Lennox CB26UH, CB26UH-R, CBX26UH, CBX26UH-R Installation Instructions Manual

INSTALLATION
E2011 Lennox Industries Inc.
Dallas, Texas, USA
TXV
RETAIN THESE INSTRUCTIONS
RFC
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
INSTRUCTIONS
CB(X)26UH(−R) Series Units
AIR HANDLERS
505,059M (65937170) 07/11 Supersedes 05/11
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CB(X)26UH Series Units 3. . . . . . . . . . . . . . . . . . . . . . .
Requirements 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Clearances 4. . . . . . . . . . . . . . . . . . . . . . . . .
Installation 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Condensate Drain 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System and Filters 8. . . . . . . . . . . . . . . . . . . . . . . .
Connecting Refrigerant Lines 9. . . . . . . . . . . . . . . . . . .
Sealing the Unit 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connections 9. . . . . . . . . . . . . . . . . . . . . . . . .
Airflow − Cooling Blower Speed 12. . . . . . . . . . . . . . . . . .
Check−Out Procedures 15. . . . . . . . . . . . . . . . . . . . . . . . .
Operation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cabinet Insulation 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List
Package 1 of 1 contains the following:
1 − Assembled air handler unit for upflow or horizontal air
discharge application (includes upflow and horizontal drain pans)
NOTE  For downflow application, order kit 12W61 (0658731−75).
Check equipment for shipping damage. If found, immediately report damage to the last carrier. Check the unit rating plate to confirm that delivered unit matches order.
Litho U.S.A.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs and HCFCs and HFCs) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
IMPORTANT
This unit must be matched with an outdoor unit as spe­cified in Lennox Engineering Handbook.
07/11 505,059M (65937170)
*2P0711* *P505059M*
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installa­tion, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further infor­mation, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Page 1
CB(X)26UH Unit Dimensions − inches (mm)
BC
1 (25)
LINE VOLTAGE RIGHT,
LEFT AND TOP
LOW VOLTAGE
RIGHT SIDE ONLY
AIR FLOW
A
CONDENSATE DRAIN SUCTION LINE
F
LIQUID LINE
PIPING PLATE (4) (2−1/4 X 3−3/4)
FILTER ACCESS
E
D
3/4 (19)
2-1/2 (64)
G
(OPENING) (OPENING)
2-1/2 (64)
1-1/2 (38)
H
1-1/2 (38)
FRONT VIEW SIDE VIEW
OPTIONAL DUCT ADAPTOR KIT (KIT ALLOWS DIRECT
CONNECTION OF THE DUCTWORK TO THE RETURN AIR
OPENING OF THE AIR HANDLER, NOT REQUIRED IF AN
EXTERNAL FILTER IS USED.)
CB(X)26UH Dimensions (for Upflow and LH/RH Horizontal Air Discharge Applications)
−018, −024 −030, −036 −037*, −042, −048* −060
Dimension
A 46−3/4 1187 51 1295 54 1372 60 1524 B 18−1/2 470 21−1/4 540 21-1/4 540 21-1/4 540 C 22 559 22 559 26 660 26 660 D 11 279 12−1/2 318 12 305 11− 3/ 4 298 E 16 406 18−1/2 470 16−3/4 425 17 432 F 5−1/2 140 6 152 4 102 4 102 G 13−1/2 343 16 406 16 406 16 406 H 19 483 19 483 23 584 23 584
Supply Air
Opening
Return Air
Opening
Depth 17 432 17 432 21 533 21 533
Width 16−1/2 419 19−1/4 489 19−1/4 489 19−1/4 489
Depth 18−1/4 464 18−1/4 464 22−1/4 565 22−1/4 565
Width 13−1/2 343 16−1/4 413 16−1/4 413 16−1/4 413
* −037 and −048 units not available in RFC model.
inches mm inches mm inches mm inches mm
505059M 0511
Page 2
CB(X)26UH Series Air Handlers
All CB(X)26UH air handlers are designed for indoor installation only. As shipped, the units are ready for installation in either upflow or horizontal left−hand air discharge applications. All units may be installed with optional field−installed electric heat and a matched remote outdoor unit.
S CBX26UH air handlers may be installed with a
matched HFC−410A remote outdoor unit. These units are completely assembled, including a factory installed check/expansion valve.
S CB26UH air handlers may be installed with a matched
HCFC−22 remote outdoor unit. These units are completely assembled, including a factory installed check/expansion valve.
Table 1. Orifice (RFC) Part Number (Sizes − in.)
HCFC−22
Model
018 100484−08 (0.057)
024 100484−11 (0.061)
030 100484−21 (0.072)
036 100484−23 (0.074)
042 100484−30 (0.082)
037, 048 not supported
060 100484−44 (0.098)
13HPD / HP13 XC13 / XP13
Note 1 − Orifice ships with Air Handler.
NOTE 1
HFC−410A
Refer to orifice table in
outdoor unit installation
Note 2 − Orifice ships with outdoor units.
NOTE 2
manual
S CB26UH−R (RFC) units may be installed with a
matched remote 13HPD/ HP13 outdoor unit. These units are equipped with an HCFC−22 refrigerant flow control device (see orifice table 1). Also, these units can be used with HCFC−22 (13ACD/AC13), or HFC−410A refrigerant provided the RFC shipped with the outdoor unit is installed in place of the RFC device shipped with the CB26UH−R unit.
Requirements
of Air Conditioning and Ventilation Systems" (NFPA No. 90A) and Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems" (NFPA No. 90B).
IMPORTANT
The CB(X)26UH units are designed to match, and must be used with, outdoor units as rated. The indoor sections are manufactured with a check/expansion valve (TXV) or refrigerant flow control (RFC) device to provide opti­mum refrigerant control and system performance with a variety of different capacities of outdoor units.
TXV unitsIn some cases, the rating of the outdoor unit may require that the coil assembly installed TXV be changed to obtain rated performance.
All models are designed for indoor installation only. The installation of the air handler, field wiring, duct system, etc. must conform to the requirements of the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or wastewater codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual. Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air−Conditioning Systems (latest edition). The air handler is shipped from the factory completely assembled. The unit is provided with flanges for the connection of the duct system.
Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation.
Select the final air discharge position which best suits the site conditions. Consider required clearances, space, routing requirements for refrigerant line, condensate disposal, filters, duct system, wiring, and accessibility for service. Refer to the air handler rating plate on the air handler for specific information.
WARNING
Excessive Weight Hazard − Use two or more people when moving and installing the unit. Failure to do so can result in back or other type of injury.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation. Read this instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.
In addition to conforming to manufacturer’s installation instructions and local municipal building codes, installation of Lennox air handler units (with or without optional electric heat), MUST conform with National Fire Protection Association (NFPA) standards: Standard for Installation
WARNING
Danger of explosion. Keep flammable ma­terials and vapors, such as gasoline, away from air handler. Place air handler so that heating elements are at least 18 inches (46 cm) above the floor for a garage installa­tion. Failure to follow these instructions can result in death, explosion, or fire.
NOTES  During cooling operation, excessive sweating may occur if
the air handler is installed in a very humid space. If installed in an unconditioned space, sealant should be
applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
Electrical wires should be sealed on the inside where they exit the conduit opening. Sealant is required to prevent air leakage into, and condensate from forming inside of, the air handler, the control box, and on the electrical controls.
Page 3
CB(X)26UH SERIES
This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances.
The air handler must be installed so that free access is allowed to the coil/filter compartment and blower/control compartment.
Horizontal applications of the air handler must be installed sloped (approximately 5/8 inch) toward the drain pan openings to ensure proper condensate drainage.
Installation Clearances
NON−DUCTED RETURN CLOSET INSTALLATION
The air handler can be installed in a closet with a false bottom to form a return air plenum. It may also be installed with a return air plenum under the air handler.
Louvers or return air grilles are field-supplied. Local codes may limit application of systems without a ducted return to single story buildings.
When a CB(X)26UH unit is installed in a closet with a louvered return opening, the minimum open area for the louvers will be:
S 320 square inches for −018 and −024 models; S 360 square inches for −030 and −036 models; S 450 square inches for −042 thru −060 models.
If the free area is not known, assume a 25% free area for wood or a 75% free area for metal louvers or grilles. Using the louver dimensions and the 25% or 75% assumption, determine if the open area meets the minimum open area listed above.
If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow for the free flow of return air. When not installed in front of the opening, there must be adequate clearance around the air handler to allow for the free flow of return air.
If a filter is to be installed at the air handler, early models require a filter rack be formed using factory−supplied flanges. Lay the unit on its back and pry out the filter rack tabs as shown in figure 1. Repeat procedure on opposite side.
Figure 1. Filter Rack Tabs (Pre April 2006)
Later models are equipped with rails in which the filter slides. Two screws and a bracket must be removed to insert and remove the filter (see figure 2).
BRACKET
SCREWS
(DUCT ADAPTER AND SELF TAPPING SCREWS
− OPTIONAL FOR AT­TACHING RETURN AIR DUCT)
Installation
GENERAL INFORMATION
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal inju­ry or loss of life. Installation and service must be per­formed by a qualified installer or service agency.
CB(X)26UH units are factory−assembled and configured for installation in upflow or horizontal left−hand air discharge applications.
Each unit consists of a blower assembly, refrigerant coil, and controls, in an insulated galvanized steel factory finished enclosure. Knockouts are provided for electrical wiring entrance.
For ease in installation, it is best to make any necessary coil configuration changes before setting air handler in place.
505059M 0511
FILTER RAILS
Figure 2. Filter Rails (April 2006 and Later)
UPFLOW APPLICATION
1. The air handler must be supported on the bottom only and set on solid floor or field-supplied support frame. Securely attach the air handler to the floor or support frame.
2. If installing a unit in an upflow application, remove the horizontal drain pan. IMPORTANT − The horizontal
drain pan is not required in upflow air discharge installations; its removal provides the best efficiency and air flow.
3. Place the unit in the desired location and level it. Connect return and supply air plenums as required using sheet metal screws.
Page 4
4. Install units that have no return air plenum on a stand that is at least 14" from the floor. This will allow proper air return.
HORIZONTAL DRAIN PAN
IMPORTANT! REMOVE PAN
FOR BEST EFFICIENCY
AND AIR FLOW.
HORIZONTAL DRAIN
UPFLOW
DRAIN PAN
UPFLOW DRAIN CON-
NECTIONS (BOTH
SIDES; USE ONE SIDE
OR OTHER)
CONNECTIONS (BOTH SIDES; NOT USED)
Figure 3. Upflow Configuration
HORIZONTAL APPLICATIONS
IMPORTANT
When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right− or left−hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.
NOTE  This unit may be installed in left−hand or right−hand air discharge horizontal applications. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove service and access panels if installing in the horizontal position.
1. Determine whether left-hand or right-hand air discharge is required. If right-hand is required, perform Right−Hand Discharge Modification on page 6.
2. Determine knockouts required for drain line connections.
3. With access door removed, knock out drain line opening for installing drain lines.
4. Set unit so that it is sloped toward the drain pan end of the unit (see figure 10 on page 7).
5. The horizontal configuration is shown in figure 5.
6. If the unit is suspended, the entire length of the cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2 inch to avoid damaging the coil or filter. See figure 4. Use sheet metal screws to connect the return and supply air plenums as required.
AIR FLOW
Drains
ANGLE IRON OR SHEET METAL
1/2 IN. SCREWS
MAX.
AIR FLOW
FRONT VIEW END VIEW
ELECTRICAL INLET CLEAR-
ANCE 4 IN. (102 MM)
Figure 4. Suspending Horizontal Unit
NOTE  When the unit is installed in horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE  For applications where return air ducting is to be connected to the bottom of the coil blower, Lennox offers a duct adapter kit which mounts on the filter door side of the end of the unit (shown in figure 2). This provides a metal edge for attaching the return air duct. One duct adapter and two self−tapping screws are needed for each installation. Packages of 10 adapters/20 screws are available: 0658731−85 (Catalog No. X8103) for the
−018/−024 size units; 0658731−86 (Catalog No. X8104) for the −030 to −060 size units.
KNOCKOUT
LEFT-HAND DRAINS
Figure 5. Left-Hand Discharge Configuration
RIGHT−HAND AIR DISCHARGE MODIFICATION
For horizontal right−hand air discharge, the following field modifications are required.
1. Remove and set aside blower and coil access covers.
2. Remove the coil support bracket (detail A, figure 7).
3. Remove coil assembly, bottom drain pan and horizontal drain pan as one assembly from the air handler.
4. Remove two screws, blow off prevention bracket (where used; see table 2), and horizontal drip shield. Rotate the brackets 180º and reinstall using the same screws.
5. Move the horizontal drain pan to the opposite side of the coil. Be sure drain holes toward the back of the unit are plugged (see figure 8). Remove the plugs from the front drain pan ports.
6. Re−install modified coil/drain pan assembly in air handler in the same orientation as before.
Page 5
CB(X)26UH SERIES
7. Install the coil support bracket on the opposite side of the air handler (figure 7, detail B).
AIR FLOW
Drains
RIGHT-HAND DRAINS
KNOCKOUT
Figure 6. Right-Hand Discharge Configuration
REMOVE DRAIN PAN FROM HERE
REMOVE 2 SCREWS, BLOW OFF PREVENTION BRACKET(S), AND DRIP SHIELD FROM HERE
REMOVE COIL SUPPORT BRACKET FROM HERE
THEN...
ROTATE SHIELD AND BRACKET AND REINSTALL
NOTE − EXPANSION VALVE SHOWN ON COIL IS NOT ON CB26UH−R (RFC) EQUIPPED UNITS.
THEN...
Table 2. Blow Off Prevention Bracket
Model Front Rear
−018 None None
−024 None None
−030 Yes Yes
−036 Yes Yes
−037 None None
−042 None None
−048* Yes None
−060 Yes None
* −048 model supported in TXV units only.
REINSTALL PAN HERE
THEN...
REINSTALL BRACKET HERE
BRACKET SHOWN AS SHIPPED
BRACKET SHOWN FOR RIGHT HAND DISCHARGE
DETAIL A
Figure 7. Field Modification for Right−Hand Discharge
PLUGGED END
COIL ASSEMBLY
OPEN END FOR CONDENSATION
DRAIN
Figure 8. Right-Hand Drain Plug Location
DETAIL B
REFRIGERANT METERING DEVICE
NOTE  See the outdoor unit installation instructions and the Lennox Engineering Handbook for approved fixed orifice match−ups and application information.
CB26UH−R units are equipped with a factory−installed refrigerant flow control (RFC) device (see table 1 on Page 3).
IMPORTANT
If a unit equipped with an RFC device is used in an ap­plication which requires conversion to an expansion valve, the fixed orifice must be removed before the ex­pansion valve is installed.
505059M 0511
Page 6
The coil has a fixed orifice in the liquid line (see figure 9). Remove the rubber plug from the vapor line of the coil.
O−RING
DISTRIBUTOR
FIXED ORIFICE
STRAINER
LIQUID LINE STUB
Figure 9. Metering Device Installation
Condensate Drain
IMPORTANT
On units of this type, where the blower draws" rather than blows" air through the coil, traps must be installed in the condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.
IMPORTANT
A field−fabricated secondary drain pan, with a drain pipe to the outside of the building, is required in all installations over a finished living space or in any area that may be damaged by overflow from the main drain pan. In some localities, local codes may require an secondary drain pan for any horizontal installation.
INSTALL CONDENSATE DRAIN
1. Remove the appropriate drain knockouts. If necessary, remove the indoor coil assembly from the cabinet.
2. Connect primary drain line connection to the primary drain pan connection. The primary drain connection is flush with the bottom of the inside of the pan. Secondary connection is raised above the bottom of the inside of the pan.
NOTE  When making drain fitting connections to the drain pan, hand tighten the fitting and use a sealant. Over−tightening the fittings can split connections on the drain pan.
3. If the auxiliary drain line is to be used, remove the plug and route the drain line so that water draining from the outlet will be easily noticed by the homeowner.
4. After removal of drain pan plugs, check the drain port to see if holes have been drilled. If not drilled, use a 19/32" bit to drill out the primary drain hole; use a 3/8" drill bit for the secondary drain hole. Remove all drill shavings.
5. Make sure drain ports and drain pan are free of all debris.
6. Plug and check any unused drain pan openings for tightness. Torque plugs to 30 in. lb. to prevent water leaks or seepage from the drain pan.
The air handler is provided with ¾" NPT condensate drain connections.
SLOPING THE DRAIN
Make sure the unit is sloped (similar to the slope shown in figure 10) so that the drain pan will empty completely without water standing in the pan.
THIS CORNER SHOULD BE 5/8" (+/− 1/8") HIGHER THAN DRAIN CORNER
THIS CORNER SHOULD BE 5/8" (+/− 1/8") HIGHER THAN DRAIN CORNER
DRAIN CORNER
Figure 10. Sloping the Drain
7. Install a 2" trap in the primary drain lines as close to the unit as practical (see figure 11). Make sure the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.
NOTE  Horizontal runs must have an anti−siphon air vent (standpipe) installed ahead of the horizontal run (See figure 11). An extremely long horizontal run may require an oversized drain line to eliminate air trapping.
NOTE  Do not operate air handler without a drain trap. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will prevent positive drainage without a proper trap.
8. Route the drain line to the outside or to an appropriate drain. Drain lines must be installed so they do not block service access to the front of the air handler. A 24" clearance is required for filter, coil, or blower removal and service access.
NOTE  Check local codes before connecting the drain line to an existing drainage system.
Insulate the drain lines where sweating could cause water damage.
Page 7
CB(X)26UH SERIES
ABOVE
FINISHED
SPACE?
OVERFLOW DRAIN LINE
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.
LENNOX #
X3169
COMPACT OVERFLOW SWITCH WITH 3/4" FEMALE SLIP INLET
NO
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING
CLEAN OUT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
VENT
AIR HANDLER DRAIN PAN
OVERFLOW
DRAIN
YES
NOTE  WHEN A AIR HANDLER IS LOCATED ABOVE A FINISHED SPACE THE SECONDARY
DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.
SECONDARY
DRAIN PAN
OPTIONAL
MAIN
DRAIN
SAFETY
PAN
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4" (19.1MM) SECONDARY DRAIN LINE MUST BE:
S CONNECTED TO SECONDARY DRAIN PAN
OR
S CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE AIR HANDLER DRAIN PAN.
PRIMARY AND SECONDARY TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES  GENERALLY, TWO INCHES (51MM).
*LENNOX P−TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J−TRAP 91P90.
Figure 11. Typical Main and Overflow Drain
TEST CONDENSATE DRAIN
Test the drain pan and drain line after installation:
1. Pour several quarts of water into drain pan, enough to fill drain trap and line.
2. Check to make sure the drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the end of the primary drain line.
3. Correct any leaks found.
Duct System and Filters
DUCT SYSTEM
The air handler is provided with flanges for the connection of the plenum and ducts. The air handler is equipped with flanges that can form a filter rack for the installation of the air filter, or the filter may be installed as part of the return air duct system.
Supply and return duct system must be adequately sized to meet the system’s air requirements and static pressure capabilities. The duct system should be insulated with a minimum of 1" thick insulation with a vapor barrier in conditioned areas or 2" minimum in unconditioned areas.
1" X 3/4" X 3/4"
REDUCING
TEE WITH
PLUG
LENNOX* P−TRAP
49P66, J−TRAP #
91P90 OR ANY
PVC SCH 40 P− OR
J−TRAP 3/4"
FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL) TRAPS ARE REQUIRED ON ALL DRAIN LINES CONNECTED TO COIL.
2"
(51MM)
TRAP DEPTH
TO APPROVED
DRAIN
DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)
Table 3. Unit Air Filter Size Chart
Model Filter Size
−018 / −024 15" x 20" (Effective 22 Mar 11)
−030 / −036 18" x 20"
−037 through −060 18" x 25"
Supply plenum should be the same size as the flanged opening provided around the blower outlet and should extend at least 3 ft. from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.
INSTALLING DUCT SYSTEM
Install the conditioned air plenum, ducts and air filters (not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air−Conditioning Systems (latest edition).
Connect supply air duct to the flange on top of the air handler. If an isolation connector is used, it must be nonflammable.
505059M 0511
Page 8
A return air duct system is recommended. If the unit is installed in a confined space or closet, a return connection must be run, full size, to a location outside the closet.
Connecting Refrigerant Lines
Refrigerant lines must be connected by a qualified technician in accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dehydrated, refrig­erant−grade copper lines. Air handler coils should be installed only with specified line sizes for approved sys­tem combinations.
Handle the refrigerant lines gently during the installation process. Sharp bends or possible kinking in the lines will cause a restriction.
Do not remove the caps from the lines or system connec­tion points until connections are ready to be completed.
WARNING
There must be an airtight seal between the bottom of the air handler and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas−fueled appliance (i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed.
IMPORTANT
When sealing the cabinet, be sure to seal closed any space around the holes where the drain lines exit the cabinet using duct tape and/or Permagum. Warm air must not be allowed to enter through any gaps or holes in the cabinet.
Make sure the liquid line and suction line entry points are sealed with either Armaflex material or with Permagum. Permagum may also be used to seal around the main and auxiliary drains and around open areas of electrical inlets.
1. Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit. Run the lines in as direct a path as possible avoiding unnecessary turns and bends.
2. Make sure that the suction line is insulated over the entire exposed length and that neither suction nor liquid lines are in direct contact with floors, walls, duct system, floor joists, or other piping.
3. Connect the suction and liquid lines to the evaporator coil.
4. To avoid damaging the rubber grommets in the cabinet while brazing, slide the rubber grommets over the refrigerant lines until they are away from the heat source.
5. Braze using an alloy of silver or copper and phosphorus with a melting point above 1,100°F.
NOTE  Do not use soft solder.
6. Reinstall the rubber grommets after brazing is finished.
7. Make sure outdoor unit has been put in place according to the Installation Instructions and is connected to the refrigerant lines.
Sealing the Unit
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow−off problems. This is especially important when the unit is installed in an unconditioned area.
Electrical Connections
WARNING
Electric shock hazard! − Disconnect all power supplies before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
WARNING
Electric Shock Hazard.
Can cause injury or death.
Foil-faced insulation has conductive characteristics sim­ilar to metal. Be sure there are no electrical connections within a ½" of the insulation. If the foil-faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e.g. fuses or circuit breakers), the current can be enough to cause an electric shock hazard that could cause person­al injury or death.
S All field wiring must be done in accordance with
National Electrical Code, applicable requirements of UL and local codes, where applicable.
S Electrical wiring, disconnect means and over−current
protection are to be supplied by the installer. Refer to the air handler rating plate for maximum over−current
Page 9
CB(X)26UH SERIES
protection, minimum circuit ampacity, as well as operating voltage.
S The power supply must be sized and protected
according to the specifications supplied on the product.
S This air handler is factory−configured for 240 volt,
single phase, 60 cycles. For 208−volt applications, see 208 Volt Conversion" later in this section.
S For optional field-installed electric heat applications,
refer to the instructions provided with the accessory for proper installation.
WARNING
USE COPPER CONDUCTORS ONLY
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Route the field supply wires to the air handler electrical connection box.
WARNING
Electrically ground air handler. Connect ground wire to ground terminal marked GND".
Failure to do so can result in death or elec­trical shock.
4. Use UL−listed wire nuts to connect the field supply conductors to the unit black and yellow leads, and the ground wire to ground terminal marked GND."
5. Replace the air handler access panel.
CONNECT BLACK TO BLACK
CONNECT UNIT ’S YELLOW CONDUC­TOR TO WHITE FIELD SUPPLY CONDUCTOR
GND
CONNECT GROUND WIRE TO GROUND TERMI­NAL MARKED GND"
Figure 12. Making Electrical Connections
208 VOLT CONVERSION
WARNING
Electric shock hazard! − Disconnect all power supplies before servicing.
Replace all parts and panels before op­erating. Failure to do so can result in death or electrical shock.
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Using the wiring diagram in figure 13 as a reference, move the 2 connected black transformer leads from the 240 volt terminal on the transformer to the 208 volt terminal on the transformer.
505059M 0511
Page 10
WARNING
USE COPPER
CONDUCTORS
ONLY
Figure 13. Wiring Diagram
Page 11
CB(X)26UH SERIES
AIR HANDLERTHERMOSTAT
R
G
SEE
NOTE
BU
COOLING-ONLY APPLICATION
AIR HANDLERTHERMOSTAT
R
G
W
BK
SEE
NOTE
BU
CONDENSING
UNIT
NOTE
SEE
NOTE
R
G
SEE
BU
W
HEAT-ONLY APPLICATION
AIR HANDLERTHERMOSTAT HEAT PUMP UNIT
R
G
BU
W
BK
AIR HANDLERTHERMOSTAT
CONDENSING
UNIT
COOLING APPLICATION WITH
ELECTRIC HEAT
HEAT PUMP APPLICATION WITH ELECTRIC HEAT
NOTE − Connect common wire only if required (Refer to the appropriate thermostat installation instructions)
Figure 14. Low Voltage Connections
Airflow  Cooling Blower Speed
The cooling blower speed is factory configured to provide correct airflow for an outdoor unit that matches the maximum cooling capacity rating of the air handler.
If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler, the cooling blower speed may need to be changed. Refer to Blower Performance Chart, table 4.
CHANGE BLOWER SPEED
NOTE  Refer to wiring diagram (figure 13) and blower performance (table 4).
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Locate pin number 2 on the blower relay. Two black wires are connected to this terminal pin. One connects to pin number 5 on the blower relay, one connects to an in−line splice connecting to a red wire.
4. Remove the wire going to the 4−pin blower motor connector from the splice.
5. Connect the blower lead [Red (LO), Black (HI)] onto the splice from the 4−pin blower motor connector.
NOTE  Reuse the factory−installed plastic cap on whichever wire is not used.
WARNING
Electric shock hazard! − Disconnect all
6. Replace all panels.
7. Reconnect power.
power supplies before servicing.
Replace all parts and panels before op­erating.
Failure to do so can result in death or elec­trical shock.
NOTES FOR TABLE 4 − All air data measured external to unit with 1 inch non−pleated air filter in place.
Electric heaters have no appreciable air resistance. All factory settings are high−speed. All data given while air handler is operating with a dry dx coil.
505059M 0511
Page 12
Model External Static Pressure
in. w.g. Pa cfm L/s cfm L/s
.10 25 1020 460 755 340 .20 50 960 435 715 325
−018
(LOW SPEED)
−024
(MEDIUM
SPEED)
−030
(MEDIUM
SPEED)
−036
(LOW SPEED)
−037
(LOW SPEED)
−042
(MEDIUM
SPEED)
−048
(supported in
TXV only)
(MEDIUM
SPEED)
−060
(MEDIUM
SPEED)
.30 75 885 400 675 305 .40 100 800 365 625 285 .50 125 690 315 570 260 .60 150 525 250 500 235
.10 25 1040 470 1000 455 .20 50 980 445 940 425 .30 75 905 410 870 395 .40 100 815 370 785 355 .50 125 705 320 680 310 .60 150 535 250 530 250
.10 25 1350 610 1145 520 .20 50 1290 585 1090 495 .30 75 1225 555 1030 465 .40 100 1150 520 960 435 .50 125 1065 485 875 395 .60 150 965 455 775 365
.10 25 1560 705 1405 635 .20 50 1480 670 1340 610 .30 75 1390 630 1270 575 .40 100 1290 585 1185 540 .50 125 1170 530 1090 495 .60 150 1015 480 975 460
.10 25 1570 740 1330 625 .20 50 1520 715 1310 620 .30 75 1440 680 1250 590 .40 100 1300 615 1180 555 .50 125 1170 550 1070 505 .60 150 950 450 840 395
.10 25 1940 880 1785 810 .20 50 1845 835 1705 775 .30 75 1745 790 1615 730 .40 100 1630 740 1515 685 .50 125 1495 680 1400 635 .60 150 1330 630 1265 595
.10 25 1945 880 1870 850 .20 50 1860 845 1790 810 .30 75 1765 800 1700 770 .40 100 1660 155 1600 725 .50 125 1540 700 1485 675 .60 150 1395 660 1350 635
.10 25 2160 980 2075 940 .20 50 2065 935 1985 900 .30 75 1960 890 1885 855 .40 100 1845 835 1775 805 .50 125 1710 775 1645 745 .60 150 1550 730 1495 705
Table 4. CB(X)26UH Blower Performance (2−Speed)
Air Volume at Specific Blower Taps
High (Black) Low (Red)
Page 13
CB(X)26UH SERIES
Model Ext. Static Pressure
in. w.g. Pa cfm L/s
0.10 25 655 309 794 375 1074 507
0.20 50 647 305 786 371 1000 472
−018
(LOW SPEED)
−024
(MEDIUM
SPEED)
−030
(MEDIUM
SPEED)
−036
(LOW SPEED)
−042
(MEDIUM
SPEED)
−048
(MEDIUM
SPEED)
−060
(MEDIUM
SPEED)
0.30 75 628 296 747 353 913 431
0.40 100 578 273 672 317 809 382
0.50 125 480 227 555 262 672 317
0.60 150
0.10 25 655 309 794 375 1074 507
0.20 50 647 305 786 371 1000 472
0.30 75 628 296 747 353 913 431
0.40 100 578 273 672 317 809 382
0.50 125 480 227 555 262 672 317
0.60 150
0.10 25 860 406 1020 481 1199 566
0.20 50 851 402 1006 475 1195 564
0.30 75 842 397 1003 473 1182 558
0.40 100 813 384 963 454 1121 529
0.50 125 721 340 886 418 1033 487
0.60 150
0.10 25 1135 536 1354 639 1494 705
0.20 50 1120 529 1345 635 1469 693
0.30 75 111 2 525 1317 621 1417 669
0.40 100 1079 509 1260 595 1336 630
0.50 125 995 470 1090 514 1250 590
0.60 150
0.10 25 1202 567 1404 663 1540 727
0.20 50 1192 563 1413 667 1530 722
0.30 75 1160 547 1386 654 1507 711
0.40 100 1116 527 1303 615 1386 654
0.50 125 998 471 1192 563 1254 592
0.60 150
0.10 25 1593 752 1759 830 1886 890
0.20 50 1582 747 1709 806 1820 859
0.30 75 1526 720 1636 772 1742 822
0.40 100 1444 681 1538 726 1606 758
0.50 125 1318 622 1395 658 1446 682
0.60 150
0.10 25 1782 841 2066 975 2109 995
0.20 50 1755 828 1960 925 2067 975
0.30 75 1672 789 1860 878 1949 920
0.40 100 1554 733 1714 809 1770 835
0.50 125 1393 657 1476 697 1586 748
0.60 150
Table 5. CB(X)26UH Blower Performance (3−Speed)
Air Volume at Specific Blower Taps
Low (Red) Med (Blue) High (Black)
cfm L/s
cfm L/s
505059M 0511
Page 14
Check−out Procedures
IMPORTANT
During installation, service or maintenance, make sure that copper tubing does not rub against metal edges or other copper tubing. Care should also be taken to ensure that tubing does not become kinked. Use wire ties to se­cure tubing to prevent movement.
Do not secure electrical wires to tubing that carries hot refrigerant gas. Heat from the tubing may melt the wiring insulation causing a short circuit.
NOTE − Refer to outdoor unit installation instructions for system start−up instructions and refrigerant charging instructions.
PRE-START-UP CHECKS
S Is the air handler properly and securely installed? S If horizontally configured, is the unit sloped up to 1/4
inch toward drain lines?
S Will the unit be accessible for servicing? S Has an auxiliary pan been provided under the unit with
separate drain for units installed above a finished ceiling or in any installation where condensate overflow could cause damage?
S Have ALL unused drain pan ports been properly
plugged?
S Has the condensate line been properly sized, run,
trapped, pitched, and tested?
S Is the duct system correctly sized, run, sealed, and
insulated?
S Have all cabinet openings and wiring been sealed? S Is the indoor coil factory-installed TXV properly sized
for the outdoor unit being used?
S Have all unused parts and packaging been disposed
of?
S Is the filter clean, in place, and of adequate size? S Is the wiring neat, correct, and in accordance with the
wiring diagram?
S Is the unit properly grounded and protected (fused)? S Is the thermostat correctly wired and in a good
location?
S Are all access panels in place and secure?
CHECK BLOWER OPERATION
S Set thermostat to FAN ON. S The indoor blower should come on.
CHECK COOLING OPERATION
S Set thermostat to force a call for cooling
(approximately 5ºF lower than the indoor ambient temperature).
S The outdoor unit should come on immediately and the
indoor blower should start between 30 − 60 seconds later.
S Check the airflow from a register to confirm that the
system is moving cooled air.
S Set the thermostat 5ºF higher than the indoor
temperature. The indoor blower and outdoor unit should cycle off.
CHECK ELECTRIC HEATER (IF USED)
S Set thermostat to call for auxiliary heat (approximately
5°F above ambient temperature). The indoor blower and auxiliary heat should come on together. Allow a minimum of 3 minutes for all sequencers to cycle on.
S Set the thermostat so that it does not call for heat.
Allow up to 5 minutes for all sequencers to cycle off.
Operation
COOLING (COOLING ONLY OR HEAT PUMP)
When the thermostat calls for cooling, 24 volts is put on the blower time−delay relay coil. After a delay, the indoor blower relay energizes. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
On heat pumps, circuit R and O energizes the reversing valve, switching the valve to the cooling position. (The reversing valve remains energized as long as the thermostat selector switch is in the COOL position.)
At the completion of the cooling demand and after the relay’s time-delay, the compressor and outdoor fan will cycle off.
HEATING (ELECTRIC HEAT ONLY)
When the thermostat calls for heat, the circuit between R and W is completed, and the heat sequencer is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat sequencer can be connected with the first sequencer to W on the thermostat subbase, or they may also be connected to a second stage on the subbase.
HEATING (HEAT PUMP)
When the thermostat calls for heating, 24 volts is put on the blower time−delay relay coil. After a delay, the normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor. Circuit R and G energizes the blower relay, starting the indoor blower motor.
If the room temperature should continue to fall, the circuit between R and W1 is completed by the second-stage heat room thermostat. Circuit R−W1 energizes a heat sequencer. The completed circuit will energize supplemental electric heat (if applicable). Units with a second heat sequencer can be connected with the first sequencer to W1 on the thermostat. They may also be connected to a second heating stage W2 on the thermostat subbase.
TIME DELAY RELAY
On early production units, the indoor blower relay energizes after a 30 second delay and it remains energized for 30 seconds after the call is satisfied. The indoor blower will remain on for approximately 30 seconds before cycling off.
Page 15
CB(X)26UH SERIES
In January 2006, the blower relay was changed to 1 second delay ON and 45 second delay OFF.
Cabinet Insulation
EMERGENCY HEAT (HEATING HEAT PUMP)
If the selector switch on the thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat (if applicable). A jumper should be placed between W2 and E on the thermostat subbase so that the electric heat control will transfer to the first-stage heat on the thermostat. This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position.
Accessories
Contact your Lennox dealer for the following accessories:
S Electric Heat KitSee the accessory kit label on the
front panel of the air handler for the electric heat kit options and accessories.
Maintenance
IMPORTANT
Do not operate system without a filter. A filter is required to protect the coil, blower, and internal parts from exces­sive dirt and dust. The filter is placed in the return duct by the installer.
IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation. In­sulation loses its insulating value when wet, damaged, separated or torn.
Matt- or foil−faced insulation is installed in indoor equipment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet. The temperature/humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal corrosion and subsequently, component failure.
REPAIRING DAMAGED INSULATION
Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all−purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil−faced tape.
S Inspect air filters at least once a month and replace or
clean as required. Dirty filters are the most common cause of inadequate heating or cooling performance.
S Replace disposable filters. Cleanable filters can be
cleaned by soaking in mild detergent and rinsing with cold water.
S Install new/clean filters with the arrows on the side
pointing in the direction of airflow. Do not replace a cleanable (high velocity) filter with a disposable (low velocity) filter unless return air system is properly sized for it.
S If water should start coming from the secondary drain
line, a problem exists which should be investigated and corrected. Contact a qualified service technician.
GLUE −make sure there is full coverage of glue on the metal or insulation so there are no areas where air pockets may form which can lead to sweating.
1. CUT INSULATION IN X PATTERN
2. APPLY GLUE
3. PRESS GLUED TABS AGAINST CABINET
Figure 15. Repairing Insulation
505059M 0511
Page 16
Loading...