Lennox ASC 020S, ASC 045D, ASC 025S, ASC 055D, ASC 070D Installation, Operating And Maintenance Manual

...
Page 1
INSTALLATION, OPERATING
AND MAINTENANCE
AIR COOLED CONDENSING UNIT
ASC/ASH
20 - 230 kW
www.lennoxemea.com
MIL152E-1217 01/2019
Page 2
TABLE OF CONTENTS
ASC/ASH
INSTALLATION OPERATION MAINTENANCE MANUAL
POINTS TO BEAR IN MIND
DATA PAGE FOR COMMISSIONING OF THE UNIT
1 -
GENERAL CHARACTERISTICS
1.1 4
Physical data
1.2 5
Electrical data
1.3 6
Fan performance
1.4 6
Operating limits
Piping drawings
1.5 7
Unit dimensions
1.6 11
2 -
INSTALLATION
2.1 12
Preliminary preparations
2.2 12
Unit acceptance
2.3 13
Unit location
2.4 13
Installation clearances
2.5 14
Inside location
2.6 15
Refrigerant connections
2.7 19
Electrical connections
2.8 21
Dry contact board control
2.9 22
Options installation
3 -
COMMISSIONING AND OPERATION
3.1 23
Preliminary checks before fi rst installation
Preliminary checks at fi rst installation
3.2 24
4 -
MAINTENANCE
4.1 25
Preventive maintenance
4.2 25
Corrective maintenance
4.3 26
Fault diagnosis
WARNING: Read this manual before carrying out installation, repair or maintenance work.
All the technical and technological information contained in this manual, including any drawings and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in the operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
• 1 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 3
• 2 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 4
POINTS TO BEAR IN MIND
DANGER AND WARNING SIGNS
Abrasive surfaces Low temperatures High temperatures Risk of injury from
moving objects
Electrical voltage Risk of injury from
rotating objects
ELECTRICAL CONNECTIONS
Make sure to switch off the power before installing, repairing or carrying out maintenance on the unit, in order to prevent serious electrical injury.
Keep local and national legislation in mind when installing the unit.
Standard Guidelines to Lennox equipment
All technical data contained in these operating instructions, including the diagrams and technical description remains the property of Lennox and may not be used (except for the purpose of familiarizing the user with the equipment), reproduced, photocopied, transferred or transmitted to third parties without prior written authorization from Lennox.
The data published in the operating instructions is based on the latest information available. We reserve the right to make modifi cations without notice.
We reserve the right to modify our products without notice without obligation to modify previously supplied goods.
These operating instructions contain useful and important information for the smooth operation and maintenance of your equipment.
The instructions also include guidelines on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault-free operation. Read the operating instructions carefully before starting the equipment, familiarize yourself with the equipment and handling of the installation and carefully follow the instructions. It is very important to be properly trained in handling the equipment. These operating instructions must be kept in a safe place near the equipment.
Like most equipment, the unit requires regular maintenance. This section concerns maintenance and management personnel. If you have any queries or would like to receive further information on any aspect relating to your equipment, do not hesitate to contact us.
The manufacturing of these units is made under the requirements of the ISO 9001 and ISO 14001.
• 3 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 5
DATA PAGE FOR UNIT COMMISSIONING
UNIT: ___________________________________________ SERIAL NUMBER : ___________________________________ CONTROL PANEL IDENTIFICATION CODE : _________________________________________________________________ INST ALLA TION ADDRESS: _______________________________________________________________________________ INSTALLER : _____________________________________ INSTALLER TEL : ____________________________________ INST ALLER ADDRESS : __________________________________________________________________________________
______________________________________________________________________________________________________ COMMISSIONING DATE : ________________________________________________________________________________ CHECKS : _____________________________________________________________________________________________
______________________________________________________________________________________________________ SUPPLY VOLTAGE : _______________________________ RATED VOLTAGE OF THE UNIT : _______________________
YES NO
Unit on shock absorbers Drainage with trap Main power supply connection Control panel connection Compressor oil level indicator
DATA INPUT:
COOLING CYCLE
Air intake temperature to the outdoor coil:
Air output temperature to the outdoor coil:
Circuit 1
High pressure:
Circuit 2 Circuit 1
Low pressure:
Circuit 2
ELECTRIC POWER CONSUMPTION (Amps)
Compressor 1: . . . . . . . . . . . . . . . . . . .
Compressor 2 : . . . . . . . . . . . . . . . . . .
Compressor 3 : . . . . . . . . . . . . . . . . . .
Outdoor fan section 1 . . . . . . . . . . . . .
Outdoor fan section 2 . . . . . . . . . . . . .
C 2ºC 1ºC 2ºC
Air intake temperature to the outdoor coil:
Air output temperature to the outdoor coil:
High pressure:
Low pressure:
Compressor 1: . . . . . . . . . . . . . . . . .
Compressor 2 : . . . . . . . . . . . . . . . .
Compressor 3 : . . . . . . . . . . . . . . . .
Outdoor fan section 1 . . . . . . . . . . .
Outdoor fan section 2 . . . . . . . . . . .
HEATING CYCLE
C 2ºC 1ºC
C Circuit 1 Circuit 2 Circuit 1 Circuit 2
Options installed : ____________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________ Comments : _________________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________
• 4 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 6
1. GENERAL CHARACTERISTICS
1.1.- PHYSICAL DATA
A S C 020 S N M 3 M
Air cooled
condensing unit
S: Outdoor unit Split
C: Cooling only
H: Heat pump
S: One Circuit
D: Two Circuits
Approximate cooling
Type of refrigerant
M: R-410A
- - -
capacity in kW
Units valid for combine with air treatment units
ASC/ADC: Cooling only unit R-410A. ASH/ADH: Heat pump unit R-410A.
MODELS
Type of compressor Scroll Number of compressors
Cooling only unit ASC/ADC
Net weight
Air fl ow m Refrigerant charge NITROGEN (*)
MODELS
Type of compressor Scroll Number of compressors
Net weight
Air fl ow m Refrigerant charge NITROGEN (*)
Heat pump unit ASH/ADH
Optional Soft starter Optional FP1
Cooling only unit ASC/ADC
Heat pump unit ASH/ADH
Optional Soft starter Optional FP1
ASC/ASH 020S 025S
255 443 452 520
kg
3
/h
258 452 463 537
3666
6800 9750 11500 11300
ASC/ASH 040S 045D
12222
255 443 452 481 520
kg
3
/h
258 452 463 499 537
36666
11000 9750+9750 11500+11500 11300+11300 11000+11000
1
N/A
055D 070D 085D
N/A
M: 400V/3/50
Number
of revision
030S 035S
n/a: not available
n/a: not available
MODELS
Type of compressor Scroll Number of compressors
Cooling only unit ASC/ADC
Net weight
Air fl ow m Refrigerant charge NITROGEN (*)
Heat pump unit ASH/ADH
Optional Soft starter Optional FP1
ASC/ASH 100D 120D
22344
632 797 906 1659 1679
kg
748 828 932 1684 1704
9 9 9 n/a n/a
40 40 40 80 80
3
/h
22700+18100 22700+18100 22700+22700 28600+28600 36000+36000
140D 200D 230D
(*) The units are supplied with nitrogen gas; this must be removed and the unit charged with refrigerant R-410A, depending on unit model.
(See page
21 to calculate refrigerant charge for model ASC/ADC and ASH/ADH units to work with Air treatment units).
R-410A factory refrigerant precharge kit is available as an option.
• 5 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 7
1. GENERAL CHARACTERISTICS
1.2.- ELECTRICAL DATA
ELECTRICAL CONSUMPTION FOR STANDARD UNITS
MODELS ASC/ASH
Voltage Ph/V/Hz
Maximum absorbed power (kW)
Compressor Fan Total power
Maximum current (A)
Compressor Fan Total current Start up current (A)
MODELS ASC/ASH
Voltage Ph/V/Hz
Maximum absorbed power (kW)
Compressor Fan Total power
Maximum current (A)
Compressor Fan Total current Start up current (A)
020S 025S 030S 035S 040S 045D 055D
3N~400V
50Hz
3~400V 50Hz
8,25 10,1 11,8 15,6 16,9 20,2 23,6
0,3 0,69 0,69 0,84 0,84 1,38 1,38
8,55 10,79 12,49 16,44 17,74 21,58 24,98
15 21 22 25,6 31 42 44
1,6 3 3,4 3,4 3,4 6 6,8 16,6 24 25,4 29 34,4 48 50,8 87,5 97,4 104 138 17,2 121 129
070D 085D 100D 120D 140D 200D 230D
3~400V 50Hz
31,1 33,8 42,6 45,6 55,9 78,8 88,2 1,68 1,68 3,05 3,05 4 4,2 8
32,78 35,48 45,65 48,65 59,9 83 96,2
51,2 62 77,6 84 102 142 159
6,8 6,8 6,4 6,4 8 9,6 16
58 68,8 84 90,4 110 151,6 175
167 206 221 228 292 302,9 358
ADDITIONAL ELECTRICAL CONSUMPTION FOR THE OPTIONS
FP1 OPTION ASC/ASH
Voltage Ph/V/Hz
Maximum absorbed power kW
Maximum current A
Start up current A
100D FP1
(Low Speed/
High speed)
2,00 / 6,20 2,00 / 6,20 1,00 / 5,2 5,8 / 14,2 2 / 10,4
3,2 / 9,8 3,2 / 9,8 1,6 / 8,2 9,6 / 22,8 3,2 / 16,4
3,2 / 9,8 3,2 / 9,8 1,6 / 8,2 9,6 / 22,8 3,2 / 16,4
120D FP1
(Low Speed/
High speed)
140D FP1
(Low Speed/
High speed)
3/400V/50Hz
200D FP1
(Low Speed/
High speed)
230D FP1
(Low Speed/
High speed)
• 6 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 8
1. GENERAL CHARACTERISTICS
1.3.- FAN PERFORMANCES
1.3.1.- CONDENSING UNIT WITH AVAILABLE HIGH PRESSURE FAN (OPTION)
Air fl ow data / FP1 option / Low speed.
MODELS
Fan type Fan number
Airfl ow rate m3/h
50
Absorbed power kW Airfl ow rate m3/h
75
Absorbed power kW
(Pa)
Airfl ow rate m3/h
100
Absorbed power kW Airfl ow rate m
Available static pressure
125
Absorbed power kW
Air fl ow data. FP1 option. High speed.
MODELS
Fan type Fan number
Airfl ow rate m3/h
50
Absorbed power kW Airfl ow rate m
100
sure Pa,
Available static pres-
Absorbed power kW Airfl ow rate m
125
Absorbed power kW
100D - 120D - 140D 200D 230D
Axial “short case” - direct coupling
900 r.p.m. (Low speed) 3~400V
24
19000 + 19000 28000 + 28000
510
18000 + 18000 24000 + 24000
5,1 10.2
17000 + 17000 22000 + 22000 N/A
5,2 10,4 N/A
3
/h
15000 + 15000 20000 + 20000 N/A
5,3 10,6 N/A
100D - 120D - 140D 200D - 230D
Axial “short case”-direct coupling
1450 r.p.m. (High speed) 3~400V
24
22000 + 22000 34000 + 34000
9,2 18,4
3
/h
20000 + 20000 28000 + 28000
9,3 18,6
3
/h
18000 + 18000 24000 + 24000
9,4 18,8
n/a: Not available
1.4.- OPERATING LIMITS (For installation with air treatment units. Example)
COOLING ONL Y UNITS
Cooling cycle operation
HEAT PUMP UNITS
Cooling cycle operation
Heating cycle operation
(*)
With low temperature 0ºC kit (option)
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
Maximum temperatures Minimum temperatures
32ºC DB
23ºC WB
(20S-25S-30S-45D-55D)
(35S-40S-70D-85D-100D-120D-140D)
45ºC
------------­47ºC
Maximum temperatures Minimum temperatures
32ºC DB
23ºC WB
20S-25S-30S-45D-55D)
-------------
(35S-40S-70D-85D-100D-120D-140D)
(See tables for heating capacities)
47ºC
27ºC DB
Depending on model
DB:
Dry bulb temperature.
21ºC DB
15ºC WB
+10ºC STANDARD UNIT
(*) / (**)
21ºC DB
15ºC WB
0ºC
15ºC DB
-10ºC DB
-11ºC WB
• 7 •
(**)
With option kit low temperature -15ºC or kit -15ºC and low noise level.
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
WB:
Wet bulb temperature
Page 9
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
COOLING ONLY UNITS
AIR TREATMENT UNIT. EXAMPLE CONDENSING UNIT
ASC 020S/025S/030S/035S/040S
DS
Fan
Coil
Expansion valve
(ELEMENTO OPCIONAL)
OPTION ELEMENT
AIR TREATMENT UNIT. EXAMPLE
Fan
Filter drier
Service valve option
C1
SVL1
Service valve option
Service valve
option
C1
Scroll compressor
LPT1
LP1
CH1
HP1
Suction accumulator (long distance connection option).
CONDENSING UNIT
ASC 045D/055D/070D/085D
LPT1
Scroll compressor
LP1
CH1
Suction accumulator (long distance connec­tion option).
HP1
Fan motor
HPT1
PT1
Coil
Fan motor
PT1
HPT1
Coil
DS
055D/070D/085D
Coil
Expansion
valve
Filter drier
SVL1
Service valve option
Service valve
option
LP2
LPT2
Scroll compressor
CH3
Suction accumulator ( long distance connec-
C2
SVL3
Expansion valve
OPTION ELEMENT
(ELEMENTO OPCIONAL)
Filter drier
Pressure gauge (5/16” to be fi tted by the installer) High pressure switch, circuit 1 Discharge sensor High pressure switch, circuit 2
DS HP2 SVL1 CH1
Liquid solenoid valve. (long distance option) To be connected by the installer to air treatment unit.
SVL3 CH3
Low pressure switch, circuit 1 High pressure transducer, circuit 1
LPT1 HPT1
Low pressure transducer, circuit 2 High pressure transducer, circuit 2
LPT2 HPT2
tion option).
Service valve option
HP1
Crankcase heater (Low ambient option) Crankcase heater (Low ambient option)
Outdoor temperature sensor
OS
Fan motor
HP2
PT2
HPT2
OS
Coil
• 8 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 10
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
COOLING ONLY UNITS
AIR TREATMENT UNIT. EXAMPLE
Coil
Fan
Expansion valve
Coil
Filter drier
CONDENSING UNIT
ASC 100D/120D/140D
LPT1
Service valve
option
C1
Suction accumulator (Low ambient
-15ºC and low noise level option).
Service valve option
LPT2
Service valve
option
C2
Scroll compressor
1
CH
Scroll compressor
2
CH
Scroll compressor
3
CH
Suction accumulator (Low ambient -15ºC and low noise level option).
HPT1
HPT2
Fan motor
Coil
Fan motor
Coil
Expansion valve
Filter drier
Service valve option
OPTION ELEMENT
Pressure gauge. (5/16” to be fi tted by the installer) High pressure switch, circuit 1.
Discharge sensor High pressure switch, circuit 2.
DS HP2
SVL1 CH...
Liquid solenoid valve. (long distance option) To be connected by the installer to air treatment unit.
SVL3 HPT1
Low pressure switch, circuit 1 High pressure transducer, circuit 2
LPT1 HPT2
HP1
Crankcase heater (Low ambient option)
High pressure transducer, circuit 1
Low pressure transducer, circuit 2 Outdoor temperature sensor
LPT2 OS
• 9 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 11
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
COOLING ONLY UNITS
CONDENSING UNIT
ASC 200-230D
Service valve
(option)
C1
Service valve
(option)
Service valve
(option)
C2
Scroll compressor
LPT1
LPT2
Fan motor
HP1
CH1
CH2
HP2
CH3
CH4
HPT1
Coil
Fan motor
HPT2
Coil
Service valve
(option)
OPTION ELEMENT
Pressure gauge (5/16” to be fi tted by the installer) Crankcase heater (0°C Low ambient option)
Low pressure switch
LPT1 HPT1
Circuit 1 Low pressure switch
LPT2 HPT2
Circuit 2 High pressure switch
HP1 OS
Circuit 1 High pressure switch
HP2
Circuit 2
CH...
High pressure transducer Circuit 1
High pressure transucer Circuit 2
Outdoor temperature sensor
• 10 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 12
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
HEAT PUMP UNITS
AIR TREATMENT UNIT. EXAMPLE
CONDENSING UNIT
ASH 020S/025S/030S/035S/040S
DS
Fan
Coil
Expansion valve
Check valve Check valve
(ELEMENTO OPCIONAL)
OPTION ELEMENT
AIR TREATMENT UNIT. EXAMPLE
Fan
Filter drier
LPT1
LP1 HP1
option
Scroll compressor
Service valve
C1
SVL1 SVL2
Service valve option
Check valve
CONDENSING UNIT
ASH 045/055D/070D/085D
Service valve option
C1
Scroll compressor
LP1 HP1 PT1
LPT1
H1
C
Suction accumulator (Long distance connection option)
1
H
C
Suction accumulator
(Remote connection option)
Filter drier
Check valve
4-way valve
4-way valve
Expansion valve
HPT1
PT1
Suction accu­mulator
HPT1
Fan motor
Coil
OS
Fan motor
Coil
DS
Expansion
Coil
64D/76D/86D
Filter drier
valve
Check valve Check valve
Check valve
SVL1
Service val-
ve option
LP2
LPT2
SVL2
Filter drier
Scroll compressor
3
H
C
Check valve
HP2
Service valve option
C2
Service valve
option
SVL3 SVL4
Check valve
HP1
HPT2
valve
Filter drier
Expansion
Check valve Check valve
(ELEMENTO OPCIONAL)
OPTION ELEMENT
Pressure gauge (5/16” to be fi tted by the installer) High pressure switch, circuit 1. Discharge sensor High pressure switch, circuit 2.
DS HP2 SVL1 CH...
Liquid solenoid valve (long distance option) To be connected by the installer to air treatment unit.
SVL3 HPT1 SVL2
Liquid solenoid valve (long distance option) High pressure transducer, circuit 2
SVL4
Low pressure switch, circuit 1 Outdoor temperature sensor
LPT1 OS
Low pressure transducer, circuit 2
LPT2
Suction accumulator (Long distance connection option)
Filter drier
Crankcase heater High pressure transducer, circuit 1
Expansion valve
4-way valve
Expansion valve
Check valve
Suction accumulator
Fan motor
HPT2
PT2
Suction accumu­lator
OS
Coil
• 11 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 13
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
HEAT PUMP UNITS
AIR TREATMENT UNIT. EXAMPLE
UNIDAD INTERIOR CIH 100D/120D/140D
DS
Fan
Coil
Expansion valve
Check valve
DS
Coil
Fan
Expansion valve
Check valve
OPTIONAL ELEMENT
Filter drier
Liquid receiver
Check valve
Filter drier
112D/128D
C1
SVL1
Check
valve
C2
SVL3
Check
valve
CONDENSING UNIT
UNIDAD EXTERIOR ASH 100D/120D/140D
Scroll compressor
option
Service valve
C
C
Scroll compres-
ve option
Service val-
SVL2
Check valve
option
Service valve
Service valve
option
Scroll compressor
C
SVL4
Check valve
1
H
2
H
3
H
sor
(Long distance connection
Filter
drier
Expansion valve
Check valve
Suction accumulator (Long
distance connection option)
Filter drier
Expansion valve
Check valve
4-way valve
Suction accumulator
option)
Suction accu­mulator
4-way valve
Suction accumulator
Fan motor
HPT1LPT1
PT1LP1
Coil
Fan motor
HPT2LPT2
PT2LP2
OS
Coil
Pressure gauge (5/16” to be fi tted by the installer) High pressure switch, circuit 1. Discharge sensor High pressure switch, circuit 2.
DS HP2 SVL1 CH...
Liquid solenoid valve. (long distance option) To be connected by the installer to air treatment unit.
SVL3 HPT1 SVL2
Liquid solenoid valve. (long distance option) High pressure transducer, circuit 2
SVL4
Low pressure switch, circuit 1 Outdoor temperature sensor
LPT1 OS
Low pressure transducer, circuit 2
LPT2
• 12 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
HP1
Crankcase heater High pressure transducer, circuit 1
HPT2
Page 14
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
HEAT PUMP UNITS
CONDENSING UNIT
ASH 200-230D
Service valve
(option)
Scroll compressor
Fan motor
C1
Service valve
(option)
Service valve
(option)
C2
LPT1
Scroll compressor
Scroll compressor
LPT2
Scroll compressor
CH1
CH2
CH3
CH4
Check valve
Filter drier
Check valve
HP1 HPT1
4-way valve
Suction accumulator
Expansion valve
HP2
4-way valve
HPT2
Coil
Fan motor
Coil
Service valve
(option)
OPTIONAL ELEMENT
Filter drier
Check valve
Pressure gauge (5/16” to be fi tted by the installer) Crankcase heater (0°C Low ambient option)
Low pressure switch
LPT1 HPT1
Circuit 1 Low pressure switch
LPT2 HPT2
Circuit 2 High pressure switch
HP1 OS
Circuit 1 High pressure switch
HP2
Circuit 2
• 13 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Suction accumulator
Expansion valve
CH...
High pressure transducer Circuit 1
High pressure transucer Circuit 2
Outdoor temperature sensor
Page 15
1. GENERAL CHARACTERISTICS
1.6.- DIMENSIONS OF ASC/ASH/ADC/ADH UNIT
1195
Main switch
(optional)
020S
660
Main switch (option)
Electrical box
1375
Power supply cable entry
Access to gas and liquid
lines
025S/030S/035S/040S
1
1
9
5
8
9
1635
0
Electrical box
045D/055D/070D/085D 100D/120D/140D
Main switch
(optional)
Electrical box
Main switch (optional)
Access to gas and liquid lines
Electrical box
Access to gas and
liquid lines
Access to gas and liquid lines
1960
Power supply
Main switch
Electrical box
(optional)
1195
2250
1635
Access to gas and
200D-230D
2128
2250
1420
liquid lines
Power supply
2227
2300
• 14 •
Power supply
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Access to gas and liquid lines
Page 16
2. INSTALLATION
2.1.- PRELIMINARY PREPATATIONS
All INSTALLATION, SERVICE and MAINTENANCE work must be carried out by QUALIFIED
PERSONNEL.
The unit must be transported in a VERTICAL POSITION on its metal mounting frame. Any other position may cause serious damage to the machine. When the unit is received, it should be checked to assure that it has received no shocks or other damage, following the instructions on the packaging. If there is damage, the unit may be rejected by notifying the LENNOX Distribution Department and stating why the machine is unacceptable on the transport agent’s delivery note. Any later complaint or claim made to the LENNOX Distribution Department for this type of damage cannot be considered under the Guarantee. Suffi cient space must be allowed to facilitate installation of the unit. The unit may be mounted outdoors. When the unit is mounted on the fl oor, ensure that the position is not subject to fl ooding.
When positioning the unit, be sure that the Rating Plate is always visible since this data will be necessary to ensure correct maintenance.
The units are designed to be installed with ducts designed by qualifi ed technical staff. The joints to be used between ducts and openings in the unit should be Elastic Joints. Avoid the use of BYPASS joints between the extraction air and input air. The structure where the unit is placed must be able to support the weight of the unit during operation.
2.2.- UNIT RECEPTION
How to hoist the unit
WITH HOOK
Crane
Use separators
Hook
Sling 6 m
Use separators
WITH BALANCE BEAM
Crane
Balance
beam
Sling
NOTE:
Use slingers of 6 m with the hook in order to prevent pressure on the top of the unit because it can be damaged.Whenever it is possible, use balance beam.
Hooker
• 15 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 17
2. INSTALLATION
2.3.- UNIT LOCATION
- The bedplate is made up of metal sections, capable of withstanding the weight of the unit.
- If the unit is fl oor mounted, then the profi les should be isolated with shock absorbing material such as anti-vibration units or pads. Bear in mind that the fans rotate at approximately 850 rpm.
- The unit is able to work in normal radio interference conditions for commercial and residential installations. For any other conditions please consult us.
- If the outside temperature in the area where the heat pump unit is to be installed is low or the operating cycle is too long, it may be necessary to install an electrical heater in the drip tray , to prevent the formation of ice in the coil during the defrost cycle.
1. Mounting on a low sensitivity area.
Unit
Rubber mounting
2. Mounting on a medium sensitivity area.
Unit
Damping spring
Metal and concrete structure Support
Rubber mounting
3. Mounting on a high sensitivity area (Check fl oor loading).
Unit
Metal and concrete structure
Support
Damping spring
Rubber mounting
2.4.- INSTALLATION CLEARANCES
FAILURE TO INSTALL THE UNITS AS SHOWN WILL IMPACT PERFORMANCE AND RELIABILITY.
INSTALLATION CLEARANCES DETAILING AVM POSITIONS
1195 1145
3m (*)
1m (*)
1m (*)
1
m
1m (*)
1m (*)
ASC/ASH 020S
660
400
O14
130
25
• 16 •
3 m
1 m
1 m
1 m
1 m
1 m
3 m
1 m
1 m
ASC/ASH 025S/030S/035S/040S
ASC/ASH 045D/055D/070D/085D
1195 1145
980
800
800
1195
955
O14
1960
90
25
955
O14
90
25
Size in mm.(*) Clearance around the unit.
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 18
2. INSTALLATION
INSTALLATION CLEARANCES DETAILING AVM POSITIONS
2250
ASC/ASH 100D/120D/140D
965
682
1420
682
965
14
28
160
(*) Clearance around the unit.
2.5.- INDOOR LOCATION
Air outlet
Air outlet duct (2)
Unit
ASC/ASH 200D/230D
2300
752
784
696
675 700
675
675
14
700 675
2250
100
34
Size in mm.
Air inlet
Auxiliary drip tray (heat pump unit)
In heat pump units with double circuits and cooling units 100D-140D only, if only one duct is going to be installed, a
Air inlet duct (1)
regulated pressure damper should be installed for each fan, to avoid air by-pass through the fan if it has stopped.
For inside location, keep the following advice in mind:
- During the heat pump defrost cycle, the units produce a large quantity of melted water. If you wish to drain this water, adequate drainage should be installed below the unit to collect and lead the water to the desired location.
- Air duct installation:
If an air duct has been installed, the operating limits will be reduced (see operating limits section in this manual). (1) The air intake plenum (option) available for models 100D-140D facilitates the installation of the air intake duct. (2) The discharge plenum (option) permits the installation of a square discharge duct with options FP1.
• 17 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 19
2. INSTALLATION
2.6- REFRIGERANT CONNECTIONS
The unit is supplied with the gas and liquid lines sealed with copper caps out­side the casing with possibility to install pipe lines (unless the unit is supplied
Copper cap
Refrigerant pipe
lines
with the factory precharged refrigerant kit (option) or service valves kit (option).
Brazing
Standard units are fi lled with Nitrogen gas, which must be removed before any operation on the unit.
As an option, the unit can be supplied with service valves on the gas and liquid lines, with Nitrogen charge (N
) or refrigerant charge (R-410A).
2
FOR STANDARD UNITS AND UNITS SUPPLIED WITH SERVICE VALVES PROCEED AS FOLLOW:
1. Remove the nitrogen gas through the high and low 5/16” service ports located inside and provide a low vacuum for safety.
2. Remove the caps from the connecting lines.
3. Braze the piping connection lines. Select piping diameter from TABLE 1. (When brazing refrigerant pipes, nitrogen gas must be supplied into the pipes through the service ports to remove the air).
4. Leak test: Add nitrogen gas, check that a pressure of 5 kg/cm2 has been reached and that there are no leaks in the circuit or brazing by applying soapy water to the pipes which will cause the bubbles to form where there are leaks. To detect small leaks, proceed as follows:
Add nitrogen gas and check that a pressure of 25 kg/cm2 has been reached, there are no leaks if the pressure remains the same for at least 24 hours and the fi nal pressure is not less than 10% below the initial pressure.
5. Ensure that the gas line is insulated.
6. Evacuation: Remove the nitrogen gas, connect the gauge manifold and vacuum pump to both the liquid and gas lines, fully open the gauge manifold valve and switch on the vacuum pump. Check to make sure the gauge shows a pressure of -750mm Hg. Once a level of -750mm Hg is reached, keep the vacuum pump running for at least one hour.
7. Refrigerant charge:
- Check TABLE 3.1. and 3.2. for the amount of refrigerant charge, depending on the length and size of the pipe connections.
- Disconnect the vacuum pump and connect to the refrigerant-charging bottle. Open the charging pump and purge the air from
the hose at the pressure gauge manifold.
- Set up the amount of additional refrigerant on the weighing scale, open the high pressure and charged in the liquid state. If
the total amount of refrigerant charge has not been reached because the pressure is balanced, turn off the high side of the gauge manifold, turn on the unit, and add the remaining amount of the refrigerant charge required slowly through the low side of the pressure gauge. (With R-410A refrigerant, the charging bottle must be in a vertical position and charged in the liquid state). Close the pressure gauge, disconnect it from the from the service port of the unit and fi t caps on the service ports. The unit is then ready to operate.
During installation, keep the gas and liquid pipes covered, in order to prevent humidity and dirt from entering them. Take special care that the refrigerant pipes are insulated. Avoid collapse on lines installation.
FOR UNITS SUPPLIED WITH SERVICE VALVES AND FACTORY PRECHARGED REFRIGERANT KIT, PROCEED AS FOLLOWS:
1. Release the refrigerant pressure from the connecting line through the service port located in that line.
2. Remove the caps from the connecting lines.
3. Braze the interconnection line to the indoor unit.
4. With the service ports closed, evacuate and connect the vacuum pump to the 5/16” service port on the connecting line to achieve a pressure of -750 mm Hg; after that, keep the vacuum pump running for at least one hour in order to provide a vacuum to the connecting lines and the indoor unit. Disconnect the vacuum pump.
5. Refrigerant charge:
To the indoor
Copper cap
unit
Service port
Copper tube to connect to indoor unit
Service valve
To outdoor unit piping
Remove vacuum pump and connect the refrigerant bottle. Check TABLE 2 for
refrigerant charge per meter of copper pipe for the corresponding model.
Adjust the amount of refrigerant on the weighting scale and open the pressure gauge to charge in liquid state (with R-410A
refrigerant, the charging bottle must be in a vertical position and it is important to charge in the liquid state).
Close the pressure gauge, disconnect it from the service port of the unit and fi t the caps.
6. Open the service valves.
7. The unit is ready to operate.
• 18 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 20
2. INSTALLATION
2.6- REFRIGERANT CONNECTIONS
To locate outdoor and indoor units, refer to the following information:
OUTDOOR UNIT
2%
POSITION A: A siphon suction must be installed in the vertical part of the gas line,
2
A
1
and siphons must be installed every 8 meters in the rising section. The minimum suction speed must not be below 6m/s. Maximum vertical length 16m.
L
INDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
2%
OUTDOOR UNIT
B
2%
2
L
2%
INDOOR UNIT
2
1
POSITION B: Slope the lines toward the outdoor unit. Take special care with lines longer than 10, and avoid collapse.
1
POSITION C: Install a siphon at the base of the vertical of the gas line, no more siphons are necessary . Maximum vertical length 16 m.
A, B, C :
L
C
L : 1 = 2 =
Unit positions Total length Gas line Liquid line
2%
NOTE: The units are supplied with welded connections. As an option, service valves are available for liquid and gas lines.
- GAS LINES MUST ALWAYS BE INSULATED.
- THE HORIZONTAL LINES MUST SLOPE AT LEAST 2% TOWARDS THE OUTDOOR UNIT.
- THE MAXIMUM SPEED IN THE LINES, SHOULD NOT BE MORE THAN 15 m/sec.
Legislation does not allow refrigerant gas emissions to the atmosphere, so the refrigerants have to be recycled to avoid being released to the atmosphere. Those recycled refrigerants shall be processed afterwards by an authorized waste manager. Those components derived from the recycling of the unit have to be managed by authorized waste manager or be left in local waste facilities according the local normative in each country.
• 19 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 21
2. INSTALLATION
2.6- REFRIGERANT CONNECTIONS
For units with 2 circuits, please be sure to connect indoor unit circuits C1 and C2 to the corresponding C1 and C2 circuits of the outdoor unit.
Note :
MODELS 100D and 120D USE DIFFERENT SIZES OF PIPE CONNECTIONS : LARGE SIZE FOR CIRCUIT 1 AND SMALL SIZE FOR CIRCUIT 2.
TABLE 1: REFRIGERANT LINES SELECTION
Total line length.
(Length refri-
gerant lines
between indoor
unit and outdoor
unit.)
Total line length.
(Length refri-
gerant lines
between indoor
unit and outdoor
unit.)
REFRIGERANT LINES
Ø Liquid
0 to 30 m. (Standard con­nection of unit)
30 to 65 m.
0 to 30 m. (Standard con­nection of unit)
30 to 65 m.
Ø Gas
Max. nr of bends
Ø Liquid
Ø Gas
Max. nr of bends
Ø Liquid
Ø Gas
Max. nr of bends
Ø Liquid
Ø Gas
Sizes
020S 025S 030S 035S 040S 045D 055D
C1 1/2” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” C2 n/a n/a n/a n/a n/a 5/8” 5/8” C1 7/8” 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 1/8” 1 1/8” C2 n/a n/a n/a n/a n/a 1 1/8” 1 1/8”
6 12 8 18 12 12 8
C1 5/8” 5/8” 5/8” 3/4” 3/4” 5/8” 5/8” C2 n/a n/a n/a n/a n/a 5/8” 5/8” C1 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 5/8” 1 1/8” 1 3/8” C2 n/a n/a n/a n/a n/a 1 1/8” 1 3/8”
12 18 18 18 18 18 18
070D 085D 100D 120D 140D 200D 230D
C1 5/8” 5/8” 3/4” 3/4” 3/4” 7/8” 7/8” C2 5/8” 5/8” 5/8” 5/8” 3/4” 7/8” 7/8” C1 1 3/8” 1 3/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” 2 1/8” C2 1 3/8” 1 3/8” 1 3/8” 1 3/8” 1 5/8” 1 5/8” 2 1/8”
18 12 12 12 12 12 12
C1 3/4” 3/4” 7/8” 7/8” 7/8” n/a n/a C2 3/4” 3/4” 3/4” 3/4” 7/8” n/a n/a C1 1 3/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” n/a n/a C2 1 3/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” n/a n/a
Max. nr of bends
18 18 12 12 12 n/a n/a
n/a: not available
With lines length between 40 and 65 m, long distance option must be selected.
Units are factory pre-charged with Nitrogen (N2). The installer should remove the nitrogen and charge the units with the R-410A refrigerant shown in the following tables and also the charge per meter of line shown in TABLE 2.
The unit is supplied as standard with brazed connections. A factory pre-charged kit is available as an option. If fi tted, TABLE 2 is the only one to take into account (this option includes service valves).
TABLE 2: WEIGHT OF R-410A REFRIGERANT PER METER OF LINE
g/m
LIQUID GAS
1/2” 7/8” 108 5/8” 1-1/8” 177 5/8” 1-3/8” 182 3/4” 1-3/8” 265 3/4” 1-5/8” 271 7/8” 1-5/8” 374
• 20 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 22
2. INSTALLATION
2.6- REFRIGERANT CONNECTIONS
TABLE 3.1 : REFRIGERANT CHARGE
Charge of refrigerant (gr) R-410A for 0 meters of line (Cooling only) ASC + Air T. Unit
020S 025S 030S 035S 040S 045D 055D 070D 085D 100D 120D 140D 200D 230D
C1
5155 5315 5700 7950 9745 6250 5775 7870 9800 12130 15585 15500 23100 24250
C2
------ ------ ------ ------ ------ 6250 5775 7870 9800 10450 10045 15400 23100 24250
Charge of refrigerant (gr) R-410A for 0 meters of line (Heat pump) ASH + Air T. Unit
020S 025S 030S 035S 040S 045D 055D 070D 085D 100D 120D 140D 200D 230D
C1
5725 5900 6330 8835 10830 6940 6420 8740 10900 13480 17315 17230 25660 26950
C2
------ ------ ------ ------ ------ 6940 6420 8740 10900 11600 11160 17100 25660 26950
Note :
MODELS 100D and 120D USE DIFFERENT SIZES OF PIPE CONNECTIONS : LARGE SIZE FOR CIRCUIT 1 AND SMALL SIZE FOR CIRCUIT 2.
REFRIGERANT CHARGE FOR THE SET:
EXAMPLE: To install a ASH 030S + Air treatment unit, with 22 m refrigerant line length between the condensing and Air treatment unit,
the refrigerant charge must be calculated as follows: 1 TABLE 1 (p. 20) shows that for 22m of line length between the condensing and Air treatment unit, the line sizes are: liquid 5/8”
and gas 1 1/8”. TABLE 2 (p. 20) shows, for line sizes of 5/8”-1 1/8”, the charge per meter of line is: 177 g/m x 22m = 3894 g.
2 3 TABLE 3.1 shows charge of refrigerant for a set with 0m line length is: 6330 g. 4 To determine the charge of the set:
Add the charge in the refrigerant lines + the charge in the Air treatment unit and condensing refrigerant units.
Total charge for the set: 3894 + 6330 = 10224 g
Note: If the condensing unit includes the factory pre-charged kit, only the weight of refrigerant per meter of line in TABLE 2 is taken into account.
100D to 140D units with 3 compressors are working using three capacity steps and 200D-230D with 4 capacity steps. See the picture below for the installation in the case of units with tandem compressor circuit. An additional gas line has to be used to assure the correct operation of the system.
Condensing unit with capacity reduction
Tandem compressor circuit
4
Min 0.25% gradient
2
H1
15 m max
H1
5 m max
H2
0,15 m min
H4
Coupled trap
2
Lower trap with double tubes
3
Higher trap with double tubes
4
23
H4
4
H4
• 21 •
H2
Indoor unit
3
100D 120D 140D 200D 230D
Circuit 1 Circuit 1 Circuit 1 Circuits 1 & 2 Circuits 1 & 2
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Models with tandem compressor
Page 23
2. INSTALLATION
2.7.- ELECTRICAL CONNECTIONS
- BEFORE MAKING ANY ELECTRICAL CONNECTIONS, ENSURE THAT ALL CIRCUIT BREAKERS ARE OPEN.
- IN ORDER TO MAKE THE ELECTRICAL CONNECTIONS, FOLLOW THE ELECTRICAL DIAGRAM SUPPLIED WITH THE UNIT.
INDOOR SECTION
RS
CO2
AS
AS
HR/T
HR/T
RS
Air treatment unit. Example
DS
DADS
BAC
LDRP
DPT
DIFS
5
6
4
3
2
AS OS
OS
HR/T
Note: The length of all cables for connection with indoor unit must be less than 65 m.
CONNECTION OF CONTROL ELEMENTS:
COMPONENT
DS OS AS RS
RS HR/T
CO2
DPT
OS HR/T
AS HRT
Discharge sensor Outdoor sensor STANDARD Remote ambient sensor Remote duct sensor
Duct remote sensor for enthalpic free-cooling 6G x 1 mm² (shielded) CO2 Air quality probe. (Available only with enthalpic
free-cooling) Air differential pressure transducer 3 x 1 mm² (shielded)
Outdoor sensor for enthalpic free-cooling 5 x 1 mm² (shielded)
Remote ambient sensor for enthalpic free-cooling 6G x 1 mm² (shielded)
Electrical box
PT1 PT2
Split unit
STANDARD
OPTION
1
OUTDOOR SECTION
Condensing
unit
N/A
N/A
To connect by installer
2 x 1 mm² (shielded)
4 x 1 mm² (shielded)
DIFS
LDRP
DADS BAC
Dirty fi lter sensor 2 x 1,5 mm²
Long distance connection
Smoke detector 7 x 1,5 mm² Hot water coil 5 x 1,5 mm²
VOLTAGE OPERATING LIMITS: 342-462V
• 22 •
3 x 1,5 mm² (units 1 circuit)
2 x (3 x 1,5 mm²) (units 2 circuits)
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 24
2. INSTALLATION
2.7.- ELECTRICAL CONNECTIONS
POWER SUPPLY
Power supply
11 2 456
020S 5G x 4 mm² 5G x 16 mm²
Power supply with
electrical heater
Power supply
Fan Free-cooling Exhaust fan Return fan
025S
030S
035S
040S
045D
055D
085D
100D
140D
200D
230D
4G x 6 mm² 4G x 16 mm²
4G x 1,5 mm²
(STD/HP1) & (HP2/HP3)
4G x10 mm²
4G x 16 mm²
3 x 35 mm² +
1 x 16 mm²
3 x 50 mm² +
1 x 25 mm²
6G x 1,5 mm² 4G x 1,5 mm²
4G x 1,5 mm² (STD/HP1)
3 x 25 mm² +
1 x 16 mm²
3 x 50 mm² 1 x 25 mm²
3 x 70 mm² +
1 x 35 mm²
3 x 95 mm² +
1 x 50 mm²
Standard - ELHS Medium - ELHM High - ELHH Modulating - EHHM
3 x 70 mm² +
1 x 35 mm²
3 x 95 mm² +
1 x 50 mm²
N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A
4G x 2,5 mm² (HP2/HP3)
4G x 2,5 mm² (STD/HP1)
2 x (4G x 1,5 mm²) (HP2/HP3)
Power supply
Electrical heater (3)
N/A
4G x 1,5 mm²070D
4G x 2,5 mm²120D
n/a: not available
020S
025S
030S
035S
040S
4G x 2,5 mm² +
6G x 1,5 mm²
4G x 6 mm² +
6G x 1,5 mm²
4G x 6 mm² + 6G x 1,5 mm²
4G x 10 mm² +
6G x 1,5 mm²
4G x 10 mm² +
7G x 1,5 mm²
045S
055D
070D
085D
100D
4G x 10 mm² +
6G x 1,5 mm²
4G x 10 mm² +
6G x 1,5 mm²
4G x 25 mm² +
6G x 1,5 mm²
4G x 25 mm² +
7G x 1,5 mm²
120D
140D
200D N/A N/A N/A N/A
230D
N/A N/A N/A N/A
• 23 •
n/a: not available
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 25
2. INSTALLATION
2.7.- ELECTRICAL CONNECTIONS
COMFORT AND SERVICE TERMINAL CONNECTION
2.8.- DRY CONTACT BOARD CONTROL
The AIRCOOLAIR condensing unit can be remotely controlled via dry contacts on the BM60 and BE60. The expansion board BE60 is an additional board fi xed on DIN rail. This board is supplied in stand on AIRCOOLAIR condensing unit.
Description of the various connectors :
1 Power supply of the board 2 Analog output 0/10V : not used 3 Network bus to the CLIMATIC 60 BM60 4 4 digital inputs : dry contacts only 5 LED status of the network bus 6 Serial address dip-switch of the network bus 7 4 analog input con gurable by pair B1-B2 and B3-B4 8 4 digital outputs : dry contact only
6 digital inputs are dry contacts. They are factory confi gured as follow :
2 inputs on the BM60
• BM-J4-ID4 : TCB B = Cooling/Heating - Contact closed = the unit operates in heating mode and open contact = the unit opera­tes in cooling mode
• BM-J4-ID7 : TCB G = On/Off - Contact closed = On.
4 inputs on the BE60
• BE-J4-ID1 : TCB Y1 = 50% power engaged when the contact is closed
• BE-J4-ID2 : TCB Y2 = 100% power engaged when the contact is closed
• BE-J4-ID3 : Available
• BE-J4-ID4 : Available
• 24 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 26
2. INSTALLATION2. INSTALLATION
2.9 - OPTIONS INSTALLATION
COMMUNICATION CAPABILITIES
1. BMS MODBUS_RS485 or TCP/IP connection.
2. BMS LONWORKS_Echelon connection.
3. BMS BACnet - RS485 or TCP/IP connection.
BM60
SERIAL CARD SERIAL CARD SERIAL CARD SERIAL CARD
CH1
BM60 BM60 BM60
CH2
CH3
MODBUS
LON WORKS FTT 10A
BACNET
230V
Cable c. section (mm2) two wire S12E racing from min. 0.2 a max. 2.5 mm AWG 20/22 1000m. max.
RS485
RS232
BMS
2
SERIAL CARD
Connect a 120 1/4 W ter­minating resistor, MODBUS
only.
LON WORKS FTT 10A
BM60
CH4
MODBUS BACNET
A master-slave connection is possible :
SERIAL
BM60
CARD
J11 J10
LAN
Cable c. section (mm²)
3 shielded pairs
AWG24
500 m max.
C
B
DC60
DC60
A
DT50
DS60
SERIAL
RT1
CARD
Cable c. section (mm²)
3 shielded pairs
AWG24
500 m max.
A
DT50
DS60
B
BM60
J11 J10
C
Cable c. section (mm²)
DC60
SERIAL
RT2
3 shielded pairs
AWG24
500 m max.
Cable c. section (mm²)
3 shielded pairs
AWG24
500 m max.
A
DT50
DS60
CARD
B
BM60
J11 J10
C
DC60
SERIAL
RT3
Cable c. section (mm²)
3 shielded pairs
AWG24
500 m max.
A
DT50
DS60
CARD
B
BM60
J11 J10
C
RT12
• 25 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 27
3. COMMISSIONING AND OPERATION
3.1.- PRELIMINARY CHECKS BEFORE STARTUP
- Check that the power supply is the same as stated on the Rating Plate which is in agreement with the electrical diagram for the unit and that cable sizes are correct.
- Check that tightness of the electrical connections to their terminals and to ground.
- Check the control panel connections.
(If the connection is incorrect, the unit will not operate and the control panel display will not light).
- Check with your hand that the fans are turning freely.
FIGURE FOR THE STANDARD UNIT CONFIGURATION FOR MODELS: 045D-055D-070D-085D
m o
d e
s e
t o n
o
f
f
CHECK COMPRESSOR OIL LEVEL
- Part of the compressor oil is pumped to the system when the compressor starts, so for split systems part of the oil can be placed in the system: piping lines, traps, evaporator, etc.
- The quantity of oil in the system depends on the refrigerant charge. The compressor cannot work with incorrect or excessive refrigerant.
- It may be necessary to add oil to the system, depending on the piping length.
- See below an example of calculation of the oil quantity to be added to the system.
EXAMPLE:
ASH 030S + Air treatment unit with 65 m. (with remote option).
- Refrigerant charge = 6.33 kg (TABLE 3.1, p. 21).
- Refrigerant charge to add with 65 m = 182g/m x 65 = 11.83kg. (TABLE 2, p. 20).
- Total refrigerant charge = 6.33 + 11.83 = 18.16 kg.
- Oil compressor charge (l) = 3.25
- Oil compressor charge (kg) = 2.925 (density = 0.9).
- Permissible quantity in the system (kg) = 0.03 (= 2.925 x 0.01).
- Permissible refrigerant charge (kg) = 6 (= 0.03/ 0.005).
- Excess refrigerant charge = 18.16 - 6 = 12.16
60.8 g (= 12.16 x 5 g) quantity of oil to be added to the system.
0.55 l of oil to be added to the system.
In the event of having to add oil, remember the type of oil is synthetic POE. The original oil charge, including the compressor, is ICI Emkarate RL32-3MAF. This type of oil must also be used when replacing the oil completely. If only topping up, RL32-3MAF or Mobil EAC Artic 22C can be used.
• 26 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 28
3. COMMISSIONING AND OPERATION
3.2.- PRELIMINARY CHECKS AT STARTUP
To start the unit, follow the instructions given in the User Manual for the control supplied with the unit (requiring operation in any of the modes, cooling, heating, or automatic). After a time delay, the unit will start. With the unit operating, check that the fans are turning freely and in the correct direction.
CHECK THAT THE COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
- If you have the option phase rotation indicator, use it to check the correct rotation.
- If you do not have three phase return lock, check the correct direction of rotation. The suction pressure decreases and the discharge pressure increases when the compressor is started.
- If the connection is incorrect, rotation will be reversed, causing a high noise level and a reduction in the amount of current consumed. If this occurs, the compressor’s internal protection system will operate to shut down the unit. The solution is to disconnect, reverse two of the phases and connect again.
ASTP Protection is included with the unit compressors. See "Fault diagnosis" for more information.
WITH OPERA TING UNIT, CHECK:
- Low pressure and high pressure.
- Use the evaporating and liquid temperature to calculate superheat and subcooling.
- Adjust the refrigerant charge and/or expansion valve according to the preceding values.
COMPRESSOR OIL LEVEL
The oil level must always be checked. When the compressor is at rest, the level should be between 1/4 and 3/4 in the sight glass, while when running the level should be between 3/4 and full. In the event of having to add oil, remember the type of oil is synthetic POE. The original oil charge in the compressor is ICI Emkarate RL32-3MAF. This type of oil must also be used when replacing the oil completely. When only topping up, RL32-3MAF or Mobil EAC Artic 22C can be used.
The unit must be installed in accordance with local safety codes andregulations and can only be used in a well ventilated area. Please readcarefully the manufacturer’s instructions before starting this unit
All work on the unit must be carried out by a qualifi ed and authorised employee.
Non-compliance with the following instructions may result in injury or serious accidents.
Work on the unit:
The unit shall be isolated from the electrical supply by disconnection and locking using the main isolating switch. Workers shall wear the appropriate personal protective equipment (helmet, gloves, glasses,etc.).
Electrical system:
Electrical connections can become loose during transport. Please check them before starting-up the unit Compressors with specifi c rotation direction. Check the correct rotation direction of the fan before closing the compressor circuit breakers. If the direction is incorrect, the phases must be reversed at the head of the main switch. Work on electric components shall be performed with the power off (see below) by employees having valid electrical qualifi cation and authorisation.
Refrigerating circuit(s):
After more than 12 hours of power cut, the cranckcase heater (compressor) should be powered for 5 hours before any return to service. Non-compliance with this instruction can cause deterioration of the compressors. Monitoring of the pressures, draining and fi lling of the system under pressure shall be carried out using connections provided for this purpose and suitable equipment.
To prevent the risk of explosion due to spraying of coolant and oil,
the relevant circuit shall be drained and at zero pressure before
any disassembly or unbrazing of the refrigerating parts takes place. There is a residual risk of pressure build-up by degassing the oil or by heating the exchangers after the circuit has been drained. Zero pressure shall be maintained by venting the drain connection to the atmosphere on the low pressure side. The brazing shall be carried out by a qualifi ed brazier. The brazing shall comply according to code ASME section IX following the procedures specifi c.
Before starting up
- Test the circuit to the maximum working pressure(see the nameplate)
- Verifi fy the operation of the high pressure swich.
- Check the piping and the components of the refrigerant circuit.
Replacing components:
In order to maintain CE marking compliance, replacement of components shall be carried out using spare parts, or using parts approved by Lennox. Only the coolant shown on the manufacturer’s nameplate shall be used, to the exclusion of all other products (mix of coolants, hydrocarbons, etc.).
CAUTION:
In the event of fi re, refrigerating circuits can cause an explosion and spray coolant gas and oil.
• 27 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 29
4. MAINTENANCE
4.1.- PREVENTIVE MAINTENANCE
PREVENTIVE MAINTENANCE PREVENTS COSTLY REPAIRS.
THIS REQUIRES PERIODIC INSPECTIONS:
GENERAL STATE OF THE CASING:
Furniture, paint, damage due to shocks, rust spots, levelling and suppor­ting, condition of the shock absorbers, if installed, screwed panels, etc.
COMPRESSOR:
If a sight glass is fi tted, check the oil level. Check the condition of the silentbloc mountings.
ELECTRICAL CONNECTIONS:
State of hoses, tightness of screws, earthing, current consumption of the compressor and fans and check that the unit is receiving the correct voltage.
COOLING CIRCUIT:
Check that the pressures are correct and that there are no leaks. Check that there is no damage to the pipe insulation, that the condition of the coils is good and that they are not blocked by bits of paper or plastic drawn in by the air fl ow, etc.
FANS:
Check that fans turn freely and in the correct direction without excessive noise.
CONTROL:
Check Set Points and normal operation.
4.2.- CORRECTIVE MAINTENANCE
MAKE SURE THAT THE UNIT IS FULLY DISCONNECTED FROM THE POWER SUPPLY WHEN CARRYING OUT ANY TYPE OF
If any component in the cooling circuit is to be replaced, follow these recommendations:
- Always use original replacement parts.
- If the component can be isolated, it is not necessary to remove the entire refrigerant charge, if the component cannot be isolating and the refri­gerant charge is removed, it should be removed through the Schrader valves located in the outdoor section. Create a slight vacuum as a safety measure.
- Regulation prohibits the release of refrigerant into the atmosphere.
- If cuts must be made in the pipe work, use pipe cutters. Do not use saws or any other tools that produce lings.
- All brazing must be carried out in a nitrogen atmosphere to prevent corrosion forming.
- Use silver alloy brazing rod.
- Take special care that the ame from the torch is directed away from the component to be welded and cover with a wet rag to prevent overhea- ting.
- Take very special care if 4-way or check valves are to be replaced since these have internal components that are very heat-sensitive such as plastic, tefl on, etc.
- If a compressor is to be replaced, disconnect it electrically and un-braze the suction and discharge lines. Remove the securing screws and replace the old compressor with the new one. Check that the new compressor has the correct oil charge, screw it to the base and connect the lines and electrical connections.
- Evacuate above and below through the Schrader valves of the outdoor unit until -750 mm Hg is reached. Once this level of vacuum has been
ched, keep the pump running for at least one hour.
rea
DO NOT USE THE COMPRESSOR AS A VACUUM PUMP.
- Charge the unit with refrigerant according to the data on the Rating Plate for the unit and check that there are no leaks.
IMPORTANT
WORK ON THE MACHINE.
Wet rag
Direction of the fl ame
Silver alloy welding rod
Nitrogen
PRECAUTIONS TO BE TAKEN WHEN USING OF R-410A Refrigerant:
R-410A refrigerant is used in the unit; the following standard precautions for this gas should therefore be taken:
- The Vacuum Pump must have a Check Valve or Solenoid Valve fi tted.
- Pressure Gauges and Hoses for exclusive use with R-410A Refrigerant should be used.
- Charging should be carried out in the Liquid Phase.
- Always use scales to weigh-in charge
- Use the Leak Detector exclusive for R-410A Refrigerant.
- Do not use mineral oil, only synthetic oil to ream, expand or make connections.
- Keep pipes wrapped before using them and be very thorough about any possible dirt (dust, fi lings, burrs, etc.).
- When there is a leak, collect what remains of the charge, create a vacuum in the unit and completely recharge with new R-410A Refrigerant.
- Brazing should always be carried out in a nitrogen atmosphere.
- Reamers should always be well sharpened.
• 28 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Component to be welded
Page 30
4. MAINTENANCE
4.3.- FAULT DIAGNOSIS
In case of failure or malfunction of the unit, the display on the control panel will show an error or alarm warning which is explained in the control panel manual. Nevertheless, whenever there is a unit fault, the unit should be shut down and our service technicians consulted.
FAULT POSSIBLE CAUSES POSSIBLE SOLUTIONS
UNIT DOES NOT START
UNIT STOPS DUE TO HIGH PRESSURE DURING THE COOLING CYCLE
UNIT STOPS DUE TO HIGH PRESSURE DURING THE HEA TING CYCLE
UNIT STOPS DUE TO LOW PRESSURE
Fault in the power supply or insuffi cient voltage.
Connect the power supply or check the
voltage. Circuit breakers have opened. Reset. Power cable or control panel cable is
defective.
High pressure switch is defective.
Outdoor fan is not working.
Inspect and correct.
Check cut-off pressure switch or replace
pressure switch if necessary.
Check for voltage, inspect the motor and
turbine or replace if necessary.. Outdoor fan turns in the wrong direction. Reverse the power phases. Outdoor coil is dirty or clogged for pas-
sing air.
Excess refrigerant charge.
Inspect and clean.
Remove the charge and charge according
to the data on the rating plate. The same causes and solutions as the cold cycle but with reference to the coils and
indoor fan.
Check the cut-off pressure with a pressure Low pressure switch defective.
gauge and replace the pressure switch if
necessary.
Indoor fan is not working.
Check for voltage and inspect the motor,
turbine and replace if necessary. Indoor fan turns in the wrong direction. Reverse the power phases. Lack of refrigerant. Leak. Correct leak, create vacuum and charge. Dirty air fi lter. Inspect and clean
UNIT STARTS AND STOPS IN SHORT CYCLES
Clogged cooling circuit. Dirty fi lter drier.
Compressor overcharged.
Compressor cuts off due to Klixon. Check input voltage and voltage drop.
Inspect and correct or change the fi lter
drier.
Inspect suction and discharge pressure
values and correct.
Lack of refrigerant. Correct leak and replace.
LOAD AND ABNORMAL NOISE IN THE COMPRESSOR (SCROLL)
All the components derived from the recycling of the unit should be managed according local legislation, and have to be classi­ ed and separated while dealt by authorized waste manager or be left in local waste facilities.
Refrigerant fl uids, electronic boards, heat exchangers and the oil extracted from the refrigerant circuit, as well as the oil reci- pients used must be recycled as hazardous waste according the local normative through an authorized waste manager or be left in local waste facilities. The rest of the components considered as non-hazardous wastes must be recycled according to the corresponding norms. At the end of its life, the equipment should be recycled in local waste facilities or by an authorized waste manager.
Power supply phases inverted. (three-phase compressor).
Check and reverse power phases.
• 29 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 31
4. MAINTENANCE
4.3.1.- SAFETY DEVICES
Unit with specifi c compressor protection
ASTP COMPRESSOR PROTECTION:
This device protects the compressor against high discharge temperatures. When the temperature reaches critical values, ASTP protection causes the "Scrolls" to separate. The compressor stops pumping but the motor continues to run.
- Occasionally, when the compressor stops and starts, there is a metallic noise due to the compressor scrolls. This is normal.
- Connect high and low pressure gauges and check that the operating pressures are normal.
- Measure electrical consumption for the unit and check that it is close to that indicated on the specifi cation plate.
- Check the electrical consumption of the compressor and the fans against that specifi ed in the physical data sheets.
- In the case of a Heat Pump unit, make a cycle change on the Control Panel, checking that the 4-way valve makes the change correctly. Check the pressures in the new cycle.
- Split and Multi-split: Low pressure switch and high pressure switch are reset automatically and if it operates 3 times in one day, they change to manual reset, through the control unit.
- With C60 control: Low pressure switch and high pressure switch are reset automatically and if it operates 3 times in one day, they change to manual reset, through the control unit.
La unidad incorpora compresor con protección específi ca
• 30 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 32
NOTES
• 31 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Page 33
SALES OFFICES :
BELGIUM AND LUXEMBOURG PORTUGAL
+ 32 3 633 3045 +351 229 066 050
+ 32 3 633 3045 +351 229 066 050
FRANCE RUSSIA
+33 1 64 76 23 23 +7 495 626 56 53
+33 1 64 76 23 23 +7 495 626 56 53
GERMANY SPAIN
+49 (0) 211 950 79 600 +34 915 401 810
+49 (0) 211 950 79 60 +34 915 401 810
ITALY UKRAINE
+ 39 02 495 26 200 +38 044 585 59 10
+ 39 02 495 26 200 +38 044 585 59 10
NETHERLANDS UNITED KINGDOM AND IRELAND
+ 31 332 471 800 +44 1604 669 100
+ 31 332 471 800 +44 1604 669 100
POLAND
+48 22 58 48 610
+48 22 58 48 610
OTHER COUNTRIES :
LENNOX DISTRIBUTION
LENNOX DISTRIBUTION
+33 4 72 23 20 20
+33 4 72 23 20 20
Due to LENNOX EMEA ongoing commitment to quality, the specifi cations, ratings and dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualifi ed installer and servicing agency.
www.lennoxemea.com
MIL152E-1217 01/2019
Loading...