Legrand RC3APTCBK User Manual

IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC3STC, RC3ATC, RC3ARTTC, RC3CTC, RC3CRTTC, and RC3SHTC
RC3ATC-LJB, RC3ARTTC-LJB, RC3ATCLJB25 and RC3ARTTCLJB25
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s). Step 2. Remove 7" [178mm] dia. section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
For Tile Applications up to a Maximum of 3/4" [19.1mm] Thick.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.
or pillar to leave enough room for Poke-Thru cover assembly.
Step 3. Core drill hole. Step 4. Stem Assembly: Step 5. Cover Assembly:
Catalog No. RC3STC Catalog No. RC3CTC Insert stem into hole. or RC3CRTTC. Remove
disposable plate and replace with carpet/tile flange. Install with four #6-32 x 1/4" [6.4mm] FHMS.
24" [610mm] Min Center – Center
7"
[178mm] Diameter
CAUTION: Poke-Thru cannot be rotated
in hole after insertion into floor.
4" Diameter Core Drill
4 1/16" [103mm] Actual Diameter
Push Down
Four #6-32 x 1/4" FHMS
RC3Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 586 R2 – Updated April 2005
Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL Listed to U.S. and Canadian safety standards, made for interior use only, and should be installed in conformance with current local and/or the National Electrical Code.
COMPLETE ASSEMBLY:
Step 6. Cat. Nos. RC3ATC or RC3ARTTC. Step 7. Wire the power circuit.
Wire the Poke-Thru device. (Can be completed above floor.) Refer to wiring schematic in Step 8.
Step 8. Connect Poke-Thru conductors according Step 9. If circuit is connected to an isolated ground,
to required device configuration. See apply IG icon on receptacle slide as shown. schematic below.
CAUTION: Receptacle mounting means not grounded. NOTE: The orange triangle shall only be placed on devices
Grounding wire connection required. For isolated that are wired for isolated ground. See NEC 250-146(d). ground wiring; connect ground leads to a separate isolated grounding conductor. See NEC 250-146(d).
2
Two #6-32 Slide Cover Mounting Screws
Outlet Box
Cover Plate Screw
WHITE or NEUTRAL from branch circuit
WHITE
from poke-thru receptacle
BLACK or HOT from branch circuit
BLACK from poke-thru receptacle
GREEN (jumper wire) from poke- thru junction box
GREEN
from poke-thru receptacle
CONVENTIONAL WIRING SCHEMATIC
WHITE or NEUTRAL from branch circuit
WHITE from poke-thru receptacle
BLACK or HOT from branch circuit
BLACK from poke-thru receptacle
GREEN (jumper wire) from poke-thru junction box
ISOLATED GROUND from branch circuit
GREEN from poke-thru receptacle
ISOLATED GROUND WIRING SCHEMATIC
GREEN or GROUND from branch circuit SYSTEM GROUND
GREEN or GROUND from branch circuit SYSTEM GROUND
WARNING: Ground wire from junction box must be connected to SYSTEM GROUND.