IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC3STC, RC3ATC, RC3ARTTC, RC3CTC, RC3CRTTC, and RC3SHTC
RC3ATC-LJB, RC3ARTTC-LJB, RC3ATCLJB25 and RC3ARTTCLJB25
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s). Step 2. Remove 7" [178mm] dia. section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
For Tile Applications up to a Maximum of 3/4" [19.1mm] Thick.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.
or pillar to leave enough room for Poke-Thru cover assembly.
Step 3. Core drill hole. Step 4. Stem Assembly: Step 5. Cover Assembly:
Catalog No. RC3STC Catalog No. RC3CTC
Insert stem into hole. or RC3CRTTC. Remove
disposable plate and
replace with carpet/tile
flange. Install with four
#6-32 x 1/4" [6.4mm] FHMS.
24" [610mm] Min
Center – Center
7"
[178mm] Diameter
CAUTION: Poke-Thru cannot be rotated
in hole after insertion into floor.
4" Diameter Core Drill
4 1/16" [103mm] Actual Diameter
Push Down
Four #6-32 x 1/4" FHMS
RC3Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 586 R2 – Updated April 2005
Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.
All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold electrical
products are UL Listed to U.S. and Canadian safety standards,
made for interior use only, and should be installed in conformance
with current local and/or the National Electrical Code.