24" [610mm] Min
Center – Center
6 1/2"
[165mm] Diameter
CAUTION: Poke-thru cannot be rotated in
hole after insertion into floor.
3" [76mm] Diameter Core Drill
3 1/16" [78mm] Actual Diameter
#6-32 x 1/4" FHMS
(4) required
RC9AMD Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 002 956 – March 2003
Walker® electrical systems conform to and should be properly grounded
in compliance with requirements of the current National Electrical Code
or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if
improperly installed or used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should be installed in
conformance with current local and/or the National Electrical Code.
IMPORTANT: Please read all instructions
before beginning.
Products Covered: RC9AM2STC, RC9AMDTC, RC9AMDRTTC, RC9CMDTC, RC9CMDRTTC, & RC9SHMDTC
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the
surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1 Layout and locate position of hole(s).
Step 3 Core drill hole.
Step 4 Stem Assembly
Catalog No. RC9AM2STC
Insert stem into hole.
Step 5 Cover Assembly
Catalog No.: RC9CMDTC
Remove disposable plate
and replace with carpet/tile
flange. Install with (4) #6-32
x 1/4" [6.4mm] FHMS
Step 2 Remove 6 1/2" [165mm] section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of
2' [610mm] on center and not more
than one hole per each 65 sq. ft.
[6 sq. m] of floor area in each span.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall or
pillar to leave enough room for poke-thru cover assembly.
NOTE: For tile installations up to a maximum of 3/4" [19.1 mm] thick.
For tile thickness greater than 3/4" [19.1mm] consult factory.
Push Down