Litho U.S.A.
09/05504,719M
*2P0905**P504719M*
Page 1
Page 2
CB29M Upflow and Downflow Unit Dimensions − inches (mm)
3/4
(19)
SUPPLY
AIR OPENING
3/4
(19)
LOW VOLTAGE
INLETS (TOP &
RIGHT SIDE)
5/8
(16)
11-1/16
(281)
LINE VOLTAGE
INLETS (TOP &
LEFT SIDE)
Top View
D
BC
AIR
FLOW
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)
A
SUCTION
LINE
LIQUID
RETURN AIR
5/8
(16)
F
Front ViewSide View
5/8
(16)
FILTER
ACCESS
LINE
Upflow Position
(25)
PIPING PLATE DETAIL
(For upflow and downflow positions)
1-1/8 (29)
2
(51)
5-3/8
(137)
2-3/4
(70)
1-3/4 (44)
BLOWER
COIL
RETURN AIRFILTER
1
E
(16)
5/8
INSTALLED)
LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)
FILTER
SUCTION
LINE
LIQUID
LINE
OPTIONAL
ELECTRIC
HEAT
(FIELD−
4-3/8 (111)
SUCTION LINE
CONDENSATE
DRAINS (2)
(HORIZONTAL)
LIQUID LINE
CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)
3-1/2 (89)
5/8
(16)
5/8 (16)
E
1 (25)
F
RETURN
AIR
OPENING
Top View
BC
COIL
11-1/16 (281)
BLOWER
SUPPLY
AIR
5/8
(16)
5/8
(16)
AIR FLOW
SUPPLY AIR
D
Front ViewSide View
Downflow Position
(Kit number 83M57 (LB−909844A) required to convert
unit to downflow applications.)
FILTER
ACCESS
5/8 (16)
5/8
(16)
A
Model No.CB29M-21/26 & CB29M-31CB29M-41 & CB29M-46CB29M-51 & CB29M-65
Dimensioninchmminchmminchmm
A45-1/4114949-1/4125152-1/21334
B16-1/441321-1/454021-1/4540
C20-5/852420-5/852422-5/8575
D14-3/437519-3/450219-3/4502
E194831948321533
F153512050820508
Page 2
504719M 09/05
Page 3
CB29M Horizontal Left− and Right−Hand Unit Dimensions − inches (mm)
CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)
CONDENSATE
DRAINS (2)
(HORIZONTAL)
PIPING
PLATE
DETAIL
3/4
(19)
5/8
(16)
5/8
(16)
5/8
(16)
3/4
(19)
5-3/8
(137)
5-3/4
(46)
F
RETURN
AIR
OPENING
End View
11-1/16
(281)
2
(51)
1-3/4
(44)
E
LOW VOLTAGE
INLETS (TOP &
LEFT SIDE)
FILTER
LIQUID
LINE
SUCTION
1-1/2
(38)
LINE
1-1/8
(29)
4-3/8
(111)
LIQUID
LINE
COIL
SUCTION
LINE
Top View
BLOWER
OPTIONAL ELECTRIC
HEAT (FIELD−INSTALLED)
5/8
(16)
C
A
(25)
1
FILTER ACCESS
AIR
FLOW
Front View
B
Horizontal Position (Right-Hand Air Discharge)
C
OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
5/8
(16)
BLOWER
FILTER
Top View
A
COIL
SUCTION
LINE
LIQUID
LINE
For dimensions A"
through F", see
chart on Page 2.
LINE VOLTAGE
INLETS (TOP &
RIGHT SIDE)
LOW VOLTAGE
INLETS (BOTTOM
& RIGHT SIDE)
4-3/8
(111)
PIPING
1-1/8
PLATE
DETAIL
SUCTION
LIQUID
(29)
LINE
LINE
11-1/16
(281)
SUPPLY
AIR
OPENING
End View
2
(51)
5/8
(16)
3/4
(19)
5-3/8
(137)
3/4
(19)
D
3/4
(19)
3/4
(19)
SUPPLY
D
AIR
OPENING
LINE VOLTAGE INLETS
(BOTTOM & LEFT SIDE)
End View
FILTER
5-3/4
(146)
ACCESS
1-1/2
(38)
B
CONDENSATE DRAINS (2)
(HORIZONTAL)
AIR
FLOW
Front View
1-3/4
(44)
Horizontal Position (Left-Hand Air Discharge)
Page 3
(25)
1
E
RETURN
AIR OPENING
End View
CB29M/CB30M SERIES
5/8
F
(16)
5/8
(16)
Page 4
CB30M Upflow and Downflow Unit Dimensions − inches (mm)
3/4
(19)
SUPPLY
AIR OPENING
D
11-1/16
(281)
LINE VOLTAGE
INLETS (TOP &
LEFT SIDE)
Top View
3/4
(19)
LOW VOLTAGE
INLETS (TOP &
RIGHT SIDE)
5/8
(16)
BC
AIR
FLOW
G
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)
A
SUCTION
H
RETURN AIR
5/8
(16)
F
Front ViewSide View
5/8
(16)
FILTER
ACCESS
LINE
LIQUID
LINE
Upflow Position
(25)
PIPING PLATE DETAIL
(For upflow and downflow positions)
1-1/8 (29)
2
(51)
5-3/8
(137)
2-3/4
(70)
1-3/4 (44)
BLOWER
COIL
LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
RETURN AIRFILTER
1
E
5/8
(16)
FILTER
SUCTION
LINE
LIQUID
LINE
OPTIONAL
ELECTRIC
HEAT
(FIELD−
INSTALLED)
(LEFT SIDE)
4-3/8 (111)
SUCTION LINE
CONDENSATE
DRAINS (2)
(HORIZONTAL)
LIQUID LINE
CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)
3-1/2 (89)
5/8
(16)
5/8 (16)
E
1 (25)
F
RETURN
AIR
OPENING
Top View
BC
COIL
11-1/16 (281)
BLOWER
SUPPLY
AIR
5/8
(16)
5/8
(16)
AIR FLOW
SUPPLY AIR
D
Front ViewSide View
Downflow Position
(Kit number 83M57 (LB−909844A) required to convert
unit to downflow applications.)
5/8
(16)
FILTER
ACCESS
H
A
G
5/8 (16)
Model No.CB30M-21/26CB30M-31CB30M-41CB30M-46CB30M-51 & CB30M-65
Dimensioninchmminchmminchmminchmminchmm
A45-1/4114949-1/4125151129552-1/2133458-1/21486
B16-1/441321-1/454021-1/454021-1/454021-1/4540
C20-5/852420-5/852422-5/857522-5/857524-5/8625
D14-3/437519-3/450219-3/450219-3/450219-3/4502
E1948319483215332153323584
F1535120508205082050820508
G24-5/862524-5/862526-3/867027-7/870827-7/8708
H20-5/852424-5/862524-5/862524-5/862530-5/8778
Page 4
504719M 09/05
Page 5
CB30M Horizontal Left− and Right−Hand Unit Dimensions − inches (mm)
CONDENSATE
DRAINS (2)
(UPFLOW AND
DOWNFLOW)
CONDENSATE
DRAINS (2)
(HORIZONTAL)
PIPING
PLATE
DETAIL
3/4
(19)
5/8
(16)
5/8
(16)
5/8
(16)
3/4
(19)
5-3/8
(137)
5-3/4
(46)
F
RETURN
AIR
OPENING
End View
11-1/16
(281)
2
(51)
1-3/4
(44)
E
LOW VOLTAGE
INLETS (TOP &
LEFT SIDE)
FILTER
LIQUID
LINE
SUCTION
(25)
1-1/2
(38)
1
LINE
1-1/8
(29)
4-3/8
(111)
LIQUID
FILTER ACCESS
LINE
COIL
SUCTION
LINE
H
Top View
FLOW
Front View
BLOWER
OPTIONAL ELECTRIC
HEAT (FIELD−INSTALLED)
A
G
AIR
C
5/8
(16)
B
Horizontal Position (Right-Hand Air Discharge)
C
OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
5/8 (16)
BLOWER
FILTER
Top View
A
G
COIL
SUCTION
LINE
H
LIQUID
LINE
For dimensions A"
through H", see
chart on Page 4.
LINE VOLTAGE
INLETS (TOP &
RIGHT SIDE)
LOW VOLTAGE
INLETS (BOTTOM
& RIGHT SIDE)
4-3/8
(111)
PIPING
1-1/8
PLATE
DETAIL
SUCTION
LIQUID
(29)
LINE
LINE
11-1/16
(281)
SUPPLY
AIR
OPENING
End View
2
(51)
5/8
(16)
3/4
(19)
5-3/8
(137)
3/4
(19)
D
3/4
(19)
SUPPLY
3/4
(19)
D
AIR
OPENING
LINE VOLTAGE INLETS
(BOTTOM & LEFT SIDE)
B
CONDENSATE DRAINS (2)
(HORIZONTAL)
FLOW
End View
Horizontal Position (Left-Hand Air Discharge)
Requirements
Installation of Lennox blower coil units with or without optional electric heat must conform with standards in the National Fire Protection Association (NFPA) Standard for
Installation of Air Conditioning and Ventilation Systems
NFPA No. 90A," and Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA No. 90B," manufacturer’s installation instructions and local municipal building codes.
This unit is certified for installation clearances to combustible material as listed on the unit rating plate. Accessibility
and service clearances must take precedence over combustible material clearances.
AIR
Front View
Page 5
1-3/4
(44)
5-3/4
(146)
FILTER
ACCESS
1-1/2
(38)
(25)
1
E
RETURN
AIR OPENING
End View
5/8
F
(16)
5/8
(16)
Installation
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
personal injury or loss of life. Installation and service must be performed by a qualified installer or
service agency.
The CB29M and CB30M units are factory−configured for
upflow or horizontal right−hand discharge installation. For
downflow or horizontal left−hand discharge, some field
modification is required.
CB29M/CB30M SERIES
Page 6
IMPORTANT
2. No further adjustment is necessary. Set unit so that it is
sloped 1/4 inch toward the drain pan end of the unit.
Kit number 83M57 (LB−109844A) must be installed
for downflow application.
Disassembling CB30M Blower Coil Unit
These units are shipped from the factory fully assembled.
The CB30M blower coil unit’s sections may be separated
to facilitate movement at some installation sites. If required, disassemble the unit as follows:
1. Remove access panels from both blower and coil assemblies. This will lighten the cabinet for lifting.
2. Remove one screw from the left and right posts inside
the unit. Remove one screw from each side on the
back of the unit. Unit sections will now separate.
3. To reassemble, align cabinet sections and reinstall
screws. Replace access panels.
Upflow Application
1. Remove access panels. Remove corrugated padding
from the space between the blower and coil assemblies.
2. To ensure proper operation, remove the horizontal
drain pan from units in upflow configurations (see figure 1).
3. Place unit in desired location. Make sure that unit is
level. Connect return and supply air plenums as required using sheet metal screws.
4. Install units that have no return air plenum on a mounting stand at least 14" from the floor for proper air return. Lennox offers an optional upflow unit stand.
(45K31 for CB29M−21, −26, and −31; 45K32 for
CB29M−41 through −65.)
NOTE − For horizontal applications, an auxiliary drain
pan is recommended. Refer to local codes.
NOTE − For horizontal applications in high humidityareas, seal around the exiting drain pipe, liquid line,
and suction line to prevent infiltration of humid air.
Right−Hand Discharge Configuration
Downflow
Drain Pan
Horizontal
Drain Pan
No Adjustment
is Necessary
Horizontal Drip ShieldUpflow/
Figure 2
3. If the unit is to be suspended, it must be supported
along the entire length of the cabinet (see figure 3). If
using a chain or strap, attach a piece of angle iron or
sheet metal to the unit (either above or below the unit),
so that the full length of the cabinet is supported. Use
securing screws which are no longer than 1/2 inch to
avoid damaging the coil or filter. Use sheet metal
screws to connect the return and supply air plenums.
Suspending Horizontal Unit
Angle Iron or
Sheet Metal
1/2 IN.
SCREWS
MAX.
Electrical Inlet Clearance
4 in. (102 mm)
Upflow Configuration
Upflow/
Downflow
Drain Pan
Horizontal Drain Pan
(Remove for Optimum Performance)
Figure 1
Horizontal Right−Hand Discharge Application
1. Remove access panels. Remove corrugated padding
from the space between the blower and coil assembly.
FRONT VIEWEND VIEW
Figure 3
CAUTION
When removing the coil, there is possible danger of
equipment damage and personal injury. Be careful
when removing the coil assembly from a unit
installed in right− or left−hand applications. The coil
may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.
504719M 09/05
Page 6
Page 7
Horizontal Left−Hand Discharge Application
NOTE − For horizontal applications, an auxiliary drain pan
is recommended. Refer to local codes.
Remove the access panels and the corrugated padding
from the space between the blower and coil assembly before operation. Make the following modifications:
1. (See Detail A in figure 4.) Pull coil assembly from unit.
Pull off the horizontal drain pan.
2. Remove drain plugs from back drain holes on horizontal drain pan and re−install them on front holes.
3. Rotate drain pan 180° front to back and install it on the
opposite side of coil.
Left-Hand Discharge Modifications
Coil shown in upflow position for easy conversion
Detail A
(DRAIN
PAN)
PLUGGED
END
ORIGINAL
PLUG
LOCATION
NEW PLUG
LOCATION
Detail B
(TOP CAP)
OPEN END FOR
CONDENSATION
DRAIN
TOP CAP ROTATED TO
CORRECT POSITION
COIL
ASSEMBLY
TOP CAP
SCREWS
4. (See Detail B and C in figure 4.) Remove screws from
top cap. Remove horizontal drip shield screw located
in the center of the back coil end seal.
5. Rotate horizontal drip shield 180° front to back.
6. Remove plastic plug from left hole on coil front end
seal and re−install plug in back hole. Re−install horizontal drip shield screw in front coil end seal. Drip shield
should drain downward into horizontal drain pan inside
coil.
7. Rotate top cap 180° front to back and align with unused screw holes. Holes must align with front and back
coil end plates. Note that top cap has a 45° bend on
one side and 90° bend on the other. The 90° bend
must be on the same side as the horizontal drain
pan. See figure 4.
NOTE − Use extreme care when re−installing screws
into coil end plate engaging holes. Misaligned screws
may damage coil.
8. (See figure 5.) From the upflow position, flip cabinet
90° to the left and set into place. Replace coil assembly. Secure coil in place by bending down tab on cabinet support rail.
Left−Hand Discharge Configuration
Securing Tab on
Cabinet Support Rail
Horizontal
Drip Shield
Horizontal
Drain Pan
CABINET
SUPPORT
TOP
CAP
90_
BEND
DRAIN PAN
90_
BEND
Figure 4
Detail C
ALIGN HOLES
WITH HOLES
IN COIL END
PLATE.
BACK COIL
END SEAL
Figure 5
NOTE − For horizontal applications in high humidity
areas, seal around the exiting drain pipe, liquid line
and suction line to prevent infiltration of humid air.
9. Knock out drain seal plate from access door. Secure
plate to cabinet front flange with screw provided.
10. Flip access door and replace it on the unit.
11. Set unit so that it is sloped 1/4 inch toward the drain
pan end of the unit. Connect return and supply air plenums as required using sheet metal screws.
12. If the unit is to be suspended, it must be supported
along the entire length of the cabinet (see figure 3). If
using a chain or strap, attach a piece of angle iron or
sheet metal to the unit (either above or below the unit),
so that the full length of the cabinet is supported. Use
securing screws which are no longer than 1/2 inch to
avoid damaging the coil or filter. Use sheet metal
screws to connect the return and supply air plenums.
Page 7
CB29M/CB30M SERIES
Page 8
Downflow Application
NOTE − If downflow application is required, separately order kit number 83M57 and install per kit’s instructions.
Also, use metal or class I supply and return air plenums.
WARNING
If electric heat section with circuit breakers (ECB29)
are applied to downflow CB29M or CB30M unit, circuit breakers must be rotated 180_ to the UP position. See ECB29 installation instructions for more
details.
Combustible Flooring Additive Base
BLOWER
COIL UNIT
Combustible
Floor Additive
Base
Properly−Sized
Floor Opening
Figure 6
On combustible flooring, use an additive base (figure 6).
Cut an appropriately sized opening for combustible base
(see dimensions in figure 7). Set the additive base into
opening. Connect supply air plenum to the additive base.
Set the unit on the additive base so flanges of the unit drop
into the base opening and seal against the insulation strips.
The unit is now locked in place. Install return air plenum
and secure with sheet metal screws.
Downflow Combustible Base Dimensions
1-5/8 (41)
15 (381)
CB29M−21/26 & 31
CB30M−21/26
20 (508)
CB29M−41 to −65
CB30M−31 to 65
1-5/8 (41)
5/8 (16)
11-3/8
(289)
1-5/8 (41)
SUPPLY
AIR
OPENING
TOP VIEW
22-1/8 (562)
13-3/8 (340)
OPENING
SIDE VIEW
Figure 7
inches
(mm)
18−1/4 (464)
CB29M−21/26 & 31
CB30M−21/26
23−1/4 (591)
CB29M−41 to −65
CB30M−31 to 65
2 (51)
If the homeowner reports water dripping from supply air diffusers, check the shields and tape. Make sure the tape is
completely attached to the edges of the drip shield, and
that the drip shield is wedged firmly in place.
Field Piping Connections
All CB29M/CB30M coils are equipped with a factory−
installed, internally mounted expansion valve. Use Lennox
L15 (sweat) series line sets as shown in Table 1 or use
field−fabricated refrigerant lines. L10 (flare) line sets may
be used by cutting off flare nut. Refer to the piping section
of the Lennox Unit Information Service Manual for proper
size, type and application of field−fabricated lines.
Table 1
Refrigerant Line Sets
CB29M
CB29M
Unit
−21/263/8 in
−31 −413/8 in
−46 −513/8 in
−653/8 in
NOTE − CB29M/CB30M series evaporators use nitrogen or dry air as a holding charge. If there is no pressure
when the rubber plugs are removed, check the coil or line
set for leaks before installing. After installation, pull a
vacuum on the line set and coil before releasing the unit
charge into the system.
1. Use a wet rag to protect TXV bulb (or remove it) when
brazing suction line.
2. Be aware of filter access panel when connecting lines.
Filter must be accessible.
3. Place heat shield (damp rag) against piping plate and
around the suction line connection. Heat shield must
be in place to guard against damage to the paint.
4. With heat shield in place, sweat in suction line elbow,
provided, and line set. After procedure is completed,
remove heat shield.
5. Place heat shield against piping plate and around the
liquid line connection. Sweat in the liquid line elbow
(provided) and the line set.
6. Refer to instructions provided with outdoor unit for leak
testing, evacuating and charging procedures.
Liquid
Line No.
(8 mm)
(10 mm)
(10 mm)
(10 mm)
Vapor/
Suction Line
5/8 in
(16 mm)
3/4 in.
(19 mm
7/8 in.
(22 mm)
1−1/8 in.
(29 mm)
L10
Line Sets
L10−26
20 ft. − 50 ft.
(6 m − 15 m)
L10−41
20 ft. − 50 ft.
(6 m − 15 m)
L10−65
30 ft. − 50 ft.
(9 m − 15 m)
FIELD
FABRICATED
L15
Line Sets
L15−26
20 ft. − 50 ft.
(6 m − 15 m)
L15−41
20 ft. − 50 ft.
(6 m − 15 m)
L15−65
30 ft. − 50 ft.
(9 m − 15 m)
FIELD
FABRICATED
504719M 09/05
Page 8
Page 9
Condensate Drain
Connect main condensate drain and route downward to an
open drain or sump. Do not connect drain to a closed waste
system. Refer to figure 8 for typical condensate trap configuration.
Typical Condensate Drain Connection
Minimum 1 inch (25 mm) pitch
per 10 feet (3048mm) of line
Trap must be deep enough to
offset maximum static difference
(generally, 2" [51mm] minimum).
Figure 8
It is recommended that the auxiliary drain be connected to
a drain line for all units. If auxiliary drain is not connected, it
must be plugged with provided cap. For downflow units,
the auxiliary drain MUST be connected and routed to a
drain. See figure 9 for auxiliary and main drain locations.
Left−Hand
Discharge
Upflow or
Downflow
Pipe diameter difference
Coil
drain
pan
Right−Hand
Discharge
Filters
IMPORTANT
Filter access panel must be in place during unit operation. Excessive warm air entering the unit may result in water blow−off problems.
Each unit includes a factory−installed filter. Note that filter
access door fits over access panel. Air leakage will occur if
access panel is placed over filter door.
Filters should be inspected monthly and must be cleaned
or replaced when dirty to assure proper furnace operation.
Reusable filters supplied with some units can be washed
with water and mild detergent. Some units are equipped
with standard throw−away type filters which should be replaced when dirty.
To remove filter, loosen the thumbscrews holding the filter
panel in place. Slide filter out of the guides on either side of
cabinet, insert new filter and replace panel. See Table 2 for
replacement filter sizes.
Main drain on rightAuxiliary drain on left
Figure 9
The following practices are recommended to ensure condensate removal (see figures 8 and 9):
1. Drain piping should not be smaller than the drain connections at drain pan.
2. A trap must be installed in the main drain line.
3. The trap must be deep enough to offset the difference
in static pressure between drain pan and atmosphere.
Generally, two inches is satisfactory for medium static
applications.
4. Horizontal runs must be sloped 1 inch per 10 feet of
drain line to offset friction.
5. An open vent in drain line will sometimes be required due
to line length, friction and static pressure.
6. Drain construction and routing should facilitate future
cleaning and must not interfere with filter access.
7. Auxiliary drain should run to an area where homeowner will notice any drainage. Refer to local codes.
Table 2
Filter Dimensions
Unit Model No.
CB29M/CB30M−21/26, CB29M−3115 x 20 (381 x 508)
CB29M−41, −46, CB30M−3120 x 20 (508 x 508)
CB29M−51, −65, CB30M−41, −4620 x 22 (508 x 559)
CB30M−51, −6520 x 24 (508 x 610)
Filter Size
Inches (mm)
Sealing the Unit
It is very important to seal the unit so that warm air is not
allowed into the cabinet. Warm air introduces moisture,
which results in water blow−off problems. This is especially
important when the unit is installed in an unconditioned
area.
Make sure the liquid line and suction line entry points are
sealed with either the provided Armaflex material or with
Permagum. Permagum may also be used to seal around
the main and auxiliary drains and around open areas of
electrical inlets.
Page 9
CB29M/CB30M SERIES
Page 10
Blower Speed Adjustments
External Static
Minimum Blower Speeds (With Electric Heaters)
For the minimum allowable speed for the CB29M/CB30M
series units with electric heat, refer to the ECB29 installation instructions.
Air Volume Adjustment
Blower Speed Tap Selection
harness
connector
Blower speed selection is accomplished by changing the
taps at the harness connector at the blower motor. See figure 10. Refer to unit wiring diagram in figure 11. Refer to
Tables 3 through 20 for blower performance data.
Press the tab to release wire connector.
select connector location for new speed.
Insert wire until it clicks.
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
LowHigh
Electrical
WARNING
USE COPPER CONDUCTORS ONLY.
Run 24V Class II wiring only through specified low
voltage opening. Run line voltage wiring only
through specified high voltage opening. Do not
combine voltage in one opening.
Wiring must conform to the current National Electric Code
ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA
Standard C22.1, and local building codes. Refer to follow-
ing wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
Select the proper supply circuit conductors in accordance with Tables 310−16 and 310−17 in the National
Electric Code, ANSI/NFPA No. 70 or Tables 1 through 4
in the Canadian Electric Code, Part I, CSA Standard
C22.1.
This unit is provided with knockouts for conduit. Reducer
washers are provided, in bag assembly to allow use of
smaller conduit. Use provided caps to seal holes not
used. Refer to figure 11 for unit schematic wiring diagram. Refer to figures 13 and 14 for typical field wiring.
Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension illustration for
specific location.
504719M 09/05
Page 16
Page 17
System Wiring Diagrams
CB29 & CB30 Typical Wiring Diagram − Single Phase
Figure 11
Page 17
CB29M/CB30M SERIES
Page 18
CB29 & CB30 Typical Wiring Diagram − Three Phase
504719M 09/05
Figure 12
Page 18
Page 19
CIRCUIT 1
FIELD−SUPPLIED
WIRE NUTS
Typical Field Wiring − Cooling Only Application
NOTE − USE COPPER CONDUCTORS ONLY.
REFER TO UNIT RATING PLATE FOR MINIMUM
CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
LINE VOLTAGE FIELD INSTALLED
CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC
NOTE − ALL REMAINING WIRES ARE FACTORY
INSTALLED
TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM.
FACTORY INSTALLED JUMPERS
(Black)
(Orange)
4
7
FUSE
6
1
3
9
CIRCUIT 1
Typical Field Wiring − Cooling Application With Electric Heat
CIRCUIT BREAKERS
OR TERMINAL BLOCK
4
7
FUSE
NOTE − USE COPPER CONDUCTORS ONLY.
REFER TO UNIT RATING PLATE FOR MINIMUM
6
1
3
9
CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
LINE VOLTAGE FIELD INSTALLED
CLASS 2 VOLTAGE FIELD INSTALLED
NEC/CEC
NOTE − ALL REMAINING WIRES ARE FACTORY
INSTALLED
TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM.
THERMOSTAT HEAT ANTICIPATION SETTING 0.4
AMP ELECTRIC HEAT
WHEN TWO−STAGE THERMOSTAT IS USED,
CONNECT SECOND STAGE HEAT BULB TO TERMINAL W2" AND REMOVE JUMPER BETWEEN
TERMINALS R" AND W2."
FACTORY INSTALLED JUMPERS
L3 CONNECTION USED ON (Y−VOLTAGE)
3−PHASE ELECTRIC HEATERS ONLY.
Figure 13
Page 19
CB29M/CB30M SERIES
Page 20
CIRCUIT 1
Typical Field Wiring − Heat Pump Only Application
CIRCUIT BREAKERS
OR TERMINAL BLOCK
FUSE
LINE VOLTAGE FIELD INSTALLED
4
7
6
1
3
9
NOTE − ALL REMAINING WIRES ARE FACTORY INSTALLED
TO EXTERNAL LOAD 24VAC AT .50 AMP MAXIMUM
FACTORY INSTALLED JUMPERS
Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED (HP21).
USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC
THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1
IN HEAT PUMP UNIT.
COMMON USED ONLY ON SOME THERMOSTATS.
AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY
ON SOME THERMOSTATS.
CLASS 2 VOLTAGE FIELD INSTALLED NEC/CEC
1
CIRCUIT 1
CIRCUIT
BREAKERS OR
TERMINAL
BLOCK
EC W1 GO Y1 RLT
2
5
W1 OY1R
C
COMMON
ELECTRIC HEAT
COMPRESSOR
REVERSING VALVE
HEAT PUMP CLASS 2
VOLTAGE TERMINALS
Typical Field Wiring − Heat Pump Application With Electric Heat
K22
6
ECW1GOY1R L
FUSE
4
6
1
3
9
7
S23
L
POWER
SERVICE LIGHT
T
THERMISTOR
6
4
Y2
3
Y2
2ND STAGE COMPRESSOR
Y2
T
LINE VOLTAGE FIELD
INSTALLED
CLASS 2 VOLTAGE FIELD
INSTALLED NEC/CEC
NOTE − ALL REMAINING WIRES
ARE FACTORY INSTALLED
THERMOSTAT HEAT ANTICIPATION
SETTING 0.4 AMP ELECTRIC HEAT
FACTORY INSTALLED JUMPERS
WHEN OUTDOOR THERMOSTAT IS
USED, CONNECT LEADS TO
TERMINALS R" AND W2" AND
REMOVE JUMPER BETWEEN
TERMINALS R’ AND W2."
EMERGENCY HEAT RELAY (USED
ONLY IF OUTDOOR T’STAT IS
USED) FIELD PROVIDED AND
INSTALLED NEW INDOOR UNIT.
24VAC 5VA MAX NEC/CEC CLASS 2
504719M 09/05
USING SERVICE LIGHT OPTION (S54) WITH SOME ELECTRONIC
THERMOSTATS MAY REQUIRE MOVING S54 COMMON WIRE TO Y1 IN
HEAT PUMP UNIT.
COMMON USED ONLY ON SOME THERMOSTATS.
Y2 USED ONLY WHEN TWO-SPEED COMPRESSOR IS USED (HP21)
AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON
SOME THERMOSTATS.
HEAT PUMP CLASS 2
VOLTAGE TERMINALS
Figure 14
Page 20
C
W1
COMMON
ELECTRIC HEAT
O
Y1
COMPRESSOR
REVERSING VALVE
RL
POWER
SERVICE LIGHT
7
T
Y2
THERMISTOR
2ND STAGE COMPRESSOR
8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.