1.6.2 Guarantee extension and maintenance contracts 7
1.7 Copyright 7
2 Regulatory and safety requirements 8
2.1 General notes 8
2.2 Denitions of “Skilled Technician” and “Operator” 8
2.2.1 Skilled Technician 8
2.2.2 Operator 8
2.3 Personal Protective Equipment 9
2.4 Hazard signs in the workplace 9
2.5 Signs on the equipment 9
2.6 General warnings 10
2.7 How to proceed in an emergency 11
2.7.1 First-aid procedures 11
2.7.2 Fire procedures 11
3 Technological description 12
3.1 Trimod MCS technology 12
3.2 Features 14
3.3 Models 16
3.4 Block diagram of interconnections and distributions of the EPS 20
4 Unpacking and positioning 21
4.1 Visual check 21
4.1.1 Equipment and supplied accessories check 21
4.2 Unpacking 21
4.3 Check of the content 21
4.4 Movement 22
4.5 Positioning constraints 22
4.6 Final operations 22
5 Communication devices 23
5.1 RS232 serial ports 23
5.2 Contact interface 24
5.3 Emergency Power O (EPO) 24
5.4 Logic level interface 25
5.5 Network card (SNMP) slot 26
User manual
3
Contents
6 Control panel 27
6.1 Description 27
6.2 Service Mode 28
6.3 Main screen 28
6.4 Main menu and submenu 30
6.4.1 UPS Status 31
6.4.2 UPS Setup 33
6.4.3 Power Modules 37
6.4.4 Events 39
6.4.5 Tools 39
6.4.6 Log Out 39
6.5 POWER ON/OFF menu 40
6.6 Switching o the EPS 40
6.7 Switching on the EPS 40
7 Diagnosis 41
7.1 Luminous and audible notications 41
7.2 Messages 43
8 Installation and maintenance 50
8.1 Introduction 50
8.2 Installation 50
8.3 Preventive maintenance 50
8.4 Periodical checks 50
8.5 Ordinary maintenance 50
8.6 Extraordinary maintenance 50
9 Warehousing 51
9.1 EPS 51
9.2 Batteries 51
10 Dismantling 52
10.1 Battery disposal 52
10.2 EPS dismantling 52
10.3 Electronic component dismantling 52
11 Technical data 53
4
Trimod MCS
1. Introduction
CAUTION
The instructions in this manual are intended for an OPERATOR (paragraph 2.2.2)
1.1 General information
Congratulations on your LEGRAND TRIMOD MCS EPS purchase.
Thanks to this EPS, your critical equipment will always be protected by a constant and reliable electricity supply.
LEGRAND is specialized in designing and producing EPS. Trimod MCS is unique in its kind: it is modular, redundant and
belongs to the last generation of medium power EPS.
High reliability, low running costs and excellent electrical performance are some of its features. The high quality standard
of LEGRAND in design and production allows Trimod MCS to pass the strictest quality tests.
The EPS has been designed in compliance with the existing European Union directives, with the technical standards that
include their requirements and with the eco-design guidelines.
The equipment is produced at an ISO14001 certified factory.
This publication, simply defined “user manual” herein, contains all the information for the use of the Trimod MCS EPS, also
referred to as “equipment” in this manual.
User manual
The contents of the user manual are intended mainly for an operator (see paragraph 2.2.2) or for people, generically defined as “users”, who have the need and/or obligation to provide instructions or work directly on the equipment for their
assigned tasks.
These people can be the following:
- managers;
- heads of operating areas;
- department heads;
- direct private users.
The original text of this publication, drafted in Italian, is the only reference for the resolution of disputes of interpretation
linked to translations into other languages.
1.2 Purpose of the manual
The purpose of this manual is to provide the operator with instructions for safely using the equipment after the installation performed by a skilled technician.
Any adjustments and extraordinary maintenance operations are not dealt with in this manual because they are the sole
preserve of the LEGRAND Technical Support Service.
The reading of this manual is essential but does not substitute the skill of the technician who must have received adequate preliminary training.
The intended use and configurations envisaged for the equipment and shown in this manual are the only ones allowed
by the Manufacturer.
Any other use or configuration must be previously agreed with the Manufacturer in writing and, in this case, the written
agreement will be attached to the installation and user manual.
This manual also makes reference to laws, directives and standards that the operator is required to be aware of and consult.
5
1. Introduction
1.3 Symbols in the manual
Some operations are shown in graphic symbols that draw the attention of the reader to the danger or the importance
they imply:
DANGER
This indication shows a danger entailing a high degree of risk that, if not avoided, will lead to death or serious injury or
considerable damage to the equipment and the things around it.
WARNING
This indication shows a danger entailing a medium degree of risk that, if not avoided, could lead to death or serious injury
or considerable damage to the equipment and the things around it.
CAUTION
This indication shows a danger entailing a low level of risk that, if not avoided, could lead to minor or moderate injury or
material damage to the equipment and the things around it.
INDICATION
This symbol indicates important information which should be read carefully.
1.4 Where and how to keep the manual
This manual must be kept in a safe, dry place and must always be available for consultation.
It is recommended to make a copy of it and file it away.
If information is exchanged with the Manufacturer or the authorised assistance personnel, it is essential to refer to the
equipment’s rating plate data and serial number.
INDICATION
The supplied manuals are an integral part of the equipment and must therefore be kept for their entire lifetime.
In case of need (for example in case of damage that even partially compromise the consultation) the operator is required
to get a new copy from the Manufacturer, quoting the publication code on the cover.
1.5 Update of the manual
The manual reflects the state of the art when the equipment was put onto the market. The publication conforms with the
directives current on that date. The manual cannot be considered inadequate when new standards come into force or
modifications are made to the equipment.
Any addition the Manufacturer considers appropriate to send to the users, must be kept together with the manual of
which they will become an integral part.
The updated version of the manual is available on the Internet at http://www.ups.legrand.com
1.6 Manufacturer's liability and guarantee
The skilled technician and the operator shall scrupulously comply with the precautions indicated in the manuals. In particular they must:
- always work within the operating limits of the equipment;
- always carry out constant and careful maintenance through a skilled technician who complies with all the procedures
indicated in the installation and maintenance manual.
The Manufacturer declines all indirect or direct responsibility arising from:
- installation and wiring completed by personnel not possessing the qualifications required by the regulations of the
country of installation for working on equipment operating on dangerous voltages;
- installation and wiring completed by personnel not wearing the Personal Protective Equipment required by the regulations of the country of installation;
- failure to observe the installation, maintenance instructions and use of the equipment which differs from the specifications in the user manual;
- use by personnel who have not read and thoroughly understood the content of the user manual;
- use that does not comply with the specific standards used in the country where the equipment is installed;
- modifications made to the equipment, software, operating logic unless they have been authorised by the Manufacturer
in writing;
6
Trimod MCS
- repairs that have not been authorised by the LEGRAND Technical Support Service;
- damage caused intentionally, through negligence, by acts of God, natural phenomena, fire or liquid infiltration.
- damage caused by the use of batteries or protections other than those indicated in the installation and maintenance
manual;
- damage caused by failure to install or establish the safety protections indicated in the manuals, or by failure to comply
with the safety labels.
Transfer of the equipment to others also requires the handing over of all the manuals. Failure to hand over the manuals
shall automatically nullify any right of the buyer, including the terms of the guarantee where applicable.
If the equipment is sold to another party in a country where a dierent language is spoken, the original owner shall be
responsible for providing a faithful translation of the manuals in the language of the country where the equipment will
be used.
1.6.1 Guarantee terms
The terms of the guarantee may vary depending on the country where the EPS is sold. Check the validity and duration
with LEGRAND's local sale representative.
If there should be a fault in the equipment, contact the LEGRAND Technical Support Service which will provide all the
instructions on what to do.
Do not send anything back without LEGRAND's prior authorization.
User manual
The guarantee becomes void if the EPS has not been brought into service by a properly trained skilled technician
(see paragraph 2.2.1).
If during the guarantee period the EPS does not conform with the characteristics and performance laid down in this manual, LEGRAND at its discretion will repair or replace the EPS and relative parts.
All the repaired or replaced parts will remain LEGRAND's property.
LEGRAND is not responsible for costs such as:
- losses of profits or earnings;
- losses of equipment, data or software;
- claims by third parties;
- any damage to persons or things due to improper use, unauthorized technical alterations or modifications;
- any damage to persons or things due to installations where the full compliance with the standard regulating the specific
usage applications have not been guaranteed.
1.6.2 Guarantee extension and maintenance contracts
The standard guarantee can be consolidated in an extension contract (maintenance contract).
Once the guarantee period has passed, LEGRAND is available for giving a technical assistance service able to meet all
requirements, maintenance agreements, 24/7 availability and monitoring.
For more information contact the LEGRAND Technical Support Service.
1.7 Copyright
The information contained in this manual cannot be disclosed to any third party. Any partial or total duplication of the
manual by photocopying or other systems, including electronic scanning, which is not authorised in writing by the Manufacturer, violates copyright conditions and may lead to prosecution.
LEGRAND reserves the copyright of this publication and prohibits its reproduction wholly or in part without previous written authorisation.
7
2. Regulatory and safety requirements
DANGER
Before carrying out any operation on the equipment, it is necessary to read the entire manual carefully, especially
this chapter.
Look after this manual carefully and consult it repeatedly while using the EPS.
2.1 General notes
The equipment has been made for the applications given in the manuals. It may not be used for purposes other than
those for which it has been designed, or differently from those specified.
2.2 Definitions of “Skilled Technician” and “Operator”
2.2.1 Skilled Technician
The professional figure who will carry out the installation, start up and ordinary maintenance is called "Skilled Technician".
This definition refers to people who have specific technical qualification and are aware of the method of installing, assembling, repairing, commissioning and safe use of the equipment.
In addition to the requirements listed in the paragraph below for general operators, the Skilled Technician must be qualified in accordance with the safety regulations in force in the country of installation on the measures to implement when
working in presence of hazardous voltage. He must also use the Personal Protective Equipment required by the safety
regulations in force at the country of installation for all the activities indicated in the installation and maintenance manual
(see paragraph 2.3)
WARNING
The safety manager is responsible for protection and company risks prevention according to what is indicated in the
European directives 2007/30/EC and 89/391/EEC regarding safety in the workplace.
The safety manager must ensure that all the people working on the equipment have received all the instructions included
in the manuals with particular reference to those contained in this chapter.
2.2.2 Operator
The professional figure assigned to the equipment for normal use is called "Operator".
This definition refers to people who know how to operate the equipment as described in the user manual and have the
following requisites:
1. technical education, which enables them to operate according to safety standards in relation to the dangers linked to
the presence of electric current;
2. training on the use of Personal Protective Equipment and basic first aid interventions.
The company safety manager in choosing the person (operator) who uses the equipment, must consider:
- the person’s work fitness according to the laws in force;
- the physical aspect (not disabled in any way);
- the psychological aspect (mental stability, sense of responsibility);
- the educational background, training and experience;
- the knowledge of the standards, regulations and measures for accident prevention.
He should also impart training in such a way as to provide thorough knowledge of the equipment and its component
parts.
The operator shall consult the user manual at any time. He shall also follow the requirements provided to achieve maximum safety for himself and others during all operating phases.
Some typical activities the operator is expected to carry out are:
- the use of the equipment in its normal operating status and the restore of the functioning after it shuts down;
- the activation of the necessary provisions for maintaining the quality performance of the EPS;
- the cleaning of the equipment;
- cooperation with personnel responsible for ordinary maintenance activities (skilled technicians).
8
Trimod MCS
2.3 Personal Protective Equipment
DANGER
The equipment poses a considerable risk of electric shock and a high short circuit current. During use and maintenance
operations, it is forbidden to operate without the equipment listed in this paragraph.
People responsible for operating this equipment and/or passing close to it must not wear garments with flowing sleeves,
nor laces, belts, bracelets or other metal pieces that might cause a danger.
The following signs sum up the minimum Personal Protective Equipment to wear at all times.
Additional requirements may be pro vided for by the safety regulations in force in the country of installation.
Anti-accident and no-spark shoes
with rubber sole and reinforced toe
Safety gloves for protection from mechanical risks
User manual
Dielectric gloves for protection from dangerous
voltages
Protective clothing for electrical work
Electrical protection helmet and visor
Insulated tools
2.4 Hazard signs in the workplace
The following signs must be exhibited at all points of access to the room where the equipment is installed:
Electric current
This sign indicates the presence of electrical live parts.
How to proceed in an emergency
Do not use water to quench res but just the extinguishers specically designed for putting out res in electrical
equipment.
No smoking
This sign indicates that smoking is not allowed.
2.5 Signs on the equipment
Displayed on the equipment are explanatory plates that can vary depending on the country the equipment is intended
for and constructional standards applied.
Make sure the instructions are adhered to. It is strictly prohibited to remove these plates and to work in a way that differs
from what is written there.
The plates must always be clearly read and they must be cleaned periodically.
If a plate deteriorates and/or it is no longer legible, even partially, the Manufacturer must be contacted for another one
in order to replace it.
9
2. Regulatory and safety requirements
CAUTION
The plates must not be removed or covered. No other plates may be affixed to the equipment without the Manufacturer's
prior written authorisation.
WARNING
Potential risks can be drastically reduced by wearing the Personal Protective Equipment listed in this chapter. These protections are indispensable. Always operate with due care around dangerous areas marked by the appropriate warning
signs on the equipment.
2.6 General warnings
DANGER
The EPS works with dangerous voltages. Only SKILLED TECHNICIANS must perform the installation and ordinary
maintenance operations. No part of the EPS can be repaired by the operator.
Extraordinary maintenance operations must be carried out by LEGRAND Technical Support Service personnel.
WARNING
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
a) remove watches, rings or other metal objects;
b) use tools with insulated handles;
c) wear rubber gloves and boots;
d) do not lay tools or metal parts on top of batteries;
e) disconnect the charging source prior to connecting or disconnecting battery terminals;
f ) determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with
any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if the ground
connections are removed during installation and maintenance (applicable to remote equipment and battery supplies
without a grounded supply circuit).
g) never leave powered cables uncovered.
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes.
The batteries installed inside the cabinet must be disposed of correctly. For the disposal requirements refer to local laws
and relevant standards.
CAUTION
The EPS works with TT and TN systems. It has a pass-through neutral architecture: the status of the output neutral is
the same as the input neutral.
When the output load needs a different neutral status from the input status, it is necessary to place downstream of the
EPS a suitably scaled isolation transformer protected in compliance with the standards in force.
CAUTION
Do not open the battery fuse holders while the EPS is powering the loads in battery mode.
WARNING
To reduce the risk of fire or electric shock, the EPS must work in clean and indoor environments with controlled temperature and humidity. It must be kept away from inflammable liquids and corrosive substances. The room temperature must
not be above +40°C (+104°F) and the relative humidity must be a maximum of 95% not condensing.
10
Trimod MCS
CAUTION
The equipment generates, uses and can radiate radio frequency energy. If it is not installed and used in accordance with
the instructions in the manuals, it may cause harmful interference with radio communications.
Trimod MCS 3,5,7 and 10 are category C2 products according to standard EN62040-2.
In the home environment these devices could cause radio interference; in this case appropriate countermeasures must
be taken.
All other Trimod MCS models are category C3 products according to standard EN62040-2.
They can therefore be used in commercial and industrial environments; nevertheless restrictions or adequate countermeasures might be necessary to avoid radio interference.
CAUTION
- The equipment must be maintained and used according to the instructions written in the manuals
- The departmental manager must instruct the operating and maintenance personnel on the safe use and maintenance
of the equipment.
- Only specifically-trained, highly skilled personnel are allowed access to the equipment order to perform maintenance.
While the maintenance operation is being carried out, signs saying "Maintenance work in progress" must be affixed in
the department in such a way that they can be easily seen from each and any access area.
- Any intervention on the equipment must be done only after it has been disconnected from the power supply network
by means of a switch disconnector and must be locked with an appropriate padlock.
- The EPS must not be turned on if liquid is leaking from the batteries.
- Depositing flammable material near the equipment is strictly forbidden. The equipment should always be locked, and
only specifically trained personnel are allowed access to them.
- Do not disable any safety, signalling or warning devices and do not ignore any alarms, warning messages or notices, no
matter whether they are generated automatically or represented by plates fixed to the equipment.
- Do not run the equipment with fixed protections not installed (panels etc.).
- In case of breaking, buckling or malfunctioning of the equipment or parts of it, repair or replace immediately.
- For no reason can the equipment, the devices and the operation sequence, be modified, disabled or tampered with in
any way, without prior consultation with the Manufacturer.
- When replacing fuses, only use ones of the same type.
- The replacement of the batteries is an operation intended to be carried out by a skilled technician.
- Keep a register in which to enter the date, time, type, performer’s name and any other useful information about each and
any routine- and extraordinary-maintenance operation.
- Do not use oils or chemical products for cleaning because they could scratch, corrode or damage certain parts of the
equipment.
- The equipment and workplace must be kept completely clean.
- Upon completion of the maintenance operations, before connecting the power supply, carry out a careful check in order
to make sure that no tools and/or material of any kind have been left next to the equipment.
User manual
CAUTION
The skilled technician must not leave at the disposal of the operator:
- the keys for opening the EPS door;
- the installation and maintenance manual.
2.7 How to proceed in an emergency
The following information are general.
For the specific interventions consult the regulations in force in the country where the equipment is installed.
2.7.1 First-aid procedures
When administering first aid, adhere to the company rules and the usual procedures.
2.7.2 Fire procedures
Do not use water to quench fires but just the extinguishers specifically designed for putting out fires in electrical equipment.
11
3. Technological description
3.1 Trimod MCS technology
LEGRAND® has developed an innovative project that is the only one of its kind by producing Trimod MCS, the EPS with 3,
5, 7, 10, 15, 20, 30, 40, 60 and 80 kVA power.
The concepts underlying the project are modularity, expandability and redundancy in such a way as to offer maximum
reliability and to be the guarantee of considerable savings.
Trimod MCS is EPS designed in accordance with EN 50171 for the preservation of power supply in emergency and security
systems. Some of its features are:
- permanent overload capability of 120% in relation to the rated power;
- batteries with rated life expectancy of 10 years;
- battery polarity inversion protection
- protection against complete discharge;
- short circuit protection;
- high current battery charger for full charge time of 12 hours;
- IP20 metal enclosure according to EN 60598-1.
If the mains is available, the EPS output is enabled by default. It is possible to change this setting from the control panel.
If the mains input is missing, the output is supplied by the EPS in battery mode.
Trimod MCS is a modular EPS whose base module is single phase and can be programmed to obtain the desired input/
output configuration. It is thus possible to manage three phase and single phase voltages on input and output to have a
choice of the traditional three phase/three phase, three phase/single phase, single phase/three phase and single phase/
single phase. At the same time it is possible to obtain simultaneously single phase and three phase lines on output or two
or more single phase lines even with different power.
For every configuration it is possible to have redundancy that is both complete and partial. For example, one normal three
phase (or redundant) line can coexist with a redundant single phase (or normal) line on output.
The philosophy underlying modularity has also been applied to the batteries that have been supplied in individual drawers that can be extracted and make installation and maintenance easier.
The EPS is controlled by one command board.
The command board (CM) and the power modules (PM) are identified by a unique address inside the system, as shown below:
CM 0 PM 0 PM 1PM 2
12
Trimod MCS 3-5-10 Trimod MCS 20Trimod MCS 7-15
CM 0 PM 0 PM 1PM 2
PM 3 PM 4PM 5
Trimod MCS
User manual
Trimod MCS 30Trimod MCS 40
CM 0 PM 0 PM 1PM 2
PM 3 PM 4PM 5
PM 6 PM 7PM 8
CM 0 PM 0PM 1PM 2
PM 3PM 4PM 5
PM 6PM 7PM 8
PM 10 PM 11
PM 9
Trimod MCS 60
Trimod MCS 80
13
3. Technological description
The command board is connected to a control panel with display from which it is possible to verify the status and setups
of the EPS and to a communication interface with RS-232 and SNMP connection, dry contacts and logical contacts. It is
possible to access all the EPS functions from the control panel and communicate through any of the interfaces present
thereby guaranteeing the redundancy of the peripherals as well. In installations with three separate single phase line on
output, it is possible to manage each line independently through the software. For example, it is possible to prioritise the
autonomy of one of them during battery operation. A bypass input line separated from that of the mains input makes it
possible to supply the bypass with a second power source (the neutral wires of the two lines must be in common).
The technology used in the hardware and the firmware of the EPS represents the current state of the art.
A sophisticated microprocessor-type control optimises the performance both on the Booster/PFC side and on the output inverter. The recharge curve of the battery has been designed to get the maximum useful life and have the greatest
autonomy possible if the main power goes off. The electronic boards are entirely assembled on LEGRAND automated
lines and tested to the highest quality standards. Every device goes through an extended period of operation at full load
before being sent to the customer.
3.2 Features
Modular-redundant architecture
The modular-redundant architecture is the best solution for protecting the nerve centres of a company and has the following advantages:
- there is one control of the devices supplied;
- modular expandability;
- module redundancy;
- easy maintenance;
- low running cost;
- compactness.
Efficiency
Trimod MCS concentrates particularly on both the energy absorbed from the mains and the energy provided to the load.
They are characterised by high efficiency (up to 96%), PF on input>0,99, THDi <3%.
The advantages of a high efficiency are:
- reduction of the power absorbed from the EPS but not supplied to the load and transmitted to the environment as heat;
- less heat loss transmitted to the environment means reducing the need for ventilation or air conditioning systems in the
installation site;
- no power factor correction cost and so no increase in charges;
- no need to increase the size of any generator upstream of the EPS.
Expandability
Most EPS systems on the market are of the non-modular and non-expandable type thus requiring an initial upscaling of
the system to make future expansions possible.
The advantages of an expandable system are:
- optimisation of investments for EPS, making them adequate for the current requirements without precluding future
expansions and avoiding wastes of energy;
- increase in the efficiency of the system thanks to proper sizing.
Reliability
To obtain a level of redundancy with traditional EPS, it is necessary to put at least two in parallel thereby doubling the
power acquired, the space occupied and the electricity consumed. Trimod MCS modular architecture makes it possible to
have redundant configurations within a single cabinet.
The advantages are:
- a redundant modularity EPS can be configured as a power redundant N+X system. Even in the case of a fault in a
module, the equipment continues to function avoiding any downtime;
- clear indications and a large display make it possible to find the fault more quickly;
- the modular architecture makes it possible to speed up the solution to problems through the simple replacement of the
faulty module without interrupting the service;
- high percentage of faults resolved at the first attempt.
Power module
The high-efficiency single phase module, available in three power sizes of 3400 VA (PM4), 5000 VA (PM6) and 6700 VA
(PM7) respectively, and is mainly made up of the following functional blocks:
- command and control logic (managed by a microprocessor);
- PFC rectifier/booster;
- inverter;
- battery charger;
- automatic bypass.
In each power module there is a microcontroller that can oversee the main functions of the individual unit, monitor its
correct operation and flag up any malfunctions.
The power module is Plug & Play to make the power expansion and any maintenance operation easier. Every module is
put in parallel with other identical ones until reaching the power of the EPS.
The modules are independent of each other and can function even if there is a fault in one of them. At the front of the
module there is a multicoloured LED with traffic-light code green-yellow-red, making it possible to identify the operating
status of the electronic unit quickly.
14
The power modules are housed on shelves also called “tunnels” that can house three modules.
The block diagram of the power module is the following:
Trimod MCS
User manual
Batteries
The battery modules are designed for easy insertion into the dedicated cabinet and they do not need any operation for
their connection. A drawer consists of five 12V-9Ah batteries, connected in series and thanks to the Plug & Play connection it is easy to extract and insert it in the cabinet.
The nominal battery voltage for the Trimod MCS is 240Vdc, therefore a complete branch consists of four battery drawers
(for a total of twenty 12Vdc batteries) that form what is called KB (Battery Kit).
In order to ensure the maximum level of safety, the voltage of each drawer is properly isolated into two branches of 24 V
and 36 V and it is only restored when the drawer is completely inserted into its housing.
This allows conformity with the standard EN 62040-1 on electrical safety that requires the use of adequate protection and
particular care when handling dangerous voltages above 50 Vdc where direct contact is possible.
The battery operation autonomy of the EPS can be increased by adding more battery drawers in multiples of four, using
both the seats in the EPS cabinet if available, and the seats in the additional modular battery cabinets.
Digital display and alarm display
Trimod MCS is managed by a microprocessor-type command board (according to the version) and it has a backlit LCD
alphanumeric display with twenty characters on four lines.
The display is incorporated in the control panel where there is also a high-brightness operating status indicator with
traffic light type green-yellow-red.
Five keys situated near the display enable the user to display the operating data, set the operating parameters, analyse
the status of the individual power modules, select the language in which the messages are to be displayed and carry out
a guided set of functional tests and procedures.
BCM - Battery Charger Module 3 108 51
The additional battery charger module works in parallel and in sync with the battery chargers in the power modules and
it is managed by the same algorithm that governs the recharging cycle. Every additional battery charger module provides
up to 15A of charge current that are added to the current of the battery chargers inside the power modules. Every power
module can provide up to 2.5A of charge current. This guarantees a reduction of the charge time in installations requiring
long autonomies and increases the availability of the UPS after a black out. During operation, the module takes current
from the input phase where it is installed.
It is possible to install any quantity of BCMs as long as there is at least one power module and enough empty slots inside
the EPS cabinet. All the information regarding the operating status of the BCM is given by the LED on the front of the
module and by what is shown on the EPS display.
The module is managed by a microprocessor to optimize performance and reliability. It is recommended to install it together with a battery cabinet with capacity exceeding 60 Ah.
ECO MODE
One functioning mode of Trimod MCS is called “eco mode”. With this mode it is possible to save energy while guaranteeing uninterruptability of the power supply to the load connected. During the functioning in eco mode, the load
is powered directly from the electrical mains through the automatic bypass circuit inside the power modules. This
means that the output voltage and frequency are the same as the mains. The advantage obtained in the eco mode is
a greater electrical efficiency and consequently a reduction in consumption. If the output voltage leaves the window
of tolerance (-20% / +15% of the voltage set on the output), the EPS actuates its inverter stage and powers the load
with the energy stored in the batteries. The autonomy during the battery operation depends on the configuration of
the UPS (nominal power, battery capacity) and on the percentage of load applied. When the mains are back within the
tolerance values, the EPS switches automatically back to the eco mode. It is possible to change the operating mode
between on-line and eco mode (and viceversa) both with the EPS on and with the UPS off (in this case entering the
Service Mode).
15
3. Technological description
3.3 Models
16
Trimod MCS 3-5-10 Trimod MCS 7-15
Trimod MCS
User manual
Trimod MCS 30Trimod MCS 20
17
3. Technological description
18
Trimod MCS 40Trimod MCS 60Trimod MCS 80
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.