IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC4ATC, RC4ARTTC, RC4CTC, RC4CRTTC, RC4STC, RC4SRTTC, and RC4SHTC
RC4ATC-LJB, RC4ARTTC-LJB, RC4ATCLJB25 and RC4ARTTCLJB25
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s). Step 2. Remove 7" [178mm] dia. section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
For Tile Applications up to a Maximum of 3/4" [19.1mm] Thick.
NOTE: Be certain to drill hole at least 4 1/4" [108mm] from any wall NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.
or pillar to leave enough room for Poke-Thru cover assembly.
Step 3. Core drill hole. Step 4. Stem Assembly: Step 5. Cover Assembly:
Catalog No. RC4STC Catalog No. RC4CTC Insert stem into hole. Remove disposable plate
and replace with carpet/tile flange. Install with four #6-32 x 1/4" [6.4mm] FHMS.
24" [610mm] Min Center – Center
7"
[178mm] Diameter
CAUTION: Poke-Thru cannot be rotated
in hole after insertion into floor.
4" Diameter Core Drill
4 1/16" [103mm] Actual Diameter
Push Down
Four #6-32 x 1/4" FHMS
RC
4
Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 636 R2 – Updated April 2005
Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL Listed to U.S. and Canadian safety standards, made for interior use only, and should be installed in conformance with current local and/or the National Electrical Code.
COMPLETE ASSEMBLY:
Step 6. Cat. Nos. RC4ATC or RC4ARTTC. Step 7. Wire the power circuit. See wiring diagram.
Wire the Poke-Thru device. (Can be completed above floor.) Refer to wiring schematic in Step 8.
Step 8. Wiring Diagram. Connect receptacle Step 9. If circuit is connected to an isolated ground
leads to branch circuit conductors apply IG icon on receptacle slide as shown. as required.
WARNING: Ground wire from junction box must be connected
to SYSTEM GROUND.
CAUTION: Receptacle mounting means not grounded. NOTE: The orange triangle shall only be placed on devices
Grounding wire connection required. For isolated that are wired for isolated ground. See NEC 250-146(d). ground wiring; connect ground leads to a separate isolated grounding conductor. See NEC 250-146(d).
2
Two #6-32 Slide Cover Mounting Screws
NOTE: Gasket and gasket
support must be removed before wiring data connections.
Gasket
Gasket Support
Branch Circuit Conductors
Electrical and Communication Cables May be Connected to Unit Prior to or After Activation.
Junction Box
24.5 cu. in. [400cm
3
]
Circuit “B”
Circuit “A”
Circuit “A” Circuit “B”
Line Black Red
Neutral White White w/Blue Stripe
Ground Green Green w/Yellow Stripe
Electrical Wiring Chart