LEGRAND Wattstopper EQ41-LCAP Installation Instructions Manual

Wattstopper
Architectural Dimming Equinox 41 LCD Keypad French Description
No: IS-00711 – rev. A
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
Spanish Description
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
®
Are...
Legrand’s Equinox 41-LCAP LCD Touchscreen is designed to be installed in a single gang box and is a similar size to traditional keypads. Legrand’s Equinox 41-LCAP uses self discovering widgets, eliminating countless hours of tedious programming. Navigate and control, with real time feedback. Widgets may be further personalized or additional controls setup directly on the touchscreen, by selecting the Settings Menu in the upper right hand corner of the screen with the gear symbol . In the settings menu the administrator of the system can change or create the following: scenes, event timers, schedules, etc. The interface uses intuitive gestures; swipe left and right to change widgets, touch and release for normal button operation, or press and hold for dim-cycle, shade controls, etc.
OVERVIEW
FEATURES AND OPERATION OVERVIEW
Vertical screen orientation displays main room button screen, as a default, with all widgets appropriate for the space where the touchscreen is located, in the widget bar
Equinox platform provides built-in widgets using Legrand’s proprietary auto discovery widgets for fast automatic screen design
Equinox 41-LCAP incorporates consistent user experience interface. In-wall touchscreens, tablets and smart phones use the same user interface
Power over Ethernet, PoE or PoE+
- PoE optional Ethernet 4 Port PoE Injector part number DA2400 or COM-POE-SWITCH
Communicates over Ethernet, via Ethernet Bus
Firmware upgradeable over Ethernet from Design Center
Built-in ambient light sensor for “Active,” AUTO mode screen brightness
Built-in proximity activation, 6” maximum, may be programmed to execute a task with a hand wave across front of station
Dual operation mechanical buttons, bottom left and right;
- Left navigates to default widget
- Right may be programmed with a task from Design Center
Three types of users are supported on the system. Using a variety of users you can limit what is available to specic individuals as well as limit permissions.
- Administrators - All permissions and visibility into the system. Only one system-wide administrator can be assigned whose
password is set up at system startup. The admin password can be created or changed from within Equinox view. It is not
dependent on the rst time initialization screen.
- Managed Users - A password protected user who can have a wide variety of permissions granted to them, including the
creation of other users. There is no limit to the number of managed users.
- Guest Users - Recommended to be the default user on all screens in public areas, guest users cannot make any changes
to the system and have no permissions to set. They cannot be password protected.
Top of screen displays:
- Administrator/user details
- Access help topics
- Manage settings including appearance, access/permissions, areas and rooms, devices, events, groups, repair, schedules,
scenes, and systems
Main screen automatically displays widgets based on Design Center project le (order may be changed in user/settings directly from the app) including shades, lighting, home, and scenes
Raise/lower dimmable loads, shades, hue and intensity settings using sliders
1
FEATURES AND OPERATION OVERVIEW (continued)
NOTE: If buttons are held in too long, the screen will boot to service
mode, and will not load the application code. Repeat manual reboot – without holding buttons to long – to clear this mode.
Station reset – simultaneously press and hold both mechanical buttons for three seconds until the screen goes dark, then release
Station reset into Service Mode – simultaneously press and hold both mechanical buttons for ten seconds
- Service mode is automatically used when updating rmware from Design Center
- If the application code is corrupt it may cause the screen to lock, preventing Design Center from updating or reloading the
rmware. Use this option to reboot the screen to service mode allowing Design Center to update the corrupted rmware.
- To manually exit Server Mode use the Station Reset option (above)
SPECIFICATIONS
Description Specication
Dimensions, HWD (at wall surface) 4.9” x 3.44” x 0.44” (124mm x 87mm x 11mm)
Dimensions, HWD (overall) 4.9” x 3.44” x 1.1” (124mm x 87mm x 28mm)
Finished Weight 8.8 oz. or 249.5g
Power Ethernet with PoE, PoE+, 5W
Wiring Connections Communication and power: PoE/PoE+ via Ethernet RJ45
Surge Suppression Yes
Maximum Gangs Single gang only
LCD Button Status Automatic (white = off, orange = on)
Mounting US/European style, single gang, wall boxes or low-voltage brackets
Addressing Self-addressing through software
Finish Trim: Titanium, Touchscreen: Black glass
Glass Surface Chemically strengthened
Ambient Operating Temperature 32-95°F (0-35°C)
Ambient Operating Humidity 5-95% non-condensing
CE/FCC Compliant Yes
Equinox 41-LCAP is compatible with InFusion Design Center version 3.8 software or higher. For new projects it is recommended that rmware and software be kept to the most current release.
Installation of Legrand products should be performed or supervised by a certied Legrand installer. The Equinox 41-LCAP
touchscreen installs into US/European style, single gang, wall boxes or low-voltage brackets. Connect to local network via PoE/PoE+
RJ45 Ethernet connection.
No: IS-00711 – Rev. A
SYSTEM REQUIREMENTS
INSTALLATION
2
in station bottom
B
ETHERNET PoE or PoE+
INSTALLATION OVERVIEW
EQUINOX 41-LCAP
TOUCHSCREEN
Harv...
Open Rest Ge...
RJ45 CONNECTOR
PoE/PoE+
ETHERNET BUS
SCREWS*
4 SQUARE JUNCTION
NETWORK PANEL
OR SWITCH
*Ethernet Bus: Power and communication; Ethernet, PoE or PoE+, (Optional) - Ethernet 4 Port PoE Injector (part# DA2400)
BOX RING
*Use flat-head screws provided US – 6-32 x 0.75”
EQUINOX 41-LCAP
LCD SCREEN
EQUINOX 41-LCAP STATION INSTALLATION STEPS
1. Run PoE Ethernet bus to four square junction box
2. Install ring with screws provided (gure A)
3. Connect RJ45 to station
4. Install station by rotating (gure B) and connecting the top rst.
Press station in and hold on bottom center while securing the hex screw with provided allen wrench (gure C)
A
No: IS-00711 – Rev. A
Press and hold here on
front, bottom center
1/16” HEX
C
Set 1/16” hex screw
3