IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC9AM114TC, RC9114TCLJB
CAUTION: DO NOT operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of
the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electric Code.
Step 1. Layout and locate position of hole(s). Step 2. Remove 6 1/2" [165mm] section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.
or pillar to leave enough room for poke-thru cover assembly.
Step 3. Core drill hole. Step 4. Insert assembly into hole.
CAUTION: Poke-Thru cannot be rotated in hole after insertion into floor.
RC9AM114TC & RC9114TCLJB
Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 002 364 R1 – Updated November 2002
Walker® electrical systems conform to and should be properly grounded
in compliance with requirements of the current National Electrical Code
or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if
improperly installed or used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should be installed in
conformance with current local and/or the National Electrical Code.
24" [610mm] Min
Center – Center
6 1/2"
[165mm] Diameter
3" [76mm] Diameter Core Drill
3 1/16" [78mm] Actual Diameter
Push Down
CAUTION: Be certain to drill hole at least 4" [102mm] from any wall or
pillar to leave enough room for poke-thru cover assembly.
CAUTION: For tile thickness greater than 3/4" [19.1mm] consult factory.
CAUTION: Poke-Thru cannot be rotated in hole after insertion
into the floor.