Lennox AC13 -018, AC13 -030, AC13-036, AC13 -024, Elite AC13 Series Installation Instructions Manual

...
INSTALLATION
2008 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
CAUTION
IMPORTANT
INSTRUCTIONS
Elite® Series AC13 Units
AIR CONDITIONER
506109−01 10/08 Supersedes 07/08
Table of Contents
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . .
AC13 Air Conditioner Units 1. . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 3. . . . .
Removing Existing Outdoor Unit 5. . . . . . . . . . . . . . . . .
Positioning New Outdoor Unit 6. . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 7. . . . . . . . . . . . . . . . .
New or Replacement Line Set 8. . . . . . . . . . . . . . . . . . .
Brazing Connections 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing Indoor Unit Metering Device 11. . . . . . . . . . .
Installing New Indoor Unit Metering Device 12. . . . . . . .
Testing for Leaks 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 14. . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 15. . . . . . . . . . .
Electrical Connection 15. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Charging Procedures 16. . . . . . . . . . . . . . .
System Operation 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Homeowner Information 22. . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 23. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 24. . . . . . . . . . . . .
Shipping and Packing List
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1  Assembled outdoor unit 1  Refrigerant flow control kit (Fixed Orifice)
Litho U.S.A.
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox AC13 Engineering Handbook.
10/08 506109−01
*2P1008* *P506109-01*
AC13 Air Conditioner Units
The AC13 Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HCFC−22 refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox AC13 Engineering Handbook.
This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:
Thermal expansion valve (TXV) Fixed orifice
Page 1
Unit Dimensions − Inches (mm)
SUCTION LINE CONNECTION
RUN
CAPACITOR
CONTACTOR
DISCHARGE
LINE
OUTDOOR FAN
COMPRESSOR
UNIT SUPPORT
FEET
TOP VIEW
DISCHARGE AIR
SIDE VIEW
LIQUID LINE CONNECTION
LIQUID LINE
CONNECTIONS
SUCTION LINE
SUCTION VALVE AND GAUGE PORT/SUCTION LINE CONNECTIONS
PARTS ARRANGEMENT
C
LIQUID LINE CONNECTION
ELECTRICAL INLETS
SUCTION LINE CONNECTION
A
2 (51)
4−1/4 (108)
4−3/4 (121)
1 (25)
UNIT SUPPORT FEET
B
SIDE VIEW
8−1/2 (216)
8−3/4 (222)
5−1/2 (140)
13−1/2
(343)
AC13−018, −024, −030 AND −036
9−1/2 (241)
8−1/4 (210)
D
E
F
G
AC13 BASE WITH ELONGATED LEGS
BASE SECTIONS
AC13 A B C D E F G H J
−018
−024
−030
−036
−042
−048
−060
27(686) 27 (686) 28 (711)
27(686) 27 (686) 28 (711)
31 (787) 27 (686) 28 (711)
31 (787) 27 (686) 28 (711)
35 (889) 27 (686) 28 (711) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
35 (889) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92) 4−1/2 (114) 20−5/8 (524)
45 (1143) 30−1/2 (775) 35 (889) 13−7/8 (352) 7−3/4 (197) 3−1/4 (83) 27−1/8 (689) 3−5/8 (92 4−1/2 (114) 20−5/8 (524)
Page 2
506109−01 10/08
K
J
H
K
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.
Table 1. Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
USING MANIFOLD GAUGE SETS
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings. See figure 3 for a typical manifold gauge connection setup.
OPERATING SERVICE VALVES
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
The liquid and suction line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem.
1/12 TURN
12
1
2
3
4
7
5
6
9
10
8
11
1/6 TURN
12
1
2
3
4
7
5
6
11
10
9
8
Figure 1. Cap Tightening Distances
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque listed.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Operating Angle−Type Service Valve
To Access Angle−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
SERVICE PORT CAP
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CLOSED TO BOTH
INDOOR AND
OUTDOOR UNITS
FRONT-SEATED
CORE
VALVE STEM
TO INDOOR
UNIT
TO OUTDOOR UNIT
Figure 2. Angle−Type Service Valve
(Font−Seated Closed)
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
Page 3
AC13 SERIES
OUTDOOR UNIT
OUTDOOR
COIL
(UNCASED COIL SHOWN)
TXV OR FIXED ORIFICE
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HCFC−22
DRUM
HIGH
LIQUID LINE
SERVICE VALVE
COMPRESSOR
Figure 3. Typical Gauge Manifold Connections
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Angle−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
SERVICE PORT CAP
SERVICE PORT
CORE
OPEN TO BOTH
INDOOR AND
OUTDOOR UNITS
TO INDOOR
UNIT
TO OUTDOOR UNIT
STEM CAP
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Figure 4. Angle−Type Service Valve
(Back−Seated Opened)
1. Remove stem cap with a wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes and 5/16" for suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
Without Torque Wrench: Finger tighten and i\use
an appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 1.
SUCTION LINE SERVICE VALVE
Operating Ball−Type Service Valve
To Access Ball−Type Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in figure 1.
To Open and Close Ball−Type Service Valve:
A valve stem cap protects the valve stem from contamination and assures a leak−free seal.
1. Remove stem cap with a wrench.
2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
3. Replace the stem cap and tighten as follows:
With Torque Wrench: Tighten finger tight and then
tighten per table 1.
Without Torque Wrench: Finger tighten and use an
appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in figure 1.
NOTE − A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified valve listed.
506109−01 10/08
Page 4
OPEN TO LINE SET WHEN VALVE IS CLOSED, TO BOTH LINE SET AND UNIT WHEN VALVE IS OPEN.
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
TO INDOOR UNIT
BALL (SHOWN CLOSED)
STEM CAP
VALV E STEM
Figure 5. Ball−Type Service Valve
Recovering Refrigerant from Existing HCFC−22 System
Remove existing HCFC−22 refrigerant using one of the following methods:
METHOD 1:
Use this method if the existing outdoor unit is not equipped with manual shut−off valves, and plan on using existing HCFC−22 refrigerant to flush the system.
NOTE − Use recovery machine instructions for specific setup requirements.
Perform the following task:
1. Disconnect all power to the existing outdoor unit.
2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections.
3. Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
RECOVERY MACHINE
CLEAN RECOVERY CYLINDER
Figure 6. Typical Refrigerant Recovery (Method 1)
MANIFOLD GAUGES
OUTDOOR UNIT
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and plan on using new HCFC−22 refrigerant to flush the system.
IMPORTANT: Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if
applicable) when tripped can cycled the compressor OFF.
Compressor can stop pumping due to tripped internal
pressure relief valve.
Compressor has internal vacuum protection that is
designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals).
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
1. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
2. Pump as much of the existing HCFC−22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.
NOTE − It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
3. When the low side system pressures reach 0 psig, close the suction line valve.
4. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Removing Existing Outdoor Unit
Perform the following task at the existing outdoor unit:
Disconnect line set at the service valves. Disconnect electrical service at the disconnect switch. Remove old outdoor unit.
Page 5
AC13 SERIES
Positioning New Outdoor Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 7 for mandatory installation clearance requirements.
*
*
* SEE NOTES BELOW THIS FIGURE FOR FURTHER DETAILS.
Figure 7. Installation Clearances
*
*
Some localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 8.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 9.
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BUILDING STRUCTURE
MOUNTING SLAB
NOTES:
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36
in. (914 mm)
Clearance to one of the remaining two sides may be
12 in. (305 mm) and the final side may be 6 in. (152 mm)
48 in. (1219 mm) clearance required on top of unit. A clearance of 24 in. (610 mm) must be maintained
between two units
POSITIONING CONSIDERATIONS
INSTALL UNIT AWAY
FROM WINDOWS
GROUND LEVEL
Figure 9. Slab Mounting at Ground Level
NOTE − If necessary for stability, anchor unit to slab as described in Stabilizing Unit on Uneven Surfaces on page.
ELEVATING THE UNIT (SMALL−BASE UNITS)
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be done by cutting four equal true−cut lengths of Schedule (SCH) 40, 4" (101.6mm) piping to the height required as illustrated in figure 10.
BASE
TWO 90° ELBOWS
INSTALLED IN LINE SET
WILL REDUCE LINE SET
VIBRATION.
Figure 8. Outside Unit Placement
506109−01 10/08
LEG DETAIL
4" (101.6MM) SCH 40 PIPING
Figure 10. Elevated Slab Mounting using Feet
Extenders (Small Base Units)
Page 6
NOTE − Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
The inside diameter of the 4" (101.6mm) piping is approximately 0.25" (6.35mm) greater than the pre−installed feet on the unit. Devise a shim that will take up the space and hold the extenders onto the feet during this procedure. Small strips of 0.125" (3.175mm) thick adhesive foam may be used. One or two small 1" (25.4mm) square strips should be adequate to hold the extender in place.
ELEVATING THE UNIT (LARGER−BASE UNITS)
Unlike the small−base units which use round support feet, the larger−base units are outfitted with elongated support feet as illustrated in figure 11 which uses a similar method for elevating the unit.
If additional elevation is necessary, raise the unit by extending the length of the unit support feet. This may be achieved by using a 2" SCH 40 female threaded adapter. The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2" SCH 40 male threaded adaptors which can be threaded to the female threaded adaptors to make additional adjustments to the level of the unit.
BASE
Removing and Installing Panels
CAUTION
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
REMOVING PANELS
Remove the louvered panels as follows:
1. Remove two screws, allowing the panel to swing open slightly as illustrated in figure 12.
NOTE − Hold the panel firmly throughout this procedure
2. Rotate bottom corner of panel away from hinge corner post until lower three tabs clear the slots as illustrated in figure 12, detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated in figure 12, detail A.
PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.
LIP
SCREW
HOLES
LEG DETAIL
2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER
Figure 11. Elevated Slab Mounting using Feet
Extenders (Larger Base Units)
ROOF MOUNTING
Install unit at a minimum of four inches above the surface of the roof. Care must be taken to ensure weight of unit is properly distributed over roof joists and rafters. Either redwood or steel supports are recommended.
Page 7
DETAIL A
DETAIL B
ROTATE IN THIS DIRECTION;
Detail C
THEN DOWN TO REMOVE
IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.
PANEL
Figure 12. Removing/Installing Louvered Panels
(Details A, B and C)
AC13 SERIES
HOLD DOOR FIRMLY TO THE HINGED SIDE TO MAINTAIN FULLY−ENGAGED
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.
TABS
Figure 13. Removing/Installing Louvered Panels
(Detail D)
INSTALLING PANEL
Install the louvered panels as follows:
1. Position the panel almost parallel with the unit as illustrated in figure 13, detail D with the screw side as close to the unit as possible.
2. With a continuous motion slightly rotate and guide the lip of top tab inward as illustrated in figure 12, details A and C; then upward into the top slot of the hinge corner post.
3. Rotate panel to vertical to fully engage all tabs.
4. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
5. When panel is correctly positioned and aligned, insert the screws and tighten.
STABILIZING UNIT ON UNEVEN SURFACES
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
With unit positioned at installation site, remove two side louvered panels to expose the unit base pan. Install the brackets as illustrated in figure 14 using conventional
practices; replace the panels after installation is complete.
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unsta­ble in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
Slab Side Mounting
#10 1/2" LONG SELF−
DRILLING SHEET
METAL SCREWS
STABILIZING
BRACKET (18 GAUGE
METAL − 2" WIDTH;
HEIGHT AS REQ’D)
#10 1−1/4" LONG
HEX HD SCREW
AND FLATWASHER
CONCRETE SLAB − USE PLASTIC PLASTIC ANCHOR (HOLE DRILL 1/4")PLASTIC SLAB − NO PLASTIC ANCHOR (HOLE DRILL 1/8")
COIL
BASE PAN
CORNER POST
Deck Top Mounting
STABILIZING BRACKET (18 GAUGE METAL − 2" WIDTH; HEIGHT AS REQ’D); BEND TO FORM RIGHT ANGLE
FOR EXTRA
ONE BRACKET PER SIDE (MIN.); FOR EXTRA STABILITY, 2 BRACKETS PER SIDE, 2" FROM EACH CORNER.
STABILITY
MINIMUM 1 PER SIDE
Figure 14. Installing Stabilizer Brackets
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set is not being installed then proceed to Brazing Connections on page 10.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. Also, consider the following when placing and installing a high−efficiency air conditioner.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or sweat connections). Use Lennox L15 (sweat, non−flare) series line set, or use field−fabricated refrigerant lines as listed in table 2.
NOTE − When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following points:
506109−01 10/08
Page 8
Loading...
+ 16 hidden pages