Legrand RC7AFFTC User Manual

Products Covered: RC7FF114TC, RC7FF114TCLJB CAUTION DO NOT operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the
surface finish of the product. Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electric Code.
RC7FF114TC & RC7FF114TCLJB Poke-Thru Series
INSTALLATION INSTRUCTIONS
Walker® electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Walker electrical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the National Electrical Code.
24" [610mm] Min Center – Center
6 1/2"
[165mm] Diameter
3" [76mm] Diameter Core Drill 3 1/16" [78mm] Actual Diameter
Push Down
CAUTION: Be certain to drill hole at least 4" [102mm] from any wall or
pillar to leave enough room for poke-thru cover assembly.
CAUTION: For tile thickness greater than 3/4" [19.1mm],
consult factory.
CAUTION: Poke-Thru cannot be rotated in hole after insertion
into the floor.
IMPORTANT: Please read all instructions
before beginning.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each 65 sq. ft. [6 sq. m] of floor area in each span.
Step 2 Remove 6 1/2" [165mm] section from carpet
or tile. Use template provided.
Step 1 Layout and locate position of hole(s).
Step 3 Core drill hole.
Step 4 Insert assembly into hole.
RC7FF114TC
Replace
RC7FF114TCLJB Poke-Thru
(Applies to installations in the City of Chicago or other locations where local codes require the use of EMT compression fittings, and a junction box suitable for use in environmental air spaces.)
Once unit is pushed into the Cored Hole, from below, install an EMT Compression Fitting (not supplied) and Junction Box (not supplied) to the Conduit System. Complete installation per NEC and Local Codes.
Step 5 With assembly installed, remove screw plugs
and install conduit adapters as necessary.
Step 6 Completed assembly.
Step 7. Follow steps 1 through 6 for installation.