Lennox AIR CONDITIONER Installation Manual

Page 1
INSTALLATION MANUAL
For correct installation, read this manual before starting installation. This manual may be subject to change without notice for purpose of improvement.
FOR SLIM DUCT/CEILING TYPE
AIR CONDITIONER
Page 2
CONTENT
ACCESSORIES..................................................................................................1
INSTALLATION PLACE......................................................................................2
INDOOR UNIT INSTALLATION..........................................................................3
INSTALL THE CONNECTING PIPE...................................................................5
REFRIGERANT PIPE CONNECTION.............................................................7
WIRING............................................................................................................8
TEST OPERATION...........................................................................................10
CONNECT THE DRAIN PIPE..........................................................................5
Page 3
To install properly, please read this manual at first. The air conditioner must be installed by qualified persons. When installing the indoor unit or its tubing, please follow this manual as strictly as possible. When all the installation work is finished, please turn on the power only after a thorough check. No further announcement if there is any change of this manual caused by product improv­ement.
Note: The installor should illustrate to users how to correctly use and maintain the air-condi­ tioner, as well as remind users to carefully read and keep both Installation Manual and Owner's Manual well.
INSTALLATION INFORMATION
ACCESSORIES
1. Remote controller..................1
2. Frame...................................1
3. Mounting screw
(ST2.9x10-C-H).....................2
4. Alkaline dry batteries(AM4)
...............................................2
1
Remote controller & Its Frame
1
2
3
Remote controller
Remote controller holder
Mounting screw B ST2.9x10-C-H
C
Never throw or beat the controller. Before installation, operate the remote controller to determine its location in a reception range. Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment. (It is necessary to prevent image disturbances or noise interferences.) Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove. Note that the positive and negative poles are in right positions when loading batteries.
Cautions on remote controller installation
5.
..............................................1
Remote controller manual
1 1 2 1
Name of Accessories Owner's manual Installation manual Pipe insulating material Signal receiver display board
Q'ty
(This manual)
Qutline
Usage
(Heat resisting) Receive Signal
Page 4
The Indoor Unit
There is enough room for installation and maintenance. The ceiling is horizontal, and its structure can endure the weight of the indoor unit. The air outlet and the air inlet are not impeded, and the influence of external air is the least. The air flow can reach throughout the room. The connecting pipe and drainpipe could be extracted out easily. There is no direct radiation from heaters
INSTALLATION PLACE
Location in the following places may cause malfunction of the machine. (If unavoidable, please consult your local dealer.)
a. There exists petrolatum. b. There is salty air surrounding(near the coast). c. There is caustic gas(the sulfide, for example) existing in the air (near a hot spring). d. The Volt vibrates violently(in the factories). e. In buses or cabinets. f. In kitchen where it is full of oil gas. g. There is strong electromagnetic wave existing. h. There are inflammable materials or gas. i. There is acid or alkaline liquid evaporating. j. Other special conditions.
1. Select the correct carry-in path.
2. Move this unit as originally packaged as possible.
3. If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
Cautions
Notes Before Installation
2
NOTE:
Remark per EMC Directive 89/336/EEC For to prevent flicker impressions during the start of the compressor (technical process), following installation conditions apply.
1. The power connection for the air conditioner has to be done at the main power distribution. The distribution has to be of a low impedance, normally the required impedance reaches a 32A fusing point.at
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance, please refer to your contract with the power supplier restrictions do apply for products like washing machines, air conditioners or electrical if ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question contact your local dealer.
Page 5
3
INDOOR UNIT INSTALLATION
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the operation, determine the direction of the pipes to be drawn out. Especially in case there is a ceiling, position the refrigerant pipes, drain pipes, indoor & outdoor lines to the connection places before hanging up the machine. The installation of hanging screw bolts.
Wooden construction
Install the main body
Installing f10 hanging screw bolts. (4 bolts)
Please refer to the following figure for the distance measurement between the screw bolts. Please install with f10 hanging screw bolts.
The handling to the ceiling varies from the constructions, consult the construction personn­els for the specific procedures.
1. The size of the ceiling to be handled ... ... do keep the ceiling flat. Consolidate the roof
beam for possible vibration.
2. Cut off the roof beam.
3. Strengthen the place cut off, and consolidate the roof beam.
Put the square timber traversely over the roof beam, then install the hanging screw bolts. (Refer to Chart 1)
Chart 1
Timber over the beam
Roof beam
Hanging screw bolts
Ceiling
New concrete bricks
(Blade shape insertion)
(Slide insertion)
Chart 2
Inlaying or embedding the screw bolts. (Refer to Chart 2)
Install and use directly the supporting angle steel. (Refer to chart 4)
For Original concrete bricks
Use embedding screw bold, crock and stick harness. (Refer to Chart 3)
Steel roof beam structre
Steel bar
Hanging screw bolt
Hanging bolts
Supporting angle steel
Embedding screw bolt
Chart 3
Chart 4
(Pipe hanging and embedding screw bolt)
Overhanging the indoor unit
(1) Overhang the indoor unit onto the hanging screw bolts with block. (2) Position the indoor unit in a flat level by using the level indicator, unless it may cause leakage.
Screw nut
Washer
Hanging screw bolt
Overhang part
Chart 5
Page 6
Install the main body
Chart 6
2This chart takes the unit with scroll casing as an example,
which may differ from what you have purchased.
Note:
4
A B C D E F G
Capacity
24000Btu/h
170
18000Btu/h
743
685
170
713
685
927
490
1. Install the dust proof net according to the installation manual;
2. Install the canvas air passage underneath the dust proof net.
Installing the dust proof net and canvas air passage
Pipe Connection
The maximum static pressure in the outside of the unit is 50Pa, the length of the air pipe attached is determined by this parameter.
30000Btu/h
36000Btu/h 48000Btu/h 60000Btu/h
963
905
170933 905 1140
885
855
199
912
885
1169
1085 1055 1991112
1085
1369
1277 1247 1991308 1277
1500
743
685
713
685
927
A B
C
D
E
40
45
19
10
19
145
0
0
0
0
Drain point
(Liquid Side fN)
Connecting point of
refrigerant pipe
Connecting point of
refrigerant pipe
(Gas Side fM)
4-10x16 Long hole for hanging
F
G
H
K
L
I
J
H
570I290J231K130
240
L M
16
19
19 19 19
16
N
9.53
12.7
12.7
12.7
12.7
9.53
490
570
490
570
590
670
590
670
590
670
290 231
290 231 330 231 330 231 330 231
130
240
130
240
230
340
230
340
230
340
Page 7
5
INSTALL THE CONNECTING PIPE
The drain pipe of indoor unit must be heat insulated, or it will condense dew, as well as the connections of the indoor unit. Hard PVC binder must be used for pipe connection, and make sure there is no leakage. With the connection part to the indoor unit, please be noted not to impose pressure on the side of indoor unit pipes. When the declivity of the drain pipe downwards is over 1/100, there should not be any win ding. The total length of the drain pipe when pulled out traversely shall not exceed 20m, when the pipe is over long, a prop stand must be installed to prevent winding. Refer to the figures on the right for the installation of the pipes.
CONNECT THE DRAIN PIPE
1.5m~2m
Insulating material
Downward declivity lower than 1/100
VP30
Downward declivity lower than 1/100
Put as deep as possible (about 10cm)
Bend
S shape
1. Install indoor unit drain pipe
The outlet has PTI screw bread, Please use sealing materials and pipe sheath (fitting) when connecting PVC pipes.
CAUTIONS
2. Drainage test
Check whether the drainpipe is unhindered New built house should have this test done before paving the ceiling.
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements:
The max height drop...................................................................................................20m
(If the height drop is more than 10m, you had better put the outdoor unit over above the indoor unit.)
The length of refrigerant pipe.......................................................................less than 30m
The number of bends....................................................................................Less than 15
Page 8
Do not let air, dust, or other impurities fall in the pipe system during the time of installation. The connecting pipe should not be installed until the indoor and outdoor units have been fixed already. Keep the connecting pipe dry, and do not let moisture in during installation.
1) Connect the indoor unit at first, then the outdoor unit. ,
Bend the tubing in proper way. Don t harm them.
The Procedure of Connecting Pipes
1. Measure the necessary length of the connecting pipe, and make it by the following way.
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds with hands before fasten the flare nuts. (Refer to chart 11) Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Cautions
2) The stop valve of the outdoor unit should be closed absolutely (as original state). Every
time you connect it, first loosen the nuts at the part of stop valve, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection.
o
The bending angle should not exceed 90 C Bending position is preferably in the bendable pipe. The larger the better it is . Do not bend the pipe more than three times.
Be sure to use the same insulating materials when you buy the brass pipe. (More than 9mm thick)
Cut out a desired concave at the bending part of the insulating pipe. Then expose the pipe(cover it with tapes after bending). To prevent collapsing of deforming, please bend the pipe at its biggest radius. Use bender to get a small radius pipes.
3) Expel the air (refer to the Expel The Air ) after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
Notices For Benable pipe.
Bend the connecting pipe of small wall thickness.
Use the market brass pipe.
Chart 11 Chart 12 Chart 13
Use frozen oil
Bend the pipe with thumb
Min-radius 100mm
Make the ends straight
6
Page 9
2. Locate The Pipe
1) Drill a hole in the wall (suitable just for the size of the wall conduit, 90mm in general), then set on the fittings such as the wall conduit and its cover.
2) Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation.
3) Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
3. Connect the pipes.
4. Then, open the stem of stop valves of the outdoor unit to make the refrigerant pipe conne­ cting the indoor unit with the outdoor unit fluently flow.
5. Be sure of no leakage by checking it with leak detector or soap water.
6. Cover the joint of the connecting pipe to the indoor unit with the soundproof/insulating sheath (fittings), and bind it well with the tapes to prevent leakage.
REFRIGERANT PIPE CONNECTION
7
A
90+4
_
45+2
_
Amm
f6. 5mm3
f9.53mm
f12.7mm
f16mm
f19mm
8.7
8.3
15.8 15.4
12.4
12.0
19.0
18.6
23.3
22.9
1. Cut a pipe with a pipe cutter.
2. Insert a flare nut into a pipe and flare the pipe.
Outside­diameter
Max Min
90
lean crude burr
Chart 16
Chart 15
Table 1
Too large torque will harm the bellmouthing and too small will cause leakage. Please determine the torque according to Table 2.
Chart a
Table 2
Put the connecting tubing at the proper position, wrench the nuts with hands then fasten it with a wrench. (Refer to Chart a)
Caution
f9.53
10~12 .Nm
f12.7
12~14
.
Nm
Fasten the nut
Tubing Size
Torque
f19
9
35~40
.
Nm
Page 10
8
1. The air conditioner should use separate power supply with rated voltage
2. The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit.
3. The wiring work should be done by qualified persons according to circuit drawing.
4. A leakage protector should be installed according to the National Standard concerning electrical appliance.
5. Be sure to locate the power wiring and the signal wring well to avoid cross-disturbance and their contact with connecting pipe or stop value body.
6. The wiring attached to this air conditioner is 10m long. Be sure to prolong it with wiring of the same type and proper length if necessary. Generally, do not twist two wiring together unless the joint is soldered well and covered with insulator tape.
7. Do not turn on the power until you have checked carefully after wiring.
WIRING
Attaching wiring
The Specification of Power
Caution:
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
Table 3
(A)
2
(mm )
2
(mm )
208-230V~, 60Hz
TYPE(Cooling only)
POWER
GROUND WIRING
OUTDOOR UNIT POWER WIRING
STRONG ELECTRIC SIGNAL
INDOOR/OUTDOOR CONNECTING WIRING
CIRCUIT BREAKER/FUSE
INDOOR UNIT POWER WIRING
PHASE 1-PHASE
FREQUENCY AND VOLT
25/12 35/16
30000-36000Btu/h
1-PHASE
3x1.0
2.0
2.5
3x2.5
WEAK ELECTRIC SIGNAL
3x2.5
1-PHASE
70/35
6.0
48000-60000Btu/h
3x6.0
3x1.0
18000-24000Btu/h
208-230V~, 60Hz 208-230V~, 60Hz
3x1.0
2x1.0
2x1.02x1.0
Page 11
9
Chart 23
Wiring Chart
Installing wiring chart, refer to link circuit chart for details.
Ground wiring
Ground wiring
Power supply
Switch/Fuse (Available locally)
Power wiring (to indoor)
Power linking wiring (Outdoor)
24V~ elec-signal link wiring
Indoor Unit
Outdoor Unit
Ground the air conditioner properly in case to affect its anti-interference function
Power supply
Outdoor
Indoor
Power in
Page 12
1. The test operation must be carried out after the entire installation has been completed.
2. Please confirm the following points before the test operation:
3. According to the user s re quirement, in stall th e re mote c ontroller fr ame w here th e re mote controller s s ignal c an r each th e in door u nit s moothly.
4. Test operation
TEST OPERCETION
The indoor unit and outdoor unit are installed properly. Tubing and wiring are correctly completed. The refrigerant pipe system is leakage-checked. The drainage is unimpeded. The heating insulation works well. The ground wiring is connected correctly. The length of the tubing and the added stow capacity of the refrigerant have been recorded. The power voltage fits the rated voltage of the air conditioner. There is no obstacle at the outlet and inlet of the outdoor and indoor and indoor units. The gas-side and liquid-side stop values are both opened. The air conditioner is pre-heated by turning on the power.
Set the air conditioner under the mode of COOLING with the remote controller, and check the following points per the Owner s M anual If th ere is a ny m alfunction, p lease resolve it through chapter Troubles And Causes in the Owner s Manual .
1) The indoor unit a. Whether the switch on the remote controller works well. b. Whether the buttons on the remote controller works well. c. Whether the air flow louver moves normally. d. Whether the room temperature is adjusted well. e. Whether the indicator lights normally. f. Whether the temporary buttons works well. g. Whether the drainage is normal. h. Whether there is vibration or abnormal noise during operation. I. Whether the air conditioner heats well in the case of the HEATING/COOLING type.
2) The outdoor unit a. Whether there is vibration or abnormal noise during operation. b. Whether the generated wind, noise, or condensed water by the air conditioner have influ­ enced your neighborhood. c. Whether any of the refrigerant is leaked.
A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is restarted immediately after shut off .