IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC7KTC
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers.
This may result in damage to the surface finish of the product.
Step 1. Remove junction box cover and disconnect wires. Step 2. Remove slide holder and receptacle.
Lift out receptacle and attached conductors.
CAUTION: De-energize circuit before removing junction box cover.
Step 3. Release tabs on communication jacks Step 4. Remove four #6-32 flange screws and detach
and lift out. Cut terminations. Existing existing flange. Remove two #8-32 screws
communication jacks and adapters will from plastic receptacle shell and discard.
not mount in RC7ATC flange.
RC7
Replacement Scrub Water
Cover Assembly Kit
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 002 151 R1 – Updated October 2003
Walker® electrical systems conform to and should be properly grounded
in compliance with requirements of the current National Electrical Code
or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if
improperly installed or used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should be installed in
conformance with current local and/or the National Electrical Code.
2
Step 5. Cut existing carpet to 6 1/2" [165mm] Step 6. Install new receptacle barrier with two #8-32
diameter surrounding existing hole. screws to existing Poke-Thru stem.
Step 7. Insert receptacle conductors into opening and position flange onto stem. Attach flange with four #6-32
screws. Attach wiring label to inside of junction box cover. Reconnect circuit conductors and replace
junction box cover. Connect Poke-Thru according to required device configuration (see schematic below).
CAUTION: Receptacle mounting means not grounded. Grounding
wire connection required. For isolated ground wiring,
connect ground leads to a separate isolated grounding
conductor. See NEC250-146(d).
WHITE or NEUTRAL
from branch circuit
WHITE
from poke-thru receptacle
BLACK or HOT
from branch circuit
BLACK
from poke-thru receptacle
GREEN (jumper wire)
from poke- thru junction box
GREEN
from poke-thru receptacle
CONVENTIONAL WIRING SCHEMATIC
WHITE or NEUTRAL
from branch circuit
WHITE
from poke-thru receptacle
BLACK or HOT
from branch circuit
BLACK
from poke-thru receptacle
GREEN (jumper wire)
from poke-thru junction box
ISOLATED GROUND
from branch circuit
GREEN
from poke-thru receptacle
ISOLATED GROUND WIRING SCHEMATIC
GREEN or GROUND
from branch circuit
SYSTEM GROUND
GREEN or GROUND
from branch circuit
SYSTEM GROUND
WARNING: Ground wire from junction box must be connected to SYSTEM GROUND.
Wiring Label
NOTE: Factory supplied junction box shown. Junction boxes
must be located in an accessible location. Poke-Thru
devices with an “LJB” or “LJB25” suffix are supplied
without a junction box (supplied by others).