High/Low/Off PIR Fixture Integrated Outdoor Sensor
Haut/Bas/Éteint Luminaire avec détecteur IRP extérieur intégré
No: 24057 – 12/17 rev. 3
Catalog Number • Numéro de Catalogue • Número de Catálogo: FSP-211
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
FSP-211-U is BAA and TAA compliant (Product produced in the U.S.)
14-18 AWG Soli
LOAD
FSP-211
High/Low PIR
LINE
Occupancy Sensor
230 VAC, 50 Hz
d CU Wire Only
NEUT
Class 2 Wiring Only
18-20 AWG Solid CU Wire Only
GRND
DIM-
(grey)
DIM+
(violet)
15195r1
1200W max ballast
5E4
DESCRIPTION AND OPERATION
The FSP-211 is a motion sensor that dims lighting from high to low
based on movement. This slim, low-profile sensor is designed for
installation inside the bottom of a light fixture body. The PIR lens
module connects to the FSP-211 through a 1.30" diameter hole in
the bottom of the fixture.
The sensors use passive infrared (PIR) sensing technology that
reacts to changes in infrared energy (moving body heat) within the
coverage area. Once the sensor stops detecting movement and
the time delay elapses lights will go from high to low mode and
eventually to an OFF position if it is desired. Sensors must directly
“see” motion of a person or moving object to detect them, so
careful consideration must be given to sensor luminaire placement
and lens selection. Avoid placing the sensor where obstructions
may block the sensor’s line of sight.
The FSP-211 operates at 120V/277V, and 230V-240V Single
Phase. No power pack is required. It is designed to be installed in
both indoor and outdoor environments.
PIR Sensor
Motion Indicator
Red LED
Light Sensor
IR Transmitter
Alto/Bajo/Apagado Sensor PIR para fixturas y uso exterior
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
Voltage ..................... 230-240V, 50/60Hz, Single Phase: TUV, CE
Body ......1.38” x 3.8” x 0.9” (35.1mm x 96.5mm x 22.9mm)
Weight ........................................................................2.8 oz (80 g)
Coverage
FSP-L2 Lens @ 8’ height ....................... up to 44’ diameter
FSP-L3 Lens @ 20’ height ..................... up to 40’ diameter
FSP-L7 Lens @ 40’ height ................... up to 100’ diameter
Adjustments and Features
High Mode ............................................................ 0 V -10 V
Low Mode ............................................. . . . 0 V - 9.8 V, Off
Time Delay ...............................30 seconds, 1 min - 30 min
Cut Off ...........................Disable, 1 min - 59 min ,1 hr - 5 hr
Sensitivity .......................... On-Fix, Off-Fix, Low, Med, Max
Hold Off Setpoint .......................... Auto, None, 1 fc - 250 fc
Ramp Up .........................................Disable, 1 sec - 60 sec
Fade Down ......................................Disable, 1 sec - 60 sec
Photocell Setpoint for On/Off ................................. 1-250 fc
®
SPECIFICATIONS
parameters to operate. If adjustments are needed, Wattstopper
FSIR-100 configuration tool must be used.
Once powering the device up, the FSP-211 will use factory default
IR Receiver
Factory Defaults
High Mode ....................................................................10 V
Low Mode .............................................................. . . . 1 V
Time Delay ................................................................. 5 min
Cut Off ........................................................................... 1 hr
Sensitivity .................................................................... Max
Hold Off Setpoint .................................................... Disable
Ramp Up ................................................................. Disable
Fade Down .............................................................. Disable
Photocell Setpoint for On/Off .................................. Disable
OPEN DEVICE for installation in the Listed Enclosure per
Installation Instructions.
INSTALLATION
L
L
15195r1
G Solid CU Wire Only
G Solid CU Wire Only
1. Determine an appropriate mounting location inside the light fixture
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
minimizing the electric light contribution to the sensor’s photocell.
Allow a minimum distance of 0.2" (5.1mm) from the wiring end of
the sensor to the wall of the fixture.
2. Drill a hole 1.30" (33.0mm) in diameter through the sheet metal in
the bottom of the fixture.
3. Add the rubber gasket to the threaded collar, and install the sensor
Inside Fixture
Wall
FSP-211
Rubber
Gasket
face down, parallel to the mounting surface. Ensure the rubber
gasket touches the inside surface of the fixture. Install the plastic
nut (or optional collar) securely against the fixture to a torque of
25-30 in-lbs to ensure IP rating is maintained.
4. Align the locking features between the sensor and lens module and
Tightening Nut
(or Optional Collar)
Outside
Fixture Wall
Tightening Nut
(or Optional Collar)
Lens Assembly
Rubber
Gasket
Fixture
Wall
push the lens module forward until the o-ring seals firmly. Turn the
lens module clockwise to ensure it locks in place.
5. Connect wires as shown in wiring diagram.
6. Restore power from the circuit breaker.
NOTE: An optional collar can be installed in place of the tightening nut.
NOTE: The Outside Fixture Wall thickness should be no
greater than 0.125" (3.18mm) for optimal sensor
mounting and security.
See the Ordering Information table on page 4 for details.
LENS OPTIONS
Several lenses are available for use with the FSP-211. Lenses give coverage at mounting heights between 8' - 40' for applications such
as offices, warehouses, and outdoor use. Density and range of the coverage is determined by the type of lens and mounting height.
Lens modules are IP-66 rated when combined with an FSP-211 sensor mounted to an outdoor-rated fixture. See the FSP-Lx Lens
Coverage Guide for more information.
NOTE: The FSP-211 must be grounded to
ensure signal integrity, not for safety
ground.
OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC LOCATION PER
INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE.
USING THE FSIR-100 CONFIGURATION TOOL
Non-Dimming
Driver
WIRING
NEUTRAL
LOAD
* GROUND
LINE
LOAD
LINE
14-18 AWG Solid CU Wire Only
FSP-211
High/Low PIR
Occupancy Sensor
230 VAC, 50 Hz
1200W max ballast
5E4
18-20 AWG Solid CU Wire Only
(grey)
DIM-
GRND
NEUTRA
NEUT
15195r1
(violet)
DIM+
Dimming
Driver
NEUTRAL
LOAD
*GROUND
LINE
LOAD
LINE
14-18 AW
FSP-211
High/Low PIR
Occupancy Sensor
230 VAC, 50 Hz
1200W max ballast
5E4
18-20 AW
(grey)
DIM-
GRND
NEUTRA
NEUT
(violet)
DIM+
The configuration process establishes the appropriate parameters for the FSP-211 operation. This is done through the FSIR-100
configuration tool. If no configuration steps are taken, the sensor will use its default parameter values.
The FSIR-100 Wireless IR Configuration Tool is a handheld tool for changing defaults and testing of Wattstopper FSP-211.It provides
wireless access to the FSP-211 sensors for parameter changes and testing.
The FSIR-100 display shows menus and prompts to lead you through each process. The navigation pad provides a simple way to
navigate through the customization fields.
Within a certain mounting height of the sensor, the FSIR-100 allows modification of the system without requiring ladders or tools; simply
with a touch of a few buttons.
The FSIR-100 IR transceiver allows bi-directional communication between the FSP-211 and the FSIR-100 configuration tool. Simple
menu screens let you see the current status of the sensor and make changes. It can change FSP-211 sensor parameters such as high/
low mode, sensitivity, time delay, cut off, and more. With the FSIR-100 you can also establish and store FSP-211 parameter profiles.
2
BATTERIES
Select
Right/Next
IR tx/rx
The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three rechargeable AAA
NiMH batteries. The battery status displays in the upper right corner of the display. Three bars next
to BAT= indicates a full battery charge. A warning appears on the display when the battery level falls
below a minimum acceptable level. To conserve battery power, the FSIR-100 automatically shuts off
10 minutes after the last key press.
• If communication is not successful, (if possible) move closer to the sensor.
• If still not successful, there may be too much IR interference from other sources. Programming
the unit at night when there is no daylight available may be the only way to communicate with
the sensor.
NAVIGATION
Navigate from one field to another using (up) or (down) arrow keys. The active field is indicated
by flashing (alternates) between yellow text on black background and black text on yellow
background.
Once active, use the Select button to move to a menu or function within the active field. Value
fields are used to adjust parameter settings. They are shown in “less-than/greater-than” symbols:
<value>. Once active, change them using(left) and(right) arrow keys. The right key increments
and the left key decrements a value. Selections wrap-around if you continue to press the key
beyond maximum or minimum values. Moving away from the value field overwrites the original
value. The Home button takes you to the main menu. The Back button can be thought of as an
undo function. It takes you back one screen. Changes that were in process prior to pressing the
key are lost.
Power
On/Off
Back
Left
Down
FSP-2X1
HBP-111
BAT=
Home/Main
Menu
Up
IR COMMUNICATION
IR communication can be affected by the mounting height of the sensor and high ambient lighting such as
direct daylight or electric light such as floodlights, and some halogen, fluorescent lamps, LED’s.
When trying to communicate with the FSP-211, be sure to be positioned under the sensor without any
obstructions. Every time the commissionng tool establishes communication with the FSP-211, the controlled
load will cycle.
15'-32'
* Distance may vary depending on
the lighting environment
TROUBLESHOOTING
Lights will not go to High Mode:
• Check all wire connections and verify the load and the ground wires are tightly secured.
• Make sure that the sensor is not obstructed.
• Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness
in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient
light will cause the lights to be held OFF. See the new settings section for instructions.
• If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go into Low Mode:
• The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor’s view for that time period.
• To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after 5
seconds.
• If lights still do not fade to Low Mode, call 800.879.8585 for technical support
3
Lights will not turn OFF:
• Cut Off time may be set to “None.”
• Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor’s view for that time period when
the lights are in Low Mode.
• To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to low mode after
5 seconds, and the OFF (if cut off is enabled) after 10 sec.
• If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
• If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
• If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
There is no IR communication:
Perform a power cycle on the FSP-211.
OPERATION DURING POWER-UP
During the sensor warm-up period, which can last up to 5 seconds after initial power-up (or after a lengthy power outage), the load will
remain ON until the selected time delay expires.
ORDERING INFORMATION
Catalog #Description
FSP-211Digital High/Low PIR Fixture Integrated Sensor
FSIR-100Configuration Tool
FSP-L260° lens, up to 44’ diameter at 8’ height
FSP-L3360° lens, up to 40’ diameter at 20’ height
FSP-L7360° lens, up to 100’ diameter at 40’ height
FSP-C1Small collar, for use with FSP-L2 and FSP-L3 lenses
FSP-C2Large collar, for use with FSP-L7 lens
Sensor is White.
4