Lennox Cb-19-21, Cb19-26, Cb19-31, Cb19-41, Cb19-51 Specification Data

...
ENGINEERING DATA
COILS – BLOWER COIL UNITS
CB19 AND CBH19 SERIES
UP-FLOW, DOWN-FLOW AND HORIZONTAL
BLOWER COIL UNITS
*12,600 to 65,500 Btuh (3.7 to 19.2 kW) Cooling Capacity
11,500 to 60,000 Btuh (3.4 to 17.6 kW) Heat Pump Heating Capacity
6,400 to 102,400 Btuh (1.9 to 30.0 kW) Optional Electric Heat
*ARI Standard 210/240 Ratings With Matching Outdoor Unit
CB19/
CBH19
Bulletin #210056
January 1995
Supersedes
Applications —
signed for multi-position installation in a basement, utility room, alcove, closet, crawlspace or attic. Units are applicable to expansion valve systems in cooling applications and check and expansion valve systems in heat pump applica­tions. Units have factory installed check and expansion valve. Several models are available in varying sizes with a wide range of cooling and heating capacities. See Condensing Unit bulletins in section Cooling Units — Condensing Units for cooling capacities. See Heat Pump Outdoor Unit Bulletins in section Heat Pumps — Matched Remote Systems for cooling and heating capacities. Optional field installed electric heaters are available in several sizes for additive heating capacity.
CB19 models are applicable to up-flow or down-flow dis­charge air applications. Units are shipped for up-flow ap­plications and may easily be field converted to the down­flow position by turning the unit upside down and repositioning the coil, drip shields and cabinet access panel. Filters are not furnished and must be provided by the install­er. An optional side return air adapter with filter(s) is avail­able for up-flow applications only. An optional additive base is available for models with electric heat installed in the down-flow position on combustible floors.
CBH19 models are designed for horizontal discharge air ap­plications. Units are furnished with left hand air discharge as standard and may be field changed to right hand discharge by turning the unit over (end for end) and repositioning the coil. CBH19-51 and CBH19-65 models are furnished in a two piece cabinet with blower and optional electric heaters in one sec­tion and the indoor coil in the other. Hardware is furnished for field connection of cabinets. Filters are not furnished and must be provided by the installer.
The CB19 and CBH19 blower coil units are de-
CB19 MODEL — UP-FLO CB19 MODEL — DOWN-FLO
CBH19 MODEL — HORIZONTAL
Typical Applications
Horizontal Installation
Up-Flow Installation
with optional electronic air cleaner
The maple leaf symbol in this bulletin denotes Canadian only usage where applicable
NOTE — Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Down-Flow Installation
1995 Lennox Industries Inc.
FEATURES
Completely Tested —
ing condensing units in the Lennox Research Laboratory envi­ronmental test room in accordance with ARI Standard 210/240-89. Optional electric heaters are rated in accordance with U.S. Department of Energy (DOE) test procedures and Federal Trade Commission (FTC) labeling regulations. Blower performance data is according to actual unit tests conducted in Lennox air test chamber. Blower-coil units and components within are bonded for grounding to meet safety standards for servicing required by U.L., C.S.A., CEC and NEC.
Cabinet —
completely insulated with thick fiberglass insulation. The pre­painted steel cabinets have a finish of mildly textured enamel with a primer coat on the unpainted side of all panels. Remov­able panels provide complete service access. Electrical inlets are provided in both sides of cabinet. Return air entry is pos­sible in either side or bottom of cabinet on up-flow units.
Drain Pan —
pipe drains extended outside of cabinet for ease of connec­tion. See dimension drawings.
Constructed of heavy gauge galvanized steel and
Deep, corrosion resistant drain pan has dual
Direct Drive Blower —
built direct drive blower. Each blower is statically and dynami­cally balanced as an assembly before it is installed in the unit. Multi-speed motor is resiliently mounted. A choice of blower speeds is available. See blower performance tables. Change of blower speeds is easily accomplished by a simple change in wiring.
Refrigerant Line Connections —
lines have sweat connections and extend outside of the cabinet for ease of connection. See dimension drawings for locations.
Check and Expansion Valve Furnished —
sion valve furnished and factory installed on all models.
Copper Tube/Enhanced Fin Evaporator Coil —
signed twin coils, assembled in a ‘V’ configuration, provides extra large surface and contact area, excellent heat transfer and low air resistance for maximum efficiency. Precise cir­cuiting gives uniform refrigerant distribution. Lennox fabri­cated coil is constructed of precisely spaced ripple-edged alu­minum fins fitted to durable seamless copper tubes. Fins are strengthened to resist bending and are equipped with collars that grip tubing for maximum contact area. Lanced fins pro­vide maximum exposure of fin surface to air stream. Flared shoulder tubing joints and silver soldering provide tight, leak­proof joints. Long life copper tubing is easy to field service. Coil is thoroughly factory tested under high pressure to in­sure leakproof construction.
Transformer and Blower Cooling Relay —
former and blower cooling relay are furnished as standard equipment and are factory installed in the unit control box. A terminal strip is also furnished as standard.
Blower coil units are tested with match-
Equipped with a Lennox designed and
Suction (vapor) and liquid
Check and expan-
Lennox de-
A 24 volt trans-
OPTIONAL ACCESSORIES (Must Be Ordered Extra)
Electric Heat (Optional) —
internal to the unit cabinet and are available in several kw sizes, see Electric Heat table. The helix wound nichrome bare heat­ing elements are exposed directly in the air stream resulting in instant heat transfer, low element temperatures and long ser­vice life. Each heating element is equipped with accurately lo­cated limit control with fixed temperature off setting and auto­matic reset. In addition, elements have supplemental thermal cutoff safety fuses providing positive protection in case of ex­cessive temperatures. Cutoff fuses are mounted external to the element face plate for quick and easy replacement. Ther­mal sequencer relay brings the heating elements on and off line, in sequence and equal increments, with a time delay between each element. Sequencer also initiates and terminates blower operation. Heating control relay(s), is furnished as standard. Control box and access cover are constructed of heavy gauge galvanized steel. Heaters are factory assembled with controls installed and wired and only require plug-in field connection.
Additive electric heaters field install
Circuit Breakers —
(208/240v-1ph) and ECB19-15,-20 and -25 kw (208/240v-3ph) electric heaters are equipped with circuit breakers to provide overload and short circuit protection. Breakers are factory wired and mounted on electric heat unit. Circuit breakers are current sensitive and temperature actuated to shut off heater if current draw is excessive. Must be reset manually. Circuit breakers qualify as the disconnect means at unit in many areas and eliminate the need for a field provided disconnect. Consult local electrical code in your area.
ECB19-12.5,-15,-20,-25 and -30 kw
Single-Point Power Source Control Box (Optional) —
Box (21H39) may be used with optional electric heat when two or three circuits (if required by code) are specified. Field installs external to the unit cabinet on either side or top. Pro­vides single power service connection to the unit. Constructed of heavy gauge steel with baked enamel finish, prepunched mounting holes, electrical inlet knockouts, and terminal strip. Removeable cover provides easy access. Box is 7” x 7” x 4” deep (178mm x 178mm x 102mm), shipping weight is 5 lbs. (2 kg.)
CCB1 EfficiencyPlus Humidity Control (Optional) —
CCB1 Humidity Control (35H00) is an electronic control which installs next to the room thermostat and allows the selection of the desired indoor humidity level in the cooling mode. During the heating season the control is inoperable. The CCB1 controls the indoor humidity by alter­ing the indoor blower speed and the compressor speed. Humidity level desired may be accomplished by adjusting a vertical slide to a set point on a scale of 40% thru 60% with 50% recommended as the ini­tial set point. Five indicator lights (MIN — MAX) in a bar graph configuration indicate the difference in the actual rel­ative humidity and the set point. This indicates the demand imposed on the system equipment, the more lights on, the longer the equipment will operate to obtain the desired hu­midity level. If no lights are on, the humidity is at or below the set point. Control is not furnished and must be ordered extra. Requires EBR1 Blower Relay Kit
EBR1 Blower Relay Kit (Optional) —
(75H90) allows CCB1 to be used with CB19/CBH19 blower
coil units.
Down-Flow Additive Base (Optional) —
base is required for models with electric heat installed in the down-flow position on combustible floors. Base is not furnished and must be ordered extra for field installation. See Specifica­tions table and dimension drawing.
Air Filters (Not Furnished) —
Specifications tables for sizes. Filter rails are provided in return air opening of unit. See dimension drawings.
Filters must be ordered extra. See
EBR1 Blower Relay Kit
An optional additive
CB19 Up-Flow Side Return Air Filter Adaptor (Optional) —
Field installs on either side return air opening of up-flow cabi­net. Constructed of heavy gauge galvanized steel with a baked­on paint finish. Equipped with flanges for ease of duct connec­tion. Access panel allows easy removal an replacement of filter(s). One inch thick (25mm) frame type filter is furnished as standard. Media is washable or vacuum cleanable oil coated polyurethane. CB19-21 thru 41 adaptor requires one filter. CB19-51 and CB19-65 model has two. See Specification table for sizes. CB19-51 and CB19-65 fiberglass insulated adaptor is shipped knocked down and must be field assembled.
—2—
Control
The
SPECIFICATIONS — CB19 UP-FLOW/DOWN-FLOW
p
{{Number and size of filters
Filter Adaptor
ECB19-2.5
ECB19-5
ECB19-6
ECB19-75
ECB19-8
Heat
ECB19-10
ECB19-12.5
ECB19-15
ECB19-20
ECB19-25
ECB19-30
Evaporator
Coil
Condensate drain connection (pvc) — in. (mm) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19)
Nominal cooling capacity — tons (kW) 1-1/2 (5.3) 2 (7.0) 2-1/2 (8.8) 3 (10.6) 4 (14.1) 5 (17.6)
Refrigerant HCFC-22
Blower wheel nominal diameter x width — in. (mm)
Blower motor output — hp (W) 1/10 (75) 1/5 (149) 1/3 (149) 1/3 (249) 1/3 (249) 1/2 (373)
Electrical characteristics 208/230 volts — 60 hz — 1 ph 208/230/460 volt 60 hz – 1 ph
Shipping weight — lbs. (kg) 1 package 143 (65) 146 (66) 167 (76) 167 (76) 209 (95) 213 (97)
Side Return Air
(Up-Flow Only)
Down-Flow
Combustible Base
Electric
Capacity
{Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations {{Filters are not furnished and must be ordered extra.
*Includes additional blower motor heat capacity.
Model Number CB19-21 CB19-26 CB19-31 CB19-41 CB19-51 CB19-65
Net face area — ft.2 (m2) 4.22 (0.39) 4.22 (0.39) 5.27 (0.49) 5.27 (0.49) 7.0 (0.65) 7.0 (0.65)
Tube outside diameter — in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Number of rows 3 3 3 3 3 3
Fins per inch (fins per m) 12 (472) 12 (472) 13 (512) 13 (512) 14 (551) 14 (551)
Suct. (vapor) line conn. – in. (mm) sweat 5/8 (16) 5/8 (16) 3/4 (19) 3/4 (19) 7/8 (22.2) 1-1/8 (28)
Liquid line conn. — in. (mm) sweat 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
9 x 7
(229 x 178)
in. (1) 16 x 20 x 1 (1) 20 x 20 x 1 (1) 20 x 25 x 1
mm (1) 406 x 508 x 25 (1) 508 x 508 x 25 (1) 508 x 635 x 25
b Optional Accessories (Must Be Ordered Extra) b
Catalog number 95G73 95G74 95G75
Number and size
of filters
Shipping weight — lbs. (kg) 4 (2) 5 (2) 24 (11)
in. (1) 16 x 20 x 1 (1) 20 x 20 x 1 (2) 16 x 25 x 1
mm (1) 406 x 508 x 25 (1) 508 x 508 x 25 (2) 406 x 635 x 25
Catalog number 85G52 85G53 85G54
Ship. wt. – lbs. (kg) 8 (4) 8 (4) 8 (4)
*Output — Btuh (kW) 9,000 (2.6) 9,500 (2.8) - - - - - - - - - - - - - - - -
{A.F.U.E.
*Output — Btuh (kW) 18,000 (5.3) 18,000 (5.3) 18,000 (5.3) 18,000 (5.3) 19,000 (5.6) - - - -
{A.F.U.E.
*Output — Btuh (kW) 21,000 (6.2) 22,000 (6.4) 22,000 (6.4) 22,000 (6.4) 23,000 (6.7) - - - -
{A.F.U.E.
*Output — Btuh (kW) 25,000 (7.3) 25,000 (7.3) 25,000 (7.3) 25,000 (7.3) 26,000 (7.6) - - - -
{A.F.U.E.
*Output — Btuh (kW) 28,000 (8.2) 28,000 (8.2) 29,000 (8.5) 29,000 (8.5) 29,000 (8.5) 30,000 (8.8)
{A.F.U.E.
*Output — Btuh (kW) 35,000 (10.3) 35,000 (10.3) 35,000 (10.3) 35,000 (10.3) 36,000 (10.5) 37,000 (10.8)
{A.F.U.E.
*Output — Btuh (kW) - - - - 44,000 (12.9) 44,000 (12.9) 44,000 (12.9) 45,000 (13.2) 46,000 (13.5)
{A.F.U.E.
*Output — Btuh (kW) - - - - 52,000 (15.2) 52,000 (15.2) 53,000 (15.5) 53,000 (15.5) 54,000 (15.8)
{A.F.U.E.
*Output — Btuh (kW) - - - - - - - - - - - - 70,000 (20.5) 70,000 (20.5) 71,000 (20.8)
{A.F.U.E.
*Output — Btuh (kW) - - - - - - - - - - - - - - - - 87,000 (25.5) 88,000 (25.8)
{A.F.U.E.
*Output — Btuh (kW) - - - - - - - - - - - - - - - - - - - - 105,000 (30.8)
{A.F.U.E.
100% 100% - - - - - - - - - - - - - - - -
100% 100% 100% 100% 100% - - - -
100% 100% 100% 100% 100% - - - -
100% 100% 100% 100% 100% - - - -
100% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100%
- - - - 100% 100% 100% 100% 100%
- - - - 100% 100% 100% 100% 100%
- - - - - - - - - - - - 100% 100% 100%
- - - - - - - - - - - - - - - - 100% 100%
- - - - - - - - - - - - - - - - - - - - 100%
9 x 8
(229 x 203)
10 x 7
(254 x 178)
10 x 9
(254 x 229)
11 x 8
(279 x 203)
12 x 9
(317 x 229)
—3—
SPECIFICATIONS — CBH19 HORIZONTAL
{{Numb
fil
Shippi
ht
lbs. (kg)
ECB19-5
ECB19-6
ECB19-7
ECB19-8
Heat
y
ECB19-10
Capacity
ECB19-12.5
ECB19-15
ECB19-20
ECB19-25
ECB19-30
Model Number CBH19-21 CBH19-26 CBH19-31 CBH19-41 CBH19-51 CBH19-65
Blower section - - - - - - - - - - - - - - - - B19-51 B19-65 Indoor coil section - - - - - - - - - - - - - - - - CH19-51 CH19-65
Net face area — ft.2 (m2) 4.22 (0.39) 4.22 (0.39) 5.27 (0.49) 5.27 (0.49) 7.22 (0.67) 7.22 (0.67) Tube outside diameter — in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Evaporator
Coil
Condensate drain connection (mpt) — in. (mm) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) (2) 3/4 (19) Nominal cooling capacity — tons (kW) 1-1/2 (5.3) 2 (7.0) 2-1/2 (8.8) 3 (10.6) 4 (14.1) 5 (17.6) Refrigerant HCFC-22
Blower wheel nominal diameter x width — in. (mm)
Blower motor output — hp (W) 1/10 (75) 1/5 (149) 1/3 (149) 1/3 (249) 1/3 (249) 1/2 (373)
Electrical characteristics 208/230v — 60 hz — 1 ph 208/230/460v 60 hz – 1 ph
Number of packages in shipment
Electric
Capacit
{Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations {{Filters are not furnished and must be ordered extra.
*Includes additional blower motor heat capacity.
Number of rows 3 3 3 3 3 3 Fins per inch (fins per m) 12 (472) 12 (472) 13 (512) 13 (512) 14 (551) 14 (551) Suct. (vapor) line conn. — in. (mm) sweat 5/8 (16) 5/8 (16) 3/4 (19) 3/4 (19) 7/8 (22.2) 1-1/8 (28) Liquid line connection — in. (mm) flare 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
er and size of
ng weig
9 x 7
(229 x 178)
in. (1) 16 x 20 x 1 (1) 20 x 20 x 1 (1) 20 x 25 x 1
ters
mm (1) 406 x 508 x 25 (1) 508 x 508 x 25 (1) 508 x 635 x 25
Complete unit 149 (68) 149 (68) 176 (80) 178 (81) 240 (109) 242 (109) Blower section - - - - - - - - - - - - - - - - 118 (54) 120 (54)
9 x 8
(229 x 203)
10 x 7
(254 x 178)
10 x 9
(254 x 229)
11 x 8
(279 x 203)
Coil section - - - - - - - - - - - - - - - - 122 (55) 122 (55)
1 1 1 1 2 2
b Optional Accessories (Must Be Ordered Extra) b
ECB19-2.5
*Output — Btuh (kW) 9,000 (2.6) 9,500 (2.8) - - - - - - - - - - - - - - - -
{A.F.U.E. 99.8% 99.8% - - - - - - - - - - - - - - - -
*Output — Btuh (kW) 18,000 (5.3) 18,000 (5.3) 18,000 (5.3) 18,000 (5.3) 19,000 (5.6) - - - -
{A.F.U.E. 99.7% 99.7% 99.9% 100% 100% - - - -
*Output — Btuh (kW) 21,000 (6.2) 22,000 (6.4) 22,000 (6.4) 22,000 (6.4) 23,000 (6.7) - - - -
{A.F.U.E. 99.7% 99.7% 99.9% 100% 100% - - - -
*Output — Btuh (kW) 25,000 (7.3) 25,000 (7.3) 25,000 (7.3) 25,000 (7.3) 26,000 (7.6) - - - -
{A.F.U.E. 99.7% 99.7% 99.9% 100% 100% - - - -
*Output — Btuh (kW) 28,000 (8.2) 28,000 (8.2) 29,000 (8.5) 29,000 (8.5) 29,000 (8.5) 30,000 (8.8)
{A.F.U.E. 99.7% 99.7% 99.8% 100% 100% 100%
*Output — Btuh (kW) 35,000 (10.3) 35,000 (10.3) 35,000 (10.3) 35,000 (10.3) 36,000 (10.5) 37,000 (10.8)
{A.F.U.E. 99.7% 99.7% 99.8% 99.9% 100% 100%
*Output — Btuh (kW) - - - - 44,000 (12.9) 44,000 (12.9) 44,000 (12.9) 45,000 (13.2) 46,000 (13.5)
{A.F.U.E. - - - - 99.5% 99.7% 99.9% 100% 100%
*Output — Btuh (kW) - - - - 52,000 (15.2) 52,000 (15.2) 53,000 (15.5) 53,000 (15.5) 54,000 (15.8)
{A.F.U.E. - - - - 99.5% 99.7% 99.9% 100% 100%
*Output — Btuh (kW) - - - - - - - - - - - - 70,000 (20.5) 70,000 (20.5) 71,000 (20.8)
{A.F.U.E. - - - - - - - - - - - - 99.8% 99.8% 100%
*Output — Btuh (kW) - - - - - - - - - - - - - - - - 87,000 (25.5) 88,000 (25.8)
{A.F.U.E. - - - - - - - - - - - - - - - - 99.8% 99.9%
*Output — Btuh (kW) - - - - - - - - - - - - - - - - - - - - 105,000 (30.8)
{A.F.U.E. - - - - - - - - - - - - - - - - - - - - 99.9%
12 x 9
(317 x 229)
BLOWER DATA
UP-FLOW SIDE RETURN AIR FILTER ADAPTOR RESISTANCE
Air Volume Filter Resistance
cfm L/s in. wg. Pa
400 190 .01 2 600 285 .02 5
800 380 .03 7 1000 470 .05 12 1200 565 .08 20 1400 660 .08 20 1600 755 .08 20 1800 850 .09 22 2000 945 .09 22 2200 1040 .10 25 2400 1135 .10 25
—4—